insulation monitor dap im 230v

2
DAP-IM DAP-IM DAP-IM DAP-IM DAP-IM Devices for single-phase isolating transformers installations, with or without middle point. The monitoring to the overload and the high temperature alarms of the transformer are included, the overload transformer measurement is incorporated too. It also has detection and indication if the continuity to earth or to equipotential bonding busbar is lost. The REP-IM REP-IM REP-IM REP-IM REP-IM repeats all the signs of DAP-IM DAP-IM DAP-IM DAP-IM DAP-IM inside the medical room for can be permanently monitored by the medical staff. Leds bars for the measurement of the isolation of the installation and of the overload of the transformer are included. INSULA INSULA INSULA INSULA INSULATION MONITOR FOR MEDICAL TION MONITOR FOR MEDICAL TION MONITOR FOR MEDICAL TION MONITOR FOR MEDICAL TION MONITOR FOR MEDICAL LOCA LOCA LOCA LOCA LOCATIONS TIONS TIONS TIONS TIONS The DAP-IM is a Insulation Monitoring Device for permanently monitor the insulation resistance to earth of unearthed IT System in medical locations according to international standard IEC 60364-7-710.

Upload: derargh

Post on 12-Jan-2016

215 views

Category:

Documents


1 download

DESCRIPTION

Insulation Monitor

TRANSCRIPT

Page 1: Insulation Monitor DAP IM 230V

DAP-IMDAP-IMDAP-IMDAP-IMDAP-IM

Devices for single-phase isolating transformers installations, with or without middle point. Themonitoring to the overload and the high temperature alarms of the transformer are included, the overloadtransformer measurement is incorporated too.

It also has detection and indication if the continuity to earth or to equipotential bonding busbar is lost.

The REP-IMREP-IMREP-IMREP-IMREP-IM repeats all the signs of DAP-IMDAP-IMDAP-IMDAP-IMDAP-IM inside the medical room for can be permanently monitoredby the medical staff. Leds bars for the measurement of the isolation of the installation and of the overload ofthe transformer are included.

INSULAINSULAINSULAINSULAINSULATION MONITOR FOR MEDICALTION MONITOR FOR MEDICALTION MONITOR FOR MEDICALTION MONITOR FOR MEDICALTION MONITOR FOR MEDICALLOCALOCALOCALOCALOCATIONSTIONSTIONSTIONSTIONS

The DAP-IM is a Insulation Monitoring Device for permanently monitor the insulationresistance to earth of unearthed IT System in medical locations according to internationalstandard IEC 60364-7-710.

Page 2: Insulation Monitor DAP IM 230V

The information contained in this catalogue can be subjeted to changes without prior notice and in no case represents an undertaking from the manufacturer side.

Cód

. CB

I760

3300

7032

7-0

Des

igne

d an

d pr

inte

d in

Spa

in.

Distributed by:

TECHNICAL CHARACTERISTICS REP-IMTECHNICAL CHARACTERISTICS REP-IMTECHNICAL CHARACTERISTICS REP-IMTECHNICAL CHARACTERISTICS REP-IMTECHNICAL CHARACTERISTICS REP-IM

- Repeater the alarms and measure signs for the medical locations.- Yellow lamp to indication alarm state.- Green lamp state of normal operation.- Monitoring of the isolation in bar of 8 leds.- Yellow led for the indication of the isolation alarm.- Signalling of the lost of continuity of the connection to earth.- Measurement loads of the transformer from 20% to 100% in bar of 8 leds.- Yellow led for the indication of alarm of overload of the transformer alarm.- Yellow led to indicate high temperature transformer alarm.- Acoustic signalling of alarm state.- Key for the stop of the acoustic alarm.- Connection to 2 wires with the monitor DAP-IM.- Power supply of 12VAC.- Box DIN to embed of 108 x 108mm, with a depth 45 mm.- External dimensions 116,9 x 116,9mm and weight of 180gr.

TECHNICAL CHARACTERISTICS DAP-IMTECHNICAL CHARACTERISTICS DAP-IMTECHNICAL CHARACTERISTICS DAP-IMTECHNICAL CHARACTERISTICS DAP-IMTECHNICAL CHARACTERISTICS DAP-IM

- Device for single-phase IT Systems to 230VAC ± 20% to 50/60Hz.- Device for single-phase IT Systems to 110VAC ± 20% to 50/60Hz.- Isolation measurement from 1000kΩ to 50kΩ.- Monitoring of isolation in bar of leds.- Level of isolation alarm adjustable between 1000kΩ to 50kΩ.- Yellow led for the indication of isolation alarm.- Detection of the lost of continuity of the connection to earth or to equipotential bonding busbar.- Measurement of the overload of the transformer by means of the a CM-IM*.- Selector for the load current of the transformer in 10, 20, 30, 40 or 50A.- Monitoring loads of the transformer from 20% to 100% in bar of 8 leds.- Yellow led for the indication of the overload transformer alarm.- Input for connection the temperature sensitive device (type PTC or Thermal fuse or similar).- Yellow led for indication for the high temperature in the transformer alarm.- Voltage output of 12VAC for REP-IM power supply.- Only 2 wires for connection the alarms and measures to repeat device REP-IM.- Green led to indicate normal operation.- Test Key for the verification of the operation of the device.- Power supply 230VAC ± 20% to 50/60Hz and power consumption of 9VA.- Power supply 110VAC ± 20% to 50/60Hz and power consumption of 9VA.- Box for rail fixing DIN.- Dimensions 105 x 85 x 70 mm and weight of 480gr.

* CM-IM: current transformer for the measurement of the isolation transformer load.

87 85

105

45

70

65

76

116,9

116,

9 108

108

451,5