inter-turn rotor defect
DESCRIPTION
Inter-turn rotor defectTRANSCRIPT
Rotor Tester
Model Inuo-Rotor
• This Rotor tester detects shorted
turns in rotor windings based on the
recurring pulse phenomenon and
uses the RSO testing technique.
• Suitable for generators with
capacity greater than 100 MW
• In-built oscilloscope
• Determines inter-turn insulation
effectiveness
• Analyses all types of faults
• Locates position of shorted
windings
• Provides trending analysis of
insulation faults
Features
1. Determines insulation effectiveness
Tests and analyzes insulation effectiveness of symmetric generator rotor
windings through analysis of wave characteristics, using the recurring pulse
phenomenon. This device uses high-frequency low-voltage pulses which is
non-destructive to the rotor windings under test.
2. Analysis of faults
Analyzes qualitatively the inter-turn faults, distinguishing between metal
and non-metal short-circuits. Locates position of windings with insulation
fault. Provides trending of insulation faults.
Address:
5 Upper Aljunied Link, #02-07 Quartz Industrial Building, Singapore 367903
Phone: +65 6276 6733 Fax: +65 6276 6793
InuoSys Solutions Pte Ltd
E-mail: [email protected]
3. Testing Scope
Suitable for testing generators of capacity greater than 100 MW.
4. Test Equipment characteristics
This tester comes with an in-built Repetitive Surge Oscilloscope. It has a
large storage capacity as well as an USB output port. This is a user-friendly
device that works with both Windows 2000 and Windows XP. The device
casing is made of high strength incombustible plastic.
Specifications
Address:
5 Upper Aljunied Link,
#02-07 Quartz Industrial Building, Singapore 367903
Phone: +65 6276 6733 Fax: +65 6276 6793
InuoSys Solutions Pte Ltd
E-mail: [email protected]
Power Input 250W, 100V~240V single-phase AC,
95V~250V DC
Working Temperature -10°°°°C - +55°°°°C
Storage Temperature -40°°°°C - +65°°°°C
Working Humidity 5% - 95%
Impact Survivality 1.5 G in any direction
Vibration Resistivity 1.5 G @ 10 – 100 Hz in any direction
MTBF 50,000 hours
Operating Altitude Sea Level ≤≤≤≤ 4,000 m
Equipment TMFZ-1 device, a set of test wires, ABS high
strength plastic casing
Dimensions 400××××291××××213 mm3
Weight 10 Kg
Principle of Operation
1. Cylindrical Rotor Structure of Turbine Generator
The cylindrical rotor of a turbine generator has axial slots on the rotor body for
embedding rotor windings that are held in place by wedges. Figure 1 shows the
cross-sectional view of one of the slots. Each slot contains 6 to 8 turns of field
windings. These field conductors are insulated from the rotor body by the slot
insulation, from the slot wedge by the wedge insulation and from each other by
the inter-turn insulation.
Fig. 1 Rotor Insulation Structure
To prevent vibrations when the rotor is rotating at high speeds, the
cross-sectional placement of the embedded windings, main insulation and
inter-turn insulation must be magnetically balanced. Figure 2 shows an
expanded view of the rotor windings, which is strictly symmetrical from an
electrical circuitry viewpoint.
Address:
5 Upper Aljunied Link, #02-07 Quartz Industrial Building, Singapore 367903
Phone: +65 6276 6733 Fax: +65 6276 6793
InuoSys Solutions Pte Ltd
E-mail: [email protected]
Fig. 2 Rotor Windings Diagram
Based on circuit analysis theory, the rotor windings of a generator can be
modeled just like a full loopback circuit, that is, equivalent to the high frequency
response circuit shown in Figure 3.
Fig. 3 High Frequency response equivalent circuit for rotor windings
2. Conventional Testing Methods
Many conventional test methods are available today for detection of shorted
turns in rotor windings, such as: DC winding resistance measurement,
Generator no-load test, short-circuit characteristics curves, AC impedance and
power loss tests, flux probe analysis etc.
Address:
5 Upper Aljunied Link, #02-07 Quartz Industrial Building, Singapore 367903
Phone: +65 6276 6733 Fax: +65 6276 6793
InuoSys Solutions Pte Ltd
E-mail: [email protected]
(a) DC Winding Resistance
According to DL/T596-1996, during each overhaul, the rotor DC winding
resistance should be measured off-line, and these readings are then compared
to a baseline set of data. After adjustments to the readings to compensate for
temperature differences, the variation of the readings from the baseline should
not exceed 2%. In the DC Winding resistance test, as the rotor is off-line, the
inductance and capacitance of the windings have no effect and the equivalent
circuit is as shown in Figure 4.
Fig. 4 Equivalent Circuit in DC Winding Resistance Test
The rotor of a generator usually has about 6 to 8 slots per pole, each slot
containing 6 to 8 turns, giving a total of about 110 turns and the DC winding
resistance is in the mΩΩΩΩ range. The structure of the rotor is such that there is a
very low probability of inter-turn insulation breakdown and short circuit due to
metallic contamination between remotely positioned turns. Insulation
breakdown usually occurs between adjacent turns and when this happens, the
total DC winding resistance remains unchanged. Even if a short circuit due to
metallic contamination does occur between adjacent turns, the change in total
resistance is less than 1%. On top of this, if a different test instrument is used
each time for measurement, there is no basis for comparison. Hence, the
sensitivity of the DC winding resistance test in detecting inter-turn faults is very
low.
Address:
5 Upper Aljunied Link, #02-07 Quartz Industrial Building, Singapore 367903
Phone: +65 6276 6733 Fax: +65 6276 6793
InuoSys Solutions Pte Ltd
E-mail: [email protected]
(b) Impedance and Power Loss
This method is commonly used to detect inter-turn short circuits in a rotor
(sttaic status). Normally, the test power source used is at 50 Hz, but at times, a
100 Hz power source is used because of the need to reduce power supply.
When using a 50 Hz power source for measuring the rotor impedance, the
winding inter-turn capacitance Czj1 ~ Czjn and the winding capacitance to ground
Cj_1 ~ Cj_n are viewed as open circuit, while the values of the inter-turn
insulation resistance Rzj1 ~ Rzjn and the winding resistance to ground are
considered as infinity, resulting in the equivalent circuit shown in Figure 5.
Fig. 5 Equivalent Circuit in AC Impedance Test
This test is conducted for several conditions: before the rotor is moved out,
when the rotor is out, when the rotor is moved in, at different rotating speeds of
the rotor. The measurements taken are voltage, current and power loss while
the impedance, usually in the range of 4~8 ΩΩΩΩ, is calculated from the relevant
measured values. From analysis of the impedance values, under the effect of a
50 Hz supply, the rotor is purely inductive, so any change in the inter-turn
insulation resistance would not cause changes to inductance. A change in
inductance will only occur if there is short circuit caused by metallic
contamination and this change should be less than 1%. Upon conversion to
impedance value, the change should also be less than 1%. The power loss is due
to the resistance of the conductors, that is copper loss, reflecting the change in
resistance. This change in resistance thus measured is not as accurate as when
measuring the DC resistance directly.
Address:
5 Upper Aljunied Link, #02-07 Quartz Industrial Building, Singapore 367903
Phone: +65 6276 6733 Fax: +65 6276 6793
InuoSys Solutions Pte Ltd
E-mail: [email protected]
The accuracy of the impedance and power loss measurements are affected by
many factors, for example, rotor position, air-gap between rotor and stator,
rotating speed of rotor, short-circuit resistance and fault location, level of test
voltage, slot wedge and retaining ring structure etc. Hence it is difficult to
stipulate a standard for measurements, analysis is limited to a comparison of
the current set of measurements against a previous set of measurements. A
combination of other test methods is required to reach conclusive results.
(c) Measuring Generator No-Load and Short-circuit Characteristics Curve
This method is limited by measurement precision. Generally, the number of
rotor shorted winding turns has to exceed the total number of turns by 3 ~ 5%
in order for the condition to be reflected in the no-load and short-circuit
characteristics curve. As a result, sensitivity of detection is low and this method
is used together with other tests in order to reach a conclusive result.
(d) Flux Probe Measurements
This technique is based on measuring the main rotor flux and the rotor slot
leakage flux caused by the exciting current flowing through the rotor field
windings. This method requires a micro coil (flux probe) to be mounted on a
stator wedge and positioned in the air-gap of the generator. The probe detects a
combination of fluxes – the leakage flux in each rotor slot that is proportional to
the current flowing through the effective turns in that slot and the flux that
crosses the air-gap. The nearer the probe is to the rotor surface, the higher the
sensitivity. This method is superior to the three earlier mentioned methods for
the detection of short circuits due to metallic contamination, but it is unable to
detect insulation status for short circuits not caused by metallic contamination.
Obviously, this method cannot be used if generators do not have the air-gap flux
probes installed. Installing probes would require the generator to be taken out
of service.
Address:
5 Upper Aljunied Link, #02-07 Quartz Industrial Building, Singapore 367903
Phone: +65 6276 6733 Fax: +65 6276 6793
InuoSys Solutions Pte Ltd
E-mail: [email protected]
3. Theory of RSO technique
The recurrent pulse testing technique is called RSO (Repetitive Surge
Oscillograph) method. This technique applies travelling wave transmission
principles and is implemented based on neural network signature and high
frequency waves transmission symmetry through the same medium. This
method has been successfully tested in the laboratories and on generators.
The RSO method uses the time domain reflectometry theory to detect a short in
field windings. In essence, when a pulse is applied to the rotor winding circuit,
a shorted turn would cause reflections that cane be analyzed. A signal generator
is used to send a succession of step-shaped low voltage pulses along the rotor
field windings, and at the fault location, there will be a sudden impedance
change that will cause a reflected wave and a transmitted wave to occur,
resulting in a response characteristics curve that is different from that of a
normal loop back circuit that does not have sudden impedance variations. The
RSO technique uses the variation in impedance along the field windings
experienced by the travelling wave to detect anomalies. The extent of the
inter-turn short circuit is indicated by the degree of variation in the wave
impedance. The resultant reflected signals could be viewed on a dual-channel
oscilloscope screen as two separate waveforms or as a single summed trace.
The non-flatness of the combined trace is indicative of faults; blips on the
combined trace mean anomalies in the field windings and the wave amplitude of
a blip indicates the extent of damage. By analyzing the position of the anomaly
on the oscillogram, the approximate location of the fault can be inferred.
Therefore, even if there is only a single shorted turn in the field windings, the
RSO testing technique is sensitive enough to detect it.
Techniques for detecting inter-turn short-circuit in the generator rotors
involves two aspects: the early discovery of shorted turns and the location of
the inter-turn short circuit.
Address:
5 Upper Aljunied Link, #02-07 Quartz Industrial Building, Singapore 367903
Phone: +65 6276 6733 Fax: +65 6276 6793
InuoSys Solutions Pte Ltd
E-mail: [email protected]
The RSO technique is able to bring about early discovery of inter-turn metallic
contaminated short circuits and detection of one or more shorted turns caused
by non-metallic short circuit and insulation failure. In addition, this technique is
more accurate in locating the slot where the fault lies and the location of the
shorted turns.
Figure 6 shows a typical connection arrangement for RSO testing.
Fig. 6 RSO Testing Connection
4. Case Studies
(a) Short-circuit due to metallic contamination
During maintenance of a 1000 MW generator set for a certain power generation
station, impedance, air-gap flux waveform and RSO measurements were made.
Under the same controlled test environment, the impedance and waveform
measurements indicated normal conditions, however, the RSO Tester indicated
that the eighth turn of the rotor’s field winding is short-circuited by a metallic
contamination.
Address:
5 Upper Aljunied Link, #02-07 Quartz Industrial Building, Singapore 367903
Phone: +65 6276 6733 Fax: +65 6276 6793
InuoSys Solutions Pte Ltd
E-mail: [email protected]
The baseline normal operating condition data for this generator set:
(1) Impedance Values
Table 1 1000MW Generator Set AC Impedance (1)
(2) Flux Probe Waveform
Fig. 7 Flux Probe Waveform
Address:
5 Upper Aljunied Link, #02-07 Quartz Industrial Building, Singapore 367903
Phone: +65 6276 6733 Fax: +65 6276 6793
InuoSys Solutions Pte Ltd
E-mail: [email protected]
(3) RSO Tester results
Fig. 8 RSO Measurement: Waveform (1)
The measurements for this generator set during overhaul:
(1) Impedance Values
Table 2 1000MW Generator Set AC Impedance (2)
Address:
5 Upper Aljunied Link, #02-07 Quartz Industrial Building, Singapore 367903
Phone: +65 6276 6733 Fax: +65 6276 6793
InuoSys Solutions Pte Ltd
E-mail: [email protected]
(2) Flux Probe Waveform
This data is not available during overhaul of this generator set.
(3) RSO Tester results
Fig. 9 RSO Measurement: Waveform (2)
The conclusion based on the RSO Test data and waveform is:
There is a coil-to-coil short-circuit in the rotor field windings of this generator.
The degree of short circuit-ness is one shorted turn, and the short-circuit
location is at the eighth turn of the rotor field windings at the excitation end.
Address:
5 Upper Aljunied Link, #02-07 Quartz Industrial Building, Singapore 367903
Phone: +65 6276 6733 Fax: +65 6276 6793
InuoSys Solutions Pte Ltd
E-mail: [email protected]
Fig. 10 Rotor of 1000MW Generator Set
Upon removing the retaining ring on-site, it was observed that the insulation on
the bridge between the 7th and the 8th coils showed evidence of overheating,
and that under the bridge between the 7th and 8th coils, two turns of field
winding were already welded together.
(b) Short-circuit not caused by metallic contamination
During maintenance of a 300 MW generator set for a certain power generation
station, impedance and RSO measurements were made. Under the same
controlled test environment, the impedance readings indicated normal
conditions, however, the RSO Tester indicated a short circuit caused by non-
metallic contamination between the 3rd and 4th coil of the rotor’s field winding
on the exciting side.
Address:
5 Upper Aljunied Link, #02-07 Quartz Industrial Building, Singapore 367903
Phone: +65 6276 6733 Fax: +65 6276 6793
InuoSys Solutions Pte Ltd
E-mail: [email protected]
(1) Impedance Values
Current I (A) Power P (W) Impedance Z ()
20 11.515 167.5 1.736
40 22.185 525.0 1.802
60 31.935 1217.0 1.878
80 41.340 2022.5 1.934
80 41.340 2022.5 1.934
60 32.170 1140.0 1.864
40 22.300 370.0 1.793
20 11.340 95.0 1.763
Table 3 300MW Generator Set AC Impedance
(2) RSO Tester results
Fig. 11 Rotor of 300MW Generator Set: Before internal sweep Waveform
Address:
5 Upper Aljunied Link, #02-07 Quartz Industrial Building, Singapore 367903
Phone: +65 6276 6733 Fax: +65 6276 6793
InuoSys Solutions Pte Ltd
E-mail: [email protected]
Fig. 12 Rotor of 300MW Generator Set: After external sweep Waveform
Fig. 13 Rotor of 300MW Generator Set
Address:
5 Upper Aljunied Link, #02-07 Quartz Industrial Building, Singapore 367903
Phone: +65 6276 6733 Fax: +65 6276 6793
InuoSys Solutions Pte Ltd
E-mail: [email protected]