About this Document Gateway Module RMG12.2-NN
DOK-CONTRL-RMG12.2****-PR02-EN-P
INTERBUS Gateway Module RMG12.2-NN
Configuration
DOK-CONTRL-RMG12.2****-PR02-EN-P
• DOK-MTC200-TECHN*UNTERL-04M1-EN-P
• DOK-MTC200-TEC*DOC*4V3-04M1-EN-P
• Drawing number: 120-0400-B308-02
This document is used for
• configuring, installing and commissioning the Gateway module.
• Specifications of the Gateway module
Documentation identification ofprevious releases
Releasedate
Comment
DOK-CONTRL-RMG12.2****-PR02-EN-P 02.1999 First issue
INDRAMAT GmbH, 1999
Copying this document and giving it to others and the use orcommunication of the contents thereof without express authority areforbidden. Offenders are liable for the payment of damages. All rights arereserved in the event of the grant of a patent or the registration if a utilitymodel or design. (DIN 34-1)
All rights are reserved with respect to the content of this documentationand the availability of the product.
INDRAMAT GmbH • Bgm.-Dr.-Nebel-Str. 2 • D-97816 Lohr a. Main
Phone 09352/40-0 • Tx 689421 • Fax 09352/40-4885
Dept. ECS (RW)
This document is printed on paper bleached without chlorine.
Title
Type of document
Document code
Internal file reference
Purpose of the document
Configuration control
Copyright
Validity
Published by
Note
Gateway Module RMG12.2-NN Contents I
DOK-CONTRL-RMG12.2****-PR02-EN-P
Contents
1 General 1-11.1 Brief Description................................................................................................................................... 1-1
1.2 Selecting the Data Word Width............................................................................................................ 1-1
1.3 Installation Instructions......................................................................................................................... 1-1
1.4 Dimensions .......................................................................................................................................... 1-2
2 Specifications 2-32.1 General ................................................................................................................................................ 2-3
Supply voltage............................................................................................................................... 2-3
EMC .............................................................................................................................................. 2-3
General information about addressing .......................................................................................... 2-3
2.2 Addressing ........................................................................................................................................... 2-3
2.3 Redundant Power Supply..................................................................................................................... 2-4
2.4 Pin Assignments .................................................................................................................................. 2-5
2.5 Diagnosis Indicators............................................................................................................................. 2-5
INTERBUS diagnostics ................................................................................................................. 2-5
System diagnostics ....................................................................................................................... 2-6
2.6 Activating/De-activating I/O Error Message ......................................................................................... 2-6
3 Applications 3-13.1 Addressing ........................................................................................................................................... 3-1
3.2 Typical Application ............................................................................................................................... 3-2
4 Accessories 4-14.1 Cables and Connectors ....................................................................................................................... 4-1
5 Figures 5-1
II Contents Gateway Module RMG12.2-NN
DOK-CONTRL-RMG12.2****-PR02-EN-P
Gateway Module RMG12.2-NN General 1-1
DOK-CONTRL-RMG12.2****-PR02-EN-P
1 General
1.1 Brief Description
The RMG12.2-NN gateway module permits data to be exchangedbetween two physically independent INTERBUS rings. In each ring, theRMG12.2-NN appears as a remote bus slave device with a selectabledata width between one and ten words. The redundant structure of thepower supply of the RMG12.2-NN unit provides the following benefits:
• The power supply units are isolated from each other.
• The RMG12.2-NN always starts its operation, irrespective of the powersupply that is actually applied.
• Both rings can be started up independently of each other.
• Interruption-free automatic changeover to the functioning secondpower supply unit if a power supply fails during the simultaneousoperation.
1.2 Selecting the Data Word Width
A 16-step rotary switch (S1) on the front panel of the gateway modulepermits the module’s data word width to be selected.
CONFIGS1
X2
X3
UL
RC
BA
RD
IN
OUT
INTE
RBU
S
RMG12.2-NN_D-Breite.FH7
0
8
C 4DE
F
32
1
79A
B 56
setting thedata word widthfor both rings
Figure 1-1: Selecting the data word width for both rings
1.3 Installation Instructions
The RMG12.2-NN unit can be installed in an RMB12.2-02 or RMB12.2-04rack. Using the brackets provided and a DIN rail, the module can bemounted directly onto the mounting plate of a switchgear cabinet.
1-2 General Gateway Module RMG12.2-NN
DOK-CONTRL-RMG12.2****-PR02-EN-P
1.4 Dimensions
82,5
36
ca. 4023,5
total installation depth ca. 162
1641,3
192
214
52
44,8
38,4
total installation depth for installation in base rack RMB02.1-04 ca. 179
bracket(included in
delivery)
DIN railTS 35x27x15
0
8
C 4DE
F
32
1
79A
B 56
RMG12.2-NN
CONFIG
IN
UL
H1
S1
X2
X1
X4
X3
X6
RC
BA
RD
UL
RC
BA
RD
X5
IN
OUT
+UL
0VL
+UL
0VL
OUT
RECOIN
TER
BUS
INTE
RBU
S
8
RMG12.2-NN_Maß.FH7
Figure 1-2: Mounting dimensions of RMG12.2-NN
Gateway Module RMG12.2-NN Specifications 2-3
DOK-CONTRL-RMG12.2****-PR02-EN-P
2 Specifications
2.1 General
Permissible cable cross-section for thesupply voltage:
up to 1.5 mm2
Protection rating: IP 20, DIN VDE 0470, EN 60529
Humidity (storage/transport): 75%, no condensation
85%, no condensation (occasional)
DIN 40 040 Class F
Atmospheric pressure: 860 ... 1080 hPa, 1500m (operation)
860 ... 1080 hPa, 3500m (storage)
Operating temperature: +5°C ... 45°C, DIN 40 040 Class KV
Storage temperature: -30°C ... +85°C
Interfaces: 2 x INTERBUS-IN (9-way male)
2 x INTERBUS-OUT (9-way female)
Supply voltage
Nominal value: 24 VDC
Permissible ripples: 4,0 Vss within the permissible voltage range
Permissible voltage range: 19.5 ... 28,5 VDC, including ripples
Power consumption: approximately 5W
EMC
Noise immunity to IEC 801-02 (ESD): Class 3, judgement criterion 2
Noise immunity to IEC 801-04 (Burst): Class 3, judgement criterion 2
(1 KV, no singular errors)
General information about addressing
In order to be able to address the devices in the INTERBUS systemdirectly, each device has an unambiguous address assigned. In addition,each INTERBUS module possesses an identification code (ID code) thatshows the connected configuration unambiguously.
2.2 Addressing
Local bus device: DI/DO
ID code: 03(HEX) = 03(DEC)
Data width: 1 - 10 words = 16 bits
2-4 Specifications Gateway Module RMG12.2-NN
DOK-CONTRL-RMG12.2****-PR02-EN-P
2.3 Redundant Power Supply
The power to the gateway module is supplied via the two connectorsX5and X6 (X5 has priority). The power supply connected to X5 feeds thegateway module when both power supplies are connected. The powersupply via X6 is selected if the power at X5 drops. The electroniccomponents do not notice any interruption during the switchover process.
The diagram below shows the method of operation:
RMG12.2-NN_Netzteil.FH7
+UL
X5X6
+U
X1 X3
X2 X4
IBS1
IBS1 IBS2
IBS2
+UL
24V
5V
Abb. 2-3: Power supply unit, method of operation
Gateway Module RMG12.2-NN Specifications 2-5
DOK-CONTRL-RMG12.2****-PR02-EN-P
2.4 Pin Assignments
X4
X3
GND
+5V
RBST
DO2
DO2
DI2
DI2
OUT
DO1
GND
DO1
DI1
DI1
IN
X2
X1
GND
+5V
RBST
DO2
DO2
DI2
DI2
OUT
DO1
GND
DO1
DI1
DI1
IN
GND
+24V
X5
1
2
3PE
GND
X6
1
2
3 PE
5
9
3
1
7
6
2
3
1
7
6
2
+24V
RMG12.2
RMG12.2-NN_Anschl.FH7
5
9
3
1
7
6
2
3
1
7
6
2
pin assignments*:
INTERBUSring 1
INTERBUSring 2
supply voltage+24VDC±20%
Pauf ca. 5W
supply voltage+24VDC±20%
Pauf ca. 5W
* Caution! The terminal designations DO and DI are always related to the master of the INTERBUS ring.
Figure 2-4: Pin assignments of the INTERBUS interfaces
2.5 Diagnosis Indicators
There are four LEDs and one 7-segment display on the RMG12.2-NNfront panel. These indicator elements are explained below:
INTERBUS diagnostics
UL LED green Supply voltage for the module electronics
ON: UL supply voltage OK
OFF: UL supply voltage is missing
RC LED green Remotebus Check
Monitoring the incoming remote bus (X3)
ON: Incoming remote bus connection is established
OFF: Incoming remote bus connection is disturbed
2-6 Specifications Gateway Module RMG12.2-NN
DOK-CONTRL-RMG12.2****-PR02-EN-P
BA LED green Bus-Active
ON: Data transfer on the INTERBUS is active
OFF: No data transfer
RD LED red Remotebus Disable
ON: The ongoing remote bus is switched off
OFF: The ongoing remote bus is connected
System diagnostics
When the power to the gateway module is switched on, the diagnosismessages shown below are displayed in succession for approximately 2... 3 seconds.
A steady "b" = operational is displayed if system is running and stable.
In the event of a malfunction, the display blinks and indicates the faultyINTERBUS ring.
8.8.8.8.8.
5.7.b.0.
1. RMG12.2-NN_Diag.FH7
- "S" is displayed as a start character during the startup phase.
- When the system is running, the selected data word width (here: 7) is displayed briefly.
- In the event of a system error in the 1st INTERBUS-S ring, "0" is displayed aserror message.
- Once the data word width has been displayed, the display changes to "b". (= operational)
- In the event of a system error in the 2nd INTERBUS-S ring, "1" is displayed aserror message.
Figure 2-5: Meanings of the 7-segment display
2.6 Activating/De-activating I/O Error Message
An error message is available that reports the failure of an INTERBUSdevice. It provides a mutual I/O error message in the event of a failure ofan INTERBUS branch. The error message can be activated and de-activated as required.
The switch for activating/de-activating the error messages is accessiblethrough an opening in the enclosure at the rear of the RMG12.2-MMmodule. The I/O error message is active when the slide switch is in itsbottom position (see Figure below).
Gateway Module RMG12.2-NN Specifications 2-7
DOK-CONTRL-RMG12.2****-PR02-EN-P
RMG12.2-NN_Fehlerm.FH7
rear view:
inactive
active
Figure 2-6: Activating the I/O error message
2-8 Specifications Gateway Module RMG12.2-NN
DOK-CONTRL-RMG12.2****-PR02-EN-P
Gateway Module RMG12.2-NN Applications 3-1
DOK-CONTRL-RMG12.2****-PR02-EN-P
3 Applications
3.1 Addressing
The absolute address of an INTERBUS device results automaticallyfrom its physical location in the ring. Deviating from this, the user canassign each module a logical address between 1 and 999 via the SPSinterface. Both devices on a gateway module need not necessarily havethe same logical address assigned.
SPS 1(Master)
SPS 2(Slave)
log.device 3
SPS 3(Slave)
log.device 3
log.device 2
log.device 2
RMG12.2-NN_Konf.FH7
to furtherdevices
to furtherdevices
RMG12.2
log.device
2
log.device
1
ÜÞ
RMG12.2
log.device
3
log.device
1
ÜÞ
to furtherdevices
remote bus 1
remote bus 2
remote bus 3
Figure 3-7: Typical addressing
Addressing
Data width (S1) Output Input
1 word %QW*.0 %,W*.2
2 words %QW*.0 - %QW*.2 %,W*.4 - %,W*.6
3 words %QW*.0 - %QW*.4 %,W*.6 - %,W*.10
.
. .
.
.
10 words %QW*.0 - %QW*.18 %,W*.20 - %,W*.38Figure 3-8: Addressing as a function of the data width
* Logical device no. 1...999 of the corresponding SPS
3-2 Applications Gateway Module RMG12.2-NN
DOK-CONTRL-RMG12.2****-PR02-EN-P
3.2 Typical Application
RMG12.2-NN_Appl.FH7
MTS-R01 withINTERBUS master
X3.6
ISP200-R MTC200-R
Master station
RMG12.2
BTM 15
X2
X3
IKS 056
% %
Emergency Stop
0
1
2
4
68
10 20
120
100
80
70
6050
4030
0
1
2
4
68
10 20
120
100
80
70
6050
4030
X2
X3
RECO 12
X2
X1
X4
X3
IKS 056
IKS 056
IKS 056
IKS 056
IKS 056
Slave stations
RMG12.2
X2
X1
X4
X3
MTC200-RIKS 056
IKS 056
to furtherdevices
X6
X5
X6
to furtherdevices
to furtherdevices
RMG12.2-NN
CONFIG
IN
UL
H1
S1
X2
X1
X4
X3
X6
RC
BA
RD
UL
RC
BA
RD
X5
IN
OUT
+UL
0VL
+UL
0VL
OUT
RECO
INTE
RBU
SIN
TER
BUS
0
8
C 4DE
F
32
1
79A
B 56
8
RME02.1-32-DC024
X1
X2
X3
X4
123456789
0VL
123456789
0VL
0VL
123456789
123456789
I*.3.0
0VL
I*.3.1I*.3.2I*.3.3I*.3.4I*.3.5I*.3.6I*.3.7
I*.2.0I*.2.1I*.2.2I*.2.3I*.2.4I*.2.5I*.2.6I*.2.7
I*.1.0I*.1.1I*.1.2I*.1.3I*.1.4I*.1.5I*.1.6I*.1.7
I*.0.0I*.0.1I*.0.2I*.0.3I*.0.4I*.0.5I*.0.6I*.0.7
Q*.1.0Q*.1.1Q*.1.2Q*.1.3Q*.1.4Q*.1.5Q*.1.6Q*.1.7
X1
X2
X3
X4
123456789
123456789
10
10
RMA02.1-32-DC024-050
123456789
10
Q*.0.0
0VL
123456789
10+UL
Q*.0.1Q*.0.2Q*.0.3Q*.0.4Q*.0.5Q*.0.6Q*.0.7
0VL
+UL
Q*.2.0Q*.2.1Q*.2.2Q*.2.3Q*.2.4Q*.2.5Q*.2.6Q*.2.7
0VL
+UL
Q*.3.0Q*.3.1Q*.3.2Q*.3.3Q*.3.4Q*.3.5Q*.3.6Q*.3.7
0VL
+UL
X60
X64
0 5
1
6
2
7
3
8
4
90 5
1
6
2
7
3
8
4
9
MTS-R01.1
RESET
H1
PROG U1
X2
COM
123456
X1+24VGND
NC
WD
DEVICE-NOX3
RECO
8
H1
X1
RX
TX
8
U1
MTC-R01.1
H1
DIAG
RX
TX
123456
X1+24VGND
NC
WD
8
RME02.1-32-DC024
X1
X2
X3
X4
123456789
0VL
123456789
0VL
0VL
123456789
123456789
I*.3.0
0VL
I*.3.1I*.3.2I*.3.3I*.3.4I*.3.5I*.3.6I*.3.7
I*.2.0I*.2.1I*.2.2I*.2.3I*.2.4I*.2.5I*.2.6I*.2.7
I*.1.0I*.1.1I*.1.2I*.1.3I*.1.4I*.1.5I*.1.6I*.1.7
I*.0.0I*.0.1I*.0.2I*.0.3I*.0.4I*.0.5I*.0.6I*.0.7
RME02.1-32-DC024
X1
X2
X3
X4
123456789
0VL
123456789
0VL
0VL
123456789
123456789
I*.3.0
0VL
I*.3.1I*.3.2I*.3.3I*.3.4I*.3.5I*.3.6I*.3.7
I*.2.0I*.2.1I*.2.2I*.2.3I*.2.4I*.2.5I*.2.6I*.2.7
I*.1.0I*.1.1I*.1.2I*.1.3I*.1.4I*.1.5I*.1.6I*.1.7
I*.0.0I*.0.1I*.0.2I*.0.3I*.0.4I*.0.5I*.0.6I*.0.7
Q*.1.0Q*.1.1Q*.1.2Q*.1.3Q*.1.4Q*.1.5Q*.1.6Q*.1.7
X1
X2
X3
X4
123456789
123456789
10
10
RMA02.1-32-DC024-050
123456789
10
Q*.0.0
0VL
123456789
10+UL
Q*.0.1Q*.0.2Q*.0.3Q*.0.4Q*.0.5Q*.0.6Q*.0.7
0VL
+UL
Q*.2.0Q*.2.1Q*.2.2Q*.2.3Q*.2.4Q*.2.5Q*.2.6Q*.2.7
0VL
+UL
Q*.3.0Q*.3.1Q*.3.2Q*.3.3Q*.3.4Q*.3.5Q*.3.6Q*.3.7
0VL
+UL
RME02.1-32-DC024
X1
X2
X3
X4
123456789
0VL
123456789
0VL
0VL
123456789
123456789
I*.3.0
0VL
I*.3.1I*.3.2I*.3.3I*.3.4I*.3.5I*.3.6I*.3.7
I*.2.0I*.2.1I*.2.2I*.2.3I*.2.4I*.2.5I*.2.6I*.2.7
I*.1.0I*.1.1I*.1.2I*.1.3I*.1.4I*.1.5I*.1.6I*.1.7
I*.0.0I*.0.1I*.0.2I*.0.3I*.0.4I*.0.5I*.0.6I*.0.7
Q*.1.0Q*.1.1Q*.1.2Q*.1.3Q*.1.4Q*.1.5Q*.1.6Q*.1.7
X1
X2
X3
X4
123456789
123456789
10
10
RMA02.1-32-DC024-050
123456789
10
Q*.0.0
0VL
123456789
10+UL
Q*.0.1Q*.0.2Q*.0.3Q*.0.4Q*.0.5Q*.0.6Q*.0.7
0VL
+UL
Q*.2.0Q*.2.1Q*.2.2Q*.2.3Q*.2.4Q*.2.5Q*.2.6Q*.2.7
0VL
+UL
Q*.3.0Q*.3.1Q*.3.2Q*.3.3Q*.3.4Q*.3.5Q*.3.6Q*.3.7
0VL
+UL
Q*.1.0Q*.1.1Q*.1.2Q*.1.3Q*.1.4Q*.1.5Q*.1.6Q*.1.7
X1
X2
X3
X4
123456789
123456789
10
10
RMA02.1-32-DC024-050
123456789
10
Q*.0.0
0VL
123456789
10+UL
Q*.0.1Q*.0.2Q*.0.3Q*.0.4Q*.0.5Q*.0.6Q*.0.7
0VL
+UL
Q*.2.0Q*.2.1Q*.2.2Q*.2.3Q*.2.4Q*.2.5Q*.2.6Q*.2.7
0VL
+UL
Q*.3.0Q*.3.1Q*.3.2Q*.3.3Q*.3.4Q*.3.5Q*.3.6Q*.3.7
0VL
+UL
RME02.1-32-DC024
X1
X2
X3
X4
123456789
0VL
123456789
0VL
0VL
123456789
123456789
I*.3.0
0VL
I*.3.1I*.3.2I*.3.3I*.3.4I*.3.5I*.3.6I*.3.7
I*.2.0I*.2.1I*.2.2I*.2.3I*.2.4I*.2.5I*.2.6I*.2.7
I*.1.0I*.1.1I*.1.2I*.1.3I*.1.4I*.1.5I*.1.6I*.1.7
I*.0.0I*.0.1I*.0.2I*.0.3I*.0.4I*.0.5I*.0.6I*.0.7
X2
RMK12.2-IBS-BKL
RCBARDLDE
DIAG
RECONF
X4ALARM
GND
X3
OUT
IN
UL
X1
1
2
3
INTE
RBU
S
F1F/2,5A
24VDC
+UL
0VL
1
2
RECO
~
24V=
RME02.1-32-DC024
X1
X2
X3
X4
123456789
0VL
123456789
0VL
0VL
123456789
123456789
I*.3.0
0VL
I*.3.1I*.3.2I*.3.3I*.3.4I*.3.5I*.3.6I*.3.7
I*.2.0I*.2.1I*.2.2I*.2.3I*.2.4I*.2.5I*.2.6I*.2.7
I*.1.0I*.1.1I*.1.2I*.1.3I*.1.4I*.1.5I*.1.6I*.1.7
I*.0.0I*.0.1I*.0.2I*.0.3I*.0.4I*.0.5I*.0.6I*.0.7
Q*.1.0Q*.1.1Q*.1.2Q*.1.3Q*.1.4Q*.1.5Q*.1.6Q*.1.7
X1
X2
X3
X4
123456789
123456789
10
10
RMA02.1-32-DC024-050
123456789
10
Q*.0.0
0VL
123456789
10+UL
Q*.0.1Q*.0.2Q*.0.3Q*.0.4Q*.0.5Q*.0.6Q*.0.7
0VL
+UL
Q*.2.0Q*.2.1Q*.2.2Q*.2.3Q*.2.4Q*.2.5Q*.2.6Q*.2.7
0VL
+UL
Q*.3.0Q*.3.1Q*.3.2Q*.3.3Q*.3.4Q*.3.5Q*.3.6Q*.3.7
0VL
+UL
RME02.1-32-DC024
X1
X2
X3
X4
123456789
0VL
123456789
0VL
0VL
123456789
123456789
I*.3.0
0VL
I*.3.1I*.3.2I*.3.3I*.3.4I*.3.5I*.3.6I*.3.7
I*.2.0I*.2.1I*.2.2I*.2.3I*.2.4I*.2.5I*.2.6I*.2.7
I*.1.0I*.1.1I*.1.2I*.1.3I*.1.4I*.1.5I*.1.6I*.1.7
I*.0.0I*.0.1I*.0.2I*.0.3I*.0.4I*.0.5I*.0.6I*.0.7
X60
X64
0 5
1
6
2
7
3
8
4
90 5
1
6
2
7
3
8
4
9
MTS-R01.1
RESET
H1
PROG U1
X2
COM
123456
X1+24VGND
NC
WD
DEVICE-NOX3
RECO
8
X60X60
RME02.1-32-DC024
X1
X2
X3
X4
123456789
0VL
123456789
0VL
0VL
123456789
123456789
I*.3.0
0VL
I*.3.1I*.3.2I*.3.3I*.3.4I*.3.5I*.3.6I*.3.7
I*.2.0I*.2.1I*.2.2I*.2.3I*.2.4I*.2.5I*.2.6I*.2.7
I*.1.0I*.1.1I*.1.2I*.1.3I*.1.4I*.1.5I*.1.6I*.1.7
I*.0.0I*.0.1I*.0.2I*.0.3I*.0.4I*.0.5I*.0.6I*.0.7
Q*.1.0Q*.1.1Q*.1.2Q*.1.3Q*.1.4Q*.1.5Q*.1.6Q*.1.7
X1
X2
X3
X4
123456789
123456789
10
10
RMA02.1-32-DC024-050
123456789
10
Q*.0.0
0VL
123456789
10+UL
Q*.0.1Q*.0.2Q*.0.3Q*.0.4Q*.0.5Q*.0.6Q*.0.7
0VL
+UL
Q*.2.0Q*.2.1Q*.2.2Q*.2.3Q*.2.4Q*.2.5Q*.2.6Q*.2.7
0VL
+UL
Q*.3.0Q*.3.1Q*.3.2Q*.3.3Q*.3.4Q*.3.5Q*.3.6Q*.3.7
0VL
+UL
X60
X64
0 5
1
6
2
7
3
8
4
90 5
1
6
2
7
3
8
4
9
MTS-R01.1
RESET
H1
PROG U1
X2
COM
123456
X1+24VGND
NC
WD
DEVICE-NOX3
RECO
8
H1
X1
RX
TX
8
U1
MTC-R01.1
H1
DIAG
RX
TX
123456
X1+24VGND
NC
WD
8X60
RMG12.2-NN
CONFIG
IN
UL
H1
S1
X2
X1
X4
X3
X6
RC
BA
RD
UL
RC
BA
RD
X5
IN
OUT
+UL
0VL
+UL
0VL
OUT
RECO
INTE
RBU
SIN
TER
BUS
0
8
C 4DE
F
32
1
79A
B 56
8
~
24V=
~
24V=
~
24V=
X5
Figure 3-9: Possible applications
Gateway Module RMG12.2-NN Accessories 4-1
DOK-CONTRL-RMG12.2****-PR02-EN-P
4 Accessories
4.1 Cables and Connectors
Connectorname
Order number ofINDRAMAT cable
Mating connector ofthe unit
INDRAMAT
cable
Cable end
X1, X2, X3, X4
IKS056/..
MN: 255 96891
INS 526MN: 259 762INK 234
MN: 220 143
INS 525MN: 259 759
9 1 INTERBUS
connection
X5, X6 ---- 1) ---- 2) not yetdefined
supply
voltage
1) not available as a finished cable
2) included in the delivery of the RMG12.2-NN unit
4-2 Accessories Gateway Module RMG12.2-NN
DOK-CONTRL-RMG12.2****-PR02-EN-P
Gateway Module RMG12.2-NN Figures 5-1
DOK-CONTRL-RMG12.2****-PR02-EN-P
5 Figures
Figure 1-1: Selecting the data word width for both rings 1-1Figure 1-2: Mounting dimensions of RMG12.2-NN 1-2Figure 2-3: Pin assignments of the INTERBUS interfaces 2-5Figure 2-4: Meanings of the 7-segment display 2-6Figure 2-5: Activating the I/O error message 2-7Figure 3-6: Typical addressing 3-1Figure 3-7: Addressing as a function of the data width 3-1Figure 3-8: Possible applications 3-2
5-2 Figures Gateway Module RMG12.2-NN
DOK-CONTRL-RMG12.2****-PR02-EN-P
Gateway Module RMG12.2-NN Service Agencies
DOK-CONTRL-RMG12.2****-PR02-EN-P
Sales & Service Facilities
Germany
Vertriebsgebiet Mitte Germany Centre V/S Service
INDRAMAT GmbHBgm.-Dr.-Nebel-Str. 2D - 97816 Lohr am Main
Phone: +49 (0)9352/40-0Fax: +49 (0)9352/40-4885
Vertriebsgebiet Ost Germany East V/S Service
INDRAMAT GmbHBeckerstraße 31D - 09120 Chemnitz
Phone: +49 (0)371/35 55-0Fax: +49 (0)371/35 55-333
Vertriebsgebiet West Germany West V/S Service
INDRAMAT GmbHHarkortstraße 25D - 40849 Ratingen
Phone: +49 (0)2102/43 18-0Fax: +49 (0)2102/41 315
Vertriebsgebiet Nord Germany North V/S Service
INDRAMAT GmbHKieler Straße 212D - 22525 Hamburg
Phone: +49 (0)40/85 31 57-0Fax: +49 (0)40/85 31 57-15
Vertriebsgebiet Süd Germany South V/S Service
INDRAMAT GmbHRidlerstraße 75D-80339 München
Phone: +49 (0)89/540138-30Fax: +49 (0)89/540138-10
Gebiet Südwest Germany South-West V/S Service
INDRAMAT GmbHBöblinger Straße 25D-71229 Leonberg
Phone: +49 (0)7152/9 72-6Fax: +49 (0)7152/9 72-727
INDRAMAT Service-Hotline
INDRAMAT GmbHPhone: +49 (0)172/660 04 06
or
Phone: +49 (0)171/333 88 26
Service agencies in Germany
Service Agencies Gateway Module RMG12.2-NN
DOK-CONTRL-RMG12.2****-PR02-EN-P
Europe
Austria V/S Service
Mannesmann Rexroth Ges.m.b.H.Geschäftsbereich INDRAMATHägelingasse 3A - 1140 Wien
Phone: +43 (0)1/9852540-400Fax: +43 (0)1/9852540-93
Austria V/S Service
Mannesmann Rexroth G.m.b.H.Geschäftsbereich INDRAMATIndustriepark 18A - 4061 Pasching
Phone: +43 (0)7221/605-0Fax: +43 (0)7221/605-21
Belgium V/S Service
Mannesmann Rexroth N.V.-S.A.Geschäftsbereich INDRAMATIndustrielaan 8B-1740 Ternat
Phone: +32 (0)2/5823180Fax: +32 (0)2/5824310
Denmark V/S Service
BEC ASZinkvej 6DK-8900 Randers
Phone: +45 (0)87/11 90 60Fax: +45 (0)87/11 90 61
United Kingdom V/S Service
Mannesmann Rexroth Ltd.INDRAMAT Division4 Esland Place, Love LaneGB - Cirencester, Glos GL7 1YG
Phone: +44 (0)1285/658671Fax: +44 (0)1285/654991
Finland V/S Service
Rexroth Mecman OYAnsatie 6SF-017 40 Vantaa
Phone: +358 (0)9/84 91 11Fax: +358 (0)9/84 91 13 60
France V/S Service
Mannesmann Rexroth S.A.Division INDRAMATParc des Barbanniers4, Place du VillageF-92632 Gennevilliers Cedex
Phone: +33 (0)141 47 54 30Fax: +33 (0)147 94 69 41Hotline: +33 (0)6 08 33 43 28
France V/S Service
Mannesmann Rexroth S.A.Division INDRAMAT270, Avenue de LardenneF - 31100 Toulouse
Phone: +33 (0)5 61 49 95 19Fax: +33 (0)5 61 31 00 41
France V/S Service
Mannesmann Rexroth S.A.Division INDRAMAT91, Bd. Irène Joliot-CurieF - 69634 Vénissieux Cedex
Phone: +33 (0)4 78 78 53 65Fax: +33 (0)4 78 78 52 53
Italy V/S Service
Mannesmann Rexroth S.p.A.Divisione INDRAMATVia G. Di Vittoria, 1I - 20063 Cernusco S/N.MI
Phone: +39 (0)2/92 36 52 70Fax: +39 (0)2/92 36 55 12
Italy V/S Service
Mannesmann Rexroth S.p.A.Divisione INDRAMATVia Borgomanero, 11I - 10145 Torino
Phone: +39 (0)11/7 71 22 30Fax: +39 (0)11/7 71 01 90
Italy V/S Service
Mannesmann Rexroth S.p.A.Divisione INDRAMATVia del Progresso, 16 (Zona Ind.)I - 35020 Padova
Phone: +39 (0)49/8 70 13 70Fax: +39 (0)49/8 70 13 77
Italy V/S Service
Mannesmann Rexroth S.p.A.Divisione INDRAMATVia de Nicola, 12I - 80053 Castellamare di Stabbia NA
Phone: +39 (0)81/8 72 30 37Fax: +39 (0)81/8 72 30 18
Italy V/S Service
Mannesmann Rexroth S.p.A.Divisione INDRAMATViale Oriani, 38/AI - 40137 Bologna
Phone: +39 (0)51/34 14 14Fax: +39 (0)51/34 14 22
Netherlands V/S Service
Hydraudyne Hydrauliek B.V.Kruisbroeksestraat 1P.O. Box 32NL - 5281 RV Boxtel
Phone: +31 (0)411/65 19 51Fax: +31 (0)411/65 14 83
Netherlands V/S Service
Hydrocare B.V.Kruisbroeksestraat 1P.O. Box 32NL - 5281 RV Boxtel
Phone: +31 (0)411/65 19 51Fax: +31 (0)411/67 78 14
Spain V/S Service
Mannesmann Rexroth S.A.Divisiòn INDRAMATCentro Industrial SantigaObradors s/nE-08130 Santa Perpetua de MogodaBarcelona
Phone: +34 937 47 94 00Fax: +34 937 47 94 01
Spain V/S Service
Goimendi S.A.División IndramatJolastokieta (Herrera)Apartado 11 37E - 20017 San Sebastian
Phone: +34 9 43/40 01 63Fax: +34 9 43/39 17 99
Sweden V/S Service
Rexroth Mecman Svenska ABINDRAMAT DivisionVaruvägen 7S - 125 81 Stockholm
Phone: +46 (0)8/727 92 00Fax: +46 (0)8/64 73 277
Switzerland - East V/S Service
Mannesmann Rexroth AGGeschäftsbereich INDRAMATGewerbestraße 3CH-8500 Frauenfeld
Phone: +41 (0)52/720 21 00Fax: +41 (0)52/720 21 11
Switzerland - West V/S Service
Mannesmann Rexroth SADépartement INDRAMATChemin de l`Ecole 6CH-1036 Sullens
Phone: +41 (0)21/731 43 77Fax: +41 (0)21/731 46 78
Russia V/S Service
Tschudnenko E.B.Arsenia 22RUS - 153000 IvanovoRußland
Phone: +7 093/223 96 33or +7 093/223 95 48Fax: +7 093/223 46 01
Slowenia V/S Service
DOMELElektromotorji in gospodinjskiaparati d. d.Otoki 21SLO - 64 228 Zelezniki
Phone: +386 64/61 73 32Fax: +386 64/64 71 50
Turkey V/S Service
Mannesmann Rexroth Hidropar A..S.Fevzi Cakmak Cad No. 3TR - 34630 Sefaköy Istanbul
Phone: +90 212/541 60 70Fax: +90 212/599 34 07
European Service agencies (without Germany)
Gateway Module RMG12.2-NN Service Agencies
DOK-CONTRL-RMG12.2****-PR02-EN-P
Outside Europe
Argentina V/S Service
Mannesmann Rexroth S.A.I.C.Division INDRAMATAcassusso 48 41/7RA - 1605 Munro (Buenos Aires)
Phone: +54 (0)1/756 01 40+54 (0)1/756 01 36
Argentina V/S Service
NAKASEAsesoramiento TecnicoCalle 49, No. 5764-66RA - 1653 Villa BalesterProvincia de Buenos Aires
Phone: +54 (0) 1/768 24 13Fax: +54 (0) 1/768 36 43
Australia V/S Service
AIMS - Australian IndustrialMachinery Services Pty. Ltd.Unit 3/45 Horne STCampbellfield 3061AUS - Melbourne, VIC
Phone: +61 (0)3/93 59 02 28Fax: +61 (0)3/93 59 02 86
Brazil V/S Service
Mannesmann RexrothAutomação Ltda.Divisão INDRAMATRua Georg Rexroth, 609Vila Padre AnchietaBR - 09951-270 Diadema-SP[ Caixa Postal 377 ][ BR-09901-970 Diadema-SP ]
Phone: +55 (0)11/745 90 60+55 (0)11/745 90 70
Fax: +55 (0)11/745 90 50
Canada V/S Service
Basic Technologies CorporationBurlington Division3426 Mainway DriveBurlington, OntarioCanada L7M 1A8
Phone: +1 905/335 55 11Fax: +1 905/335-41 84
China V/S Service
Mannesmann Rexroth (China) Ldt.Shanghai Office - Room 206Shanghai Internat. Trade Centre2200 Yanan Xi LuPRC - Shanghai 200335
Phone: +86 21/62 75 53 33Fax: +86 21/62 75 56 66
China V/S Service
Mannesmann Rexroth (China) Ldt.Shanghai Parts & Service Center199 Wu Cao Road, Hua CaoMinhang DistrictPRC - Shanghai 201 103
Phone: +86 21/62 20 00 58Fax: +86 21/62 20 00 68
China V/S Service
Mannesmann Rexroth (China) Ldt.15/F China World Trade Center1, Jianguomenwai AvenuePRC - Beijing 100004
Phone: +86 10/65 05 03 80Fax: +86 10/65 05 03 79
China V/S Service
Mannesmann Rexroth (China) Ldt.A-5F., 123 Lian Shan StreetSha He Kou DistrictPRC - Dalian 116 023
Phone: +86 411/46 78 930Fax: +86 411/46 78 932
Hong KongV/S Service
Rexroth (China) Ldt.19 Cheung Shun Street1st Floor, Cheung Sha Wan,Kowloon, Hong Kong
Phone: +852 27/41 13 51/-54oder/or +852 27/41 14 30Fax: +852 27/86 07 33
India V/S Service
Mannesmann Rexroth (India) Ltd.INDRAMAT DivisionPlot. 96, Phase IIIPeenya Industrial AreaIND - Bangalore - 560058
Phone: +91 (0)80/8 39 21 01Fax: +91 (0)80/8 39 43 45
India V/S Service
Mannesmann Rexroth (India) Ltd.INDRAMAT DivisionPlot. A-58, TTC Industrial AreaThane Turbhe Midc RoadMahape VillageIND - Navi Mumbai - 400 701
Phone: +91 (0)22/7 61 46 22Fax: +91 (0)22/7 68 15 31
Indonesia V/S Service
PT. Rexroth WijayakusumaJl. Raya Bekasi Km 21PulogadungRI - Jakarta Timur 13920
Phone: +62 21/4 61 04 87+62 21/4 61 04 88
Fax: +62 21/4 60 01 52
Japan V/S Service
Rexroth Automation Co., Ltd.INDRAMAT Division1F, I.R. BuildingNakamachidai 4-26-44Tsuzuki-ku, Yokohama-shiJ - Kanagawa-ken 224-004
Phone: +81 459/42-72 10Fax: +81 459/42-03 41
Korea V/S Service
Mannesmann Rexroth-Seki Co Ltd.1500-12 Da-Dae-DongROK - Saha-Ku, Pusan, 604-050
Phone: +82 (0)51/2 60 06 18Fax: +82 (0)51/2 60 06 19
Korea V/S Service
Seo Chang Corporation Ltd.Room 903, Jeail Building44-35 Yeouido-DongYeoungdeungpo-KuC.P.O.Box 97 56ROK - Seoul
Phone: +82 (0)2/7 80 82 08+82 (0)2/7 80 82 09
Fax: +82 (0)2/7 84 54 08
Mexico V/S Service
Rexroth Mexico S.A. de C.V.Calle Neptuno 72Unidad Ind. VallejoMEX - 07700 Mexico, D.F.
Phone: +52 5 754 17 11+52 5 754 36 84+52 5 754 12 60
Fax: +52 5 754 50 73+52 5 752 59 43
South Africa V/S Service
HYTEC Automation (Pty) Ltd.28 Banfield Road,Industria NorthRSA - Maraisburg 1700
Phone: +27 (0)11/673 20 80Fax: +27 (0)11/673 72 69
Taiwan V/S Service
Rexroth Uchida Co., Ltd.No.1, Tsu Chiang StreetTu Cheng Ind. EstateTaipei Hsien, Taiwan, R.O.C.
Phone: +886 2/2 68 13 47Fax: +886 2/2 68 53 88
Service agencies outside Europe
Service Agencies Gateway Module RMG12.2-NN
DOK-CONTRL-RMG12.2****-PR02-EN-P
Outside Europe / USA
USA V/S Service
Mannesmann Rexroth CorporationINDRAMAT Division5150 Prairie Stone ParkwayUSA -Hoffman Estates, IL 60192-3707
Phone: +1 847/6 45 36 00Fax: +1 847/6 45 62 01
USA V/S Service
Mannesmann Rexroth CorporationINDRAMAT DivisionCentral Region Technical CenterUSA - Auburn Hills, MI 48326
Phone: +1 248/3 93 33 30Fax: +1 248/3 93 29 06
USA V/S Service
Mannesmann Rexroth CorporationINDRAMAT DivisionSoutheastern Technical Center3625 Swiftwater Park DriveUSA - SuwaneeGeorgia 30174
Phone: +1 770/9 32 32 00+1 770/9 32 19 03
USA V/S Service
Mannesmann Rexroth CorporationINDRAMAT DivisionNortheastern Technical Center99 Rainbow RoadUSA - East Granby,Connecticut 06026
Phone: +1 860/8 44 83 77+1 860/8 44 85 95
USA V/S Service