  • Catalogue 2011

    a Nexans company

  • 202/2

    011

    While every care is taken to ensure that the information contained in this publication is correct, no legal responsibility can be accepted for any inaccuracy. Nexans Network Solutions N.V. - Div. Euromold reserves the right to alter or modify the characteristics of its products described in this catalogue as standards and technology evolve.

    EUROMOLDEuromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium voltage energy distribution. Euromold provides a complete range of accessories for underground cables: premoulded EPDM rubber connectors for cables and epoxy bushings for transformers and switchgear, as well as a large range of cold-shrinkable terminations and joints from 12 to 42 kV.Euromold is also the manufacturer of electrical components for the high voltage accessories of the Nexans group.

    ISO 9001 CertificateSince 1992, Euromolds commitment to quality is demonstrated by its ISO 9001 certification.

    Laboratory accreditationSince June 2000, Euromolds independent ELAB laboratory obtained the BELAC accreditation no.144-TEST conform with the European standards for laboratories ISO 17025 for electrical testing of low and medium voltage cable accessories according to the international standards HD 623 and HD 629.

    International standardsAll our products meet the International standards like CENELEC HD 629.1, CENELEC EN 50180, IEC 60137, IEC 60502-4 or country speci-fications. Official certificates, CESI, KEMA, ATEX prove the conformity of our products. Long duration tests of existing or new products are con-tinuously performed in our test fields.

    Nexans Network SolutionsDiv. Euromold

    COMPANY PRESENTATION

  • 302/2

    011

    SEPARABLE CONNECTORSAND BUSHINGS

    INTERFACE B

    Table of contents400LR - elbow connector400TE - tee connector400T1 - equipment bushing400AR-1 - equipment bushing400AR-2 - equipment bushing400AR-8 - equipment bushing400SFR-P - equipment bushingAccessoriesPossible arrangements

    Interface BDimensions according to European CENELEC EN 50180 and 50181 (in mm).

    900.2

    Dia. 460.2

    Dia. 560.2

    Dia. 700.2

    40min

    Dia. forpin 14 0 -0.04

    11min

  • 4 02/20

    11

    Connecting possibilities

    BUSHINGS / ACCESSORIES

    CONNECTION CONNECTORS / ACCESSORIES

    (K)(M)400DR Dead-end receptacle

    (K)(M)400TE/GTee connector

    (K)(M)400SOPStand-off plug

    400GPEarthing plug

    dead-ending of equipment

    one cable toequipment

    cableisolation

    cableearthing

    (K)400RTPAReducing tap plug

    (K)(M)400CP-SC Connecting plug

    two cables to equipment

    tap-off630/250A

    in-line junction

    (K)(M)400LR/GElbow connector

    (K)400SFR-PEquipment bushing

    (K)(M)400AR-8Equipment bushing

    Equipmentinterface

    (K)(M)400AR-1Equipment bushing

    (K)(M)400T1Equipment bushing

    (K)(M)400AR-2Equipment bushing

  • 502/2

    011

    Specifications and standardsThe separable connector 400LR meets the requirements of CENELEC HD 629.1.

    Up to 36 kV - 400 A

    DesignSeparable connector comprising:1. Conductive EPDM insert.2. Conductive EPDM jacket.3. Insulating EPDM layer moulded between the insert and the jacket.4. Type B - 400 A interface as described by CENELEC EN 50180 and 50181.5. Conductor connector.6. Cable reducer.7. Earthing lead.

    The screen break design enables cable outer sheath testing without removing or dismantling the connector.

    400LRINTERFACE B

    ELBOW CONNECTOR

    ApplicationSeparable elbow connector (plug-in type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors...).

    6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV

    12/20 (24) kV12.7/22 (24) kV

    18/30 (36) kV

    Technical characteristics ThethickconductiveEPDM

    jacket provides a total safe to touch screen which ensures safety for personnel.

    Eachseparableconnectoristested for AC withstand and partial discharge prior to leaving the factory.

    210 mm

    365 mm

    4

    5

    1

    2

    3

    7

    6

    Separable connector

    type

    VoltageUm(kV)

    CurrentIr

    (A)

    Conductor sizes (mm2)

    min max400LR/G

    K400LR/G

    M400LR/G

    12

    24

    36

    400

    400

    400

    50

    25

    35

    240

    240

    185

  • 6

    Kit contentsThe complete (K)(M)400LR/G elbow connector kit comprises the following components:

    The kit also comprises lubricant, wipers,

    installation instructions and crimp chart.

    Ordering instructionsSelect the part numberwhich gives the best centring to the cable core insulation diameter and substitute X using table X, according to the conductor size and type.Add a 'K' for use up to 24 kV and add an 'M' for use up to 36 kV.

    Conductor

    contact

    400LRC-X

    Pin contact

    + hex. key

    400LRF

    Bail

    restraint

    400BA

    Connector housing

    (K)(M)400BLR/G

    Cable reducer

    411CA-W

    Orderingpart number

    Dia. over core insulation (mm)

    min max

    400LR/G-11-X400LR/G-15-X400LR/G-19-X400LR/G-22-X400LR/G-25-X400LR/G-27-X

    12.0

    16.0

    20.0

    23.5

    26.5

    28.5

    17.5

    22.0

    26.5

    31.0

    32.5

    37.5

    Example:The copper wire screened cable is 12 kV, 150 mm2 stranded copper with a diameter over core insulation of 23.5 mm.Order a 400LR/G-19-150(K)M-11-2 elbow connector kit.

    (K)(M)400LR/G-W-Xconnector kit

    Table X

    Table W

    Conductorsizes

    (mm)

    Aluminium Copper

    DIN hexagonal Deep indent DIN hexagonal

    25

    35

    50

    70

    95

    120

    150

    185

    240

    -

    35(K)M-12-2

    50(K)M-12-2

    70(K)M-12-2

    95(K)M-12-2

    120(K)M-12-2

    150(K)M-12-2

    185(K)M-12-2

    240(K)M-12-2

    -

    35KM-12-1

    50(K)M-12-1

    70(K)M-12-1

    95(K)M-12-1

    120(K)M-12-1

    150(K)M-12-1

    185(K)M-12-1

    240(K)M-12-1

    25(K)M-11-2

    35(K)M-11-2

    50(K)M-11-2

    70(K)M-11-2

    95(K)M-11-2

    120(K)M-11-2

    150(K)M-11-2

    185(K)M-11-2

    240(K)M-11-2

    For applicationsoutdoors and in humid climate.

    Order: +MWS.

    Components can be ordered individually.

    For use withcopper tape

    screened cables. Order: Kit MT.

    For use with Alupe orC 33-226 cables.

    Please contact our representative.

    For use with fabric tape (graphite) screened cables.

    Order additionalsemi-conductive tape

    (type TSC).

    For use withother cable types.

    Please contact our representative.

  • 702/2

    011

    Specifications and standardsThe separable connector 400TEmeets the requirements of CENELEC HD 629.1.

    Up to 36 kV - 400 A

    400TEINTERFACE B

    TEE CONNECTOR

    6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV

    12/20 (24) kV12.7/22 (24) kV

    18/30 (36) kV

    ApplicationSeparable tee connector (plug-in type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors...).

    Technical characteristics ThethickconductiveEPDM

    jacket provides a total safe to touch screen which ensures safety for personnel.

    Eachseparableconnectoristested for AC withstand and partial discharge prior to leaving the factory.

    Separable connector

    type

    VoltageUm(kV)

    CurrentIr

    (A)

    Conductor sizes (mm2)

    min max400TE/G

    K400TE/G

    M400TE/G

    12

    24

    36

    400

    400

    400

    70

    25

    35

    240

    240

    185

    255 mm

    220 mm

    390 mm

    4 9

    5

    1

    3

    2

    10 6 8

    7

    11

    DesignSeparable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Type B - 400 A interface as described by CENELEC EN 50180 and 50181. 5. Conductor connector. 6. Basic insulating plug (with VD point). 7. Cable reducer. 8. Conductive rubber cap. 9. Clamping pin contact. 10. Bail restraint. 11. Earthing lead.

    The screen break design enables cable outer sheath testing without removing or dismantling the connector.

  • 8

    The kit also comprises lubricant, wipers,

    installation instructions and crimp chart.

    Kit contentsThe complete (K)(M)400TE/G elbow connector kit comprises the following components:

    Ordering instructionsSelect the part numberwhich gives the best centring to the cable core insulation diameter and substitute X using table X, according to the conductor size and type.Add a 'K' for use up to 24 kV and add an 'M' for use up to 36 kV.

    Orderingpart number

    Dia. over core insulation (mm)

    min max

    400TE/G-11-X400TE/G-15-X400TE/G-19-X400TE/G-22-X400TE/G-25-X400TE/G-27-X

    12.0

    16.0

    20.0

    23.5

    26.5

    28.5

    17.5

    22.0

    26.5

    31.0

    32.5

    37.5

    (K)(M)400TE/G-W-Xconnector kit

    Conductor

    contact

    400TEC-X

    Clamping

    pin contact

    400TEF

    Bail

    restraint

    400T-BA

    Connector housing (K)

    (M)400BT/G

    Basic

    insulating

    plug +

    rubber cap

    (K)(M)400BIPA

    Cable reducer

    411CA-W

    Example:The copper wire screened cable is 24 kV, 240 mm2 stranded aluminium with a diameter over core insulation of 32.1 mm.Order 3 x K400TE/G-27-240(K)M-12-2 tee connector kit.

    Conductorsizes

    (mm)

    Aluminium Copper

    DIN hexagonal Deep indent DIN hexagonal

    25

    35

    50

    70

    95

    120

    150

    185

    240

    -

    35(K)M-12-2

    50(K)M-12-2

    70(K)M-12-2

    95(K)M-12-2

    120(K)M-12-2

    150(K)M-12-2

    185(K)M-12-2

    240(K)M-12-2

    -

    35KM-12-1

    50(K)M-12-1

    70(K)M-12-1

    95(K)M-12-1

    120(K)M-12-1

    150(K)M-12-1

    185(K)M-12-1

    240(K)M-12-1

    25(K)M-11-2

    35(K)M-11-2

    50(K)M-11-2

    70(K)M-11-2

    95(K)M-11-2

    120(K)M-11-2

    150(K)M-11-2

    185(K)M-11-2

    240(K)M-11-2

    Table X

    Table W

    For applicationsoutdoors and in humid climate.

    Order: +MWS.

    Components can be ordered individually.

    For use withcopper tape

    screened cables. Order: Kit MT.

    For use with Alupe orC 33-226 cables.

    Please contact our representative.

    For use with fabric tape (graphite) screened cables.

    Order additionalsemi-conductive tape

    (type TSC).

    For use withother cable types.

    Please contact our representative.

  • 902/2

    011

    Up to 36 kV - 400 A

    Equipmentbushing

    type

    VoltageUr

    (kV)

    CurrentIr

    (A)

    Dimensions (mm)

    A B C D E Dia. F Dia. G Dia. H

    400T1K400T1M400T1400AR-1

    K400AR-1M400AR-1400AR-2

    K400AR-2M400AR-2

    122436122436122436

    400400400400400400400400400

    310310310380380380329329329

    144144144213213213138138138

    303030303030363636

    M12M12M12M12M12M12M16M16M16

    222222222222404040

    888888747474100100100

    128128128128128128150150150

    161616161616303030

    400T1 /400AR-1 /400AR-2INTERFACE B

    EQUIPMENT BUSHINGS

    ApplicationFor use in equipment insulated with oil fluid, typically for transformers, switchgear, capacitors...

    6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV

    12/20 (24) kV12.7/22 (24) kV

    18/30 (36) kV

    Technical characteristics Each bushing is tested forAC withstand and partialdischarge prior to leaving thefactory.

    Ordering instructionsTo order the equipment bushing, specify the type.The bushings are supplied with an earth jumper (/J) or an earth plate (/GS). This earth connection must be specified when ordering.E.g. K400AR-1/J.

    Specifications and standardsThe plug-in type equipment bushings are moulded epoxy insulated parts and meet the requirements of IEC 60137. The (K)(M)400T1 also meets CENELEC EN 50180 .

    In mm

    Minimum oil level:-12 kV: 40 mm-24 kV: 50 mm-36 kV: 70 mm

    E

    Dia. G

    133

    B

    A

    Dia. F

    Dia. 70D

    10

    C

    Dia.H

  • 10

    FIXINGS FOR EQUIPMENT BUSHINGS

    In mm

    400AR-1/J and 400T1/J Bushings

    400AR-2/GS Bushing

    Bushing clamping kitTo order the bushing clamping kit, according to NFC 52-053 standards, simply specify KBCNF-400 (for bushing type 400AR-2).Contents: - 4 x claw clamp NF - 1 x sealing gasket.

    Fixing dimensions standards NF C 52-053French standards.

    Fixing dimensions standards DIN 42 538German standards.

    Dia. 105Dia. 171

    6030

    6 fixingstuds

    M10M10 or M12

    Dia. 105Dia. 171

    50 to 7025

    4 fixingstuds

    55

    Dia. 140Dia. 90

    30

    M10

    6 fixingstuds

    Fixing dimensions

    Bushing clamping kitTo order the bushing clamping kit, simply specify: KBCDS-400B. Contents: - 1 x fixing flange - 6 x stud clamp F - 1 x sealing gasket.

    400AR-2/J Bushing

    bushing interface

    fixing studs

    equipmentconnection

    sealing gasket

    earthjumper

    F DIN 42 538stud clamp

    fixing flange

    NF C 52-053claw clamp

    equipment

    earthplate

    tabs for thebail restraint

    fixing flangeB DIN 42 538

    E DIN 42 538stud clamp

    bushinginterface

    fixing studs

    equipment

    sealing gasket

    equipmentconnection

    tabs for thebail restraint

    earthjumper

    Bushing clamping kitTo order the bushing clamping kit, according to DIN 42 538 standards, simply specify KBCD-400B.Contents: - 1 x fixing flange B - 6 x stud clamp E - 1 x sealing gasket.

  • 11

    02/2

    011

    Equipmentbushing

    type

    VoltageUr

    (kV)

    CurrentIr

    (A)

    400AR-8

    K400AR-8

    M400AR-8

    12

    24

    36

    250

    250

    250

    Up to 36 kV - 250 A

    400AR-8INTERFACE B

    EQUIPMENT BUSHING

    ApplicationFor use in equipment insulated with oil fluid, typically for transformers, switchgear, capacitors...

    Technical characteristics Each bushing is tested forAC withstand and partial discharge prior to leavingthe factory.

    Ordering instructionsTo order the equipment bushing, specify the type.The bushings can be supplied with an earth jumper (/J).E.g. M400AR-8/J.

    In mm.

    6/10 (12) kV6,35/11 (12) kV8,7/15 (17,5) kV

    12/20 (24) kV12,7/22 (24) kV

    18/30 (36) kV

    80

    231.528

    Dia. 74

    Dia. 110

    20

    Minimum oil level:-12 kV: 40 mm-24 kV: 50 mm-36 kV: 70 mm

    M10

    8.5Dia.20

    Specifications and standardsThe plug-in type equipment bushings 400AR-8 are moulded epoxy insulated parts and meet the requirements of CENELEC EN 50180 and IEC 60137.

  • 12

    In mm.

    FIXINGS FOR EQUIPMENT BUSHINGS

    400AR-8/J Bushing

    55

    M10

    Dia. 78

    Dia. 123

    25

    4 fixingstuds

    Fixing dimensions standards DIN 42 538German standards.

    Bushing clamping kitTo order the bushing clamp-ing kit, according to DIN 42 538 standards, simply specify: KBCD-200.Contents: - 1 x fixing flange A - 4 x stud clamp E - 1 x sealing gasket.

    4 x fixing stud M10

    A DIN 42 538fixing flange

    E DIN 42 538stud clamp

    equipment

    tabs for thebail restraint

    bushing interface

    sealing gasket

    equipmentconnection

    earth jumper

  • 13

    02/2

    011

    Up to 24 kV - 400 A

    400SFR-PINTERFACE B

    EQUIPMENT BUSHING

    ApplicationFor use in equipment insulated with SF6 gas.

    6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV

    12/20 (24) kV12.7/22 (24) kV

    DesignThe equipment bushing is a moulded epoxy insulated part with a connector interface in accordance with CENELEC EN 50180. The 400SFR-P bushing has a shank outside this standard, adapted for use in SF6 gas.

    Technical characteristics Each bushing is tested forAC withstand and partialdischarge prior to leaving thefactory.

    Ordering instructionsTo order the equipment bushing, simply specify the type.

    Specifications and standardsThe plug-in type equipment bushing 400SFR-P meets the requirements of CENELEC EN 50180 and IEC 60137.

    Equipmentbushing

    type

    VoltageUr

    (kV)

    CurrentIr

    (A)

    400SFR-P

    K400SFR-P

    12

    24

    400

    400

    Dia. 70

    95

    33

    218

    Dia. 109

    Dia. 25

    Dia. 70

    M12

    In mm.

  • 14

    FIXINGS FOR EQUIPMENT BUSHINGS

    400SFR-P Bushing for gas insulated switchgear

    In mm.

    MOUNTED

    equipment

    sealingO-ringgasket

    equipmentconnection

    bushinginterface 6 fixing

    screwsM6

    UNMOUNTED

    earthconnection

    M4

    60

    6060

    Dia. 91.5Dia. 103.1

    83

    M6

    M4

  • 15

    02/2

    011

    ACCESSORIESINTERFACE B

    Up to 24 kVApplicationFor use with connectors and bushings with an interface B as described by CENELEC EN 50180 and 50181.

    Technical characteristics All these products, except theearthing plug, are tested forAC withstand and partialdischarge prior to leaving thefactory. 6/10 (12) kV

    6.35/11 (12) kV8.7/15 (17.5) kV

    12/20 (24) kV12.7/22 (24) kV

    18/30 (36) kV

    400DRDead-end receptacleFits over a bushing with a type B interface to provide 'dead-end' facility.Is used with a 400BA restraint bail.

    Ordering instructionsOrder400DR for 12 kV,K400DR for 24 kV orM400DR for 36 kVapplications.Can be supplied with integral earth lead: add -/G.

    400GPEarthing plugIs designed to support and earth connectors with a type B interface when removed from equipment.

    Ordering instructionsOrder 400SOP for 12 kV,K400SOP for 24 kV orM400SOP for 36 kVapplications.

    Ordering instructionsOrder 400GP for 12 kV, 24 or 36 kVapplications.

    400SOPStand-off plugIs designed to support and 'dead-end' connectors with a type B interface when removed from equipment.

  • 16

    400CP-SCConnecting plugFor connecting a 400TE and one or more 430TB, 400TB or 440TB connectors, thus creating a multiple cable connection to equipment.

    Ordering instructionsOrder 400CP-SC for 12 kV,K400CP-SC for 24 kV orM400CP-SC for 36 kVapplications.

    400RTPAReducing tap plugProvides a type A interface to a 400TE connector.A 'C' spanner, 600SW, is used to tighten the reducing tap plug on to its mating part.

    Ordering instructionsOrder 400RTPA for 12 kV orK400RTPA for 24 kVapplications.Order 600SW for the 'C'spanner.

    Kit MTEarthing kit for copper tape screened cablesContains a tinned copper braid (25 mm - L=500 mm), a tinned copper wire for cleating and water sealing mastic.

    Ordering instructionsOrder Kit MT for 12 kV, 24 kV or 36 kV applications.

    400BIPABasic insulating plugActs as a tightening nut for the 400TE tee connector kit.The plug contains a voltage detection point.The conductive rubber protection cap is included.

    Ordering instructionsOrder 400BIPA for 12 kV,K400BIPA for 24 kV orM400BIPA for 36 kVapplications.

  • 17

    02/2

    011

    POSSIBLE ARRANGEMENTSINTERFACE B

    400TE/GSingle cable arrangement.Order 400TE/G for 12 kV,K400TE/G for 24 kV or M400TE/G for 36 kV applications.

    400TE/G-P2Dual cable arrangement.Order 400TE/G-P2 for 12 kV, K400TE/G-P2 for 24 kV or M400TE/G-P2 for 36 kV applications.

    400TE/G-P4Single cable arrangement with tap-off.Order 400TE/G-P4 for 12 kVor K400TE/G-P4 for 24 kV applications.

    250

    110

    basic insulating

    plug

    500

    110 245

    basic insulating

    plug

    400TCS clamping

    screw

    connecting plug

    475

    110 233

    reducing tap plug

    type A separable connector

    In mm

  • 18

    basic insulating

    plug

    stand-off plug

    basic insulating

    plug

    earthing plug

    Connector on earthing plugOrder 400GP for 12 kV, 24 kV and 36 kV applications.

    Connector on stand-off plugOrder 400SOP for 12 kV, K400SOP for 24 kV or M400SOP for 36 kV applications.

    In mm

    110

    600

    400TR test rod

    insulating shroud

    Cable and equipment testing

  • Additional catalogue information on power cable accessoriesis available by contacting us at the address below:

    NexansNetworkSolutionsN.V.-Div.EuromoldZuidIII,Industrielaan12,B-9320ErembodegemTel.:+32(0)53850211Fax:+32(0)[email protected]

    Catalogue also available on CD-ROM

    Distributed by: