Introduction to 3-Phase Meters
Northwest Electric Meter SchoolAugust 21,2017
Adam Schwab ~ Meter/Relay Tech.Grant County PUD
2
Meter Pulling device
Objectives• Provide a brief overview of polyphase meters
• Provide a basic description of electromechanical meter construction and operation
• Introduce the meter constant calculation for electromechanical meters
• Provide a short introduction to the meter form and wiring connections
3
Introduction
• The 3-phase meter functions under the same principles as the single phase meter.
• A 3-phase meter is basically 3 single phase meters combined in one meter.
• Can measure kilowatt hour consumption or kilowatt demand or both.
Blondel’s Theorem
• In a system of N current carrying conductors, N-1 elements, properly connected, will measure the power used. All voltage coils must have a common tie to the conductor in which there is no current coil.
4
Base Design
• A – Base meter– All connections to meter are made on the bottom of the base which
can’t be detached from the meter. Requires no socket or base.
• S – Base meter (Socket) – All connections to the meter are made to the meter socket, which
enables you to change out the meter without rewiring.
• K – Base meter– All connections are made to socket. The meter has bus attached to
the back which has to be bolted into the base.
• Switchboard meter– All connections are made to switchboard meter case, meter simply
slides out and can be replaced very easily.
A -BASE
5
A-BASE CONVERSION
A – Base Meter
6
S(Socket) – Base meter, socket and test switch
K - Base
7
Switchboard Meter
Measuring Capacity
• Self Contained– Class 100– Class 200– Class 320– Class 480(K-base)
• Transformer rated (CT Meter)– Class 10– Class 20
8
Types
• Electromechanical
• Hybrid– Typically electromechanical meter with an
electronic demand register.
• Solid State / Electronic
Prove the meter constant
• (Kh x Rr x Rs) / 10,000 = Meter Constant– Kh = Watthour constant. The number of watthours
represented by one revolution of the disk.
– Rr = Register ratio. The number of revolutions of the gear which meshes with the disk shaft, per complete rotation of the fastest dial pointer.
– Rs = Shaft gear reduction (first reduction). The number of revolutions of the disk rotor shaft per complete revolution of the gear it engages.
9
Get Kh, Rr and Model #
Metering Symbols
• Kh Watthour constant. The number of watthour per disk revolution.
• Rs Shaft gear reduction (ratio between rotor shaft and first gear )
10
Shaft Reductions
Get Rs for the meter
Some CommonMeter Forms
andPossible connections.
Meter forms are defined in ANSI standardC12.10
11
Form 9S
4WireCT RatedWye
Form 9 wiring example
12
Form 5S
3 or 4 wire serviceWye or DeltaCT rated
Form 5S wiring example
13
Form 6S
4 WireWyeCT ratedZ-coil
Form 6S wiring example
14
Form 8S
4 WireDeltaCT rated
Form 8S wiring example
15
Form 12S
3 WireWye or DeltaSelf contained
Form 12S wiring example
16
Form 15S
4 WireDeltaSelf contained
Form 15S wiring example
17
Form 16S
4 WireWyeSelf contained
Form 16S wiring example
18
Form 14S
Two half turns
4 WireWyeSelf containedZ-coil
Electromechanical Basics
• Voltage is passed through a potential coil.
• Current is passed through a current coil.
• Current and voltage fluxes are created and combined to produce torque on the disk and cause rotation.
19
Electromechanical Meters
• An aluminum Laminated disk– Rotor– Creep holes– Worm Gear on shaft. (Single cut or double)– Magnetic bearings are on top and bottom, and suspend
the disk, minimizing friction. (or jewel bearings)– The sectored disk restricts eddy currents induced in the
disk from reacting with the flux of other stators.
• Stators (2, 2.5, 3) A stator is formed by a potential coil and a current coil.
Electromechanical Meters cont.
• Magnetic Shields– Placed around the voltage coils prevent leakage flux from reacting
with the wrong eddy currents and causing metering errors.
• Current coil shields– Made of plastic– To isolate technician from voltage during adjustment.
• Potential coil lights– Indicate that voltage is present– Can be incandescent or Led
• Voltage ranges are often narrow.
20
Electromechanical Meters cont.
• Mechanical register.– Many intricate gears– Acts like an adding machine and accumulates the
revolutions of the disk.– Pointer style or cyclometer.
• Can be calibrated and repaired in the shop or field.– There are adjustment screws for Full Load, Light Load
and Power Factor.
• Are sometimes heavy due to amount of metal parts.
Magnetic shield
Light Load Adj.
Power Factor Adj.
Full Load Adj.
21
Sectored Disk
Current Coil
Potential Coil
Magnetic Bearing
Register
Retarding Magnet
Potential indicatingLight
22
Demand Motor
Demand Register
Kilowatt hour Register
Electronic Basics
• Current is passed through a current sensor. (Small CT)• Voltage is measured with the equivalent of a digital multi-
meter.• The voltage, current and angle are mathematically
computed to find kilowatt hour consumption.• The values are then displayed on the LCD screen. Much
more information is available.• Much more accurate then electromechanical meter at very
light loads. (No friction from register or disk)
23
Electronic Meters
• Automatic-wide voltage range
• LCD display and register
• Voltage indicators for each phase
• Current sensors
• No moving parts to wear out
• Lightweight and easily handled
Electronic Meters cont.
• Need to be factory calibrated and repaired (some first generation meters had some adjustments)
• Auto detect wye or delta
• Multiple form replacement– Electronic > Mechanical
• 45S = 5S
• 9S = 8S and 9S (6S requires moving C phase potential)
• 16S = 14S, 15S And 16S
24
Electronic Meters cont.
• Site survey software– Per phase values for:
• Voltage and voltage angle• Current and current angle• Power factor
– Total harmonic distortion– Much more can be available– Diagnostics for many conditions, with user
adjustable thresholds.
Electronic Meter
25
Electronic Meter Brains
Current Sensor
26
Switchboard Meters
• Commonly used in substation metering
• With both current transformers and voltage transformers.
• Commonly contain a modem for remote interrogation.
• KYZ outputs for customer or SCADA indication. (Supervisory Control And Data Acquisition)
• Bidirectional (4 Quadrant) metering
27
Switchboard Meter
Switchboard Meter Case
28
Switchboard Meter
29
Can you guess which form # ?