Page 1: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

Compatibility Report

Comtrol IO-Link Master

Banner Engineering TL50 Tower Light

Page 2: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 2

Table of Contents

Table of Contents .................................................................................................................................................................... 2

Test Report Overview ............................................................................................................................................................. 3

IO-Link Master – IO-Link Diagnostics Page ............................................................................................................................ 3

Configuring IO-Link Settings Settings ..................................................................................................................................... 4

After Configuring Friendly Port Names ................................................................................................................................ 5

Setting Up Passwords ............................................................................................................................................................. 6

IO-Link Device Configuration .................................................................................................................................................. 7

Loading the IODD Files ....................................................................................................................................................... 7

Verifying that the Correct IODD Files Loaded ................................................................................................................... 10

Changing Tower Light Parameters Using the GUI ............................................................................................................ 11

Changing Parameters Using the ISDU Interface............................................................................................................... 16

Using the Data Storage Feature ........................................................................................................................................... 19

Resetting the Tower Light to Factory Defaults ...................................................................................................................... 23

Automatic Download ............................................................................................................................................................. 26

Clearing Data Storage ........................................................................................................................................................... 28

Manual Data Storage ............................................................................................................................................................ 30

Using the Device Validation Feature ..................................................................................................................................... 35

Incompatible Device Attached to Port ............................................................................................................................... 35

Using the Data Validation Feature ........................................................................................................................................ 37

Page 3: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 3

Test Report Overview

The Banner Engineering TL50 Tower Light operates properly with the Comtrol IO-Link Master. This report contains the following topics:

• IO-Link Master – IO-Link Diagnostics page

• Configuring IO-Link settings

• Setting up passwords

• IO-Link device configuration

• Using the data storage feature

• Using the device validation feature

The Tower Light was tested using Application Base v1.4.16 (and WebGUI 1.4.1.28) on the IO-Link Master 4-EIP (machine mountable IP67). This report does not illustrate all Comtrol IO-Link Master features, such as: EtherNet/IP and Modbus/TCP configuration, uploading the latest software, or network configuration.

IO-Link Master – IO-Link Diagnostics Page

A Banner Engineering TL50 Tower Light was connected to the Comtrol IO-Link Master and upon connection, the IO-Link Diagnostics page immediately displayed the device on Port 3.

Page 4: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 4

Configuring IO-Link Settings Settings

During IO-Link configuration, the Minimum Cycle Time can be left to the default value, as the IO-Link Master negotiates the required Cycle Time with each IO-Link device.

This example shows configuring a port-friendly name. The Data Storage and Device Validation features are discussed later in this report after using the IO-Link Master to configure the IO-Link device parameters.

Page 5: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 5

After Configuring Friendly Port Names

You can use the IO-Link Settings page to customize the Port Name. The IO-Link Diagnostics page now displays a friendly port name.

Page 6: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 6

Setting Up Passwords

The IO-Link Master ships from the factory without passwords and administrative permissions are granted. You can use the Advanced | Accounts page to set up passwords for the IO-Link Master. Admin, Operator, and User permissions are defined in the help system on the Accounts page.

Page 7: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 7

IO-Link Device Configuration

You can use the Comtrol IO-Link Master to configure the IO-Link device.

• If an IODD file is loaded, you may want to use the table (GUI) on the top of the IO-Link Device – Port page to change parameter settings.

• If an IODD file is not loaded, you can use the ISDU Interface on the bottom of the IO-Link Device – Port page

This section discusses the following topics:

• Loading IODD files

• Verifying that the correct IODD file is loaded

• Changing IO-Link device parameters using the GUI

• Resetting to the IO-Link device to factory defaults

• Changing IO-Link device parameters using the ISDU Interface

Loading the IODD Files

The following image shows loading the IODD file for the TL50 Tower Light .

1. Click Attached Devices | IODD Files.

2. Click the UPLOAD FILE button.

3. Click CHOOSE FILE and select the file set to upload.

Page 8: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 8

4. Click the UPLOAD button.

5. If there are files in the IODD file set that are not required by the associated xml file, the IO-Link Master does not load the files, and displays an Ignored Files message. Click Ok to close the message.

6. Click the file name in the table if you want to review the xml file.

Page 9: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 9

7. Optionally, click the hyperlink if you want to view the xml file in your browser.

Page 10: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 10

Verifying that the Correct IODD Files Loaded

The IO-Link Master can verify that the correct IODD files for a product have loaded using the Configuration Summary page.

1. Click Attached Files | Configuration Summary.

2. Verify that the port that the device is connected to displays an xml file name in the IODD Name field, as illustrated in this image.

Page 11: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 11

Changing Tower Light Parameters Using the GUI

The TL50 displays properly in the IO-Link Device – Port page:

1. Click Attached Devices | Port 3 (in this example). The TL50 displays in the PORT page. You can collapse parameter group to speed up the page loading.

Page 12: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 12

2. Click the EDIT button to make parameter changes using the GUI.

In this example the following changes were made in the table, Index 67 Sub-Indexes 1 through 7 changed from 1 to 10.

Page 13: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 13

3. Observe that the changes have been made.

4. At this point, Modbus Poll was opened and configured to send PDO.

5. Open Read/Write Definition and configure it as shown.

Note: The first digit of the Address is the port number. This example uses Port 3. Quantity means the number of registers.

Page 14: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 14

6. Connect using the appropriate IP address.

7. Enter the appropriate hex value to operate the segments using the Banner EZ-Light TL50 with IO-Link Data Map to

determine register value using the IO-Link Process Data Out (Master to Device) section.

Page 15: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 15

This is image shows that the Light Tower is lit (155h).

Page 16: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 16

Changing Parameters Using the ISDU Interface

This shows using the IO-Link ISDU Interface to change configuration parameters.

Please note:

• You must enter the decimal value for the ISDU Block Index and ISDU Sub-index.

• You must enter the hexadecimal value in the interface.

• The following screenshots do not illustrate the system responses. The IO-Link Master responds with a command executed notification.

The following shows how to use the IO-Link ISDU Interface to change IO-Link device configuration parameters. The PDO is set to 189 so that every other segment is flashing.

1. Expand the IO-Link Device ISDU Interface at the bottom of the page.

Page 17: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 17

The following images do not display the complete web page.

2. Verify that the Tower Light responds to queries.

a. Enter the ISDU Block Index and the ISDU Sub-index.

b. Click GET.

3. Change Index 67 | Sub-index 2 to 1 and click SET. Notice that this index uses a gradient, which must taken into consideration when using the ISDU Interface.

Page 18: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 18

4. Change Index 67 sub-index 4 to 1.

5. To verify the parameter changes, click the REFRESH button. Optionally, you can perform a GET on each changed index.

Page 19: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 19

Using the Data Storage Feature

The following examples illustrate automatic and manual data storage. Index 67 has been changed accordingly before enabling the Automatic Upload feature and after resetting the Tower Light to factory defaults, the Download Data Storage feature. Sub-indexes 1, 3 and 5 are set at 10 and Sub-indexes 2 and 4 are set to 1.

This example automatically uploads data storage using the above values.

1. Access the Configuration | IO-Link Settings page.

2. Click the EDIT button on the corresponding port.

3. Click Automatic Upload Enable to On.

4. Click SAVE. The data storage (Tower Light configuration) uploads to the IO-Link Master as soon as the SAVE button is clicked.

Page 20: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 20

5. Refresh (F5) the IO-Link Settings page to verify that the port contains Storage Contents.

Page 21: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 21

6. Click Diagnostics | IO-Link, which displays Automatic Data Storage Configuration for Upload-Download is enabled.

Page 22: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 22

7. Click the EDIT button, set Automatic Upload Enable to Off, and click SAVE.

8. Access the IO-Link Device – Port page and reset the settings to their factory settings.

Page 23: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 23

Resetting the Tower Light to Factory Defaults

The Tower Light can be returned to the factory defaults.

1. Click Attached Devices | Port 3 (in this example) and the COMMAND button.

2. Scroll down and click the Restore Factory button.

Page 24: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 24

3. Click OK to the Refresh message.

Page 25: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 25

5. Click the Cancel button to return to user mode.

6. You can verify that the parameters returned to their factory default values.

Page 26: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 26

Automatic Download

This shows how automatic download works. Remember, previously values were uploaded to the IO-Link Master. You must upload data storage into the IOLM before it can be downloaded to the Tower Light.

1. Return to the IO-Link Settings page, click EDIT, set the Automatic Download Enable option to On, and click SAVE.

Page 27: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 27

2. Verify that the Data Storage parameters have automatically downloaded to the device.

3. Click Configuration | IO-Link.

4. Click the EDIT button.

5. Set Automatic Download Enable to Off.

6. Click SAVE.

Page 28: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 28

Clearing Data Storage

This shows how clearing data storage on the IO-Link Master works.

1. Click Configuration | IO-Link.

2. Click the EDIT button.

3. Click the CLEAR button and then click CONTINUE.

Page 29: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 29

4. Click Ok to the Done message and then click SAVE.

Page 30: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 30

Manual Data Storage

The following illustrates how Manual Data Storage works. This procedure downloads the data storage from the port from the previous automatic upload.

1. Click Configuration | IO-Link Settings.

2. Click the EDIT button.

3. Click the UPLOAD button under Data Storage Manual Ops.

Page 31: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 31

4. Click CONTINUE.

5. Click Ok to the DONE message.

6. Click SAVE or CANCEL to close the port.

Page 32: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 32

7. Observe that the port contains data storage on the port.

8. Set the Tower Light back to factory defaults.

Page 33: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 33

9. Return to the IO-Link Settings page.

10. Click the EDIT button.

11. Click the DOWNLOAD button and then click the CONTINUE button.

12. Click Ok to the Done message that Data Storage Download successful on Port 1.

Page 34: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 34

13. Click SAVE or CANCEL and return to the Port page, observe that the values were downloaded on the Tower Light.

Page 35: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 35

Using the Device Validation Feature

The DF-GI supports Device Validation, Compatible or Identical. Identical Device Validation is not illustrated since only one Tower Light was available for this report.

Incompatible Device Attached to Port

1. Click Configuration | IO-Link page, click EDIT, and set Device Validation mode to Compatible.

2. Click the GET ATTACHED button.

3. Click SAVE.

Page 36: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 36

4. Remove the Tower Light from Port 1 and connect another IO-Link device (not a TL50).

5. The IO-Link LED on the IO-Link Master is now flashing red to indicate that an incompatible device is connected to the port. In addition, the IO-Link Diagnostics page displays that an incompatible device is attached to the port.

6. Reconnect the TL50 to Port 3.

Page 37: IO-Link Master and SICK MLG10A-0140I10501 Light Grid · 1/19/2017 Banner Engineering TL50 Tower Light 7 IO-Link Device Configuration You can use the Comtrol IO-Link Master to configure

1/19/2017 Banner Engineering TL50 Tower Light 37

Using the Data Validation Feature

1. Click Configuration | IO-Link page, click EDIT, and set Data Validation mode to Strict.

2. Click the GET ATTACHED button.

3. Click SAVE.