Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information under the control of public authorities, in order to promote transparency and accountability in the working of every public authority, and whereas the attached publication of the Bureau of Indian Standards is of particular interest to the public, particularly disadvantaged communities and those engaged in the pursuit of education and knowledge, the attached public safety standard is made available to promote the timely dissemination of this information in an accurate manner to the public. इंटरनेट मानक !ान $ एक न’ भारत का +नम-णSatyanarayan Gangaram Pitroda “Invent a New India Using Knowledge” प0रा1 को छोड न’ 5 तरफJawaharlal Nehru “Step Out From the Old to the New” जान1 का अ+धकार, जी1 का अ+धकारMazdoor Kisan Shakti Sangathan “The Right to Information, The Right to Live” !ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता ह Bharthari—Nītiśatakam “Knowledge is such a treasure which cannot be stolen” IS 6234 (2003): Portable Fire Extinguishers Water Type (Stored Pressure) -Specification [CED 22: Fire Fighting]

Upload: others

Post on 10-Mar-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second

Disclosure to Promote the Right To Information

Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information under the control of public authorities, in order to promote transparency and accountability in the working of every public authority, and whereas the attached publication of the Bureau of Indian Standards is of particular interest to the public, particularly disadvantaged communities and those engaged in the pursuit of education and knowledge, the attached public safety standard is made available to promote the timely dissemination of this information in an accurate manner to the public.

इंटरनेट मानक

“!ान $ एक न' भारत का +नम-ण”Satyanarayan Gangaram Pitroda

“Invent a New India Using Knowledge”

“प0रा1 को छोड न' 5 तरफ”Jawaharlal Nehru

“Step Out From the Old to the New”

“जान1 का अ+धकार, जी1 का अ+धकार”Mazdoor Kisan Shakti Sangathan

“The Right to Information, The Right to Live”

“!ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता है”Bhartṛhari—Nītiśatakam

“Knowledge is such a treasure which cannot be stolen”

“Invent a New India Using Knowledge”

है”ह”ह

IS 6234 (2003): Portable Fire Extinguishers Water Type(Stored Pressure) -Specification [CED 22: Fire Fighting]

Page 2: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second
Page 3: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second
Page 4: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second

IS 6234 : 2003Reaffirmed 2008

( )

Indian Standard

PORTABLE FIRE EXTINGUISHER WATER TYPE

(STORED PRESSURE) — SPECIFICATION

( Second Revision)

ICS 13 220 10

© BIS 2003

B U R E A U O F I N D I A N S T A N D A R D S MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG

NEW DELHI 110002

August 2003 Price Group 3

Page 5: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second

.AMENDMENT NO.1 MARCH 2005TO

IS 6234': 2003 PORTABLE FIRE EXTINGUISHER,WATER TYPE (STORED PRESSURE)­

SPECIFICATION

( SecondRevision)

( Page I, clause 7,1.2) _. Substitute '600' for '300'.

[ Page 2, clause S, Table I, Sl No:(ii), col 3 and 4 J - Add the followingunder col 3 and 4:

(3) (4)

b) Stainless Steel IS 6913

[ Page 2, Table 1, Sl No. (ix), col 4 ]- Substitute 'Havingbursting pressureofnotlessthan SOkgficm

2 'for 'IS 14933'.

( Page 3, clause 9.1 ) - Insert 'or Post Office Red' after 'fire red' and'No. 538' after 'No. 536'.

( Page 3, clause 10.3 ) - Substitute the following for the existing:

'10.3 Leakage Test

A suitable viscosity soap solution be applied with the help of a brush to all thejoints and fittings of extinguishers charged with extinguishing medium andpressurized at 12 kgf/cm2 It is to be visually observed for 10 minutes for anybubbling.' .

(eED 22)

Reprography Unit, BlS. New Delhi. India

Page 6: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second

AMENDMENT NO.2 NOVEMBER 2006TO

IS 6234: 2003 PORTABLE FIRE EXTINGIJISHERWATER TYPE (STORED PRESSURE)­

SPECIFICATION

( ..~econd Revision)

(Second cover, Foreword, para 3) - Insert the following new clause:

.. A scheme for labelling environment friendly products known as Era Mark hasbeen introduced at the instance of the Ministry of Environment and Forests(MEF), Government of India. The ECO Mark would be administered by theBureau of Indian Standards (BIS) under the B15;Act, 1986 as per the ResolutionsNo. 71 dated 21 February 1991 and No. 425 dated 28 October 1992 published inthe Gazette of the Government of India. For a product to be eligible for markingwith ECO logo. it shall also carry the lSI Mark of BIS besides meeting additionaloptional environment friendly requirements. For this purpose, the StandardMark of BIS would be a single mark being a combination of the lSI Mark andthe ECO logo. Requirements to be satisfied for a product to qualify for the HISStandard Mark for ECa friendliness being included in the relevant publishedIndian Standards through an amendment, These requirements arc optional;manufacturing units are free to opt for the lSI Mark alone also.

The Amendment is based on the Gazette Notification No. 160dated 1 April 1999for Fire Extinguishers as environment friendly products published in the Gazetteof the Government of India.'I

( Page 4, clause 11 ) - Insert the following new clauses after 1t andrenumber the subsequent clauses:

'12 ADDITIONAL REQUIREMENTS FOR ECO MARK

12.1 General Requirements

12.1.1 Any fire extinguisher having BIS Standard Mark qualifies forconsideration of ECO Mark.

12.1.2 The products manufacturer must produce the consent clearance as perprovisions of the Water (Prevention and Controi ofPollution) Act. 1974, the

Price Group j.

Page 7: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second

Amend No.2 to IS 6234 : 2003

Water (Prevention and Control of Pollutiom Cess Act, 1977 and the Air(Prevention 011(} Control of Pollutions Act, 1981 respectively, along withauthorization if required under the Environment (Protection) A(:I, 1986 and theRules framed thereunder to the Bureau of Indian Standards while applying forEC() Mark.

12.1.3 The products 111ay display in brief the criteria based on which the producthas been awarded ECa Mark.

12.1.4 The product may carry along with instructions for proper use so as tomaximize product performance with statutory warning. if any, minimize wasteand method of safe disposal.

12.1.5 TIle material used for product packaging (excluding refills) shall berecyclable, reusable or biodegradable.

12.1.6 The product must display a list of critical ingredients in descending orderof quantity present in percent by weight, The list of such critical ingredientsshall be identified by the Bureau of Indian Standards.

12.2 Specific Requirements

12.2.1 TIle fire extinguisher shall not contain any Ozone Depleting Substance(ODS) relevant to fire extinguishers industry as identified under the MontrealProtocol (see Annex C).

12.2.2 Gas based extinguishing media once discharged in the atmosphere shouldnot have atmospheric life time of more thana year (see Annex D).

]2.2.3 Chemical used shall not 113VC global warming potential (see Annex E).

12.2.4 TIle metallic body and other metal parts of the fire extinguishers shall befree of lead or lead alloys.

12.2.5 TIle coating used for the metallic part shall not be formulated withmercury and mercury compounds or be tinted with pigments of lead, cadmium,chromium VI and their oxides. Excluded are natural impurities entailed by theproduction process up to the amount 0.1 percent by weight which are containedin the raw material.

N()'fE - (:'()2 extinguishers may he permittedtill suitablesubstitutesarc available.

2

Page 8: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second

Amend No.2 to IS 6234 : 2003

ANNEXC(Clause 12.2.1)

LIST OF OWNE DEPLETING SUBSTANCES (ODS) CONTROLLEDBY MONTREAL PROTOCOL

...-------------.....--.----

-----,---

,------------------ --- -- ---

Page 9: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second

Amend No.2 to IS 6234 : 2003

ANNEXDtClause 12.2.2)

LI~T OF ATMOSHPERIC LIFE TIME OF GAS-BASED AGENTS

--- ---me Destgnatton Atmospheric Life T'"Je

--- -- (Year)on (CF31) < 1day---

HCFC (Blend A) 12-HCFC-125 36HCFC-124 6HFC·227 fa 250

----~....-... ...... ~....---..-..II~ .................... .......-

HFC-21 250---- --HFC·227 ea 41-------

) FC3-1-1() 260()-() 1 Halon 1101 65

--...-.....-...........--........-- _.--. - ...-.-....---............~---

IG 541 --- --- ----1055 ------.IG 01 -..--,,....,.,,,.................-..

trade Iva

Haloll J3NAFS III----FE 2~

FE 241FE 1(,----- -FE 11-----FM 2()O(EA 41(Halon 11

--....--. -...,---....-

lllergc!!-_~!8~lltC

Ar~~

4

Page 10: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second

Amend No.2 to IS 6234 : 2003

ANNEX E(Clause 12.2.3)

LIST OF SUBSTAN(~ES HAVING GLOBAL WARMING POTENTIAL(GWP)

lie Xnme ---=1 G~1) (lOOyearJ 1~C02.........................on 11() I 5600-- -~I].cn .~onJtc -_..- ~_~gEn ._.A ~IO 5 500

-~ ._--- --M 2()O 3 100..... ~

E Il 12 1oo- --- ---- -E 16 8000---------- --

E 2..J1 480-- .- --"E 25 3100F~ III 1450..._-~ .....~

"'F 11 e 5...... ___---------1-- - --

~._.-- -- .. -F

t----.................. --- -----

F- ---- .--I~

----------~

NA(

-~ .... -------'lrn--_.. _.......,.......---~{~I

In,--~

A--...------A- ------

CE

( CEO 22 )

Reprography Umt, BIS.New Deihl, Ind.a

Page 11: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second

AMENDMENT NO. 3 FEBRUARY 2010 TO

IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ―

SPECIFICATION

( Second Revision )

(Page 3, clause 9.1) ― Substitute the following for the existing: “Each extinguisher body except stainless steel body shall be painted either with epoxy powder coating or synthetic enamel paint. The shade shall be ‘Fire Red’ or ‘Post Office Red’ conforming to Shades No. 536 or 538 of IS 5. Stainless steel body shall be buffed.

NOTES

1 Whenever epoxy powder coating is applied on the external surface of mild steel body for anti-corrosive treatment, synthetic enamel paint coating is not required.

2 The body of extinguisher shall be of good finish, clear of all burrs and sharp edges.”

(CED 22)

Reprography Unit, BIS, New Delhi, India

Page 12: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second

I-Ife righting Sccnonal Cornrn ittce, CEI) 22

I ()Rl:,\V()Rf)

I Ills Indian Standard (Second Revision) was adopted by the Bureau of Indian Standards, after the draft finalizedb) the Fire I· IghtJng Sectional ('0111111 ittee had been approved by the Civil Engineering Division Council.

Portable fire extinguisher, water type is one of the type of the tire extinguisher used as first-aid fire fightingapplrancc. This typeofextinguisher IS suitable for fighting fires in Class A tires such as wood, textiles, paper, etc,I hl' details In regard to maintenance ofthis appliance in efficient conditions are given ill IS 2190 : 1991 'Code ofpractice for selection, installation and maintenance of first-aid fire extinguishers (second rcvisionv.

l-or the purpose of deciding whether a particular requirement of this standard is complied with, the final value,obvervcd or calculated, expressing the result of a test or analysis, shall be rounded off in accordance withIS ~ . 1960 .. Rules for rounding uff numcncal values irevtsed)', The number of Significant places retained in therounded off value should be the same as that of the <pccificd value in this standard.

Page 13: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second

IS 6234 : 2003

Indian Standard

PORTABLE FIRE EXTINGUISHER WA~rER TYPE(STORED PRESSURE) - SPECIFICATION

(Second Revision)

-+K~oo

7.1.2 For austenitic steel bodies, the minimum thicknessmeasured shall be greater than the minimum thicknesscalculated using the following forrnula:

7.1.1 The body shall have measured wall thicknessgreater than the minirnum thickness calculated usingthe following formula:

D

D

300s

where

where

S -=- minimum thickness, in mm;

D -- external diameter of the body, on the largestexternal normal to the longitudinal axis in rnrn:and

K =- the coefficient with a value of:

0.45 for n S 80 rnrn:0.50 for D "> 80 'TIm and $ 100 mm: and

0.70 forD .» IOu mm.

portion of minimum 10 mm length or three times theshell thickness, whichever is greater, The welding shallbe done by an electrical arc welding process Thereshall not be any longitudinal seam in the cylinder.

The thickness of the she ll shall be calculated inaccordance with 7.1.1. But it shall not be less than1.6 mm. The neck ring shall be welded", tth the bodyof the cylinder and shall be threaded to suit the type ofvalves thread. The threads shall be in accordance withClass A of IS 2643 (Part I).

The liquid capacity of the extinguisher when filled tothe specified level indicated in exterior of the bod)' shall

b90 +- 0 5 ).c . _ 0 0 Itres.

5 MATERIAL

I SCOPE

4 CAPAC-'ITY

The materials for the construction of various parts ofthe tire extinguisher shall be as given in 'Table I.

The standards listed at Annex A, contain provisions,which through reference in this text, constituteprovisions of this standard. At the time of publication,the editions indicated were valid. All standards arcsubject to revision, and parties to agreement based onthis standard are encouraged to investigate thepossibility of applying the most recent editions of thestandards given in Annex A.

2 REFERENCES

3 PRINCIPLE AND DESIGN

This standard lays down the requirements regardingprinciple, capacity" material, shape, design, construc­tion, anti-corrosive treatment and tests of portable,water type (stored pressure) fire extinguisher.

3.1 The method ofexpulsion ofwater is by air pressurestored in the container. The method of operation shallbe upright by one hand by pressing a trigger typesqueeze grip mechanism.

3.2 During the operation, the jet, where possible, shouldbe able to strike the burning surface and engu If fire.

6 SHAPE

The shape of the body shall be cylindrical with outsidediameter of 175 ± 5 mm. The size of the filler openingshall not be less than 20 mrn,

7 CONS1'RUCTION

S minimum thickness, in mm:

D - external diameter of the body, or the largestexternal measurement normal to the longitudinalaxis in mrn; and

K -= the coefficient, the value of v.hich is 0.30 forD ~ 100nun.'

7.1 The cylinder shall be ofwelded construction havingcold or hot drawn cylindrical portion withhemispherical, ellipsoidal or torispherical ends weldedto it or two halves cold or hot drawn and circumstantialwelded together. The end or dished part shall be havinghem i-spherical, semi-ellipsoidal or torispherical shapeand the end shall have cylindrical skirt or parallel

This is subject to an absolute minimum thickness of0.64 mm, including..all tolerances.

7.1.3 Thetop and bottom ofwater type (stored pressure)tire extinguisher shall have a thickness after formingequal to or greater than the minimum wall thickness ofthe cyl indcr un less the dome or bottom is formed

Page 14: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second

IS 6234 : 2003

Table I Materials of Construction of Various Parts of Fire Extinguishers

(C'lau.\e 5)

~I 'n. ( umpunent

(t) (2)

I) Bod)

II} Neck ring

III) Valve body

Washcrv and 0 range;

~laterial~

a) Mlid steel sheet

h) Stamless steel xheet

Mild steel

a) Stainless steel

h) Forged brass

c) Leaded bronze

d) Pla~lll.

Rubber

Relevant IS No.

(4)

I~ .;11

IS 6911

IS 2062

IS 1875

IS 6911

Grade FLD of IS 6912

Grade I I B-2 of IS 318

Cuntormmg to requirements givenIII Anncv B

Requirements In respect of hardness asapplicable to I ype 3 of IS 5382 and alsoacid/alkah resistant (st!e Note)

v)

\ II)

\111)

Spindle

\prll'~

~l) Br,t~~

b) ~t(t1nlc~, "led

,t) hr.l'>',

h) t upper

L) PI"...,1Il.

h) Bra~,

Grade 2 of 1\ 24 I or I ypc I of I~ 319

I~ 0528

Grade 1 of I'; 4454 (Part 1)

Alloy No 2 of I~ 407

l~ 1~4)

( uulornung to requirements given 111

I\nne\ Ii

Contornung to requirements glvcn IIIAnnex B

(nude 2 ot IS 2YJ or I >p~' 101 IS 319

I~ 14933

N\)' I When d piece 01 2 5 em cut Irorn ~m~ portion ,... dipped in 20 percent sulphuric acrd 5 percent sodrum hydroxidevulutrun tor 10 nun. there ...hall be no sign of corrosion or d.un.rue

integral wuh the cylinder In the case of integral 00111<:

and bottom, the thickness of the cylinder shall not be1110n: thJI1 15 percent than that of the dome or bottom.

7.2 (;:l~ Space

7.2.1 A gus space shall be provided above the waterlevel 111 the body of the extinguisher.. which shall be ofsuft u.rent \ olume to ensure that when subjected tooperation, it meets the requirements ofper formance test(l~ given In 10.5

7.3 Neck Ring

7.3.1 The neck ring shall be suitably threaded eitherexternally or Internally in accordance with Class A ofIS 2643 (Parts 1 and 2) or IS 4218 (Part 3). It shallhave the filler opening size as specified in 6. Thethreaded length shall not be less than 16 mm.

7.4 Valve

7.4.1 '"I he screw thread of the valve shall be in

2

accordance with (~Ia~s A of IS 2643 (Part 1) or IS 4218(Part 3) for a nunimum length of 16 111111 to suit thethread of the neck ring

7.4.2 The squeeze grip valve assembly with a springloaded pressurescaled sliding spindle shall be providedIn such a way that it is operated by manual depressionby means ofa cantileverpivotedgnp level. '[he spindleshall be so designed that the operation of theextinguisher can be regulated by means of depressingand releasing the extinguisher squeeze grip handle. Asafety pin/seal shall be provided to prevent inadvertentoperation by accident.

7.5 Discharge Fittings

7.5.1 Hoseand Nozzle

The discharge hose shall bescrewed to the valve body.The design of the nozzle and its orifice shall be suchthat it meets the performance requirements as givenin 10.5. The discharge hose shall be 0.6 m length.

Page 15: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second

7.5.2 Pressure Gauge

A suitable pressure gauge shall be fitted to valveassembly or to the cylinder to indicate the pressureinside the cy linder. The gauge dial shall indicate theoperating pressure range of the extinguisher preferablywith the colour code. The zero charging and maximumindicated pressure shall be shown in numerable andmarked to ensure the correct charging of pressure of10 kgf/cm'.

7.5.3,C,)Jphon Tube

The syphon tube shall be fitted with the discharge valveassembly by means of a press tit type, soldering brazingor suitable threads in accordance with IS 2643 (Part 2).The syphon tube shall not be completely disengagedduring use, syphon tube shall be notched or otherwiseprevented from restricting the discharge in anunintended manner,

8 AN'fl-('ORROSIVE TREArrMENT

8.1 All mternal and external surface of the body shallbe completely epoxy powder coated to a minimumo050 mm thickness. The thickness of the coating shallbe measured as given in IS 3203. The internal surfaceof the body shall have plastic/rubber lining of aminimum thickness of 0.5 mrn as an alternative topowder coating.

8.2 Test for Phlstic Lining

a) Test [or Adhesion of Plustu: l.inmg (TypeTest) - Subject the unfilled extinguisher to apressure 15 kgf/cm 2 and store for 120 .:) h at271-5 tll'.

Release the pressure and ex am inc theextinguisher internally for cracking, separationfrom the wall of the body or lrfting of thehning, and bubbles between the lining and thehody

b) Test [or Conunuuv of Plustic LUling Fi IIthe extinguisher body up to I() mm of the topof the lining with a I percent m/m solution ofNaCI in water containing sufficienthydrocarbonsurfactant to reduce the surface tension ofthe solution to less than 40 MN/nl. Check thelining for continuity by the application of a500 1. 50 M insulation resistance test acrossthe lining through connections made to themetal body and to an electrode introducedinto the solution in the extinguisher body.

8.3 Phosphating in accordance with the provisions ofIS 3618 may be applied on the external surface of thebody as an alternate.

9 PAINTING

9.1 Each extinguisher shall be painted with fire red

3

IS 6234 : 2003

colour conforming to shade No. 536 of IS 5. The paintshall conform to IS 2932.

9.2 A picture showing operation of the extinguisher rnthe correct manner shall be shown on the body/label ofthe extinguisher.

9.3 The extinguisher shall be With Jetter ~ A' Indicatingthe suitability for respective class of fire as laid downin IS 2190. The letter A shall be 2 5 ± 0.5 ern height,painted in black colour centrally inside an equilateraltriangle of side 5.0 j 0.5 em minimum. The triangleshall be coloured golden yellow.

10 TEST REQUIREMENTS

10.1 Ilydrostatic Pressure Test

The extinguisher body and valve asscrnbly ~hall becapable of withstanding the internal hydraulic pressureof 3.0 MN/n12 (30 kgf/cm? ) without rupture, leakageor visible distortion for a period of 2 min. This testshall be carried out before the extinguishers are coatedfor anti-corrosive treatment and painting.

10.2 In case of ultimate failures test, the mechanicalfailure shall not occur at the pressure of less than4.5 MNI rn2 (45 kgf/ crn ').

10.3 Leakage 'fest

The extinguisher's valve assembly after being coveredby inverted glass-transparent-jar shall be dipped insuitahle water tank filled with water, to the level morethan the height of extinguisher for 24 h there shall notbe any collection of even a single bubble on the insidetop of the inverted glass jar after a lapse of 24 h. Theair bubble collected on the inside top of glass jar duringthe initial 6 h shall be neglected.

10.3.. 1 Retention oj Pressure

Ihe extinguisher shall be discharged for 2 s and thepressure drop shall be noted. Aftcr an interval of15min the pressure shall be noted again and there shallnot be variation of more than 5 percent in the pressuredrop. This test shall be conducted twice on extinguisherand mean reading shall be taken of the pressure dropswhich shall not be more than 5 percent. After 2 eye Icsof discharge, the extinguisher shell should be kept for24 h and drop in pressure shall not be 1110rc than5 percent to pass this test. The tire extinguisher shallbe capable of functioning on ON-()FF basis.

10..4 Drop Test (Resistance to Shock a nd MechanicalDamage)

This test shall be conducted at a temperature of27 1: 5°C. The extinguishers shall be filled with waterto 90 percent of its volume and pressurized to its ratedpressure. The extinguisher with its fitting shall bedropped from a height of 3 In on a concrete surface,first with cylinder axis with cylindrical axis vertical with

Page 16: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second

IS 6234 : 2003

Its head up There shall be no leakage from the bodyThe leakage shall be observed by Immersing theextinguisher In the water

Drop test shall be type test

10.5 Performance Test

When the extinguisher IS set In operation under normaltemperature conditions of 27 ± 5 °C with a streamstarting In honzontal direction In wind-free condition,the water shall be expelled In the form of a Jet whichshall maintain an effective throw ot not less than 6 mtor the mmrmurn penod uf 45 \ provided that dt least9'; percent of water IS discharged from the extinguisherwithin the maximum period of 120 s

JJ WORKMANSIIIP AND FINI~.I

All the components of the extinguisher shall have\0100th finish and shall be free trom burrs, sharp andJagged edges and other visual defects that may bemjunous or detnrnental m any manner to the users

4

12 MARKING

12.1 Each extinguisher shall be clearly andpermanently marked with the following mformanon

a) Name of the manufacture or trade-mark, if any,

b) Method of operation In prominent letters,

c) fhe words water type (Stored pressure),

d) The capacity of the extinguisher In lures,

e) Ihe words 'Recharge after use',

f) A declaration to the effect that the body of theextinguisher has been tested to a pressure of30 kgt/cm',

g) The .(yords 'Keep this end up' while using,

h) Letter Indicating the suitabihty of the unit forclass of fires. and

J) Year of manufacture and 51 No of theextingursher

Page 17: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second

IS 6234 : 2003

ANNEXA

(( 'lause 2)

LIST OF REFERRED INDIAN STANDARDS

IS No Tille IS No Tille

High pressure fire fighting hoseSpecification

Spec ification for stet: 1 w ires formechanical springs: Part 1 Patentedand cold drawn steel wires­lJnalloyed (second revision)

Specification for rubber 'Scalingrings for gas mams, water mains andsewers (firs! revision)

Methods for dcterrn ination ofInciting point and melting range

Stainless steel wire (first revtsiom

Stainless steel plate, sheet and strip(first revts Ion)

Spee i fi cat ion fo r ph 0 sphat etreatment o f i ron and stcc I forprotection against corrosion

ISO general purpose rnetnc screwthreads : Part 3 Basic dimensionstfirst revisions

Methods of testing local th ickncssof e IeCt r0 p Iated co a t 111 gs (IIrs I

revision)

14933 : 2001

7188: 1974 Methods of test for cellulose acetateflakes

8543 Methods of testing plastics: Part 1(Part l/Sec 2). Characterization of pol) mer1979 structure and SIze, Section 2

Determination of density of solidplastics

t--l54 (Pari I) .1981

6911 : 1992

3618 : 1966

5382 : 1985

5762 : 1970

6528 : 1995

42 I8 (Part 3) .1976

3203 : )982Colours for ready mixed paintsand enamels (fourth revision)

Naval brass rods and sections formachining purposes (third reVISIOII)

Specification for leaded tin bronzeingots and castings tsecond re\'ISIO!1)

Free cutting brass bars .. rods andsections Specifrcation ifourthrcvts1011)

Specification for brass tubes forgeneral purposes itlun! revision)

Cold rolled low carbon steel sheetsand strips (fourth revisions

Solid drawn copper and copper alloyt 1IbC's 1'0 r con den serand he atexchangers (thll-J revtstonv

Carbon steel billets, blooms. slabsand bars for forgings (f?fth revision)

Steel for general structural purposes(fifth revisions

Selection, installation andmaintenance of f irst-ard fireextinguishers -- Code of practicetsecond revision)

Dimensions for pipe threads forfastening purposes:

Basic profile and dimensions (firstrevision)

Tolerances (first revision)

Enarncl, synthetic, exterior(a) undercoating, (b) finishing -­Specification (second revtston)

(Part 1) : 1Q7 5

)875 : 1992

(Part 2) : 1975

2932 : 1993

154) : 1994

2643

2190 : 1992

2062 : 1992

5) 3 : 199--1

407 : 1981

319 : 1989

318 : 1981

5 : 1994

191 : 1989

5

Page 18: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second

IS b234 : 2003

ANNEXO

(Table 1)

REQUIREMENTS FOR PLASTIC NOZZLE AND VALVE BODY

B-2 BURST PRESSURE TEST

B-1 PHYSICAL TESTS

8-3.3 Alkali Resistance Test

The sample shall then be submerged in 10 percent

B-2.1 If the sample passes the requirement mentionedin 8-1,. the following burst pressure test shall be doneon the second sample.

8-2.2 The sample of cap shall be subject to internalhydraulic pressure of 5 MN/m2 (50 kgf/cm") afterblocking the plunger hole (if any). The pressure shallbe built up gradually over a period of 30 sandmaintained for) min. There shall be no mechanicalfailure of cap and cap threads.

8-3.5 UV Exposure Test

The sample shall then be exposed at 27 ± 3 °C toxenon are ultra violet radiations for 100 minfollowed by exposure at a relative humidity of 60 i 5percent and temperature 62 i: 5 °C for 20 min.The cycle shall be repeated 60 times and the capshall then be subjected to internal hydrostaticpressure mentioned in 8-3.4 and shall pass therequirement.

sodium bicarbonate solution for 72 h at a temperatureof 27 ± 3 °C and then shall be removed, rinsed withpotable water and dried. The sample shall not showany sign of discolouration, distortion or deteriorationof any kind.

8-3.4 The sample shall then be screwed and unscrewedinto neck ring of the fire extinguisher for 100 times(each operation). The samples shall not show any signof damage or distortion of threads. The sample shallthen be first tested for internal hydrostatic pressure of4.5 MNlrn2 (45 kgf/cm') after blocking the plunger hole(ifany). The pressure shall be built up over a period of30 s and maintained for 1 min. There shall not be anysign of leakage. It shall be then kept suspended in anoven maintaining the temperature of60 ± 1 °C for 72 hand after removing, when it attains ternperature of27 ± 3°C, it shall be kept in refrigerator at a temperatureof - 5 ± 3 °C for 72 h. After this period, the sampleshall be removed and when it attains the temperatureof27 ± 3 °C and at this stage. it does not show any signof discolouration, distortion and deterioration of anykind, it shall be subject to internal hydrostatic pressuretest as mentioned above and there shall not be any signof leakage. This cycle of test (that is, keeping in oventhen in refrigerator and subjecting to hydrostaticpressure) shall be further repeated 2 times with a gapof 24 h and the sample shall be observed and shallnot show any sign of discolouration, distortion ordeterioration besides passing the hydrostaticpressure test.

15 t 1 percent

1.25 ± 0.02

215 to 225 -c

Requirements

ii) Melting point

iii) Ash content

From a sample of cap, requirements of followingproperties shall be checked:

Sl Property Method ofNo. Test, Refto

IS

i) Specific gravity IS 8543(Part I/Sec2)

IS 5762

IS 7188

8-3 AGEING TEST

B-3. J If the sample passes the requirement mentionedin B-2.1and 8-2.2, the following tests shall be done onthe third sample in the order as indicated below, andthe sample shall pass all the tests.

8-3.2 Acid Resistant Test

The sample shall be submerged in 10 percent dilutehydrochloric acid for 72 h at the temperature of271- 3 "C. It shall then be removed, rinsed with potablewater and dried. 'The sample shall not show any signof discolouration, distortion or deteriorationof any kind.

6

Page 19: IS 6234 (2003): Portable Fire Extinguishers Water …AMENDMENT NO. 3 FEBRUARY 2010 TO IS 6234 : 2003 PORTABLE FIRE EXTINGUISHER, WATER TYPE (STORED PRESSURE) ― SPECIFICATION ( Second

Bureau of Indian Standards

HIS is a statutory institution established under the Bureau of InlJU.l1I Standards Act, 1986 to promote harmoniousdevelopment of the activities of standardization, marking and quality certificatiun of goods and attending toconnected matters in the country.

Copyright

131S has the copyright of all its publications. No part of these publications may be reproduced in any fonnwithout the prior permission in writing of HIS. This does not preclude the free use, in the course of implementingthe standard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating tocopyright be addressed to the Director (Publication), BIS.

Review of Indian Standards

Amendments are issued to standards as the need arises on the basis of comments, Standards are also reviewedperiodically: a standard along with amendments is reaffirmed when such rev-ew indicates that no changes arcneeded: if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standardsshou III ascertain that they are in possession of the latest amendments or edition by referring to the latest issue of'HIS Catalogue.' and 'Standards: Monthly Additions'.

This Indian Standard has been developed from Doc: No. ('FI) ~2 (6003)

Amendments Issued Since Publication

Amend No Date of Issue

BUREAU OF INDIAN srrAN[)AkDS

Text Affected

Southern : ('.I,'r. Campus, IV Crosv Road, ('IIENNAI6001IJ

l leudquarters:

Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002Telephones 2J~3 0131, 2323 3375, 2323 9402

Regional Offices:

Central Manak Bhavan, 9 Bahadur Shah Zafar MargNbW I)ELIII 110002

Eastern 1/14 C i.r. Scheme VII ~1, V.J.P. Road, KankurgachiK()LKATA 700054

Northern : S('() 335-336, Sector J4-A, (~IIANr)ICjARII 160022

Brunches

Telegrams: ManaksansthatCommon to all offices)

Telephone

{2J2376172323 3841

{2337 8499,233785612J37 8626, 23379120

{60 3843609285

{2254 1216,2254 14422254 2519, 2254 2315

Manakalaya, (:9 MIDC', ~1arol, Andheri (East) {2832 9295, 2832 7858MllMI3A14000lJ) 2832 7891, 2832 7892

: AI1MELlI\BAf). UAN(iAL()RE IJIIOPAL. BlllIBANESI1WAR. ('()IMBA'f()RE, FARJI)ABAfl.(jJIAZIABAIJ. GLJWAl1ATI. ~IYl)ERAHAD, JAIPIJR, KANPIJR. LlJCKN()W. NAl,PlJR.NALAGARI-I. PA'fNA. PlJNE. RAJK{)T. l'I-IIRlJVANANTIIAPlJRArvl. VISAKllAPA'rNAM.

Printed at Simco Printing Press, Delhi