jerzy zemajtis [email protected] big 5

64
Big 5 Conference, July 27, 2020 Jerzy Zemajtis [email protected]

Upload: others

Post on 17-Nov-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

Big 5 Conference, July 27, 2020

Jerzy [email protected]

Page 2: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

Jerzy Zemajtis, PhD, PE Senior Engineer, ACI

Jerzy Zemajtis, PhD, PE, is a Senior Engineer at ACI. His role at ACI is to provide technical and administrative support to ACI's Technical Committees. He received his BS and MS in civil engineering from the Technical University of Gdansk, Poland, and his PhD in civil engineering from Virginia Tech.

Mr Zemajtis worked as a Structural Engineer in Virginia Beach, VA, and Vancouver, Canada, and as a Civil/Materials Engineer at Construction Technology Laboratories in Chicago, IL, before joining the ACI Engineering Department in 2010. He is a licensed engineer in Washington and British Columbia.

Concrete Cracking

Page 3: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

Reference Documents

3

Page 4: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

Learning Objectives

1. Understand what strength test is and is not2. Learn proper methods of sampling, fabrication,

handling and curing strength test specimens3. Understand acceptance criteria for strength

tests4. Learn how to interpret strength tests not

meeting acceptance requirements and how to investigate non-compliant concrete

5. Learn how to address low strength concrete issues in production

4

Page 5: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

Presentation Outline

1. What is a strength test and why it’s needed?2. How often must strength tests be conducted?3. What are acceptance criteria for strength tests?4. How to investigate strength tests not meeting acceptance

requirements?5. Strength is still low – now what?6. Who pays for testing?7. How can concrete producer avoid low strengths?8. Additional resources

5

Page 6: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?

specified concrete compressive strength — the specified resistance of a concrete specimen to axial compressive loading used in design calculations and as the basis for acceptance of concrete used in the work.

specified concrete compressive strength

specified strength

strength compressive strength

6

Page 7: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?

ACI 318-19: 26.12.1(a) “Evaluation of hardened concrete shall be based on strength tests.”

7

Page 8: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?

ACI 318: 26.12.1• “A strength test is the average of the

compressive strengths of at least two 150 x 300 mm cylinders or at least three 100 x 200 mm cylinders made from the same sample of concrete taken in accordance with ASTM C172 at the point of delivery, handled and standard-cured in accordance with ASTM C31, and tested in accordance with ASTM C39 at 28 days or at test age designated for fc′.”

8

Page 9: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?

ACI 318: 26.12.1• “A strength test is the average of the

compressive strengths of at least two 150 x 300 mm cylinders or at least three 100 x 200 mm cylinders made from the same sample of concrete taken in accordance with ASTM C172 at the point of delivery, handled and standard-cured in accordance with ASTM C31, and tested in accordance with ASTM C39 at 28 days or at test age designated for fc′.”

9

Page 10: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?

ACI 318: 26.12.1• “A strength test is the average of the

compressive strengths of at least two 150 x 300 mm cylinders or at least three 100 x 200 mm cylinders made from the same sample of concrete taken in accordance with ASTM C172 at the point of delivery, handled and standard-cured in accordance with ASTM C31, and tested in accordance with ASTM C39 at 28 days or at test age designated for fc′.”

10

Page 11: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?a. What is NOT a strength test?

ACI 318-19, R26.12.1What is NOT a strength test?• Tests on cylinders field cured • Tests on cylinders from laboratory trial batches

11

Page 12: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?b. How to sample concrete?

ACI 318: 26.12.1• “…sample of concrete taken in accordance with

ASTM C172 at the point of delivery…” Make composite sample

• Minimum volume• Number of portions• Portion of the batch

Stationary MixersPaving MixersRevolving Drum Truck Mixers or AgitatorsContinuous MixersOpen-Top Truck Mixers, Agitators, Nonagitating Equipment, or Other Types of Open-Top Containers

12

Page 13: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?b. How to sample concrete? – Composite sample

13

Page 14: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?c. How to make specimens for testing?

ACI 318: 26.12.1• …handled and standard-cured in accordance

with ASTM C31…Testing Requirements

- Cylinder SizeSampling Concrete

- ASTM C 172Molding Specimens

- Casting Cylinders- Consolidation

Initial and Final CuringTransportation to Laboratory

composite sample

14

Page 15: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?c. How to make specimens for testing?

ASTM C31, Standard Practice for Making and Curing Concrete Test Specimens in the Field• D ≥ 3 x NMAS

D = cylinder diameterNMAS = nominal maximum aggregate size

• Wet sieve through a 50 mm sieve when NMAS > 50 mm

Cylinder size (mm) Nominal maximum aggregate size (mm)100x200 or 150x300 25.0

150x300 only 37.5

15

Page 16: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?c. How to make specimens for testing?

ASTM C31, Standard Practice for Making and Curing Concrete Test Specimens in the Field

16

Slump, mm Consolidation < 25 Vibration ≥ 25 Vibration or rodding

Consolidation by Vibration

Consolidation by Rodding

Cylinder size, mm

No. of layers

No. of vibrator insertions/ layer

No. of layers

Rod diameter, mm

No. of roddingsper layer

100x200 2 1 2 10 25150x300 2 2 3 16 25

Page 17: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?c. How to make specimens for testing?

ASTM C31, Standard Practice for Making and Curing Concrete Test Specimens in the Field

Consolidation by Vibration

Consolidation by Rodding

Cylinder size, mm

No. of layers

No. of vibrator insertions/ layer

No. of layers

Rod diameter, mm

No. of roddingsper layer

100x200 2 1 2 10 25150x300 2 2 3 16 25

Slump, mm Consolidation < 25 Vibration ≥ 25 Vibration or rodding

17

Page 18: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?c. How to make specimens for testing?

ASTM C31, Standard Practice for Making and Curing Concrete Test Specimens in the Field

Activity Timing fc’ Temp. Moisture

Initial Curing

Up to 48 h after molding

< 40 MPa 16 – 27°C Store in an environment that

controls the loss of moisture

≥ 40 MPa 20 – 26°C

18

Page 19: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?c. How to make specimens for testing?

ASTM C31, Standard Practice for Making and Curing Concrete Test Specimens in the Field

Activity Timing fc’ Temp. Moisture

Initial Curing

Up to 48 h after molding

< 40 MPa 16 – 27°C Store in an environment that

controls the loss of moisture

≥ 40 MPa 20 – 26°C

Transp. ≥ 8 h after final set;Transp. time ≤ 4 h All Protect from

freezingWrap in plastic, wet

burlap; caps on molds

19

Page 20: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?c. How to make specimens for testing?

ASTM C31, Standard Practice for Making and Curing Concrete Test Specimens in the Field

Activity Timing fc’ Temp. Moisture

Initial Curing

Up to 48 h after molding

< 40 MPa 16 – 27°C Store in an environment that

controls the loss of moisture

≥ 40 MPa 20 – 26°C

Transp. ≥ 8 h after final set;Transp. time ≤ 4 h All Protect from

freezingWrap in plastic, wet

burlap; caps on moldsFinal

Curing Until testing All 21 – 25°C Keep in water storage tanks or moist rooms

20

Page 21: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?c. How to make specimens for testing?

ASTM C31, Standard Practice for Making and Curing Concrete Test Specimens in the Field

Activity Timing fc’ Temp. Moisture

Initial Curing

Up to 48 h after molding

< 40 MPa 16 – 27°C Store in an environment that

controls the loss of moisture

≥ 40 MPa 20 – 26°C

Transp. ≥ 8 h after final set;Transp. time ≤ 4 h All Protect from

freezingWrap in plastic, wet

burlap; caps on moldsFinal

Curing Until testing All 21 – 25°C Keep in water storage tanks or moist rooms

Test prep. ≤ 3 h prior to test All Ambient

20 – 30°CMaintain free moisture

on cylinders

21

Page 22: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?d. Factors affect strength?

• Smaller size cylinders yield higher strengths100x200 mm cylinder strengths = ~4% higher

than 150x300 mm• Moist curing results in

higher long-term strength

Sources: • Price, W. H., “Factors Influencing Concrete Strength,” ACI Journal

Proceedings, Vol. 47, American Concrete Institute, 1951, pp. 417–432.• Kosmatka, Steven H.; Kerkhoff, Beatrix; and Panarese, William C.;

Design and Control of Concrete Mixtures, EB001, 14th edition, Portland Cement Association, Skokie, Illinois, USA, 2003

22

Page 23: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?d. Factors affect strength?

• Smaller size cylinders yield higher strengths100x200 mm cylinder strengths = ~4% higher

than 150x300 mm• Moist curing results in

higher long-term strength• Lower temperature results in

higher long-term strengthSources: • Price, W. H., “Factors Influencing Concrete Strength,” ACI Journal

Proceedings, Vol. 47, American Concrete Institute, 1951, pp. 417–432.• Kosmatka, Steven H.; Kerkhoff, Beatrix; and Panarese, William C.;

Design and Control of Concrete Mixtures, EB001, 14th edition, Portland Cement Association, Skokie, Illinois, USA, 2003

23

Page 24: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?f. Who can conduct the tests?

ACI 318: 26.12.1

Activity ACI 318 Requirement

Acceptance testing Testing agency compliant with ASTM C1077

Specimen preparation (for strength tests) Certified field testing technicians

Laboratory testing Certified laboratory technicians

24

Page 25: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?f. Who can conduct the tests?

https://www.concrete.org/certification/https://www.concrete.org/education/aciuniversity

25

Page 26: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

1. What is a strength test and why it’s needed?g. Example

• ASTM C39 (100x200 cyl.)Cylinder 1: 29.5 MPaCylinder 2: 30.1 MPaCylinder 3: 30.4 MPa

Average: 30 MPa

Compressive (Cylinder) StrengthsStrength Test

26

Page 27: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

Strength Test

1. What is a strength test and why it’s needed?g. Example

• ASTM C39 (100x200 cyl.) (150x300 cyl.)Cylinder 1: 29.5 MPa 29.4 MPaCylinder 2: 30.1 MPa 26.6 MPaCylinder 3: 30.4 MPa

Average: 30 MPa 28 MPaStrength Test

27

Compressive (Cylinder) Strengths

Page 28: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

2. How often must strength tests be conducted?

ACI 318-19, 26.12.2.1 (a)

Strength-test specimens must be made for each concrete mixture at least:• Once a day• Once for each 110 m3 of concrete• Once for each 460 m2 of slabs or

walls (governs when thickness is less than 240 mm)

28

Page 29: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

2. How often must strength tests be conducted?

ACI 318-19, 26.12.2.1 (b)

Minimum of five strength tests must be made for each concrete mixture• From 5 randomly selected

batches• From each batch if fewer than 5

batches are used

29

Page 30: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

2. How often must strength tests be conducted?

ACI 318-19, 26.12.2.1 (c)

Strength-tests NOT required:• Total quantity < 38 m3

• Evidence of satisfactory strength • Approved by building official

30

Page 31: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

3. What are acceptance criteria for strength tests?

ACI 318-19, 26.12.3.1 (a)

Acceptable strength level:• Each strength test:

• ≥ fc′ - 3.5 MPa (fc′ ≤ 35 MPa)• ≥ 0.9 fc′ (fc′ > 35 MPa)

• Average of any 3 consecutive strength tests ≥ fc′

(ACI 301-16, 1.6.6)

31

Page 32: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

3. What are accept. criteria for strength tests? a. Example

• Placement requiring 80 m3 of concrete with fc′ = 28 MPa. Use 10 ready-mix trucks (batches) 8 m3 each.

• Random sampling – trucks 2, 3, 5, 7, 10• Concrete strength tests (average of 3 100x200 mm cyls):

Truck 2: 27.2 MPaTruck 3: 23.9 MPaTruck 5: 28.6 MPaTruck 7: 28.5 MPaTruck 10: 29.0 MPa

Average of 3 consec. tests

26.6 MPa27.0 MPa28.7 MPa

32

Page 33: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

3. What are accept. criteria for strength tests? a. Example

Truck 2: 27.2 MPa Average of 3Truck 3: 23.9 MPa consec. testsTruck 5: 28.6 MPa 26.6 MPaTruck 7: 28.5 MPa 27.0 MPaTruck 10: 29.0 MPa 28.7 MPa

33

Page 34: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

3. What are accept. criteria for strength tests? a. Example

Truck 2: 27.2 MPa Average of 3Truck 3: 23.9 MPa consec. testsTruck 5: 28.6 MPa 26.6 MPaTruck 7: 28.5 MPa 27.0 MPaTruck 10: 29.0 MPa 28.7 MPa

ACI 318-19, 26.12.3.1 (a) (and 301-16, 1.6.6)•Each strength test:

• ≥ fc′ - 3.5 Mpa (fc′ ≤ 35 MPa)• ≥ 0.9 fc′ (fc′ > 35 MPa)

•Average of any 3 consecutive strength tests ≥ fc′ 28 MPa

24.5 MPa

34

fc′ = 28 MPa

Page 35: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

3. What are accept. criteria for strength tests? a. Example

ACI E702.3Example problem with

strength tests from 15 batches of concrete

Acceptance criteriaRecommendations for

further actionsAdditional reading list

35

Page 36: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

3. What are accept. criteria for strength tests? a. Example

Truck 2: 27.2 MPa Average of 3Truck 3: 23.9 MPa consec. testsTruck 5: 28.6 MPa 26.6 MPaTruck 7: 28.5 MPa 27.0 MPaTruck 10: 29.0 MPa 28.7 MPa

ACI 318-19, 26.12.3.1 (a) (and 301-16, 1.6.6)•Each strength test:

• ≥ fc′ - 3.5 Mpa (fc′ ≤ 35 MPa)• ≥ 0.9 fc′ (fc′ > 35 MPa)

•Average of any 3 consecutive strength tests ≥ fc′ 28 MPa

24.5 MPa

36

Page 37: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

3. What are accept. criteria for strength tests? b. What steps are needed (by concrete supplier) if acceptance criteria are not met?

Requirement Required Action(s) (ACI 318-19, 26.12.3.1 b)

Each strength test:• ≥ fc′ - 3.5 MPa

(fc′ ≤ 35 MPa)• ≥ 0.9 fc′

(fc′ > 35 MPa)

• Steps shall be taken to increase subsequent strength tests

Average of any 3 consecutive strength tests ≥ fc′

• Steps shall be taken to increase subsequent strength tests

• Increase “cm” content;• Reduce water content;• Use water-reducing

admixture to improve dispersion of “cm”

• Make other changes in mixture proportions;

• Reduce delivery time;• Make closer control of air

content; • Reduce conc. temperature• Improve quality of testing,

incl. strict compliance with ASTM C172, C31, & C39.

37

Page 38: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

3. What are accept. criteria for strength tests? b. What steps are needed (by concrete supplier) if acceptance criteria are not met?

38

Page 39: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

3. What are accept. criteria for strength tests? b. What steps are needed (by concrete supplier) if acceptance criteria are not met?

ACI 211.8R

39

Page 40: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

3. What are accept. criteria for strength tests? b. What steps are needed (by concrete supplier) if acceptance criteria are not met?

Requirement Required Action(s) (ACI 318-19, 26.12.3.1 b)

Each strength test:• ≥ fc′ - 3.5 MPa

(fc′ ≤ 35 MPa)• ≥ 0.9 fc′

(fc′ > 35 MPa)

• Steps shall be taken to increase subsequent strength tests

Average of any 3 consecutive strength tests ≥ fc′

• Steps shall be taken to increase subsequent strength tests

40

Page 41: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

4. How to investigate strength tests not meeting acceptance requirements?

Requirement Required Action(s) (ACI 318-19, 26.12.3.1 b)

Each strength test:• ≥ fc′ - 3.5 MPa

(fc′ ≤ 35 MPa)• ≥ 0.9 fc′

(fc′ > 35 MPa)

• Steps shall be taken to increase subsequent strength tests

• Investigate strength tests 26.12.6

Average of any 3 consecutive strength tests ≥ fc′

• Steps shall be taken to increase subsequent strength tests

…applicable only for evaluation of in-place strength at the time of construction.

41

Page 42: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

4. How to investigate strength tests not meeting acceptance requirements?

• ACI 318-19, 26.12.6.1

“(a) If any strength test of standard-cured cylinders falls below fc′ by more than the limit allowed for acceptance, or if tests of field-cured cylinders indicate deficiencies in protection and curing, steps shall be taken to ensure that structural adequacy of the structure is not jeopardized.”

42

Page 43: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

4. How to investigate strength tests not meeting….?a. What is the “limit allowed for acceptance”?

• ACI 318-19, 26.12.6.1

“(a) If any strength test of standard-cured cylinders falls below fc′ by more than the limit allowed for acceptance, or if tests of field-cured cylinders indicate deficiencies in protection and curing, steps shall be taken to ensure that structural adequacy of the structure is not jeopardized.”

From acceptance criteria:• fc′ ≤ 35 MPa

LAFA = fc′ - 3.5 MPa• fc′ > 35 MPa

LAFA = 0.9 fc′

43

Page 44: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

4. How to investigate strength tests not meeting….?b. What are field cured cylinders needed for?

• ACI 318-19, 26.12.6.1

(a) If any strength test of standard-cured cylinders falls below fc′ by more than the limit allowed for acceptance, or if tests of field-cured cylinders indicate deficiencies in protection and curing, steps shall be taken to ensure that structural adequacy of the structure is not jeopardized.

318-19, 26.5.6.3.2• 3-100x200 mm or

2-150x300 mm cylinders field cured

• If req’d by building official or LDP

44

Page 45: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

4. How to investigate strength tests not meeting….?c. What is needed to ensure structural adequacy?

• ACI 318-19, 26.12.6.1

(a) If any strength test of standard-cured cylinders falls below fc′ by more than the limit allowed for acceptance, or if tests of field-cured cylinders indicate deficiencies in protection and curing, steps shall be taken to ensure that structural adequacy of the structure is not jeopardized.

• Structural analysis• Field cured cylinders• In-place tests

(see ACI 228.1R, Report on Methods for Estimating In-Place Concrete Strength)

45

Page 46: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

4. How to investigate strength tests not meeting….?d. How to estimate in-place strength?

ACI 228.1R:Rebound number (ASTM C805)Penetration resistance (ASTM C803)Pullout test (ASTM C900)Pull-off test (ASTM C1583)Ultrasonic pulse velocity (ASTM C597)Maturity method (ASTM C1074)Cast-in-place cylinders (ASTM C873)Combined methods

“In all cases, sufficient correlation data are required, and permission may have to be granted before using in-place test methods.”

In ACI 318-19 Commentary and in ACI 301-16

46

Page 47: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

4. How to investigate strength tests not meeting acceptance requirements?

• ACI 318-19, 26.12.6.1

(a) If any strength test of standard-cured cylinders falls below fc′ by more than the limit allowed for acceptance, or if tests of field-cured cylinders indicate deficiencies in protection and curing, steps shall be taken to ensure that structural adequacy of the structure is not jeopardized.

• Structural analysis• Field cured cylinders• In-place tests

(see ACI 228.1R, Report on Methods for Estimating In-Place Concrete Strength)

Core Testing

Low Strength

Confirmed

47

Page 48: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

3. What are accept. criteria for strength tests? b. What steps are needed (by concrete supplier) if acceptance criteria are not met?

Requirement Required Action(s) (ACI 318-19, 26.12.3.1 b)

Each strength test:• ≥ fc′ - 3.5 MPa

(fc′ ≤ 35 MPa)• ≥ 0.9 fc′

(fc′ > 35 MPa)

• Steps shall be taken to increase subsequent strength tests

• Investigate strength tests 26.12.6

Average of any 3 consecutive strength tests ≥ fc′

• Steps shall be taken to increase subsequent strength tests

48

Page 49: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

3. What are accept. criteria for strength tests? b. What steps are needed (by concrete supplier) if acceptance criteria are not met?

Requirement Required Action(s) (ACI 318-19, 26.12.3.1 b)

Required Action(s)(ACI 301-16, 1.6.6.2)

Each strength test:• ≥ fc′ - 3.5 MPa

(fc′ ≤ 35 MPa)• ≥ 0.9 fc′

(fc′ > 35 MPa)

• Steps shall be taken to increase subsequent strength tests

• Investigate strength tests 26.12.6

• Steps shall be taken to increase subsequent strength tests

• Core testing

Average of any 3 consecutive strength tests ≥ fc′

• Steps shall be taken to increase subsequent strength tests

• Steps shall be taken to increase subsequent strength tests

49

Page 50: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

4. How to investigate strength tests not meeting….?e. How to test cores and interpret results?

ACI 318-19, 26.12.6.1 (b)(ACI 301-16, 1.6.4.3)• Test in accordance with ASTM C42• Cores drilled from area in question • 3 cores for each failed strength test

Each core ≥ 0.75 fc′

Average (3 cores) ≥ 0.85 fc′

50

Page 51: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

5. Strength is still low – now what?

• Standard cured cylinders – failed• Structural adequacy – in doubt • Field cured cylinders – failed• In-place strength evaluation – failed• Core testing – failed

ACI 318-19, 26.12.6.1 (g)…responsible authority shall be permitted to order a

strength evaluation in accordance with Chapter 27 for the questionable portion of the structure

51

Page 52: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

6. Who pays for testing?

ACI 318-19 SILENTACI 301-16, 1.6.3 and 1.6.4

Test type Responsible for paymentConcrete strength tests (part of QA) Owner

Additional testing of materials or concrete because of failure to meet specification requirements

Contractor

Tests to verify strength of concrete in structure

Contractor (only if subsequent testing confirms

concrete does not meet acceptance criteria)

52

Page 53: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

7. How can concrete producer avoid low strengths?

• What’s the difference between specified strength and required average strength?

• What is statistics and how can it help?

53

Page 54: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

Definitions from ACI CT-18

• required average strength — the average strength of concrete used in mixture proportioning to ensure a high likelihood that the concrete will meet specified strength acceptance criteria

54

Page 55: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

14.0 17.5 21.0 24.5 28.0 31.5 35.0 38.5 42.0

Prob

abili

ty

Normal Distribution FunctionMean = 28 MPa, Standard Deviation = 3 MPa

0%

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

14.0 17.5 21.0 24.5 28.0 31.5 35.0 38.5 42.0

Cumulative Normal Distribution FunctionMean = 28 MPa, Standard Deviation = 3 MPa

7. How can concrete producer avoid low strengths?a. What is statistics and how can it help?

13%

Area = 13%

fc’

55fc’ - 3.5 MPa

fc’ - 3.5 MPa

fc’

Page 56: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

0%

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

14.0 17.5 21.0 24.5 28.0 31.5 35.0 38.5 42.0

Prob

abili

ty

Strength, MPa

Cumulative Distribution Functions

Specified Strength

Required Average Strength

Acceptance (f'c - 3.5 MPa)

ACI 214R:“The fcr

′ should be established where failure to meet fc′ is anticipated at no more than 1 in 100 times (0.01).”

13%

1% fc’ fcr'

7. How can concrete producer avoid low strengths?b. What’s the difference between specified strength and required average strength?

?

56

fc’ - 3.5 MPa

Page 57: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

7. How can concrete producer avoid low strengths?b. What’s the difference between specified strength and required average strength?

ACI 301-16, 4.2.3• Strength test data not available

fc’ = 30 MPa fcr’ = 38.3 MPa

fc’ = 50 MPa fcr’ = 60 MPa

57

Page 58: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

7. How can concrete producer avoid low strengths?b. What’s the difference between specified strength and required average strength?

ACI 301-16, 4.2.3• Strength test data

availableExample: fc’ = 30 MPa, ss = 4 MPa, n = 15fcr

’ = fc’+1.34kss = 36.2 MPa fcr

’ = fc’+2.33kss-3.5 = 37.3 MPa

58

Page 59: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

7. How can concrete producer avoid low strengths?b. What’s the difference between specified strength and required average strength?

ACI 301-16, 4.2.3• Strength test data

availableExample: fc’ = 50 MPa, ss = 4 MPa, n = 15fcr

’ = fc’+1.34kss = 56.2 MPa fcr

’ = 0.9fc’+2.33kss = 55.8 MPa

59

Numerical Example: MNL-2, Manual of Concrete Inspection

Page 60: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

7. How can concrete producer avoid low strengths?c. What are control charts?

ACI 214R• Individual

strength tests• Average of five

tests • Range of two

cylinder breaks in each test

Required strength

Specified strength

Required strength

Average range of 2 cylinders

60

Page 61: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

7. How can concrete producer avoid low strengths?c. What are control charts?

61

Page 62: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

8. Additional resources

• ACI ACI 318-19, Building Code Requirements for Structural Concrete• ACI 301-16, Specifications for Structural Concrete• ACI 228.1R-19, Report on Methods for Estimating In-Place Concrete

Strength• ACI 214R, Guide to Evaluation of Strength Test Results of Concrete• ACI MNL-2, Manual of Concrete Inspection• ACI 211.8R-15, Guide to Troubleshooting Concrete Mixture Issues

as Influenced by Constitutive Materials, Jobsite Conditions, or Testing Practices

• ACI 212.3R, Report on Chemical Admixtures for Concrete• ASTM STP 169D, Significance of Tests and Properties of Concrete

and Concrete-Making Materials

62

Page 63: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

Thank youFor the most up-to-date information please

visit the American Concrete Institute at:www.concrete.org

Page 64: Jerzy Zemajtis jerzy.zemajtis@concrete.org Big 5

ACI Local Representative

Mr. Ahmad Mhanna Director, Middle East /North Africa Region

E-mail: [email protected]

ACI Middle East Regional OfficeSecond Floor, Office # 02.01/07

The Offices 02 Building, One CentralDubai World Trade Center Complex, Dubai, UAE

Phone: +971.4.516.3208 & 3209