june 2007 vol. 25. no. 4 jobhealth...
TRANSCRIPT
1 3MJobHealthHighlights Vol.�5.No.4 June�007
JobHealth HighlightsTechnical Information for Occupational Health and Safety Professionals
IntroductionOn August 24, 2006, the Occupational Safety and Health Administration (OSHA)
completed the revision of its respiratory protection regulation, 29 CFR 1910.134,
by issuing a fi nal rule specifying respirator Assigned Protection Factors (APFs).1
The APF values and their use were the subject of an earlier 3M publication.2 In
the preamble to the fi nal rule, OSHA describes its reasoning for setting each of
the APFs. This article will focus on the two APF values that were most discussed
during the rulemaking: the APF of 10 for all half facepieces, and the “qualifi ed”
APF of 1000 for hoods and helmets.
DiscussionWhen OSHA proposes any regulation, it is bound by law to use “. . . the latest
scientifi c data in the fi eld” and “(w)henever practicable, the standard promulgated
shall be expressed in terms of objective criteria and of the performance desired.”3
This is exactly what OSHA did in developing the APF table. The rulemaking was
based on a comprehensive review of the available literature and data on respirator
performance. Careful consideration was given to data generated in simulated
workplace protection factor (SWPF) and particularly, workplace protection factor
(WPF) studies. Both types of study simultaneously measure the concentration
of an air contaminant outside and inside respirators worn by people performing
either simulated or actual work activities. SWPF studies use artifi cially generated
contaminants and are done under carefully controlled laboratory conditions. WPF
studies are performed in real workplaces, using contaminants generated by the
work process, i.e., the contaminants for which the respirators are selected to provide
protection.
ASSIGNEDPROTECTIONFACTORS:KEYELEMENTSOFTHEFINALRULE
Figure1.Aloosefittingfacepiecewithheadprotection.
LarryJanssen,C.I.H.LarryJanssenisaCertifiedIndustrialHygienistwiththe3MOH&ESDLaboratory.
June 2007 Vol. 25. No. 4
� 3MJobHealthHighlights Vol.�5No.4 June�007
Figure�.Ahelmet-stylerespiratoryinletcoveringwithaweldingvisor.
Half Facepiece RespiratorsFor half facepiece respirators, OSHA concluded that WPF data “. . . is a better
measure of the protection provided by half mask respirators than data collected
only from SWPF studies or other highly controlled studies.”1 The half facepiece
WPF database OSHA analyzed ultimately consisted of 1339 data points. Data from
elastomeric and filtering facepiece respirators were examined separately. In addition
to OSHA’s own analysis, four statisticians were consulted to analyze the data to
determine the level of protection provided by each type of half facepiece respirator.
The data were also carefully evaluated to determine if both types of half facepieces
should be given an assigned the protection factor of 10, which OSHA had proposed.4
The result of OSHA’s analysis is shown in Table I.
Elastomeric Half Facepieces Filtering Facepieces
Number of Data Points 579 760
Percentage of WPFs less than 10 4.5 1.6
5th percentile WPF 1� 18
TableI.SummaryofAnalysisofWPFDataforHalfFacepieces
OSHA chose the lower 5th percentile point estimate of the WPF distribution to
establish APFs. This value represents the level of protection that 95% of respirator
users are expected to exceed. Conversely, 5% of WPFs are expected to be lower
than the 5th percentile estimate. As shown in Table I, the WPF data OSHA
analyzed agree well with this expectation. From the extensive data analyses, OSHA
concluded that an APF of 10 was appropriate for both elastomeric and filtering half
facepiece respirators.
It is also important to note that while substantial data were presented and analyzed
to support the APF of 10 for all half facepieces, no data were presented to suggest
the APF for either elastomeric or filtering half facepieces should be a value other
than 10. For instance, while some participants in the rulemaking argued for an APF
of 5 for filtering facepieces, their arguments were based on assumptions or opinions
rather than objective data. OSHA made numerous requests for supporting data
during the entire rulemaking, but none were provided. OSHA’s comment regarding
criticism of its own data analysis illustrates this point: “In all cases, concerns raised
by commenters about the composition of the dataset used in the metaanalysis, or the
statistical methods used to conduct the analyses, were unsubstantiated by evidence
submitted to the record despite repeated requests by OSHA for either specific
examples or additional evidence.”1 Thus, OSHA’s decision to use an APF of 10 for
all half facepieces fulfills its legal obligation as well as being the only technically
defensible decision it could make.
WPFdatawasgivenprecedenceoverSWPFdata.
3 3MJobHealthHighlights Vol.�5.No.4 June�007
Hoods and HelmetsOSHA proposed a “qualifi ed” APF of 1000 for hood and helmet powered air
purifying respirators (PAPR) and supplied air respirators (SAR).4 That is, OSHA
included an alternative APF of 25 for hoods and helmets unless it could be shown
that a particular device maintained positive pressure during use. There are
basically two reasons that OSHA included this caveat:
1) The National Institute for Occupational Safety and Health (NIOSH) had
recommended an APF of 25 for hoods and helmets since 1987.5 It is interesting to
note that 25 was based on WPF studies of PAPR with loose-fi tting facepieces, which
have been recognized as a different type of respiratory inlet covering for many
years6 (see Figures 1 and 2).
2) While several WPF studies and one SWPF study7 of PAPR and SAR indicated
the APF of 1000 was appropriate, the SWPF study also reported on one hooded
SAR whose performance was far less than a SWPF of 1000.
OSHA believed that maintenance of positive pressure inside the hood or helmet
during use would assure adequate protection.
A number of problems with the “positive pressure” criterion were presented during
the subsequent stages of the rulemaking. For example, OSHA did not specify a
test procedure to determine compliance with the criterion. That lacking, the test
conditions could have been selected such that all devices would pass or all devices
would fail. In either case, the test results would have been meaningless. Secondly,
all the devices that were shown to perform very well in the SWPF study OSHA cited
as the basis for the APF of 10007 had two or more negative pressure occurrences
during their testing. This indicates that maintenance of positive pressure is not the
only factor that determines the protection a device will provide.
For these reasons, OSHA maintained the dual APFs of 1000 or 25 for hoods and
helmets but changed the criterion for “earning” the APF of 1000. The caveat now
reads: “The employer must have evidence provided by the respirator manufacturer
that testing of these respirators demonstrates performance at a level of protection of
1000 or greater to receive an APF of 1000. This level of performance
can best be demonstrated by performing a WPF or SWPF study or
equivalent testing. Absent such testing, all other PAPRs and SARs
with helmets/hoods are to be treated as loose-fi tting facepiece
respirators, and receive an APF of 25.”
The revised caveat is much more reasonable than was proposed,
because it is based on the measured performance of each device.
However, it is still vague in that, as OSHA acknowledged, SWPF
and WPF yield different performance values and must be interpreted
differently. In addition, it is not known what test results might be
the protection
positive pressureMaintenance of
is not the only factorthat determines
a device will provide
Pleaserecycle.©3M�007.Allrightsreserved.
Occupational Health and Environmental Safety Division3MCenter,Building�35-�E-91St.Paul,MN55144-1000U.S.A.1-800-�43-4630www.3M.com/OccSafety
“equivalent” to either SWPF or WPF. (3M has WPF or SWPF data for all of its
hood and helmet style products. See Technical Data Bulletin #175 for details).8
ConclusionOSHA’s final APFs, including those for half facepieces and hood/helmet style
respirators are based on the best available information and data. OSHA was bound
by law to use this procedure. The qualified APF for hoods and helmets is intended
to account for uncertainty about the performance of specific designs. Since
performance data will likely be collected on many hoods and helmets, the dual APF
may someday become unnecessary.
References1. “Assigned Protection Factors; Final Rule,” Federal Register 71:164 (24 August 2006)
pp. 50122-50192.
2. 3MOccupationalHealthandEnvironmentalSafetyDivision:“Assigned Protection Factors” 3M Regulations Update # 26 (November 2006).
3. Occupational Safety and Health Act of 1970. Public Law 91-596 (online) Available at http://www.osha.gov/pls/oshaweb/owadisp.show_document?p_table=OSHACT&p_id=2743. Accessed May 3, 2007.
4. “Assigned Protection Factors; Proposed Rule,” Federal Register 68:109 (6 June 2003) pp. 34036-34119.
5. NationalInstituteforOccupationalSafetyandHealth(NIOSH): Respirator Decision Logic (DHHS/NIOSH Pub. No. 87-108). Washington, DC: U.S. Department of Health and Human Services/NIOSH, 1987.
6. AmericanNationalStandardsInstitute:American National Standard for Respiratory Protection (ANSI Z88.2). New York: American National Standards Institute, 1992.
7. CohenH.J.,Hecker,L.H.,Matthies,D.K.,Johnson.J.S.,Bierman,A.H.,Foote,K.L.: Simulated workplace protection factor study of powered air-purifying and supplied air respirators AIHAJ 62(5):595-604 (2001).
8. 3MOccupationalHealthandEnvironmentalSafetyDivision:“Assigned Protection Factors (APF) for 3M™ Hoods and Helmets” 3M Technical Data Bulletin # 175 (October 2006).
For more information, please contact Health and Safety ServicesTechnicalAssistance:1-800-�43-4630Fax-on-Demand:1-800-646-1655Internetsites:www.3M.com/OccSafetywww.respexam.com
Subscribe
Ifyouwouldliketobenotifiedbye-mailwheneachnewissueofJHHbecomesavailable,registeratwww.3M.com/jhh