SMACNA TESTING & RESEARCH INSTITUTE HEADQUARTERS: 4201 LAFAYETTE CENTER DRIVE, CHANTILLY, VIRGINIA 20151-1219 MAILING ADDRESS: P.O. BOX 221230, CHANTILLY, VIRGINIA 20153-1230 PHONE (703) 803-2980 FAX (703) 803-3732 www.smacnatri.org June 21, 2013 Randy A. Acosta, II Sal. J. Acosta Sheet Metal Mfg. Co., Inc. 930 Remillard Court San Jose, CA 95122 Re: Acosta Spiral Seam Elbow Dear Randy, The SMACNA Testing & Research Institute (STRI) verifies in the attached independent engineering report the Acosta Spiral Seam Elbow as submitted and tested to be applicable to the ANSI/SMACNA HVAC Duct Construction Standards, 3 rd edition 2006; Chapter 3 Round, Oval and Flexible Duct when constructed in accordance with the following requirements of Chapter 3: Section 3.1 Round Duct Construction Standards Figure 3-1 thru 3-2 Transverse Joints/Longitudinal Seams Figure 3-3 thru 3-4M Round Duct Reinforcement/Companion Flange Joints Table 3-5. 3-5M Round Duct Gage Unreinforced Table 3-10 thru 3-13M Required Gage for Spiral Seam Duct Professionally yours, SMACNA Testing & Research Institute Eli P. Howard, III Executive Director Attachments: Leakage of Spiral Seam Elbows Strength of Spiral Seam Elbows – Collapse Testing

Upload: others

Post on 31-Oct-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: June 21, 2013 · AMCA Publication 511-07 (Rev.8/08), Certified Ratings Program — Product Rating Manual for Air Control ... All five elbows evaluated have zero to negligible leakage

SMACNA TESTING & RESEARCH INSTITUTE

HEADQUARTERS: 4201 LAFAYETTE CENTER DRIVE, CHANTILLY, VIRGINIA 20151-1219 MAILING ADDRESS: P.O. BOX 221230, CHANTILLY, VIRGINIA 20153-1230

PHONE (703) 803-2980 FAX (703) 803-3732 www.smacnatri.org

June 21, 2013 Randy A. Acosta, II Sal. J. Acosta Sheet Metal Mfg. Co., Inc. 930 Remillard Court San Jose, CA 95122 Re: Acosta Spiral Seam Elbow Dear Randy,

The SMACNA Testing & Research Institute (STRI) verifies in the attached independent

engineering report the Acosta Spiral Seam Elbow as submitted and tested to be

applicable to the ANSI/SMACNA HVAC Duct Construction Standards, 3rd edition 2006;

Chapter 3 Round, Oval and Flexible Duct when constructed in accordance with the

following requirements of Chapter 3:

Section 3.1 Round Duct Construction Standards

Figure 3-1 thru 3-2 Transverse Joints/Longitudinal Seams

Figure 3-3 thru 3-4M Round Duct Reinforcement/Companion Flange Joints

Table 3-5. 3-5M Round Duct Gage Unreinforced

Table 3-10 thru 3-13M Required Gage for Spiral Seam Duct

Professionally yours, SMACNA Testing & Research Institute

Eli P. Howard, III Executive Director Attachments: Leakage of Spiral Seam Elbows Strength of Spiral Seam Elbows – Collapse Testing

Page 2: June 21, 2013 · AMCA Publication 511-07 (Rev.8/08), Certified Ratings Program — Product Rating Manual for Air Control ... All five elbows evaluated have zero to negligible leakage
Page 3: June 21, 2013 · AMCA Publication 511-07 (Rev.8/08), Certified Ratings Program — Product Rating Manual for Air Control ... All five elbows evaluated have zero to negligible leakage
Page 4: June 21, 2013 · AMCA Publication 511-07 (Rev.8/08), Certified Ratings Program — Product Rating Manual for Air Control ... All five elbows evaluated have zero to negligible leakage
Page 5: June 21, 2013 · AMCA Publication 511-07 (Rev.8/08), Certified Ratings Program — Product Rating Manual for Air Control ... All five elbows evaluated have zero to negligible leakage
Page 6: June 21, 2013 · AMCA Publication 511-07 (Rev.8/08), Certified Ratings Program — Product Rating Manual for Air Control ... All five elbows evaluated have zero to negligible leakage
Page 7: June 21, 2013 · AMCA Publication 511-07 (Rev.8/08), Certified Ratings Program — Product Rating Manual for Air Control ... All five elbows evaluated have zero to negligible leakage
Page 8: June 21, 2013 · AMCA Publication 511-07 (Rev.8/08), Certified Ratings Program — Product Rating Manual for Air Control ... All five elbows evaluated have zero to negligible leakage
Page 9: June 21, 2013 · AMCA Publication 511-07 (Rev.8/08), Certified Ratings Program — Product Rating Manual for Air Control ... All five elbows evaluated have zero to negligible leakage
Page 10: June 21, 2013 · AMCA Publication 511-07 (Rev.8/08), Certified Ratings Program — Product Rating Manual for Air Control ... All five elbows evaluated have zero to negligible leakage
Page 11: June 21, 2013 · AMCA Publication 511-07 (Rev.8/08), Certified Ratings Program — Product Rating Manual for Air Control ... All five elbows evaluated have zero to negligible leakage
Page 12: June 21, 2013 · AMCA Publication 511-07 (Rev.8/08), Certified Ratings Program — Product Rating Manual for Air Control ... All five elbows evaluated have zero to negligible leakage
Page 13: June 21, 2013 · AMCA Publication 511-07 (Rev.8/08), Certified Ratings Program — Product Rating Manual for Air Control ... All five elbows evaluated have zero to negligible leakage