kamel elhamy, 2013 abb transformers · pdf file · 2017-09-15product scope...

14
© ABB January 31, 2012 | Slide 1 ABB Transformers Egypt Our transformers support the systems that keep our world running Kamel Elhamy, 2013

Upload: phungkhanh

Post on 28-Mar-2018

227 views

Category:

Documents


5 download

TRANSCRIPT

© ABB

January 31, 2012 | Slide 1

ABB Transformers Egypt Our transformers support the systems that keep our world running

Kamel Elhamy, 2013

Factory Information

Key data 2012

Annual volume

40 MUSD

Employees

135

Total Close Area

7,500 m2

Total Area

20,000 m2

Line Capacity Units

MVA Average kVA

SDT ( ” 315 kVA )

900

150

160

MDT ( 316 ÷ 2499 kVA )

3000 1900

630

LMDT ( 2500 ÷ 5000 kVA )

150

450

3000

© ABB Group January 31, 2012 | Slide 2

TOTAL per year

4050

2500

Product scope definition SDT and MDT

Rated Power

Product type

50 - 2499 kVA,

Oil Immersed Distribution Transformer

Cooling

ONAN

System voltages § HV ”36 kV

(LI 170 AC 70)

§ LV ”1,1 kV

(LI - AC 3)

§ HV multi layer ,enamelled or paper insulated ,Cu or Al wire

§ Winding on the core leg

§ LV foil winding with Al or Cu foil or flat wire

§ Pole mount for SDT, Ground mount for SDT and MDT

© ABB Group January 31, 2012 | Slide 4

§ Three legs Cold Rolled Grain Oriented (CRGO) Silicon Steel core

§ Corrugated type tank

§ Strip layer insulation in MDT HV winding

§ Hermetically Sealed or Conservator Type

Product scope definition SDT and MDT Standard equipment included

§ Conservator type Off-circuit tap changer in 5 pos equipment

§ High and low voltage porcelain bushings acc to DIN standards

Optional equipment

§ Plug in bushings on HV § Painted in alternative

§ 7 pos Off-circuit tap changer § Top cover mounted

§ Thermometer pocket § Lifting lugs § Earthing terminals § Rating plate § Drain /Sampling device § Pressure relief device

(for hermetically sealed )

§ Bi-directional rollers (for ground mount)

§

§

§

§

Silica gel breather Oil level indicator without

contacts

Buchholz relay: 630-2499

kVA

Optional § Oil level indicator

with 1or 2contact

§ Buchholz relay <630

kVA

§ Flat Bars bushings on LV

§ Dial type thermometer (with

contacts)

§ Pressure relief device

(with contacts)

§ Multi protection device (DGPT 2 or similar)

§ Air filled cable boxes § Terminal box

§ Alternative loss

combinations

On special request

and dependent of

design department

loading

§ HV dual voltage § HV / HV transformer

RAL colors

§ Oil Level Indicator

© ABB Group January 31, 2012 | Slide 5

§ Side mounted bushings on LV

Product scope definition LMDT

Rated Power

2500-3150 kVA

2500 - 5000 kVA

Oil Immersed Hermetically Sealed or

Conservator Type

>3150 kVA

Conservator type with radiator cooling

Cooling

ONAN

System voltages

HV ”36 kV

LV ”12 kV For ratings above 3150 kVA

§ Winding on the mandrel

§ HV multi layer winding, round or flat , enamelled or paper

insulated Cu wire

§ LV foil winding with Cu foil, layer winding with Cu flat wire

§ Strip layer insulation

§ Up to 3400 kVA oval core shape, Above round core shape

© ABB Group January 31 , 2012 | Slide 6

§ Three legs Cold Rolled Grain Oriented (CRGO) Silicon Steel core

Product scope definition LMDT

§

§

Standard equipment included

Off-circuit tap changer in 5 pos Conservator type High and low voltage equipment porcelain bushings acc to

§

§

Optional equipment

Plug in bushings on HV § Painted in alternative Off-circuit tap changer with RAL colors max 7 pos

DIN § Top cover mounted

§ 2 Thermometer pockets

§ Dial type thermometer with contacts

§ Lifting lugs § Earthing terminals § Rating plate § Drain valve § Pressure relief device (Hermetically sealed type)

§ Multi protection device (DGPT 2 or similar)

(Hermetically sealed type)

§ Bi-directional rollers

© ABB Group January 31 , 2012 | Slide 7

§ Silicagel breather § Oil level indicator with one contact

§ Buchholz relay § Optional

§ Oil level indicator with

2 contacts

§ Oil level indicator § Winding temperature

indicator

§ Air filled cable boxes § Skid base § Terminal box § Filter valves (>3400 kVA)

§ Alternative loss

combinations

(>3400kVA)

Core Manufacture HV Winding L V Winding

Oil Filling Drying process

Active Part

Routine Test Special Test

Production Process- Active parts

© ABB Group January 31 , 2012 | Slide 8

Rib Manufacture Rib Welding Spot Welding

Shot blasting Leakage Test

Final Assembly

Cover Painting Tank Painting

Production Process- Tank

© ABB Group January 31 , 2012 | Slide 9

Testing of transformers 50 - 5000 kVA TRANSFORMER TESTS ACCORDING TO IEC 60076

Measurement of winding resistance Measurement of voltage ratio and check of phase displacement

Routine Tests

Measurement of short-circuit impedance and load loss

Measurement of no-load loss and current

Applied voltage test Induced voltage test

Measurement of insulation resistance Special Tests

Measurement of zero sequence impedence

Lightning impulse test Type tests

© ABB Group January 31, 2012 | Slide 10

Temperature rise test

MECHANICAL TESTS

Pressure test

Paint thickness and adhesion test

Green Transformer Program- BIOTEMP

• ABB Transformers Egypt participated in Cairo exhibition “ Electricx 2011 “ with its

produced BIOTEMP 500 kVA 22/0.4 KV. Indicating the following advantages :

1- BIOTEMP is human and nature friendly

2- BIOTEMP can withstand cont. over load 10 % starting from full load without more

cooling.

3- BIOTEMP fire point temperature is more than 300C.

© ABB Group

May 16, 2013 | Slide 10

© ABB Group January 31, 2012 | Slide 11

New Painting System Oxsilian

Shot blasting pre- treatment

Powder Powder Primer Top coat

§ Flow coat painting

§ New electrostatic painting line by Q2

to improve external view

§ Standard Colour RAL7035

© ABB Group January 31, 2012 | Slide 12

§ Overall thickness 80-120 microns

Existing painting System

Quality Management § ISO 9001:2008 Quality

§ ISO BS OHSAS 18001:2007 Operational Health & Safety

§ ISO 14001:2004 Environment

© ABB Group January 31, 2012 | Slide 13

Export Reference List

§ Algeria (O&G Utility)

§ Libya

§ Sudan

§ Djibouti (Utility)

§ Ivory Coast

§ Senegal

§ Togo

§ Benin

§ Ghana

§ Burkina Faso

§ Nigeria

§ Cameroun

§ Gabon (Utility)

§ Uganda (Utility)

§ Kenya

§ Rwanda

§ Tanzania

§ DR Congo (Utility)

§ Angola

§ Zambia (Utility)

§ Botswana

§ Mozambique

© ABB Group January 31, 2012 | Slide 14

© ABB Group January 31 , 2012 | Slide 15