keypad / display visit us at mcs-problem solving
TRANSCRIPT
KEYPAD / DISPLAY
Visit us at www.mcscontrols.com
MCS-Problem Solving
This presentation will discuss solving problems
using information provided by the MCS-
MAGNUM
Some forms of information recorded include: Print to File, Alarm Info & Graphs
We will review solving the following 2 problems Problem1: Unsafe Oil & No Amps
Problem2: Suct Superheat Hunting
Problem Solving
Problem1: Unsafe Oil & No Amps
We have a Print to File
We have an Alarm Info Print
Print to File
Print to File (System Info Portion)
Print to File (Alarms Portion)
Print to File (Alarm Info Portion)
What Do We Do?
If we have no amps there is something
mechanical holding off the power to the common
of our relay.
It could be a high discharge mechanical
switch?
It could be the motor overload?
It could be a circuit breaker?
Check the wiring diagram.
Problem2: Suct Superheat Hunting
We have a graph showing interaction of data
Graph
Graph Expanded Scale
Interaction of Data
When Liquid Injection comes on it drives Discharge temperature down in 1 min & 15 sec from 180F to 170F. Then, because of the large amount of refrigerant it goes down another 10F to 160F.
Next we see Suction temperature and Suction Superheat going down.
Solution Modulate Liquid Injection so it brings down discharge temperature at a slower pace and has very little overshoot.
Graph (After Liquid Injection Adj)
Graph (After Liquid Injection Adj)
Results After Adjustments
When Liquid Injection comes on now it drives Discharge temperature down in 7 to 12 min depending on load. The overshoot is usually less than 1 F.
Next we see Suction temperature remains steady to maybe .5 F
So by analyzing the interaction of data we can pinpoint the problem an resolve.