lec3 power system

Upload: parth

Post on 07-Jul-2018

235 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/18/2019 lec3 power system

    1/34

    POWER SYSTEMS ILecture 3

    06-88-590-68

    Electrical and Computer Engineering

    University of Windsor 

    Dr. Ali Tahmasebi

  • 8/18/2019 lec3 power system

    2/34

    1

    Per Unit Calculations

    l A key problem in analyzing power systems is the

    large number of transformers.

     –  It would be very difficult to continually have to refer 

    impedances to the different sides of the transformers

    l This problem is avoided by a normalization of all

    variables.

    l This normalization is known as per unit analysis.

    actual quantityquantity in per unit

     base value of quantity=

  • 8/18/2019 lec3 power system

    3/34

    2

    Per Unit Conversion Procedure, 1 

    1. Pick a 1f  VA base for the entire system, SB

    2. Pick a voltage base for each different voltage level,

    VB. Voltage bases are related by transformer turns

    ratios. Voltages are line to neutral.3. Calculate the impedance base, ZB= (VB)

    2/SB

    4. Calculate the current base, IB = VB/ZB

    5. Convert actual values to per unit

     Note, per unit conversion on affects magnitudes, not

    the angles. Also, per unit quantities no longer have

    units (i.e., a voltage is 1.0 p.u., not 1 p.u. volts)

  • 8/18/2019 lec3 power system

    4/34

    3

    Per Unit Solution Procedure

    1. Convert to per unit (p.u.) (many problems are

    already in per unit)

    2. Solve

    3. Convert back to actual as necessary

  • 8/18/2019 lec3 power system

    5/34

    4

    Per Unit Example

    Solve for the current, load voltage and load power 

    in the circuit shown below using per unit analysis

    with an SB of 100 MVA, and voltage bases of 

    8 kV, 80 kV and 16 kV.

    Original Circuit

  • 8/18/2019 lec3 power system

    6/34

    5

    Per Unit Example, cont’d

    2

    2

    2

    80.64

    100

    8064

    100

    162.56

    100

     Left  B

     Middle

     B

     Right  B

    kV  Z 

     MVA

    kV  Z 

     MVA

    kV  Z 

    VA

    = = W

    = = W

    = = W

    Same circuit, with

    values expressed 

    in per unit.

  • 8/18/2019 lec3 power system

    7/34

    6

    Per Unit Example, cont’d

    L

    2*

    1.0 0 0.22 30.8 p.u. (not amps)3.91 2.327

    V 1.0 0 0.22 30.8

     p.u.

    0.189 p.u.

    1.0 0 0.22 30.8 30.8 p.u.

     L L L L

    G

     I  j

    V S V I 

     Z 

    Ð °= = Ð - °+

    = Ð °- Ð - °́ 2.327Ð 90°

    = 0.859Ð - 30.8°

    = = =

    = Ð °́ Ð °=0.22Ð °

  • 8/18/2019 lec3 power system

    8/34

    7

    Per Unit Example, cont’d

    To convert back to actual values just multiply the

     per unit values by their per unit base

    LActual

    ActualL

    ActualG

    MiddleB

    ActualMiddle

    0.859 30.8 16 kV 13.7 30.8 kV

    0.189 0 100 MVA 18.9 0 MVA

    0.22 30.8 100 MVA 22.0 30.8 MVA

    100 MVAI 1250 Amps

    80 kV

    I 0.22 30.8 Amps 275 30.8

    = Ð - °́ = Ð - °

    = Ð °́ = Ð °

    = Ð °́ = Ð °

    = =

    = Ð - °́ 1250 = Ð - °A

  • 8/18/2019 lec3 power system

    9/34

    8

    Per Unit Equivalent of Transformers

  • 8/18/2019 lec3 power system

    10/34

    9

    Three Phase Per Unit

    1. Pick a 3f  VA base for the entire system,

    2. Pick a voltage base for each different voltage

    level, VB. Voltages are line to line.

    3. Calculate the impedance base

    Procedure is very similar to 1f  except we use a 3f 

    VA base, and use line to line voltage bases3

     BS   f  

    2 2 2, , ,3 1 1

    ( 3 )3

     B LL B LN B LN  B

     B B B

    V V V  Z S S S 

    f f f  = = =

    Exactly the same impedance bases as with single phase!

  • 8/18/2019 lec3 power system

    11/34

    10

    Three Phase Per Unit, cont'd

    4. Calculate the current base, IB

    5. Convert actual values to per unit

    3 1 13 1B B

    , , ,

    3I I

    3 3 3

     B B B

     B LL   B LN B LN  

    S S S 

    V    V V 

    f f f  f f  

    = = = =

    Exactly the same current bases as with single phase!

  • 8/18/2019 lec3 power system

    12/34

    11

    Three Phase Per Unit Example

    Solve for the current, load voltage and load power 

    in the previous circuit, assuming a 3f  power base of 

    300 MVA, and line to line voltage bases of 13.8 kV,

    138 kV and 27.6 kV (square root of 3 larger than the1f  example voltages). Also assume the generator is

    Y-connected so its line to line voltage is 13.8 kV.

    Convert to per unit

    as before.  Note the

    system (per phase) is

    exactly the

    same!

  • 8/18/2019 lec3 power system

    13/34

    12

    3  Per Unit Example, cont'd

    L

    2*

    1.0 00.22 30.8 p.u. (not amps)

    3.91 2.327

    V 1.0 0 0.22 30.8

     p.u.

    0.189 p.u.

    1.0 0 0.22 30.8 30.8 p.u.

     L L L L

    G

     I  j

    V S V I 

     Z 

    Ð °= = Ð - °

    +

    = Ð °- Ð - °́ 2.327Ð 90°

    = 0.859Ð - 30.8°

    = = =

    = Ð °́ Ð °=0.22Ð °

    Again, analysis is exactly the same in p.u.!

  • 8/18/2019 lec3 power system

    14/34

    13

    3  Per Unit Example, cont'd

    L

    Actual

    ActualL

    ActualG

    MiddleB

    ActualMiddle

    0.859 30.8 27.6 kV 23.8 30.8 kV

    0.189 0 300 MVA 56.7 0 MVA

    0.22 30.8 300 MVA 66.0 30.8 MVA

    300 MVAI 125 (same cur 0 Amps

    3138 kVI 0.22 30.

    rent!)

    8

    = Ð - °́ = Ð - °

    = Ð °́ = Ð °

    = Ð °́ = Ð °

    = =

    = Ð - °́  Amps 275 30.81250 = Ð - °A

    Differences appear when we convert back to actual values

  • 8/18/2019 lec3 power system

    15/34

    14

    3  Per Unit Example 2

     •  Assume a 3f  load of 100+j50 MVA with VLL of 69

    kV is connected to a source through the per-phase

    network below:

    What is the supply current and complex power?

    Answer: I=467 amps, S = 103.3 + j76.0 MVA

  • 8/18/2019 lec3 power system

    16/34

    15

    Per Unit Change of MVA Base

    l Parameters for equipment are often given using

     power rating of equipment as the MVA base

    l When only one component is considered, the

    nameplate values of that component are selected as

     base values

    l In a larger system, all per-unit data must have the

    same power base

  • 8/18/2019 lec3 power system

    17/34

    16

    Per Unit Change of MVA Base

    • To convert from an “old” base to a “new” base:

     = ,  ×,

    ,  =

    , =

    , ×,

    ,

    but   =

      → ,  = ,  ×

    ,

    ,

    ,

    ,

      or

    ,  = ,  ,

    ,

    ,

    ,

  • 8/18/2019 lec3 power system

    18/34

    17

    Per Unit Change of Base Example

     •  A 30 MVA, 240/480 kV transformer has a leakage

    reactance or 2.71%. What is the reactance on a 100

    MVA and 230 kV base?

       = 0.0271×240

    230

    100

    30  =0.098  ..

       = 0.098×

    =52.032  W

  • 8/18/2019 lec3 power system

    19/34

    18

    Transformer Reactance

    l Transformer reactance is often specified as a

     percentage, say 10%. This is a per unit value

    (divide by 100) on the power base of the

    transformer.l Example: A 350 MVA, 230/20 kV transformer has

    leakage reactance of 10%. What is p.u. value on

    100 MVA base? What is value in ohms (230 kV)?

    2

    1000.10 0.0286 p.u.350

    2300.0286 15.1

    100

    e X   = ´ =

    ´ = W

  • 8/18/2019 lec3 power system

    20/34

    19

    Three Phase Transformers

     •  There are 4 different ways to connect 3f  transformers

    Y-Y   - 

    Usually 3f  transformers are constructed so all windings

    share a common core

  • 8/18/2019 lec3 power system

    21/34

    20

    3  Transformer Interconnections

      -Y   Y- 

  • 8/18/2019 lec3 power system

    22/34

    21

    Y-Y Connection

    Magnetic coupling with An/an, Bn/bn & Cn/cn

    1, , An AB A

    an ab a

    V V I a a

    V V I a= = =

  • 8/18/2019 lec3 power system

    23/34

    22

    Y-Y Connection: Per Phase Model

    Per phase analysis of Y-Y connections is exactly the

    same as analysis of a single phase transformer.

     NOTE: In this simplified circuit, RC 

    is ignored.

  • 8/18/2019 lec3 power system

    24/34

    23

    Y-Y Connection: Per Phase Model

    Y-Y connections are common in transmission

    systems.

    Key advantages are the ability to ground each sideand there is no phase shift is introduced.

    Main disadvantage is that the undesirable 3rd harmonic

    exciting current will cause difficulties to the rest of thenetwork.

  • 8/18/2019 lec3 power system

    25/34

    24

      -  Connection

    Magnetic coupling with AB/ab, BC/bb & CA/ca

    1 1, , AB AB A

    ab ab a

    V I I a

    V I a I a= = =

  • 8/18/2019 lec3 power system

    26/34

    25

      -  Connection: Per Phase Model

    Per phase analysis similar to Y-Y except impedances

    are decreased by a factor of 3.

    To use the per phase equivalent we need to use

    the delta-wye load transformation

     =

    Р -30°

  • 8/18/2019 lec3 power system

    27/34

    26

      -  Connection

     •  Advantage of a Dwinding (in any combination) is

    that it can trap the 3rd harmonic exciting current

     •  Key disadvantage is D-Dconnections can not be

    grounded; not commonly used.

  • 8/18/2019 lec3 power system

    28/34

    27

      -Y Connection

    Magnetic coupling with AB/an, BC/bn & CA/cn

  • 8/18/2019 lec3 power system

    29/34

    28

      -Y Connection V/I Relationships

    , 3 30

    30 30Hence 3 and 3

    For current we get

    1

    13 30 303

    130

    3

     AB ABan ab an

    an

     AB Anab an

     ABa AB

    ab

     A AB AB A

    a A

    V V a V V V  

    V a

    V V V V 

    a a

     I  I a I 

     I a

     I I I I 

    a I 

    = = ® = Ð °

    Ð ° Ð= =

    = ® =

    = Ð - °® = Ð °

    I = Ð °

  • 8/18/2019 lec3 power system

    30/34

    29

      -Y Connection: Per Phase Model

     Note: Connection introduces a 30 degree phase shift!

    Common for generator step-up since there is a neutralon the high voltage side which can be grounded,

    reducing insulation requirement of transformer.

    Even if a = 1 there is a sqrt(3) step-up ratio

  • 8/18/2019 lec3 power system

    31/34

    30

    Y-  Connection: Per Phase Model

    Exact opposite of the D-Y connection, now with a

     phase shift of -30 degrees.

  • 8/18/2019 lec3 power system

    32/34

    31

    Load Tap Changing Transformers

    l LTC transformers have tap ratios that can be varied 

    to regulate bus voltages

    l The typical range of variation is ±10% from the

    nominal values, usually in 33 discrete steps(0.0625% per step).

    l Because tap changing is a mechanical process, LTC

    transformers usually have a 30 second deadband to

    avoid repeated changes.

    l Unbalanced tap positions can cause "circulating

    vars"

  • 8/18/2019 lec3 power system

    33/34

    32

    Phase Shifting Transformers

    l Phase shifting transformers are used to control the

     phase angle across the transformer 

    l Since power flow through the transformer depends

    upon phase angle, this allows the transformer toregulate the power flow through the transformer 

    l Phase shifters can be used to prevent inadvertent

    "loop flow" and to prevent line overloads.

  • 8/18/2019 lec3 power system

    34/34

    33

     Autotransformers

    l Autotransformers are transformers in which the

     primary and secondary windings are coupled 

    magnetically and electrically.

    l This results in lower cost, and smaller size and weight. Also smaller leakage impedances results

    in smaller series voltage drop (advantage) but also

    higher short-circuit current (disadvantage).

    l Another disadvantage is loss of electrical isolation between the voltage levels. This can be an

    important safety consideration when  a is large.