Page 1: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Line Sensors for Distribution Automation: Practical Deployment, Data Collection and Use Cases

TAV Networks, Dayton Power & Light, and Pacific Gas & Electric

UU Course 202 - January 30, 2017Distributech 2017

©TAVNetworks,Inc.2017 1

Page 2: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

InstructorsJoe Tavormina

• Comms&SensorsSystems:TAVNetworks,Inc.

Jeff Teuscher

• DistributionOpsManager:DaytonPower&Light

Stan Thompson

• PilotOperations:PacificGas&ElectricCompany

Jared Hafer

• DeploymentProjectManager:PacificGas&ElectricCompany©TAVNetworks,Inc.2017 2

Page 3: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Schedule 08:00 – Introduction to Line Sensors and Use Cases (15 minutes, Joe Tavormina)

08:15 –The Role of Line Sensors in Utility Operations (15 minutes, Jeff Teuscher)

08:30 – Theory and Operation of Line Sensors (30 minutes, Joe Tavormina)

09:00 – Use Case 1: Bracketing Fault Location (30 minutes, Stan Thompson)

09:30- Use Case 2: Calculating Fault Location (30 minutes, Stan Thompson)

10:15 – Break (15 minutes)

10:15 – Use Case 3: Asset Management (15 minutes, Jeff Teuscher)

10:30 – Use Case 4: Power Quality Investigation (15 minutes, Jeff Teuscher)

10:45 – Use Case 5: Vegetation Management (15 minutes, Joe Tavormina)

11:00 – Planning and Executing a Deployment Project (45 minutes, Jared Hafer)

11:45 – Q&A (15 minutes)

12:00 – End

©TAVNetworks,Inc.2017 3

Page 4: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Content• Line Sensors: in Distribution Automation

• Line Sensors: Operations and Communication• Current and Voltage sensing• Power harvesting, consumption, and management• Radio communications

• Deployment: Practical Aspects • Data management in today’s world of growing network security

requirements• Use of Line Sensor data in today’s utility operations environment• Streamlining data presentation for system operators

• Based on real world Line Sensor projects at PG&E and DP&L©TAVNetworks,Inc.2017 4

Page 5: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Purpose• ProvideattendeesabasisforplanningandexecutingLineSensorprojects• ReviewintendedbusinessbenefitsneededtojustifyLineSensorprojects• Discussrisksthatarelikelytobeencounteredduringprojectexecution• Discussintegrationintoexistingutilityoperationalprocessesandapplicationofdatareceivedfromlinesensors

• Sharereal-worldchallengesexperiencedandlessonslearnedinprojectsat:

• PacificGas&ElectricCompanyinCalifornia(PG&E)• DaytonPowerandLight(DP&L)inOhio

©TAVNetworks,Inc.2017 5

Page 6: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Objectives• After taking this course the participant will be familiar with:

• ThepracticaluseanddeploymentofLineSensors• BusinessbenefitsthatcanrealizedusingLineSensors• Sensordatamanagement,theuseofcellularandmeshradionetworks,radiocoverage,andoperationunderlowpowerconditions

• PlanningforbothphysicaldeploymentandITintegration• “Lessonslearned”fromfielddeploymentsatPG&E&DP&L

©TAVNetworks,Inc.2017

• Be ready to mastermind a deployment project:

6

Page 7: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Introduction to Line Sensors and Use CasesJoeTavormina

7

Page 8: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Line Sensor ExamplesOverhead Underground

TollgradeSentientEnergy

Eaton

PG&EExperimentalVoltageSagMonitor

SurfaceOperableVaultInstallation

PadMountInstallationOverheadInstallation

Grid-Sentry©TAVNetworks,Inc.2017 8

Page 9: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

UseCasesandBusinessBenefitsUse Case BusinessBenefits

FaultDetection,Location,andRapidRestoration• Readilyidentifiableandimmediatebenefits• DirectimpactonCAIDIandSAIDImetrics• Faultbracketing• High-precisioncalculatedfaultlocation

• Morerapidpowerrestoration• Moreefficientuseofrestorationresources• Improvementsinoutageperformance• Potentialdetectionofhigh-impedancefaults

PowerQualityMonitoring• ImmediateuseasanDistributionPlanningtool• Potentialuseasadynamicfeedbackmechanism

• DatasourceforDMSanddatahistorian

AssetManagement• CostsavingsinOperationsandMaintenance• Inexpensiveformofsubstationautomation

• Situationalawarenessalongextentofdistributionlines

• VerificationofRecloseroperation• VerificationofCapBankintegrity

VegetationManagement• Experimentalatthistime– requiresnewanalytics • Condition-basedvegetationmanagement

©TAVNetworks,Inc.2017 9

Page 10: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Adoption Decision 1: Cellular or Mesh Network?• CellularNetwork(Verizon,AT&T,Sprint,etc.):

• Radiocoverage(reliabilityfromwithinpadmountcover?)• Long-termnetworksupport(2G,3G,4G,LTE,etc.)• Operationalcostforbandwidthconsumption

• MeshNetwork(SSN,Cisco,Itron,etc.900MHz):• Radiocoveragetobattery-backedRadioRelaybackhauldevice• LatencyandTrafficCapacityinamulti-hopmeshnetwork• Capitalcostfornetworkdeployment

• Other:• SatelliteCommunications(“Satcom”)• Wi-Fi

©TAVNetworks,Inc.2017 10

Page 11: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Adoption Decision 2: IT Strategy for Head End?• UseCase

• Setsrequirements

• OperatorInterface• UseofExistingand/orAdditionalGUI?

• DataRepository• DMS,PiHistorian,SCADA,orother?

• DataCenter• In-HouseorHosted?• SecurityMandates

PG&EITDesignforTollgradeLineSensorPilotDeployment©TAVNetworks,Inc.2017 11

Page 12: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

The Role of Line Sensors in Utility OperationsJeffTeuscher

12

Page 13: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Sensor Roles on the Distribution System• Faultlocationandmagnituderecording• Reducefieldpatrollingtolocationcausesoflineoutages• Powerqualitydatacanbecapturedandanalyzedtopredictfutureequipmentfailurethroughdatatrending

• Fieldequipmentmonitoring– lowercostalternative• Sensorsprovidemanydatapointsfordistributionsystemtoanalysis• Circuitbalancingtools• EngineeringPlanningtoolsforquickaccesstolineloading• Alertsonreversepowerflows• Voltagesensing

©TAVNetworks,Inc.2017 13

Page 14: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Asset Management Functions• Allowassetstobemonitoredreal-time• Trackequipmentoperationstodecidemaintenancecycles• Powerqualitydatacanbecapturedandanalyzedtopredictfutureequipmentfailurethroughdatatrending

• SensordatacanfeedDistributionManagementSystemsforreal-timemodelingofthedistributionsystem.Allowsforoptimizationoftheutilityassets

• Sensorscanprovidemanydatapointsforassetsystemstoanalyze• Dataiskeytobetteranalyticsandthisleadstobetterassetmanagement

©TAVNetworks,Inc.2017 14

Page 15: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Hydraulic Recloser plus Line Sensor • CostSavingsof$2000perinstallation

• HydraulicRecloser+Sensor=$2500+$1000=$3500• ElectronicRecloser=$5500

• Sensorwillalerttheoperationscenterwhenithasoperatedandwenttolockout

• Sensorwillallowfortrackingnumberofoperationsontherecloser

• Sensorwillprovidereal-timeamperagedatatounderstandloadingontherecloser

©TAVNetworks,Inc.2017 15

Page 16: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Sensors as an alternative to expensive distribution assets

• HydraulicRecloserandSensorvsElectronicRecloser• CircuitMonitoringatSubstationvsRTUandDigitalRelays• PlanningTools– SensorsMonitoringLoadvsLoadLoggerTechnology• MonitorCapacitorGroundforcurrentflow.Signalsablownfuseonthethreephasebank.

• Monitorcircuitbalanceatpointsalongthecircuit.• Potentialtouseforvegetationgrowth.Basedonsmallinterruptionorsmallcurrentfluctuations.

• Faultdetectionandreportingonthedistributionsystem

©TAVNetworks,Inc.2017 16

Page 17: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Sensors as Circuit Monitors at Substations• SubstationsthatdonothaveanRTUinstalledtoday.• Sensorswillbedeployedoneachcircuitleavingthesubstation.• Circuitmonitoringcanbeachievedatmuchreducedcost.SensorsareApproximately$3500percircuitinstalled.

• RTUwithcommunicationsisapproximately$50k- $75kbeforedigitalrelaysareinstalled.

• Sensorallowscircuitloading,alertwhencircuithasoperated,aggregateofcircuitloadsprovidestransformerloading.

• Sensorsaremonitoringonly,whereasRTUprovidescontrolatthesubstation.

©TAVNetworks,Inc.2017 17

Page 18: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Sensors as Planning Tools• Sensors=$1000each– LoadLoggersare$1600each

• Sensorsprovidedatanearreal-timeloaddatatotheengineers

• Sensorsdon’tneedbatteries• LoadLoggersneedtobeinstalledforaperiodoftimeandthenremovedtoretrievethedata

• Loadloggerneedssoftwaretodownloaddata• Sensorsuppliesdatatoutilitysystemofchoice

©TAVNetworks,Inc.2017 18

Page 19: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Theory and Operation of Line SensorsJoeTavormina

19

Page 20: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Line Sensors provide most business benefits for a fraction of the cost

• Easeofinstallation• EaseofintegrationintoADMS,SCADAand/orHistorian• “No”batteriesincluded• Noneedtorolltruckstoreadsubstationloads.Canbecollectedwiththesensors.

• Abilitytocapturefaultcurrentevents.Magnitudeandduration.• Abilitytoprovideconductorlinetemperature– DynamicLinerating.• Monitorneutralcurrentatcapacitorbanks– largecurrentsshowcapacitorhasblownonephaseofthe3Φ bank.

©TAVNetworks,Inc.2017 20

Page 21: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Current Measurement• BasedonRogowskicoil• SplitringpermitsinstallationonDistributionLine

Reference:EEPublishers,July2016,“Rogowskicoilsinsmarttransformer

monitoring”

Reference:Weiku.comTollgradeLightHouseMVCurrentSensor ©TAVNetworks,Inc.2017 21

Page 22: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Voltage Measurement• Directvoltagemeasurementat>12KVisexpensive,andcanposesafetyrisks

• Example:TollgradeMVPowerSensor

• Directvoltagemeasurementontransformersecondarycanserveasaproxy

• Examples:PG&EVSM,QNALineWatch

TollgradeLightHouseMVPowerSensor

QinetiQ-NALineWatch

PG&EVoltageSagMonitor

©TAVNetworks,Inc.2017 22

Page 23: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Line Sensor Data Collection• EventDriven• Periodicmeasurements

• Daily/hourly• Interval• Perphase• Current/EMF(Voltage)

• Other• PhaseIdentification(Automatic?Needsregionalmasterreferenceunit)

• Localreadingsfromfieldmeasurements• Head-endsetting/configuration

©TAVNetworks,Inc.2017

CellularorMeshNetworkbackhaul:◦ Verizon,AT&T,Sprint,etc.◦ SSN,Cisco,Itron,etc.(900MHz)

Phaseanglemeasurements:◦ Seevoltageandcurrentwaveformsnotinphase

◦ Takecorrectiveaction(capacitors/inductors)

23

Page 24: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Example of Sensor Data on 4kV Circuit

©TAVNetworks,Inc.2017

7 Days24

Page 25: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Configuring Set Points and Alarms• DNP3points/mapping?

• IdentifywhatisdeliveredtoDMS• ONLYfaultdata?(Minimalalerts)• Currentload,phaseimbalance,communicationsstatus,temperature,locationchangesandmoreareallconfigurabletosendalertstoDMS

• (verynoisy/falsepositives)

• Matchingknowntripsettings?• Existingprotectivedevicesettings• Feeder/device/loadspecific• Distributionengineerknowledge

• Outagetimers?• Definesensortimertoallowforprotectivedevicestooperate• Typically~60secondsforrecloserstoattempt3

©TAVNetworks,Inc.2017 25

Page 26: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Communication Performance Factors• RadioNetworkCoverage

• OverheadDistribution• UndergroundDistribution• StatisticalModeling

• PowerConsumption• QualityofService

• Availability• TransmissionLatency• Capacity• ReconnectionTime

• CostFactors• CapitalExpenditure• OngoingDataTransmission• RelativeDeploymentCosts AntennaGainisoneofmanyfactorsthat

affectsCommunicationPerformance©TAVNetworks,Inc.2017 26

Page 27: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Overhead Communications• Radiocoverageimprovesby~5dBvs.groundcoverageattypical30-ftlineheight

RFSignalLevelatPotentialLSLocations MeasuredRFPathLossagreeswithstatisticalpredictions

ThisRFTestRigwasusedtoconfirmRF

CoverageatpotentialLineSensor

deploymentlocations

©TAVNetworks,Inc.2017 27

Page 28: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Underground Communications• Radiocoveragediminishes by5-35dBvs.groundcoveragedependingonlocalconditions

• Earthgrade• Compositeormetallicvaultcovers?

• Specialproblemsincludeflooding

©TAVNetworks,Inc.2017 28

Page 29: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Inductive Power Harvesting

• ApplicableforCurrentLineSensors• PrimaryCurrentRequirements?

• 6-12ampsfor“normal”functionality• Typicallyemploysupercapacitors• NOTbatteries

• 3-6ampsminimumloadtooperatein“lowpowermode”• Differentlevelsoffunctionalityinlowpower?• Maynotcapturewaveformsinthismode• Maynotbeabletoqueryhistoricaldata

©TAVNetworks,Inc.2017 29

Page 30: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Power Harvesting Limitations

Debrisinthemagneticjawpreventedthislinesensorfromproperlyharvestingpowerandrechargingits

battery

10Amps

0.2Watts

©TAVNetworks,Inc.2017 30

Page 31: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Establishing Deployment Guidelines• “RulesofThumb”fordeployment

• OptimalspacingofOverheadmeshradiorelays• AnticipatedreliabilityofOverheadCellularDatacomms• FeasibilityofUndergroundCellularDatacomms

• “FirstPass”networkdesignobjectives• 95.0%or99.5%coverage,andatwhatcost?• CoveragegoalsforPilotDeploymentprojectsmaydiffer

• PowerHarvestingLimitations• Averagecurrentatdesiredlocation

• Pre-installationNetworkDesign/FieldSurveyprocess

©TAVNetworks,Inc.2017 31

Page 32: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Product ComparisonTollgrade Sentient Eaton Grid-Sentry

Product LightHouseMV MM3 GridAdvisorII GS-200

FaultIndication Yes Yes Yes YesCurrentMeasurement Average Average/Max/Min Nominal/Fault Average/Max/MinRMSCurrentRange 3or6- 600A 6or12- 800A 3- 600A 10- 1000AMaxVoltage 69KV 90KV 69KV 138KVHarmonicsMeasurement Np Yes No NoWaveformCapture Yes Yes No YesRadioCommunications Cellular,WiFi Cellular,Mesh,WiFi Cellular Cellular,Mesh,WiFiSCADAInterface SMSorDNP3 DNP3 DNP3 DNP3OperationalTempRange -40to+60C -40to+85C -40to+85C -40to+65CWeight 6lbs. 6.5lbs. 2.5lbs. 3.5lbs.

©TAVNetworks,Inc.2017 32

Page 33: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Bracketing Fault LocationStanThompson

33

Page 34: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

PG&E Company Profile

• PacificGasandElectricCompanyincorporatedinCaliforniain1905basedinSanFrancisco.

• PrimaryBusiness:Thetransmissionanddeliveryofenergy.PGEemploysapproximately20,000people.

• Goal:EstablishthebestoperatingUtilitiesintheU.S.Achievethefirstquartile

©TAVNetworks,Inc.2017 34

Page 35: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

PG&E Company Profile (continued)• ServiceareastretchesfromEurekainthenorthtoBakersfieldinthesouth,andfromthePacificOceaninthewesttotheSierraNevadaintheeast

• 141,215circuitmilesofelectricdistributionlinesand18,616circuitmilesofinterconnectedtransmissionlines

• 42,141milesofnaturalgasdistributionpipelinesand6,438milesoftransportationpipelines

• 5.4millionelectriccustomeraccounts• 4.3millionnaturalgasaccounts

©TAVNetworks,Inc.2017 35

Page 36: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

PG&E Business Benefits from Line Sensors

1. Reducecostofoutageresponse

2. Increasedsystemreliability

3. Assessmentoflinesensorcapabilities

©TAVNetworks,Inc.2017

Linesensorsareamodern,cost-effectivealternativetoanalogdevicesfordetectingandlocatingelectricdistributionlinefaults,whilealsoprovidingsignificantadditionaloperationalbenefits.

36

Page 37: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

PG&E Line Sensor Use Cases • Fasteroutagerestoration

• “Narrowdown”thelocationofafault• Reduceoutageresponsetime

• Providemoreaccuratecurrentflowinformationtooperatorsandengineers

• Providemoreaccuratecurrentflowtoengineerstosupportbetterplanningofthedistributionsystem

©TAVNetworks,Inc.2017 37

Page 38: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Missing PiecesNoexistingsystemsthatcanutilizethebestofallexistingsystemsand

stillprovideinexpensiveinstantaneouscommunication

©TAVNetworks,Inc.2017 38

Page 39: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Currently In-Use Isolated Systems

GIS– GeographicInformationSystem

• EvolvedoveralongtimeperiodatPG&E

©TAVNetworks,Inc.2017 39

Page 40: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Current Isolated Systems (continued)

FLISR– FaultLocation,IsolationandServiceRestoration(FLISR)• Distributionautomationapplicationthatnetworksgroupsofswitchesonafeedertovastlyimprovethereliabilityofutilitydeliveredpowerby“localizing”outages.

OMS– OutageManagementSystem• Onlytracksliveissues,onceresolved,theyaregone.Rowbaseddatabase.

©TAVNetworks,Inc.2017 40

Page 41: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Current Isolated Systems (continued)

ILIS– OutageTrackingTool• Slowtoupdateandcumbersometofollow.Historicaloutlineofeventsaftertheyhavehappenedandhavebeenresolved.

©TAVNetworks,Inc.2017 41

Page 42: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Current Isolated Systems (continued)DMS– DataManagementSystem

• Operatorscanseeiconswhencallscomeinandthepowergrid,buttheydon’tknowwheretheoutageisandoftendispatchT-Mento20-40milesofpowerlinestocheckitout.

©TAVNetworks,Inc.2017 42

Page 43: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Line Sensors Are New & Must Integrate With Existing Processes

©TAVNetworks,Inc.2017 43

Page 44: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

PG&E DTOC• TheDTOChousedtheLineSensorPilotOperationsTeam

©TAVNetworks,Inc.2017 44

Page 45: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

PG&E Decided to Create a Distribution Technology Ops Center (DTOC)

• NewDepartment• DefinedRolesforparticipatingengineers

©TAVNetworks,Inc.2017 45

Page 46: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Line faults were actively monitored and reported during the pilot project

©TAVNetworks,Inc.2017 46

Page 47: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

PG&E Line Sensor Pilot Project Timeline• 2014

• DTOCevaluatedaboutadozenLineSensorproductsfromvariousmanufacturers

• 2015• DTOCchose2overheadand1undergroundvendorforthepilotdeployment• Midyear,DTOCsuccessfullydeployedover1,300overheadlinesensorsonover200feederswithbothcellularandMeshtechnologies.

• 2016• DTOCdeployedover30undergroundcellularlocationsin2016,andover30rurallocationstoinvestigatesecondaryusecases

©TAVNetworks,Inc.2017 47

Page 48: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

What were the Real Issues during the Pilot?

• Logisticalissuesofdeployingandinstallinglinesensors• ITIntegration– Eachdatabasehasit’sownsetofrequirements• CaptureDatafromthelinesensors– Whowillreceive&monitorthedata?Interpretdatafromfield- Reporttherightdatatotherightparty

©TAVNetworks,Inc.2017 48

Page 49: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Pilot uncovered who really cared about Line Sensors

1. ProgramSponsor2. Dispatcher3. FieldCrews4. EOCTeams

©TAVNetworks,Inc.2017 49

Page 50: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Line Sensor Project Metrics - Outage Benefit Analysis MethodologyCreatetheOutageReportCard:

• ILISReportandOISOutageReport(RawData)forsustainedoutages.

Filterouteventswithnopossiblebenefits:• Planned/crewrequestedoutages• Transmissionline/substation/sourcesideoutages• Eventswithabnormalswitching/FLISR• Non-mainlineoutages(fuses/transformers)• NolinesensorsbeyondarecloserorSCADAswitch

Answerfivequestionsregardingthoseoutageswithpotentialbenefits:• Didthelinesensorsbehaveproperly?• Wasthereaswitchingoperationavailable?• Weredispatchdirectivesavailable?• WasCFL(CalculatedFaultLocation)dataavailable?• WouldtheCFLdatahaveprovidedadditionaldispatchdirectives?

©TAVNetworks,Inc.2017 50

Page 51: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

The kickoff for line sensor hardware installationIdentifythesitelocations

• Cellularcoverage?Mesh?• Meshischeapertooperate

Createtheplan/schedulefordeliveryandinstallation

CoordinatewithVendors,createpurchaseordertoreceiveinventory

©TAVNetworks,Inc.2017 51

Page 52: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Circuit Map Change Sheet• Oncethesitesare

qualifiedandselected,aCircuitMapChangeSheetwasapprovedbytheengineerinordertoinstalladeviceonthepowerline

• ThissheetgivestheT-linemantheauthoritytoinstallthedeviceandthelocationatwhichtobeinstalled.

• ThereisinformationneededfromtheT-linemantoberecordedthatneedstogobacktotheoperationsteam.

©TAVNetworks,Inc.2017 52

Page 53: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Inventory Master ListWhenaCMCSsheetisreceived,allofthedatafromtheT-linemanmustberecordedtobeabletoproducestatisticsandtogetthedevicesuploadedintotheirrespectivedatabases.

©TAVNetworks,Inc.2017 53

Page 54: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Enter device deployment data into Vendor Head Ends (Tollgrade)WhentheCMCScomesbackfromthefield,thedatareceivedneedstobeenteredintothevendorspecificheadendsothattheuntilwillbegintoworkandcollectdata.

©TAVNetworks,Inc.2017 54

Page 55: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Enter device deployment data into Vendor Head Ends (Sentient)

WhentheCMCScomesbackfromthefield,thedatareceivedneedstobeenteredintothevendorspecificheadendsothattheuntilwillbegintoworkandcollectdata.

©TAVNetworks,Inc.2017 55

Page 56: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Inventory Record was captured in GISWhenadeviceisinstalledonthegrid,thedeviceinformationneedstobeuploadedintotheGISdatabaseinventoryrecord.TheGISwillpushthedataintotheDMSservertocreatethelocationinfo.

©TAVNetworks,Inc.2017 56

Page 57: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

An IT specialist on the project team was responsible for planning Data Flow

©TAVNetworks,Inc.2017 57

Page 58: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Remember this slide?

©TAVNetworks,Inc.2017 58

Page 59: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

PI Historian served as the link to the Line Sensor devices and data

©TAVNetworks,Inc.2017 59

Page 60: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Loading Data as displayed via PI Data Link

©TAVNetworks,Inc.2017 60

Page 61: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Other examples of engineering data from Pi Historian

Communicationissues

Lowpowerissues

Faultycircuits

Outages©TAVNetworks,Inc.2017 61

Page 62: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

PG&E selected 7 DNP3 points for common status reporting for all Line Sensors

• DataPointName

• LossOfCurrent

• HighCurrentStatus

• PermanentFault

• MomentaryFault

• LineDisturbance

• SagFault

• SurgeFault

©TAVNetworks,Inc.2017 62

Page 63: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

• Tollgrade• FaultCurrent(a)• HighCurrent(a)• HighCurrentStatus(b)• LineDisturbance(b)• LineDisturbanceCurrent(a)• LossOfCurrent(b)• MomentaryFault(b)• MomentaryFaultCurrent(a)• PermanentFault(b)• PowerFactor(a)• RMSCurrent(a)• SagDipsExceedingThresh(a)• SagFault(b)• SurgeDipsExceedingThresh(a)• SurgeFault(b)

• Sentient– CurrentDirection(b)– FaultAlert(b)– FaultThresholdCurrent(a)– LossofCommunication(b)– LossofServiceAlert(b)– LossofVoltageAlert(b)– RMSCurrent(a)

Note:faultclassificationlogicintheDMS

DNP Points were mapped into PI Historian (vendor specific)

©TAVNetworks,Inc.2017 63

Page 64: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

CMCS

GIS DMS

HeadEnd

CommunicationServer

Concentrator

InventorySensorMasterList

HeadEndEntry

EIEnterpriseIntegration

PIConnectorPIServerPIInterface

ProvisioningTaskListLineSensors

DNPIndex IT

HeadEndHeadEndHeadEndHeadEnds

Provisioning Task List was Complex!

©TAVNetworks,Inc.2017 64

Page 65: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

415DCLocations:

DiagnosticsCenter

7PendingGISUploadEATONCOOPER:1TOLLGRADE:5

SENTIENTCELL:1

36NewLocations:

HeadendIntegrationinprocess;GISawaiting

receipt.

332PILocations:STAMI:106TOLLG:228

408GISLocations:EC:56

STAMI:107STCELL:12TOLLG:233

83NOT inPI

EATONCOOPER:57SENTIENTCELL:13SENTIENTAMI:1TOLLGRADE:12

168DMSLocations:

ALLTOLLGRADE

164NOT inDMS

SENTIENTAMI:106TOLLGRADE:58

Task List Status Tracking was also Complex

©TAVNetworks,Inc.2017 65

Page 66: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Final Product: Distribution Operators viewed Line Sensor status via DMS

©TAVNetworks,Inc.2017 66

Page 67: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

• Onelinesensorsymbolperlocation(3sensors)displayedintheDMS• Select“LineSensorDisplay”optionintherightclickmenuoffaLineSensorsymboltoaccessreporteddata

• “NOCOM”tagnexttosymbolwhenLScommunicationslost

Normal• Orange=NoFault(default)

Faulted• BlinkingCyan=PermanentFault

Symbols in the DMS

©TAVNetworks,Inc.2017 67

Page 68: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

RightclickonaLSsymbolandlaunchtheLineSensorDisplayto

seeitsdata

DMS example showing multiple Line Sensors

©TAVNetworks,Inc.2017 68

Page 69: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

AnimatedSymbolsinDMSleadtofaultedzone

LSdata

SelectingaLSnamewilllocateitintheDMSmapandshowLoading

Databelow

Line Sensor Display after a Right-Click

©TAVNetworks,Inc.2017 69

Page 70: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Live DMS Display of LS Data1.SingleLine

Diagram

3.LoadingDataof

selectedLS

2.OperationalData

3devicesperlocation

©TAVNetworks,Inc.2017 70

Page 71: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Single Line Diagrams

• TheSingleLineDiagram(SLD)isusedasareferencetoindicatethelocationsofLSonthefeederinrelationshiptotheprotectivedevices

• LScorrelatewithrowsinthetablebelowthediagram• LSareshownasgraydiamonds(notanimated)intheSLD• Substationandprotectivedevicesareshownasredsymbols

©TAVNetworks,Inc.2017 71

Page 72: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Operational Data Table

• PerLSLocation:• Feeder– NameoffeederwhereLineSensorisinstalled• LineSensor– NameofLSlocation(OperationName)

• PerLSDevice:• PhaseID– LabelassociatedwithaLSdeviceatagivenlocationonthefeeder.Linesensorsareinstalledintriplets,e.g.,LS100254_1on“A”,LS100254_2on“B”,LS100254_3on“C”.

• LastLoadingData– LatestofperiodicallycollectedRMSCurrentvalues(e.g.,@15min)fromassociatedLS

• Status– CommunicationandPowerstatusofLS(detailsfollow)• Fault– detailsoffaultsreportedbytheLS(detailsfollow)

©TAVNetworks,Inc.2017 72

Page 73: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Status

Status

• Com– communicationsstatusofLSdevice• Blank=CommunicatingOK• “NOCOM”=LShasnotcommunicatedfor75minutesorlonger.Alldatacellswillshowasgraytext

• “NOTCOMMISIONED”=LSispresentintheDMSbutPIdatahasnotyetbeencommissioned.ThisisatemporarystatefornewlyinstalledLSwhilecommissioningisinprogress.Alldatacellswillbeblank

• Power• ON=AssociatedLSisenergized• OFF=notenergized

©TAVNetworks,Inc.2017 73

Page 74: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Fault Data

Fault

• PermanentFault• Fault=ColorcodeindicatingthepresenceofasustainedfaultreportedbyLSdevice(Orange=NoFault;BlinkingCyan=Fault;Gray=Statusunknown(whendevicenotcommunication))

• FaultCurrent=ValueandTimestampoflatestreportedpermanentfault

• MomentaryFault• FaultCurrent=ValueandTimestampoflatestreportedpermanentfault

Notice: Fault Current values older than 24 hours show as gray text; recent values as black

©TAVNetworks,Inc.2017 74

Page 75: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Loading Data

• RMSCurrenthistoricdatatrendofselectedLS(indicatedbyredrectangularframe)isshownbelowthetable

• Mouse-overthegraphforRMSvaluesataspecifictime• Selectgraphsectiontozoomin

©TAVNetworks,Inc.2017 75

Page 76: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Summary of Data Products from Project• 10minReportCards

• Operators• Engineers• T-Men

• MorningHealthChecktomakesuredevicesareonline• ReportingToolsformanagement

• Appshowingvariousmetric–periodicperformancereportschedulebased

• Determining“UpTime”

• SpecialAnalysis• Warriorsgame

©TAVNetworks,Inc.2017 76

Page 77: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Line Sensors on Warriors Stadium Feeders

• 6locationsestablishedonOaklandJ1110and1103feeders

• Loadvalueslooknormalandconsistent.• NoeventsfromLineSensordata.• Investigatingoutofphaseononesensor.

©TAVNetworks,Inc.2017 77

Page 78: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

©TAVNetworks,Inc.2017 78

Page 79: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

©TAVNetworks,Inc.2017 79

Page 80: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

©TAVNetworks,Inc.2017 80

Page 81: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

EGTDiagnosticCenterOaklandArena- LineSensorMonitoring

OaklandJ1110

AthleticsVS.TigersMay29th

Peak161Amps

AthleticsVS.TwinsMay31th225PeakAmps

• 7locationsonactivepowerfeedstotheStadiummonitoringtheWarriorsgame• Loadvalueslooknormalandconsistent(peakingatgametimes)• NosuspecteventsfromLineSensordata

Game7WarriorsVS.Thunder18:00

AthleticsVS.Twins13:05May30th218PeakAmps

AthleticsVS.TigersMay27th

Peak221Amps

Game6WarriorsVS.Thunder18:00

AthleticsVS.Tigers

May28thPeak215Amps

Game5WarriorsVS.Thunder18:00

May26thPeak196Amps

©TAVNetworks,Inc.2017 81

Page 82: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Tollgrade

©TAVNetworks,Inc.2017

Page 83: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Sample of Wave Form from Head End

©TAVNetworks,Inc.2017

Page 84: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Value added use cases for Engineers:• Failingequipment

• Capbanks,transformers,orunreliablemetering

• Balancetheloadbetweenthephases• Realtimecurrentreadings

LowcostsubstitutetoSCADA• DistributedGeneration

©TAVNetworks,Inc.2017 84

Page 85: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Characteristic Waveforms

FuseOperation

CapBankoperationCablejointfault/Splice

LoadSwitching

©TAVNetworks,Inc.2017

Page 86: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

CFL

©TAVNetworks,Inc.2017 86

Page 87: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

DG reports

©TAVNetworks,Inc.2017

Page 88: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Calculating Fault LocationStanThompson

88

Page 89: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

First Let’s Define CFL: The Broad Definition

TraditionalCFL(TCFL):• Calculationoffaultlocationbasedsolelyondata

collectedatsubstationusingVoltage/Currentreadings.• AnexampleofhowtodothisusesCYME

ComprehensiveCFL(CCFL):• Calculationoffaultlocationisbasedon:

• Voltageandcurrentmeasurementsmadeatthesubstation

• Currentmeasurementmadeontheprimaryofthedistributionline(LineSensors)

• Voltagemeasurementsmadeontransformersecondariesalongthedistributionline.(VoltageSagMonitors)

CalculatedFaultLocationisanattempttodeterminethelocationofafaultwithinseveralpolespans

©TAVNetworks,Inc.2017

Page 90: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Traditional Calculated Fault Location (TCFL)OurExperiencetoDate

TCFLcalculatesthenumberofwire-milestothefaultlocationusingCYMEcalculationvoltageandcurrentdatacollectedatthesubstation

ActualFault

Location

IndicatedFaultLocations

TypicalResultUsingSubstationCFL

Strengths:• Usesdataalreadyavailable

fromlinereclosersandsubstationrelaysandalternativetolargelinesensorrollout

• Reasonablejobofcalculatingthedistance

Shortcomings:• Identifiesmultiplepotential

locations– numerouslocationsdonotleadtomeaningfulbenefit

• Errorsareoftenintroducedduetoimprecisemodelingassumptions©TAVNetworks,Inc.2017

Page 91: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Original Visualization of CYME Analysis

©TAVNetworks,Inc.2017

Page 92: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

New Visualization of CYME Analysis

©TAVNetworks,Inc.2017

Page 93: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Results: Bracketing of a Fault Location Using Line Sensors

PossibleFaultLocation

ActualFault

Substation 1234

LS100128@ SW 4223

30.5

R4676

SCADA LS100146

@ SW 4115

40S9267SS 9273

R4068

SCADA

R4782

SCADA

SensorLocation Date/Time SensorName Phase RMSCurrent40 5/18/201617:12 LS100146_1 A 150440 5/18/201617:13 LS100146_3 B 27640 5/18/201617:12 LS100146_2 C 1447

InthisexampletheLineSensorsbracketthe

faulttothetopbranch.

LineSensorsbracketafaultlocation.LineSensorsprovideloadingdataforswitchingandcapacityplanningdecisions.Strengths:• Easytoinstall&tounderstandfaultlocation

information• Reasonablejobofcalculatingthedistance• PotentiallyprovidesadditionaldataforCCFLmodel• Providesdataforswitchingandcapacityplanning

Shortcomings:• Willnotworkwithlowcurrent• 10xthecostofnon-communicatingfaulted

circuitindictors(FCI)

©TAVNetworks,Inc.2017

Page 94: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Bracketing of a Fault Location Using Line Sensors

PossibleFaultLocation

ActualFault

Hollister 2104

LS100128@ SW 4223

30.5

R4676

SCADA LS100146

@ SW 4115

40S9267SS 9273

R4068

SCADA

R4782

SCADA

SensorLocation Date/Time SensorName Phase RMSCurrent40 5/18/201617:12 LS100146_1 A 150440 5/18/201617:13 LS100146_3 B 27640 5/18/201617:12 LS100146_2 C 1447

InthisexampletheLineSensorsbracketthe

faulttothetopbranch.

LineSensorsbracketafaultlocation.LineSensorsprovideloadingdataforswitchingandcapacityplanningdecisions.

Strengths:• Easytoinstall&tounderstandfaultlocation

information• Reasonablejobofcalculatingthedistance• PotentiallyprovidesadditionaldataforCCFLmodel• Providesdataforswitchingandcapacityplanning

Shortcomings:• Willnotworkwithlowcurrent• 10xthecostofnon-communicatingfaultedcircuit

indictors(FCI)

©TAVNetworks,Inc.2017

Page 95: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

ShortcomingsNecessitateMovingfromTCFLtoCCFL

FillingtheGapwithVSMs:1. ReducethenumberofpotentiallocationsfromTCFL2. ImprovetheaccuracyofthemodeledlineimpedancesinTCFL3. ProvidesensordatainlocationswhereLSisnotpractical

TCFLShortcomings

• Estimatesafaultdistancefromsubstationbutdoesn'tdeterminewhichbranchthefaultison(andtherecanbemany)• Modelingassumptionsarenotpreciseandcanleadtoerrorsinprediction• Lackofcurrentmeasuringdevices?

LSShortcomings

• LineSensorsdeterminewhetherthefault/currentpassedtheirparticularlocationhoweverthismaynotlocalizetheactualfaultlocation.• Theydon’tworkfardownthelineduetolackofcurrent,

• Cannotinstallifwireistoosmall,moreexpensiveinstallation• LineSensorspreciselymeasurethecurrent;butcannotmeasurethevoltage

The “Calculation Gap” that led to use of Voltage Sag Monitors

©TAVNetworks,Inc.2017

Page 96: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Voltage Sag Monitors Monitors Help Fill The Gap

• VSMspreciselymeasurethevoltagethatlinesensorscannot• Thefindingsthusfarindicatethatvoltagesagmonitorshaveaplace&thereismuchmorepotentialforleveragingdata

©TAVNetworks,Inc.2017

Page 97: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Our Experience to Date with VSM• VoltageSagMonitorsthatmeasureandreportvoltagedropduringfaultevents

• AdditionalVSMsensorcomplementsaforementioned• Supplementsthecalculationforfaultlocation.

ThemeasuredRMSvoltageduringthefaultevent,whencombinedwiththeVSM

installationlocationalongthedistributionline,canbeusedto

predictthefaultlocation

VoltageSag

©TAVNetworks,Inc.2017

Page 98: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Using Comprehensive Data to Pinpoint CCFL

Hollister 2104

LS100128@ SW 4223

30.5

R4676

SCADA LS100146

@ SW 4115

40S9267SS 9273

R4068

SCADA

R4470

SCADA

V

4ad69323.8%

V

4ad69299.7%

V

4ad69b10.9%

V

4acbb449.3%

V

4ad64791.9%

R4782

SCADA

R41808SCADA

V

4ad64620.6%

FaultLocationUsing:1. SubstationCFLAlone2.TCFLplusLineSensors3.TCFL,LS,plusVoltageSag

©TAVNetworks,Inc.2017

Page 99: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

VSM Conclusions: More “Bang for the Buck”• VSMscanbedeployedallthewaytotheendofthefeeder

• VSMsmakeCFLaccurate

• VSMsprovidepowerqualityandvoltagedataimportantforDG

• AugmentationofTraditionalCFLwithVSMconvertsa“nice-to-know”applicationtoamission-criticalbenefitforoperators

• PGEfoundvalueusingthevoltagesagmonitors

©TAVNetworks,Inc.2017

Page 100: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

VSM Relationship to Smart Meters• Weinstalled5Msmartmeters.

• CantheyfulfillthefunctionofaVSM?Yes...Inprinciple,butthereisno“quickfix.”Time,moneyandresearchwillbenecessary.

• SMaremissioncritical– billing– wouldrequirehardwareimplications&thiswouldbeamanyyearprocess.

VSMsareimmediatelyapplicable©TAVNetworks,Inc.2017

Page 101: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

BothTraditionalCFL&LineSensorshadshortcomingsthatcanbemitigatedwithuseofVSMs

Recommendations

• VSMsareacostattractivesolutiontosolvingtheCCFLpuzzle;(ofoursolutionsthisisalowercostapproach.

• VSMfunctionmaybeincludedinaSmartMeterfunctioninthefuturebutthatisalongwayoff.

• VSMsprovideasolutionforneartermCCFLefforts.

• VSMrolloutwillpayforitselfquickly&willfilltheneedduringtheyearsitwill taketodevelopSmartMeterimplementation

©TAVNetworks,Inc.2017

Page 102: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

102

• WhatworkedforPG&Eisacombinationoflinesensors,CFL,voltagemonitorsandexistinginfrastructure,resultinginthedisseminationofcrucialinformationwithin10minutes

Conclusions

©TAVNetworks,Inc.2017

Page 103: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

BREAK(15 minutes)

©TAVNetworks,Inc.2017 103

Page 104: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Asset ManagementJeffTeuscher

104

Page 105: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

DP&L OverviewServingtheRegionforOver100Years

• 6,000squaremilesin24countiesinOhio

• 1,400employees• Generation• CustomerServiceOperations• FieldOperations

• DP&LisanAEScompany• IndianapolisPower&LightissisterAEScompany

©TAVNetworks,Inc.2017 105

Page 106: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

AES, A Fortune 200 Global Energy Company

• 17countriesacross4continents• 35gigawatts(GW)ofgeneratingcapacity

• 7 utilitycompaniesincluding8GWofgeneratingcapacity

• $15billioninannualrevenues• Aglobalworkforceofapproximately21,000people

©TAVNetworks,Inc.2017 106

Page 107: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Asset Management Function• Allowassetstobemonitoredreal-time• Trackequipmentoperationstodecidemaintenancecycles• Powerqualitydatacanbecapturedandanalyzedtopredictfutureequipmentfailurethroughdatatrending

• SensordatacanfeedDistributionManagementSystemsforreal-timemodelingofthedistributionsystem.Allowsforoptimizationoftheutilityassets

• Sensorscanprovidemanydatapointsforassetsystemstoanalyze• Dataiskeytobetteranalyticsandthisleadstobetterassetmanagement

©TAVNetworks,Inc.2017 107

Page 108: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Line Sensors - an alternative to expensive distribution assets

• HydraulicRecloserandSensorvsElectronicRecloser• CircuitMonitoringatSubstationvsRTUandDigitalRelays• PlanningTools– SensorsMonitoringLoadvsLoadLoggerTechnology

• MonitorCapacitorGroundforcurrentflow.Signalsablownfuseonthethreephasebank.

• Monitorcircuitbalanceatpointsalongthecircuit.• Potentialtouseforvegetationgrowth.Basedonsmallinterruptionorsmallcurrentfluctuations.

• Faultdetectionandreportingonthedistributionsystem

©TAVNetworks,Inc.2017 108

Page 109: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Sensor as Circuit Monitor at Substations• SubstationsthatdonothaveanRTUinstalledtoday.• Sensorswillbedeployedoneachcircuitleavingthesubstation.• Circuitmonitoringcanbeachievedatmuchreducedcost.SensorsareApproximately$3500percircuitinstalled.

• RTUwithcommunicationsisapproximately$50k- $75kbeforedigitalrelaysareinstalled.

• Sensorallowscircuitloading,alertwhencircuithasoperated,aggregateofcircuitloadsprovidestransformerloading.

• Sensorsaremonitoringonly,whereasRTUprovidescontrolatthesubstation.

©TAVNetworks,Inc.2017 109

Page 110: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Sensors as Planning Tools• Sensors=$1000each– LoadLoggersare$1600each.

• Sensorsprovidedatanearreal-timeloaddatatotheengineers.

• Sensorsdon’tneedbatteries.• LoadLoggersneedtobeinstalledforaperiodoftimeandthenremovedtoretrievethedata.

• Loadloggerneedssoftwaretodownloaddata.

• Sensorsuppliesdatatoutilitysystemofchoice.

©TAVNetworks,Inc.2017 110

Page 111: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Hydraulic Recloser and Sensor • CostSavingsof$2000perinstallation

• (HydraulicRecloser+Sensor=$2500+$1000=$3500• ElectronicRecloser=$5500)

• Sensorwillalerttheoperationscenterwhenithasoperatedandwenttolockout.

• Sensorwillallowfortrackingnumberofoperationsontherecloser.

• Sensorwillprovidereal-timeamperagedatatounderstandloadingontherecloser.

©TAVNetworks,Inc.2017 111

Page 112: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Program at DP&L• Installalinesensoratfourlocationswithhydraulicreclosers.• Unitisinstalledontheloadsideoftherecloser.• Installationisononeruralcircuit.

©TAVNetworks,Inc.2017 112

Page 113: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Circuit One-line Diagram

©TAVNetworks,Inc.2017 113

Page 114: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Data from the Sensor for Recloser Monitoring and Maintenance• Simulatecounterwithoperationsofsensor.• Loadingontherecloser•Open/closetimingoftheoperations•Totalinterruptenergyontheunit

©TAVNetworks,Inc.2017 114

Page 115: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Sensor Data Chart on 3 single phase reclosers

©TAVNetworks,Inc.2017 115

Page 116: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Power Quality MonitoringJeffTeuscher

116

Page 117: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Problem• LimestoneMiningOperationemployeeswerereceivingshockswhentheyweresettingchargesintothewall.

• Customercontactedtheutilityforhelponfindingtheproblemasthecustomerwasconcernedforemployeesafety.

• Two13.2GroundedYprimarymeteredservicestothemine.• Bothservicesareclosetotheutilitysubstation• CustomerrunsfourwireoverheadprimarytomultipleMV-LVtransformers.• GroundingpracticeswereMSHAnon-coal(primaryneutralbondedtosecondaryneutralandlocalearthelectrode)

• Customerthoughttheydidnotusetheneutralbutwasunsureoftheactualuseoftheneutralfortransformersandother

• CustomerwasunwillingtotakeanyoutagestoseparatephasesandneutralfromutilityforstandardNEV(neutraltoearthvoltage)test.

• Detailedinspectionofcustomerfacilitieswasoverlydifficultandexpensive

©TAVNetworks,Inc.2017 117

Page 118: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Problem Area in Mine

©TAVNetworks,Inc.2017 118

Page 119: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Circuit Map to Limestone Mine

©TAVNetworks,Inc.2017 119

Page 120: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Diagnostics/Findings• Criticaltoknowdetailsofneutralcurrentinneutralwirewithoutrequiringanoutageforthecustomeroranextensiveinspection

• TotalcurrentandcorrelationtoNEV• Amountofcurrentduetocustomerload• Amountofcurrentduetosubstationneutralreturncurrent

• PQmeteratmeteringpoint• Measuredneutralcurrentdemandedbycustomer• Measuredfrequencyspectrumofdemandedneutralcurrent• MeasuredNEV.

• Linesensor• Measuredthetotalneutralcurrent(customerdemandandsubstationreturn)• Measuredfrequencyspectrumoftotalcurrent– especiallyimportantthirdharmonic.• TrenddatawenttoPIdatahistorianforcorrelationwithPQandrevenuemeter

• NeutralcurrentandNEVatthesubstationwasdeterminedtobealmostall3rd harmonic.• Thisofferedanopportunitytofurtheridentifycurrentcontributions• Thirdharmonicwouldbesubstation• Fundamentalwouldmostlybecustomer

©TAVNetworks,Inc.2017 120

Page 121: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Line Sensor Current Chart

TSAA085228.217

TSAA0851Bad

10/20/2016 1:40:35 AM10/11/2016 4:20:35 AM 8.89 days

Plot-0

0

5

10

15

20

25

30

0

30 Ledtofindingcapacitorwithblownfuse

Highneutralcurrentclearedaftertreeoutage

©TAVNetworks,Inc.2017 121

Page 122: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Conclusion• NeutralcurrentmonitorsconfirmedNEVwascausedlocallyandnotbyutility

• Neutralcurrentsinrevenuemeterandlinesensorpredominantlyfundamental.• Neutralcurrentmagnitudeinrevenuemeterscloselymatchedthelinesensorcurrentmeasurement.

• NEVcorrelatedwithcurrentrecordedinPIbylinesensor.• Nooutageorextensiveinspectionwasneeded• Neutralcurrentmonitorsconfirmedfaultyequipmentononeserviceandblowncapacitorfuseontheother

• Faultyequipmenthadhighlyfluctuatingneutralcurrentandequipmentfailedwhilethelinesensorwasinservice.Linesensorconfirmedthecurrentreductionafterrepairs.

• LinesensorandPQmeteronotherserviceindicatedneutralcurrentmaybeduetocapacitor.Capacitorwaseasilylocatedanddidhaveblownfusewithotherphasesconnectedtoneutral.

• Strayvoltagewasfromthecustomerhighneutralcurrents• LightingcarriedNEVintotheminethroughtheequipmentgroundingconductorthatwasbondedtotheprimaryneutralasperMSHAandNECrequirements

• Highmoisturecontentandstrataconductivity“energized”largeareasoftheminewall.• Customernowunderstandsimportanceofverylowprimaryneutralcurrentandhasestablishedamonitoringprogram.

©TAVNetworks,Inc.2017 122

Page 123: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Other PQ Sensor Charts

-2500

-2000

-1500

-1000

-500

0

500

1000

1500

2000

1 31 61 91 121

151

181

211

241

271

301

331

361

391

421

451

481

511

541

571

601

631

661

691

721

751

781

811

841

871

901

931

961

991

1021

1051

1081

1111

1141

1171

1201

1231

1261

1291

1321

1351

1381

SensorAmps

ValuesAmps

Potentialofanintermittentfault–Couldrepresentafailinglinearrestor

©TAVNetworks,Inc.2017 123

Page 124: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Sensor PQ – Harmonic Distortion

-200

-150

-100

-50

0

50

100

150

1 30 59 88 117

146

175

204

233

262

291

320

349

378

407

436

465

494

523

552

581

610

639

668

697

726

755

784

813

842

871

900

929

958

987

1016

1045

1074

1103

1132

1161

1190

1219

1248

1277

1306

1335

1364

1393

ValuesAmps

ValuesAmps

LinefaultandHarmonicdistortionofthecurrentwaveshape.

©TAVNetworks,Inc.2017 124

Page 125: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Sensor Data

©TAVNetworks,Inc.2017 125

Page 126: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Vegetation ManagementJoeTavormina

126

Page 127: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Grid Maintenance Today

• Mostlyreactive(followingoutage)• Agingassets• Decliningnumberofpersonnel• Outagesaredifficulttolocate• Rootcauseofoutageoftennotresolved

Credit:MarionTremblay,Hydro-QuebecIREQ,DistributechFebruary2016

©TAVNetworks,Inc.2017 127

Page 128: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Outages may be avoided by locating and characterizing non-persistent faults

Credit:MarionTremblay,Hydro-QuebecIREQ,DistributechFebruary2016

• Non-oxidizedconductorindicatesarecentfaultprobablycausedbyvegetation

©TAVNetworks,Inc.2017 128

Page 129: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Vegetation issues lead to financial liabilities

PG&Etopayoutatleast$350millioninButteFireclaimsByDanaM.Nicholsdana@calaverasenterprise.comNov28,2016

Almost100ofthe1,856individualswhoaresuingPacificGasandElectricCo.overlossescausedbytheButteFirehaveagreedtosettlementswiththeutilitycompanyanditscontractorTreesInc.,accordingtoacourtdocument.

AttorneysfortheplaintiffsandthedefendantssaidinajointcasemanagementstatementfiledNov.18that53householdsincluding98plaintiffsandatotalof123individuals(someofwhomwerenotnamedplaintiffs)havesettledtheirclaims.

TheButteFirethatbeganSept.9,2015,burnedmorethan70,000acresanddestroyedmorethan500CalaverasCountyhomesaswellashundredsofbarns,shedsandwellhouses.TheCaliforniaDepartmentofForestryandFireProtectionconcludedinareportissuedinAprilthatatreetrimmingcrewhiredbyPG&Efailedtoremoveagraypinethatlaterfell,contactedapowerline,andstartedthefire.

PG&E,ContractorsToPay$51MToEndCalif.WildfireSuitsBy KurtOrzeck

Law360,LosAngeles(June6,2013,8:31PMEDT)--PacificGasandElectricCo.anditscontractorshaveagreedtopay$50.5milliontosettlelitigationovertwoCaliforniawildfiresthatburnedmorethan18,000acresofnationalforestandcost$13.5milliontosuppress,theU.S.DepartmentofJusticeannouncedThursday.

TheU.S.allegesthatthedefendants'neglectcausedthePowerFireandtheWhiskeyFire,whichoccurredinOctober2004andJune2008,respectively.ThefirstfireoccurredinEldoradoNationalForestinAmadorCountyinaremotelocationneartheSaltSprings...

©TAVNetworks,Inc.2017 129

Page 130: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Assessment of non-persistent faults from Hydro-Quebec• Non-persistentfaultsrepresentupto70%offaultsindistributioncircuits

• Typicallycausedbyvegetationcontactordefectiveequipment

• Oftendeteriorateintooutages• Oftenresponsibleformanyrepetitiveunsolvedoutages

Credit:BryanTexasUtilitiesWebSite

©TAVNetworks,Inc.2017 130

Page 131: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Voltage Sag Measurements can be used to Locate Fault and Identify Cause

Reference:MarionTremblay,Hydro-QuebecIREQ,DistributechFebruary2016

• Hydro-QuebecMILESproject• Locatedandrepairedlooseconductorthatheatedandexpandedunderhighcurrentload

• Locatednon-persistent,repetitivefaultduetovegetationinpresenceofwindgusts(norain)

• PG&ELineSensorPilotproject• AddressingliabilitiesrelatedtoforestfiresinthefoothillsofEasternCalifornia

©TAVNetworks,Inc.2017 131

Page 132: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Analysis of non-persistent faults requires analytics beyond current practice

• Assetassociationsandlocation• Eventrecords• Backgroundanalysis• Notificationsmanager• e.g.SensorConnectbyTAVNetworks,Inc.

Sensor SensorManager

SensorDB

DataEvent

DATA

ACK

SaveEventData

OK Sensor

Sensor

Sensor

SensorManager

WebService

WebClient

ManagementInterface

SensorInterface

SensorData

SensorDBInterface

ConfigData

ConfigDBInterface

WebClientInterface

©TAVNetworks,Inc.2017 132

Page 133: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Potential Benefits• Reductionofoutagefrequency(upto~50%)

• ReductioninSAIDIIndex(upto~60%)

• ReductioninOutageswithUnknownCause(upto~90%)

• Avoidanceofunnecessaryinvestment(Millionsof$$$)

• Mitigationofliabilityforwildfires

Credit:AsplundhWebSite

©TAVNetworks,Inc.2017 133

Page 134: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Lessons Learned from Line Sensor Deployment ProjectsJaredHafer

134

Page 135: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Planning a Line Sensor Project – Scope• WhatBusinessBenefitsaredesiredfromtheLineSensorDeployment?

• Needs• Wants• Expectations

• Anticipationofscope“creep”?• Plantopreventthis“creep”?

©TAVNetworks,Inc.2017 135

Page 136: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Articulating Anticipated Business Benefits• FaultDetection,Location,andRapidRestoration

• DecreaseWindshieldTimeforTroublemenbyknowingaprecisefaultlocation• Decreasedoutagedurationsforcustomersduetofasterresponses

• PowerQualityMonitoring• Distributionplanning• Troubleshooting

• AssetManagement• CostsavingsinOperationsandMaintenance• Substationautomation

• OtherbenefitstoutilitiesfromLineSensors?

©TAVNetworks,Inc.2017 136

Page 137: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Planning a Line Sensor Project – DeploymentIdentifydeploymentlocations

• Outsidesubstation• Afterfirstrecloser• Knowntroubledareas• NoSCADAareas• ForReliabilityorPlanning?

Qualifylocations• Currentonfeeder• Radionetworkcoverage• Localconditions(i.e.insidevault?)

• FieldInspectionConfirmation

©TAVNetworks,Inc.2017

Installationorders/maps• Lat/long• ProtectivedeviceID• Conductorsize(2/4/6AL/CUmayneedalineguard)

• Hotstickvsrubbergloveinstall• Access/propertyissues

Installationtraining/documentation

• ProcessfordeterminingRFcoverage,linecurrent,phaseID,andlocation

• DeploymentdatamanagementLine Guard

137

Page 138: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Deployment Schedule Issues/Risks• Significantschedulerisksduringdeployment

• Weather- Onewouldbeshockedtolearnhowmanyofourclientsforgettoconsiderwintersnoworextremesummerheatwhenputtingtogethertheirdeploymentschedules.

• UninformedCustomers- Uninformedcustomerswillasktheirneighborsortheinternetwhatthenewdevicebeinghungontheirpowerlineis.Besuretoletcustomersknowwhatyouaredoingandwhy,sotheyareproperlyinformed.

• LegalIssues- Canadevicebeinstalledwhereitisdesired?Ispermissionneededorarerightofwayagreementsrequiredinadvanceofinstallations?

• UnreliableVendors- Whathappenswhenanequipmentvendormissesadeliverydate,orequipmentfailsinthefield?

• Howcanknownprojectrisksbemitigated?

©TAVNetworks,Inc.2017 138

Page 139: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Planning a Line Sensor Project – QA• Whatisthedeploymentsuccesscriteria?• Howwillsuccessmetricsbemonitored/tracked?• Whatprocesseswillbeputintoplacetoremediatedevicesthatarenotfunctioningproperly?

Deploymentlocationswerescreenedforcommunicationsviability.Theoneontherightwasdeemedtoorisky.©TAVNetworks,Inc.2017 139

Page 140: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Planning a Line Sensor Project - Resources

• Whatexistingresourcesareavailableforassignmenttoproject?

• Whatadditionalresourcesneedtobeengagedfortheproject?

• Howwillhumanresourcesbemanagedfortheproject?

©TAVNetworks,Inc.2017 140

Page 141: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Planning a Line Sensor Project – IT Integration• Legacyinformationsystems

• GIS• DataHistorian• OutageManagement• DistributionManagement• SCADA

• DatarepositoryforLineSensors• Deploymentdatamanagement

• Paper-based?• Electronic?

DMS

SCADA

Gateway Supplier-SpecificHeadEnd

DNP3

VPNTermination

LineSensor Line

Sensor

LineSensor

ODN

UDN

NoProvisioningPermittedByPolicyfromwithinODN

Operators&DataUsers

One-WayDataPath

©TAVNetworks,Inc.2017 141

Page 142: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Planning a Line Sensor Project – Ops Integration

• LegacyOperationalProcesses

• NewDecisionProcesses

• PrimaryUsers• ExistingGUIs• Constraints

• ExecutiveUsers• Metrics• PeriodicReporting

©TAVNetworks,Inc.2017 142

Page 143: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Lesson Learned – IT Development• LineSensordeploymentdrives:

• Accelerationoforganizationaldecisionsregarding“AdvancedDMS”• Exposenetworksecurityconcerns• HighlightthesignificantcostassociatedwithITassetsanddevelopment

• Response:• PostponementofITIntegrationduringpilotproject• Adoptionofhostednetworkmanagementanddatacollection

©TAVNetworks,Inc.2017 143

Page 144: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Lesson Learned – Deployment Planning• LineSensordeploymentsuccessrequiresconfirmationof:

• RFCoverage• LineCurrent• PhaseIdentification• Location• LocalConditions

• Response:• FieldEngineeringisrequired• Appropriatefieldengineeringresourcesarerequired• Appropriatefieldengineeringtoolsarerequired

©TAVNetworks,Inc.2017 144

Page 145: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Lesson Learned – Deployment Data• LineSensoradoptionrequires:

• Integrationwithlegacyinformationsystems• Retoolingoflegacyoperationaldecisionprocesses

• Response:• Paper-basedprocessesareslowandtime-consuming• Installationdatacollectedonpapergetslost• Deploymentprojectplanneedsspecialconsiderationofthisproblem• Datamanagementtoolsthataddressthisproblemareneeded

©TAVNetworks,Inc.2017 145

Page 146: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Lesson Learned – Field Engineering Tools• FieldEngineeringToolsconservesignificanttimeandcostduringadeploymentproject

• LocationQualification• DeploymentDataCollection&Management

©TAVNetworks,Inc.2017 146

Page 147: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Q&A(15 minutes)

©TAVNetworks,Inc.2017 147

Page 148: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Index of AbbreviationsNLOS – Non Line Of SightODN – Operational Data NetworkOMS – Outage Management SystemPG&E – Pacific Gas & Electric CompanyRTU – Remote Terminal Unit (part of SCADA system) SCADA – Supervisory Control and Data AcquisitionUDN – Unsecured Data Network

©TAVNetworks,Inc.2017

ADMS – Advanced DMSAMI – Automated Metering InfrastructureCPUC – California Public Utility CommissionDA – Distribution Automation DMS – Distribution Management SystemDNP3 – A Common Serial Communication ProtocolDP&L – Dayton Power & LightNERC-CIP – DoE Regulating Entity

148

Page 149: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Presenters – UU Course 202• Joe Tavormina

• Principal,TAVNetworks,Inc.• TAVNetworksisaCommunicationsandSensorCompany• Email:[email protected],Tel:(775)831-0200

• Jeff Teuscher• OperationsManager,DaytonPower&Light(DP&L)• Email:[email protected],Tel:(937)331-4090

• Stan Thompson• OperationsProjectManager(Contract),PacificGas&ElectricCompany• Email:[email protected],Tel:(775)415-1000

• Jared Hafer• DeploymentProjectManager,BaltimoreGas&Electric(Contract)• Email:[email protected],Tel:(707)415-1000

©TAVNetworks,Inc.2017 149

Page 150: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Course Evaluation

• Pleasecompetethecourseevaluation– availablefromyourcellphone!Textthe#80464withthe5digitcodeattheendoftheUUcoursetitle

• CourseCode:16564• Fillinyournametoenteradrawingtowina$100Amazongiftcard!

©TAVNetworks,Inc.2017 150

Page 151: Line Sensors for Distribution Automation · ©TAV Networks, Inc. 2017 31. Product Comparison Tollgrade Sentient Eaton Grid-Sentry Product LightHouse MV MM3 GridAdvisor II GS-200 Fault

Thank you for AttendingUU202:LineSensorDeploymentforDistributionAutomation:Practical

Deployment,DataCollectionandUseCases(#16564)