list of control cables mv protections00
DESCRIPTION
ables MV353TRANSCRIPT
LIST OF CONTROL
CABLES MEDIUM
VOLTAGE PROTECTIONS
Equipment: DETAILED ENGINEERING
Order: VEC001101
Customer: ROYAL GK PTE LTD
DOCUMENT ORDER DATE
Nov-2012
List of control cables medium voltage protections VEC001101
INDEX
CUSTOMER
ROYAL GK PTE LTD
CONSISTENTS WITH OUR CONTINUAL PRODUCT IMPROVEMENT POLICY, GUASCOR POWER RESERVES THE RIGHT TO CHANGE ANY SPECIFICATION WITHOUT PRIOR NOTICE. i
- CONTENIDO -
1 MEASUREMENT TABLES ................................................................................ 1
DOCUMENT ORDER DATE
Nov-2012
List of control cables
medium voltage protections VEC001101 INDEX
CUSTOMER
ROYAL GK PTE LTD
CONSISTENTS WITH OUR CONTINUAL PRODUCT IMPROVEMENT POLICY, GUASCOR POWER RESERVES THE RIGHT TO CHANGE ANY SPECIFICATION WITHOUT PRIOR NOTICE. 1
1 MEASUREMENT TABLES
From To Cable Description
Amount
Transformer 1 Transformer Cell Room PLC (C-1) RV-K 10x1,5 mm² Alarms Trafo DGPT2 relay. 52
Transformer 2 Transformer Cell Room PLC (C-2) RV-K 10x1,5 mm² Alarms Trafo DGPT2 relay. 43
Transformer 3 Transformer Cell Room PLC (C-3) RV-K 10x1,5 mm² Alarms Trafo DGPT2 relay. 34
Transformer 4 Transformer Cell Room PLC (C-4) RV-K 10x1,5 mm² Alarms Trafo DGPT2 relay. 32
Transformer 5 Transformer Cell Room PLC (C-5) RV-K 10x1,5 mm² Alarms Trafo DGPT2 relay. 41
Transformer 6 Transformer Cell Room PLC (C-6) RV-K 10x1,5 mm² Alarms Trafo DGPT2 relay. 50
Transformer 7 Transformer Cell Room PLC (C-7) RV-K 10x1,5 mm² Alarms Trafo DGPT2 relay. 52
Transformer 8 Transformer Cell Room PLC (C-8) RV-K 10x1,5 mm² Alarms Trafo DGPT2 relay. 43
Transformer 9 Transformer Cell Room PLC (C-9) RV-K 10x1,5 mm² Alarms Trafo DGPT2 relay. 34
Transformer 10 Transformer Cell Room PLC (C-10) RV-K 10x1,5 mm² Alarms Trafo DGPT2 relay. 32
Transformer 11 Transformer Cell Room PLC (C-11) RV-K 10x1,5 mm² Alarms Trafo DGPT2 relay. 41
Transformer 12 Transformer Cell Room PLC (C-12) RV-K 10x1,5 mm² Alarms Trafo DGPT2 relay. 50
Transformer 13 Transformer Cell Room PLC (C-13) RV-K 10x1,5 mm² Alarms Trafo DGPT2 relay. 57
Transformer 14 Transformer Cell Room PLC (C-14) RV-K 2x1,5 mm² Alarm Aux Trafo temperature. 57
Transformer Cell Room (C-
15) Incoming Switchgear Stall (C-18) RV-K 4x4 mm² Signs of CTs differential protection 125
Transformer Cell Room (C-
16) Incoming Switchgear Stall (C-19) RV-K 4x4 mm² Signs of CTs differential protection 125
Transformer Cell Room (C-
15) Incoming Switchgear Stall (C-18) RV-K 8x1,5 mm² Book exchange signals
125
DOCUMENT ORDER DATE
Nov-2012
List of control cables
medium voltage protections VEC001101 INDEX
CUSTOMER
ROYAL GK PTE LTD
CONSISTENTS WITH OUR CONTINUAL PRODUCT IMPROVEMENT POLICY, GUASCOR POWER RESERVES THE RIGHT TO CHANGE ANY SPECIFICATION WITHOUT PRIOR NOTICE. 2
From To Cable Description
Amount Transformer Cell Room (C-
16) Incoming Switchgear Stall (C-19) RV-K 8x1,5 mm² Book exchange signals
125
Transformer 15 Incoming Switchgear Stall PLC
RV-K 4x6 mm²
(3F+N) Food 400Vac
57
Transformer 15 Incoming Switchgear Stall PLC
RV-K 3x(16x2,5
mm²)
Tap Alarm and
Controller
57
Transformer 16 Incoming Switchgear Stall PLC
RV-K 4x6 mm²
(3F+N) Food 400Vac
49
Transformer 16 Incoming Switchgear Stall PLC
RV-K 3x(16x2,5
mm²)
Tap Alarm and
Controller
49
T15 cell resistances Trafo Incoming Switchgear Stall (C-18) RV-K 2x4 mm² TI Signal Ground
12
T16 cell resistances Trafo Incoming Switchgear Stall (C-19) RV-K 2x4 mm² TI Signal Ground
12
T15 cell resistances Trafo Incoming Switchgear Stall PLC RV-K 8x1,5 mm² State disconnector
12
T16 cell resistances Trafo Incoming Switchgear Stall PLC RV-K 8x1,5 mm² State disconnector
12