Page 1: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

This work was performed under the auspices of the U.S.

Department of Energy by Lawrence Livermore National

Laboratory under Contract DE-AC52-07NA27344.

LLNL Data Center Consolidation Initiative

October 29, 2013

Anna Maria Bailey, PE

LLNL-PRES-457823

Page 2: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory

Mission

Continue to develop projects to

improve optimization of LLNL’s data

centers and reduce energy intensity

Developed in 2009

Achievements

• DOE FEMP 2009 Energy Award

• B453 LEED Gold Certified 2009

• B451 LEED Silver Certified 2011

• B112 SVLG Recognition 2012

— Collaboration

– Lawrence Berkeley Laboratory

– Romonet

– Syska Hennessey

• B112 Uptime Green IT Nominee 2013

• Patented HPC Modular Solutions 2013

Benchmarking

Computational fluid dynamics -CFD

LEED certifications

Consolidations

Liquid cooling advances

Innovative electrical and

mechanical distribution

Metering and sub-metering

Lighting control systems

Integrated control systems

Lower power usage effectiveness

(PUE)

Power management systems

Ma

ste

r P

lan

Co

re C

om

pe

ten

cie

s

2

Page 3: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory

Increase efficiencies and decrease redundant labor support

Reduce footprint, water usage and energy intensity site wide

Reduce facility and network infrastructure

Repurpose redundant equipment

Clear out spaces that are not properly utilized

Right size server maintenance contracts

Standardize IT support model to “One Lab”

Continue to virtualize services

Address FY 2012 DOE Sustainability Requirements

• Data Center: > 500SF and > 1 server

• Fully meter by FY15 all enduring data centers

• Obtain a LLNL site wide weighted average PUE of 1.4 by FY15

— Consolidation provides $40M cost avoidance to achieve metering

requirements

3

Page 4: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory 4

LLNL is one square mile

61 rooms site wide

29 facilities

High Performance Computing (HPC) Simulation

13 rooms

HPC Data Analytics

4 rooms

Enterprise Computing

44 rooms

HPC

Enterprise

Page 5: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory

Initial Condition - 61 rooms identified and surveyed

23 Enterprise rooms have been shutdown to date since survey began in 2011

• Consolidated into enduring facilities

• Virtualized various applications

• 26,210 SF total space shutdown (7,790 SF cold and dark and balanced

repurposed)

• $305,308 annual energy savings

• $43,547 annual maintenance savings on cold and dark rooms

• Over 500 servers consolidated into B-112 Enterprise Data Center

Remaining Rooms

• 13 HPC Simulation

• 4 HPC Data Analytics

• 21 Enterprise

— Nearly 4000 servers reside outside of B-112

— Classified and Unclassified

5

Page 6: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory 6

FY 12 – FY 15 Projects

13 Enterprise rooms to close

Repurpose 6 Enterprise rooms to secure network support and infrastructure

Repurpose B-115

HPC to Enterprise Computing

Page 7: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory 7

*Classified Center

FY12 – FY13 FY14

Data

Center

Building/

Room

Size

(Sq. Ft.)

Annual

Energy

Savings

Annual

Facility

Maintenance

Savings

Facility and

Operations

@165k

SQ.

< 800 =.5

800 /1500 = 1

>1500 = 1.5

# of Devices

to Consolidate

to

B-112

Data Center

Building/

Room

Size

(Sq.

Ft.)

Annual

Energy

Savings

Annual

Facility

Maintenance

Savings

Facility and

Operations

@165k

SQ.

< 800 =.5

800 /1500 = 1

>1500 = 1.5

# of Devices to

Consolidate to

B-112

23 RMs 26,210 305k 43k 3

(FTE) were

realigned

500 111/170 842 10k 1k 1 24

191/2210 600 15k 1k .5 14

543/1073 1742 15k 3k 1.5 40

132n/1470 743 10k 1k .5 91

Total 26,21

0

305k 43k 500 Total 3927 50k 6k 577K 169

Page 8: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory 8

*Classified Center

FY14 – FY15 FY16

Data

Center

Building/

Room

Size

(Sq.

Ft.)

Annual

Energy

Savings

Annual

Facility

Maintenance

Savings

Facility and

Operations

@165k

SQ.

< 800 =.5

800 /1500 = 1

>1500 = 1.5

# of Devices

to

Consolidate

to

B-112

Data

Center

Building/

Room

Size

(Sq.

Ft.)

Annual

Energy

Savings

Annual

Facility

Maintenance

Savings

Facility and

Operations

@165k

SQ.

< 800 =.5

800 /1500 = 1

>1500 = 1.5

# of Devices to

Consolidate to

B-112

121/1146 672 13k 2k .5 137 5 6240 56k 15k 5 2400

121/1347 2000 29k 3k 1.5

131/2280 1956 41k 3k 1.5 114 `

170/1008* 973 20k 2k 1 78

111/178* 537 11k 1k .5 5

132/2506* 2204 48k 5k 1.5 15

Total 8342 162k 16k 1M 349 Total

6240 56k 15k 825k 2400

Page 9: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory

Standardize: Reduce labor costs resulting from fewer facilities and configurations

Virtualize: Reduce costs for hardware, space and utilities

Software: Reduce licensing costs for unused licenses

Hardware: Better accountability of assets

Security: Timely system patches

Best Practices from IT Community

• Reduce costs for paid vendor technical support

• Reduce costs for training, especially with travel

Integrated Systems Management

— Reduce personnel costs

— Lower utility costs

Vendor Financing (Managed Lifecycle and Leasing)

— Conserves expenditures by spreading purchase cost over time

9

Survey

Measure

Improve

Page 10: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory

Savings to Date - $348K

Projected FY14/FY15 Savings - $1.8M

Projected FY16- FY18 Savings - $896k

$600k of additional cost saving is projected through maintenance (hardware/network) contract consolidate and 30% of the physical servers being virtualized

Upon completion, approximately 45,000 SF will be shutdown or repurposed

Total Savings $3.6M

10

Page 11: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory

• B-115

— HPC has outgrown facility and will

consolidate to other Livermore

Computing facilities

— Identified as enduring for Enterprise

Computing (Backup unclassified

and primary classified) until other

facilities can be constructed

— FY13 - West and east rooms

• Repurposing equipment from

closed data center rooms

— FY14 Remainder of consolidation

• Study underway

11

Page 12: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory

Future HPC generation systems require

major facility innovation

• Liquid cooling advances

• Efficient electrical distribution

• Robust structural solutions

25 Year Master Plan

• HPC Facility Gap Analysis

— Systems spread across facilities that

range from 9 to 60 years old

• Site-wide consolidations

• Shared resources with other Laboratories

• Sustainable HPC modular solutions

Page 13: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory

Page 14: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory

Developed a process to access probability of siting future extreme scale systems to

meet mission by system class. Facilities were evaluated for modifications required.

Ranked building with system class versus required infrastructure modifications:

Structural (S), Electrical (E) and Mechanical (M)

Page 15: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory

Utilize existing facilities based on their enduring capabilities

Demolish or repurpose aging facilities that cannot meet mission

Build new facilities to meet mission

— Focus on sustainability and energy efficiency through flexibility

— Scale footprint with the computational technology

— Deploy innovative HPC facility design methodologies

Page 16: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory

• Clear, unencumbered space

• Scalable mechanical and electrical infrastructure

• Advance liquid cooling options

• Deploy free cooling

• Cool roof

• Accommodate increased weights

• Decrease space impediments

Page 17: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory

FUTURE HPC

UNCLASSIFIED

FACILITY 2015 FUTURE HPC

SRD FACILITY

2018

FUTURE HPC HIGH

SIDE DATA

ANALYTICS AND

ENTERPRISE

FACILITY 2020

112

Page 18: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory

Benchmarking

Computational fluid dynamics -CFD

LEED certifications

Consolidations

Liquid cooling advances

Innovative electrical and

mechanical distribution

Metering and sub-metering

Lighting control systems

Integrated control systems

Lower power usage effectiveness

(PUE)

Power management systems

Ma

ste

r P

lan

Co

re C

om

pe

ten

cie

s

18

Laboratory “Mission” comes first

Understand the obstacles and challenges

Develop a strategic vision

Obtain senior management support

Provide continual leadership

Remain patient

Stay focused

Continue to survey, measure and improve

Page 19: LLNL Data Center Consolidation Initiative · LLNL Data Center Consolidation Initiative October 29, 2013 Anna Maria Bailey, PE LLNL-PRES-457823 . Lawrence Livermore National Laboratory

Lawrence Livermore National Laboratory

Anna Maria Bailey

Lawrence Livermore National Laboratory

7000 East Ave PO Box 808 L-554

Livermore, CA 94550

Phone - (925) 423-1288 / Email – [email protected]

Andy Ashbaugh

Lawrence Livermore National Laboratory

7000 East Ave PO Box 808 L-720