MAC-D R410A SeriesAir-cooledModular Chiller/Heat pumpModel: MAC210D5-MAC1680D5MAC230D5-MAC1840D5MAC210DR5-MAC1680DR5MAC230DR5-MAC1840DR5http://www.hvacvn.comhttp;//www.savame.comTRANSCRIPT
Catalogue MAC-D-2013 (50Hz)
MAC-D R410A Series Air-cooledModular Chiller/Heat pump
Model: MAC210D5-MAC1680D5MAC230D5-MAC1840D5MAC210DR5-MAC1680DR5MAC230DR5-MAC1840DR5
60kW-536kWRefrigerant:Cooling Capacity:
64kW-528kW Heating Capacity:
R410A
Air-cooled modular chiller/heat pump
2
Overview
McQuay Air Conditioning (Shenzhen) Co., Ltd. of McQuay China Asian Manufacturing Base of McQuay Air-cooled Heat Pump
European Manufacturing Base of McQuay Air-cooled Heat Pump in Cecchina Italy
McQuay Cecchina Factory, ItalyMcQuay Aubum Factory, USA
Nomenclature
Test CNAS L0778
Quality Management System Certification
Environment Management System Certification
XK06-015-00378
The test center is certified by China National Accreditation
Service for Conformity Assessment
China National Industrial Product
Manufacture License
Based on the successful McQuay air-cooled modular chiller/heat pump R22 series, McQuay MAC-D R410A series is a new generation of air-cooled chillers/heat pumps. They ideally combine the advanced and mature chiller technology with new type environment-friendly refrigerant. In addition, this series features outstanding performance, high capacity, low sound level, easy installation, and flexible system management, taking the lead in the global market.
MAC 210 D R M 5 - F BA E
Export sales code Detailed description Power supply F: 380V/3Ph/50Hz;
Refrigerant code 5: R410A Code for modular connected units M: master unit/single unit;S: slave unit;
Function type R: heat pump; Omitted for cooling-only units. Design series Cooling capacity code, 21HP. McQuay air-cooled modular chiller
Qualityassurance
ISO 9001Certificate No. : 9601019
ISO 14001Certificate No. : EMS 80362
BS - OHSAS 18001Certificate No. : 7644
Air-cooled modular chiller/heat pump
2
Overview
McQuay Air Conditioning (Shenzhen) Co., Ltd. of McQuay China Asian Manufacturing Base of McQuay Air-cooled Heat Pump
European Manufacturing Base of McQuay Air-cooled Heat Pump in Cecchina Italy
McQuay Cecchina Factory, ItalyMcQuay Aubum Factory, USA
Nomenclature
Test CNAS L0778
Quality Management System Certification
Environment Management System Certification
XK06-015-00378
The test center is certified by China National Accreditation
Service for Conformity Assessment
China National Industrial Product
Manufacture License
Based on the successful McQuay air-cooled modular chiller/heat pump R22 series, McQuay MAC-D R410A series is a new generation of air-cooled chillers/heat pumps. They ideally combine the advanced and mature chiller technology with new type environment-friendly refrigerant. In addition, this series features outstanding performance, high capacity, low sound level, easy installation, and flexible system management, taking the lead in the global market.
MAC 210 D R M 5 - F BA E
Export sales code Detailed description Power supply F: 380V/3Ph/50Hz;
Refrigerant code 5: R410A Code for modular connected units M: master unit/single unit;S: slave unit;
Function type R: heat pump; Omitted for cooling-only units. Design series Cooling capacity code, 21HP. McQuay air-cooled modular chiller
Qualityassurance
ISO 9001Certificate No. : 9601019
ISO 14001Certificate No. : EMS 80362
BS - OHSAS 18001Certificate No. : 7644
Air-cooled modular chiller/heat pump
3
R410A - no chlorineSunshine (ultraviolet B)
Ozone (O3)
Stra
tosp
here
(ozo
ne d
ense
are
a)
Trop
osph
ere
CFC leakage
Earth
Low sound level
Environment-friendly Refrigerant
Main Features
McQuay is committed to protecting the global ecosystem and has developed air-cooled chiller/heat pump with R410A, a new type of environment-friendly refrigerant. Without chlorine, the environment-friendly R410A causes no harm to the ozonosphere (ODP=0).
Thanks to the newly designed spiral blades, the outdoor units feature smooth air flow, significantly reducing the turbulence and lowering the air flow sound level. Unique compressor sound-insulation design and fully hermetic volute compressor minimizes the operation noise. Moreover, unique Night Mode brings down nightly noise greatly and ensures you a sound sleep.
Cooling tower Boiler Cooling pump
Easy Installation MAC R410 series is designed to best facilitate user installation. The refrigerant system is made hermetic in the factory. Customers do not need to connect any copper pipe or refill refrigerant or invest more money for complex water systems.
New type spiral blade Semi-M shaped heat exchanger
Isolation-designed compressor
Air-cooled modular chiller/heat pump
4
Compact Size
Multi-grade Modulation
Main Features
Reliable Operation
MAC R410 series features 2-grade modulation which can be transformed to multi-grade modulations in modular combinations. With operation grades controlled electronically, the unit exerts less shock to the power grid and saves more energy.
Moreover, MAC R410 series features compact size. Its dimensions and weight are significantly reduced. MAC R410 can be lifted without large lifting tools and located on the roof, balcony or any possible outdoor space.
MAC R410 series adapts modular design and one by one start, reducing the impact upon the grid when starting. All units have undergone strict and long-term test, ensuring reliable operation even under extreme hot/cold conditions. Units themselves, moreover, have multiple protections. The security of units is maximally guaranteed.
Outstanding Performance MAC R410 series features leading-edge scroll technology and name-brand accessories which are strictly tested for high compatibility and reliability. Equipped with efficient scroll compressors and precise electronic expansion valves, these units feature high EER and COP, especially at partial load.
Air-cooled modular chiller/heat pump
4
Compact Size
Multi-grade Modulation
Main Features
Reliable Operation
MAC R410 series features 2-grade modulation which can be transformed to multi-grade modulations in modular combinations. With operation grades controlled electronically, the unit exerts less shock to the power grid and saves more energy.
Moreover, MAC R410 series features compact size. Its dimensions and weight are significantly reduced. MAC R410 can be lifted without large lifting tools and located on the roof, balcony or any possible outdoor space.
MAC R410 series adapts modular design and one by one start, reducing the impact upon the grid when starting. All units have undergone strict and long-term test, ensuring reliable operation even under extreme hot/cold conditions. Units themselves, moreover, have multiple protections. The security of units is maximally guaranteed.
Outstanding Performance MAC R410 series features leading-edge scroll technology and name-brand accessories which are strictly tested for high compatibility and reliability. Equipped with efficient scroll compressors and precise electronic expansion valves, these units feature high EER and COP, especially at partial load.
Air-cooled modular chiller/heat pump
5
Control
Intelligent Control System
Basic Operating Mode
Parameter Setting
Fault alarm and protection
Parameter Display Other functions
Defrost Mode
MAC-D features user-friendly intelligent control system. Micro chip and large-scaled LCD display are employed to make the control swift and easy. ■ Group control: One single controller can control a group made up by one master unit and
maximum 15 slave units.■ BMS: MAC-D provides interfaces for BMS. One serial port can support maximum 31
support one master unit and maximum 15 slave units.
■ Cooling ■ Heating
■ 13 protections and fault alam functions ■ Indoor controller lock
■ Auto defrost ■ Mannual defrost
■ Real time setting ■ Weekly timing on/off (one on/off per day)■ Cooling water inlet temperature ■ Heating water inlet temperature ■ Anti-freezing/defrost temperature setting ■ Defrost point A/B temperature setting
■ Running status display ■ Setted inlet temperature ■ Actual inlet temperature ■ Timing point ■ Anti-freezing/defrost temperature
■ Error log inquiry ■ Average compressor worn time ■ Remote on/off ■ Water system two-way valve control ■ Auxiliary electric heating
Memory function■ Backup battery for realtime clock■ Customized parameters
preservation after power failure
Note:■ The length of communication wire between the master unit and the wired controller
is 40m. The length of communication wire attached to the slave unit is 5m. ■ The main board of the unit provides an interface for remote control. But remote
controllers are not provided and should be installed on site.
gateway and one gateway can
Air-cooled modular chiller/heat pump
6
Specification
Note:
outdoor ambient temperature 35°C. ;C°54 erutarepmet retaw gnivael ;wofl retaw detar :yticapac gnitaeh lanimon rof snoitidnoc gnikroW
outdoor dry/web bulb temperature 7°C/6°C.
the connecting pipes should meet certain standards.
contact Shenzhen McQuay for support.
Model MAC210D5 MAC210DR5 MAC230D5 MAC230DR5
Nominal cooling capacity kW 60 60 65 68MBtu/h 205 205 222 229
Nominal heating capacity kW -- 64 -- 66MBtu/h -- 218 -- 225
Cooling input power kW 18.8 19.8 19.2 21.0Cooling operation current A 35.5 37.2 36.9 36.8
Heating input power kW -- 20.5 -- 20Heating operation current A -- 38.2 -- 36.2
Power supply 380V/3Ph/50HzEER 10.9 10.3 11.5 11.3COP -- 3.0 -- 3.38
Compressor Type Hermetic scroll compressorQuantity Unit 2
Fan Type New type axial fan
Quantity Unit 2H/L power input kW 1.15x2 / 0.45x2
Heat exchanger
Type High efficiency BPHE
Water flow (cooling)
m3/h 10.3 10.3 11.2 11.5l/s 2.86 2.86 3.11 3.19
gpm 45.4 45.4 49.3 50.6
Water flow (heating)
m3/h -- 11
44
-- 11.4l/s -- 3.06 -- 3.16
gpm -- 48.4 -- 50.237.3Unit WPD kPa 38
Water pipe connection size DN502"
Unit dimensions
(Length×Width×Height)
mm 1990×840×1840inch 78.3×33.1×72.4
Packing dimensions
(Length×Width×Height)
mm 2010×890×2010inch 79.1×35×79.1
Unit weight kg 520 540 520 515lb 1146 1190 1146 1133
Btu\h\W
Air-cooled modular chiller/heat pump
7
Operating Limit
Dimensions
Unit: mm
Cooling mode Heating mode
Temperature range Temperature range
Outlet water temp (°C) Outlet water temp (°C)
Am
bient temp °C
Am
bient temp °C
Mounting hole of anchor bolt 14-14x20
Magnified view of mounting hole of anchor bolt 14x20
Water inlet Rc2
Water outlet Rc2
MAC210D/DR/230D MAC230DRA 171 165B 369 390
Air-cooled modular chiller/heat pump
8
Installation Illustration
Note: 1. The groundwork should be concrete or V-iron structures, and must be strong enough to bear the operating
weight of the unit. 2. Each unit must be fixed by four M12 bolts. 3. A 20mm-thick rubber cushion should be added to the base as a bumper. 4. Applicable model: MAC210DM5/MAC210DS5/
MAC210DRM5/MAC210DRS5/MAC230DM5/ MAC230DS5/MAC230DRM5/MAC230DRS5
Unit: mm
Unit: mm
Ventilation space above the unit
>3,000 mm
Unit height
Distan
ce be
twee
n
the un
it and
the w
all:
>1,80
0 mm
Front-to-back distance between two units: > 400 mm
Distan
ce be
twee
n the
unit
and t
he w
all: >
1,800
mm
Distance between the unit
and the wall: >1,800 mm
Distance between the unit and the
wall: >1,800 mmLeft-to-right distance
between two units: > 1,500 mm Left-to-right distance
between two units: > 1,500 mm
Installation Space
Front-to-back distance between two units: > 400 mm
Front-to-back distance between two units: > 400 mm
Front-to-back distance between two units: > 400 mm
Air-cooled modular chiller/heat pump
9
Water System
Air-cooled modular chiller/heat pump
10
Water System
Legends for the Water System Illustration:
Air-cooled modular chiller/heat pump
11
Requirements on Water Supply
A relief valve must be installed for the water supply system.
A suitable water drainage valve must be installed at the lowest point in the water system.
frequent startup in the case of low load.
due to thermal expansion and contraction. A bypass must be installed for the water circuit. The water system must be fully cleaned before water infusion and system startup.
Water Quality RequirementsItem Requirement pH Between 7 and 9 Suspended matter Suspended material concentration <15mg / l DH CaO content <200mg / l Solid impurity Solid impurities size <1mm Mineralization Open circle: water mineralization <350mg / l Corrosivity Cl-, CO2 and other corrosive substances <100mg / l
Fan Coil Unit
Ceiling Concealed Unit MCW-C/F/H Model MCW200-1200C/F/H
Air Flow 180 -2040m3/h ESP 0,30,60,80Pa
Cooling Capacity 2130 -10700W
An air vent valve must be installed at the highest point in the water system.
insulated
in accessory kit
Air-cooled modular chiller/heat pump
12
Single SkinMHW
Model MHW015A-MHW050A Air Flow 1500 - 5000m3/h
ESP 70 - 150Pa Cooling Capacity 6000 - 87000W
Single SkinMSW
Model MSW020H-MSW150H MSW040V-MSW250V
Air Flow 2000 - 25000m3/h ESP 80 - 300Pa
Cooling Capacity 12000 - 450000W
Double SkinMDW
Model MDW020H-MSW250H MDW040V-MSW250V
Air Flow 2000 - 25000m3/h ESP 80 - 300Pa
Cooling Capacity 12000 - 450000W
Double SkinMDM
Model MDM0304-MDM1826 Air Flow 2000 - 100000m3/h
ESP 80 - 1000Pa Cooling Capacity 14000 -700000W
Air Handling Unit
Air-cooled modular chiller/heat pump
12
Single SkinMHW
Model MHW015A-MHW050A Air Flow 1500 - 5000m3/h
ESP 70 - 150Pa Cooling Capacity 6000 - 87000W
Single SkinMSW
Model MSW020H-MSW150H MSW040V-MSW250V
Air Flow 2000 - 25000m3/h ESP 80 - 300Pa
Cooling Capacity 12000 - 450000W
Double SkinMDW
Model MDW020H-MSW250H MDW040V-MSW250V
Air Flow 2000 - 25000m3/h ESP 80 - 300Pa
Cooling Capacity 12000 - 450000W
Double SkinMDM
Model MDM0304-MDM1826 Air Flow 2000 - 100000m3/h
ESP 80 - 1000Pa Cooling Capacity 14000 -700000W
Air Handling Unit
While utmost care is taken in ensuring that all details in the publication are correct at the time of going to press, we are constantly striving for improvement and therefore reserve the right to alter model specifications and equipment without notice.Details of specifications and equipment are also subject to change to suit local conditions and requirements and not all models are available in every market.