Page 1: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

Copyright 2008 Force10 Networks, Inc

Managing Data Center Power & Cooling

Debbie Montano

[email protected]

Page 2: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

2 Copyright 2008 Force10 Networks, Inc

Agenda

 Data Center Power Crunch  Strategies for Reducing Power Across IT

 Power Efficiencies in Networking Today and Moving Forward

 Customer Case Studies

 Q&A

Page 3: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

3 Copyright 2008 Force10 Networks, Inc

The Greening of The Data Center

  Until recently power efficiency in the Data Center has not been paramount in IT rollouts

  This is now changing and is being driven by: –  Rising power costs –  Blackouts/Brownouts and capacity planning –  Limits to grid/sub-station scaling (No more power available) –  Politic pressures and “green” legislation to drive greater data

center efficiencies

If we as an industry don’t lead the process we will be dragged

to an unacceptable position

Page 4: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

4 Copyright 2008 Force10 Networks, Inc

Energy & Power

  Energy –  Joule (J) –  Watt-Hour (Whr) –  Kilowatt-Hour (KWhr) –  British Thermal Unit (BTU)

  Power – rate of use of energy –  Joule/second –  Watt == Joule/second –  Kilowatt = 1000 Watts –  BTU / hour –  1 Watt == 3.413 BTU/hr

–  Ton (usually = 12,000 BTU/hr)

Analogy:   Gallons of water

  Gallons/hour = rate of use of water

Page 5: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

5 Copyright 2008 Force10 Networks, Inc

63% of 369 IT professionals said that running out of space or power in their data centers had already occurred

Data Center Crisis: Power/Cooling

Data Center Power Density Went from 2.1 kw/Rack in 1992 to 14 kw/Rack in 2006

3 Year Costs of Power and Cooling, Roughly Equal to Initial Capital Equipment Cost of Data Center

Moore’s Law: More Transistors… More MIPs… More Watts… More BTUs

1 watt of power consumed requires 3.413 BTU/hour of cooling to remove the associated heat

Page 6: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

6 Copyright 2008 Force10 Networks, Inc

Growing Power Density

Page 7: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

7 Copyright 2008 Force10 Networks, Inc

Growing Power Density

Culprit or Savior?

Brave New World of >15 KW

per sq foot

Page 8: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

8 Copyright 2008 Force10 Networks, Inc

Force10 Customers Data Center Power Considerations

Page 9: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

9 Copyright 2008 Force10 Networks, Inc

Force10 Customers Data Center Power Considerations

1. Prime mover in budgets 2. Network 10% of power budget…Biggest relief

by increasing density and utilization 3. From planning to build >12 months

Page 10: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

10 Copyright 2008 Force10 Networks, Inc

Agenda

 Data Center Power Crunch  Strategies for Reducing Power Across IT  Power Efficiencies in Networking Today and

Moving Forward  Customer Case Studies

 Q&A

Page 11: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

11 Copyright 2008 Force10 Networks, Inc

IT Components Data Centre Grid

The Big Picture – The Watt Walkthrough

Total system efficiency comprises three main elements- the Grid, the Data Centre and the IT Components. Each element has its own efficiency factor- multiplied together for 100 watts of power generated, the CPU receives only 12 watts

0% 10% 20% 30% 40% 50% 60% 70% 80% 90%

100%

Page 12: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

12 Copyright 2008 Force10 Networks, Inc

IT Components Data Centre Grid

A Series of Conversion Efficiencies

Fuel Source

Carbon Conversion

factor

Renewables

Server Utilisation

Operating System

Efficiency

Software Optimization

Page 13: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

13 Copyright 2008 Force10 Networks, Inc

IT Components Data Centre Grid

A Series of Conversion Efficiencies

Fuel Source

Carbon Conversion

factor

Renewables

Server Utilisation

Operating System

Efficiency

Software Optimization

Carbon Efficiency

Page 14: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

14 Copyright 2008 Force10 Networks, Inc

IT Components Data Centre Grid

A Series of Conversion Efficiencies

Fuel Source

Carbon Conversion

factor

Renewables

Server Utilisation

Operating System

Efficiency

Software Optimization

Carbon Efficiency

Grid Efficiency

Page 15: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

15 Copyright 2008 Force10 Networks, Inc

IT Components Data Centre Grid

A Series of Conversion Efficiencies

Fuel Source

Carbon Conversion

factor

Renewables

Server Utilisation

Operating System

Efficiency

Software Optimization

Carbon Efficiency

Grid Efficiency

Data Centre Efficiency

Page 16: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

16 Copyright 2008 Force10 Networks, Inc

IT Components Data Centre Grid

A Series of Conversion Efficiencies

Fuel Source

Carbon Conversion

factor

Renewables

Server Utilisation

Operating System

Efficiency

Software Optimization

Carbon Efficiency

Grid Efficiency

IT Efficiency

Data Centre Efficiency

Page 17: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

17 Copyright 2008 Force10 Networks, Inc

Server Utilisation

Operating System

Efficiency

Software Optimization

IT Components Data Centre Grid

A Series of Conversion Efficiencies

Fuel Source

Carbon Conversion

factor

Renewables

Carbon Efficiency

Grid Efficiency

IT Efficiency

Data Centre Efficiency

OS/Software Efficiency

Page 18: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

18 Copyright 2008 Force10 Networks, Inc

Data Center Best Practices

 Majority of efficiency improvement from rectifying inefficient cooling (60% of your wattage work set)

 Hot/Cold Row Cooling

 Minimize leakage/blocking/bypasses

Page 19: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

19 Copyright 2008 Force10 Networks, Inc

Tips

 Stay diligent about hot and cool aisle flow  Ruthless air flow… watch out for cabling,

other obstructions.  Blank your racks as well as your slots

 How cool? --- the mid-point of recommended range is 74 degrees and 50% humidity1

 Get your tiles rights… perforated for cold, solid for hot

 Read your electric bill. 1. Source: American Society of Heating, Refrigeration and Air Conditioning Engineers [ASHRAE] TC9.9

Page 20: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

20 Copyright 2008 Force10 Networks, Inc

IT Comprehensive Approach

 Minimize power consumption and maximize power efficiency at every level within the infrastructure

CPU Chips

Power Supplies

Servers

Storage Devices

Cabling

Networking

Page 21: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

21 Copyright 2008 Force10 Networks, Inc

CPU Chips

 Power efficient architectures – A dual core processor can deliver >60% higher

performance than a single core processor dissipating the same power

–  e.g. integrated memory controllers – Application-specific multi-core chip architectures include

cluster computing, transaction processing, and multi-tasking.

 Processor Power Management with Dynamic Clock Frequency and Voltage Scaling (CFVS)

 Future: Transistors with Lower Leakage Current –  replace the silicon dioxide gate dielectric with hafnium-

based high-k material

Page 22: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

22 Copyright 2008 Force10 Networks, Inc

Clock Frequency and Voltage Scaling

  Dynamically adjusting CPU performance (via clock rate and voltage) to match the workload

  Uses the operating system’s power management utility via industry-standard Advanced Configuration and Power Interface (ACPI) calls

  75% power savings at idle and 40-70% power savings for utilization in the 20-80% range

Pow

er (w

atts

)

Without CFVS

CPU Utilization (%) 0% Idle

100%

Wor

kloa

d pe

r wat

t

Without CFVS

With CFVS

CPU Utilization (%) 0% Idle

100%

Page 23: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

23 Copyright 2008 Force10 Networks, Inc

Servers

  Blade Servers: –  Chassis “sharing” can reduce

power consumption by 20-50% – Larger chassis’ are more

efficient (>80%) – Blade servers inspired by

modular switch/routers – Even esoteric edge

improvements scale up   Server Virtualization:

–  Applications consolidated on a smaller number of servers, eliminating power consumption by many low utilization servers dedicated to single applications

–  Potentially #1 improvement (5-20x “compression”)

VM Monitor/Hypervisor

Virtual Machine 1

Virtual Machine N

Guest OS 1 Guest OS N

Physical Machine

Application 1

Application N

Page 24: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

24 Copyright 2008 Force10 Networks, Inc

Storage

 Power consumption in storage devices is primarily by spindle motors and is largely independent of the capacity of the disk –  The bigger the disk, the better

 Maximize TBytes/watt to the highest capacity disks – Must keep I/O characteristics compatible with the

applications being served

 Unified Ethernet storage virtualization technologies and large-scale tiered storage maximize power efficiency by minimizing storage over-provisioning

Page 25: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

25 Copyright 2008 Force10 Networks, Inc

Agenda

 Data Center Power Crunch  Strategies for Reducing Power Across IT

 Power Efficiencies in Networking Today and Moving Forward

 Customer Case Studies

 Q&A

Page 26: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

26 Copyright 2008 Force10 Networks, Inc

Switch/Routers

  Little difference in Gbps/watt for fixed configuration and stackable switches

  Considerable differences for modular switch/routers due to backplane technology and box-level densities –  Heavy copper traces reduce

backplane resistance and wasted power consumption

–  Force10 E-Series uses patented 4 layer, 4 ounce copper backplane that has power efficiency of 4.5 Gbps/watt (= backplane capacity/ power consumption)

–  10-20x less resistance

Page 27: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

27 Copyright 2008 Force10 Networks, Inc

Unified Data Center Fabric

  Ethernet can provide LAN connectivity, storage networking, and cluster interconnect across the data center

  With a unified fabric, power is conserved –  No additional sets of switches for specialized fabrics –  Higher utilization on existing switches –  Only one network adapter per server –  Efficient cable management

Servers SAN or

Storage Cluster

Cluster IPC

LAN

Disc Arrays

NAS

Users

Page 28: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

28 Copyright 2008 Force10 Networks, Inc

SOA Applications

Services

Common Pool of Computing Resources

Traditional Applications

Cluster Applications

Infrastructure Virtualization

Enterprise Service Bus

Workload Management

Cluster Middleware

Servers Storage

Firewalls/ Load Balancers

Switches

Servers Storage

Firewalls/ Load Balancers

Switches

PODs

Virtualization-Ready Networking

  Applications draw on a shared pool of resources

  No resources dedicated to a single application – higher utilization

  Workloads of various applications peak at different times in the business cycle

  Shared resource model: Do the same job with far fewer resources

Single, most effective way to manage and scale power is to increase server/storage/network utilization

Page 29: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

29 Copyright 2008 Force10 Networks, Inc

System configured with full switch fabric, route processor, and power redundancy and 672 line-rate GbE 1000 Base-T ports

Slot Watts

Chassis (common + SFMs) 1,055

0 48-port 1000base-T (LR) 290

1 48-port 1000base-T (LR) 290

2 48-port 1000base-T (LR) 290

3 48-port 1000base-T (LR) 290

4 48-port 1000base-T (LR) 290

5 48-port 1000base-T (LR) 290

6 48-port 1000base-T (LR) 290

RP0 RPM-EF 125

RP1 RPM-EF 125

7 48-port 1000base-T (LR) 290

8 48-port 1000base-T (LR) 290

9 48-port 1000base-T (LR) 290

10 48-port 1000base-T (LR) 290

11 48-port 1000base-T (LR) 290

12 48-port 1000base-T (LR) 290

13 48-port 1000base-T (LR) 290

Total Power 5,365

Power Efficiency in Watts/Gbps 8 (=5365/672) DC Current @ 40V 134

E1200 System Power Efficiency

Page 30: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

30 Copyright 2008 Force10 Networks, Inc

Maximizing Network Power Efficiency

  In the Core and Data Center – E-Series resilient, scalable,

high density switches –  collapsed Distribution/

Access Tier--2-Tier switching –  elimination of numerous low

density switches

E-Series in the Core

Source: Enterprise Rental Car

Power Saved on 270 Node DC

2 Force10 E1200s

= 10,600 watts

5 Catalysts

6000s =

20,000 watts

Firewall/LB

Servers NAS/SCSI

Layer 2/3 Routers & Switches

Page 31: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

31 Copyright 2008 Force10 Networks, Inc

Maximizing Network Power Efficiency

  In the Wiring Closet – C-Series resilient,

scalable, high density wiring closet switches

– Collapsed Distribution/ Access Tier--2-Tier switching

– Eliminate numerous low density switches

C-Series in the Core

Core

Wiring Closet

Vertical Risers

Distribution/ Access Switch

Comparison – Large Campus

3

C-Series =

9,400 watts

8 Catalyst 4500s

= 22,000 watts

Page 32: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

32 Copyright 2008 Force10 Networks, Inc

Lowest power consumption of any switch on the planet 480 Gbps switching on 125 watts!!!

Introducing the Force10 S2410 Highest Density, Lowest Latency and Price

  Industry-leading density and flexibility –  24 line-rate 10 GbE ports

in 1 RU –  Full function switch –  XFP or CX4 interfaces

  Drives down 10 GbE port prices to spur adoption –  List pricing starting at $24,000 (CX4) –  Reduces 10 GbE switching latency

to Infiniband levels –  300 nanoseconds

S2410 Fiber and CX4 Versions

Page 33: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

33 Copyright 2008 Force10 Networks, Inc

Power Efficiency Going Forward

 Becoming a key metric for product comparison – Servers: Application workload/watt (e.g., Mflops/watt) – Storage: GBytes/watt – Networking: Gbps/watt

  IEEE Energy Efficient Ethernet working group

 EPA considering Energy Star Rating for Data Center equipment, including switch/routers

 Force10 member of TheGreenGrid.org and can provide updated power calculators to model power and cooling in TCO calculations

Page 34: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

34 Copyright 2008 Force10 Networks, Inc

10 GbE

1 GbE

Timing of Application Needs

Date

Rat

e M

b/s

1995 2000 2005 2010 2015 2020

1,000,000

100,000 100 GbE 40 GbE

10,000

1,000

100

Source: IEEE 802.3 HSSG

Page 35: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

35 Copyright 2008 Force10 Networks, Inc

Agenda

 Data Center Power Crunch  Strategies for Reducing Power Across IT

 Power Efficiencies in Networking Today and Moving Forward

 Customer Case Studies  Q&A

Page 36: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

36 Copyright 2008 Force10 Networks, Inc

Enterprise Rental Car

Remove Wasteful Interconnects

CAP-EX   75% lower up front cost,

> $1 million savings   One device, versus five   28 less line cards

OP-EX   81% less power   81% less cooling needed

(air conditioning)   80% less rack space

48 x 10 GbE Interconnects

270 line-rate nodes 270 line-rate nodes

4 x 10 GbE uplinks

90 90 90

4 x 10 GbE uplinks OP-EX

BTU / hr 12,812

Power 3,760 W

OP-EX

BTU / hr 67,960

Power 19,920 W

Page 37: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

37 Copyright 2008 Force10 Networks, Inc

MareNostrum–Barcelona Super Computing Centre

  Build #1 super computing center in Europe to focus on computational, earth and life sciences

  Location -TorreGironaChapel   153 sqm with 2,560 GbE nodes - 94.21 tera flops   Non-blocking supercomputing   Create a scalable, flexible environment

  Raised floor to accommodate high flow reqs   Cooling water storage tanks   IBM blue gene and 1350 blade servers drove

massive Gigabit densities

Solution

Client Requirements

Benefits   High density Ethernet (8 watts/gbe)   Supports 21KW/rack (400 W/sq ft) of cooling   Flexibility for the future –supercomputing

performance upgrade underway   World’s most beautiful supercomputing center

Page 38: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

38 Copyright 2008 Force10 Networks, Inc

Yahoo! Case Study

 Bandwidth doubling every year  Expects 10 GbE server scale in 1-3 yrs.   20 Gigabit bandwidth in metro transport  Explicitly dual-vendor – interoperability

a must

  Running 80 KM WDM optics   “POD” design with 300+ GbE nodes   Extreme Gigabit densities

  Power footprint of 2.5 KW per 300 nodes   1/3 the cooling budget of previous switch

and over $2.5M in power & cooling savings in 3 years

  Substantial (4-8x) saving over SONET

Solution

Client Requirements

Benefits

Page 39: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

39 Copyright 2008 Force10 Networks, Inc

Coming Soon…

Page 40: Managing Data Center Power & Cooling · 2008-04-22 · The Greening of The Data Center Until recently power efficiency in the Data Center has not been paramount in IT rollouts This

40 Copyright 2008 Force10 Networks, Inc

Q & A Force10 Confidential. Do not Distribute.