550 SOUTH HOPE STREET, SUITE 1700 • LOS ANGELES, CALIFORNIA 90071 • TEL 213-362-0707 • FAX 213-688-3018 • WWW.NYASE.COM LOS ANGELES • SAN FRANCISCO • IRVINE March 30, 2016 Ms. Joanne Williams Senior Leasing Specialist UCLA Real Estate 10920 Wilshire Boulevard, Suite 810 Los Angeles, CA 90024 Re: University of California Seismic Rating for 261 South Figueroa, Los Angeles Dear Joanne: Nabih Youssef Associates (NYA) have performed an Independent Review of the 261 Building in the Figueroa Courtyard located at 261 South Figueroa Street in Los Angeles. The review consisted of a site visit to observe the existing condition of the exposed structural elements, identification of potential falling hazards that pose a significant life or safety risk to occupants, a review of structural drawings and an ASCE 41-13 Tier 1 and deficiency only Tier 2 evaluation. Description: The 261 Building is 4-stories tall, irregular-shaped in-plan with re-entrant corners and large openings in the floor diaphragms, and vertically irregular with setbacks. The building is clad with 4” thick pre-cast concrete panel veneers. The building was constructed in 1979 and designed to the 1976 edition of the Uniform Building Code. The roof and typical floors are constructed of post-tensioned concrete slabs spanning to reinforced concrete beams and columns with drop panels. The concrete columns are continuous to the foundation. The foundation system consists of reinforced concrete spread footings. The lateral-force-resisting system consists of the post-tensioned concrete roof and floor slabs acting as structural diaphragms to transfer seismic inertial forces to the distributed reinforced concrete shear walls. Pedestrian bridges provide access to adjacent office buildings on the campus. A 2 inch gap separates the bridges from the building. The building was subjected to moderate ground motion during the 1994 Northridge Earthquake. Recorded ground motion near the site indicates peak ground acceleration of approximately 0.2g. We are not aware of any reports of structural damage to the building resulting from the earthquake. The structures on the campus were visually inspected in 2009. Cosmetic hairline cracks in the pre-cast panels, and horizontal and diagonal cracks in concrete shear walls in the other buildings were observed. The cracks in the concrete shear walls were repaired with injected epoxy. No significant cracks were observed in the shear walls of the 261 Building. Observation: A site visit was performed by Owen Hata of NYA on March 17, 2016, to observe the condition and characteristics of the building. Observations were limited to visible areas of the structure. The building structure appeared to be in general conformance with the original structural drawings, no significant structural alteration was observed. The building generally appeared to be in good condition and there were no obvious signs of structural distress. Minor hairline cracks were observed in the post-tensioned

Upload: others

Post on 12-Jun-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

550 SOUTH HOPE STREET, SUITE 1700 • LOS ANGELES, CALIFORNIA 90071 • TEL 213-362-0707 • FAX 213-688-3018 • WWW.NYASE.COM

L O S A N G E L E S • S A N F R A N C I S C O • I R V I N E

March 30, 2016 Ms. Joanne Williams Senior Leasing Specialist UCLA Real Estate 10920 Wilshire Boulevard, Suite 810 Los Angeles, CA 90024 Re: University of California Seismic Rating for 261 South Figueroa, Los Angeles Dear Joanne:

Nabih Youssef Associates (NYA) have performed an Independent Review of the 261 Building in the Figueroa Courtyard located at 261 South Figueroa Street in Los Angeles. The review consisted of a site visit to observe the existing condition of the exposed structural elements, identification of potential falling hazards that pose a significant life or safety risk to occupants, a review of structural drawings and an ASCE 41-13 Tier 1 and deficiency only Tier 2 evaluation.

Description:

The 261 Building is 4-stories tall, irregular-shaped in-plan with re-entrant corners and large openings in the floor diaphragms, and vertically irregular with setbacks. The building is clad with 4” thick pre-cast concrete panel veneers. The building was constructed in 1979 and designed to the 1976 edition of the Uniform Building Code.

The roof and typical floors are constructed of post-tensioned concrete slabs spanning to reinforced concrete beams and columns with drop panels. The concrete columns are continuous to the foundation. The foundation system consists of reinforced concrete spread footings.

The lateral-force-resisting system consists of the post-tensioned concrete roof and floor slabs acting as structural diaphragms to transfer seismic inertial forces to the distributed reinforced concrete shear walls.

Pedestrian bridges provide access to adjacent office buildings on the campus. A 2 inch gap separates the bridges from the building.

The building was subjected to moderate ground motion during the 1994 Northridge Earthquake. Recorded ground motion near the site indicates peak ground acceleration of approximately 0.2g. We are not aware of any reports of structural damage to the building resulting from the earthquake. The structures on the campus were visually inspected in 2009. Cosmetic hairline cracks in the pre-cast panels, and horizontal and diagonal cracks in concrete shear walls in the other buildings were observed. The cracks in the concrete shear walls were repaired with injected epoxy. No significant cracks were observed in the shear walls of the 261 Building.

Observation:

A site visit was performed by Owen Hata of NYA on March 17, 2016, to observe the condition and characteristics of the building. Observations were limited to visible areas of the structure. The building structure appeared to be in general conformance with the original structural drawings, no significant structural alteration was observed. The building generally appeared to be in good condition and there were no obvious signs of structural distress. Minor hairline cracks were observed in the post-tensioned

Page 2: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

261 South Figueroa Street – 16080.00 March 30, 2016

Page 2 of 7

550 SOUTH HOPE STREET, SUITE 1700 • LOS ANGELES, CALIFORNIA 90071 • TEL 213-362-0707 • FAX 213-688-3018 • WWW.NYASE.COM

L O S A N G E L E S • S A N F R A N C I S C O • I R V I N E

concrete slabs, shear walls and pre-cast concrete panels. The cracking is common for a concrete building of this age.

The seismic separation between the building and the pedestrian bridge may be inadequate. However, the floor of the building and bridge deck vertically align, thus any impact would result in limited localized damage.

The exterior of the building consists of pre-cast concrete veneer with aluminum storefront system at the ground floor and glazed curtain wall system at the upper floors. The pre-cast panels are anchored to the structure at 24” o.c. horizontally and vertically. The building does not have any canopy or ornamentation that pose a falling hazard.

Evaluation:

The building is located on a flat site and is not susceptible to landslide. The site is not located within an Alquist-Priolo Earthquake fault zone – a geologic zone where surface rupture may occur. The site is located in an area recognized by the State of California where historic occurrence of liquefaction, or local geological, geotechnical and groundwater conditions indicate a potential for permanent ground displacement. However, USGS regional liquefaction hazard maps indicate that the site is located in a region of low susceptibility to liquefaction.

An ASCE 41-13 Tier 1 and deficiency only Tier 2 assessment was performed assuming a site soil classification D, and design spectral acceleration at short period and one second period for BSE-1E, 0.993g and 0.547g, respectively.

Tier 1 noncompliant characteristics were evaluated with a deficiency only Tier 2 assessment and were determined to be compliant.

Conclusion:

Based on observations made during our site visit and the results of the ASCE 41-13 Tier 1 and deficiency only Tier 2 assessment, the expected earthquake performance of the building conforms to University of California seismic rating of “IV” (“Fair”).

Sincerely,

NABIH YOUSSEF & ASSOCIATES

Nabih Youssef, S.E. Principal

Enclosure

References:

Structural drawings for Exchange Square Garden Office Development, Marvin A. Hornstein & Associates, January 12, 1978. Engineering Report 201-281 S. Figueroa Street, Retrocon, November 15, 2009.

Page 3: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

261 South Figueroa Street – 16080.00 March 30, 2016

Page 3 of 7

550 SOUTH HOPE STREET, SUITE 1700 • LOS ANGELES, CALIFORNIA 90071 • TEL 213-362-0707 • FAX 213-688-3018 • WWW.NYASE.COM

L O S A N G E L E S • S A N F R A N C I S C O • I R V I N E

Seismic Hazard Zone Report for the Hollywood 7.5-Minute Quadrangle, Los Angeles County, CA, prepared by State of California, Department of Conservation Division of Mines and Geology, Report No. 026, 1998. State of California Seismic Hazard Zone, Hollywood Quadrangle, March 25, 1999. University of California Seismic Safety Policy, September 15, 2014.

Page 4: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

261 South Figueroa Street – 16080.00 March 30, 2016

Page 4 of 7

550 SOUTH HOPE STREET, SUITE 1700 • LOS ANGELES, CALIFORNIA 90071 • TEL 213-362-0707 • FAX 213-688-3018 • WWW.NYASE.COM

L O S A N G E L E S • S A N F R A N C I S C O • I R V I N E

Photo 1 – Southeast Elevation

Photo 2 – Northeast Elevation

Page 5: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

261 South Figueroa Street – 16080.00 March 30, 2016

Page 5 of 7

550 SOUTH HOPE STREET, SUITE 1700 • LOS ANGELES, CALIFORNIA 90071 • TEL 213-362-0707 • FAX 213-688-3018 • WWW.NYASE.COM

L O S A N G E L E S • S A N F R A N C I S C O • I R V I N E

Photo 3 – West Elevation

Photo 4 – Typical Framing - Ground Floor

Page 6: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

261 South Figueroa Street – 16080.00 March 30, 2016

Page 6 of 7

550 SOUTH HOPE STREET, SUITE 1700 • LOS ANGELES, CALIFORNIA 90071 • TEL 213-362-0707 • FAX 213-688-3018 • WWW.NYASE.COM

L O S A N G E L E S • S A N F R A N C I S C O • I R V I N E

Photo 5 – Typical Framing - 2nd Floor

Photo 6 – Typical Framing – 4th Floor

Page 7: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

261 South Figueroa Street – 16080.00 March 30, 2016

Page 7 of 7

550 SOUTH HOPE STREET, SUITE 1700 • LOS ANGELES, CALIFORNIA 90071 • TEL 213-362-0707 • FAX 213-688-3018 • WWW.NYASE.COM

L O S A N G E L E S • S A N F R A N C I S C O • I R V I N E

Photo 7 – East Atrium

Photo 8 – Low Roof

Page 8: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

261 South Figueroa - 16080.00 March 30, 2016

550 SOUTH HOPE STREET, SUITE 1700 • LOS ANGELES, CALIFORNIA 90071 • TEL 213-362-0707 • FAX 213-688-3018 • WWW.NYASE.COM L O S A N G E L E S • S A N F R A N C I S C O • I R V I N E

APPENDIX A – ASCE 31 CHECKLISTS

Page 9: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

261 South Figueroa March 30, 2016

3.7.9 Basic Structural Checklist For Building Type C2: Concrete Shear Wall Buildings With Rigid or Stiff Diaphragms

This Basic Structural Checklist shall be completed where required by Table 3-2.

Each of the evaluation statements on this checklist shall be marked compliant (C), non-compliant (NC), or not applicable (N/A) for a Tier 1 Evaluation. Compliant statements identify issues that are acceptable according to the criteria of this standard, while non-compliant statements identify issues that require further investigation. Certain statements may not apply to the buildings being evaluated. For non-compliant evaluation statements, the design professional may choose to conduct further investigation using the corresponding Tier 2 evaluation procedure; the section numbers in parentheses following each evaluation statement correspond to Tier 2 evaluation procedures.

C3.7.9 Basic Structural Checklist For Building Type C2

These buildings have floor and roof framing that consists of cast-in-place concrete slabs, concrete beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral forces are resisted by cast-in-place concrete shear walls. In older construction, shear walls are lightly reinforced, but often extend throughout the building. In more recent construction, shear walls occur in isolated locations and are more heavily reinforced with boundary elements and closely spaced ties to provide ductile performance. The diaphragms consist of concrete slabs and are stiff relative to the walls. Foundations consist of concrete spread footings, mat foundations, or deep foundations.

Building System

C NC N/A LOAD PATH: The structure shall contain a minimum of one complete load path for Life Safety and Immediate Occupancy for seismic force effects from any horizontal direction that serves to transfer the inertial forces from the mass to the foundation. (Tier 2: Sec. 4.3.1.1)

The PT concrete roof and floor diaphragms transfer seismic inertial forces to distributed reinforced concrete shear walls that are continuous to the foundation.

C NC N/A MEZZANINES: Interior mezzanine levels shall be braced independently from the main structure, or shall be anchored to the lateral-force-resisting elements of the main structure. (Tier 2: Sec. 4.3.1.3)

The building being evaluated does not have a mezzanine.

C NC N/A WEAK STORY: The strength of the lateral-force-resisting-system in any story shall not be less than 80% of the strength in an adjacent story, above or below, for Life Safety and Immediate Occupancy (Tier 2: Sec. 4.3.2.1)

The concrete shear walls are continuous to the foundation and the steel reinforcement ratio increases at the lower levels.

C NC N/A SOFT STORY: The stiffness of the lateral-force-resisting-system in any story shall not be less than 70% of the stiffness in an adjacent story above or below, or less than 80% of the average stiffness of the three stories above or below for Life Safety and Immediate Occupancy.

The concrete shear walls are continuous to the foundation and no soft story exists.

C NC N/A GEOMETRY: There shall be no changes in horizontal dimension of the lateral-force-resisting system of more than 30% in a story relative to adjacent stories for Life Safety and Immediate Occupancy, excluding one-story penthouses and mezzanines. (Tier 2: Sec. 4.3.2.3)

Page 10: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

261 South Figueroa March 30, 2016

There is a change of in the horizontal dimension of the lateral-force resisting system of more than

30% due to the setback at the 4th floor. Linear Dynamic Procedure was performed and walls evaluated.

C NC N/A VERTICAL DISCONTINUITIES: All vertical elements in the lateral-force-resisting system shall be continuous to the foundation. (Tier 2: Sec. 4.3.2.4)

All concrete shear walls are continuous to the foundation.

C NC N/A MASS: There shall be no change in effective mass more than 50% from one story to the next for Life Safety and Immediate Occupancy. Light roofs, penthouses and mezzanines need not be considered. (Tier 2: Sec. 4.3.2.5)

There is a change in effective mass of more than 50% at the 4th floor due to the building setback. Linear Dynamic Procedure was performed and walls evaluated.

C NC N/A TORSION: The estimated distance between the story center of mass and the story center of rigidity shall be less than 20% of the building width in either plan dimension for Life Safety and Immediate Occupancy. (Tier 2: Sec. 4.3.2.6)

Linear Dynamic Procedure was performed and walls evaluated.

C NC N/A DETERIORATION OF CONCRETE: There shall be no visible deterioration of concrete or reinforcing steel in any of the vertical- or lateral-force-resisting elements. (Tier 2: Sec. 4.3.3.4)

No visual evidence of deterioration of concrete or reinforcing steel was observed in areas accessed.

C NC N/A POST-TENSIONING ANCHORS: There shall be no evidence of corrosion or spalling in the vicinity of post-tensioning or end fittings. Coil anchors shall not have been used. (Tier 2: Sec. 4.3.3.5)

No visual evidence of corrosion or spalling in vicinity of post-tensioning or end fittings was observed in areas accessed.

C NC N/A CONCRETE WALL CRACKS: All existing diagonal cracks in wall elements shall be less than 1/8" for Life Safety and 1/16" for Immediate Occupancy, shall not be concentrated in one location, and shall not form an X pattern. (Tier 2: Sec. 4.3.3.9)

Observed cracks in wall elements accessed were less than 1/8”.

Lateral-Force-Resisting System

C NC N/A COMPLETE FRAMES: Steel or concrete frames classified as secondary components shall form a complete vertical load carrying system. (Tier 2: Sec. 4.4.1.6.1)

Concrete frames form a complete vertical load carrying system.

C NC N/A REDUNDANCY: The number of lines of shear walls in each principal direction shall be greater than or equal to 2 for Life Safety and Immediate Occupancy. (Tier 2: Sec. 4.4.2.1.1)

Review of the structural drawings indicate that there are 2 or more lines of concrete shear walls in each principal direction.

C NC N/A SHEAR STRESS CHECK: The shear stress in the concrete shear walls, calculated using the Quick Check procedure of Section 3.5.3.3, shall be less than the greater of 100 psi or 2 cf ' for Life Safety and Immediate Occupancy. (Tier 2: Sec. 4.4.2.2.1)

The shear stress in the concrete walls, calculated using the Quick Check procedure, are greater than 100 psi or 2 cf ' . The concrete shear walls were evaluated using shear forces from dynamic analysis, expected strength and m-factors, and were found to have adequate strength.

Page 11: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

261 South Figueroa March 30, 2016

C NC N/A REINFORCING STEEL: The ratio of reinforcing steel area to gross concrete area shall be not less than 0.0015 in the vertical direction and 0.0025 in the horizontal direction for Life Safety and Immediate Occupancy. The spacing of reinforcing steel shall be equal to or less than 18" for Life Safety and Immediate Occupancy. (Tier 2: Sec. 4.4.2.2.2)

The ratio of steel reinforcing steel area to gross concrete area was greater than 0.0015 in the vertical direction and 0.0025 in the horizontal direction. The spacing of reinforcing steel was less than 18” o.c.

Connections

C NC N/A TRANSFER TO SHEAR WALLS: Diaphragms shall be connected for transfer of loads to the shear walls for Life Safety and the connections shall be able to develop the lesser of the shear strength of the walls or diaphragms for Immediate Occupancy. (Tier 2 Sec. 4.6.2.1)

Review of structural drawings(37/S-21) indicate #4 dowels at 24” o.c. transfer seismic loads to shear walls.

C NC N/A FOUNDATION DOWELS: Wall reinforcement shall be doweled into the foundation for Life Safety and the dowels shall be able to develop the lesser of the strength of the walls or the uplift capacity of the foundation for Immediate Occupancy. (Tier 2: Sec. 4.6.3.5)

Structural drawings (34/S-14) indicates that wall reinforcement is doweled into foundation.

Page 12: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

261 South Figueroa March 30, 2016

3.7.9S Supplemental Structural Checklist For Building Type C2: Concrete Shear

Wall Buildings With Rigid or Stiff Diaphragms

This Supplemental Structural Checklist shall be completed where required by Table 3-2. The Basic Structural Checklist shall be completed prior to completing this Supplemental Structural Checklist.

Lateral-Force-Resisting System

C NC N/A DEFLECTION COMPATIBILITY: Secondary components shall have the shear capacity to develop the flexural strength of the components for Life Safety and shall meet the requirements of 4.4.1.4.9, 4.4.1.4.10, 4.4.1.4.11, 4.4.1.4.12 and 4.4.1.4.15 for Immediate Occupancy. (Tier 2: Sec. 4.4.1.6.2)

Exterior columns have spiral #4 at 3” o.c. Interior columns have #4 ties at 12” o.c. and have adequate shear strength to resist shear forces from expected inter-story deformation.

C NC N/A FLAT SLABS: Flat slabs/plates not part of lateral-force-resisting system shall have continuous bottom steel through the column joints for Life Safety and Immediate Occupancy. (Tier 2: Sec. 4.4.1.6.3)

Structural drawings(17/S-21) indicate that columns have 8” thick drop panels or frame beams.

C NC N/A COUPLING BEAMS: The stirrups in coupling beams over means of egress shall be spaced at or less than d/2 and shall be anchored into the confined core of the beam with hooks of 135 or more for Life Safety. All coupling beams shall comply with the requirements above and shall have the capacity in shear to develop the uplift capacity of the adjacent wall for Immediate Occupancy. (Tier 2: Sec. 4.4.2.2.3)

Stirrups in coupling beams over means of egress are spaced at 18” o.c. with 135 hooks.

C NC N/A OVERTURNING: All shear walls shall have aspect ratios less than 4 to 1. Wall piers need not be considered. This statement shall apply to the Immediate Occupancy Performance Level only. (Tier 2: Sec. 4.4.2.2.4)

Subject building is being evaluated to Life Safety Performance Level.

C NC N/A CONFINEMENT REINFORCING: For shear walls with aspect ratios greater than 2.0, the boundary elements shall be confined with spirals or ties with spacing less than 8db. This statement shall apply to the Immediate Occupancy Performance Level only. (Tier 2: Sec. 4.4.2.2.5)

Subject building is being evaluated to Life Safety Performance Level.

Page 13: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

261 South Figueroa March 30, 2016

C NC N/A REINFORCING AT OPENINGS: There shall be added trim reinforcement around all wall openings with a dimension greater than three times the thickness of the wall. This statement shall apply to the Immediate Occupancy Performance Level only. (Tier 2: Sec. 4.4.2.2.6)

Subject building is being evaluated to Life Safety Performance Level.

C NC N/A WALL THICKNESS: Thickness of bearing walls shall not be less than 1/25 the unsupported height or length, whichever is shorter, nor less than 4". This statement shall apply to the Immediate Occupancy Performance Level only. (Tier 2: Sec. 4.4.2.2.7)

Subject building is being evaluated to Life Safety Performance Level.

Diaphragms

C NC N/A DIAPHRAGM CONTINUITY: The diaphragms shall not be composed of split-level floors and shall not have expansion joints. (Tier 2: Sec. 4.5.1.1)

The PT concrete slab diaphragms do not have split level floors or expansion joints.

C NC N/A OPENINGS AT SHEAR WALLS: Diaphragm openings immediately adjacent to the shear walls shall be less than 25% of the wall length for Life Safety and 15% of the wall length for Immediate Occupancy. (Tier 2: Sec. 4.5.1.4)

A number of shear walls are located immediately adjacent to elevator shafts, stairwells or atrium openings that are greater than 25% of the length of the wall. However, the diaphragm has adequate strength to transfer loads to the walls and/or there are beams framing into the wall that act as drag struts.

C NC N/A PLAN IRREGULARITIES: There shall be tensile capacity to develop the strength of the diaphragm at re-entrant corners or other locations of plan irregularities. This statement shall apply to the Immediate Occupancy Performance Level only. (Tier 2: Sec. 4.5.1.7)

Subject building is being evaluated to Life Safety Performance Level.

C NC N/A DIAPHRAGM REINFORCEMENT AT OPENINGS: There shall be reinforcing around all diaphragm openings larger than 50% of the building width in either major plan dimension. This statement shall apply to the Immediate Occupancy Performance Level only. (Tier 2: Sec. 4.5.1.8)

Subject building is being evaluated to Life Safety Performance Level.

Connections

C NC N/A UPLIFT AT PILE CAPS: Pile caps shall have top reinforcement and piles shall be anchored to the pile caps for Life Safety, and the pile cap reinforcement and pile anchorage shall be able to develop the tensile capacity of the piles for Immediate Occupancy. (Tier 2: Sec. 4.6.3.10)

Subject building is being evaluated does not have pile foundations.

Page 14: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

261 South Figueroa March 30, 2016

3.8 Geologic Site Hazards And Foundations Checklist

This Geologic Site Hazards and Foundations Checklist shall be completed where required by Table 3-2.

Each of the evaluation statements on this checklist shall be marked compliant (C), non-compliant (NC), or not applicable (N/A) for a Tier 1 Evaluation. Compliant statements identify issues that are acceptable according to the criteria of this standard, while non-compliant statements identify issues that require further investigation. Certain statements may not apply to the buildings being evaluated. For non-compliant evaluation statements, the design professional may choose to conduct further investigation using the corresponding Tier 2 evaluation procedure; the section numbers in parentheses following each evaluation statement correspond to Tier 2 evaluation procedures.

Geologic Site Hazards The following statements shall be completed for buildings in levels of high or moderate seismicity.

C NC N/A LIQUEFACTION: Liquefaction susceptible, saturated, loose granular soils that could jeopardize the building's seismic performance shall not exist in the foundation soils at depths within 50 feet under the building for Life Safety and Immediate Occupancy. (Tier 2: Sec. 4.7.1.1)

Regional USGS liquefaction susceptibility maps indicate that the site is located in an area considered to have a low susceptibility to liquefaction.

C NC N/A SLOPE FAILURE: The building site shall be sufficiently remote from potential earthquake-induced slope failures or rockfalls to be unaffected by such failures or shall be capable of accommodating any predicted movements without failure. (Tier 2: Sec. 4.7.1.2)

The subject site is located in a region with relatively flat terrain.

C NC N/A SURFACE FAULT RUPTURE: Surface fault rupture and surface displacement at the building site is not anticipated. (Tier 2: Sec. 4.7.1.3)

The site is not subject to the jurisdiction of the Alquist-Priolo Special Studies Zone Act.

Condition of Foundations The following statement shall be completed for all Tier 1 building evaluations.

C NC N/A FOUNDATION PERFORMANCE: There shall be no evidence of excessive foundation movement such as settlement or heave that would affect the integrity or strength of the structure. (Tier 2: Sec. 4.7.2.1)

No visual evidence of excessive foundation movement was observed in areas accessed

The following statement shall be completed for buildings in levels of high or moderate seismicity being evaluated to the Immediate Occupancy Performance Level.

C NC N/A DETERIORATION: There shall not be evidence that foundation elements have deteriorated due to corrosion, sulfate attack, material breakdown, or other reasons in a manner that would affect the integrity or strength of the structure. (Tier 2: Sec. 4.7.2.2)

Subject building is being evaluated to Life Safety Performance Level.

Capacity of Foundations The following statement shall be completed for all Tier 1 building evaluations.

C NC N/A POLE FOUNDATIONS: Pole foundations shall have a minimum embedment depth of 4 ft for Life Safety and Immediate Occupancy. (Tier 2: Sec. 4.7.3.1)

Subject building does not have pole foundations.

Page 15: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

261 South Figueroa March 30, 2016

The following statements shall be completed for buildings in levels of moderate seismicity being evaluated to the Immediate Occupancy Performance Level and for buildings in levels of high seismicity.

C NC N/A OVERTURNING: The ratio of the horizontal dimension of the lateral-force-resisting system at the foundation level to the building height (base/height) shall be greater than 0.6Sa. (Tier 2: Sec. 4.7.3.2)

L/H = 28.5’/48.75’= 0.58 > 0.6*0.99g = 0.59

C NC N/A TIES BETWEEN FOUNDATION ELEMENTS: The foundation shall have ties adequate to resist seismic forces where footings, piles, and piers are not restrained by beams, slabs, or soils classified as Class A, B, or C. (Section 3.5.2.3.1, Tier 2: Sec. 4.7.3.3)

Per notes on structural drawings, spread footings embedded in undisturbed shale (soil type C).

C NC N/A DEEP FOUNDATIONS: Piles and piers shall be capable of transferring the lateral forces between the structure and the soil. This statement shall apply to the Immediate Occupancy Performance Level only. (Tier 2: Sec. 4.7.3.4)

Subject building is being evaluated to Life Safety Performance Level.

C NC N/A SLOPING SITES: The difference in foundation embedment depth from one side of the building to another shall not exceed one story in height. This statement shall apply to the Immediate Occupancy Performance Level only. (Tier 2: Sec. 4.7.3.5)

Subject building is being evaluated to Life Safety Performance Level.

Page 16: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

261 South Figueroa - 16080.00 March 30, 2016

550 SOUTH HOPE STREET, SUITE 1700 • LOS ANGELES, CALIFORNIA 90071 • TEL 213-362-0707 • FAX 213-688-3018 • WWW.NYASE.COM L O S A N G E L E S • S A N F R A N C I S C O • I R V I N E

APPENDIX B – CALCULATIONS

Page 17: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral
Page 18: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral
Page 19: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

β =β =β =β =

Σ

Page 20: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

3/15/2016 DesignMaps Summary Report

http://ehp1-earthquake.cr.usgs.gov/designmaps/us/summary.php?template=minimal&latitude=34.056106&longitude=-118.253583&siteclass=3&riskcategory=-1… 1/1

Report Title

Building Code Reference Document

Site Coordinates

Site Soil Classification

Design Maps Summary ReportUser–Specified Input

261 South FigueroaTue March 15, 2016 17:38:06 UTC

ASCE 41-13 Retrofit Standard, BSE-1E(which utilizes USGS hazard data available in 2008)

34.05611°N, 118.25358°W

Site Class D – “Stiff Soil”

USGS–Provided Output

SS,20/50 0.859 g SXS,BSE-1E 0.993 g

S1,20/50 0.306 g SX1,BSE-1E 0.547 g

Although this information is a product of the U.S. Geological Survey, we provide no warranty, expressed or implied, as to theaccuracy of the data contained therein. This tool is not a substitute for technical subject-matter knowledge.

Page 21: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral
Page 22: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral
Page 23: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral
Page 24: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral
Page 25: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

Mod

e: 1

T =

0.35

sec

Page 26: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

Mod

e: 2

T =

0.30

sec

Page 27: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral

Mod

e: 3

T =

0.26

sec

Page 28: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral
Page 29: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral
Page 30: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral
Page 31: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral
Page 32: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral
Page 33: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral
Page 34: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral
Page 35: March 30, 2016 Ms. Joanne Williams Senior Leasing ......beams, one-way joists, two-way waffle joists, or flat slabs. Floors are supported on concrete columns or bearing walls. Lateral