marine environment protection committee ......reported results and verification as adhered to within...

19
I:\MEPC\75\MEPC 75-INF.12.docx E MARINE ENVIRONMENT PROTECTION COMMITTEE 75th session Agenda item 4 MEPC 75/INF.12 22 January 2020 ENGLISH ONLY Pre-session public release: HARMFUL AQUATIC ORGANISMS IN BALLAST WATER Information on the type approval of the Bawat BWMS Mk2 manufactured by Bawat A/S Submitted by Denmark SUMMARY Executive summary: This document provides information to the Organization by the Danish Authorities that have type-approved the Bawat Ballast Water Management System Mk2 in accordance with the Code for Approval of Ballast Water Management Systems (BWMS Code), in compliance with regulation D-3.1 of the International Convention for the Control and Management of Ships' Ballast Water and Sediments, 2004 Strategic direction, if applicable: 2 Output: 2.2 Action to be taken: Paragraph 26 Related documents: Resolutions MEPC.228(65); MEPC.279(70) and MEPC.300(72) Introduction 1 The Danish Authorities (Danish Environmental Protection Agency (DEPA) and Danish Maritime Authority (DMA)) hereby notify the Organization of its decision to type approve the Bawat Ballast Water Management System (BWMS) Mk2 by Bawat A/S. 2 The Bawat BWMS Mk2 utilizes heat (pasteurization) treatment. Lloyd's Register, on behalf of the Danish Authorities, has reviewed the technical documentation, test plans and reports throughout the type approval process. Surveys of factory acceptance tests, the test facilities and the test ship have also been performed by Lloyd's Register/DHI Denmark on behalf of the Danish Authorities.

Upload: others

Post on 29-Jul-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

I:\MEPC\75\MEPC 75-INF.12.docx

E

MARINE ENVIRONMENT PROTECTION COMMITTEE 75th session Agenda item 4

MEPC 75/INF.12 22 January 2020 ENGLISH ONLY

Pre-session public release: ☒

HARMFUL AQUATIC ORGANISMS IN BALLAST WATER

Information on the type approval of the Bawat BWMS Mk2

manufactured by Bawat A/S

Submitted by Denmark

SUMMARY

Executive summary: This document provides information to the Organization by the Danish Authorities that have type-approved the Bawat Ballast Water Management System Mk2 in accordance with the Code for Approval of Ballast Water Management Systems (BWMS Code), in compliance with regulation D-3.1 of the International Convention for the Control and Management of Ships' Ballast Water and Sediments, 2004

Strategic direction, if applicable:

2

Output: 2.2

Action to be taken: Paragraph 26

Related documents: Resolutions MEPC.228(65); MEPC.279(70) and MEPC.300(72)

Introduction 1 The Danish Authorities (Danish Environmental Protection Agency (DEPA) and Danish Maritime Authority (DMA)) hereby notify the Organization of its decision to type approve the Bawat Ballast Water Management System (BWMS) Mk2 by Bawat A/S. 2 The Bawat BWMS Mk2 utilizes heat (pasteurization) treatment. Lloyd's Register, on behalf of the Danish Authorities, has reviewed the technical documentation, test plans and reports throughout the type approval process. Surveys of factory acceptance tests, the test facilities and the test ship have also been performed by Lloyd's Register/DHI Denmark on behalf of the Danish Authorities.

Page 2: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

MEPC 75/INF.12 Page 2

I:\MEPC\75\MEPC 75-INF.12.docx

3 As a conclusion to this process, the Danish Authorities find that the Bawat BWMS Mk2 satisfies the requirements of the new Code for Approval of Ballast Water Management Systems (BWMS Code), adopted by resolution MEPC.300(72), on the basis of testing, reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted by resolution MEPC.279(70), and latest type approval relevant BWM.2 circulars. 4 In accordance with resolution MEPC.228(65) on Information reporting on type approved ballast water management systems, the following information is provided:

.1 approval date: 31 October 2019;

.2 name of the Danish Authorities: DEPA and DMA;

.3 name of the BWMS: Bawat BWMS Mk2;

.4 a copy of the type approval certificate can be found in the annex to this document;

.5 results from land-based and shipboard testing (summarized in the annex).

Description of the BWMS 5 The Bawat BWMS Mk2 employs pasteurization as the treatment process. The process involves heating the ballast water to be treated to a given pasteurization temperature (TPAST) and maintaining this temperature for a given minimum residence time (tRT). In the BWMS' Pasteurizing Unit the temperature of the ballast water is raised to a minimum treatment temperature of 64°C. Depending on the treatment temperature applied, the ballast water is kept at this elevated temperature for minimum residence times according to the following expressions:

• 64 °C ≤ TPAST < 72 °C: tRT ≥ -5 × TPAST + 400 s

• TPAST ≥ 72 °C: tRT ≥ 40 s

6 On-board Bawat BWMS Mk2 installations are exploiting ship surplus heat sources (e.g. main engine jacket cooling water, economizer or scavenge air) for the treatment process. The system is designed and integrated specifically for each ship on an assessment of excess heat available for ballast water treatment, layout of the heating system, amount of water to be ballasted/deballasted during cargo operations, number of ballast water tanks, trade pattern, etc. 7 The Bawat BWMS Mk2 main operational procedure is treatment in-voyage and not in operation during port stays. Therefore, the Treatment Rated Capacity (TRC) is not linked to the capacity of the ship's ballast water pumps, and for this reason the Bawat BWMS Mk2 is not dependent on the ship's ballast pump capacity for treatment operations. 8 The Bawat BWMS Mk2 design also qualified to be in accordance with Lloyd's Register Rules for Ships. Overview of the Bawat BWMS Mk2 type approval process 9 Based on review of documentation required in paragraphs 1.3 and 1.4 of the annex to the 2016 Guidelines (G8), inspections of the control and monitoring system during functional

Page 3: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

MEPC 75/INF.12 Page 3

I:\MEPC\75\MEPC 75-INF.12.docx

tests, installations at the test site including a verifying Site Acceptance Test and witnessing of commissioning test cycles, Lloyd's Register qualified the system design to be in accordance with paragraph 4 of the 2016 Guidelines (G8) and paragraph 5 of the annex. The test set-up was verified to be in accordance with paragraphs 1.5 to 1.13 of the annex to the 2016 Guidelines (G8). 10 Land-based testing for the Bawat BWMS Mk2 was conducted independently by DHI Denmark in the period from 2 October to 13 December 2017. The BWMS was operated by DHI during testing. 11 The Bawat BWMS Mk2 was tested according to the manufacturer's performance claims, as applied within five consecutive successful test cycles in all (three) salinities and with challenge water characteristics as defined in paragraph 2 of the annex to the 2016 Guidelines (G8). The system successfully met the ballast water performance standard described in regulation D-2. 12 DHI Denmark is certified and audited by an independent accreditation body (Danak). A Quality Management Plan (QMP), Quality Assurance Project Plan (QAPP), and test plans have been reviewed by Lloyd's Register on behalf of the Danish Authorities and found in compliance with paragraph 2 of the annex to the 2016 Guidelines (G8). 13 All methods for sampling, analysis and augmentation of test water have been validated by DHI in accordance with paragraph 2.4.21 and paragraph 4 of the annex to the 2016 Guidelines (G8) and to the satisfaction to the Authorities. Organism in size class ≥ 10 to < 50 µm were enumerated employing the CMFDA/FDA vital staining methodology. 14 A System Design Limitation evaluation was completed at first prior to the start of testing and validated by the land-based and shipboard tests, and later revised, amended and validated prior to the completion of the Type Approval Report in accordance with paragraphs 1.14 to 1.15 and 6 of the annex to the BWMS Code.

15 The System Design Limitations identified and validated during land-based and shipboard tests are:

.1 The applied pasteurization dose (TPAST

, tRT

) must be on or above the Bawat

Pasteurization Efficacy Threshold (BPET) expressed as

• 64 °C ≤ TPAST < 72 °C: tRT ≥ -5 × TPAST + 400 s

• TPAST ≥ 72 °C: tRT ≥ 40 s

Pasteurization Temperature lower than 64°C implies that the ballast water is not treated in accordance with the type approval. The Bawat BWMS Mk2 includes flow optimization controls based on the pasteurization temperature. Should the applied pasteurization dose decrease below the Bawat Pasteurization Efficacy Threshold (BPET), the control system will adjust the flow rate in order to maintain the residence time above the BPET.

.2 The Bawat BWMS Mk2 has been found to hold no limitations of ballast water temperature.

.3 The Bawat BWMS Mk2 has been found to hold no limitation with the salinity of ballast water.

.4 The Bawat BWMS Mk2 has been found to hold no limitations with respect to post-treatment holding time.

Page 4: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

MEPC 75/INF.12 Page 4

I:\MEPC\75\MEPC 75-INF.12.docx

16 The shipboard testing was conducted by DHI Denmark in the period from 4 October 2018 to 15 April 2019 onboard M/V X-Press Karakoram (IMO 9348924); at the time of testing named Wan Hai 310. The BWMS was operated by the ship's crew during testing in harbours and coastal waters during its trade route between Singapore and Japan with multiple port calls (e.g. Port Klang/Malaysia, Hong Kong and Yokohama). 17 In total six test cycles were conducted. The tests were designed to meet the requirements as defined in paragraph 2 of the annex to the 2016 Guidelines (G8). These tests along with the extended continued service of the BWMS of more than seven months were designed to assess the biological efficacy (BE) and operational performance of the Bawat BWMS Mk2 whilst installed on board a seagoing ship. 18 Before commencement of testing, the ship''s assigned class society (Lloyd’s Register) conducted a survey of the installation on board and verified that it was assembled in a location and configuration consistent with its final intended use. The reliability of the BWMS was according to the specifications of the manufacturer. 19 To fulfil the requirements of evaluating Bawat's claimed minimum holding time as specified in paragraph 2.4.5, and to evaluate regrowth as specified in section 2.6, both of the annex to the 2016 Guidelines (G8), the above testing was divided with minimum two test cycles without holding time before discharge, with minimum two test cycles with 24 hours, and two test cycles with five days holding time between uptake and discharge in all (three) salinities. 20 The Danish Authorities find that the system has demonstrated performance to the standard described in regulation D-2 with no required limitation to the holding time between uptake and discharge. 21 To fulfil the requirement to evaluate effective performance in a range of ballast water temperatures in accordance with paragraphs 2.46 to 2.48 of the annex to the BWMS Code, a validation in respect of details within Bawat provided system design limitation report, and subsequent supporting land-based and shipboard testing results were verified. 22 Bawat provided a demonstration of scaling and vulnerability by computational fluid dynamics (CFD) covering the full range of Bawat BWMS Mk2 models. Further, Bawat provided a vulnerability assessment of the Bawat BWMS Mk2 model range, showing compliance with paragraph 4.15 of the BWMS Code and BWM.2/Circ.33/Rev.1. 23 The identified relevant operational related SDL safety measures have been incorporated in the Bawat BWMS Mk2’s control and monitoring system and the operational manual. 24 The assembled units forming part of type approval testing have been environmentally tested in accordance with IACS UR E10 by the ISO17025 accepted laboratories DELTA (a part of FORCE Technology) in Denmark from 8 May to 15 June 2017. Relevant components mounted in an identified standard configuration and which hold a valid marine type approval certificate to the same standard were not subject to further testing. Resume 25 Following the design acceptance and the preparation of a test plan suitable for validating the claimed operating ranges of the Bawat BWMS Mk2 as specified by Bawat A/S, 15 successful land-based tests in the three defined salinity ranges and five successful shipboard tests exceeding the testing period of minimum six months were conducted.

Page 5: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

MEPC 75/INF.12 Page 5

I:\MEPC\75\MEPC 75-INF.12.docx

The tests were independently performed by DHI Denmark and in accordance with the normal operating procedures of the Bawat BWMS Mk2. Action requested of the Committee 26 The Committee is invited to note the information contained in this document.

***

Page 6: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted
Page 7: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

Page 1 of 13

Certificate No: LR1900446TA

Issue Date: 31/10/2019

Expiry Date: 30/10/2024

Reference: WP37106095

71 Fenchurch Street, London, EC3M 4BS, UK

Lloyd's Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as ‘Lloyd's Register’. Lloyd's Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Lloyd's Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.

Type Approval Certificate of Ballast Water Management System (BWMS) This is to certify that the Ballast Water Management System listed below has been examined and tested in accordance with the requirements of the specifications contained in the Code for Approval of Ballast Water Management Systems (resolution MEPC.300(72)). This certificate is valid only for Ballast Water Management system referred to below, on behalf of the Danish Environmental Protection Agency (DEPA) and Danish Maritime Authority (DMA).

This certificate is issued to

Manufacturer BAWAT A/S Address Agern Allé 24, 2970 Hørsholm, Denmark

Ballast Water Management System supplied:

BAWAT BWMS Mk2 (heat (pasteurization) treatment)

Under type and model designation and incorporating:

BAWAT BWMS – 50/100/150/200/250/300/350/400/450/500/550/600/650/700/750/800/850/900/950/1000/1250/1500/1750/2000/2500/3000/3500/4000/5000

Ballast Water Management System manufactured by:

BAWAT A/S

To equipment/ assembly drawing No:

BD 2017.201 – General Piping & Instrumentation Diagram BAWAT BWMS - 2 Heating sources (Rev. G); dated 10 September 2019

Other equipment manufactured by:

Please refer to ‘BD 2018.002 - BAWAT BWMS Mk2 – Capacities and shortlisted components (Rev. E.1)’; dated 04 October 2019

To equipment/ assembly drawing No:

Please refer to ‘BD 2018.002 - BAWAT BWMS Mk2 – Capacities and shortlisted components (Rev. E.1)’; dated 04 October 2019

Treatment Rated Capacity: 50 to 5000 m3/h

Sahan Abeysekara Principal Specialist to Lloyd's Register EMEA A member of the Lloyd's Register Group

MEPC 75/INF.12 Annex, page 1

Page 8: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

Page 2 of 13

Certificate No: LR1900446TA

Issue Date: 31/10/2019

Expiry Date: 30/10/2024

Reference: WP37106095

71 Fenchurch Street, London, EC3M 4BS, UK

Lloyd's Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as ‘Lloyd's Register’. Lloyd's Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Lloyd's Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.

Type Approval Certificate of Ballast Water Management System (BWMS)

A copy of this Type Approval Certificate should be carried on board a vessel fitted with this Ballast Water Management System at all times. A reference to the test protocol and a copy of the test results should be available for inspection on board the vessel. If the Type Approval Certificate is issued based on approval by another Administration, reference to that Type Approval Certificate shall be made. Limiting Operating Conditions imposed as described in the Design Appraisal Document forms part of this certificate. This certificate remains valid up to the expiry dated unless cancelled or revoked, or until such date where it is superseded by the requirements of the Marine Equipment Directive whichever is the earlier, provided the conditions in the attached schedule are complied with and the equipment remains satisfactory in service.

Note: The certificate is not valid for equipment, the design and manufacture of which has been varied or modified from the P&I drawings and components cited within this certificate. The equipment of supplied system must be as per the specimen tested or a scaled version of it, as per the systems configuration cited within this certificate. The manufacturer should notify the nominated body named on this certificate of any modification or changes to the equipment in order to obtain valid certificate. This certificate is issued under the authority given in ‘order on management of ballast water and sediments from ships ballast water tanks and order on survey and certification of ships using ballast water and on ballast water management plans and ballast records’.

Page 9: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

Page 3 of 13

Certificate No: LR1900446TA

Issue Date: 31/10/2019

Expiry Date: 30/10/2024

Reference: WP37106095

Lloyd's Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as ‘Lloyd's Register’. Lloyd's Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Lloyd's Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.

DESIGN APPRAISAL DOCUMENT

ATTACHMENT TO CERTIFICATE OF TYPE APPROVAL No. LR1900446TA The undernoted models, identification and documents have been appraised for compliance with the relevant International Conventions for the Type Approval of Ballast Water Management Systems.

This Design Appraisal Document forms part of the Certificate that is issued under the authority given in the Bekendtgørelse om håndtering af ballastvand og sedimenter fra skibes ballastvandtanke and Bekendtgørelse om syn og certificering af skibe, der anvender ballastvand, og om ballastvandplaner og -journaler. MODEL AND TYPE DESIGNATION

BAWAT BWMS – 50/100/150/200/250/300/350/400/450/500/550/600/650/700/750/800/850/900/950/1000/1250/ 1500/1750/2000/2500/3000/3500/4000/5000

Place of production: BAWAT A/S, Hørsholm, Denmark Equipment/Assembly Drawings

Type Title Dwg. No. Rev. System Type designation

Generic P&ID General Piping & Instrumentation Diagram BAWAT BWMS - 2 Heating sources

BD 2017.201 G All

Design Guide Guide to Design of BAWAT BWMS BD 2017.009 B.1 All

Design Guide Guide to Design of BAWAT BWMS Retention Section BD 2017.004 C.1 All

Component list BAWAT BWMS Mk2 – Capacities and shortlisted components

BD 2018.002 E.1 All

PRODUCT DESCRIPTION

BAWAT BWMS Mk2 employs heat (pasteurization) treatment.

Treatment Sequence:

BAWAT BWMS Mk2 concept allows three operational scenarios:

Heat treatment (one-pass) during ballast water uptake; or Heat treatment (one-pass) during ballast water discharge; or Heat treatment (one-pass) during internal transfer from tank to tank.

The BAWAT BWMS Mk2 is approved with:

Regeneration and Heating Section plate heat exchanger models as per ‘BD 2018.002 - BAWAT BWMS Mk2 Capacities and shortlisted components’ and ‘BD 2017.009 - Guide to Design of BAWAT BWMS’.

Retention Section designs as per ‘BD 2018.002 - BAWAT BWMS Mk2 Capacities and shortlisted components’ and ‘BD 2017.004 - Guide to Design of BAWAT BWMS Retention Section’.

Page 10: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

Page 4 of 13

Certificate No: LR1900446TA

Issue Date: 31/10/2019

Expiry Date: 30/10/2024

Reference: WP37106095

Lloyd's Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as ‘Lloyd's Register’. Lloyd's Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Lloyd's Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.

SYSTEM DESIGN LIMITATIONS

This equipment has been designed for operation in the following conditions:

The applied pasteurization dose (TPAST, tRT) must be on or above the BAWAT Pasteurization Threshold (BPET) expressed as

PAST < 72 °C: tRT = -5 × TPAST + 400 s

TPAST tRT = 40 s

The pasteurization temperature must be above 64 °C for a minimum of 80 sec, as shown in BPET curve.

Pasteurisation temperature lower than 64 °C implies that the ballast water is not treated in accordance with this certificate.

The BWMS includes flow optimisation controls based on the Pasteurisation temperature.

Should the applied pasteurization dose decrease below the BAWAT Pasteurization Efficacy Threshold (BPET), the control system must adjust the flow rate in order to maintain the Residence time above the BPET.

Temperature

The BAWAT BWMS Mk2 have been found to hold no limitations of ballast water temperature, as validated during Land-based and Shipboard testing.

Salinity

The BAWAT BWMS Mk2 have been found to hold no limitation with the salinity of ballast water, as validated during Land-based and Shipboard testing.

Post-treatment Holding Time

The BAWAT BWMS Mk2 have been found to hold no limitations with respect to post-treatment holding time, as validated during Land-based and Shipboard testing.

20

30

40

50

60

70

80

90

64 66 68 70 72 74 76Pasteurization temperature, TPAST

BAWAT Pasteurization Efficacy…

Page 11: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

Page 5 of 13

Certificate No: LR1900446TA

Issue Date: 31/10/2019

Expiry Date: 30/10/2024

Reference: WP37106095

Lloyd's Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as ‘Lloyd's Register’. Lloyd's Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Lloyd's Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.

Treatment Rated Capacities (TRC)1)

BAWAT BWMS TRC

[m3/h]

Minimum Retention section volume range for tRT range (ref. to BPET)

[m3]

treatment capacity [kW] Density, water = 1.025 kg/m3

Specific heat, water = 4,19 kJ/kg°C Min. tRT at TPAST

72°C: 40 s Min. tRT at TPAST

64°C: 80 s

50 0.56 1.1 239 477 716 954 100 1.1 2.2 477 954 1,432 1,909 150 1.7 3.3 716 1,432 2,147 2,863 200 2.2 4.4 954 1,909 2,863 3,818 250 2.8 5.6 1,193 2,386 3,579 4,772 300 3.3 6.7 1,432 2,863 4,295 5,726 350 3.9 7.8 1,670 3,340 5,011 6,681 400 4.4 8.9 1,909 3,818 5,726 7,635 450 5.0 10.0 2,147 4,295 6,442 8,590 500 5.6 11.1 2,386 4,772 7,158 9,544 550 6.1 12.2 2,625 5,249 7,874 10,498 600 6.7 13.3 2,863 5,726 8,590 11,453 650 7.2 14.4 3,102 6,204 9,305 12,407 700 7.8 15.6 3,340 6,681 10,021 13,361 750 8.3 16.7 3,579 7,158 10,737 14,316 800 8.9 17.8 3,818 7,635 11,453 15,270 850 9.4 18.9 4,056 8,112 12,168 16,225 900 10.0 20.0 4,295 8,590 12,884 17,179 950 10.6 21.1 4,533 9,067 13,600 18,133

1000 11.1 22.2 4,772 9,544 14,316 19,0881250 13.9 27.8 5,965 11,930 17,895 23,860 1500 16.7 33.3 7,158 14,316 21,474 28,6321750 19.4 38.9 8,351 16,702 25,053 33,404 2000 22.2 44.4 9,544 19,088 28,632 38,1762500 27.8 55.6 11,930 23,860 35,790 47,719 3000 33.3 66.7 14,316 28,632 42,948 57,2633500 38.9 77.8 16,702 33,404 50,105 66,807 4000 44.4 88.9 19,088 38,176 57,263 76,3515000 55.6 111.1 23,860 47,719 71,579 95,439

1) TRC is the maximum inlet flow to the BWMS; a flow exceeding the given value implies that the ballast water is not treated in accordance with this certificate

Page 12: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

Page 6 of 13

Certificate No: LR1900446TA

Issue Date: 31/10/2019

Expiry Date: 30/10/2024

Reference: WP37106095

Lloyd's Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as ‘Lloyd's Register’. Lloyd's Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Lloyd's Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.

SHIP-SPECIFIC COMPONENTS DESIGN/ SELECTION Ship Information

The BAWAT BWMS Mk2 is ship-specific designed based on the ship particulars including, but not limited to, the documentation requirements included in chapter 2 of the ‘BD 2017.009 - Guide to Design of BAWAT BWMS’.

BAWAT scaled models are to be designed taking into account ship’s minimum heat power and space availability onboard.

Retention Section

The BAWAT BWMS Mk2 is required to have a retention section with a volume to meet the residence time defined by this certificate in the ‘Treatment Rated Capacities’ section. The Ballast Water Management System (BWMS) retention section shall be designed and installed in accordance with the ‘BD 2017.004 - Guide to Design of BAWAT BWMS Retention Section’.

Regeneration and Heating section(s)

The BAWAT BWMS Mk2 is required to have Regeneration and Heating section(s) plate heat exchangers (PHE) designed in accordance with document ‘BD 2017.009 - Guide to Design of BAWAT BWMS’ and the heating power requirements based on

pasteurisation temperature of 64 °C.

Sensors

The BAWAT BWMS Mk2 must be installed with a water flow meter, water temperature transmitters and water pressure transmitters according to ‘Generic Piping and Instrumentation Diagram, BAWAT BWMS’.

Control equipment

The type approved system includes the following control unit(s):

Name Model Maker Software revisionControl and Monitoring Unit (CMU) CMU 2.0 Eltronic 1.0

SHIP-SPECIFIC BWMS INSTALLATION REQUIREMENTS The additional documentation to be submitted for approval in each BWMS installation includes:

Piping and Instrumentation Diagram (P&ID) of the ballast system Ballast water pump detailsHeating power requirements and heat balance simulation deliverables as per ‘BD 2017.009 - Guide to Design of BAWAT BWMS’BWMS piping and valve arrangement deliverables as per ‘BD 2017.009 - Guide to Design of BAWAT BWMS’ Pasteurizing Unit configuration and design deliverables as per ‘BD 2017.009 - Guide to Design of BAWAT BWMS’. Information regarding the PHEs, the retention section and PC (if applicable) related to the specific installation should be submitted for design review.

Page 13: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

Page 7 of 13

Certificate No: LR1900446TA

Issue Date: 31/10/2019

Expiry Date: 30/10/2024

Reference: WP37106095

Lloyd's Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as ‘Lloyd's Register’. Lloyd's Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Lloyd's Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.

APPRAISED DOCUMENTATION

Document No. Rev. Title Date

19-4-7 0 QB Risk Assesment Hazard and Operability (HAZOP) Study of BAWAT AS's BAWAT Ballast Water Management System OLC 18 07 2017-1

18/07/2017

BD 2017.017 A Piping & Instrumentation Diagram: Mobile Treatment Unit – Test Installation

27/09/2017

BD 2017.059.004

C Piping Diagram: X-Press Karakoram 22/03/2018

BD 2017.201 GGeneral Piping & Instrumentation Diagram BAWAT BWMS - 2 Heating sources

10/09/2019

BD 2018.003 A.1 BAWAT BWMS Mk2 - System description 27/09/2019

BD 2017.018 C.3 System description BAWAT BWMS Mk2 - Ship Board Tests 27/09/2019

BD 2017.014 E Operation, Maintenance and Safety Manual - BAWAT Ballast Water Management System Mk2

02/10/2019

P10017-04-10 RP

2 Scaling of BAWAT BWMS 02/10/2019

P10017-04-RP-06

6 System Design and Operation Limitations for the BAWAT BWMS 02/10/2019

BD 2018.002 E.1 BAWAT BWMS Mk2 - Capacities and Shortlisted Components 04/10/2019

BIOLOGICAL TEST REPORTS

Document No. Rev. Title Date

11821722/2

017.10.03Biological efficacy performance evaluation of BAWAT Ballast Water Management System Mk2 in land-based test – Test Plan

03/10/2017

Final 11821722/2019-07-11-

LB

Biological efficacy performance evaluation of BAWAT Ballast Water Management System Mk2 in land-based test – Land-based test report

11/07/2019

Final

11821722 / 2018-06-28

Performance evaluation of BAWAT Ballast Water Management System Mk2 Ballast Water Management

System in shipboard test – Test Plan

28/06/2018

P10017-04-RP-08

1 BAWAT BWMS – BWMS Code and USCG Type Approval Shipboard Test Performance Report

28/06/2019

Revised final

11821722 / 2019-09-17-

SB

Biological efficacy performance evaluation of BAWAT Ballast Water Management System Mk2 in shipboard test – Shipboard test report

17/09/2019

Page 14: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

Page 8 of 13

Certificate No: LR1900446TA

Issue Date: 31/10/2019

Expiry Date: 30/10/2024

Reference: WP37106095

Lloyd's Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as ‘Lloyd's Register’. Lloyd's Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Lloyd's Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.

ENVIRONMENTAL TEST REPORTS

Document No. Rev. Title Date

m Test programme for marine type approval of BAWAT CMU 2.0 05/05/2017

DANAK-19/18349

1 Test for Marine Type Approval of BAWAT CMU 2.0 for Ballast Water Treatment System

25/09/2017

SYSTEM SUPPORTING REPORTS

Document No. Rev. Title Date

BD 2017.009 B.1 Guide to Design of BAWAT BWMS 07/03/2019

BD 2017.004 C.1 Guide to Design of BAWAT BWMS Retention Section 27/09/2019

Page 15: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

Page 9 of 13

Certificate No: LR1900446TA

Issue Date: 31/10/2019

Expiry Date: 30/10/2024

Reference: WP37106095

Lloyd's Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as ‘Lloyd's Register’. Lloyd's Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Lloyd's Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.

CONDITIONS OF APPROVAL

1. The design/selection Regeneration and Heating section(s) plate heat exchangers (PHE) for each BAWAT BWMS Mk2 installation must be verified in accordance with the document ‘BD 2017.009 - Guide to Design of BAWAT BWMS, Rev. B.1’ and the heating power require shown in the ‘Treatment Rated Capacities’ section above (Table 3.1 of the ‘BD 2017.014 - Operation, Maintenance and Safety Manual - BAWAT Ballast Water Management System Mk2, Rev. E’).

2. The design of the retention section for each BAWAT BWMS Mk2 installation must be in accordance with ‘BD 2017.004 - Guide to Design of BAWAT BWMS Retention Section, Rev. C.1’.

3. For each BAWAT BWMS Mk2 installation, the minimum flow rate selected and approved should take into account ship stability requirements (i.e. loading manual).

4. The BAWAT BWMS Mk2 must operate at all times within the allowable area defined by BAWAT Pasteurisation Efficiency Threshold (BPET), as shown in ‘System Design Limitations’ section.

5. The ‘Additional documentation’, as described in section ‘SHIP-SPECIFIC BWMS INSTALLATION REQUIREMENTS’ of this certificate, is to be submitted for approval in each BAWAT BWMS Mk2 installation.

6. Where a Personal Computer (PC) is used to control BAWAT BWMS Mk2, appropriate documentation is to be submitted for evaluation and approval, as part of specific installation. The PC shall be type approved by LR or equivalent certification in compliance with IACS UR E10.

7. All changes in software are to be recorded in accordance the approved Software Quality Plan. The records of all changes are to be forwarded to DMA for evaluation and approval. Major changes to the software are to be approved before installed in the computer.

8. The BAWAT BWMS Mk2 ballast water management system is to be installed in safe areas.

9. For installation of equipment in a hazardous area, appropriate documentation is to be submitted for evaluation and approval to show that the relevant equipment is certified as being safe for use in hazardous areas, as defined in IEC 60079-10-1.

10. The alarm in all control stations of ballast water operation including the navigation bridge need to be verified at installation commissioning of the ballast water management system.

Page 16: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

Page 10 of 13

Certificate No: LR1900446TA

Issue Date: 31/10/2019

Expiry Date: 30/10/2024

Reference: WP37106095

Lloyd's Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as ‘Lloyd's Register’. Lloyd's Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Lloyd's Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.

CONDITIONS OF CERTIFICATION BAWAT A/S hereafter referred as licensee

1. The licensee must take reasonable measures to ensure that the operator of the system is familiar with the operation of the system and is capable of operating and maintaining the system in accordance with the operating manual.

2. Significant changes in the construction of the ballast water management system must be reported to both the DMA and the recognised organisation that issued the type approval certificate on behalf of the DMA; if they potentially affect the efficiency of the system, they must be approved by the DMA.

3. Any indications that the ballast water management system is not performing to the standards of the ballast water convention must be reported to the DMA including any deficiencies identified by Port State control.

4. The licensee must report immediately all events to the DMA leading to harm either to human health or the environment as a result of the operation of the ballast water management system.

5. All accidents in connection with the ballast water management system must be reported immediately to the DMA.

6. If the licensee does not comply with these additional provisions, the type approval may be revoked by the DMA.

Sahan AbeysekaraPrincipal Specialist to Lloyd’s Register EMEA A member of the Lloyd's Register Group

Page 17: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

Page 11 of 13

Certificate No: LR1900446TA

Issue Date: 31/10/2019

Expiry Date: 30/10/2024

Reference: WP37106095

Lloyd's Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as ‘Lloyd's Register’. Lloyd's Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Lloyd's Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.

ANNEX 1 – SUMMARY OF TESTING

Summary of land-based testing for BAWAT BWMS 200 equipped with a 2.2 m3 retention section size and a rated flow rate of 200 m3/h.

Table 1 Inlet Test water conditions in Fresh, Brackish and Marine water Test Cycles

F-1 198 24 13 0.36 13.0 6.4 76 3.6

F-2 119 24 2) 13 0.36 13.0 6.4 76 5.1

F-3 103 0 / 120 12 0.34 9.8 5.3 80 5.9

F-4 131 120 12 0.34 9.8 5.3 80 4.7

F-5 160 0 / 24 8.7 0.33 9.6 7.4 74 4.2

B-1 160 0 / 24 14 20 7.3 8.5 68 4.0

B-2 189 24 13 18 7.5 7.3 54 3.7

B-3 118 24 2) 13 18 7.5 7.3 54 5.1

B-4 135 120 7.3 19 7.3 8.3 61 4.6

B-5 102 0 / 120 3.5 19 7.2 8.5 66 6.0

M-1 158 0 / 24 7.6 29 7.0 6.4 52 4.2

M-2 182 24 7.7 29 7.0 6.4 52 3.8

M-3 114 24 2) 5.2 29 7.3 6.9 50 5.4

M-4 102 0 / 120 7.2 28 6.6 7.4 46 5.9

M-5 1) 133 120 7.3 28 6.6 7.4 46 4.8

M-6 132 120 6 29 6.5 7.6 45 5.0

Requirements

Fresh and Brackish

Water - - - <1 / 10-20 >5 >5 >50 -

Marine Water

- - - 28-36 >1 >1 >1 -

1) Test cycle M-5 demonstrated non-compliance to Regulation D-2 Standard due to contamination of the test water. 2) Treatment on discharge ONLY. This is the pre-treatment holding time and NOT the holding time between treatment and discharge.

Page 18: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

Page 12 of 13

Certificate No: LR1900446TA

Issue Date: 31/10/2019

Expiry Date: 30/10/2024

Reference: WP37106095

Lloyd's Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as ‘Lloyd's Register’. Lloyd's Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Lloyd's Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.

Table 2 Average numbers (three replicates) of live organisms in Inlet, Treated and Control discharge waters.

Inlet to BWMS Discharge

Treated Control Treated Control Treated

Analysis method

Microscopy CMFDA/

FDA Microscopy

CFU Microscopy CMFDA/FDA;

(MPN F-5 only) Microscopy

Colony Forming Units [CFU/100 mL]

F-1 642,304 1,183 20,558 0 158,571 3.8 1,228 <10 <10

F-2 700,292 1,014 15,732 0 158,571 0 1,228 <10 <10

F-3 1,029,250 1,731 20,292 0 / 0 267,571 3.5/ 0 1,072 <1/<10 1.3/<10

F-4 1,031,000 2,218 22,610 1.3 267,571 0 1,072 <10 <10

F-5 337,278 2,111 21,432 0 / 2.2 138,189 182) (MPN: <0.18) /

0 1,879 <10 <10

B-1 364,447 1,077 6,726 0 / 0.67 39,780 975 <10 <10

B-2 552,248 2,158 10,792 0 164,878 0 1,103 0 <1

B-3 535,214 1,980 8,284 0 164,878 0 1,103 0 <1

B-4 263,861 1,908 9,671 0.67 44,972 0 384 <10 <10

B-5 192,764 2,038 10,450 0 / 0.33 92,287 947 <10 <10

M-1 292,472 2,754 6,650 0 / 0 101,910 0/ 0 1,999 <10 <10

M-2 192,375 2,854 7,790 0 101,910 0 1,999 <10 <10

M-3 207,625 1,764 31,768 0 82,256 0.87 1,193 <10 <10

M-4 253,236 2,249 22,363 0 / 0 93,551 0/ 0.7 1,569 <10 <10

M-5 1) 274,983 2,954 22,268 0 93,551 51 1,569 <10 <10

M-6 176,778 1,787 10,621 0 76,528 1.1 1,613 <10 <10

Requirements

- <10 <10 <1 <250 <100

1) Test cycle M-5 demonstrated non-compliance to Regulation D-2 Standard due to contamination.2) The CMFDA/FDA results for this test may have include false positives due to the nature of heat treatment. MPN analysis was

therefore applied. Test cycle F-5 thus demonstrated compliance to Regulation D-2 Standard for zero holding time with MPN analysis.

Page 19: MARINE ENVIRONMENT PROTECTION COMMITTEE ......reported results and verification as adhered to within the 2016 Guidelines for approval of ballast water management systems (G8) adopted

Page 13 of 13

Certificate No: LR1900446TA

Issue Date: 31/10/2019

Expiry Date: 30/10/2024

Reference: WP37106095

Lloyd's Register Group Limited, its affiliates and subsidiaries and their respective officers, employees or agents are, individually and collectively, referred to in this clause as ‘Lloyd's Register’. Lloyd's Register assumes no responsibility and shall not be liable to any person for any loss, damage or expense caused by reliance on the information or advice in this document or howsoever provided, unless that person has signed a contract with the relevant Lloyd's Register entity for the provision of this information or advice and in that case any responsibility or liability is exclusively on the terms and conditions set out in that contract.

Summary of shipboard testing for BAWAT BWMS 250 equipped with a 3.4 m3 retention section size and a rated flow rate of 250 m3/h.

Table 3 Inlet Test water conditions in Fresh, Brackish and Marine water Test Cycles.

SB-11) 171 0 26 33 1.1 0.16 38SB-2 210 0 31 28 0.23 1.9 46SB-3 227 0 28 26 0.25 4.0 328 SB-4 216 0 29 31 0.89 1.0 40SB-5 211 0 31 28 1.5 0.99 64SB-6 219 0 31 27 1.7 0.27 27

Table 4 Average numbers (three replicates) of live organisms in Inlet, Treated and Control discharge waters.

Inlet to BWMS Discharge

Analysis method

Microscopy CMFDA/FDA Microscopy

Microscopy CMFDA/FDA Microscopy

Colony Forming Units [CFU/100 mL]

SB-1 81,431 99 0 0.83 <10 <10 SB-2 206,321 992 0 0 <10 <10 SB-3 50,925 302 0 0.33 <10 <10 SB-4 93,907 1,334 0 0 <10 <10 SB-5 155,330 2,181 0 0 <10 <10 SB-6 98,071 329 0 0 <10 <10

Requirements <10 <10 <1 <250 <100

1) The ballast water discharge results demonstrate the biological organisms’ condition during discharge for zero holding time (T0).

2) Ballast water treatment was conducted only during discharge.

___________