AMCA 550 GREENHECK’S Test Method for High Velocity Wind-Driven Rain Resistant Louvers MARKET APPLICATION Did you know that, if located in the Hurricane Prone Region, all intake and exhaust louvers must comply with AMCA 550 (Test Method for High Velocity Wind Driven Rain Resistant Louvers) per the International Mechanical Code versions 2012 and 2015? e AMCA 550 test standard simulates external wind speeds up to 110 MPH with an external rainfall rate of 8.8 in. per hour. To pass AMCA 550 no more than 1% of the total sprayed water volume may penetrate the louver. If your state has adopted International Building Code 2012 or 2015 now is the time to ensure that all intake and exhaust louver specifications call for an AMCA 550 Listed louver if located in the Hurricane Prone Region. Hurricane Prone Region Louver Requirements US States or Territories Impacted In Part Or Whole By The Hurricane Prone Region (IBC Adoption As Of May 2016) HAWAII Key IBC 2012/2015 IBC 2009 or prior US Virgin Islands Guam Puerto Rico Building code adoptions and interpretations may vary based on local municipality requirements. Reference local building code for actual requirements. Map as shown above is as interpreted by Greenheck based on IBC 2012 figure 1609A and/or IBC 2015 figure 1609.3(1).

Upload: trancong

Post on 08-May-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MARKET APPLICATION AMCA 550 - buckleyonline.com AMCA 550 Flyer August...AMCA 550 GREENHECK’S Test Method for High Velocity Wind-Driven Rain Resistant Louvers MARKET APPLICATION Did

AMCA 550GREENHECK’S

Test Method for High Velocity Wind-Driven Rain Resistant Louvers

MARKET APPLICATION

Did you know that, if located in the Hurricane Prone Region, all intake and exhaust louvers must comply with AMCA 550 (Test Method for High Velocity Wind Driven Rain Resistant Louvers) per the International Mechanical Code versions 2012 and 2015? The AMCA 550 test standard simulates external wind speeds up to 110 MPH with an external rainfall rate of 8.8 in. per hour. To pass AMCA 550 no more than 1% of the total sprayed water volume may penetrate the louver. If your state has adopted International Building Code 2012 or 2015 now is the time to ensure that all intake and exhaust louver specifications call for an AMCA 550 Listed louver if located in the Hurricane Prone Region.

Hurricane P

rone Region Louver R

equirements

US States or Territories Impacted In Part Or Whole By The Hurricane Prone Region (IBC Adoption As Of May 2016)

HAWAII

Key

IBC 2012/2015IBC 2009 or prior

US Virgin IslandsGuamPuerto Rico

Building code adoptions and interpretations may vary based on local municipality requirements. Reference local building code for actual requirements.

Map as shown above is as interpreted by Greenheck based on IBC 2012 figure 1609A and/or IBC 2015 figure 1609.3(1).

Page 2: MARKET APPLICATION AMCA 550 - buckleyonline.com AMCA 550 Flyer August...AMCA 550 GREENHECK’S Test Method for High Velocity Wind-Driven Rain Resistant Louvers MARKET APPLICATION Did

P.O. Box 410 | Schofield, WI 54476-0410 USA | Phone 715.359.6171 | Fax 715.355.2399 | greenheck.com

AMCA 550 | August 2016 | Copyright © 2016 Greenheck Fan Corp.

For more information on the Hurricane Prone Region or louver requirements in the Hurricane Prone Region please contact your local Greenheck representative or Greenheck directly at [email protected].

Louver Selection

Hurricane P

rone Region Louver R

equirements

MARKET APPLICATION

Greenheck offers a complete line of AMCA 550 Listed louvers, ranging from high performance vertical blade products, dual-module horizontal front/vertical rear louvers and combination louver-dampers that will not only meet the function required, but the form desired.

EVH-660D• 6 inch frame depth• Vertical blades• 46% free area• Miami-Dade Notice of Acceptance and

Florida Building Code Approved• AMCA 500-L Certified o Air Performance, Water Penetration and

Wind Driven Rain• AMCA 540 and 550 Listed

EVH-501D• 5 inch frame depth• Vertical blades• 54% free area• Miami-Dade Notice of Acceptance and

Florida Building Code Approved• AMCA 500-L Certified o Air Performance, Water Penetration and

Wind Driven Rain• AMCA 540 and 550 Listed

EHV-901D• 9 inch frame depth• Horizontal front blades/vertical rear blades• 54% free area• Miami-Dade Notice of Acceptance and

Florida Building Code Approved• AMCA 500-L Certified o Air Performance, Water Penetration and

Wind Driven Rain• AMCA 540 and 550 Listed

EHV-901• 9 inch frame depth• Horizontal front blade/vertical rear blade• 54% free area• AMCA 500-L Certified o Air Performance, Water Penetration and

Wind Driven Rain• AMCA 540 and 550 Listed

EHH-601D with VCD-40• 6 inch louver frame depth• Horizontal blade louver with factory attached

control damper• 45% free area• Miami-Dade Notice of Acceptance and

Florida Building Code Approved• AMCA 500-L Certified o Air Performance, Water Penetration and Wind

Driven Rain• AMCA 540 and 550 Listed o AMCA 550 with dampers in fully

closed position

EACA-601D• 6 inch frame depth• Horizontal blade combination louver/damper• 48% free area• Miami-Dade Notice of Acceptance and

Florida Building Code Approved• AMCA 500-L Certified o Air Performance, Water Penetration• AMCA 540 and 550 Listed o AMCA 550 with dampers in fully

closed position