Remote Terminal Unit EPC 3200

30/03/2015UBOS1S C A D ASupervisory Control And Data AcquisitionCopyright 1996-2001 Dale Carnegie & Associates, Inc.1Frequently, presenters must deliver material of a technical nature to an audience unfamiliar with the topic or vocabulary. The material may be complex or heavy with detail. To present technical material effectively, use the following guidelines from Dale Carnegie Training.Consider the amount of time available and prepare to organize your material. Narrow your topic. Divide your presentation into clear segments. Follow a logical progression. Maintain your focus throughout. Close the presentation with a summary, repetition of the key steps, or a logical conclusion.Keep your audience in mind at all times. For example, be sure data is clear and information is relevant. Keep the level of detail and vocabulary appropriate for the audience. Use visuals to support key points or steps. Keep alert to the needs of your listeners, and you will have a more receptive audience.TUJUAN INSTALASI SCADAMemberikan Informasi yang cukup kepada operator, sehingga dapat melaksanakan pengoperasian system dengan keandalan yang tinggi.Mempercepat penerimaan / pengiriman informasi.

30/03/2015UBOS3Copyright 1996-2001 Dale Carnegie & Associates, Inc.UPB WARUUPB CWANGJCCUPB CGRLGUPB UNGARMASTER KOM : DATA GENERALFRONT-END : MTS 60-80MASTER KOM : MTS 30-80MASTER KOM : MTS 30-80MASTER KOM : MICRO VAXMASTER KOM : MUTSUBISHIKONFIGURASI CONTROL CENTER PLN P2B (JAWA-BALI ) TH 19823Frequently, presenters must deliver material of a technical nature to an audience unfamiliar with the topic or vocabulary. The material may be complex or heavy with detail. To present technical material effectively, use the following guidelines from Dale Carnegie Training.Consider the amount of time available and prepare to organize your material. Narrow your topic. Divide your presentation into clear segments. Follow a logical progression. Maintain your focus throughout. Close the presentation with a summary, repetition of the key steps, or a logical conclusion.Keep your audience in mind at all times. For example, be sure data is clear and information is relevant. Keep the level of detail and vocabulary appropriate for the audience. Use visuals to support key points or steps. Keep alert to the needs of your listeners, and you will have a more receptive audience.30/03/2015UBOS4Copyright 1996-2001 Dale Carnegie & Associates, Inc.UPB WARUUPB CWANGJCCUPB CGRLGUPB UNGARMASTER KOM : DATA GENERALFRONT-END : MTS 60-80MASTER KOM : MTS 30-80MASTER KOM : MTS 30-80MASTER KOM : MICRO VAXMASTER KOM : MUTSUBISHIKONFIGURASI CONTROL CENTERPLN P2B (JAWA-BALI ) TH 19894Frequently, presenters must deliver material of a technical nature to an audience unfamiliar with the topic or vocabulary. The material may be complex or heavy with detail. To present technical material effectively, use the following guidelines from Dale Carnegie Training.Consider the amount of time available and prepare to organize your material. Narrow your topic. Divide your presentation into clear segments. Follow a logical progression. Maintain your focus throughout. Close the presentation with a summary, repetition of the key steps, or a logical conclusion.Keep your audience in mind at all times. For example, be sure data is clear and information is relevant. Keep the level of detail and vocabulary appropriate for the audience. Use visuals to support key points or steps. Keep alert to the needs of your listeners, and you will have a more receptive audience.30/03/2015UBOS5Copyright 1996-2001 Dale Carnegie & Associates, Inc.SUB UPBUPB CWANGJCCUPB CGRLGUPB UNGARMASTER KOM : VAX 6610FRONT-END : MICRO VAXMASTER KOM : MICROVAXMASTER KOM : MICROVAXMASTER KOM : MICRO VAXMASTER KOM : MICRO VAXKONFIGURASI CONTROL CENTERPLN P3B (JAWA-BALI ) TH 1995 s/d 2005UPB WARUMASTER KOM : VAX 6610FRONT-END : MICRO VAX5Frequently, presenters must deliver material of a technical nature to an audience unfamiliar with the topic or vocabulary. The material may be complex or heavy with detail. To present technical material effectively, use the following guidelines from Dale Carnegie Training.Consider the amount of time available and prepare to organize your material. Narrow your topic. Divide your presentation into clear segments. Follow a logical progression. Maintain your focus throughout. Close the presentation with a summary, repetition of the key steps, or a logical conclusion.Keep your audience in mind at all times. For example, be sure data is clear and information is relevant. Keep the level of detail and vocabulary appropriate for the audience. Use visuals to support key points or steps. Keep alert to the needs of your listeners, and you will have a more receptive audience.30/03/2015UBOS6Copyright 1996-2001 Dale Carnegie & Associates, Inc.SUB UPBUPB CWANGJCCUPB CGRLGUPB UNGARMASTER KOM : VAX 6610FRONT-END : MICRO VAXMASTER KOM : MICROVAXMASTER KOM : MICROVAXMASTER KOM : MICRO VAXMASTER KOM : MICRO VAXKONFIGURASI CONTROL CENTERPLN P3B (JAWA-BALI ) TH 2005UPB WARUMASTER KOM : SUN MicrosystemFRONT-END : SUN Microsystem6Frequently, presenters must deliver material of a technical nature to an audience unfamiliar with the topic or vocabulary. The material may be complex or heavy with detail. To present technical material effectively, use the following guidelines from Dale Carnegie Training.Consider the amount of time available and prepare to organize your material. Narrow your topic. Divide your presentation into clear segments. Follow a logical progression. Maintain your focus throughout. Close the presentation with a summary, repetition of the key steps, or a logical conclusion.Keep your audience in mind at all times. For example, be sure data is clear and information is relevant. Keep the level of detail and vocabulary appropriate for the audience. Use visuals to support key points or steps. Keep alert to the needs of your listeners, and you will have a more receptive audience.30/03/2015UBOS7Copyright 1996-2001 Dale Carnegie & Associates, Inc.JARINGAN 500 kV JAWA-BALISBBRTKDIRIPITON 2GRSIKPITON 1GRATIUNGARTMLYAPEDANMTWARMDRCNDEPOKSGLNGCBATUBEKSICWANGKBGANGNDULSRLYACLGONBDSLNCRATACIBNGRWALO7Frequently, presenters must deliver material of a technical nature to an audience unfamiliar with the topic or vocabulary. The material may be complex or heavy with detail. To present technical material effectively, use the following guidelines from Dale Carnegie Training.Consider the amount of time available and prepare to organize your material. Narrow your topic. Divide your presentation into clear segments. Follow a logical progression. Maintain your focus throughout. Close the presentation with a summary, repetition of the key steps, or a logical conclusion.Keep your audience in mind at all times. For example, be sure data is clear and information is relevant. Keep the level of detail and vocabulary appropriate for the audience. Use visuals to support key points or steps. Keep alert to the needs of your listeners, and you will have a more receptive audience.m VAX3500VAX6610ContrlRTURTU70150VAX6610m VAX3500FE200FE200m VAX4300RTURTU70150m VAX4300m VAX4300m VAX4300m VAX3400RTURTU70150m VAX3400m VAX4300m VAX4300SUNmSystemSUNmSystemm VAX3400RTURTU500500m VAX3400m VAX4300m VAX4300m VAX4300m VAX4300RTURTU70150m VAX4300m VAX4300VAX6610RTURTU70150DATABASEOFF LINEMASTERRTURTU70150JARINGAN CONTROL CENTERJAWA-BALIJCCRCCCWANGRCCUNGARSUBRCCRCCWARURCCCGRLGMIMIC BOARDSUNmSystemSUNmSystemSUNmSystemSUNmSystemSUNmSystemSUNmSystemSUNmSystemSUNmSystemSUNmSystemSUNmSystemMASTEREMSHISTORICALDTS

( R T U ) Remote Terminal Unit

Remote Terminal UnitAdalah suatu perangkat komputer yang dipasang di remote station atau dilokasi jaringan yang dipantau oleh control centre.RTU berfungsi sebagai pengumpul data dan melaksanakan perintah control centre.TUGAS POKOK RTUMengumpulkan data Status / Alarm dan Pengukuran kemudian mengirimkannya ke Control Center.Meneruskan perintah Control Center.R T UInput AnalogOutput DigitalOutput AnalogInput DigitalControl CenterMMITeleinformasiRTUGARDUINDUK / DISTRIBUSIMEDIA KOMUNIKASI( OPTIC, PLC, RADIO, KABEL DLL )200, 300,1200 BdMODEMKOMPUTERSLAVE MODEMKOMPUTERMASTER MODEMMODEMDIFUSSERDIFUSSERKOMUNIKASI CONTROL CENTER DENGAN RTUKOMPUTER FRONT-END KOMPUTERFRONT-END Teleinformasi:Digital Input : ( terima besaran analog dari proses untuk indikasi, alarm dll )Digital Output : ( signal digital yang diterima dari master atau Remot kontrol untuk buka, tutup, On, Off suatu alat dll )Analog Input : ( terima besaran analog dari proses untuk pengukuran )Analog Output : ( signal analog yang diterima dari master untuk diteruskan ke prosesTeleinformasi di PLNDigital Input disebut TS ( Telesignal ) yang digunakan untuk mengetahui posisi/status peralatan misal CB, DS, LI, ES, Tap Trafo dll )Digital Output disebut RC ( Remot Control ) yang digunakan Buka/Tutup, On/Off untuk CB, DS, LI, Naik/Turun Tap Trafo dan juga bisa untuk Start unit pembangkit.Analog Input disebut TM ( Telemetering ) yang digunakan untuk mengetahui besaran listrik misal MW, MX, A, I, V dll )Analog Output ini juga disebut RC analog yang digunakan untuk pengaturanPERALATAN PENUNJANG. Power SupplyModem.Media Komunikasi.PERALATAN UTAMA REMOTE STATIONRTU (Remote Terminal Unit ).Transducer ( Pengubah).Auxiliary Relay.RTUKOMPUTERSLAVE KOMPUTERMASTER CONTOH JARINGAN RTUKOMPUTER FRONT-END KOMPUTERFRONT-END RTURTURTURTURTURTURTURTURTURTURTU POINT TO POINT LOOP MULTI POINT/PARTYLINE SERIE STARRemote Terminal Unit

EPC 3200KAPASITAS MAKSIMUM

1024 Telesinyal

256 Remote Control

128 TelemeasuringTINGKATAN RTU

Level 1 : Central Processing Unit ( CPU )Level 2 : PIA (Peripheral Interface Adapter) ACIA (Asynchronous Comonication Interface Adapter )Level 3 : Input / Output InterfaceInterfaceCPUR T UInterfaceLevel 2Control CenterLevel 1ProsesLevel 3InterfacePCLevel 2Level 1Level 3CPUMEMInterfaceInterfaceAIMODEMDIAODOPOWER SUPPLYBD20I/OCPURACK RTU EPC3200MODEMCPUMODEMDOAODIADCCDAICONTROL CENTERTRANSDUCER( MW, MX, V, A, Hz )VTCTTSD ( CB, PMS ) TSS ( Alarm ) LOAD KORDINATORUNIT PEMBANGKITOCPROSESPOSISI TAP TRAFOGARDU-INDUKRTUMacam-macam modul EPC 3200CPU Microprocessor modul (MP49) Dialog modul (MP41) Memory modul(ME43)

Modul I/O dll-BD20 : Dataway rack-AI01/02 : Power Supply-CS41 : modul Supervisory-CS00/01/05 : Dataway Bus Regeneration-AL05/07 : Logic Acquisition-RL00/04 : Logic Restitution-RA00 : Restitution Analogic-AA11 : Analog Acquisition-AA03 : Analog/Digital Converter (ADC)-MD15/50 : MODEM-DF00/01 : Analog DiffusorMICRO PROCESSOR MODUL(modul MP 49)- 8 Bit microprocessor 6809/2MHz- 3 kBytes REPROM- 2 Ch Interface Komunikasi ( V24 / RS 232 ) dengan kecepatan 50 s/d 9600 BAUDS- Dataway Bus / Highway Bus Interface- LED Indikasi dan control switch.Ch 2Ch 1Long-startReady to sendReception CarrierP B Ch 1Switch manual ChIndikasi Chmprocessor resetP B Ch 2ResetNormalMP 49Highway busConnectorDIALOG MODUL ( MP 41 )Programmable timerWatch Dog5 kBytes REPROM7 kBytes Static RAMAsynchronous Komunikasi (V24) untuk TTY, Printer, PC( u/load Database ).Asynchronous Komunikasi (V24) Trransmission Ch 50 s/d 9600 BaudsLED Indikasi dan kontrol SwithPNCHReception CarrierLoad/manualReady to sendMP 41High SpeedtLow SpeedAuto ModeDebug ModeLOADDefaultSoftware startingHighway busConnectorWatchdogMMIMEMORY MODUL ( ME 43 )

1 Page 16 kBytes RAM 32 kBytes EEPROMBattery Backup untuk RAMPNCHME 43LOADStatus MemoryHighway busConnectorWatchdogMMISteady:Battrery & PS OK

5VS DefaultDATAWAY BUSFungsi :Distribusi Catu Daya ke modul-modul RTU.Penyalur Data, Address & signal Control (signal pertukaran antara CPU dengan I/O modul ).

Hardware :Dipasang dibagian belakang rack RTU.1 rack terdiri dari 18 Slot u/CPU, PS dan I/O modul.

DATAWAY BUS SIGNALPolariti feederControl SignalAnalog input control signal - 1 Masque line - 1 Accuisition Card ackn - 1 Restitution Card ackn - Answer line - Calling Search line - Sampling signal - Reset signal - Regeneration signal - 2 Serial Chain signal.

DATAWAY SIGNAL7 polariti feeder - 1 feeder + 15 V - 1 feeder - 15 V - 1 feeder + 5 V - 1 feeder +12 V - 1 feeder dan - 2 feeder common 0 VControl signal - 8 bidirectional address line - 8 bidirectional data line - 1 Interupt line

Analog input control signal - Analog / Digital converter strat - End of convertion - ADC gate opening command - Data byte select - Analog bus ( 2 line )

Supervisory Card ( modul CS41 )-Sebagai sumber polarity remote control-Monitoring RC polarity off-Monitoring temperatur di lemari RTU-Output alarm internal RTU. POWER SUPPLY-RTU EPC 3200 membutuhkan power supply + 5V, +12V, +/- 15V yang didapatkan dari modul AI 01 dan AI 02-Modul AI 01 merubah 48V menjadi +5V/12A dan +12V/1.5A-Modul AI 02 merubah 48V menjadi +15V/3A dan -15V/2AI/O PERIPHERALACQUISITION -Acq Logic: Switching, Alarm, Fault, Counting -Acq Analog: ADC, PengukuranRESTITUTION -Res Logic : Switching Control, Order, mimic order -Res Analog : Recorder, Indikator, Order(LFC)Analog Acquisition ( modul AA 11 )-16 masukan analogInput impedansi 500 Ohm -10 s/d +10V arus -20 s/d +20 mA-Masing-masing input menggunakan Flying Capacitor 1 kOhm500 OhmDari TransducersElemen input TMKe Analog Bus100 kOhm-Input tegangan 10 s/d +10V-Input arus 20 s/d +20 mAANALOG/DIGITAL CONVERTER (MODUL AA03)Berfungsi merubah besaran Analog yang datang dari modul Analog Acq menjadi Digital ( 8 bits ).

Skala konversi yang dimiliki 0 ; +5 mA 0 ; 10 mA +4 ; +20 mA -5 ; +5 mA -10 ; +10 mA Acquisition Logic ( modul AL 05/07 )Terdiri dari 32 masukan signal logic dan dibagi 4 Bytes ( 8 bits/Byte )Masukan tegangan 48 V/16 mAOpto-coupler galvanic insulationMasing-masing input dikonversi menjadi bit 0 atau 1

Restitution Logic ( modul RL 00 )

-Terdiri 8 selection output relay (normaly open )-Kemampuan kontak 60 W, 100 VA (max 2A / 220 V)-2 buah relay untuk Close dan untuk Open.-1 buah relay untuk Eksekusi.812OCOCKe proces- 48VExecutionCloseSelectionOpenModul RL 00Restitution Logic (modul RL 04/05)-Terdiri 64 output kontak-Spesifikasi kontak RL 04 : 5W, 200V ac/dc, 250 mA RL 05 : 30W, 250V ac/dc, 2A-Output dibagi 8 grup ( masing-masing grup 8 kontak.

Restitution Analogic (modul RA 00)-Terdiri 4 output analog-Impedansi 3 kOhm maksimum-Rangkaian D/A Converter dengan accurasi 1%.-Lama conversi 30 mS-Range : 0/+5 mA, +/-5 mA, 0/+10 mA, +/-10 mA 4/20 mA, -2.5/+2.5 mA.DAC8 bit20 kHzpolarityOutputanalogRESTITUTION ANALOGIC-0/+5 Ma+/-5 mA, 0/+10 mA+/-10 mA4/20mA2.5/+2.5 mA.SERVICE MODUL (Regeneration modul)CS00: Dipasang diantara CPU dengan Peripheral dan untuk meneruskan ke rack berikutnya.CS01: Dipasang di Rack paling akhir.CS05: Dipasang bila RTU hanya menggunakan 1 rack.

SERIAL CHAINKe rack berikutnyaJamperSlot terakhirCS00MODEM-Modem yang dipakai RTU EPC (MD50)-Programable dengan Pocket Terminal / PC-Frekwensi 300 s/d 3400 Hz-Kecepatan 50 s/d 1200 Bauds

MDCPUTMTCTSLFCRCCONTROL CENTERMDHzMXMWAKVRLTMRC, TSS, TSDKE UNIT PEMBANGKITPANEL CONTROLR T UI T F 2I T F 1I T F 3T D BSERANDANGADCRANGKAIAN PROSES SISTEM SCADA PLNTELEINFORMASITSD / TSS, RCPMSTM ( kV , MW, MX, A )Tap, RCTSDTM ( kV )TM ( Kv )Busbar 1PMTTrafoCTPTBusbar 2TD-AMPAOUTPUT( mAmp )TRANSDUCER ARUS / DC ARUSDCREFERENCESOURCEFREQUENCYCURRENTTRANSDUCERAUX ILIARY SUPPLYAMPLIFIEROUTPUT( mA )TRANSDUCER FREQUENCY / DC CURRENT INPUT AC54ANALOG SWITCHMODULATORAMPLIFIERTEGANGANARUS TRANSDUCER POWER / DC CURRENTOUTPUT( mA )TD-voltANALOG SWITCHMODULATORAMPLIFIERTRANSDUCER VOLTAGE / DC CURRENTOUTPUT( mA )UVOLTAGE TRANSFORMERSUMBER DC-48 VOLT & 110 VOLT ~~__Battery110 VDCRECTIFIERFUSEBOXMAIN USE220 / 380 VACLOAD~~__Battery48 VDCRECTIFIERFUSEBOXMAIN USE220 / 380 VACPLCT PRTUPABXLOAD+

-+

-+

-+

-DC-DB48VPANELPROTEKSIMKDC-DB110 VSISTEM DC 110VSISTEM DC 48V