    maxDNA is name of control system.

    maxDNA is developed by Metso Automation USA.

    maxDNA widely used for power plant automation.

    First maxDNA control supplied to RRVUNL Kota Unit-6.

    All the modules supplied to Kota unit were imported from USA.

    From then all the modules are being manufactured at our EDN

    Bangalore unit.

    maxDNA control system is customized for specific application.

    maxDNA CONTROL SYSTEM

  • 8/13/2019 MAX SESSION-I.PPT

    2/10

    maxDNATHE REMOTE PROCESSING UNIT(Control Cabinet)

    The equipment includes

    DPUs

    Field I/O modules

    Field terminations

    Communication networks

    Power supply unit

  • 8/13/2019 MAX SESSION-I.PPT

    3/10

    maxDNARPU COMPONENTS

    The Distributed Processing Unit (DPU4F) is theprocess controller.

    The Model 4F Distributed Processing Unit (DPU)

    is a multifunction controller and data acquisitionprocessor that executescontrol algorithms,sequence logic,sequence of events time tagged to 1 ms

    resolutiondata acquisition.

  • 8/13/2019 MAX SESSION-I.PPT

    4/10

    maxDNADPU4F (CONT.) The heart of the DPU is a database called the

    Distributed Point Management System (DPMS).The DPMS is fully aware of the tag names,

    hierarchy, and other text attributes of itsconfigured points. It is loaded with aconfiguration created by the Systems engineerand executes that configuration to provide thecontrol and data acquisition functions required.

    The DPU 4F resides directly on the MAXNETcommunications network without the need forservers.

  • 8/13/2019 MAX SESSION-I.PPT

    5/10

    P

    S

    P

    S

    P

    S

    P

    S

    P

    S

    P

    S

    D

    P

    U

    I/OI/OI/OI/OI/OI/O

    I/OI/OI/OI/OI/OI/O I/OI/O

    D

    P

    U

    I/OI/OI/OI/OI/OI/O

    Switch

    Switch

    I/OI/OI/OI/OI/OI/O I/OI/O

    Schematic arrangement of RPU Cabinet

    IOP382 eight pack rack

    I/O Bus

    Connector

    Field 24V

    Field 48V

    System 24V

    I/O Bus

    Connectors

    maxDNARPU Cabinet

  • 8/13/2019 MAX SESSION-I.PPT

    6/10

    maxDNAI/O Modules

    Analog Input Digital Input

    Part Number Description Part Number Description

    IOP301 Isolated analog input; 16 channels IOP330 24 Vdc common input; 16 channels

    IOP302 4-20mA common input; 16 channels IOP334 24 Vdc isolated input; 16 channels

    IOP303 3-wire RTD input; 8 channels IOP351 Form A/B relay; 16 channels

    IOP304 Thermocouple/emf input; 16 channels

    IOP305 Voltage common input; 16 channels

    Analog Output

    Part Number Description

    IOP320 4-20 mA common output, 8 channels

    Bus address 00 to FF (256)DI module address 0 to 31AO & DO module address 32 to 252

    DI Module

    one bus addressDO module one bus addressAI module two bus addressAO module eight bus address

    TYPES OF I/O MODULES USED

  • 8/13/2019 MAX SESSION-I.PPT

    7/10

    COMMISSIONING SEQUENCE

    A- PANEL POWER-UP Check cabinet installation as per drawing( system O&M manuals).

    Check for any physical damage.

    Checking of hardwares as per configuration diagram.

    Verify I/O module addresses.

    Verify that modules are properly inserted in back plane.

    Ensure that DPU mode switch is kept at F. Verify that all backplanes are connected with ribbon cable and terminator is put to last

    backplane slot.

    Remove all P2/P3 connectors from the I/O modules to isolate field terminations.

    Ensure the panel electronic & power supply ground earthing.

    Ensure that no wirings are loose terminated.

    Check for power supply before power-up.

    Ensure that power supply connectors are properly connected to backplanes.

    Switch on power supply and check for 24VDC supply.

    Observe that DPUs boot-up and LED indications.

  • 8/13/2019 MAX SESSION-I.PPT

    8/10

    B-COMMUNICATION WITH EWS Set the EWS and connect the peripherals including respective dongle card.

    Boot-up the EWS

    maxStartup program automatically start and minimizes.

    maxStartup software version is 4.2.1.SP-2

    Without dongle card maxStartup program can not be started.

    Power on network switches Connect the network cable as per layout

    Establish the communication with EWS.

    Verify the DPU address at EWS.

    Load the application software and verify the ACTIVE LED of I/O module aregreen. ACTIVE indication should not blink.

    Unfreeze the outputs. All the outputs freezed when full application software isloaded to DPU.

    Connect P2/P3 connectors sequentially and proceed for loop checking.