maxon 5500 specifications

Upload: dcarunchio

Post on 08-Aug-2018

233 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/22/2019 Maxon 5500 Specifications

    1/8

    Series "NP" & "RG" AIRFLOBurnersPerformance Selection Data

    5/88

    Page 5505

    Operation in shaded arearequires specialconsiderations

    Operation in shaded arearequires specialconsiderations

    OptimumD

    esignArea

    Optim

    umDe

    signA

    rea

  • 8/22/2019 Maxon 5500 Specifications

    2/8

    Inlet Feed Limitations:

    NP-I NP-II NP-III RG-IV

    1-1/4" end 4' 4' 2000 4'inlet flange KBtu/hr1-1/2" back 5' 5' 4500 5'

    inlets* KBtu/hr

    Performance Selection Data(cont'd.)

    Airstream velocity across and through your burner's mixingplates must be kept uniform and within desired limits by use of asilhouette profile plate through which the burner fires. A 6" (mini-mum) profile plate should be installed surrounding the interior ductwalls at the leading edge of your burners mixing plates.

    Optimum design ranges for the various burner types are shown

    in the above graphs. Velocities (SFPM) are measured with avelometer directly in the duct at the plane of the profile plate andleading edge of burner mixing plates.

    To determine profile opening areas, add burner displacementareas (Ft2/section) from Table 1 for your complete burner assemblyto "Net Free Area" of your duct:

    "Net Free Area" of Duct (Ft2) = Fan Volume (SCFM)Velocity (SFPM)

    Net Free Area (Ft2) + Burner Displacement (Ft2) = Profile Area (Ft2)

    Various duct size/profile area relationships may give slightlydifferent field site data than is shown in Table 2. Velocities should

    always be confirmed and established by use of a velometer onactual field site installation.

    Series "NP" & "RG" AIRFLOBurnersPage 5506

    *Note: For 36 back inlet sections, not more than 6"

    off any one leg

    Pilot Capacities: Nominally rated at25,000 Btu/hr with natural gas differen-tial pressures of 4-6" w.c.

    srotcaFyticoleV:1elbaT

    )MPFS(gninepoetalpeliforptarenrubssorcayticolevderiseD 0061 0081 0002 0022 0042 0062 0082 0003 0523 0053 0573 0004 0054 0005

    )cw"(etalpeliforptagnidaererusserpyticolevetamixoppA 61.0 02.0 52.0 03.0 63.0 24.0 94.0 75.0 46.0 770. 880. 00.1 62.1 55.1

    tnemecalpsiDrenruB:1elbaT tf( 2 )noitces/

    noitceS PN GR

    thgiartS"6 52.0 33.0

    thgiartS"21 05.0 66.0

    thgiartS"81 57.0 99.0

    thgiartS"42 00.1 23.1

    telnIkcaB"21 05.0 66.0

    telnIkcaB"63 02.1 05.1

    eeT"6x"21 06.0 57.0

    woblE"6x"6 54.0 06.0

    Optim

    umDe

    signA

    rea

  • 8/22/2019 Maxon 5500 Specifications

    3/8

    Series "NP" AIRFLOBurners

    Approximate Envelope Dimensions

    (Nominal, in Inches)

    4/95

    Page 5507

    Burner Sections(All burners shown are available in NP-I, II or III versions. Use one of these numbers (I, II or III) in place of asterisk (*)

    in burner designation when ordering.)

    NP- * -2424" Straight

    NP- * -1818" Straight

    NP- * -66" Straight

    or 6"PPilot

    NP- * -12 orNP- * -12B

    12" Straight or 12BBack Inlet

    NP- * -L6" X 6" Elbow

    NP- * -T12" X 6" Tee

    NP- * -36B36B Back Inlet

    Typical End View

  • 8/22/2019 Maxon 5500 Specifications

    4/8

    Page 5508 Series "NP" AIRFLOBurnersPilots, End Closures, and End Inlet Flange Sets

    NOTE: All open ends of burner assembly must be closed off with one of these end closures or pilots.One-piece cast end closures should not be used if temperature rise exceeds 300F.

    Typical End View

    Legend:

    1 - 1/8" test connection2 - 1/4" pilot gas connection

    3 - 14mm spark ignitor connection4 - 1/2" or 3/4" UV/FR connection

    bushed to 1/4" for FR5 - Alternate 1/4" angled FR location6 - 1/8" pilot gas connection7 - 1-1/4" NPT gas inlet

    Pilot End Plate Sets

    NP-EC-SI-3/4"UV(1 pc) Pilot Set w/

    SI

    NP-EC-SI-1/2"-FR(1 pc) End Closure

    Set w/SI

    Pilot Assembly Section

    NP-6P Pilot Sec-

    tion w/Built-in Pilotincludes end platepilot w/SI onto its

    own special 6"Series NP AIRFLO

    Burner assembly

    NP-Pak Pilot Setw/orifice/cock/

    tube/SI

    NP-Pak Pilot Setw/Adj. Orifice/SI

    NP-Pak Pilot Setw/SI

    Common Dimensions (Nominal, in Inches)

    PIpe threads on this page conform to NPT(ANSI Standard B2.1)

    Plain End Closure Sets End Inlet & Pilot Flange Sets

    NP-EC (1 pc)

    End Closure Set

    NP-EP (2 pc)

    End Plate Set

    NPF- 1-1/4"- FR-SI

    (2 pc) Pilot Set w/SI

    NPF- 1-1/4"- EP

    (2 pc)End InletFlange Set

    NPF- 1-1/4" -FR-SI

    (1 pc) Pilot Set w/SI

  • 8/22/2019 Maxon 5500 Specifications

    5/8

    Series "RG" AIRFLOBurners

    Approximate Envelope Dimensions(Nominal, in Inches)

    5/88

    Page 5509

    Burner Sections

    Typical End View

    RG-IV-66" Straight or6"P Pilot

    RG-IV-12 orRG-IV-12B12" Straight or 12B

    Back Inlet

    RG-IV-1818" Straight RG-IV-2424" Straight

    RG-IV-L6" X 6" Elbow RG-IV-T12" X 6" Tee RG-IV-36B36B Back Inlet

  • 8/22/2019 Maxon 5500 Specifications

    6/8

    Series "RG" AIRFLOBurnersPilots, End Closures, and End Inlet Flange Sets

    NOTE: All "open" ends of burner assembly must be closed off with one of these end closures or pilots.

    One piece cast end closures should not be used if temperature rise exceeds 300F.

    Page 5510

    Pipe threads on this page conform to NPT(ANSI Standard B2.1)

    Legend:1 - 1/8" test connection

    2 - 1/4" pilot gas connection3 - 14mm spark ignitor connection4 - 1/2" UV/FR conn. bushed to 1/4" for FR

    5 - Alternate 1/4" angled FR location6 - 1/8" pilot gas connection

    7 - 1-1/4" NPT gas inlet

    Typical End View

    Pilot Assembly Section

    Common Dimensions(Nominal, in Inches)

    RG-EP (2 pc)End Plate Set

    RGF- 1-1/4" -FR-SI(1 pc) Pilot Set w/SI

    RGF- 1-1/4"- EP

    (2 pc)End InletFlange Set

    RGF- 1-1/4"- FR-SI(2 pc) Pilot Set w/SI

    Pilot End Plate Sets

    RG-Pak Pilot Setw/ SI

    RG-Pak Pilot Setw/orifice/cock/tube/SI

    RG-6P Pilot Sec-

    tion w/Built-in Pilotincludes end plate

    pilot w/SI and aspecial 6" Series

    RG AIRFLO

    Burner assembly

    Plain End Closure Sets End Inlet & Pilot Flange Sets

    RG-Pak Pilot Setw/Adj. Orifice/SI

  • 8/22/2019 Maxon 5500 Specifications

    7/8

    "NP" & "RG" AIRFLO Burners

    Accessories / Replacement ItemsDimensions, Nominal in Inches

    Page 5511

    Division Plate

    5/88

    1/4" dia.

    14mm Spark Ignitor

    Flame Rod (1/4" NPT)

    Adjustable Orifice

    Provides isolation of burner feed where desirable.

    Profile Plate Bracket

    Provides support for profile within closed burner loop.

    Support Bracket

    Normally used in pairs as shown here.

    Mount to burner assembly at any joint.

    External Mounting Assembly

    External Mounting Plate Used with typical pilot Opening Required

    Frequently used to provide easy accessibil ity to spark ignitor and flame supervision components.

    Includes Mounting Plate

    with two (2) feed-throughinsulators for internal

    mounting of Spark Ignitorand Flame Rod.

  • 8/22/2019 Maxon 5500 Specifications

    8/8

    "NP" & "RG" AIRFLOBurnersPage 5512

    Notes