1 MCset 4 range 1 to 24 kV Contents Presentation 2 Field of application 2 Continuity of service and complete safety 3 MCset, a comprehensive solution 4 Quality assurance - environment 7 MCset 4 range 8 Description 8 Technical characteristics 10 Operating conditions 11 Protection of people 12 Specific applications 13 Choice of functional units 14 Cubicle description 16 AD incomer and feeder - RD direct incomer 16 CL - GL line-up bussectioning 17 TT busbar metering and earthing 18 DI fuse switch feeder 19 Protection, monitoring and control 20 Protection system 20 Sepam series 20, series 40, series 80, Sepam 100 21 Instrument transformers 23 Switchgear 26 Withdrawable parts 26 DI switch cubicle 30 Accessories 33 Withdrawable parts extraction 33 Installation 35 Implementation examples 35 Connections 36 Appendix 38 Cubicle equipment 38 Current transformers (Selection guide) 39 A few references 40

Upload: buidat

Post on 28-Apr-2018

239 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

1

MCset 4 range1 to 24 kV

Contents

Presentation 2Field of application 2Continuity of service and complete safety 3MCset, a comprehensive solution 4Quality assurance - environment 7

MCset 4 range 8Description 8Technical characteristics 10Operating conditions 11Protection of people 12Specific applications 13Choice of functional units 14

Cubicle description 16AD incomer and feeder - RD direct incomer 16CL - GL line-up bussectioning 17TT busbar metering and earthing 18DI fuse switch feeder 19

Protection, monitoring and control 20Protection system 20Sepam series 20, series 40, series 80, Sepam 100 21Instrument transformers 23

Switchgear 26Withdrawable parts 26DI switch cubicle 30

Accessories 33Withdrawable parts extraction 33

Installation 35Implementation examples 35Connections 36

Appendix 38Cubicle equipment 38Current transformers (Selection guide) 39

A few references 40

Page 2: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

2

6328

0M

T200

5187

158

MT2

0052

Presentation Field of application

MCset adapts to all electrical power distribution requirements from 1 to 24 kV MCset is an indoor, metal-clad switchgear unit intended for the MV section of HV/MV substations and high power MV/MV substations.

MCset offers you:b pre-engineered and adaptable solutions tailored to your specific requirementsb significantly reduced maintenanceb local support centres throughout the world.

MCset gives you the advantages of:b continuity of service for your networksb enhanced safety for your staff and operationsb optimized investment throughout the life of your installationb the possibility of integrating your medium voltage switchboard in a monitoring and control system.

ApplicationsPower plantsb Auxiliary substations

Industryb Oil & gasb Chemical industry b Metallurgyb Car industryb Miningb Cement plantsb …

Infrastructureb Airportsb Portsb Hospitalsb Water treatmentb …

Page 3: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

3

PE

5638

6M

T200

58E

N

Presentation Continuity of service and complete safety

MCset is solidly based on extensive experience acquired throughout the world and provides your networks with a high level of dependability and safety.MCset integrates a host of innovative solutions designed around proven techniques: high performance switchgear, digital protection, monitoring and control systems, enclosures capable of withstanding internal arcing.From its very conception, MCset has taken account of three key user requirements:

Reliabilityb Type testing was carried out for each performance level in the MCset range.b The design, manufacturing and testing of MCset was carried out according to ISO 9001: 2000 quality standard.b Three-dimensional computer modeling techniques were used to study the electrical fields.

Simplicity b A user interface which is easily understood by everybody.b Interlocks and padlocks preventing operator errors.b Sepam-type protection units enabling on-site information retrieval without any additional devices.b Maintenance limited to simple, routine operating checks and cleaning and greasing every 5 to 10 years.b Easy installation due to identical civil engineering dimensions for all cubicles and installation being possible against a wall.

Safetyb Operations are all performed from the front, including access to connections and busbars.b Racking in and out is only possible with the door closed.b The power-on indicator is situated on the front of the functional unit.b The earthing switch has making capacity.b One single ‘‘anti-reflex” handle is used for all MCset operations.b Internal arc withstand developed for all functional units.

Page 4: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

4

PE

5517

0P

E55

134

MT2

0062

Presentation MCset, a comprehensive solution

MCset provides the most efficient means to control and protect a wide range of applications.Due to the devices it comprises, MCset can be easily integrated into a monitoring and control system.

Sepam protection and control unitsSepam series 20, series 40 and series 80 digital protection relays take full advantage of Merlin Gerin experience in electrical network protection.Sepam series 20, series 40 and series 80 provides all the necessary functions:b effective protection of people and propertyb accurate measurements and detailed diagnosisb integral equipment controlb local or remote indication and operation.

Easy evolutionAddition of communication, digital I/O’s, analog output, or temperature acquisition are possible due to its modular design.

PowerMeter and Circuit Monitor metering unitsThe PowerLogic PowerMeter replaces a full complement of basic analog meters. This cost effective, high performance meter provides a full complement of accurate true-rms metering values.The PowerLogic series 3000/4000 Circuit Monitor is designed for critical power users and large energy consumers, to provide the information needed to confidently enter the evolving world of deregulation.It can be adapted to meter almost any time-of-use or real-time rate.

Monitoring and controlMCset can be easily:b integrated into an existing monitoring and control system:communication of Sepam digital relay or PowerMeter/Circuit Monitor metering device through a standard protocol (Modbus)b integrated into a SMS PowerLogic electrical installation monitoring system.

Page 5: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

5

Sepam

Sepam

CM/PM

TCP/IP over Ethernet

Front socketHub

EGX400

PE

5513

8P

E55

139

PE

5514

0P

E55

137

Presentation MCset, a comprehensive solution (cont.)

MCset Transparent Ready™ optionMCset switchboards integrate Web technologies so that you can find out information about your electrical installation as easy as opening a Web page.All you need is a standard Web browser and a PC connected to your local area network.

Simple choiceA simple choice between TRe-1 and TRe-2 service levels allows you to easily order your Transparent Ready™ MCset switchboard.A customized level is also available.Your Transparent Ready™ MCset switchboard comes equipped with a Web server including Web pages dedicated to power equipment data.

Easy commissioningTransparent Ready™ equipment is delivered ready to connect and commission. A Quick Start guide, packaged with your switchboard, provides three easy-to-follow steps.

Functionalities provided TRe-1 TRe-2

Instantaneous readingsDisplays automatically updated meter values

b b

Circuit summary Displays the RMS current 3-phase average (A),the real power (kW), the power factor, the circuit breaker status (if applicable), etc.

b b

Load current summaryDisplays the current RMS value for each phase (A), for all circuits

b b

Demand current summaryDisplays the average demand current value for each phase (A), for all circuits

b b

Power summaryDisplays the present demand (kW), the peak demand (kW) and the times and dates of the records

b b

Energy summary Displays the energy (kWh) the reactive energy (kvarh), and the times and dates of the records

b b

Instantaneous readings, all devices Displays automatically updated meter values for all the communicating devices in the equipment

b

Basic historical data logging, energy and trendingDisplays automatically updated meter values for all the communicating devices in the equipment

b

Log displaysDisplays data as time curves, or tables

b

Export of data tablesAllows data tables to be exported in a standard Windows format

b

DE

5749

2EN

MCset switchboard

Page 6: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

6

MT2

0064

Presentation MCset, a comprehensive solution (cont.)

Schneider Electric Services, by your sidethroughout the life of your installationSpecifyingWe help you to define your solutions: selection guide, technical assistance, advice…

ImplementingWe oversee the completion and commissioning of your installation: design, cost optimization, guaranteed performances and dependability, commissioning tests, etc.

OperatingWe help run your daily operations in real time: maintenance contract, technical assistance, supply of replacement parts, corrective and preventive maintenance, operation and maintenance training, etc.

ModernizingWe can bring the performance of your installation up to date:installation audit, switchgear diagnosis, adaptation and modification, end of life recycling, etc.

Examples of services providedWarranty extensionA warranty extension is proposed if your installation is checked by ourselves before being commissioned.

Circuit breaker-contactor diagnosisThroughout the life of the equipment, it is possible to carry out routine measurement of its characteristics in order to optimize maintenance. This service may be part of a global installation maintenance contract.

End-of-life recyclingSchneider Electric Services has an operational subsidiary allowing you to recycle your medium voltage switchgear.

Modernizing Specifying

ImplementingOperating

MT2

0065

EN

Page 7: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

7

PE

5673

1P

E56

734

Presentation Quality assurance - environment

Certifi ed quality: ISO 9001

A major assetIn each of its units, Schneider Electric integrates a functional organization whose main role is to check quality and monitor compliance with standards.This procedure is:b uniform throughout all departmentsb recognized by many customers and approved organizations.But above all, it is its strict application that has allowed us to obtain the recognition of an independent organization: The French Quality Assurance Association (AFAQ).The quality system for the design and manufacture of MCset is certified to be in conformity with the requirements of ISO 9001: 2000 quality assurance standard.

Strict and systematic checksDuring manufacture, each MCset functional unit is subject to systematic routine testing with the aim of checking the quality and conformity of the following features:b sealing testb filling pressure testb measuring of opening and closing speedsb measuring of operating torqueb dielectric testb testing of safety systems and interlocksb testing of low voltage componentsb conformity with drawings and diagrams.The results obtained are recorded and approved by the quality control department on each device’s test certificate. This therefore guarantees product traceability:b checking SF6 switchgearv sealing testv filling pressure test.

Protected environmentAs part of the group’s environmental policy, Schneider Electric Services provides you with an operational subsidiary to recover medium voltage switchgear and thus eliminate any discharge to atmosphere.In order to help you protect the environment and to relieve you of any concerns in terms of stock or dismantling, Schneider Electric Services offers to take back your equipment at the end of its life. MCset has been designed with environmental protection in mind:b the materials used, insulators and conductors are identified, easily separable and recyclable.b the SF6 can be recovered at the end of the equipment’s life and reused after treatment.b production sites are certified to ISO 14001.

DE

5673

3

Page 8: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

8

MCset 4 range Description

PE

5655

9

Sepam

Busbars

Wiithdrawable part

Current transformers

Cablesconnection

LV control cabinet

Voltagetransformerscompartment

Page 9: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

9

MCset 4 range Description (cont.)

LSC2B (Loss of Service Continuity IEC 62271-200):this category defines the possibility of keeping other compartments energised (in service) when opening a main circuit compartment.

Make up of a MCset 4 switchboardMCset 4 switchboards are made up of several interconnected functional units. Power connections are made between functional units within a switchboard via a single busbar.The electrical continuity of all metal frames is provided by the connection of each functional unit’s earthing busbar to the switchboard’s main earthing circuit. Low voltage wiring trays are provided in the switchboard above the LV control cabinets.LV cables can enter the switchboard through the top or bottom of each functional unit.

Description of a functional unitA functional unit comprises all equipment in the main and auxiliary circuits which together provide a protection function. Each functional unit combines all the components which are required to fulfil this function:

the cubiclethe protection, monitoring and control systemthe withdrawable part.

The cubicleThe cubicle is of LSC2B (Loss of Service Continuity Category) type as defined by IEC standard 62271-200, in other words the medium voltage parts are compartmented using metal partitions (PM class) which are connected to earth and which separate:

the busbarsthe withdrawable part (circuit breaker, disconnector truck or earthing truck)MV connections, earthing switch, current sensors and voltage transformers

as required.MCset 4 guarantees a high level of protection of people; when a compartment containing a main circuit is open, the other compartments and/or functional units may remain energised.The low voltage auxiliaries and monitoring unit are in a control cabinet separated from the medium voltage section.Six basic cubicle layouts are offered:

Incomer or feeder ADDirect incomer RDLine up bussection CL - GLBusbar metering and earthing TTFuse switch feeder DI

AD and CL cubicles have withdrawable circuit breaker.

The protection, monitoring and control systemThis includes:

Sepam, protection, monitoring and control unitcurrent sensors, which may be of 3 types:

v conventional current transformersv low voltage toroid type current transformersv LPCT

zero sequence core balance current transformers (CSH type).

The withdrawable partThis includes:

the circuit breaker, the earthing truck with its closing and opening mechanism, or the disconnector truck

the lever-type propulsion mechanism for racking in-outinterlocks to fix the withdrawable part on the fixed part either in service position or

disconnected.

bbb

bbb

bbbbb

bb

b

b

bb

Page 10: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

10

MCset 4 range Technical characteristics

Technical dataRated voltage

(kV) 24Rated insulation levelPower frequency withstand voltage 50 Hz - 1 min

(r ms kV) 50

Lightning impulse withstand voltage 1.2/50 µs

(kV peak) 125

Nominal current and maximum short time withstand current (1)

Functional unit with circuit breakerShort time withstand current Ith. max (kA/3 s) 16

25(kA/1 s) 31.5

Rated current In max busbars (A) 2500 (2)

In CB (A) 63012502500

Functional unit with fuse switch (DI cubicle)Short time withstand current Ith. max (kA) 31.5 (3)

Rated current In max y (A) 200Internal arc withstand

(kA/1 s) 25

(kA/0.15 s) 31.5

Protection degreeIP3XIP4XIPX1 (2)

(1) For functional units equipped with circuit breakers, the breaking capacity is equal to the short time withstand current. In all cases, the device peak making capacity is equal to 2.5 times the short time withstand current. (2) For higher performances, consult us(3) Limited by fuses.

IAC (internal arc classification):The metal enclosed switchgear may have different types of accessibility on the various sides of its enclosure. For identify purpose of different sides of the enclosure, the following code shall be used (according to IEC 62271-200 standard).A: restricted access to authorized personnel onlyF: access to the front sideL: access to the lateral sideR: access to the rear side.

PE

5673

2

Page 11: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

11

MT2

0072

MCset 4 range Operating conditions

Operating conditionsNormal operating conditions, according to IEC 62271-1 for indoor switchgear

Ambient air temperature:less than or equal to 40°Cless than or equal to 35°C on average over 24 hoursgreater than or equal to – 5°C.Altitude:less than or equal to 1000 mabove 1000 m, a derating coefficient is applied (please consult us).Atmosphere:no dust, smoke or corrosive or inflammable gas and vapor, or salt

(clean industrial air).Humidity:average relative humidity over a 24 hour period y 95%average relative humidity over a 1 month period y 90%average vapor pressure over a 24 hour period y 2.2 kPaaverage vapor pressure over a 1 month period y 1.8 kPa.

Specific operating conditions (please consult us)MCset 4 has been developed to meet the following specific conditions:

temperature (possible derating)corrosive atmospheres, vibrations, (possible adaptation).

Storage conditionsIn order to retain all of the functional unit’s qualities when stored for prolonged periods, we recommend that the equipment is stored in its original packaging, in dry conditions sheltered from the sun and rain at a temperature of between – 25°C and + 55°C.

StandardsThe MCset 4 range meets the following international standards:

IEC 62271-1: clauses common to high voltage switchgearIEC 62271-100: high voltage alternating current circuit breakersIEC 62271-102: alternating current disconnectors and earthing switchesIEC 62271-103: switches for rated voltages above 1 and less than 52 kVIEC 62271-200: metal-enclosed switchgear for alternating current

at rated voltages of between 1 and 52 kVIEC 60282-2: high voltage fusesIEC 60255: measurement relay and protection unit (Sepam)IEC 60044-1: current transformersIEC 60044-2: voltage transformers.

bvvvbvvbv

bvvvv

bb

bbbbb

bbbb

Page 12: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

12

MT2

0076

PE

5673

0

MCset switchboard with tunnel

MCset 4 range Protection of people

MCset 4 internal arcBasic version (gas exhaust) MCset 4 is designed to eliminate the effects of internal arcing in total safety, due to:

metal flaps positioned above the enclosure, which in the case of internal fault, limit overpressure in the compartments.

nonflammable materials used for the cubicle.Internal arc versionMCset 4 is designed to withstand and protect operators in the case of failure due to an internal arc. MCset 4 has been successfully tested using type tests.Protection against internal arcing is available on 25 kA and 31.5 kA ratings.MCset 4 proposes several options to install an internal arc switchboard.

3-sided internal arc protection For an MCset 4 switchboard fitted against a wall, access to the rear of the cubicle is impossible. Internal arc protection on 3 sides is sufficient.

4-sided internal arc protectionIn the case of an MCset 4 switchboard installed in the middle of a room, internal arc protection on 4 sides is necessary in order to protect an operator who goes behind the cubicle.

Installation in a room with limited ceiling height:height exceeding 2.8 m, potential for installing a tunnel above the switchboard

to prevent reflection of hot gases on the ceiling.Ceiling height Tunnel2.8 m < h < 4 m Mandatoryh > 4 m Not mandatory

Internal arcing detector MCset 4 has 2 systems that can detect internal arcing and switch off the power supply so as to limit the fault duration.

electromechanical detectorThis system employs a positive security electromechanical tripping circuit, positioned on the cubicle’s flap valves. This set transmits the information to the Sepam to give the opening order to the circuit breaker located upstream of the fault.

optic detector (VAMP system)Internal arcing is detected by optical sensors which will measure the light caused by the initiation of arcing. Based on this information, an electronic module, after processing the information, will give the opening order to the circuit breaker located upstream of the fault.

Dependable mechanical control devicesAll operations are carried out from the front face, including access to connections and busbars.The user is guided through icon-diagrams on each front panel making it easy to understand the operating sequence and device status.Interlocks and padlocks prevent operator errors.Several additional levels of security also protect operators:

racking in and out is only possible with the door closed.the very extensive set of mechanical and electrical interlocks do not allow operator

error. These can be added to by key locks or padlocks according to specific operating procedures. Each selector can be fitted with one to three padlocks.

all operations are carried out from the front face including access to connections and busbars.

the voltage present indicator is located on the front face of the functional unit, in the immediate vicinity of the earthing switch control.

disarming of circuit-breaker when racking out. This function enables the circuit breaker control springs to be disarmed during the extraction operation.

Locking of withdrawable part/cable compartment. This function disables the possibility of racking the withdrawable part in if the front panel (cable compartment) is not installed.

Locking of the MV door open if the LV plug of the circuit breaker is not plug-in.

b

b

b

b

bv

b

v

v

bb

b

b

b

b

b

Page 13: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

13

MCset 4 range Specific applications

Seismic areasMCset 4 meets international seismic specifications. Test procedures follow IEC 60068-3-3 standard.MCset 4 is qualified following the standard:

ENDESA.

DEP Shell MCset 4 switchboards are certified by Shell in compliance with DEP 33.67.51.31 Gen (November 2006) for MV equipments.

b

PE

5657

5

Page 14: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

14

MCset 4 range Choice of functional units

The MCset 4 range comprises 10 functional applications.The table below can be used to link requirements to functional units and gives basic information on the general composition of each unit.Selection guideYou want to supply power to a transformer.The chosen solution is a transformer feeder/breaker.The corresponding functional unit will therefore be a TF-B, comprising a AD cubicle equipped with a withdrawable circuit breaker, and transformer application Sepam.

Function Incomer Feeder

Line Transformer Generator Line Transformer Transformer

Functional unit LI-B TI-B GI-B LF-B TF-B TF-S

Cubicle AD4 AD4 AD4 AD4 AD4 DI4

Device Circuit breaker Circuit breaker Circuit breaker Circuit breaker Circuit breaker Fuse-switch

Sepam protection relay series 20series 40series 80

SubstationS20S40, S41, S42S80, S81, S82

TransformerT20T40, T42T81, T82, T87

Generator

G40G82, G88, G87

SubstationS20S40, S41, S42S80, S81, S82

TransformerT20T40, T42T81, T82, T87

TransformerT20T40, T42

Single line diagrams

MT2

0080

Sepam

MT2

0081

MT2

0082

The direct incomer is produced using a specific cubicle: RD4.

Page 15: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

15

MCset 4 range Choice of functional units (cont.)

Function Feeder Bussectioning Metering and busbar earthing

Capacitor Switchboard Substation

Functional unit CB-B BS-B SS-B BB-V

Cubicle AD4 CL4 and GL4 AD4 TT4

Device Circuit breaker Circuit breaker Circuit breaker

Sepam protection relay series 20series 40series 80

Capacitor

C86

BusbarB21, B22

B83

SubstationS20S40, S41, S42S80, S81, S82

Single line diagrams

MT2

0081

MT2

0084

MT2

0081

MT2

0078

Page 16: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

16

DE

5508

5D

E57

760

AD4

1

7

2

4

5

6

3

AD4

Cubicle description AD - Incomer and feederRD - Direct incomer

DE

5778

2

RD4

H

W

RD4

H

W D

CharacteristicsAD4 RD4

Rated voltage kV 24 24Rated insulation level kV r ms 50 Hz - 1 min 50 50

kV impulse 1.2/50 µs 125 125Rated current A 630 b b

1250 b b

2500 b b

Breaking capacity kA 31.5 –Short time withstand current kA r ms 1 s 31.5 31.5

kA r ms 3 s 16 or 25 16 or 25Dimensions mm Width (W) 900 900

Height (H) 2325 2325Depth (D) (1) 1750 1750

Approximative weight (2) kg 1100 930

(1) Overall + 175 mm for 4-sided internal arcing protected switchboards, or 2 sets of CT’s.(2) Fully equipped cubicle.

MV components1 busbars for cubicle interconnection2 withdrawable part (SF1-2 circuit breaker, disconnector truck or earthing truck)3 MV connections by cables accessible from the front face4 earthing switch5 current sensors6 voltage transformers (optionally equipped with withdrawable fuses)LV control cabinet7 low voltage auxiliaries and protection, monitoring and control unit

are in one control cabinet, separated from the medium voltage part.

DE

5776

1

DE

5776

5

DE

5776

6Sepam Sepam

1

7

4

5

3

D

Page 17: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

17

DE

5509

0

DE

5676

5

V/H W/ clear rese

I tri

alarW

O

L L L

M

1

5

2

4

1

5

3

CL4 GL4

CL4 and GL4

Cubicle description CL - GLLine-up bussectioning

CharacteristicsCL4 - GL4

Rated voltage kV 24Rated insulation level kV r ms 50 Hz - 1 min 50

kV impulse 1.2/50 µs 125Rated current A 630 b

1250 b

2500 b

Breaking capacity kA 31.5Short time withstand current kA r ms 1 s 31.5

kA r ms 3 s 16 or 25Dimensions mm Width (W) 900 (x 2)

Height (H) 2325Depth (D) (1) (3) 1750

Approximative weight (2) kg 1600 (CL4 + GL4)

(1) Overall + 175 mm for 4-sided internal arcing protected switchboards.(2) Fully equipped cubicle.(3) Overall + 500 mm for upstream CTs.

The bussectioning functional unit comprises 2 cubicles mounted side by side (one cubicle equipped with a circuit breaker, the other with a busbar return).

MV components1 busbars to connect the bussectioning functional unit with other switchboard

cubicles 2 withdrawable part (circuit breaker SF1-2, disconnector truck or earthing truck)3 current sensors4 voltage transformers (optionally equipped with withdrawable fuses)LV control cabinet5 low voltage auxiliaries and protection, monitoring and control unit

are in one control cabinet, separated from the medium voltage part.

W W

H

D D

DE

5776

2

DE

5776

7

Sepam

Page 18: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

18

3

2

4

1DE

5509

5

TT4

TT4

Cubicle description TTBusbar metering and earthing

D

H

W

CharacteristicsTT4

Rated voltage kV 24Rated insulation level kV r ms 50 Hz - 1 min 50

kV impulse 1.2/50 µs 125Rated current A 630 b

1250 b

2500 b

Short time withstand current kA r ms 1 s 31.5kA r ms 3 s 16 or 25

Dimensions mm Width (W) 900Height (H) 2325Depth (D) (1) 1750

Weight kg 560

(1) Overall + 175 mm for 4-sided internal arcing protected switchboards.

MV components1 busbars to connect the TT functional unit with other switchboard cubicles2 earthing switch3 voltage transformers (optionally equipped with withdrawable fuses)LV control cabinet4 low voltage auxiliaries and protection, monitoring and control unit

are in one control cabinet, separated from the medium voltage part.

DE

5776

3

DE

5776

8

Page 19: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

19

4

1

2

3

Cubicle description DIFuse switch feeder

DE

5777

1

DI4

W

H

D

CharacteristicsDI4

Rated voltage kV 24Rated insulation level kV r ms 50 Hz - 1 min 50

kV impulse 1.2/50 µs 125Rated current A 200 b

Breaking capacity (2) kA 31.5Short time withstand current (2) kA r ms 31.5Dimensions mm Width (W) 900

Height (H) 2325Depth (D) (1) 1750

Weight kg 640

(1) Overall + 175 mm for 4-sided internal arcing protected switchboards.(2) Limited by fuses.

DI cubicles including a fuse switch are used to supply power and protect low power transformers.E.g.: auxiliary service transformers in primary substations.All operations are carried out from the front face, including access to connections and busbars. All functional interlocks meet recommendations in IEC 62271-200: b the switch is only possible to close if the earthing switch is open and the connection access panel is in placeb closing of the earthing switch is only possible if the switch is open b opening of the access panel to medium voltage connections and fuses is only possible of the earthing switches upstream and downstream of the fuses are closedb the switch is locked in the open position when the access panel is taken off.The voltage presence indicator is situated on the front face of the functional unit, integrated in the switch’s control panel.

MV components1 busbars to connect the DI functional unit with other switchboard cubicles 2 switch - earthing switch3 MV fusesLV control cabinet4 low voltage auxiliaries and protection, monitoring and control unit

are in one control cabinet, separated from the medium voltage part.

DI4

DE

5776

4D

E57

770

Page 20: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

20

PE

5517

0Protection, monitoring and control

Protection systemSepam range

Each MCset functional unit can be equipped with a comprehensive protection, monitoring and control system comprising:b instrument transformers to measure the necessary electrical values (phase current, residual current, voltages, etc.)b protection relays, providing functions adapted to the part of the network to be protectedb metering equipment, to inform operatorsb low voltage relaying, i.e. to provide control of the breaking device and of the withdrawable partb various auxiliaries: secondary circuit test units, etc.

Protection relaysmetering equipment

Switchgear (circuit breaker and contactor)

Instrument transformers

Sepam: protection, monitoring and control unitsSepam, is a range of digital monitoring protection and control units.Sepam is at the centre of the protection, monitoring and control system for MCset functional units: all the necessary protection, metering, control, monitoring and signalling functions are carried out by Sepam.

Like the MCset range, the Sepam range is a range of units defined to provide an optimal solution for each application, and includes (eg):b Sepam S, substation incomer and feederb Sepam B, bussectioningb Sepam T, transformer feederb Sepam G, generator feederb Sepam C, capacitor feeder.

Sepam advantagesReliabilityb Over 20 years of experience in multi-function digital protection relaysb Over 150,000 Sepam units in service in more than 90 countries.Qualityb Quality design based on dependability studies and strict definition of environmental constraints: temperature, pollution, EMC, dielectric strength…b Quality manufacturing based on procurement agreements with suppliers and inspection throughout all manufacturing phases.Simplicity of useb Ergonomic and intuitive user machine interface (UMI).b User friendly and powerful PC setting softwareb Predefined functions implemented by simple parameter setting.Easy installation b The same, easy-to-install remote modules for all Sepam units.Intuitive useb Clear graphic LCD display of all data required for local operation and installation diagnosisb Working language may be customized to be understood by all users.

Protection chainThe Sepam protection units combined with innovative current sensors provide a comprehensive measurement, protection and energy management chain *.A high performance, economical solutionThe modular Sepam offer provides a cost effective solution tailored to every requirement.Easy to order and installAll the components in the protection chain are referenced and can be delivered very quickly.The power of a multi-functional digital unitSepam is more than a simple protection relay, it is truly multi-functional unit notably offering:b circuit breaker diagnosis functions (switching counter and time, rearming time, cumulated broken A2)b direct circuit breaker control whatever type of release unitb remote equipment operation using the modbus communication option.

(*) Please check in the Sepam catalogue the sensor to use with each Sepam version.

DE

5777

2

Page 21: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

21

PE

5638

4

Sepam 100 MI Sepam 100 LD Sepam 100 LA

PE

6011

6

PE

6011

7

PE

6011

8

Protection, monitoring and control

Sepam series 20, series 40, series 80,Sepam 100

Sepam series 80 modular architecture1- Base unit, with integrated or remote advanced User Machine Interface.2- Parameter and protection settings saved on removable memory cartridge.3- 42 logic inputs and 23 outputs relays with 3 optional modules providing 14 inputs and 6 outputs.4- 2 independent Modbus communication ports.b direct connection to 2-wire RS 485, 4-wire RS 485 and fiber optic networks;b connection to Ethernet TCP/IP network via PowerLogicSystem webserver (Transparent Ready™). 5- Processing of data from 16 temperature sensors.6- 1 low level analog output, 0-10 mA, 4-20 mA or 0-20 mA.7- Synchro-check module8- Software tools:b Sepam parameter and protection setting and control logic customization;b local or remote installation operation;b retrieval and display of disturbance recording data.

The Sepam range of protection relays is designed for the operation of machines and electrical distribution networks of industrial installations and utility substations at all levels of voltage.It includes 3 families: b Sepam series 20, for usual applications.b Sepam series 40,for demanding applications.b Sepam series 80, for custom applications.To cover all needs, from the simplest to the most complete.

Sepam protection relayA range of solutions adapted to your applicationb Substation protection (incomers, feeders, busbars)b Transformer protectionb Motor and generator protection.

A comprehensive solution, integrating all of the necessary functions for your application b Effective protection of people and propertyb Accurate measurements and detailed diagnosisb Integral equipment controlb Local or remote indication and operation.

Flexibility and upgrading capabilityTo adapt to as many situations as possible, and allow for future installation upgrading, optional modules may be added to Sepam at any time for new functions.

Sepam 100 unitsSepam 100 units round off the Sepam range and can be installed either separately or combined with either Sepam series 20, 40 and series 80.Sepam 100 has several variants:b Sepam 100 MI, local breaking device control and signalling modules (many different line diagram types are available):b Sepam 100 LD, high impedance differential protection b Sepam 100 LA, self-powering protection (back-up protection without auxiliary power supply).

Page 22: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

22

Protection, monitoring and control

Sepam series 20, series 40, series 80Selection guide

Sepam Protections * ApplicationsBasic Specific Substation Transformer Generator Busbar Capacitor

Sepam series 20

b 10 logic inputsb 8 relay outputsb 8 temperature probe inputsb 1 Modbus communication port

DE

5749

3 Current protection

S20 T20

DE

5749

4 Voltage and frequency protection

B21

Loss of mains (ROCOF)

B22

Sepam series 40

b 10 logic inputsb 8 relay outputsb 16 temperature probe inputsb 1 Modbus communication portb logic equations editor

DE

5749

5 Current,voltage and frequency protection

S40 T40 G40

Directional earth fault

S41

Directional earth fault and phase overcurrent

S42 T42

Sepam series 80

b 42 logic inputsb 23 relay outputsb 16 temperature probe inputsb 2 Modbus communication portb logic equations editor

DE

5749

6 Current,voltage and frequency protection

S80

Directional earth fault

S81 T81

Directional earth fault and phase overcurrent

S82 T82 G82

Transformer or machine transformer- differential

T87 G88

Machine differential

G87

DE

5749

8 Voltage and frequency protection for two sets of busbars

B83

DE

5749

9 Capacitor bank unbalance

C86

(*) For other specific protection, please consult us.

Page 23: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

23

ARJP2

PE

5638

1

ARJP3

PE

5638

2

ARJA1

PE

5638

3

Protection, monitoring and control

Instrument transformers

Conventional current transformersConventional current transformers are used to provide power to metering, measuring or control devices. They measure the value of primary current from 10 A to 2500 A. They are in conformity with standard IEC 60044-2.Schneider Electric has drawn up a list of current transformers which are appropriate for use with digital protection devices in order to make it easier to determine accuracy characteristics.They are installed in the rear part of the functional unit. The energized part is entirely encapsulated in an epoxy resin, which provides both electrical insulation and excellent mechanical strength.This list is available in the selection guide on page 39.

For AD4-RD4-GL4 cubiclesTransformer ARJP2/N2Jb Double primary current, double secondary current for measurement or protectionb Frequency 50-60 HzI1n / I2n (A) 50-100 75-150 100-200 150-300 200-400 250-500 600 750Ith (kA) 40 40 31.5-40 40 40 40 50 50t (s) 1 1 1 1 1 1 1 1Measuring*protection*

cl 0.5 5-10 VA 10-20 VA 7.5-15 VA 10-20 VA 20 VA 20 VA5P10 2.5-5 VA 2.5-5 VA 2.5-5 VA 2.5-5 VA 5-10 VA 5-10 VA 7.5 VA 7.5 VA

For AD4-RD4-GL4-CL4 cubiclesTransformer ARJP3/N2Jb Single primary current, double secondary current for measurement or protectionb Frequency 50-60 HzI1n / I2n (A) 1000 / 5 1250 / 5Ith (kA) 50 50t (s) 1 1Measuring*protection*

cl 0.5 30 VA 30 VA5P20 10 VA 10 VA

For AD4-RD4-GL4-CL4 cubiclesTransformer ARJA1/N2Jb Single primary current, double secondary current for measurement or protectionb Frequency 50-60 HzI1n / I2n (A) 1500 / 5 2000 / 5 2500 / 5Ith (kA) 50 50 50t (s) 1 1 1Measuring* protection*

cl 0.5 30 VA 30 VA 30 VA5P20 15 VA 15 VA 15 VA

(*) The secondary current for measuring and protection can be of 1 A or 5 A.

Page 24: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

24

E72

965

Protection, monitoring and control

Instrument transformers (cont.)

Low voltage toroid type current transformersFor cubicle AD4-RD4 with one single-pole cable up to 630 A Transformer ARC2b Single primary current, single secondary current for protectionb Frequency 50-60 HzI1n / I2n (A) 75 100 150 200 250 300 400 600Ith (kA) 50 50 50 50 50 50 50 50t (s) 1 1 1 1 1 1 1 1Protection 5P20 2.5 VA 2.5 VA 5 VA 5 VA 5 VA 5 VA 5 VA 7.5 VA

b Single primary current, double secondary current for measurement or protectionb Frequency 50-60 HzI1n / I2n (A) 200 250 300 400 600Ith (kA) 50 50 50 50 50t (s) 1 1 1 1 1Measuringprotection

5 VA cl. 1 10 VA cl. 0.5 10 VA cl. 0.5 15 VA cl. 0.5 15 VA cl. 0.55P20 2.5 VA 5 VA 5 VA 5 VA 5 VA

For cubicle AD4-RD4 with two single-pole cables up to 630 ATransformer ARC3b Single primary current, double secondary current for measurement or protectionb Frequency 50-60 HzI1n / I2n (A) 750 1000 1250Ith (kA) 50 50 50t (s) 1 1 1Measuring protection

cl 0.5 20 VA 30 VA 30 VA5P20 7.5 VA 10 VA 10 VA

LPCT low power current transducer LPCT’s are specific current sensors with a direct voltage output of the “Low Power Current Transducer” type, in conformity with standard IEC 60044-8.LPCT’s provide metering and protection functions.They are defined by:b the rated primary currentb the extended primary currentb the accuracy limit primary current or the accuracy limit factor.These have a linear response over a large current range and do not start to saturate until beyond the currents to be broken.

For cubicle AD4-RD4 with one single-pole cable up to 630 ATransformer TLP160b Single primary current, double secondary current for measurement or protectionb Frequency 50-60 HzI1n (A) 100 to 2500Ith (kA) 40t (s) 1Accuracy class 0.5 - 5P

For cubicle AD4-RD4 with two single-pole cables up to 630 ATransformer TLP190b Single primary current, double secondary current for measurement or protectionb Frequency 50-60 HzI1n (A) 100 to 2500Ith (kA) 40t (s) 1Accuracy class 0.5 - 5P

LPCT

PE

5622

7

Page 25: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

25

E74

401

E28

678

VRQ1

Protection, monitoring and control

Instrument transformers (cont.)

Voltage transformersThese supply power to:b measuring, metering and monitoring devicesb relays or protective devicesb auxiliary LV sources for various types of switchgear; all these devices are protected and insulated from the MV section.They are installed at the bottom of the functional unit. In the withdrawable fuse version, the voltage transformers are attached to a side wall. The energized part is entirely encapsulated in an epoxy resin, which provides both electrical insulation and excellent mechanical strength.They include the following models:b with one insulated MV terminal, for connection between neutral and phase conductors in three-phase systems with withdrawable MV fuses.b with two insulated MV terminals, for connection between phase conductors.

For AD4-RD4-CL4-GL4-TT4 cubiclesTransformer VRQ1N/S2b Phase/earthb Frequency 50-60 HzPrimary voltage (kV) 20/3 22/31st secondary voltage (V) 100/3 110/32nd secondary voltage (V) 100/3 110/31st secondary accuracy class (VA)

50 VA cl.0.5100 VA cl.1

2nd secondary accuracy class (VA)

50 VA cl.3P

Zero sequence core balance current transformers (CSH type)CSH 120 and CSH 200 core balance CT’s, provide more sensitive protection by direct measurement of earth fault currents.Specifically designed for the Sepam range, they can be directly connected to the Sepam “residual current” input.They are only different in terms of their diameter:b CSH 120 - 120 mm internal diameterb CSH 200 - 200 mm internal diameter.

CSH toroid CT

Page 26: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

26

PE

5504

6Switchgear Withdrawable parts

Withdrawable part

Extraction table

Page 27: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

27

PE

5505

2

Switchgear Withdrawable parts (cont.)

These include:b the circuit breaker or contactor, the disconnector truck or the earthing truckb the lever-type propulsion mechanism for racking in-outb interlocks to fix the withdrawable parts onto the fixed part.MCset circuit breakers SF1-2, switches use sulphur hexafluoride (SF6) for insulation and breaking.The live parts are housed in an insulating enclosure in the sealed pressure system in compliance with IEC 62271-100.The devices used to equip the MCset range of functional units have outstanding features:b long service lifeb maintenance-free live partsb high electrical enduranceb very low overvoltagesb operating safetyb insensitivity to the environmentb breaking capacity and dielectric strength maintained at atmospheric pressureb low filling pressure.

Withdrawable partsCircuit breaker A circuit breaker is a safety device enabling switching and protection of electrical distribution networks. Installed in the MCset cubicle, it protects all components situated downstream during a short-circuit.

DE

5777

3

Earthing truck The earthing truck is a safety feature which allows the cubicle busbar to be earthed. It is installed instead of the circuit breaker and has the same interlock possibilities.

DE

5777

4

Disconnector truck The disconnector truck enables the upper and lower part of the cubicle to be short-circuited. It is installed instead of the circuit breaker and has the same interlock possibilities.

DE

5777

5

SF circuit breakerPresentationSF range circuit breakers equip cubicles AD4 and CL4 for rated voltage values of 24 kV.They work on the basis of the “puffer” type principle in SF6, which is used as a breaking and insulating medium.Each of the 3 poles have an independent insulating enclosure which forms a filled pressure system in compliance with IEC standard 62271-100.Each pole forms a gas-tight unit filled with low pressure SF6 at low relative pressure of 0.05 to 0.35 MPa (0.5 to 3.5 bars) according to the performance level required.No filling is required during the equipment’s life.According to the performance levels, it is possible to optionally equip SF6 circuit breakers with a pressure switch to act on an alarm in the case of a pressure drop.SF6 range circuit breakers are actuated by a GMH type spring mechanism.

Page 28: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

28

DE

5511

8

Fig. 1 Fig. 2

Fig. 3 Fig. 4

Switchgear Withdrawable parts (cont.)

Principle of the puffer breaking technique.The main contacts and arcing contacts are initially closed (Fig. 1).Pre-compression (Fig. 2)When the contacts begin to open, the piston slightly compresses the SF6 gas in the pressure chamber.Arcing period (Fig. 3)The arc appears between the arcing contacts. The piston continues its downward movement. A small quantity of gas, directed by the insulating nozzle is injected across the arc. For the breaking of low currents, the arc is cooled by forced convection. However, for high currents, thermal expansion causes the hot gases to move towards the cooler parts of the pole unit.The distance between the two arcing contacts becomes sufficient for the current to be broken when it reaches the zero point, due to the dielectric properties of the SF6.Sweeping overstroke (Fig. 4)The moving parts finish their movement and the injection of cold gas continues until the contacts are completely open.

Characteristics of SF circuit breakers in MCset cubiclesElectrical characteristics SF1/MCset 4 SF2/MCset 4Rated voltage kV, 50/60 Hz 24 24 24 24Insulation level kV, r ms 50 Hz - 1 min 50 50 50 50

kV, impulse 1.2/50 µs 125 125 125 125Rated nominal current (Ia) A 630 b b b

1250 b b

2500 b b

Breaking capacity Isc kA, r ms 16 25 25 31.5Making capacity kA, peak 40 63 63 80Short time withstand current kA, r ms 3 s 16 25 25 31.5Capacitor breaking capacity A 630 440 440 440

1250 875 8752500 1750 1750

Rated operating sequence O-3 min-CO-3 min-CO b b b b

O-0.3 s-CO-3 min-CO b b b b

O-0.3 s-CO-15 s-CO b b b b

Approximate operating time for supply of releases at Un

ms Opening 50 50Breaking 65 65Closing 70 70

Mechanical endurance Number of switching operations 10 000 10 000

Page 29: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

29

0283

68

Switchgear Withdrawable parts (cont.)

GMH operating mechanismSF range circuit breakers are actuated by a GMH operating mechanism that ensures a switching device closing and opening rate that is independent of the operator. This operating mechanism, always motorised, enables remote operation and fast reclosing cycles.The GMH operating mechanism includes:b a spring system that stores the energy needed to close and open the breakerb a manual spring charging systemb an electrical motor spring charging device that automatically recharges the mechanism as soon as the contacts close (recharging time < 15 s)b two mechanical push buttons for opening and closing, accessible with the cubicle door open (circuit breaker in test position)b an electrical closing system comprising a closing release for remote control and an anti-pumping relayb an electrical opening system comprising one or more opening releases of the following type:v shunt v undervoltage.b an operation counterb an optional “operating mechanism charged” indication contactb an end of charging contactb a black-white mechanical “open-closed” position indicatorb a multi-pin connector to isolate auxiliary circuits in the “racked out” position.Auxiliary contactsThe GMH operating mechanism is equipped with a block of 14 auxiliary contacts including:b 1 changeover contact for the electrical operating mechanismb 1 changeover contact for indicationb 1 contact for the shunt release.

Contact characteristicsRated current 10 ABreaking capacity AC 220 V (cos ϕ ≥ 0.3) 10 A

DC 110 or 220 V (L/R ≤ 0.01 s) 1.5 A

GMH operating mechanism characteristicsType of auxiliaries Spring charging

motor (M)Closing release(YF)

Opening release Available contactShunt (YO1-YO2) Undervoltage

(YM)NC NO Ch

Single DoubleSupply voltage AC (V) 50 Hz 50 - 100 - 140 - 200 - 250 - 380

60 Hz 60 - 110 - 127 - 220 - 250DC (V) 24 - 33 - 48 - 60 - 110 - 136 - 220 - 260

Consumption AC (VA) 700 120 120 240 400/100 (1)

DC (W) 570 70 70 140 100/10 (1)

Possible combinations of auxiliaries and quantities

b b b b 5 4 1

or b b b 5 4 1

or b b b 5 3 1or b b b b 5 3 1or b b b 5 3 1or b b b 5 5 1

(1) Pick-up/latched consumption.

Wiring diagram (principle) DE

5777

6

Sm1

Sn

KN

Y01

M2

SE

YF

J

M1

M

QF

SP

SQ

M3

Sm2 Sm3

YM Y02

J Circuit breakerM Spring charging motorYF Closing releaseM1-M2 End of charging contactQF Auxiliary circuit breaker contactsKN Anti-pumping relaySE Latched release contactY01-Y02 Shunt opening releasesYM Undervoltage opening releaseM3 Operating mechanism charged contactSP Pressure switch contactSQ Device ready to operate contactSm1 Closing push button (external)Sm2 Opening push button for shunt releases (external)Sm3 Opening push button for undervoltage releases

(external)Sn Closing disabling contact (external)

Page 30: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

30

E74

222

Switchgear DI switch cubicle

SM6 switchThe three rotating contacts are placed in an enclosure filled with gas to a relative pressure of 0.04 MPa (0.4 bars).The system offers maximum operating reliability:Gas tightnessThe SF6 filled enclosure is of the “sealed pressure system type”. Sealing tightness is always checked in the factory.Safetyb the switch may be in one of three positions: “closed”, “open” or “earthed”, giving a natural interlocking system that prevents operator error. Moving contact rotation is driven by a fast acting mechanism that is independent of the operator.b the device combines the breaking and disconnecting functions.b the SF6-enclosed earthing switch has a short-circuit making capacity in compliance with standards.Breaking principleThe outstanding qualities of SF6 gas are used to extinguish the electrical arc. To increase cooling of the arc, a relative movement is created between the arc and the gas. The arc strikes when the fixed and moving contacts separate. The combination of the current and a magnetic field created by a permanent magnet causes the arc to rotate around the fixed contact, extending and cooling it until it is extinguished at current zero point. The distance between the fixed and moving contacts is then sufficient to withstand the recovery voltage.This system is both simple and dependable, and it provides improved electrical endurance due to very low wear of contacts.

DE

5748

6

2 6

5431

1 Enclosure2 Cover3 Operating shaft4 Fixed contact5 Moving contact6 Seal

DE

5512

2

Contacts closed Contacts open Contacts earthed

Page 31: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

31

0414

97R

0414

96R

Switchgear DI switch cubicle (cont.)

Operating mechanism and auxiliariesCI2 double function operating mechanismb switch function:v independent closing in two steps:– operating mechanism recharged by a hand lever or motor– stored energy released by a push button or trip unit.v independent opening by push button (O) or trip unit.b earthing switch function:v independent closing by a hand lever.Operating energy is provided by the compression of a spring which causes the contacts to close or open after the neutral point is passed.b auxiliary contacts: v switch (2 O + 2 C)v switch (2 O + 3 C) and earthing switch (1 O + 1 C)v switch (1 C) and earthing switch (1 O + 1 C) if motor option.b motor option b opening release:v shunt v undervoltage (option).b closing release: shunt trip.b fuse blown release: any fuse blown trips the opening of the switch.

Motor option and releases Un DC AC (50 Hz) (1)

Supply (V) 24 48 110 125 220 120 230Motor option

(W) 200(VA) 200(s) < 7 < 7

Opening releasesShunt (W) 200 250 300 300 300

(VA) 400 750Undervoltage Pick-up (W) 160

(VA) 280 550 Latched (W) 4

(VA) 50 40Closing releasesShunt (W) 200 250 300 300 300

(VA) 400 750

(1) Please consult us for other frequencies.

Page 32: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

32

Switchgear DI switch cubicle (cont.)

Fuse ratings for MCset protection units depend, among other things, on the following criteria:b service voltageb transformer ratingb fuse technology (manufacturer).Different types of fuses with medium loaded striker maybe installed: v Solefuse fuses as per standard UTE NCF 64.210v Fusarc CF fuses as per IEC recommendation 60.282.1 and DIN dimensions 43.625.For fuse-switch combination unit, refer only to the selection table and reference list of fuses. For all other type of fuses, consult us.Example: for the protection of a 400 kVA transformer at 22 kV, select either Solefuse fuses rated 16 A or Fusarc CF fuses rated 25 A.

Fuse selection tableRating in A - no overload at –5°C < t < 40°C. Please consult us for overloads and operation over 40°C for France Transfo oil immersed type transformers.

Type of fuse

Service voltage (kV)

Transformer rating (kVA) Rated voltage (kV)

25 50 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500

Solefuse (UTE NFC standards 13.100, 64.210)20 6.3 6.3 6.3 6.3 16 16 16 16 43 43 43 43 43 63 24

Solefuse (general case, UTE NFC standard 13.200)20 6.3 6.3 6.3 6.3 16 16 16 16 31.5 31.5 31.5 43 43 63 2422 6.3 6.3 6.3 6.3 16 16 16 16 16 31.5 31.5 31.5 43 63 63

Fusarc CF and SIBA (1) (general case according to IEC 62271-105)20 6.3 6.3 10 10 16 16 25 25 31.5 40 40 50 50 63 80 100 (1) 125 (1) 2422 6.3 6.3 10 10 10 16 20 25 25 31.5 40 40 50 50 80 80 100 (1)

(1) = SIBA fuses

Fuses dimensionsSolefuse (UTE standards)

DE

5746

6 ø 55

450 23

ø 6

35 35

Ur (kV)

Ir(A)

L(mm)

Ø(mm)

Weight(kg)

24 6.3 to 63 450 55 2

Fusarc CF

DE

5746

7 ø 6ø 45 Ø

33L 23

33

Ur (kV)

Ir(A)

L(mm)

Ø(mm)

Weight(kg)

24 6.3 442 50.5 1.610 442 50.5 1.616 442 50.5 1.620 442 50.5 1.625 442 57 2.231.5 442 57 2.240 442 57 2.250 442 78.5 4.163 442 78.5 4.180 442 86 5.3

SIBA

DE

5746

7 ø 6ø 45 Ø

33L 23

33

Ur (kV)

Ir(A)

L(mm)

Ø(mm)

Weight(kg)

24 100 442 85 5.4

125 442 85 5.4

Page 33: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

33

Accessories Withdrawable parts extraction

Extraction tableAdaptable to the cubicle widths, this extraction table enables:b the withdrawable part to be removed from the cubicleb the withdrawable part to be fitted into the cubicle.

Racking handleThis handle enables:b the withdrawable part to be racked in/outb the earthing switch to be open/closed.

Extraction and lowering tool - optionAdaptable to 3 cubicle widths, this extraction tool enables:b the withdrawable part to be removed from the cubicleb the withdrawable part to be introduced into the cubicleb the withdrawable part to be lowered to the groundb the withdrawable part to be lifted from the ground.

DE

5758

2D

E57

468

DE

5746

9

Page 34: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

34

Accessories Withdrawable parts extraction (cont.)

Parts Circuit breaker positionsInsertion

Extraction

Racking-in

Racking-out

Removed Disconnected Test position Service

1 - Cradle Fool-proof protection (1)

Anti-drop (2)

No opening shutters

Shutters padlocking possible

2 - LV plug Disconnected No racking-in

Connected No unplugging

3 - Circuit breaker Closed Auto-discharge function (3)

No racking-in No racking-out

Open No closing

Open position circuit breaker locking available (3)

4 - Switchboard door Open No racking-in

Closed No door opening (4)

5 - Earthing switch Open No earthing switch closing

Closed No racking-in

(1) This protection mechanism ensures that the performance levels of the circuit breaker correspond with those of the cradle.(2) Device that prevents the circuit breaker from dropping when extracted from the cradle. The device can be either unlocked manually or when the extraction rig is put in position.(3) Option. (4) Interlocking device to be fitted to the cubicle door. If there is no interlocking, the circuit breaker device should be inhibited.

This table describes the safety functions available on MCset.How to use the tableEach of the boxes describes the functional status of each circuit breaker position and the associated parts:

Possible status

Possible status, impossible operation

Impossible status

Page 35: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

35

DE

5777

7

500 900 900 900 900 900 900 900 900 900 900 900 500

DE

5777

8

17001750150(3)

550330(1)

1200(2)

2500(1)

2800(1)(5)

- 2600(4)

AB

Installation Implementation examplesMCset 4 layout (24 kV)

Line up switchboard(2 supplies cubicles and 1 bussection at 24 kV)

Note: for further information, refer to the civil engineering guide, user and instruction manual.

Civil engineering with utility space

(1) Minimum dimensions to be complied with when installing the MCset switchboard.(2) The cable basement or cable trench depth can be reduced if it is compatible with the bending radius of the cables used.(3) Operating distance.(4) Distance needed to extract a functional unit.(5) Provide an exhaust tunnel above the switchboard when the room height is less than 4 metres (see page 12).A anchor pointB adjustment point

3 feeders cubicle AD4

incomer cubicle AD4

bussection cubicles CL4/GL4

incomer cubicle AD4

4 feeders cubicle AD4

room entrance

Page 36: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

36

PE

5623

9Installation Connections

Switchgear resistance to ageing in a substation depends on 3 key factorsb The need for correctly made connectionsNew cold connecting technologies offer easy installation and favour durability in time. Their design means they can be used in polluted environments with harsh atmospheres.b The impact of relative humidityThe installing of a heating element is essential in climates with high relative humidities and significant temperature differentials.b Ventilation controlThe dimensions of air vents must be appropriate for the dissipated energy in the substation. They must only sweep across the transformer environment.Cold connected terminalsSchneider Electric’s experience has led it to favour this technology wherever possible for optimum durability. The maximum acceptable cable cross-section for standard assemblies are: b 630 mm2 for incomer or feeder cubicles with single-pole cables;b 400 mm2 for incomer or feeder cubicles with three-pole cables;b 95 mm2 for transformer protection cubicles with fuses.Access to the compartment is only possible when the earthing switch is closed.Tightening torques for cables will be attained using a dynamo wrench set to 50 mN.

Dry, single core cable Short end piece, cold connectable Performance 3 to 24 kV - 400 A - 2500 A Cross section mm2 50 to 630 mm2

Supplier All suppliers of cold connectable terminals: Silec, 3M, Pirelli, Raychem...

Number of cables 1 to 8 per phase Comments For greater cross section and number of cables,

please consult us

Dry, three core cable Short end piece, cold connectable

Performance 3 to 24 kV - 400 A - 2500 A Cross section mm2 50 to 400 mm2

Supplier All suppliers of cold connectable terminals: Silec, 3M, Pirelli, Raychem...

Number of cables 1 to 4 per phase Comments For greater cross section and number of cables,

please consult us

Connection possibilities using dry cablesNumber of cables AD4 RD4 DI41 single per phase b (1) b b

2 single per phase b (1) b

3 single per phase b b

4 single per phase b b

1 three per cubicle b b

2 three per cubicle b b

3 three per cubicle b b

4 three per cubicle b b

(1) Possibility of installing LV core balance type transformers.

Page 37: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

37

DE

5777

9D

E57

780

DE

5778

1

P

H

Fig. 1

Fig. 2

Fig. 3

Installation Connections (cont.)

Bottom cable connectionCable connection height

Type of cubicle Configuration H (mm)AD4 - RD4 630 A LV core balance CT 530

630 to 2500 A 1 set of 3 CT’s 4202 sets of 3 CT’s 410

DI4 650 b The cubicles and cables requiring the maximum depth should be taken into consideration when determining the depth P of a switchboard cable duct (Fig. 1).b When using cables of length greater than 430 mm for MCset 4, install an additional compartment as marked (A) under the cubicle (Fig. 2).

Top cable connection (optional)The additional depth is 500 mm as a standard cubicle.Rated current In : 630 A and 1250 A

Top busbar connection (optional, fig. 3)The additional depth is 500 mm as a standard cubicle.Rated current In : 1250 A and 2500 A

Page 38: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

38

Appendix Cubicle equipment

Equipment Type of cubicleAD4 RD4 CL4 GL4 TT4 DI4

SwitchgearCircuit breaker b b

Pressure switch v v

Fuse switch b

Disconnector truck v v

Earthing truck v v

Fixed busbar b

Racking position indication contact for the withdrawable part 6 NO + 6 NC b b

Padlocking of isolating shutters for withdrawable parts v v

Locking of withdrawable part/cable compartment b

Disabling of circuit breaker operating mechanism b b

Voltage presence indicator v (3) v (3) v (3) b (3) b

Earthing switch (SMALT)Earthing switch v v v b

Earthing switch position indication contacts 2 NO + 2 NC v (1) v (1) v (1) v (7)

Earthing switch position key locking (1) v (1) v (1) v (1) v

Electromagnetic earthing switch position locking v v v

TransformersVoltage transformers Fixed VT without fuse Phase-phase

(1 or 2 per cubicle)v v v v v

Phase-earth(1 per phase)

v v v v v

With plug-in fuses Phase-earth v v v v v

Current transformer Single set 3 TC v v v v

Double set 6 TC v

LV core balance CT (4) v (6) v (6)

ConnectionsConnection with cable terminal height > 430 mm (MCset 4) v v v

Connection from top bar v v

Connection by cable from the bottom b b b

Connection by cable from the top v v

CubicleProtection index Enclosure IP3X b b b b b b

IP4X v v v v v v

IPX1 (8) v v v v v v

Compartments (9) IP2XC b b b b b b

Anti-arcing protection (2) 25 kA - 1 s v v v v v v

31.5 kA - 0.15 s v v v v v v

Lightning arrester v v v

Busbars1250 A, 2500 A Exposed v v v v v v

Insulated b b b b b b

LV control cabinetLV control cabinet key locking v v v v v v

LV control cabinet lighting (220 V AC/127 V DC) v v v v v v

Anti-condensation heating element (220 V AC/127 V DC) b b b b b b

b : basic equipment.v : option.(1) Basic equipment with earthing switch option.(2) According to the room in which the MCset switchboard is installed, you can choose AFL or AFLT, and possibly an exhaust tunnel for hot gases (≥ 4 m and ≤ 4 m).(3) Basic equipment when the cubicle is equipped with an earthing switch.(4) Connection 1 or 2 cables per phase.(5) Possibility of 1 phase-phase VT.(6) Only for 630 A cubicle.(7) 1 NO + 1 NC available.(8) For IPX2, consult us.(9) Compartment protection.

Page 39: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

39

Appendix Current transformers Selection guide

Preferred current transformers: 24 kV secondary 1 A or 5 A

Accuracy class ratio AD4 CL4Isc kA 1 s 31.5 31.5

40-80/1 or 52.5-5 VA - 5P20

v

50-100/1-52.5-5 VA - 5P20

v

75-150/1 or 52.5-5 VA - 5P20

v

100-200/1-1 or 5-52.5-5 VA - 5P20

v

150-300/1-1 or 5-52.5-5 VA - 5P2010-20 VA - cl 0.5

v

200-400/1-1 or 5-55-10 VA - 5P207.5-15 VA - cl 0.5

v

250-500/1-1 or 5-55-10 VA - 5P2010-20 VA - cl 0.5

v

600/1-1 or 5-57.5 VA - 5P2020 VA - cl 0.5

v

750/1-1 or 5-57.5 VA - 5P2020 VA - cl 0.5

v

1000/1-1 or 5-510 VA - 5P2030 VA - cl 0.5

v v

1250/1-1 or 5-510 VA - 5P2030 VA - cl 0.5

v v

1500/1-1 or 5-515 VA - 5P2030 VA - cl 0.5

v v

2000/1-1 or 5-515 VA - 5P2030 VA - cl 0.5

v v

2500/1-1 or 5-515 VA - 5P2030 VA - cl 0.5

v v

v : option.Other characteristics are available, including the possibility of having 3 secondary windings. Please consult us detailing the type of protection or measuring required as well as the impedance of the outside loads and the cabling.

Page 40: MCset 4 range Contents 1 to 24 kV - Schneider Electrickatalog.schneider-electric.cz/dsmapp/data/pdf/CZ/CMS/MCset 4.pdfMCset 4 range 1 to 24 kV Contents Presentation 2 Field of application

40

A53

-MA

PP

E74

223

E74

226

A few references MCset, a product for all your electrical distribution applications

IndustryOil, Girassol Mpg-Elf, AngolaOil, Repsol, Santander, SpainOil, Sincor (Total), VenezuelaPharmaceutical, Merck, SingaporeAutomotive, Volvo, BelgiumAutomotive, Ford, GermanyCement production, Lafarge, FranceAgri-food, Mastellone, ArgentinaAlcoa Aluminium, AustraliaGeneral Motors, ThailandBD Medical, SingaporeBridgestone, Hungary

InfrastructurePort of KSA Jeddah, Saudi ArabiaSantafe de Bogota airport, ColombiaSlim River Hospital, MalaysiaWater treatment, Degremont, ArgentinaABV Rock, Saudi ArabiaValencia Airport, SpainHamilton Hotels, AustraliaGrand Indonesia Project, Indonesia

EnergySarlux power station, ItalyEVN thermal power station, Vietnam Costa Nera SA power station, ArgentinaElectrical distribution, DES (department of electrical services), BruneiRenovation of the Chernobyl nuclear power station, UkraineWind Turbines, FranceSkagerak Nett AS, NorwayUnion Electrica, CubaPetroVietnam Refinery, Vietnam