mcu-unt-mmi manual.pdf

37
UNT-MMI-A Intelligent MCC Control & Protection Management Device Instruction Manual Baoding UNT Electric Co., Ltd

Upload: kunaljay

Post on 20-Jul-2016

52 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: MCU-UNT-MMI manual.pdf

UNT-MMI-A

Intelligent MCC Control & Protection Management Device

Instruction Manual

Baoding UNT Electric Co., Ltd

Page 2: MCU-UNT-MMI manual.pdf

Catalog

General Information.......................................................................................................1 Introduction.............................................................................................................1 Features ...................................................................................................................1 Metering and Monitoring........................................................................................1 Protection ................................................................................................................2 Control ....................................................................................................................2 Communication.......................................................................................................2

Protection and Control ...................................................................................................3 Overcurrent .............................................................................................................3 Locked/ Stalled Rotor .............................................................................................3 Acceleration Time...................................................................................................4 Overheating.............................................................................................................5 Unbalance ...............................................................................................................6 Ground Fault ...........................................................................................................7 Phase Sequence.......................................................................................................7 Phase Loss...............................................................................................................7 Overvoltage.............................................................................................................8 Undervoltage...........................................................................................................8 tE Time Protection ..................................................................................................8 Underpower...........................................................................................................10 Ultra Breaking.......................................................................................................10 Undervoltage Auto Restart....................................................................................10 Control Mode ........................................................................................................ 11 Programmable Inputs and Outputs........................................................................ 11

Hardware......................................................................................................................13 Display Module.....................................................................................................13 Main Module.........................................................................................................14

Human Interface...........................................................................................................15 Main Menu............................................................................................................15 View ......................................................................................................................16 Setting ...................................................................................................................22 Others....................................................................................................................24 Reset......................................................................................................................24 Trip Records..........................................................................................................25 Information ...........................................................................................................25

Typical Wiring..............................................................................................................26 Dimensions ..................................................................................................................27 Ordering information ...................................................................................................29 Specifications...............................................................................................................30

I

Page 3: MCU-UNT-MMI manual.pdf

General Information

Introduction

UNT-MMI-A Intelligent MCC Control & Protection Management Device is developed by Baoding UNT Electric co., Ltd. It is an intelligent motor management device designed mainly for MCC circuit. UNT-MMI-A Intelligent MCC Control & Protection Management Device is mainly applied to motor circuit that employs MCCB and contactor as the primary circuit, implementing metering, control, protection and monitoring, also telecommuting is available through field bus. It replaces conventional protection devices, meters, timers, relays, switches and panel indicators, simplifying the secondary circuit. It greatly increases the design efficiency, meanwhile decrease the field maintenance. For many years’ development, UNT-MMI-A Intelligent MCC Control & Protection Management Device has widely applied to the fields of power, petrochemistry, paper, metallurgy, nuclear industry and so on.

Features

Embed high-speed 32-bit microprocessor Metal enclosure designed, high anti-nuisance performance Pass 15 EMC tests of “National Center for Quality Supervision & Testing of Relay &

Protection Equipment” Opto-isolated 4—20mA output with optional destination Integrative design, without auxiliary components Compact design, flexible fixing Also applied to Increased Safety Motor Flexible control mode(local/remote/ECS) Internal contact point protective circuit, without external surge absorber Undervoltage auto restart Solve the defect that thermal overload relay and MCCB can’t model the electric and

thermal characteristics of the MCC load. Implement complex interlock, high efficiency Intelligent terminal, Reduce MCC and field wiring, replace timers, relays, protective

devices, meters, panel indicators Adopt Industrial field bus, easily connected with other devices Redundant network designed

Metering and Monitoring

Display phase current, ground current, line voltage, positive sequence current, negative

1

Page 4: MCU-UNT-MMI manual.pdf

sequence current, thermal capacity used, power factor, energy, etc. Trip record Analog output

Protection

Overcurrent Locked/stalled rotor Acceleration time Overheating Unbalance Ground fault Phase sequence Phase Loss Overvoltage Undervoltage tE time Underpower Ultra breaking Undervoltage auto restart

Control

Remote/local/ECS control mode Programmable input and output Normal/spare mode

Communication

Modbus@RTU through RS-485 Profibus-DP CAN

2

Page 5: MCU-UNT-MMI manual.pdf

Protection and Control

Overcurrent

Overcurrent protection is the backup protection of the MCCB. The time delay can be programmed between 0-60s. To avoid starting current, overcurrent protection is disabled in starting condition, and enabled automatically after starting.

≥1

tgl Trip

Ia>Igl

Ib>Igl

Ic>Igl

Where: Igl, ranged from 0 to 12*Ie, is the setpoint value of overcurrent.

tgl is the time delay of overcurrent, ranged from 0 to 60s.

Ie is the rated current of the motor.

Locked/ Stalled Rotor

Mechanical equipment such as pumps and fans can be quickly damaged if it gets jammed resulting in a locked rotor stall. This device will issue a trip command when the current exceeds the locked rotor trip level after a programmable time delay. This device provides exact stalled rotor protection in different states: starting state and running state.

3

Page 6: MCU-UNT-MMI manual.pdf

&

tdz1 Trip

Ia>Idz

Ib>Idz

Ic>Idz

Where: Idz, ranged from 0 to 10*Ie, is the setpoint current of locked rotor.

tdz1 is the time delay of locked rotor in starting state, ranged from 0 to 60s.

Ie is the rated current of the motor.

Starting state

&

tdz2 Trip

Ia>Idz

Ib>Idz

Ic>Idz

Where: Idz, ranged from 0 to 10*Ie, is the setpoint of locked rotor.

tdz2 is the time delay of locked rotor in running state, ranged from 0 to 60s.

Ie is the rated current of the motor.

Running state

Acceleration Time

Acceleration time is defined as the length of time required for the average motor current to drop below Full Load Current after a start command. Too long acceleration time causes overheating, damages the motor. An acceleration time trip is provided with a time delay.

4

Page 7: MCU-UNT-MMI manual.pdf

& Trip

Ia>Iqd

Ib>Iqd

Ic>Iqd

Where: Iqd, ranged from 0 to 5*Ie, is the set point of starting current.

tqd is the start time set point, ranged from 0 to 60s.

t is the accumulative time. Ie is the rated current of the motor.

t=tqd

Overheating

An overheating trip is caused when the thermal capacity value equals 100%. The device employs an advanced digital thermal model to calculate the thermal capacity. The motor thermal model accounts for all kinds of running conditions, and provides exact protections. Because of the different thermal effect of positive sequence current and negative sequence current, equivalent current Ieq is adopted in the model.

222

211 IKIKIeq +=

Where: K1=0.25 (starting condition) K=1 (running condition) K2=6

I1 is positive sequence current I2 is negative sequence current

In order to avoid the starting current, assign K1 different value in starting condition and running condition. Because the heat effect of Negative sequence current is much more than positive sequence current, K2 is assigned 6. The accumulated heat of the motor Θ∑ is:

∫ Δ−Σ=−=ΘΣ

t

eeqeeq tIIdtII0

2222 ])05.1([])05.1([

Where: △t is the time interval to calculate accumulated overheating, here △t=0.1s. The overheating of the motor ΘT is: ΘT =Ie2 * Tfr Where: Tfr is the heating time constant. A overheating protection is triggered whenΘ∑ ≥ ΘT. Θ∑ =0 stand for a steady state, and there is no accumulated overheating. In steady state, the overheating protection performance time

5

Page 8: MCU-UNT-MMI manual.pdf

is:

2222

211 05.1)()( −+

=ee

fr

IIKIIKT

t

When the motor is stopped, the accumulated overheating will decrease exponentially. The cooling time constant Tsr is 4 times longer than heating time constant, on other hand, the motor reaches a steady state again in Tsr .

When tripped due to overheating, the device checks the overheating status of the motor. To protect the motor, the protection output would not return and restart of the motor is inhibited if Θ∑ ≥ ΘT . In case of emergency, select “Reset” menu and press “ENT” to clear the thermal memory, and then start the motor. A group of overheat protection performance time is shown in the table below:

Heating time constant performance time

Overload 100 200 300 400 500

1.1*Ie 930 1860 2790 3721 4651

1.3*Ie 170 340 510 680 850

1.5*Ie 87 174 261 348 435

1.7*Ie 56 112 168 224 280

2*Ie 34 68 102 136 170

3*Ie 13 26 39 52 65

4*Ie 6.7 13.4 20 27 34

5*Ie 4.2 8.4 12.6 17 21

6*Ie 2.9 5.8 8.7 11.6 14.5

7*Ie 2.1 4.2 6.3 8.4 10.5

8*Ie 1.6 3.2 4.8 6.4 8

Unbalance

This device monitors the three current phases, and calculates the average and maximum current. A trip or an alarm is triggered when the phase is unbalanced. The unbalance degree is programmable between 10%-60%.

6

Page 9: MCU-UNT-MMI manual.pdf

tbph Trip/Alarm Ru>bph%

Where: bph, ranged from 10 to 60, is the set unbalance degree.

tbph, ranged from 0 to 60s, is the time delay of unbalance.

Ru=|(Iavr – Imax)/Iavr| ×100%, Iavr=(Ia+Ib+Ic)/3, Imax=max(Ia,Ib,Ic)

Ground Fault

Both a trip and an alarm level can be enabled when ground fault current exceeds the set point after a programmable time delay. The set point range is 0-10 *Ie.

tjd Trip/Alarm I0>Ijd

Where:

tjd, ranged from 0 to 60s, is the time delay of ground fault.

Ijd, range from 0 to 10*Ie, is the set ground fault current.

Phase Sequence

When phase sequence incorrect, negative sequence current increase greatly, and positive sequence current decrease obviously. If negative sequence current/( negative sequence current + positive sequence current)>80%,then a trip is triggered.

Phase Loss

If one of the phase current is less than 10% of rated current, and other two phase currents are more than 20% of rated current, a trip is triggered. Phase Loss causes serious rotor overheating, even damages the motor. Its sensitivity is better than overheating protection, so it is possible to detect faults early and protect the motor. This device detects phase loss through calculating 3 phase current.

7

Page 10: MCU-UNT-MMI manual.pdf

Overvoltage

Serious overvoltage will cause core saturation of the motor, increase the magnetizing current, and damage the motor. If the voltage exceeds the overvoltage level after a programmable time delay a trip or an alarm will occur.

&

tgdy Trip/alarm

Uab>Ugdy

Ucb>Ugdy

Where: Ugdy, ranged from 380V to 500V, is the set point value of overvoltage,.

tgdy, ranged from 0 to 60s, is the time delay of overvoltage.

Undervoltage

An undervoltage level can be selected for both alarm and trip. Undervoltage protection has two functions: 1. Long time undervoltage will damage the motor, so it is needed to stop the motor when

undervoltage. 2. When undervoltage, cut off the less important load to ensure the running of important device,

and to keep the system stability.

&

tddy Trip/alarm

Uab<Uddy

Ucb<Uddy

Where: Uddy, ranged from 0V to 380V, is the set value of overvoltage.

tddy, ranged from 0 to 60s, is the time delay of overvoltage.

tE Time Protection

It is applied to Increased Safety Motor. tE protection time=tEp×tEp1

8

Page 11: MCU-UNT-MMI manual.pdf

Where: tEp is the set time of tE protection tEp1 is the performance time when tEp=1

IA: the initial starting current IN: the rated current of the motor

On running condition, when the overcurrent reaches a certain degree, the device interrupts the motor power supply according to the tE time curves and tE time table. tE time protection should be enabled when starting the motor. NOTE:

1. This device couldn’t install and wire in explosive situation. 2. When applied to increased safety motor, the parameters must be set professionally. 3. When applied to increased safety motor, the rated current can not exceed the maximum

current of the motor. 4. When applied to increased safety motor, the performance time can not exceed 1.7 times

of the tE time (refer to the nameplate of the increased safety motor).

tE time curves

tE time table

1.0(S) 4.0(S) 4.3S) 4.6(S) 5.0(S) 5.5(S) 6.0(S) 15.0(S)tEp

IA/IN

3.00 4.00 16.00 17.20 18.40 20.00 22.00 24.00 60.00 3.20 3.48 13.91 14.96 16.00 17.39 19.13 20.87 52.17 3.40 3.08 12.31 13.23 14.15 15.38 16.92 18.46 46.15 3.60 2.76 11.03 11.86 12.69 13.79 15.17 16.55 41.38 3.80 2.50 10.00 10.75 11.50 12.50 13.75 15.00 37.50 4.00 2.29 9.14 9.83 10.51 11.43 12.57 13.71 34.29 4.20 2.11 8.42 9.05 9.68 10.53 11.58 12.63 31.58 4.40 1.95 7.80 8.39 8.98 9.76 10.73 11.71 29.27

9

Page 12: MCU-UNT-MMI manual.pdf

4.60 1.82 7.27 7.82 8.36 9.09 10.00 1091 27.27 4.80 1.70 6.81 7.32 7.38 8.51 9.36 10.21 25.53 5.00 1.60 6.40 6.88 7.36 8.00 8.80 9.60 24.00 5.20 1.51 6.04 6.49 6.94 7.55 8.30 9.06 22.64 5.40 1.43 5.71 6.14 6.57 7.14 7.86 8.57 21.43 5.60 1.36 5.42 5.83 6.24 6.78 7.46 8.14 20.34 5.80 1.29 5.16 5.55 5.94 6.45 7.10 7.74 19.35 6.00 1.23 4.92 5.29 5.66 6.00 6.77 7.38 18.46 6.20 1.18 4.71 5.06 5.41 5.88 6.47 7.06 17.65 6.40 1.13 4.51 4.85 5.18 5.63 6.20 6.76 16.90 6.60 1.08 4.32 4.65 4.97 5.41 5.95 6.49 16.22 6.80 1.04 4.16 4.47 4.78 5.19 5.71 6.23 15.58 7.00 1.00 4.00 4.30 4.60 5.00 6.00 6.00 15.00 8.00 1.00 4.00 4.30 4.60 5.00 5.50 6.00 15.00

Underpower

Both underpower alarm and trip are provided with a programmable time delay.

tqgl Trip/Alarm P<Pqgl

Where:

tqgl, ranged from 0 to 60s, is the time delay of ground fault.

Pqgl, ranged from 0 to 10*Pe, is the set ground fault value. Pe is the rated power of the motor.

Ultra Breaking

When the current of MCCB is beyond Ifd, to protect the contactor, the break contactor is disabled, and programmable output 2 can be programmed to control the motor. NOTE: Ifd is the maximum breaking current of the contactor, ranged from 0 to 4000A.

Undervoltage Auto Restart

It is possible to automatically restart the motor after a momentary power loss of the primary circuit if this feature is enabled. When the control voltage drops below the the dropout voltage, the contactor is de-energized. The device can restart the selected drive upon the return of the supply voltage. In many cases, the device is AC powered, and the device also loses power supply simultaneously

10

Page 13: MCU-UNT-MMI manual.pdf

after control circuit power loss. In this case, the device would not supervise the 3-phase voltage, but it is still available to restart the motor upon the return of the power supply due to the memory chip inside.

Running condition

undervoltage

Voltage recovers in t1?

Delay t2

Auto restart Motor stopped

Yes

No

Undervoltage auto restart diagram

Where: t1, ranged from 0 to 100s, is the limited of undervoltage time. t2, ranged from 0 to 600s, is the time delay of undervoltage auto restart.

Control Mode

Local mode: control the motor through the control keys on the faceplate Remote mode: remote-control the motor through the fixed input(X2-9, X2-10, X2-11) ECS mode: control the motor through communication These three mutual interlock control modes can be set through faceplate or external switch. When the device is in local mode, remote and ECS mode is disabled. When the device is in remote mode, local and ECS control is disabled. When the device is in ECS mode, local and remote control mode is disabled.

Programmable Inputs and Outputs

UNT-MMI-A Intelligent MCC Control & Protection Management Device has 5 programmable

11

Page 14: MCU-UNT-MMI manual.pdf

inputs and 2 programmable outputs. Start and stop the motor can be easily implemented through programmable inputs and outputs, also complex interlock, for example, the normal/spare logic and the interlock of temperature, water level and rotate speed. It replaces the conventional relays, making the design easy.

Starter types Starter types Internal relay control Non-reversing starter Single-relay control Reversing starter Dual-relay control Resistance Drop-Voltage starter Dual-relay control

Dual-relay control Wye-Delta transition starter Triple-relay control

Autotransformer starter Triple-relay control

Control mode Control mode Control location remarks

Local control Remote control Low-voltage switchgear cabinet

Operation box near the motor

Low-voltage switchgear cabinet

DCS connection Dual-location control

Operation box near the motor

DCS connection

Local control Remote control

ECS

Low-voltage switchgear cabinet

Operation box near the motor

DCS connection

External switch

Low-voltage switchgear cabinet

DCS connection

communication Set on the panel External switch

Triple-location control

Low-voltage switchgear cabinet

DCS connection

communication Set on the panel External switch

12

Page 15: MCU-UNT-MMI manual.pdf

Hardware

Display Module

UNT-MMI

TRIPPED ALARM REMOTE RUNNINGCOMM SPARE

START

STOP

LED indicators

RUNNING: indicates that the motor is running. COM: indicates that the device is communicating.

TRIPPED: indicates that a trip has occurred. This indicator always latches; a RESET command must be initiated to allow the latch to be reset. ALARM: indicates that an alarm existing. This indicator is never latched; after the alarm condition recover, it turns off.

REMOTE: indicates that the device is in remote control mode. SPARE: indicates that the device is in spare mode.

Display

The LCD communicates all messages in simple English.

Keypad

Program keys: ←/ESC: Move the cursor left or cancel a certain operation.

↑: Increase the selected digit or change the selected item. ↓: Decrease the selected digit or change the selected item. →/ENT: Confirm a certain operation.

Control keys: FORWARD: Start the motor in the forward direction. REVERSE: Start the motor in the reverse direction. STOP: Stop the motor.

13

Page 16: MCU-UNT-MMI manual.pdf

Main Module

GRUOND

14

Page 17: MCU-UNT-MMI manual.pdf

Human Interface

Please check carefully before the first power on. After power on, the device performs self-diagnosis, at the same time, all LED indicators turn on. After self-diagnosis, the display shows three phase currents and the status of the motor, and the running indicator turn off. Otherwise, check the power supply and the connection between display module and main module. The running indicator turns on when the motor is running, and the display shows the phase currents and the status of the motor. Press “↑” or “↓” to show the following items circularly. Refer to Figure below for more details.

Ia=xx.xxA Ib=xxx.x A

Ic=xxx.xA FORWARD

Io=xxx.xA Ie=xxxx A

If=xxxxA Dgr=xx.xx%

Uab=xxx.x V

Ucb=xxx.x V

P=xxxx KW

Q=xxxx Kvar

PF=0.xxx

KWH=xxxxxxxxxx

KVarH=xxxxxxxxxxx

2006-12-2508-26-15

ProgInput 1-5

O O O O O

ControlMode Local

Normal/spare Normal

The following abbreviations are used in the messages: OH: overheating G/F: ground fault UnderP: underpower A_time: acceleration time Func: function UV,UnderV: undervoltage OverV: overvoltage Squc: Phase sequence UltraBrk: Ultra breaking INFO: information Comm: communication Prog: programmable AStart: undervoltage auto restart Run_para: running parameter CtrlMode: control mode Unblc: unbalance Dgr: thermal capacity used Dly: delay

Main Menu

Press “ENT” or “ESC” to enter the main menu.

15

Page 18: MCU-UNT-MMI manual.pdf

VIEW SETTINGS

SYSTEM OTHERS

RESET TRIPS

INFO

Ia=xx.xxA Ib=xxx.x A

Ic=xxx.xA FORWARD

or

View

Select “VIEW” in main menu, and press “ENT” to enter. You can view all the setpoints here.

Protection ProgIO

Comm 4-20mA AStart 1.Protect

Run_para OH G/F

OC Jam tE

Unblc UnderP

A_time Squc

UnderV OverV

UltraBrk PhL

Protection ProgIO

Comm 4-20mA AStart

For example, let’s view the running parameters. Select “Run_para” and then press “ENT” to enter.

Run_para OT G/F

OC Jam tE

Running Parameter

CT Multiple xxxx

Running Parameter

CT Number xxxx

Running Parameter

Rated Cur xx.xxA

The multiple of the CT

The number of the CT

Rated current of the motor

The multiple of CT stand for the transform ratio of external CT. For example, if the transform ratio of external CT is 1200/5, then the multiple of the CT would be 240. The CT number is the module of CT. If external CT is not used, assign the CT multiple “1”, otherwise the current would be disturbed. The motor rated current must be identical with the motor nameplate, or

16

Page 19: MCU-UNT-MMI manual.pdf

malfunction may occur. 2.ProgIO ⑴ Input1

Input1 Input Mode xxxx

Input1

Mask xxxx

Input1

Func xxxx

Input mode Range: Open, Close

Mask bit. Detemine when the input is masked.

The function of the programmable input

Input1

Delay xxxxs

Time delay

Input1 Input2

Input3 Input4

There is a table (table 1) containing the alternative of programmable inputs. Table 1

Sort Optional terms Description Open External contact normally closed Input mode Close External contact normally opened Valid Valid, not masked Local Masked when the device is in local control mode Remote Masked when the device is in remote mode ECS Masked when the device is in ECS mode Spare Masked when the device is in spare state

Mask bit

Masked Masked, disabled Start A Start A Start B Start B Stop A Stop A Stop B Stop B Stop Stop Trip Button Serve as a trip push button Reset Reset trip signal output Local/Remote Switch local/remote Remote/ECS Switch remote/ECS Normal/Spare Switch normal/spare Start_Stop A Keep contactor A closed when the input is valid, and

keep contactor A opened when there is no valid input Start_Stop B Keep contactor B closed when the input is valid, and

keep contactor B opened when there is no valid input

Function

Mask Ctrl Mask the start and stop function of the programmable input

17

Page 20: MCU-UNT-MMI manual.pdf

Dis protect Disable all protections with a valid input Time delay xxx.x s

⑵output1

Output1

Output Mode xxxx

Output1

Output Pulse xxxx

Output1

Func xxxx

Output mode Range: Open, Close

Output pulse type Range: Long, Short

The function of the programmable output.

Output1

Delay xxxxs

Time delay

Input5 Output1

Output2

Output1

Length xxxxs

Length of output pulse

There is a table (table 2) containing the alternative of programmable outputs.

Table 2 Sort Optional terms Description

Open Break contact Output Mode Close Make contact Long Long pulse output Output pulse Short Short pulse output Masked Masked Prog Input 1 Energize when programmable input 1 is closed Prog Input 2 Energize when programmable input 2 is closed Prog Input 3 Energize when programmable input 3 is closed Prog Input 4 Energize when programmable input 4 is closed Prog Input 5 Energize when programmable input 5 is closed Remote Energize when the device is in remote control mode ECS Energize when the device is in ECS control mode Spare Energize when the device is in spare mode Alarm Energize when there is an alarm Trip Energize when there is a trip Trip or Alarm Energize when there is a an alarm or a trip Undervoltage Energize when undervoltage Ground Fault Energize when ground fault Forward Energize when the motor is running in the forward direction

Function

Reverse Energize when the motor is running in the reverse direction

18

Page 21: MCU-UNT-MMI manual.pdf

Super Break Super breaking output Time Delay xxx.x s Pulse Length xxx.x s

3.Comm

Comm A Address xxx

Comm A

Baud Rate xxxxx

Comm A Parity xxxx

Communication address Range: 1-230

Baud rate Range: 4800, 9600,19200

Parity check Range: Even, Odd, None

Comm A

Comm B

4.4-20mA

Protect ProgIO

Comm 4-20mA AStart

4-20mA

Destination xxx

4-20mA

Multiple xx.xx

The destination of analog output

The multiple of rated value

The table below shows the alternative of analog output destination and the multiple of rated value that corresponding to the upper limit of 4--20mA output.

Table 3 Sort Setpoint

Ia Ib Ic I0 Uab Ubc Dgr (Thermal capacity used)

Output destination

P Multiple of rated value 1-2

5.AStart

19

Page 22: MCU-UNT-MMI manual.pdf

Protect ProgIO

Comm 4-20mA AStart

AStart

Delay xxxs

AStart

UV Time xxxs

Time delay of Undervoltage Auto Restart

Undervoltage time limit that the device can restart the motor

The diagram below illuminates the undervoltage auto restart.

Running condition

undervoltage

Voltage recovers in t1?

Delay t2

Auto restart Motor stopped

Yes

No

Undervoltage Auto Restart Diagram

NOTE: ① t1 is the set time that the motor could auto restart from undervoltage, and t2 is the auto restart delay time. ② If undervoltage auto restart is not required, just set t1 to 0.

There is a table (Table 4) containing the items that you can set and view. Table 4

Sort Description The multiple of CT (1--1000) The number of CT (1--7)

Running parameters

Rated current of the motor (0.1--1000) Heating time constant Cooling time constant Enable/disable overheating protection Overheating protection trip/alarm

Setpoint value of ground fault

20

Page 23: MCU-UNT-MMI manual.pdf

Time delay of ground fault (0—55s) Enable/disable ground fault protection Ground fault protection trip/alarm Setpoint value of overcurrent Time delay of overcurrent protection (0—55s) Enable/disable overcurrent protection Overcurrent protection trip/alarm Setpoint current of Locked rotor Time delay 1 of locked rotor (0—55s, starting condition) Time delay 2 of locked rotor (0—55s, running c) Enable/disable locked rotor protection Locked rotor protection trip/alarm Alternative of tE time curve (1--15) Enable/disable tE time protection tE time protection trip/alarm Setpoint degree of unbalance Time delay of unbalance protection Enable/disable unbalance protection Unbalance protection trip/alarm Setpoint value of underpower Time delay of underpower Enable/disable underpower protection Underpower protection trip/alarm Setpoint current of acceleration time protection (1—1000A) Acceleration time (0—60s) Time delay of acceleration time protection Enable/disable acceleration time protection Acceleration time protection trip/alarm Enable/disable phase sequence protection Phase sequence protection trip/alarm Setpoint of undervoltage Time delay of undervoltage protection Enable/disable undervoltage protection Undervoltage protection trip/alarm Setpoint of overvoltage Time delay of overvoltage protection Enable/disable overvoltage protection Overvoltage protection trip/alarm Setpoint current of ultra breaking Enable/disable ultra breaking protection Ultra breaking protection trip/alarm Enable/disable phase loss protection

Config protections

Phase loss protection trip/alarm

21

Page 24: MCU-UNT-MMI manual.pdf

Input mode of programmable input 1 Mask bit of programmable input 1 Function of programmable input 1 Time delay of programmable input 1 Input mode of programmable input 2 Mask bit of programmable input 2 Function of programmable input 2 Time delay of programmable input 2 Input mode of programmable input 3 Mask bit of programmable input 3 Function of programmable input 3 Time delay of programmable input 3 Input mode of programmable input 4 Mask bit of programmable input 4 Function of programmable input 4 Time delay of programmable input 4 Input mode of programmable input 5 Mask bit of programmable input 5 Function of programmable input 5 Time delay of programmable input 5 Output pulse of programmable output 1 Function of programmable output 1 Time delay of programmable output 1 Pulse length of programmable output 1 Output pulse of programmable output 2 Function of programmable output 2 Time delay of programmable output 2

Config programmable input&output

Pulse length of programmable output 2 Address of communication port A (1-230) Baud rate of communication port A Parity check of communication port A Address of communication port B (1-230) Baud rate of communication port B

Config communication

Parity check of communication port B Destination of analog output

Config 4-20mA output Multiple of rated value Time delay of undervoltage auto restart Set undervoltage auto

restart Time limit of undervoltage

Setting

Select “SETTING” in the menu and press “ENT” key, then you enter password-input page.

22

Page 25: MCU-UNT-MMI manual.pdf

Input password

0000

Press “ESC” to move the cursor; press “↑” or “↓” to increase or decrease the selected digit, and press “ENT” to confirm. If the correct password “9998” is input, it enter to the setting page; if the password input is not correct, it return to the main menu after a message of “Password Error”. The setting pages has the same menu structure with view pages, even the operation method is identical. Press “↑” and “↓” to change the selected item or the selected digit, press “ESC” to return to the prior menu, and press “ENT” to enter to corresponding setting page. Operation example: Overheating

Run_para OH G/F

OC Jam tE

Overheating

HeatingConst:0300

Overheating

CoolingConst:0600

Overheating Enable

Heating time constant

Cooling time constant

Enable/disable overheating protection

Overheating

Alarm Trip/Alarm

Overheating

Save Cancel You can save the setting or not.

System Select “SYSTEM” in main menu, press “ENT” to enter system setting page after input password “0101”.

23

Page 26: MCU-UNT-MMI manual.pdf

VIEW SETTING

SYSTEM OTHERS

Input Password

0101

System

CtrlMode xxxx

System

Normal/spare xxxxx

System

Save Cancel

Control mode consists of local mode, remote mode and ECS mode. When the device is in local mode, you can control the motor though the push button on the faceplate and the programmable input, here the remote and ECS mode is disabled; When the device is in remote mode, remote control and programmable input control is available, here the local and ECS control is disabled; when the device is in ECS mode, ECS and programmable control is available, here the local and remote control mode is disabled.

Others

Select “OTHERS” in main menu, press “ENT” to enter system setting page after input password “1010”. There you can set time and date, clear energy consumption, clear running time of the motor and clear motor start numbers.

VIEW SETTING

SYSTEM OTHERS

Input Password

1010

Set time

Clear Energy Used

Clear Running Time

Clear Start Numbers

Reset

Select “RESET” menu in main menu, and press “ENT” key to reset trip signal output.

RESET TRIPS

INFO

Resete OK.

24

Page 27: MCU-UNT-MMI manual.pdf

Trip Records

Select “TRIPS” in main menu, press “ENT” to view the five latest trip records with pre-trip actual values, including trip type, phase currents, zero-sequence current, voltage, thermal capacity used, date and time, and so on.

Information

Select “INFO” in main menu, press “ENT” to view the moto0r running time, start numbers and protection numbers.

RESET TRIPS

INFO

Running Time

Start Numbers

Protection Numbers

25

Page 28: MCU-UNT-MMI manual.pdf

Typical Wiring

Input 4

Input 5

Input 3

Input 2

X2-1Pr

og Inp

utsPow

er

Ground

N-

Fixed

Inputs

Con

trol

Cir

cuit

Ua Ub Uc

Comm

unication

Comm A

Comm B

Shield

4-20mA Output

ProgOutput 1

ProgOutput 2

Fault TRip

Device Fault,Power Loss

CommonX2-2

X2-3

X2-4

X2-5

X2-6

X2-7

X2-8

X2-9

X2-10

X2-11

Input 1

Remote start A

Remote Start B

Remote Stop

Contactor A StatusContactor B Status

X1-1

X1-2

X1-3 L+

X1-13

X1-14

X1-12

X1-10

X3-4

X3-5

X3-6

X3-7

X3-8

X3-1

X3-2

X1-6

X1-7

-

-

+

+

X1-8

X1-9X2-14

X2-15

X2-17 X2-18 X2-19

X2-12

X2-13

X1-11

KM1KT1

KT2

KT3

Alarm X1-4

X1-5

DCS Operation

Ia Ib Ic

Alarm Signal

26

Page 29: MCU-UNT-MMI manual.pdf

Dimensions

Display Module

UNT-MMI

TRIPPED ALARM REMOTE RUNNINGCOMM SPARE

START

STOP

FRONT VIEW SIDE VIEW

Main Module

SIDE VIEW REAR VIEW

MAIN MODULE

CT

27

Page 30: MCU-UNT-MMI manual.pdf

29.0

91.1

52.0

CT1、CT2、CT3、CT4、CT6、CT7

79.5

93.7

R55.5

?30.0

56.5

52.0

111.090.0

CT5

B

C A

B

AC

28

Page 31: MCU-UNT-MMI manual.pdf

Ordering information

UNT-MMI-A × × × × × ×

1: CT1(P≤1kW) 2: CT2(1 kW <P≤10 kW) 3: CT3(10 kW <P≤25 kW) 4: CT4(25 kW <P≤50 kW) 5: CT5(50 kW <P≤75 kW) 6: CT6(75 kW <P≤200 kW, external CT output 1A)7: CT7(75 kW <P≤200 kW, external CT output 5A)1: LED display module 2: LCD display module 1: 220V/AC power supply 2: 220V/DC power supply 3: 110V/DC power supply 0: No communication 1: Profibus 2: Single Modbus 3: Double Modbus 4: CAN 0: No 4—20mA output 1: One 4—20mA output 1: Non-reversing starter 2: Reversing starter 3: Resistance Drop-Voltage starter 4: Wye-delta ransition starter 5: Autotransformer starter A: Design sequence code

29

Page 32: MCU-UNT-MMI manual.pdf

Specifications

PPoowweerr SSuuppppllyy AC nominal: 220V/50Hz DC nominal: 110V or 220V Power Range: 80%--120% Power Dissipation: 2W~6W Supply interval: 200ms EEnnvviirroonnmmeennttaall Operation temperature: -20℃--55℃ Storage temperature: -25℃--70℃ Humidity(non-condensing): 95%(max) Altitude: 2000m International Protection: IEC529-IP53 Vibration Test: Endure vibration, shock and bump test, grade 1 MMeetteerriinngg && PPrrootteeccttiioonn Metering Accuracy: Better than 1% Protection Accuracy: Better than 1% Protection time delay: <10ms OOuuttppuutt Relay Contactors: Control : 220VAC/8A(Max) Status&Signal : 220VAC/1A(Max) Programmable Output 1: 220VAC/5A(Max) Programmable Output 2: 220VAC/8A(Max) Analog Output: Output: 4—20mA Max load: 300Ω Temperature drift: 150ppm/℃ Accuracy: 0.5%

30

Page 33: MCU-UNT-MMI manual.pdf

CCoommmmuunniiccaattiioonnss Protocol: Modbus@RTU or Profibus Total station: 32 on a single channel, 122 if repeaters used Transfer medium & Max Distance:

Twisted-pair: 1km Single mode fiber 10km Multimode fiber 2km Speed:

Modbus@RTU: 6M(Max) Profibus-DP: 19.2k(Max) TTyyppee TTeessttss Fast Transient: 2kV Impulse: Differential-mode: 1kV Common-mode: 2.5kV Electrostatic Discharge : ±8kV RFI: 10V/m Insulation Resistance: ≥500MΩ Dielectric strength: 2000V,1min Shock and bump: ±5kV

31

Page 34: MCU-UNT-MMI manual.pdf

Modbus Protocol

Function code: 02—switch input

Register Address Description 10001 (0000) Programmable input 1 10002 (0001) Programmable input 2 10003 (0002) Programmable input 3 10004 (0003) Programmable input 4 10005 (0004) Programmable input 5 10006 (0005) Reserved 10007 (0006) Reserved 10008 (0007) Reserved 10009 (0008) Reserved 10010 (0009) Reserved 10011 (000A) Running in the forward direction 10012 (000B) Running in the reverse direction 10013 (000C) Remote control mode 10014 (000D) Local control mode 10015 (000E) ECS control mode 10016 (000F) Normal/Spare state (0—Normal, 1--Spare) 10017 (0010) Overheating protection 10018 (0011) Ground fault protection 10019 (0012) Overcurrent protection 10020 (0013) Trip button pressed 10021 (0014) Locked/stalled rotor protection 10022 (0015) Unbalance protection 10023 (0016) Acceleration time protection 10024 (0017) tE time protection 10025 (0018) Undervoltage protection 10026 (0019) Overvoltage protection 10027 (001A) Phase sequence protection 10028 (001B) Phase loss protection 10029 (001C) Alarm signaling 10030 (001D) Trip signaling 10031 (001E) Underpower protection 10032 (001F) SOE (1—there is new SOE information)

32

Page 35: MCU-UNT-MMI manual.pdf

Function code: 04—register input

Register Address Description 0 Programmable input 1 1 Programmable input 2 2 Programmable input 3 3 Programmable input 4 4 Programmable input 5 5 Reserved 6 Reserved 7 Reserved (remote start A) 8 Reserved (remote start B) 9 Reserved (remote stop) 10 Running in the forward direction 11 Running in the reverse direction 12 Remote control mode 13 Local control mode 14 ECS control mode

30001 (0000)

15 Normal/Spare state (0—Normal, 1--Spare) 0 Overheating protection 1 Ground fault protection 2 Overcurrent protection 3 Trip button pressed 4 Locked/stalled rotor protection 5 Unbalance protection 6 Acceleration time protection 7 tE time protection 8 Undervoltage protection 9 Overvoltage protection 10 Phase sequence protection 11 Phase loss protection 12 Alarm signaling 13 Trip signaling 14 Underpower protection

30002 (0001)

15 SOE (1—there is new SOE information) 30003 (0002) Phase current A = 30003/ctA 30004 (0003) Phase current B = 30004/ctA 30005 (0004) Phase current C = 30005/ctA 30006 (0005) Zero sequence current = 30006/ctA 30007 (0006) Positive sequence current =30007/ctA 30008 (0007) Negative sequence current =30008/ctA 30009 (0008) Thermal capacity used 30010 (0009) Active power = 30010/ctA (kW)

33

Page 36: MCU-UNT-MMI manual.pdf

30011 (000A) Reactive power = 30011/ctA (kVar) 30012 (000B) Uab 30013 (000C) Ubc 30014 (000D) ctA (CT multiple) 30015-30030 (000E-001F) Reserved 30033 (0020) Phase current A = 30033/ctA 30034 (0021) Phase current B = 30034/ctA 30035 (0022) Phase current C = 30035/ctA 30036 (0023) Zero sequence current = 30036/ctA 30037 (0024) Positive sequence current =30037/ctA 30038 (0025) Negative sequence current =30038/ctA 30039 (0026) Thermal capacity used 30040 (0027) Active power = 30040/ctA (kW) 30041 (0028) Reactive power = 30041/ctA (kVar) 30042 (0029) Uab 30043 (002A) Ubc

Pre-trip actual value

MS Byte

Trip type: 1— overheating protection 2— ground fault protection 3— overcurrent protection 4— trip button pressed 5— locked/stalled rotor protection 6— unbalance protection 7— acceleration time protection 8— tE time protection 9— undervoltage protection 10— overvoltage protection 11— phase sequence protection 12— phase loss protection 13— alarm signaling 14— trip signaling 15— underpower protection

30044 (002B)

LS Byte MS Byte Year

30045 (002C) LS Byte Month MS Byte Day

30046 (002D) LS Byte Hour MS Byte Minute

30047 (002E) LS Byte Second MS Byte Millisecond (MS)

30048 (002F) LS Byte Millisecond (LS)

SOE Information

34

Page 37: MCU-UNT-MMI manual.pdf

Function code: 05—switch output (control)

Register Address Description 00001 (0000) Start A (1—start A, 0—no operation) 00002 (0001) Start B (1—start B, 0—no operation) 00003 (0002) Reset 00004 (0003) Stop

Function code: 09—time calibration

Register Address Description 00001 (0000) Year (0-99) 00002 (0001) Month (1-12) 00003 (0002) Day (1-31) 00004 (0003) Hour (0-23) 00005 (0004) Minute (0-59) 00006 (0005) Second (0-59) 00007 (0006) Millisecond (MS) 00008 (0007) Millisecond (LS)

Millisecond range: 0-999

35