MDS Selection. Contents. Introduction Selection Consideration Selection Process Software Demonstration. Introduction. Sample of Installation. Selection Consideration. Unit & Piping Selection. Main Factors to consider during Piping Selection Location of equipment Indoor Unit - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: MDS Selection

Page 1

MDS SelectionMDS Selection

Page 2: MDS Selection

Page 2

Contents

• Introduction

• Selection Consideration

• Selection Process

• Software Demonstration

Page 3: MDS Selection

Page 3

Introduction

Page 4: MDS Selection

Page 4

Sample of Installation

Page 5: MDS Selection

Page 5

Selection Consideration

Page 6: MDS Selection

Page 6

Main Factors to consider during Piping SelectionMain Factors to consider during Piping Selection• Location of equipmentLocation of equipment• Indoor UnitIndoor Unit• Outdoor UnitOutdoor Unit• Refnet & Distributor JointRefnet & Distributor Joint

Unit & Piping Selection

These item will influence the piping layout and length of the design

Page 7: MDS Selection

Page 7

Some other factors to consider during Piping SelectionSome other factors to consider during Piping Selection• Equivalent Piping LengthEquivalent Piping Length• Type of Joint for branchesType of Joint for branches• Outdoor capacity factorOutdoor capacity factor• Piping length & height factorPiping length & height factor• Refrigerant Pipe SpecificationRefrigerant Pipe Specification

Unit & Piping Selection

Page 8: MDS Selection

Page 8

Equivalent length is the converted length and includes parts such as elbow, which has pressure losses in the pipe. The formula is as follow:

Equivalent length= Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap

Equivalent Piping Calculation

Elbow Oil Trap9.52 0.18 1.30

12.70 0.20 1.5015.88 0.25 2.0019.05 0.35 2.4022.02 0.40 3.0025.40 0.45 3.4028.58 0.50 3.7031.80 0.55 4.00

Diameter of Pipe

Equivalent Length

Recommended to install oil trap every 8 to 10 meters (vertical piping).Common for R22 and R410A

Page 9: MDS Selection

Page 9

Restriction of Piping Length

3~5 Hp 6 Hp 8~10 Hp 12~32 Hp 8 Hp 10 Hp 12~50 Hp100 125 250 350 250 250 350

Actual piping length 50 70 125 150 125 125 175Equivalent length 60 80 150 200 150 150 220

25 30

Outdoor above 20 30Indoor above 20 30

R22

40

5040

R410A

HeightBetween further indoor and outdoorMaximum height between indoor unit 15

Length (m)

Piping

Total equivalanet lengthMaximum length of longest branchMaximum equivalent length from first branch to furthers unit

Page 10: MDS Selection

Page 10

Important Factor to Consider

Example:Outdoor Model : MDS100BRPipe Diameter : 28.6 mmMain Pipe : 80mBranch Length: 20mElbows: 10 unitsOil traps: 3 units

Elbow Oil Trap9.52 0.18 1.30

12.70 0.20 1.5015.88 0.25 2.0019.05 0.35 2.4022.02 0.40 3.0025.40 0.45 3.4028.58 0.50 3.7031.80 0.55 4.00

Diameter of Pipe

Equivalent Length

Equivalent Length

= Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap= (80 + 20) + (10 X 0.5) + (3 X 3.7) = 116.1 m

Page 11: MDS Selection

Page 11

When the equivalent length is more than 90% of the maximal real length of the main tubing , the gas pipe need to be increase to one size bigger (diameter).

After expanded the gas pipe to a larger diameter, the equivalent length need to be recalculate. The formula is as follow:

Expanded Equivalent Length

= Equivalent length of main piping X 0.5 + equivalent length of the branch

Criteria 1

Criteria 2

Important Factor to Consider

Page 12: MDS Selection

Page 12

Important Factor to Consider

3~5 Hp 6 Hp 8~10 Hp 12~30 Hp100 125 250 350

Actual piping length 50 70 125 150Equivalent length 60 80 150 200

25 30

Outdoor above 20 30Indoor above 20 30

Length (m)

Piping

Height

Maximum equivalent length from first branch to furthers unit

Maximum height between indoor unit

Maximum length of longest branch

Between further indoor and outdoor

Total equivalanet length

15

40

5040

Maximum allow actual length for 10Hp is 125mCalculated Equivalent Length is 116.1mRatio of Equivalent Length over Maximum allow Actual Length= 92.88%

Equivalent length is more than 90% of the maximal real length.Hence the gas Pipe of MDS100BR need to change.

Example:

Page 13: MDS Selection

Page 13

Refrigerant Copper Pipe Specification : MDS-B

Unit & Piping Selection

Page 14: MDS Selection

Page 14

Important Factor to Consider

Example:Hence the gas Pipe of MDS100BR need to change from 28.6 mm to 39.40 mmAfter expanded the gas pipe to a larger diameter, the equivalent length need to be recalculate.

Expanded Equivalent Length = Equivalent length of main piping X 0.5 + equivalent length of the branch

Main Pipe : 80mBranch Length: 20mElbows: 10 unitsOil traps: 3 units

Equivalent Length

= Real length of tubing + No. of elbow × Equivalent length of each elbow + No. of oil trap ×Equivalent length of each oil trap= (80 + 20) + (10 X 0.5) + (3 X 3.7) = 116.1 m

Expanded Equivalent Length = [80 + (10 X 0.5) + (3 X 3.7)] X 0.5 + 20

Expanded Equivalent Length = 68.05 m

Page 15: MDS Selection

Page 15

• Type of Joint for branchesType of Joint for branches• Influence the piping layout designInfluence the piping layout design

• Outdoor capacity factorOutdoor capacity factor• Influence by the design ambient temperature and Influence by the design ambient temperature and

indoor temperatureindoor temperature• Piping length & height factor Piping length & height factor

• Influence by the location of outdoor and the total Influence by the location of outdoor and the total piping lengthpiping length

• Refrigerant Pipe SpecificationRefrigerant Pipe Specification• Use to determine the branches diameterUse to determine the branches diameter

Unit & Piping Selection

Page 16: MDS Selection

Page 16

Selection of branch joint / distributors for MDS

Unit & Piping Selection

ModelMDS-Y1MDS-Y2MDS-Y3MDS-Y4MDS-Y6MDS-Y7MDS-C1MDS-C2MDS-C3

Refnet Joint (2 Branches)

Distributors Header (4 Branches)

Optional Spec with insulation

Page 17: MDS Selection

Page 17

MDS-Y1~Y4 dimensional drawing

Unit & Piping Selection

Page 18: MDS Selection

Page 18

MDS-Y6/Y7 dimensional drawing

Unit & Piping Selection

Page 19: MDS Selection

Page 19

MDS-C1 dimensional drawing

Unit & Piping Selection

Page 20: MDS Selection

Page 20

MDS-C2~C3 dimensional drawing

Unit & Piping Selection

Page 21: MDS Selection

Page 21

Using Distribution Header may lead to imbalance refrigerant flow.

Unit & Piping Selection

Page 22: MDS Selection

Page 22

Connection Type of Refnet Joint/Distributors

Refnet Joint

Refrigerant Pipe Work

Page 23: MDS Selection

Page 23

Connection Type of Refnet Joint/Distributor

Distributor

Refrigerant Pipe Work

Page 24: MDS Selection

Page 24

Connection Type of Refnet Joint/Distributors

Refnet Joint Distributor

Refrigerant Pipe Work

Page 25: MDS Selection

Page 25

Connection Type of Refnet Joint/Distributors

Refnet Joint Distributor

Refrigerant Pipe Work

Page 26: MDS Selection

Page 26

Cooling Capacity Correction Factor (R22 & R410A)

Unit & Piping Selection

Page 27: MDS Selection

Page 27

Heating Capacity Correction Factor (R22 & R410A)

Unit & Piping Selection

Page 28: MDS Selection

Page 28

Cooling Capacity Correction Factor (R22)

Unit & Piping Selection

Page 29: MDS Selection

Page 29

Heating Capacity Correction Factor (R22)

Unit & Piping Selection

Page 30: MDS Selection

Page 30

Cooling Capacity Correction Factor (R410A)

Unit & Piping Selection

Page 31: MDS Selection

Page 31

Heating Capacity Correction Factor (R410A)

Unit & Piping Selection

Page 32: MDS Selection

Page 32

Refrigerant Pipe Specification : MDS-A (R22)

Unit & Piping Selection

Page 33: MDS Selection

Page 33

Refrigerant Pipe Specification : MDS-B (R22)

Unit & Piping Selection

Page 34: MDS Selection

Page 34

Refrigerant Pipe Specification : R410A

Unit & Piping Selection

Page 35: MDS Selection

Page 35

Additional Refrigerant Charge

Pipe Diamater (mm) 6.35 9.52 12.70 15.88 19.05

Additional Charge (g/m) 50 80 120 180 290

Pipe Diamater (mm) 6.35 9.52 12.70 15.88 19.05

Additional Charge (g/m) 45 70 120 180 260

R22

R410A

Unit & Piping Selection

Page 36: MDS Selection

Page 36

Selection Process

Page 37: MDS Selection

Page 37

Example

C

A B

D

E

F

Building Type: Bungalow

Unit & Piping Selection

Page 38: MDS Selection

Page 38

RequirementRequirementCooling only modelCooling only model• Ambient temperature : 40.0 Ambient temperature : 40.0 °C°C• Indoor temperature : 22.0 Indoor temperature : 22.0 °C °C

Other InformationOther Information• Piping lengthPiping length :: 70m70m• Height between I/OHeight between I/O :: 4m4m• Outdoor Unit located below indoorsOutdoor Unit located below indoors

Unit - AWall

Mounted

Unit - BWall

Mounted

Unit - CWall

Mounted

Unit - DWall

Mounted

Unit - ECeiling

Cassette

Unit - FCeiling

Concealed

2.7 2.7 4.8 5.0 7.5 6.0

Required Cooling Capacity

(kW)

Unit & Piping Selection

Example

Page 39: MDS Selection

Page 39

Indoor RequirementWall Mounted

WMD 09G WMD 10G WMD 15G WMD 20G WMD 25GBtu/h 8,500 9,600 12,300 19,100 22,200kW 2.5 2.8 3.6 5.6 6.5

Ceiling CassetteCKD 10C CKD 15C CKD 20C

Btu/h 9,600 12,300 19,100kW 2.8 3.6 5.6

Ceiling CassetteCKD 20A CKD 25A CKD 30A CKD 40A CKD 50A

Btu/h 19,100 22,200 30,700 38,200 47,800kW 5.6 6.5 9.0 11.2 14.0

Ceiling ConcealedCCD 10C CCD 15C CCD 20C CCD 25C

Btu/h 9,600 12,300 19,100 22,200kW 2.8 3.6 5.6 6.5

Ceiling ConcealedCCD 30C CCD 40C CCD 50C CCD 60C

Btu/h 30,700 38,200 47,800 56,000kW 9.0 11.2 14.0 16.4

COOLING ONLY MODEL

NOMINAL CAPACITY

COOLING ONLY MODEL

COOLING ONLY MODEL

COOLING ONLY MODEL

NOMINAL CAPACITY

COOLING ONLY MODEL

NOMINAL CAPACITY

NOMINAL CAPACITY

NOMINAL CAPACITY Unit - A Wall Mounted 2.7Unit - B Wall Mounted 2.7Unit - C Wall Mounted 4.8Unit - D Wall Mounted 5.0Unit - E Ceiling Cassette 7.5Unit - F Ceiling Concealed 6.0

Required Cooling Capacity(kW)

Unit & Piping Selection

Page 40: MDS Selection

Page 40

Example

A B C D E F

Capacity, kW 1.8 2.0 2.2 4.0 5.0 5.8

Model 10 10 20 20 30 25

HP of indoor unit 2.8 2.8 5.6 5.6 9.0 6.5

• Total Indoor capacity is 32.3 kW

Unit & Piping Selection

Page 41: MDS Selection

Page 41

Example

Unit & Piping Selection

ExampleSelection Criteria• Total Indoor capacity must be range between 50% ~ 120%

of the outdoor capacity.

50% of Outdoor Capacity < Indoor Capacity < 120% of Outdoor Capacity

Example:Total Indoor Capacity = 12 HP Outdoor size between 24 HP to 10 HP

• We recommend that the outdoor capacity equals to the total indoor capacity or a little larger than the indoor capacity

Page 42: MDS Selection

Page 42

Example

Selected Outdoor Selected Outdoor : : MDS120BMDS120B

Cooling CapacityCooling Capacity : 32.5kW: 32.5kW

%38.99

%1005.323.32

%100

/

CapacityOutdoorCapacityIndoorTotal

RatioOI

Comply to selection criteria

kWMDS080 24.5MDS100 28.0MDS120 32.5MDS150 40.0MDS180 47.5MDS200 50.0MDS220 55.0MDS240 65.0MDS260 70.0MDS280 75.0MDS300 80.0

ModelCooling Capacity

Unit & Piping Selection

Page 43: MDS Selection

Page 43

Example• Selected Outdoor and Indoor ModelSelected Outdoor and Indoor Model

Outdoor Model MDS 120B 32.5 kW

Indoor A WMD 10G 2.8 kW

Indoor B WMD 10G 2.8 kW

Indoor C WMD 20G 5.6 kW

Indoor D WMD 20G 5.6 kW

Indoor E CKD 30A 9.0 kW

Indoor F CCD 25C 6.5 kW

Unit & Piping Selection

Page 44: MDS Selection

Page 44

ExampleOutdoor Capacity factorOutdoor Capacity factor• Cooling only modelCooling only model• Ambient temperature : 40.0 Ambient temperature : 40.0 °C°C• Indoor temperature : 22.0 Indoor temperature : 22.0 °C°C 1.03

Unit & Piping Selection

Page 45: MDS Selection

Page 45

ExamplePiping length & height factorPiping length & height factor• Piping lengthPiping length :: 70m70m• Height between I/OHeight between I/O :: 4m4m• Outdoor Unit located below indoorsOutdoor Unit located below indoors

91%

Unit & Piping Selection

Page 46: MDS Selection

Page 46

Unit - A Wall Mounted 2.7Unit - B Wall Mounted 2.7Unit - C Wall Mounted 4.8Unit - D Wall Mounted 5.0Unit - E Ceiling Cassette 7.5Unit - F Ceiling Concealed 6.0Total Required Capacity 28.7

Required Cooling Capacity(kW)

Example

Total Capacity Total Capacity • = Outdoor Capacity X Outdoor Capacity Factor = Outdoor Capacity X Outdoor Capacity Factor • X Piping length & height FactorX Piping length & height Factor• = 32.5 kW X 1.03 X 91%= 32.5 kW X 1.03 X 91%• = 30.47 kW= 30.47 kW

Comply to requirement

Unit & Piping Selection

Indoor A WMD 10G 2.8 kW

Indoor B WMD 10G 2.8 kW

Indoor C WMD 20G 5.6 kW

Indoor D WMD 20G 5.6 kW

Indoor E CKD 30A 9.0 kW

Indoor F CCD 25C 6.5 kW

32.3 kWTOTAL

Page 47: MDS Selection

Page 47

Example

C

A B

D

E

F

Unit & Piping Selection

Building Type: Bungalow

Page 48: MDS Selection

Page 48

Example 1.1. Selection pipe diameterSelection pipe diameter

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW9.0 kW

2.8 kW

Unit & Piping Selection

Page 49: MDS Selection

Page 49

Refrigerant Pipe Specification : MDS-B

Unit & Piping Selection

Page 50: MDS Selection

Page 50

Example

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW9.0 kW

2.8 kW

Main pipeMain pipe diameter : diameter : ø ø 15.8815.88mm / ø mm / ø 28.628.6mmmm

Downstream capacityDownstream capacity

Point APoint A A-B-C : 14.9 kWA-B-C : 14.9 kWA-D-E : 17.4 kW A-D-E : 17.4 kW

Point BPoint B B-C : 8.4 kWB-C : 8.4 kWD-E : 8.4 kWD-E : 8.4 kW

Unit & Piping Selection

Page 51: MDS Selection

Page 51

Refrigerant Pipe Specification : MDS-B Point APoint A A-B-C : 14.9 kWA-B-C : 14.9 kW A-D-E : 17.4 kWA-D-E : 17.4 kW

Unit & Piping Selection

Page 52: MDS Selection

Page 52

Example

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW9.0 kW

2.8 kW

Main pipeMain pipe diameter : diameter : ø ø 15.8815.88mm / ø mm / ø 28.6028.60mmmm

A-D diameter : ø 12.70mm / ø 22.23mm

A-B diameter : A-B diameter : ø ø 9.529.52mm / ø mm / ø 19.0519.05mmmm

Unit & Piping Selection

Page 53: MDS Selection

Page 53

Example

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW9.0 kW

2.8 kW

Point BPoint BB-C : 8.4 kWB-C : 8.4 kWB-CCD25C : 6.5 kWB-CCD25C : 6.5 kW

Unit & Piping Selection

Page 54: MDS Selection

Page 54

Refrigerant Pipe Specification : MDS-B Point BPoint B B-C : 8.4 kWB-C : 8.4 kW B-CCD25C : 6.5 kW (follow indoor pipe size)B-CCD25C : 6.5 kW (follow indoor pipe size)

Unit & Piping Selection

Page 55: MDS Selection

Page 55

Example

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW9.0 kW

2.8 kW

A-B: A-B: ø ø 9.529.52

/ ø / ø 19.0519.05

B-CCD25C: B-CCD25C: ø 9.52 / ø1ø 9.52 / ø15.885.88

B-C: B-C: ø 9.52 / ø1ø 9.52 / ø15.885.88

Unit & Piping Selection

Page 56: MDS Selection

Page 56

Example

Inlet Outlet Inlet OutletTo B & C 14.90 9.52 19.05To D & E 17.40 12.70 22.23To CCD25C 6.50 9.52 15.88To C 8.40 9.52 15.88To WM D20G 5.60 6.35 15.88To WM D10G 2.80 6.35 9.52To CKD30A 9.00 9.52 15.88To E 8.40 9.52 15.88To WM D20G 5.60 6.35 15.88To WM D10G 2.80 6.35 9.52

15.88

28.60

19.05

15.88

Point E

15.88

9.52

9.52

12.70

9.52

Point A

Point B

Point C

Point D 22.23

Liquid pipe (ø, mm) Gas pipe (ø, mm)Location

Capacity (kW)

Branch

Unit & Piping Selection

Page 57: MDS Selection

Page 57

Example

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW

9.0 kW

2.8 kW

Main Pipe: ø Main Pipe: ø 15.8815.88 / ø / ø 28.628.6

B-C: ø 9.52 / ø1B-C: ø 9.52 / ø15.885.88

A-B: ø 9.52 / ø1A-B: ø 9.52 / ø19.059.05

A-D: ø12.7 / ø22.23A-D: ø12.7 / ø22.23 D-E: ø9.52 / ø1D-E: ø9.52 / ø15.885.88

Unit & Piping Selection

Page 58: MDS Selection

Page 58

Example

Selection of branchSelection of branch

Select the refnet joint of point ASelect the refnet joint of point A

A (liquid) A (liquid) : MDS-: MDS-Y2Y2

A (gas) A (gas) : MDS-: MDS-Y1Y1

A B C D E

(outer diameter)

F G H I

(outer diameter)

J K L M N

(outer diameter)

O P Q R

MDS-Y1 553 172 293 120 28.6 28.9 25.7 22.5 28.6 28.9 25.7 22.5 19.3 22.2 19.3 16.1 12.9 9.7MDS-Y2 420 142 223 80 15.88 16.1 12.9 9.7 12.7 12.9 9.7 6.5 12.7 12.9 9.7 6.5MDS-Y3 420 142 223 80 15.88 16.1 12.9 9.7 12.7 12.9 9.7 6.5 15.88 16.1 12.9 9.7MDS-Y4 493 142 223 80 22.2 22.5 19.3 16.1 19.1 19.3 16.1 12.9 9.7 19.1 19.3 16.1 12.9

Diameter (mm)Refnet model

Length(mm) Diameter (mm) Diameter (mm)

A-D diameter : A-D diameter : ø 12.70 / ø 22.23ø 12.70 / ø 22.23

A-B diameter : A-B diameter : ø 9.52 / ø 19.05ø 9.52 / ø 19.05

All unit in mm

AA

Main Pipe diameter : Main Pipe diameter : ø 15.88 / ø 28.60ø 15.88 / ø 28.60

Unit & Piping Selection

Page 59: MDS Selection

Page 59

Example

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW9.0 kW2.8 kW

Main Pipe: ø Main Pipe: ø 15.8815.88 / ø / ø 28.628.6

B-C: B-C: ø 9.52 / ø1ø 9.52 / ø15.885.88

A-B: ø 9.52 / ø1A-B: ø 9.52 / ø19.059.05

A-D: ø12.7 / ø22.23A-D: ø12.7 / ø22.23 D-E: ø9.52 / ø1D-E: ø9.52 / ø15.885.88

Liquid GasWMD 10G 6.35 9.52WMD 20G 6.35 15.88CCD 25C 9.52 15.88CKD 30A 9.52 15.88

ModelIndoor Valve Size (Ø, mm)

Unit & Piping Selection

Page 60: MDS Selection

Page 60

Example

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW9.0 kW

2.8 kW

Liquid GasTo B & CTo D & ETo CCD25CTo CTo WMD20GTo WMD10GTo CKD30ATo ETo WMD20GTo WMD10G

MDS-Y2 MDS-Y3

MDS-Y2 MDS-Y1

MDS-Y2 MDS-Y4

Refnet Joint

MDS-Y2 MDS-Y4

MDS-Y2 MDS-Y3

Point E

Point A

Point B

Point C

Point D

Location Branch

Unit & Piping Selection

Page 61: MDS Selection

Page 61

Example

Formula:

G = ∑ Li* Gi

Using liquid tube length to calculate required refrigerant. Add in refrigerant.

G : Refrigerant charge amountLi : The each section of liquid tube length in all (m)Gi : Charge amount per length ( g/m)

Unit & Piping Selection

Page 62: MDS Selection

Page 62

Example

A B C

D E

MDS120B

CCD 25C WMD 20G WMD 10G

WMD 20GCKD 30A

WMD 10G

6.5 kW5.6 kW 2.8 kW

5.6 kW9.0 kW 2.8 kW

ø ø 15.88 (10m)15.88 (10m)

ø ø 9.52 (5m)9.52 (5m)

ø ø 9.52 (2m)9.52 (2m)

ø ø 9.52 (4m)9.52 (4m)ø ø 6.35 (2m)6.35 (2m)

ø ø 6.35 (5m)6.35 (5m)

ø ø 6.35 (5m)6.35 (5m)

ø ø 6.35 (2m)6.35 (2m)

ø ø 9.52 (5m)9.52 (5m)

ø ø 9.52 (5m)9.52 (5m)

ø ø 12.7 (25m)12.7 (25m)

Total Piping Length15.88mm – 10m12.7mm – 25m9.52mm – 21m6.35mm – 14m

Unit & Piping Selection

Page 63: MDS Selection

Page 63

Example

Additional charge amount :

= ∑ Li* Gi

= (Piping Length for 15.88mm X Refrigerant Charge Amount)

+ (Piping Length for 12.7mm X Refrigerant Charge Amount)

+ (Piping Length for 9.52mm X Refrigerant Charge Amount)

+ (Piping Length for 6.35mm X Refrigerant Charge Amount)

= (10 X 180) + (25 x 120) + (21 x 80) + (14 x 50)

= 7180 g

Liquid tube diameter (mm) 6.35 9.52 12.7 15.88

Refrigerant charge amount (g/m)

50 80 120 180

Total Piping Length15.88mm – 10m 12.7mm – 25m9.52mm – 21m 6.35mm – 14m

Unit & Piping Selection

Page 64: MDS Selection

Page 64

EXV BoxEXV BoxEXV BoxEXV Box

Electronic Expansion Valve

Unit & Piping Selection

Page 65: MDS Selection

Page 65

Unit and EXV Selection - 2006

Indoor Mode R22 R410A R22 R410AWMD 09G 1/4 1/4WMD 10G 1/4 1/4WMD 15G 1/4 1/4WMD 20G 1/4 1/4WMD 25G 3/8 1/4 MEX-20-3SAP-B MEX-20-2SAP-B

CKD 10C 1/4 1/4CKD 15C 1/4 1/4CKD 20C 1/4 1/4

CKD 20A 1/4 1/4CKD 25A 3/8 1/4 MEX-20-3SAP-A MEX-20-2SAP-ACKD 30A 3/8 3/8 MEX-25-3SAP-A MEX-20-3SAP-ACKD 40A 3/8 3/8 MEX-25-3SAP-A MEX-20-3SAP-ACKD 50A 3/8 3/8 MEX-25-3SAP-A MEX-20-3SAP-A

MEX-20-2SAP-A

MEX-16-2SAP-AMEX-16-2SAP-A

MEX-20-2SAP-B

MEX-20-2SAP-A

Liquid Pipe Diamter (Inch) MEX Model

MEX-16-2SAP-BMEX-16-2SAP-BMEX-16-2SAP-B

Page 66: MDS Selection

Page 66

Unit and EXV Selection - 2006

Indoor Mode R22 R410A R22 R410ACCD 10C 1/4 1/4CCD 15C 1/4 1/4CCD 20C 1/4 1/4CCD 25C 3/8 1/4 MEX-20-3SAP-A MEX-20-2SAP-ACCD 28C - 3/8 - MEX-20-3SAP-ACCD 30C 3/8 3/8 MEX-25-3SAP-A MEX-20-3SAP-ACCD 38C - 3/8 - MEX-20-3SAP-ACCD 40C 3/8 3/8 MEX-25-3SAP-A MEX-20-3SAP-ACCD 50C 3/8 3/8 MEX-25-3SAP-A MEX-20-3SAP-ACCD 60C 1/2 3/8 MEX-25-3SAP-A MEX-25-3SAP-A

CED 15E - 1/4 - MEX-16-2SAP-ACED 20E 1/4 1/4 MEX-20-2SAP-A MEX-16-2SAP-ACED 25E 3/8 1/4 MEX-20-3SAP-A MEX-16-2SAP-ACED 28E 3/8 3/8 MEX-20-3SAP-A MEX-20-3SAP-A

CED 40D 3/8 3/8 MEX-25-3SAP-A MEX-20-3SAP-ACED 50D 3/8 3/8 MEX-25-3SAP-A MEX-20-3SAP-ACED 62C 1/2 3/8 MEX-25-3SAP-A MEX-25-3SAP-A

MEX-20-2SAP-A

Liquid Pipe Diamter (Inch) MEX Model

MEX-16-2SAP-AMEX-16-2SAP-A

Page 67: MDS Selection

Page 67

Indoor Mode R22 R410A R22 R410AWMD 09G 1/4 1/4WMD 10G 1/4 1/4WMD 15G 1/4 1/4WMD 20G 1/4 1/4 MEX-18-2SAP-D MEX-18-2SAP-DWMD 25G 3/8 1/4 MEX-18-3SAP-D MEX-22-2SAP-D

CKD 10C 1/4 1/4CKD 15C 1/4 1/4CKD 20C 1/4 1/4 MEX-18-2SAP-C MEX-18-2SAP-C

CKD 20A 1/4 1/4 MEX-18-2SAP-C MEX-22-2SAP-CCKD 25A 3/8 1/4 MEX-18-3SAP-C MEX-22-2SAP-CCKD 30A 3/8 3/8 MEX-24-3SAP-C MEX-22-3SAP-CCKD 40A 3/8 3/8 MEX-24-3SAP-C MEX-22-3SAP-CCKD 50A 3/8 3/8 MEX-24-3SAP-C MEX-22-3SAP-C

MEX-15-2SAP-CMEX-15-2SAP-C

MEX-15-2SAP-DMEX-15-2SAP-DMEX-15-2SAP-D

Liquid Pipe Diamter (Inch) MEX Model

Unit and EXV Selection - New

Marketing Bulletin: MB001-0801

Page 68: MDS Selection

Page 68

Indoor Mode R22 R410A R22 R410ACCD 10C 1/4 1/4CCD 15C 1/4 1/4CCD 20C 1/4 1/4 MEX-18-2SAP-C MEX-18-2SAP-CCCD 25C 3/8 1/4 MEX-18-3SAP-C MEX-22-2SAP-CCCD 28C - 3/8 - MEX-22-3SAP-CCCD 30C 3/8 3/8 MEX-24-3SAP-C MEX-22-3SAP-CCCD 38C - 3/8 - MEX-22-3SAP-CCCD 40C 3/8 3/8 MEX-24-3SAP-C MEX-22-3SAP-CCCD 50C 3/8 3/8 MEX-24-3SAP-C MEX-22-3SAP-CCCD 60C 1/2 3/8 MEX-24-4SAP-C MEX-24-3SAP-C

CED 15E - 1/4 - MEX-15-2SAP-CCED 20E 1/4 1/4 MEX-18-2SAP-C MEX-18-2SAP-CCED 25E 3/8 1/4 MEX-18-3SAP-C MEX-22-2SAP-CCED 28E 3/8 3/8 MEX-18-3SAP-C MEX-22-3SAP-C

CED 40D 3/8 3/8 MEX-24-3SAP-C MEX-22-3SAP-CCED 50D 3/8 3/8 MEX-24-3SAP-C MEX-22-3SAP-CCED 62C 1/2 3/8 MEX-24-4SAP-C MEX-24-3SAP-C

MEX Model

MEX-15-2SAP-CMEX-15-2SAP-C

Liquid Pipe Diamter (Inch)

Unit and EXV Selection - New

Marketing Bulletin: MB001-0801

Page 69: MDS Selection

Page 69

Software Demonstration

Page 70: MDS Selection

Page 70

Unit & Piping Selection

Page 71: MDS Selection

Page 71

The End The End