  • 7/15/2019 Midea 2005 Split Service Manual

    1/358

    CONTENTS1. DIAGNOSTIC CHART 12. The service rules of the R407C(R410a) product 53. BRIGHT STAR SERIES 84. BRIGHT ECO SERIES 45

    5. GLORY (ECO)STAR SERIES 656. GLORY GIANT 1 977. GLORY GIANT 2 1158. LIGHT STAR SERIES 1279. CUTE STAR SERIES 13910. Beta GLORY R407 15711. AC INVERT SERIES 17812. MULTI INVERTER ECO 19713. Multi-system 1 to 2 214

    14. Multi-system 1 to 3 22815. Alfa Glory H series (R410A) 24416. DC inverter(R410A) 27617. F1 STAR SERIES 30518. Alfa Glory H series 330

  • 7/15/2019 Midea 2005 Split Service Manual

    2/358

    AFLA GLORY SERIES (R410A)

    Contents

    1. Features 245

    2. Specification..246

    3. Dimensions.. 249

    4. Refrigeration cycle diagram252

    5. Pressure table..253

    6. Capacity table...256

    7. Wiring diagram..261

    8. Electronic function....265

    9. Troubleshooting.273

    10. Characteristic of temp. sensor278

  • 7/15/2019 Midea 2005 Split Service Manual

    3/358

    1.Features

    1.1 Compact design

    1.2 High efficiency and quiet operation

    1.3 A class energy level

    245

  • 7/15/2019 Midea 2005 Split Service Manual

    4/358

    2.SpecificationModel MSH-07CRN1 MSH-07HRN1 MSH-09CRN1 MSH-09HRN1 MSH-12CRN1 MSH-12HRN1

    Factor Model CE-KF20GW/N1Y-H CE-KFR20GW/N1Y-H CE-KF26GW/N1Y-H CE-KFR26GW/N1Y-H CE-KF36GW/N1Y-H CE-KFR36GW/N1

    Power su l Ph-V-Hz 1 220-240V~ 50Hz 1 220-240V~ 50Hz 1 220-240V~ 50Hz 1 220-240V~ 50Hz 1 220-240V~ 50Hz 1 220-240V~

    Ca aci t Btu/h 7000 7000 9000 9000 12000 12000

    In ut W 640 640 820 820 1120 1120

    Rated current A 2 8 2 8 3 6 3 6 5 0 5 0

    Cooling

    EER Btu/w h 11 3 2 11 3 2 11 3 2 11 3 2 11 3 2 11 3 2

    Ca aci t Btu/h 8500 11000 15000

    In ut W 690 890 1180

    Rated current A 3 0 3 9 5 3

    Heating

    COP W/W 3 6 3 6 3 6

    Moisture Removal L/h 0 7 0 7 1 0 1 0 1 2 1 2

    Max in ut consum tion W 850 1000 1000 1200 1550 1550

    Max current A 3 8 4 5 4 5 5 3 10 10

    Startin current A 15 15 22 22 30 30

    Model PA82X1C-4DZ2 PA82X1C-4DZ2 PA108X1C-4FT PA108X1C-4FT PA145X2C-4FT PA145X2C-4FT

    T e Rotar Rotar Rotar Rotar rotar rotar

    Ca aci t Btu/h 6680 6680 8870 8870 12000 12000

    In ut W 675 675 890 890 1200 1200

    Rated current RLA A 3 11 3 11 4 07 4 07 5 6 5 6

    Locked rotor Am LRA A 15 0 15 0 21 7 21 7 29 9 29 9

    Thermal rotector UP3QE0591-T71 UP3QE0591-T71 UP3QE0591-T61 UP3QE0591-T61 UP3RE0591-T56 UP3RE0591-T56

    Ca acitor uF 25 25 25 25 35 35

    Compressor

    Refri erant oil ml 350 350 330 330 480 480

    Model RPG13H RPG13H RPG13H RPG13H RPG20D RPG20D

    In ut W 36 5 36 5 36 5 36 5 51 5 51 5

    Ca acitor uF 1 2 1 2 1 2 1 2 1 5 1 5

    Indoor fan motor

    S eed hi/mi/lo r/min 1050/9200/820 1050/9200/820 1200/950/850 1200/950/850 1250/1000/800 1250/1000/800

    Number of rows 2 2 2 2 2 2

    Fin t e code H dro hil ic aluminium H dro hilic a lum inium H dro hilic a luminium H dro hilic a luminium H dr0 hiliC H dr0 h il iC

    Tubeoutside dia and t e mm 7 inner roove tube 7 inner roove 7 inner roove 7 inner roove 7 inner roove 7 inner roove

    Indoor coil

    Number of circuits 2 2 2 2 2 2

    Indoor air flow Hi/Mi/Lo m3/h 450/400/350 450/400/350 500/460/410 500/460/410 680/520/420 680/520/420

    Indoor noise level Hi/Mi/Lo dB A 34/32/30 34/32/30 36/34/32 36/34/32 39/33/28 39/33/28

    Dimension W *H*D mm 750*250*205 750*250*205 750*250*205 750*250*205 815*280*215 815*280*215

    Packin W*H*D mm 830X285X335 830X285X335 830X285X335 830X285X335 915X290X360 915X290X360

    Indoor unit

    Net/Gross wei ht K 8/10 8/10 8/10 8/10 10/12 10/12

    Model YDK24-6T YDK24-6T YDK24-6F YDK24-6F YDK36-6 YDK36-6

    In ut W 56 56 56 56 68 68

    Ca acitor uF 2 5 2 5 2 5 2 5 2 5 2 5

    Outdoor fan motor

    S eed r/min 800 800 800 800 900 900

    Number of rows 2 2 2 2 2 2

    Fin t e code Unh dro hilic aluminium H dro hilic aluminium Unh dro hilic H dro hilic aluminium Unh dro hilic H dro hilic

    Tubeoutside dia and t e mm 7 inner roove tube 7 inner roove tube 7 inner roove tube 7 inner roove tube 9 53inner roove 9 53inner roove

    Coi l len thx hei htx width mm 750x508x26 74 750x508x26 74 810x508x26 74 810x508x26 74 680x550x44 680x550x44

    Outdoor coil

    Number of circuits 2 2 2 2 2 2

    Outdoor air flow m3/h 1500 1500 1800 1800 1900 1900

    Outdoor noiselevel dB A 49 49 50 50 52 52

    Dimension W*H*D mm 700X535X235 700X535X235 780X540X250 780X540X250 760X590X285 760X590X285

    Packin W*H*D mm 815X580X325 815X580X325 910X575X335 910X575X335 890X655X360 890X655X360

    Outdoor unit

    Net/Gross wei ht K 31/34 32/35 36/39 37/40 41/45 41 5/45 5

    Refri erant t e R410A 800 820 900 920 1160 1170

    Desi n ressure MPa 4 2 4 2 4 2 4 2 4 2 4 2

    Li uid side/ Gas side mm inch 6 35/9 53 6 35/9 53 6 35/9 53 6 35/9 53 6 35/12 7 6 35/12 7

    Max refri erant i e len th m 10 10 10 10 10 10

    Refrigerant piping

    Max difference in level m 5 5 5 5 5 5

    Connection wirin No No No No No No

    Plu t e 16A 16A 16A 16A 16A 16A

    Thermostat t e Electrolic control Electrolic control Electrolic control Electrolic control Electrolic control Electrolic control

    O eration tem 17-30 17-30 17-30 17-30 17-30 17-30

    Ambient tem 18~-45 -7 -~ 45 18~-45 -7 -~ 45 18~-45 -7 -~ 45

    A lication area m2 10-14 10-14 14-21 14-21 18-26 18-26

    Qt er20 /40 /40'HQ set 128/268/296 128/268/296 113/252/276 113/252/276 92/195/228 92/195/228

    1 The noise date is base on hemi-anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient

    condition.

    246

  • 7/15/2019 Midea 2005 Split Service Manual

    5/358

    3.Dimensions

    3.1 Indoor unit

    MSH-07CRN1, MSH-07HRN1, MSH-09CRN1, MSH-09HRN1

    3.2 Indoor unit

    MSH-12CRN1, MSH-12HRN1

    247

  • 7/15/2019 Midea 2005 Split Service Manual

    6/358

    3.4 Outdoor unit

    MSH-07CRN1, MSH-07HRN1

    3.5 Outdoor unit

    MSH-09CRN1, MSH-09HRN1

    248

  • 7/15/2019 Midea 2005 Split Service Manual

    7/358

    3.6 Outdoor unit

    MSH-12CRN1, MSH-12HRN1

    530

    315

    290

    750

    110

    62

    590

    285

    249

  • 7/15/2019 Midea 2005 Split Service Manual

    8/358

    4.Refrigeration cycle diagram

    250

  • 7/15/2019 Midea 2005 Split Service Manual

    9/358

    5. Pressure table

    Note:

    *The pressure data is from 3 way valve, the pressure data are pressure above atmosphere.

    *D: Dry bulb temp.

    *W: Wet bulb temp.5.1 MSH-07CRN1

    Cooling mode Outdoor temperature (Dry bulb temp)Indoor Conditions Pressure 25C 30C 35C 40C 45C 50C

    21C D

    15C W

    Pressure

    ( kg/cm2

    )6.2 6.8 7.2 8.0 8.5 9.5

    24C D

    17C W

    Pressure

    ( kg/cm2

    )6.3 6.5 7.5 8.0 8.7 9.5

    27C D

    19C W

    Pressure

    ( kg/cm2 ) 6.1 6.9 7.7 8.2 9.1 10.0

    32C D

    23C W

    Pressure

    ( kg/cm2

    )

    7.0 7.3 7.8 8.3 9.2 10.1

    5.2 MSH-07HRN1

    Cooling mode Outdoor temperature (Dry bulb temp)Indoor

    ConditionsPressure 25C 30C 35C 40C 45C 50C

    21C D15C W Pressure( kg/cm2

    ) 6.2 6.8 7.2 8.0 8.5 9.5

    24C D

    17C W

    Pressure

    ( kg/cm2

    )6.3 6.5 7.5 8.0 8.7 9.5

    27C D

    19C W

    Pressure

    ( kg/cm2

    )6.1 6.9 7.7 8.2 9.1 10.0

    32C D

    23C W

    Pressure

    ( kg/cm2

    )

    7.0 7.3 7.8 8.3 9.2 10.1

    Heating mode OUTDOOR CONDITIONS

    Indoor Conditions Pressure12C D

    11C W

    7C D

    6C W

    0C D

    -1C W

    -4C D

    -6C W

    -7C D

    -9C W

    -15C D

    -xC W

    15CPressure

    ( kg/cm2

    )24.0 23.0 21.5 21.0 20..5 /

    18CPressure

    ( kg/cm2

    )24.6 23.5 23.0 22.6 20.8 /

    20CPressure

    ( kg/cm2

    )25.0 23.8 24.0 23.0 21.0 /

    22CPressure

    ( kg/cm2

    )25.3 24.6 24.5 23.8 21.7 /

    251

  • 7/15/2019 Midea 2005 Split Service Manual

    10/358

    5.3 MSH-09CRN1

    Cooling mode Outdoor temperature (Dry bulb temp)Indoor Conditions Pressure 25C 30C 35C 40C 45C 50C

    21C D15C W

    Pressure( kg/cm

    2)

    7.8 8.1 8.4 9.0 9.3 10.0

    24C D

    17C W

    Pressure

    ( kg/cm2

    )7.9 8.2 8.7 9.0 9.5 10.1

    27C D

    19C W

    Pressure

    ( kg/cm2

    )8.0 8.5 9.2 9.9 10.2 10.8

    32C D

    23C W

    Pressure

    ( kg/cm2

    )

    8.8 9.1 9.2 10.0 10.5 11.2

    5.4 MSH-09HRN1

    Cooling mode Outdoor temperature (Dry bulb temp)Indoor Conditions Pressure 25C 30C 35C 40C 45C 50C

    21C D

    15C W

    Pressure

    ( kg/cm2

    )7.8 8.1 8.4 9.0 9.3 10.0

    24C D

    17C W

    Pressure

    ( kg/cm2

    )7.9 8.2 8.7 9.0 9.5 10.1

    27C D

    19C W

    Pressure

    ( kg/cm2

    )8.0 8.5 9.2 9.9 10.2 10.8

    32C D

    23C W

    Pressure

    ( kg/cm2

    )

    8.8 9.1 9.2 10.0 10.5 11.2

    Heating mode OUTDOOR CONDITIONS

    Indoor Conditions Pressure12C D

    11C W

    7C D

    6C W

    0C D

    -1C W

    -4C D

    -6C W

    -7C D

    -9C W

    -15C D

    -xC W

    15CPressure

    k /cm2

    26.5 25.0 22.0 21.5 20.5 /

    18CPressure

    k /cm2

    27.0 26.0 23.5 22.5 20.8 /

    20CPressure

    k /cm2

    27.5 26.5 25.0 23.0 21.0 /

    22CPressure

    228.5 27.0 25.5 23.9 21.5 /

    252

  • 7/15/2019 Midea 2005 Split Service Manual

    11/358

    5.5 MSH-12CRN1

    Cooling mode Outdoor temperature (Dry bulb temp)Indoor Conditions Pressure 25C 30C 35C 40C 45C 50C

    21C D

    15C W

    Pressure

    ( kg/cm2

    )8.4 8.5 8.8 8.9 9.4 9.9

    24C D

    17C W

    Pressure

    ( kg/cm2

    )8.6 8.8 9.2 9.4 10.0 10.4

    27C D

    19C W

    Pressure

    ( kg/cm2

    )8.8 9.2 9.4 9.8 10.3 10.9

    32C D

    23C W

    Pressure

    ( kg/cm

    2

    )

    9.2 9.6 9.9 10.4 10.8 11.2

    5.6 MSH-12HRN1

    Cooling mode Outdoor temperature (Dry bulb temp)

    Indoor Conditions Pressure 25C 30C 35C 40C 45C 50C

    21C D

    15C W

    Pressure

    ( kg/cm2

    )8.4 8.5 8.8 8.9 9.4 9.9

    24C D

    17C W

    Pressure

    ( kg/cm2

    )8.6 8.8 9.2 9.4 10.0 10.4

    27C D

    19C W

    Pressure

    ( kg/cm2

    )8.8 9.2 9.4 9.8 10.3 10.9

    32C D

    23C W

    Pressure

    ( kg/cm2

    )

    9.2 9.6 9.9 10.4 10.8 11.2

    Heating mode OUTDOOR CONDITIONS

    Indoor Conditions Pressure12C D

    11C W

    7C D

    6C W

    0C D

    -1C W

    -4C D

    -6C W

    -7C D

    -9C W

    -15C D

    -xC W

    15CPressure

    k /cm2

    27.4 25.9 22.2 21.4 20.0 /

    18CPressure

    k /cm2

    29.8 27.2 23.8 22.0 21.1 /

    20CPressure

    k /cm2

    30.2 29.1 24.2 23.6 22.1 /

    22CPressure

    232.4 30.1 25.4 24.0 22.7 /

    253

  • 7/15/2019 Midea 2005 Split Service Manual

    12/358

    6. Capacity table

    6.1 MSH-07CRN1

    SUMMER OUTDOOR TEMPERATURE DRY

    Indoor

    Conditions

    25C 30C 35C 40C 45C 50C

    Total capacity kW 2.06 1.95 1.75 1.51 1.58 1.41

    Sensitive capacity kW 1.52 1.37 1.39 1.32 1.19 1.0721C D

    15C WInput kW. 0.53 0.58 0.62 0.63 0.78 0.80

    Total capacity kW 2.14 2.05 1.96 1.72 1.73 1.52

    Sensitive capacity kW 1.61 1.46 1.45 1.54 1.23 1.1524C D

    17C WInput kW. 0.60 0.60 0.66 0.65 0.78 0.83

    Total capacity kW 2.31 2.24 2.10 1.90 1.73 1.67

    Sensitive capacity kW 1.78 1.65 1.42 1.43 1.26 1.2827C D

    19C WInput kW. 0.55 0.63 0.64 0.70 0.79 0.84

    Total capacity kW 2.33 2.33 2.31 2.38 2.15 2.07

    Sensitive capacity kW 1.83 1.67 1.65 1.64 1.57 1.5332C D

    23C WInput kW. 0.53 0.65 0.69 0.73 0.83 0.88

    6.2 MSH-07HRN1

    SUMMER OUTDOOR TEMPERATURE DRY

    Indoor

    Conditions25C 30C 35C 40C 45C 50C

    Total capacity kW 2.04 1.94 1.70 1.61 1.53 1.41

    Sensitive capacity kW 1.52 1.41 1.39 1.32 1.19 1.0721C D

    15C WInput kW. 0.53 0.58 0.60 0.67 0.73 0.80

    Total capacity kW 2.14 2.05 1.93 1.81 1.73 1.51

    Sensitive capacity kW 1.61 1.46 1.45 1.54 1.23 1.1524C D

    17C WInput kW. 0.54 0.60 0.62 0.70 0.74 0.82

    Total capacity kW 2.31 2.24 2.05 1.95 1.70 1.65

    Sensitive capacity kW 1.78 1.65 1.54 1.43 1.26 1.2827C D

    19C WInput kW. 0.57 0.62 0.64 0.71 0.75 0.83

    Total capacity kW 2.33 2.36 2.31 2.25 2.15 2.03

    Sensitive capacity kW 1.83 1.67 1.65 1.64 1.57 1.5232C D23C W

    Input kW. 0.58 0.64 0.66 0.73 0.80 0.86

    254

  • 7/15/2019 Midea 2005 Split Service Manual

    13/358

    WINTER OUTDOOR CONDITIONS

    Indoor

    Conditions

    12C D

    11C W

    7C D

    6C W

    4C D

    3C W

    0C D

    -1C W

    -4C D

    -6C W

    -7C D

    -8C W

    Capacity kW 3.01 2.73 2.47 1.76 1.65 1.5815CInput kW. 0.76 0.66 0.60 0.58 0.50 0.45

    Capacity kW 2.86 2.64 2.34 1.69 1.53 1.4118C

    Input kW. 0.78 0.67 0.62 0.59 0.62 0.47

    Capacity kW 2.77 2.49 2.28 1.62 1.59 1.3320C

    Input kW. 0.81 0.69 0.64 0.59 0.53 0.48

    Capacity kW 2.61 2.43 2.13 1.58 1.26 1.1722C

    Input kW. 0.83 0.68 0.65 0.60 0.56 0.51

    6.3 MSH-09CRN1

    SUMMER OUTDOOR TEMPERATURE DRY

    Indoor

    Conditions25C 30C 35C 40C 45C 50C

    Total capacity kW 2.42 2.37 2.23 2.03 1.87 1.75

    Sensitive capacity kW 1.72 1.69 1.65 1.53 1.43 1.3621C D

    15C WInput kW. 0.72 0.75 0.80 0.84 0.89 0.96

    Total capacity kW 0.65 2.55 2.45 2.24 2.11 1.98

    Sensitive capacity kW 1.83 1.73 1.70 1.63 1.63 1.5724C D

    17C WInput kW. 0.70 0.76 0.84 0.88 0.92 1.01

    Total capacity kW 2.89 2.80 2.66 2.46 2.25 2.03

    Sensitive capacity kW 1.95 1.91 1.83 1.78 1.66 1.6327C D

    19C WInput kW. 0.65 0.78 0.82 0.91 0.95 1.02

    Total capacity kW 3.01 2.98 2.92 2.83 2.69 2.45

    Sensitive capacity kW 2.05 1.88 1.96 1.87 1.87 1.8532C D

    23C WInput kW. 0.64 0.80 0.88 0.98 1.03 1.10

    255

  • 7/15/2019 Midea 2005 Split Service Manual

    14/358

    6.4 MSH-09HRN1

    SUMMER OUTDOOR TEMPERATURE DRY

    Indoor

    Conditions

    25C 30C 35C 40C 45C 50C

    Total capacity kW 2.42 2.41 2.24 2.03 1.87 1.75

    Sensitive capacity kW 1.72 1.69 1.65 1.53 1.43 1.3621C D

    15C WInput kW. 0.72 0.75 0.80 0.84 0.89 0.97

    Total capacity kW 0.65 2.55 2.45 2.24 2.11 1.98

    Sensitive capacity kW 1.83 1.73 1.70 1.63 1.63 1.5724C D

    17C WInput kW. 0.68 0.76 0.81 0.88 0.93 1.02

    Total capacity kW 2.89 2.80 2.63 2.45 2.23 2.05

    Sensitive capacity kW 1.99 1.95 1.81 1.78 1.66 1.6327C D

    19C WInput kW. 0.65 0.78 0.82 0.92 0.96 1.03

    Total capacity kW 3.03 2.98 2.92 2.83 2.69 2.46

    Sensitive capacity kW 2.05 1.88 1.96 1.87 1.87 1.8532C D

    23C WInput kW. 0.65 0.80 0.86 0.95 0.99 1.08

    WINTER OUTDOOR CONDITIONS

    Indoor

    Conditions

    12C D

    11C W

    7C D

    6C W

    4C D

    3C W

    0C D

    -1C W

    -4C D

    -6C W

    -7C D

    -8C W

    Capacity kW 3.75 3.38 3.02 1.97 1.59 1.5215C

    Input kW. 0.97 0.84 0.73 0.65 0.62 0.63

    Capacity kW 3.52 3.26 2.94 1.84 1.60 1.4918C

    Input kW. 0.98 0.86 0.78 0.70 0.65 0.68

    Capacity kW 3.45 3.22 2.85 1.82 1.56 1.5020C

    Input kW. 1.02 0.89 0.80 0.74 0.68 0.67

    Capacity kW 3.18 3.13 2.72 1.73 1.58 1.4222C

    Input kW. 1.06 0.93 0.82 0.77 0.71 0.65

    256

  • 7/15/2019 Midea 2005 Split Service Manual

    15/358

    6.5 MSH-12CRN1

    SUMMER OUTDOOR TEMPERATURE DRY

    Indoor

    Conditions

    25C 30C 35C 40C 45C 50C

    Total capacity kW 3304 3198 3921 2856 2787 2684

    Sensitive capacity kW 2607 2497 2411 2304 2242 211121C D

    15C WInput kW. 907 1006 1096 1184 1259 1457

    Total capacity kW 3683 3511 3339 3166 3066 2960

    Sensitive capacity kW 2938 2790 2745 2580 2470 235924C D

    17C WInput kW. 926 1035 1127 1230 1278 1380

    Total capacity kW 3896 3718 3646 3387 3235 3232

    Sensitive capacity kW 3076 2938 2856 2690 2580 247027C D

    19C WInput kW. 943 1058 1120 1265 1322 1437

    Total capacity kW 4199 4009 3850 3614 3541 3370

    Sensitive capacity kW 3098 2990 2745 2607 255232C D

    23C WInput kW. 977 1090 1190 1310 1368 1495

    2900

    6.6 MSH-12HRN1

    SUMMER OUTDOOR TEMPERATURE DRY

    Indoor

    Conditions25C 30C 35C 40C 45C 50C

    Total capacity kW 3276 3187 3105 2821 2746 2621

    Sensitive capacity kW 2567 2457 2413 2287 2210 208721C D

    15C WInput kW. 890 1010 1082 1188 1243 1337

    Total capacity kW 3663 3503 3315 3148 3076 2932

    Sensitive capacity kW 2918 2766 2725 2557 2453 233424C D

    17C WInput kW. 915 1033 1121 1228 1278 1367

    Total capacity kW 3860 3700 3626 3371 3215 3125

    Sensitive capacity kW 3039 2913 2832 2645 2567 241927C D

    19C WInput kW. 944 1048 1120 1253 1312 1426

    Total capacity kW 4215 4100 3845 3601 3501 3313

    Sensitive capacity kW 3120 2939 2891 2715 2589 250332C D23C W

    Input kW. 969 1088 1189 1302 1349 1455

    257

  • 7/15/2019 Midea 2005 Split Service Manual

    16/358

    WINTER OUTDOOR CONDITIONS

    Indoor

    Conditions

    12C D

    11C W

    7C D

    6C W

    4C D

    3C W

    0C D

    -1C W

    -4C D

    -6C W

    -7C D

    -8C W

    Capacity kW 4446 4264 4132 3838 3335 30515CInput kW. 1141 1106 1059 1035 895 812

    Capacity kW 4380 4248 3954 3761 3258 294818C

    Input kW. 1188 1153 1142 1082 953 918

    Capacity kW 4261 4153 3877 3683 3189 287120C

    Input kW. 1224 1180 1129 1082 976 941

    Capacity kW 4106 3989 3761 3567 3045 287622C

    Input kW. 1259 1212 1153 1106 1000 836

    258

  • 7/15/2019 Midea 2005 Split Service Manual

    17/358

  • 7/15/2019 Midea 2005 Split Service Manual

    18/358

    7.2 Wiring diagram

    7.2.1 Cooling only

    7.2.1.1 MSH-07CRN1, MSH-09CRN1

    1 2 3 4 5

    1 2 3 4 5

    2 1

    2 1

    2 1

    2 1

    3 51

    3 51

    3 2 1

    3 2 1

    3

    1

    1

    1 4

    DISPLAY

    BOARD

    CN6 CN4 CN12 CN2 CN3

    CN11RED

    BLUE

    BLACK

    CN1

    TRANSFORMER

    CN5

    POWER SUPPLY INDO OR MOTOR

    STEP MOTOR

    R

    OOM

    TE

    MPERAT

    URE

    SE

    NSOR

    PI

    PE

    TEM

    PERATUR

    E

    SEN

    SOR

    JX1

    INDOOR UNIT

    TO OUTDOOR UNIT

    Y/G

    1 2(N) 3 4

    BROWN

    Y/G

    COMPRESSOR R ELAY

    CN15

    8

    765

    4321

    4

    C N7 CN16

    21

    21

    21

    21

    SW2

    WATER SWITCH

    COMPRESSOR

    CAPACITOR

    RE

    OTOOR I T

    OEROA

    REA

    Y G

    COMPRESSOR

    S

    C

    E

    R

    AC

    RE

    AC

    I NDOOR UNIT

    FAN

    CAPACITOR

    RED

    Y G

    FAN

    MOTOR

    Y G

    UE

    AC

    RED

    260

  • 7/15/2019 Midea 2005 Split Service Manual

    19/358

    7.2.1.2 MSH-12CRN1

    1 2 3 4 5

    1 2 3 4 5

    2 1

    2 1

    2 1

    2 1

    3 51

    3 51

    3 2 1

    3 2 1

    3

    1

    1

    1 4

    DISPLAY

    BOARD

    CN6 CN4 CN12 CN2 CN3

    CN11RED

    BLUE

    BLACK

    CN1

    TRANSFORMER

    CN5

    POWER SUPPLY INDO OR MOTOR

    STEP MOTOR

    R

    OOM

    TE

    MPERAT

    URE

    SE

    NSOR

    PI

    PE

    TEM

    PERATUR

    E

    SEN

    SOR

    JX1

    INDOOR UNIT

    TO OUTDOOR UNIT

    Y/G

    1 2(N) 3 4

    BROWN

    Y/G

    COMPRESSOR R ELAYCN15

    8

    765

    4321

    4

    C N7 CN16

    21

    21

    21

    21

    SW2

    WATER SWITCH

    261

  • 7/15/2019 Midea 2005 Split Service Manual

    20/358

    7.2.2 Heating/cooling

    7.2.2.1 MSH-07HRN1, MSH-09HRN1

    1 2 3 4 5

    1 2 3 4 5

    2 1

    2 1

    2 1

    2 1

    3 51

    3 51

    3 2 1

    3 2 1

    2

    1

    1 4

    DISPLAY

    BOARD

    CN6 CN4 CN12 CN2 CN3

    CN11RED

    BLUE

    BLACK

    CN1

    TRANSFORMER

    CN5

    POWER SUPPLY INDO OR MOTOR

    STEP MOTOR

    R

    OOM

    TE

    MPERAT

    URE

    SE

    NSOR

    PI

    PE

    TEM

    PERATUR

    E

    SEN

    SOR

    JX1

    INDOOR UNIT

    TO OUTDOOR UNIT

    Y/G

    1 2(N) 3 4

    BROWN

    Y/G

    COMPRESSOR R ELAYCN15

    8

    765

    4321

    4

    C N7 CN16

    21

    21

    21

    21

    SW2WATER SWITCH

    CN13

    1 21

    1

    2

    11

    262

  • 7/15/2019 Midea 2005 Split Service Manual

    21/358

    7.2.2.2 MSH-12HRN1

    1 2 3 4 5

    1 2 3 4 5

    2 1

    2 1

    2 1

    2 1

    3 51

    3 51

    3 2 1

    3 2 1

    2

    1

    1 4

    DISPLAY

    BOARD

    CN6 CN4 CN12 CN2 CN3

    CN11RED

    BLUE

    BLACK

    CN1

    TRANSFORMER

    CN5

    POWER SUPPLY

    INDO OR MOTOR

    STEP MOTOR

    R

    OOM

    TE

    MP

    ERAT

    URE

    SE

    NS

    OR

    PI

    PE

    TEM

    PER

    ATUR

    E

    SEN

    SOR

    JX1

    INDOOR UNIT

    TO OUTDOOR UNIT

    Y/G

    1 2(N) 3 4

    BROWN

    Y/G

    COMPRESSOR R ELAYCN15

    8

    765

    4321

    4

    C N7 CN16

    21

    21

    21

    21

    SW2WATER SWITCH

    CN13

    1 21

    1

    2

    11

    263

  • 7/15/2019 Midea 2005 Split Service Manual

    22/358

    8 Electronic function

    8.1 Electric Control working environment

    8.1.1 input voltage: 175~253V

    8.1.2 Input power frequency:50Hz

    8.1.3 Ambient temperature: -7C~+43C

    8.1.4 Indoor fan normal working amp is less than 1A,

    8.1.5 Outdoor fan. Normal working amp is less than 1.5A

    8.1.6 Four-way valve normal working amp is less than 1A.

    8.1.7 Swing motor: DC12V.

    8.1.8 Compressor: single-phase power supply. Its normal working amp is less than 15A

    8.2 Proper symbols and their meanings:

    TA: Indoor ambient temperature

    TE: Indoor evaporator temperature

    TS: Setting temperature through the remote controller

    I3sec: Self-protection amp of compressor, continue three seconds until turns off the compressor.

    I5MIN: Self-protection amp of compressor, continue five minutes until turns off the compressor.

    IFAN: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to lower wind.

    IRESTORE: Amp self-protection return value

    THDEFROST: High wind, defrosting temperature difference

    TMDEFROST: Middle wind, defrosting temperature difference

    TLDEFROST: Low wind, defrosting temperature difference

    TE1: Anti-cold wind, from Fan Off to Breeze temperature

    TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature

    TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature

    TE4: Anti-cold wind, from Breeze to Fan Off temperature

    TE5: Evaporator low temperature protection entering temperature

    TE6: Evaporator low temperature protection restoring temperature

    TE7: Evaporator high temperature protection, compressor off temperature

    TE8: Evaporator high temperature protection, fan off temperature

    TE9: Evaporator high temperature protection, restoring temperature

    8.3 Functions

    Remote receivingTesting and forced running

    Position set for indoor unit wind vane

    LED displaying and alarm

    On or off Timer

    Protection for the compressor

    Current protection

    High temperature protection of indoor heat exchanger at heating mode

    Auto defrosting and heating recovery at heating mode

    Anti cold air at heating mode

    Anti frozen at cooling mode

    264

  • 7/15/2019 Midea 2005 Split Service Manual

    23/358

    8.4 Protection

    8.4.1 3 minutes delay at restart for compressor.

    8.4.2 Sensor protection at open circuit and breaking disconnection

    8.4.3 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or

    too low(lower than 400RPM), the unit stops and LED displays failure information and cant returns to

    normal operation automatically.

    8.4.4 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and LED

    displays failure information and cant returns to normal operation automatically.

    8.4.5 The current protection of the compressor

    Condition Indoor fan Compressor Outdoor fan Remark

    I< IRESTORE On On On

    On On Off Heating modeIRESTORE

  • 7/15/2019 Midea 2005 Split Service Manual

    24/358

    Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. )

    Condition

    Temp. Time

    Compressor Outdoor fan

    T> TE6 On OnEvaporatorTemp. up

    T< TE6 >5 Minutes Off Off

    T> TE5 On OnEvaporatorTemp. down

    T< TE5 >5 Minutes Off Off

    8.7 Dehumidifying mode

    8.7.1 The 4-way valve is off in dehumidifying mode

    8.7.2 Compressor and Indoor Fan actions in dehumidifying mode

    NO Conditions Indoor Fan Compressor and Outdoor Fan

    1 TA TS+2LOW

    BREEZE

    ON 6minutes

    OFF 4minutes

    2 TS TA

  • 7/15/2019 Midea 2005 Split Service Manual

    25/358

    8.7.3 Low room temperature protection:

    When room temperature decreases to below 10, compressor and outdoor fan will stop(indoor fan

    is Breeze). Dehumidifying operation will be resumed when room temperature restores to over 13.

    8.7.4 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that

    of cooling mode.

    8.7.5 At dehumidifying mode, the action of fans of indoor is the same as that of air-only mode.

    8.8 Heating mode

    8.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve

    must delay 2 minutes compared with compressor if the compressor changed into non-heating mode

    or turned off. 4-way valve doesn't delay in dehumidifying mode.

    8.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except

    for the defrosting mode or the end of defrost.

    8.8.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes

    after starting and then judge temperature. Meanwhile other protections are still valid.Condition Compressor Outdoor fan

    T> Ts+3 Off OffRoom temp. up

    TTs+2 Off Off

    8.8.4 Indoor Fan actions at heating mode

    Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind

    function prevails.Anti-cold wind control function at heating mode

    Condition

    T= Indoor exchanger temp.

    Indoor fan speed

    T

  • 7/15/2019 Midea 2005 Split Service Manual

    26/358

    8.8.6 Indoor evaporator high-temperature protection at heating mode

    Condition

    T= Indoor exchanger temp.

    Compressor Outdoor fan

    T

  • 7/15/2019 Midea 2005 Split Service Manual

    27/358

    8.9.4 Defrosting Actions:

    Defrost 10or 6minutes

    45S 25S

    Compressor

    4-way Valve 23S

    40S

    Outdoor Fan

    Indoor Fan

    10S

    8.10 Automatic operation mode

    8.10.1 The air conditioner automatically selects one of the following operation modes: cooling, heating or

    fan only according to the temp. difference between room temp. (TA) and set temp. (TS).

    TATS Operation mode

    TATS>2 Cooling

    -1 TA -TS+2 Fan-only

    TA-TS

  • 7/15/2019 Midea 2005 Split Service Manual

    28/358

    constant and the fan speed is kept at low speed.

    8.14.3 Heating:

    The set temperature decrease 1 per hour. Two hours later, the set temperature will maintain as a

    constant and the air circulation is kept at low speed (Cold air proof function takes precedence over

    all).

    8.14.4 Auto:

    The economic running function operates in accordance with selected running mode by auto mode.

    8.15 Auto restart function

    In case of a sudden power failure, this function automatically sets the unit to previous settings before

    the power failure when power returns.

    270

  • 7/15/2019 Midea 2005 Split Service Manual

    29/358

    8.16 Models and Parameters

    Model MSH-07CRN2 MSH-07HRN2 MSH-09CRN2 MSH-09HRN2 MSH-12CRN2 MSH-12HRN2

    I3SEC 7.5A 7.5A 10.0A 10.0A 12.0A 12.0A

    I5MIN 6.2A 6.2A 7.5A 7.5A 8.5A 8.5A

    IFAN 5.2A 5.2A 5.5A 5.5A 7.5A 7.5A

    IRESTORE 4.2A 4.2A 4.5A 4.5A 6.5A 6.5A

    IDEFROST 3.2A 3.5A 5.0A

    TE1 28 28 34

    TE2 32 32 37

    TE3 30 30 33

    TE4 26 26 22

    TE5 4 4 4 4 3 3

    TE6 10 10 10 10 10 10

    TE7 60 60 63

    TE8 53 53 53

    TE9 50 50 50

    ANGLCOOL 200 200 200 200 155 155

    ANGLHEAT 0 0 10

    ANGLOFF 124 124 124 124 124 124

    THDEFROST 17C 17C 20C

    TMDEFROST 18C 18C 23C

    TLDEFROST 19C 19C 26C

    271

  • 7/15/2019 Midea 2005 Split Service Manual

    30/358

    9.Troubleshooting

    9.1 Display board

    1 2 3 4 5 6InfraredSignalReceiver

    1: AUTO indicator

    2: TIMER indicator

    3: PRE.-DEF. Indicator

    4: OPERATION indicator

    5: SLEEP indicator

    9.2 For all heat pump model

    Failure phenomenon Operation lamp Timer lamp

    Indoor fan speed has been out of control for over 1 minute X

    Indoor room temp. or evaporator sensor is open circuit or short circuit On

    Over current protection of the compressor occurs 4 times X

    EEROM error On

    No over-zero signal

    r Extinguish

    Flash at 5Hz

    272

  • 7/15/2019 Midea 2005 Split Service Manual

    31/358

    9.3 Diagnostic Chart

    9.3.1 After energizing, no indicator is lighted and the air conditioner cant be operated.

    After energizing, the air conditionercant be operated

    Yes

    Yes No

    No Yes

    Yes

    No

    9.3.2 Resetting phenomenon often occurs during operation. (That is automatically entering to the status when

    power is on.)

    The reason is that the instantaneous voltage of main chip is less than 4.5V. Check according to the following procedure:

    Yes

    No Yes

    No

    Check if AC220V power supply outputs to Indoor PCB.

    Check if AC220V exists at the primary coil of transformer.

    Indoor PCB is defective

    Check if AC14.5V exists at the secondary coil of transformer.

    Take off the secondary plug of transformer, and then check if

    AC14.5V exists at the secondary coil of transformer.

    The transformer is defective. Indoor PCB is defective

    After changing indoor fan motor, check if the failure releases. Indoor PCB is defective

    After changing Indoor PCB, check if the failure releases.

    Power supply circuit has problems.

    Resetting phenomenon often occurs during operation.

    273

  • 7/15/2019 Midea 2005 Split Service Manual

    32/358

    9.3.3 Failure phenomenon

    Failure phenomenon Operation lamp Timer lamp

    Indoor fan speed has been out of control for over 1 minute X

    Indoor room temp. or evaporator sensor is open circuit or short circuit On

    Over current protection of the compressor occurs 4 times X

    EEROM error On

    No over-zero signal

    r Extinguish

    Flash at 5Hz9.3.3.1 Operation lamp flashes and Timer lamp off.

    Is connector connection good?

    Is voltage being applied to the fan motor?

    Fan motor is defective

    Repair the connector

    NoYes

    Yes No

    Indoor PCB is defective

    9.3.3.2 Operation lamp flashes and Timer lamp on.

    Is connection to connector good?

    Replace the sensor

    NoYes

    Repair connector

    9.3.3.3 Operation lamp off and Timer lamp flashes

    No Yes

    Yes No

    Indoor PCB is defective

    Power supply fault Outdoor unit fault (such as the compressor)

    Yes

    After changing the main control board, check if the failure releases.

    The voltage of power supply is too low (less than 187V)?

    Operation lamp off and Timer lamp flashes

    9.3.3.4 Operation lamp on and Timer lamp flashes

    EEROM error, indoor PCB is defective.

    9.3.3.5 Operation lamp flashes, Timer lamp flashes .This is alarm signal when the main chip cant detect over-zero signal. When such failure occurs, the main

    control board must have fault.

    274

  • 7/15/2019 Midea 2005 Split Service Manual

    33/358

    275

    10. Characteristic of temp. sensor

    Temp. Resistance K Temp. Resistance K Temp. Resistance K

    -10 62.2756 17 14.6181 44 4.3874

    -9 58.7079 18 13.918 45 4.2126

    -8 56.3694 19 13.2631 46 4.0459

    -7 52.2438 20 12.6431 47 3.8867

    -6 49.3161 21 12.0561 48 3.7348

    -5 46.5725 22 11.5 49 3.5896

    -4 44 23 10.9731 50 3.451

    -3 41.5878 24 10.4736 51 3.3185

    -2 39.8239 25 10 52 3.1918

    -1 37.1988 26 9.5507 53 3.0707

    0 35.2024 27 9.1245 54 2.959

    1 33.3269 28 8.7198 55 2.8442

    2 31.5635 29 8.3357 56 2.7382

    3 29.9058 30 7.9708 57 2.6368

    4 28.3459 31 7.6241 58 2.5397

    5 26.8778 32 7.2946 59 2.4468

    6 25.4954 33 6.9814 60 2.3577

    7 24.1932 34 6.6835 61 2.2725

    8 22.5662 35 6.4002 62 2.1907

    9 21.8094 36 6.1306 63 2.1124

    10 20.7184 37 5.8736 64 2.0373

    11 19.6891 38 5.6296 65 1.9653

    12 18.7177 39 5.3969 66 1.8963

    13 17.8005 40 5.1752 67 1.830

    14 16.9341 41 4.9639 68 1.7665

    15 16.1156 42 4.7625 69 1.7055

    16 15.3418 43 4.5705 70 1.6469

  • 7/15/2019 Midea 2005 Split Service Manual

    34/358

    228

    Multi ECO SERIES

    1. Features 229

    2. Specification 230

    3. Dimensions 231

    4. Refrigeration cycle diagram 232

    5. Operation limits 233

    6. Wiring diagram 234

    7. Troubleshooting 236

    8. Electronic function 238

  • 7/15/2019 Midea 2005 Split Service Manual

    35/358

    229

    1.Features

    1.1 Compact design

    1.2 High efficiency and quiet operation

  • 7/15/2019 Midea 2005 Split Service Manual

    36/358

    230

    2.Specification

    Model MS3G-30HRN2 MS3G-27HRN2

    Power su l Ph-V-Hz 1Ph,220-240V~,50Hz 1Ph,220-240V~,50Hz

    Capacity Btu/h 9000x2+12000 9000x2+10000

    Input W 1800+1300 1800+1300

    Rated current A 8.2+5.8 8.2+5.8

    Cooling

    EER Btu/w.h 10+9.2 10+9.0

    Capacity Btu/h 10000x2+13000 10000x2+13000

    Input W 1750+1250 1750+1250

    Rated current A 8.0+5.6 8.0+5.6

    Heating

    COP Btu/w.h 3.4+3.0 3.4+2.8

    Moisture Removal L/h 1.0x2 +1.2 1.0x2 +1.2

    Max. in ut consum tion W 2200+1800 2200+1800

    Max. current A 10.0 +8.2 10.0 +8.2

    Startin current A 40+30 40+30

    Model PG295X2CS-4KU1; PG295X2CS-4KU1;

    Type Rotary / GD Toshiba Rotary / GD Toshiba

    Capacity Btu/h 18080; 13650 18080; 13650

    Input W 1760; 1310 1760; 1310

    Rated A 8.5; 6.1 8.5; 6.1

    Thermal protector Internal Internal

    Capacitor uF 35uF/440VAC; 35uF/440VAC;

    Compressor

    Refrigerant oil ml 750; 480 750; 480

    Model RPG13H RPG13H

    Input W 36.5 36.5

    Capacitor uF 1.2F/450V 1.2F/450V

    Indoor fan motor

    Speed(hi/mi/lo) r/min 1350 1350

    Indoor air flow (Hi/Mi/Lo) m3/h 550 550

    Indoor noise level (Hi/Mi/Lo) dB(A) 38/35/31 38/35/31

    Dimension mm 750250188 750250188

    Packing mm 830X336X280 830X336X280Indoor unit

    Net/Gross weight Kg 8.5/10 8.5/10

    Model YDK50-4G1 YDK50-4G1

    Input W 107Wx2 107Wx2

    Capacitor uF 4uFx2 4uFx2

    Outdoor fan motor

    Speed r/min 1150 1150

    Outdoor air flow m3/h 1450x2 1450x2

    Outdoor noise level dB(A) 57 57

    Dimension(W*H*D) mm 860X830X330

    Packing (W*H*D) mm 983X915X425Outdoor unit

    Net/Gross weight Kg 81/88

    Refri erant t e R407C 1470+820 R407C 1470+820Desi n ressure MPa 2.6 2.6

    Liquid side/ Gas mm 6.35/9.53(A

    Max. refrigerant m 15(each unit) 15(each unit)Refrigerant piping

    Max. difference in m 5 (each unit) 5 (each unit)

    O eration tem 17~30 17~30

    Ambient tem -7~45 -7~45

    A lication area m2 (14-21)x2,18-26 (14-21)x2,18-26

  • 7/15/2019 Midea 2005 Split Service Manual

    37/358

    231

    3.Dimensions

    3.1 Indoor unit

    3.2 Outdoor unit

  • 7/15/2019 Midea 2005 Split Service Manual

    38/358

    232

    4.Refrigeration cycle d iagram

    1 drive 3 system is made up of one 1 drive 1 system and one 1 drive 2 system.

    PMV1

    1 drive 2 system

    SV1Primary four-way valve SV2Secondary four-way valve PMV1PMV2Electronic expansive valve

    T1T2Indoor pipe temperature sensor

    condenser

    four-way valveevaporator

    compressor

    1 drive 1 system

    PMV2SV2 SV1

    21T2

    T1

    refrigeration distributor

    Compressor

  • 7/15/2019 Midea 2005 Split Service Manual

    39/358

    233

    5.Operation limits

    5.1Cooling operation

    Outdoor unit air temp. DB

    45

    40

    35

    30

    25

    20

    0 25 50

    Indoor air temp. DB

    Note : The chart is the result from the continuous operation under constant air temperature

    conditions. However, excludes the initial pull-down stage.

    5.2Heating operation

    Indoor air temp. DB

    30

    25

    20

    15

    10

    5

    -5 5 15 25

    Outdoor unit air temp. DB

    Note : The chart is the result from the continuous operation under constant air

    temperature conditions. However, excludes the initial pull-down stage.

    COOLING

  • 7/15/2019 Midea 2005 Split Service Manual

    40/358

    234

    6.Wiring diagram

    Indoor unit

    Outdoor unit

  • 7/15/2019 Midea 2005 Split Service Manual

    41/358

  • 7/15/2019 Midea 2005 Split Service Manual

    42/358

    236

    7.Troubleshooting

    7.1 Indoor unit

    Failure phenomenon Operation lamp Timer lamp

    Indoor fan speed has been out of control for over 1 minute X

    Indoor room temp. sensor or evaporator temp. sensor is open circuit

    or short circuit

    on

    EEROM error on

    Over current protection of the compressor occurs 4 times in 1h X

    r Extinguish

    Flash at 5Hz

    7.2 Outdoor unit (on mainboard)

    Failure phenomenon LED1 LED2 LED3 Sensor in outdoor unit

    Condenser high temperature protection RT3B or RT3A

    RT3A sensor is open circuit or short circuit RT3A

    RT4 sensor is open circuit or short circuit RT4

    RT3B sensor is open circuit or short circuit RT3B

    Flash at 2Hz

    Remark :

    Standard by a unit working b unit working a unit and b unit working

    LED1 Blinking at 0.5 Hz On Off On

    LED2 Blinking at 0.5 Hz Off On On

    LED3 Blinking at 0.5 Hz Off Off off

    7.3 Outdoor unit (on LMFPQ1)Standard by a or b unit working RT2 or RT1 sensor is open circuit or short circuit

    LED Blinking at 0.5 Hz On Blinking at5 Hz

  • 7/15/2019 Midea 2005 Split Service Manual

    43/358

    237

    7.4 Failure and Related Causes of Remote Controller

    Before requesting service or maintenance, please check the following itemsChanging function can not be set

    Symptom Checking Item Cause

    Check if Auto mode is displayed When Auto is chosen, indoor fan will

    choose Auto fan speed

    Fan speed can not be

    changedCheck if Dehumidification is

    displayed

    When dehumidification is chosen, indoor unit

    automatically chooses Auto fan speed. Fan

    speed can only be chosen under cooling,

    heating and fan mode.

    Emission signal does not blink

    Symptom Checking item Cause

    When pressing On/Off button,

    remote control signal is not

    emitted.

    Check battery Signal can not be emitted when there is

    no battery

    Temperature display is darkSymptom Checking item Cause

    Temperature display is dark Check if Fan is chosen Under Fan mode, temperature can not be

    set

    Display disappears

    Symptom Checking item Cause

    After a while, On/Off display

    disappears

    Check if set time of the timer is

    already finished

    Because set time is reached, A/C stops

    running

    After a while, Timer On display

    disappears

    Check if set time of the timer is

    already finished

    When set time for A/C running is

    reached, A/C start running automatically

    and related display disappears

    No sound for signal receipt

    Symptom Checking item Cause

    When pressing On/Off button,

    A/C doesnt give out receipt

    sound

    When pressing the button, make

    sure that the emitter of the

    remote control is directed to the

    receiver of the A/C.

    Check if power supply is well

    connected

    Direct the emitter to the receiver correctly

    and press the On/Off button repeatedly

    The A/C is turned off so it can not receive

    signals

    Button on remote control doesnt

    function

    Check the remote display The button is locked

  • 7/15/2019 Midea 2005 Split Service Manual

    44/358

    238

    8 Electronic function

    8.1 Electric Control working environment

    8.1.1 input voltage: 175~253V

    8.1.2 Input power frequency:50Hz

    8.1.3 Ambient temperature: -7

    C~+43

    C8.1.4 Indoor fan normal working amp is less than 1A,

    8.1.5 Outdoor fan. Normal working amp is less than 1.5A

    8.1.6 Four-way valve normal working amp is less than 1A.

    8.1.7 Swing motor: DC12V.

    8.2 Proper symbols and their meanings:

    TA: Indoor ambient temperature

    TE: Indoor evaporator temperature

    TS: Setting temperature through the remote controller

    TE1: Anti-cold wind, from Fan Off to Breeze temperature

    TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperatureTE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature

    TE4: Anti-cold wind, from Breeze to Fan Off temperature

    TE5: Evaporator low temperature protection entering temperature

    TE6: Evaporator low temperature protection restoring temperature

    TE7: Evaporator high temperature protection, compressor off temperature

    TE8: Evaporator high temperature protection, fan off temperature

    TE9: Evaporator high temperature protection, restoring temperature

    T3: Outdoor unit pipe sensor

    T4: Outdoor temperature sensor

    8.3 Systematic functions.

    Remote receiving.

    Testing and forced run.

    Position set for indoor unit wind vane.

    LED displaying and alarm.

    On or off Timer.

    Protection for the compressor.

    High temperature protection of indoor heat exchanger under heating mode.

    Auto defrosting and heating recovery under heating mode.Anti cold air under heating mode.

    Anti frozen under cooling mode.

  • 7/15/2019 Midea 2005 Split Service Manual

    45/358

    239

    8.4 Protection

    8.4.1 The compressor functions protection with a delay of three minutes.

    8.4.2 High temp. protection of condenser.

    8.4.3 Sensor protection at open circuit and breaking disconnection

    8.4.4 Temperature Fuse break protection8.4.5 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High

    Fan+300RPM)or too low(lower than 400RPM), the entire unit stops and LED displays

    failure information and cant returns to normal operation automatically.

    8.5 Fan-only mode

    Fan speed is high/mid/low/ Auto

    8.6 Cooling mode

    The 4-way valve is closed under cooling mode.

    The action of the compressor and the outdoor fan:

    Condition Compressor Outdoor fan

    TA>Ts+1 On OnTemp. up

    TATs On OnTemp. down

    TA

  • 7/15/2019 Midea 2005 Split Service Manual

    46/358

    240

    8.7.4 Under dehumidifying mode, the anti-freezing function of the indoor heat exchanger is

    the same as that of cooling mode.

    8.8 Heating mode

    8.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode.

    4-way valve must delay 2 minutes compared with compressor if the compressor

    changed into non-heating mode or turned off. 4-way valve doesn't delay indehumidifying mode.

    8.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating

    mode, except for the defrosting mode or the end of defrost.

    8.8.3 Action conditions of compressor under heating mode: compressor must run for 7

    minutes after starting and then judge temperature. Meanwhile other protections are still

    valid.

    Condition Compressor Outdoor fan

    TA> Ts+3 Off OffRoom temp. up

    TA

  • 7/15/2019 Midea 2005 Split Service Manual

    47/358

    241

    8.9 Defrosting operation (Available for heating only).

    8.9.1 Defrosting condition:

    When T320.

    8.9.3 Time sequence of the whole defrosting procedure is as follows

    8.10 Automatic operation mode

    8.10.1 The air conditioner automatically selects one of the following operation modes: cooling,

    heating or ventilation according to the difference between room temp. (TA) and settemp. (TS).

    TATS Operation mode

    TATS>2 Cooling

    -1 TA TS+2 Fan-only

    TATS

  • 7/15/2019 Midea 2005 Split Service Manual

    48/358

    242

    8.13 Timer Function Requirement

    The maximum length of timer is 24 hours and the minimum resolving power is 15

    minutes.

    8.14 Economic Running

    8.14.1 The economic running function is available under cooling, heating or auto mode.

    8.14.2 Cooling:The set temperature rise 1 per hour. Two hours later, the set temperature will

    maintain as a constant and the air circulation is kept at low speed.

    8.14.3 Heating:

    The set temperature decrease 1 per hour. Two hours later, the set temperature will

    maintain as a constant and the air circulation is kept at low speed (Cold air proof

    function takes precedence over all).

    8.14.4 Auto:

    The economic running function operates in accordance with the selected running mode

    by the auto mode.

    8.15 Outdoor fan motor

    Fan Speed is only one SPEED.

  • 7/15/2019 Midea 2005 Split Service Manual

    49/358

    243

    8.16 Models and Parameters(Indoor unit)

    Model MS3G-30HRN2

    HSPEEDH 1100

    HSPEEDM 1050

    HSPEEDL 1000

    HSPEEDS 800

    CSPEEDH 1100

    CSPEEDM 1020

    CSPEEDL 950

    CSPEEDS 800

    TE1 28

    TE2 32

    TE3 30

    TE4 26

    TE5 2

    TE6 7

    TE7 60

    TE8 53

    TE9 50

  • 7/15/2019 Midea 2005 Split Service Manual

    50/358

    Multi SERIES

    1. Features 215

    2. Specification 216

    3. Dimensions 217

    4. Refrigeration cycle diagram 218

    5. Operation limits 219

    6. Wiring diagram 220

    7. Troubleshooting 221

    8. Electronic function 222

    214

  • 7/15/2019 Midea 2005 Split Service Manual

    51/358

    1.Features

    1.1 Compact design

    1.2 High efficiency and quiet operation

    215

  • 7/15/2019 Midea 2005 Split Service Manual

    52/358

    2.Specification

    Model MS2G-18HRN2 MS2G-21HRN2

    Power supply Ph-V-Hz 220-240V~,1PH, 50Hz 220-240V~,1PH, 50Hz

    Capacity Btu/h 9000*2 9000+12000

    Input W 1000*2 1000+1400

    Rated current A 4.5*2 5+6

    Cooling

    EER Btu/w.h 2.4 2.4

    Capacity Btu/h 10000*2 10000+13000

    Input W 1000*2 1000+1400

    Rated current A 4.5*2 5+6Heating

    COP W/W 2.5 2.5

    Moisture Removal L/h

    Max. input consumption W 1430X2 1500+1900

    Max. current A 6.5*2 7.0+8.0

    Starting current A 19.8 33

    Model PG180X1C-4DZ3 PG225X2C-4FT

    Type Rotary Rotary

    Brand GD TOSHIBA GD TOSHIBA

    Capacity Btu/h 10800X2 10800+13600

    Input W 1000X2 1000+1290

    Rated current(RLA) A 4.4X2 4.4+5.74

    Locked rotor Amp(LRA) A 19.8 33

    Thermal protector INNER INNER

    Capacitor uF 30 35

    Compressor

    Refrigerant oil ml 400 480

    Model RPG13H RPG13H

    Brand WeiLing WeiLing

    Input W 36 36

    Capacitor uF 1.2 1.2

    Indoor fan motor

    Speed(hi/mi/lo) r/min 1330 1330

    Indoor air flow (Hi/Mi/Lo) m3/h 470/440/410 470/440/410

    Indoor noise level (Hi/Mi/Lo) dB(A) 38/34/31 38/34/31

    Dimension (W*H*D) mm 750250188 750250188

    Packing (W*H*D) mm 830X336X280 830X336X280Indoor unit

    Net/Gross weight Kg 8.5/10 8.5/10

    Model YDK94-6A YDK170-4C

    Input W 154 290

    Capacitor uF 4 5Outdoor fan motor

    Speed r/min 900/670 1110/810

    Outdoor air flow m3/h 1900 2070

    Outdoor noise level dB(A) 58 58Dimension(W*H*D) mm 895X655X345 895X655X345

    Packing (W*H*D) mm 1050X720X470 1050X720X470Outdoor unit

    Net/Gross weight Kg 58/63 60/65

    Refrigerant type g R407C/800X2 R407C/750+1000

    Design pressure MPa 1.2/2.8 1.2/2.8

    Liquid side/ Gas side mm(inch) 6.35(1/4")-9.53(3/8") 6.35(1/4")-9.53(3/8")/12.7(1/2")

    Max. refrigerant pipe m 15 15Refrigerant piping

    Max. difference in level m 5 5

    Thermostat type Electronic control Electronic control

    Operation temp 17-30 17-30

    Ambient temp -7-45 -7-45

    Application area m2 (14-21)X2 14-21,18-26

    Qtyper 20 /40 /40'HQ set 54/116/132 54/116/132

    216

  • 7/15/2019 Midea 2005 Split Service Manual

    53/358

    3.Dimensions

    3.1 Indoor unit

    3.2 Outdoor unit

    217

  • 7/15/2019 Midea 2005 Split Service Manual

    54/358

    4.Refrigeration cycle diagram

    218

  • 7/15/2019 Midea 2005 Split Service Manual

    55/358

    5.Operation limits

    5.1Cooling operation

    Outdoor unit air temp. DB

    45

    40

    35

    30

    25

    20

    0 25 50

    Indoor air temp. DB

    Note : The chart is the result from the continuous operation under constant air temperature

    conditions. However, excludes the initial pull-down stage.

    5.2Heating operation

    Indoor air temp. DB

    30

    25

    20

    15

    10

    5

    COOLING

    -5 5 15 25

    Outdoor unit air temp. DB

    Note : The chart is the result from the continuous operation under constant airtemperature conditions. However, excludes the initial pull-down stage.

    219

  • 7/15/2019 Midea 2005 Split Service Manual

    56/358

    6.Wiring diagram

    Indoor unit

    Outdoor unit

    5

    1

    3A 3

    7-9

    7-9

    A

    A 1

    .

    3--4

    A 1

    A

    1 2

    FROM INDOOR

    UNIT(A)

    Y&G

    RT3 RT3A

    8

    9

    8

    9

    (WHITE)

    (BLACK)

    RT4

    7

    7

    (RED)

    WIRING

    DIAGRAM

    COM A

    . B

    AC POWER

    T3

    COMPREOR

    FAN MOTOR

    OUTDOOR FAN

    CAPACITOR

    4-WAY VALVE

    OUTDOOR COMPREOR

    CAPACITOR

    MIDDLE TERMINAL

    6-WAY TERMINAL

    A&B SYSTEM PIPE

    TEMPERATURE SENSOR

    CONNECTORS

    TRANSFORMER

    CONNECTORS

    T2 4-WAY TERMINAL

    RT4A&B SYSTEM ROOM

    TEMPERATURE SENSOR

    PARTCODE

    S.V A

    FROM INDOOR

    UNIT(B)

    COMP

    VALVE

    FANN

    220V 50Hz

    6

    OUTDOOR UNIT

    P1

    P2

    P3

    P4P5

    P6

    P7

    P8 P9 P10 P11 P12 P13 P 14

    CN2 CN3

    BCOMP

    ACOMP

    CN7

    CN8

    RED

    BLACK

    RED RED

    RED BLUE

    BLACK

    RED

    CAP2

    CAP3

    CAP2 CAP3

    T4

    T5

    1 2

    SW1

    A COMP BCOMP RELAY

    BLACKYELLOW

    C

    S R

    RED

    BLACK

    BLUE

    C

    S R

    RED

    BLACK

    BLUE

    Y&G Y&G

    Y&G

    BLACK

    BLACKBLACK

    BLACK

    BLACK

    BLUE

    WHITE

    RED

    BLACK

    BLUE

    WHITE

    COMP

    VALVE

    FANN Y&G Y&G

    1 2

    ON

    1LEAVEING

    FACTORY

    EXPLANATION

    1

    ON

    2RAPIDLY

    CHECK

    2

    ON

    3CHECK

    ITSELF

    N I N WI W

    BLUEBLUE

    RLUERLUE

    P11

    P10

    P9 CONNECT TO FAN(HIGH SPEED)

    CONNECT TO 4 WAY VALVE

    P14

    P13

    P12 CONNECT TO 4 WAY VALVE

    CONNECT TO FAN(HIGH SPEED)

    220

  • 7/15/2019 Midea 2005 Split Service Manual

    57/358

    7.Troubleshooting

    7.1 Indoor unit

    Failure phenomenon Operation lamp Timer lamp

    Indoor fan speed has been out of control for over 1 minute X

    Indoor room temp. sensor or evaporator temp. sensor is open circuit

    or short circuit on

    EEPROM error on

    Over current protection of the compressor occurs 4 times in 1h X

    r Extinguish

    Flash at 5Hz

    7.2 Outdoor unit

    Failure phenomenon LED1 LED2 LED3

    Stand by

    High temp. protect of condenser

    Temp. sensor in condenser 1 is open circuit or short circuit

    Temp. sensor in condenser 2 is open circuit or short circuit

    Flash at 2Hz

    221

  • 7/15/2019 Midea 2005 Split Service Manual

    58/358

    8 Electronic function

    8.1 Electric Control working environment

    8.1.1 input voltage: 175~253V

    8.1.2 Input power frequency:50Hz8.1.3 Ambient temperature: -7C~+43C

    8.1.4 Indoor fan normal working amp is less than 1A,

    8.1.5 Outdoor fan. Normal working amp is less than 1.5A

    8.1.6 Four-way valve normal working amp is less than 1A.

    8.1.7 Swing motor: DC12V.

    8.2 Proper symbols and their meanings:

    TA: Indoor ambient temperature

    TE: Indoor evaporator temperature

    TS: Setting temperature through the remote controller

    TE1: Anti-cold wind, from Fan Off to Breeze temperatureTE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature

    TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature

    TE4: Anti-cold wind, from Breeze to Fan Off temperature

    TE5: Evaporator low temperature protection entering temperature

    TE6: Evaporator low temperature protection restoring temperature

    TE7: Evaporator high temperature protection, compressor off temperature

    TE8: Evaporator high temperature protection, fan off temperature

    TE9: Evaporator high temperature protection, restoring temperature

    T3: Outdoor unit pipe sensor

    T4: Outdoor temperature sensor

    8.3 Systematic functions.

    Remote receiving.

    Testing and forced run.

    Position set for indoor unit wind vane.

    LED displaying and alarm.

    On or off Timer.

    Protection for the compressor.

    High temperature protection of indoor heat exchanger under heating mode.Auto defrosting and heating recovery under heating mode.

    Anti cold air under heating mode.

    Anti frozen under cooling mode.

    222

  • 7/15/2019 Midea 2005 Split Service Manual

    59/358

    8.4 Protection

    8.4.1 The compressor functions protection with a delay of three minutes.

    8.4.2 High temp. protection of condenser.

    8.4.3 Sensor protection at open circuit and breaking disconnection8.4.4 Temperature Fuse break protection

    8.4.5 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High

    Fan+300RPM)or too low(lower than 400RPM), the entire unit stops and LED displays

    failure information and cant returns to normal operation automatically.

    8.5 Fan-only mode

    Fan speed is high/mid/low/ Auto

    8.6 Cooling mode

    The 4-way valve is closed under cooling mode.

    The action of the compressor and the outdoor fan:

    Condition Compressor Outdoor fan

    TA> Ts+1 On OnTemp. up

    TA Ts On OnTemp. down

    TA65, turn off compressor.

    8.7 Dehumidifying mode

    8.7.1 The 4-way valve is off in dehumidifying mode

    8.7.2 Compressor and Indoor Fan actions in dehumidifying mode

    Compressor run 5 minutes , and indoor fan run 5 minutes in low speed, then turn off the

    compressor, indoor fan run 5 minutes in low speed. And repeat on and off cycle.8.7.3 Low room temperature protection:

    When room temperature decreases to below 10, the compressor and the outdoor fan

    223

  • 7/15/2019 Midea 2005 Split Service Manual

    60/358

    will stop(indoor fan is Breeze). Dehumidifying operation will be resumed when room

    temperature restores to over 13.

    8.7.4 Under dehumidifying mode, the anti-freezing function of the indoor heat exchanger is

    the same as that of cooling mode.

    8.8 Heating mode8.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode.

    4-way valve must delay 2 minutes compared with compressor if the compressor

    changed into non-heating mode or turned off. 4-way valve doesn't delay in

    dehumidifying mode.

    8.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating

    mode, except for the defrosting mode or the end of defrost.

    8.8.3 Action conditions of compressor under heating mode: compressor must run for 7

    minutes after starting and then judge temperature. Meanwhile other protections are still

    valid.

    Condition Compressor Outdoor fan

    TA> Ts+3 Off OffRoom temp. up

    TATs+2 Off Off

    8.8.4 Indoor Fan actions under heating mode

    Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but

    Anti-cold wind function prevails.

    Anti-cold wind control function under heating modeCondition

    TE

    Indoor fan speed

    TE

  • 7/15/2019 Midea 2005 Split Service Manual

    61/358

    8.8.6 Indoor evaporator high-temperature protection under heating mode

    Condition Compressor Outdoor fan

    TE

  • 7/15/2019 Midea 2005 Split Service Manual

    62/358

    8.11 Forced cooling function

    8.11.1 Select forced cooling function with the forced cooling button or the switch.

    8.11.2 The compressor is unconditionally turned on, after 30 minutes cooling operation whose

    fan mode is set as low, the A/C operates under the DRY mode with a set temp. of 24

    .8.11.3 All protections of remote control cooling are available under forced cooling operation.

    8.12 Forced Auto function

    Select forced auto function with the forced auto button or the switch.

    In forced auto status the A/C operates under remote control mode with a set temp. of

    24.

    8.13 Timer Function Requirement

    The maximum length of timer is 24 hours and the minimum resolving power is 15

    minutes.

    8.14 Economic Running

    8.14.1 The economic running function is available under cooling, heating or auto mode.8.14.2 Cooling:

    The set temperature rise 1 per hour. Two hours later, the set temperature will

    maintain as a constant and the air circulation is kept at low speed.

    8.14.3 Heating:

    The set temperature decrease 1 per hour. Two hours later, the set temperature will

    maintain as a constant and the air circulation is kept at low speed (Cold air proof

    function takes precedence over all).

    8.14.4 Auto:

    The economic running function operates in accordance with the selected running mode

    by the auto mode.

    8.15 Outdoor fan motor

    T4: Outdoor temp.

    T4 Outdoor fan motor

    T4>27 High speedCooling mode

    T413 Low speedHeating mode

    T4

  • 7/15/2019 Midea 2005 Split Service Manual

    63/358

    227

    8.16 Models and Parameters(Indoor unit)

    Model MS2G-18CR MS2G-18HR

    HSPEEDH 1100

    HSPEEDM 1050

    HSPEEDL 1000

    HSPEEDS 800

    CSPEEDH 1100 1100

    CSPEEDM 1020 1020

    CSPEEDL 950 950

    CSPEEDS 800 800

    TE1 28

    TE2 32

    TE3 30

    TE4 26

    TE5 4 4

    TE6 7 7

    TE7 60

    TE8 53

    TE9 50

  • 7/15/2019 Midea 2005 Split Service Manual

    64/358

    197

    MULTI INVERTER ECO

    1. Product features 198

    2. Specification 199

    3. Dimensions 203

    4. Refrigeration cycle diagram 204

    5. Operation limits 205

    6. Capacity table 206

    7. Wiring diagram 208

    8. Electric control functions 210

  • 7/15/2019 Midea 2005 Split Service Manual

    65/358

    198

    1. Product Features

    Both indoor units can be operated either simultaneously or separately through the utilization of the advanced

    converter technique and microcomputer control.

    The flowing volume of refrigerant is adjustable through the electronic expansion valve.

    High Cooling and Heating capacity is facilitated through the famous-brand frequency converter compressor.

    Indoor noise is minimized through the optimization of the air flow system design, a four-folded evaporator and a

    big diameter Cross Flow Fan.

    The system is operable under low-voltage.

    Effective and prompt defrosting correlates into no cold feelings.

    High heating effects under extremely low temperatures.

    The systems purging function improves the quality of the air in the room.

    Wireless remote controlled function:

    ---A Manual Switch can operate the air conditioner when the remote controller is misplaced and the batteries are

    exhausted.

    ---Horizontal and vertical louvers can swing automatically and the customized setting flows the air as desired.

    ---Grounding's have been connected and are safe to use.

    ---Compressor protection function enabled.

    Indoor unit:

    1) 4-Bend heat exchanger.

    2) Trapeziform innergroove copper.

    3) Hydrophilic Aluminum Fin.

    4) Two-direction air vane technology.

    5) Sleep mode.

    6) Anti-rust cabinet.

    7) Easy-cleaned panel.

    8) Self-diagnosis auto-protection function.

  • 7/15/2019 Midea 2005 Split Service Manual

    66/358

    199

    2. Specification

    Model M2OA-18HRIN2

    Indoor unit 7000Btu/h 9000Btu/h 12000Btu/h

    Power supply Ph-V-Hz 1Ph, 220-240V~, 50HzCapacity Btu/h single: 7000-12000; Twin:16000-24000

    Input W single: 1000W-1350W; Twin:2570W-2900W

    Rated current A single: 4.8A-6.7A; Twin:11.7A-13.8ACooling

    EER Btu/w.h single: 7.0-8.9; Twin:6.2-8.3

    Capacity Btu/h single: 10000-14000; Twin:24000-27000

    Input W single: 1300W-1650W; Twin:2100W-2800W

    Rated current A single: 6.3A-8.0A; Twin:11.0A-13.5AHeating

    COP Btu/w.h single: 7.7-8.5; Twin:11.4-9.6

    Moisture Removal L/h 0.7 0.9 1.2

    Max. input consumption W single: 1800W; Twin:3200W

    Max. current A single: 13A; Twin:20A

    Starting current A 10

    Model BG240X2CS-20KU

    Type Rotary inverter

    Brand GD Toshiba

    Capacity Btu/h 18000

    Input W 1690

    Rated current(RLA) A 11.6

    Locked rotor Amp(LRA) A 60

    Thermal protector Internal

    Capacitor uF 85UF/250V

    Compress

    or

    Refrigerant oil ml RB68AF/68TF/T-68 750 ml

    Model RPG13H RPG13H RPG13C

    Brand Welling Welling Matsushita

    Input W 36 36 50

    Capacitor uF 1.2uF/

    450VAC 1.2uF/

    450VAC 1.5uF/

    450VAC

    Indoor

    fan motor

    Speed(hi/mi/lo) r/min 1050/950/750 1100/1000/800 1060/900/800

    Number of rows 2 2 2

    Tube pitch(a)x row pitch(b) mm 2113.37 2113.37 2113.37

    Fin spacing mm 1.5 1.5 1.3

    Fin type (code)Hydrophilic

    aluminium

    Hydrophilic

    aluminium

    Hydrophilic

    aluminium

    Tube outside dia.and type mm7, innergroove

    tube

    7, innergroove

    tube

    7, innergroove

    tube

    Coil length x height x width mm 57825227.34 57825227.34 63531527.34

    Indoor

    coil

    Number of circuits 2 2 2

  • 7/15/2019 Midea 2005 Split Service Manual

    67/358

    200

    Indoor air flow (Hi/Mi/Lo) m3/h 500/410/320 520/430/330 560/460/380

    Indoor noise level (Hi/Mi/Lo) dB(A) 35/32/26 36/32/26 36/32/26

    Dimension (W*H*D) mm 750*250*188 750*250*188 815*280*195

    Packing (W*H*D) mm 830*336*280 830*336*280 915*360*275Indoor

    unitNet/Gross weight kg 8.5/11 8.5/11 11/14

    Model YDK53-6M

    Brand Welling

    Input W 148

    Capacitor uF 3.0

    Outdoor

    fan motor

    Speed r/min 775

    Number of rows 1.5

    Tube pitch(a)x row pitch(b) mm 25.422

    Fin spacing mm 1.7

    Fin type (code) Hydrophilic aluminium

    Tube outside dia.and type mm 9.53 innergroove trube

    Coil length x height x width mm 77666022

    Outdoorcoil

    Number of circuits 2

    Outdoor air flow m3/h 2500

    Outdoor noise level dB(A) 60

    Dimension(W*H*D) mm 845X695X335

    Packing (W*H*D) mm 975X772X405Outdoor

    unitNet/Gross weight kg 71/74

    Refrigerant type R407C g 2200

    Design pressure(Hi/Lo) MPa 2.8/1.2

    Liquid side/ Gas side mm 6.35/9.53 6.35/9.53 6.35/12.7

    Max. refrigerant pipe length m 10 10 10Refrigera

    nt pipingMax. difference in level m 5 5 5

    Connection wiring No

    Plug type No

    Controller Remote

    Operation temp 17~30Ambient temp 18~43(cooling); -15~24(heating)

    Application area m2 14-18 18-24 20-30

    Notes: 1. Nominal cooling capacities are based on the following conditions:

    Indoor temp: 27CDB, 19CWB; Outdoor temp: 35CDB; Equivalent ref. Piping: 8m(horizontal)

    2. Nominal heating capacities are based on the following conditions:

    Indoor temp: 20CDB; Outdoor temp: 7CDB, 6CWB; Equivalent ref. Piping: 8m(horizontal)

    3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an

    anechoic room.

  • 7/15/2019 Midea 2005 Split Service Manual

    68/358

    201

    Model M3OA-27HRIN2

    Indoor unit 7000Btu/h 9000Btu/h 12000Btu/h

    Power supply Ph-V-Hz 1Ph, 220-240V~, 50Hz

    Capacity Btu/h single: 7000-12000; Twin:16000-24000; Three:24000

    Input W single: 1000W-1350W; Twin:2570W-2900W; Three:2900W

    Rated current A single: 4.8A-6.7A; Twin:11.1A-13.8A; Three: 13.8ACooling

    EER Btu/w.h single: 7.0-8.9; Twin: 6.2-8.3; Three: 8.3

    Capacity Btu/h single: 10000-14000; Twin: 24000-27000; Three: 27000

    Input W single: 1300W-1650W; Twin: 2100W-2800W; Three: 2800W

    Rated current A single: 6.3A-8.0A; Twin: 11.0A-13.5A; Three: 13.5AHeating

    COP Btu/w.h single: 7.7-8.5; Twin: 11.4-9.6; Three: 9.6

    Moisture Removal L/h 0.7 0.9 1.2

    Max. input consumption W 3200

    Max. current A 20

    Starting current A 10

    Model BG240X2CS-20KU

    Type Rotary inverter

    Brand GD Toshiba

    Capacity Btu/h 18000

    Input W 1690

    Rated current(RLA) A 11.6

    Locked rotor Amp(LRA) A 60

    Thermal protector Internal

    Capacitor uF 85UF/250V

    Compress

    or

    Refrigerant oil ml RB68AF/68TF/T-68 750 ml

    Model RPG13H RPG13H RPG13CBrand Welling Welling Matsushita

    Input W 36 36 50

    Capacitor uF 1.2uF/450VAC 1.2uF/450VAC 1.5uF/450VAC

    Indoor

    fan motor

    Speed(hi/mi/lo) r/min 1050/950/750 1100/1000/800 1060/900/800

    Number of rows 2 2 2

    Tube pitch(a)x row pitch(b) mm 2113.37 2113.37 2113.37

    Fin spacing mm 1.5 1.5 1.3

    Fin type (code)Hydrophilic

    aluminium

    Hydrophilic

    aluminium

    Hydr0philiC

    aluminium

    Indoor

    coil

    Tube outside dia.and type mm 7, innergroove tube 7, innergroove tube7, innergroove tube

  • 7/15/2019 Midea 2005 Split Service Manual

    69/358

    202

    Coil length x height x width mm 57825227.34 57825227.34 63531527.34

    Number of circuits 2 2 2

    Indoor air flow (Hi/Mi/Lo) m3/h 500/410/320 520/430/330 560/460/380

    Indoor noise level (Hi/Mi/Lo) dB(A) 35/32/26 36/32/26 36/32/26

    Dimension (W*H*D) mm 750*250*188 750*250*188 815*280*195Packing (W*H*D) mm 830*336*280 830*336*280 915*360*275

    Indoor

    unitNet/Gross weight Kg 8.5/11 8.5/11 11/14

    Model YDK53-6M

    Brand Welling

    Input W 148

    Capacitor uF 3.0

    Outdoor

    fan motor

    Speed r/min 775

    Number of rows 1.5

    Tube pitch(a)x row pitch(b) mm 25.422

    Fin spacing mm 1.7

    Fin type (code) Hydrophilic aluminium

    Tube outside dia.and type mm 9.53 innergroove trube

    Coil length x height x width mm 77666022

    Outdoor

    coil

    Number of circuits 2

    Outdoor air flow m3/h 2500

    Outdoor noise level dB(A) 60

    Dimension(W*H*D) mm 845X695X335

    Packing (W*H*D) mm 975X772X405Outdoor

    unitNet/Gross weight Kg 72/76

    Refrigerant type R407C g 2400

    Design pressure(Hi/Lo) MPa 2.8/1.2

    Liquid side/ Gas side mm 6.35/9.53 6.35/9.53 6.35/12.7

    Max. refrigerant pipe length m 10 10 10Refrigera

    nt pipingMax. difference in level m 5 5 5

    Connection wiring No

    Plug type NoController Remote

    Operation temp 17~30

    Ambient temp 18~43(cooling); -15~24(heating)

    Application area m2 14-18 18-24 20-30

    Notes: 1. Nominal cooling capacities are based on the following conditions:

    Indoor temp: 27CDB, 19CWB; Outdoor temp: 35CDB; Equivalent ref. Piping: 8m(horizontal)

    2. Nominal heating capacities are based on the following conditions:

    Indoor temp: 20CDB; Outdoor temp: 7CDB, 6CWB; Equivalent ref. Piping: 8m(horizontal)

    3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from ananechoic room.

  • 7/15/2019 Midea 2005 Split Service Manual

    70/358

    203

    3 Dimensions

    1. Indoor unit 7/9K

    2. Indoor Unit 12K

    3. Outdoor unit

  • 7/15/2019 Midea 2005 Split Service Manual

    71/358

    204

    4 Refrigeration Cycle Diagram

    Refrigeration circuit drawing of inverter trinary type

    2

    heat

    exchanger

    filter

    heat

    exchanger

    filter

    filter

    indoor unit

    heat

    exchanger

    filter

    high-pressureswitch 1

    4-wayvalve

    down part

    condenser

    3

    capillary

    capillary

    filter

    up part

    oil separator

    low-pressureswitch 2

    low-pressure oil tank

    capillary

    dischargesensor

    outdoor unit

    inverter compressor

    Refrigeration circuit drawing of inverter binary type

    2

    heat

    exchanger

    filter

    heatexchanger

    filter

    high-pressure

    switch 1

    4-wayvalve

    condenser

    down part

    3

    capillary

    capillary

    filter

    up part

    oil separator

    low-pressureswitch 2

    low-pressure oil tank

    capillary

    dischargesensor

    outdoor unit

    inverter compressor

  • 7/15/2019 Midea 2005 Split Service Manual

    72/358

    205

    5 Operation Limits

    5.1 Cooling operation

    Outdoor unit air temp.

    60

    50

    40

    30

    20

    10

    10 17 25 30 35 40

    Indoor air temp.

    Note :the chart is the result from the continuous operation under constant air temperature

    conditions. however, excludes the initial pull-down stage.

    5.2 Heating operation

    Indoor air temp.

    30

    20

    10

    5

    -5

    -15

    -15 -5 5 15 25 30

    Outdoor unit air temp.

    Note :the chart is the result from the continuous operation under constant air

    temperature conditions. however, excludes the initial pull-down stage.

  • 7/15/2019 Midea 2005 Split Service Manual

    73/358

    206

    6 Capacity Table

    6.1 Capacity table of Inverter Binary Eco type

    Indoor units can be combined by

    7000Btu/h+9000 Btu/h

    7000Btu/h+12000 Btu/h

    9000Btu/h+9000 Btu/h

    9000Btu/h+12000 Btu/h

    12000Btu/h+12000 Btu/h

    Cooling

    Indoor unit a (W) Indoor unit b (W)

    7000Btu/h 2800

    9000Btu/h 3000

    12000Btu/h 34007000Btu/h+7000 Btu/h 2300 2300

    7000Btu/h+9000 Btu/h 2500 2500

    7000Btu/h+12000 Btu/h 2200 2800

    9000Btu/h+9000 Btu/h 2500 2500

    9000Btu/h+12000 Btu/h 2400 3200

    12000Btu/h+12000 Btu/h 3200 3200

    Heating

    Indoor unit a (W) Indoor unit b (W)

    7000Btu/h 34009000Btu/h 3600

    12000Btu/h 4000

    7000Btu/h+7000 Btu/h 2800 2800

    7000Btu/h+9000 Btu/h 3000 3000

    7000Btu/h+12000 Btu/h 2600 3400

    9000Btu/h+9000 Btu/h 3000 3000

    9000Btu/h+12000 Btu/h 3000 3900

    12000Btu/h+12000 Btu/h 3900 3900

    6.2 Capacity table of Inverter Trinary Eco type

    Indoor units can be combined by

    7000Btu/h*2+9000 Btu/h

    7000Btu/h*2+12000 Btu/h

    7000Btu/h*3

    9000Btu/h*2+7000 Btu/h

    9000Btu/h*2+12000 Btu/h

    9000Btu/h*3

    12000Btu/h*2+7000 Btu/h

    12000Btu/h*2+9000 Btu/h

    7000Btu/h+9000Btu/h+12000 Btu/h

  • 7/15/2019 Midea 2005 Split Service Manual

    74/358

    207

    Cooling

    Indoor unit a (W) Indoor unit b (W) Indoor unit c (W)

    7000Btu/h 2800

    9000Btu/h 3000

    12000Btu/h 3400

    7000Btu/h+7000 Btu/h 2300 2300

    7000Btu/h+9000 Btu/h 2500 2500

    7000Btu/h+12000 Btu/h 2200 2800

    9000Btu/h+9000 Btu/h 2500 2500

    9000Btu/h+12000 Btu/h 2400 3200

    12000Btu/h+12000 Btu/h 3200 3200

    7000Btu/h*2+9000 Btu/h 2200 2200 2200

    7000Btu/h*2+12000 Btu/h 2000 2000 2600

    7000Btu/h*3 2200 2200 22009000Btu/h*2+7000 Btu/h 2200 2200 2200

    9000Btu/h*2+12000 Btu/h 2100 2100 2600

    9000Btu/h*3 2200 2200 2200

    12000Btu/h*2+7000 Btu/h 2000 2400 2400

    12000Btu/h*2+9000 Btu/h 2000 2400 2400

    Heating

    Indoor unit a (W) Indoor unit b (W) Indoor unit c (W)

    7000Btu/h 3400

    9000Btu/h 360012000Btu/h 4000

    7000Btu/h+7000 Btu/h 2800 2800

    7000Btu/h+9000 Btu/h 3000 3000

    7000Btu/h+12000 Btu/h 2600 3400

    9000Btu/h+9000 Btu/h 3000 3000

    9000Btu/h+12000 Btu/h 3000 3900

    12000Btu/h+12000 Btu/h 3900 3900

    7000Btu/h*2+9000 Btu/h 2600 2600 2600

    7000Btu/h*2+12000 Btu/h 2300 2300 32007000Btu/h*3 2400 2400 2400

    9000Btu/h*2+7000 Btu/h 2700 2700 2700

    9000Btu/h*2+12000 Btu/h 2500 2500 3200

    9000Btu/h*3 2700 2700 2700

    12000Btu/h*2+7000 Btu/h 2400 3200 3200

    12000Btu/h*2+9000 Btu/h 2400 3200 3200

  • 7/15/2019 Midea 2005 Split Service Manual

    75/358

    208

    7. Wiring Diagram7.1 Indoor unit 7/9K

    7.2 Indoor unit 12K

  • 7/15/2019 Midea 2005 Split Service Manual

    76/358

    209

    7.3 Outdoor unit M2OA-18HRIN2

    Outdoor unit M3OA-27HRIN2

  • 7/15/2019 Midea 2005 Split Service Manual

    77/358

    210

    8. Electric Control Functions8.1 Control system

    The control system adopts modular design, that is, all indoor units communicate with outdoor units, ref. to the

    following figures for the control structure between indoor units and outdoor units. In the structure, the indoor control

    board receives the information from users (for exam. set temp., fan speed etc.) and environment (ex, indoor coiltemp., indoor temp. etc.) ,and organize it to control the action of relevant parts, then transmits the signals to outdoor

    control board through the following communication circuit. Outdoor control board can deal with the information

    from indoor unit and figure out the best running mode, then transfer the instruction to indoor units to carry out it.

    Indoor unit receive the users remote control signals.

    Indoor unit Outdoor unit

    T2B

    T1T2Ts T3 T4T3

    Fan Speed Pressure switch

    Pressure switch

    4-way valve

    Fan Fan motor

    Co Compressor

    Swing motor EXV

    1 T1 Indoor ambient temp.

    2 T2 Indoor evaporator middle part temp3 T2B Indoor evaporator outlet temp.

    4 Ts Indoor setting temp.

    5 T3 Outdoor heat-exchanger outlet temp.

    6 T4 Outdoor ambient temp.

    8.2 Protection function

    8.2.1 AC Volt Protection

    a. Over-voltage protection

    When AC voltage 260V for 30 seconds, Outdoor Unit resumes operation.

    When AC voltage 270V for 30 seconds, Outdoor Unit stops operation and alarms.

    Note: Voltage sampling precision is 3%.

    b. Lack-voltage protection

    ote control

  • 7/15/2019 Midea 2005 Split Service Manual

    78/358

    211

    Volt increase (Resume)

    198

    190 MAX=78Hz 190

    180

    172 MAX=70Hz 172

    167

    Stop

    Volt decrease (Limited Frequency)

    8.2.2 AC Amp Protection

    The outdoor control board checks the compressor current and do over-current protection.

    If the compressor current is over the scheduled value, the system will stop and all indoor units will display

    malfunction code.

    Note: 1. In order to prevent protection due to too big LRA when compressor starts, the outdoor control board begins

    to check the compressor current after 10 seconds.

    2. If current protection happens, the compressor will stop and restart 3 minutes later.

    8.2.3 High-pressure Protection and Low-pressure Protection

    The High-pressure switch and Low-pressure switch are installed at suction pipe and discharge pipe separately. And

    users can select to install. Normally, the high-pressure switch is cut down when higher than 425Psi (3.3Mpa Cut

    down, 2.4Mpa Resume). While the low-pressure switch is cut down when lower than 7Psi (0.05Mpa

    On, 0.15Mpa Resume).

    Under high-pressure protection or low-pressure protection, the compressor will stop and restart 3

    minutes later.

    8.2.4 Outdoor Unit communication protection

    8.2.4.1 Communication protection between indoor unit and outdoor system chip

    If the outdoor unit cant receive the indoor signal for 30 seconds, then the indoor units are judged as no starting and

    there is no alarm signal. If the indoor units send signal to system chip for 2 minutes and no feedback signal is

    received, then judge as communication malfunction.

    8.2.4.2 Communication protection between outdoor system chip and inverter chip

    If cant receive signal or receive wrong signal for over 2 minutes, Indoor/Outdoor Unit stops operation. When the

    signal is right, Indoor/Outdoor Unit restarts.

    8.2.5 Outdoor condenser high temperature protection

    Under cooling mode, ifT365 for 3 minutes, the compressor will stop. When T352, the protection

    is not valid.

    When protection is released, the compressor restarts 3 minutes later.

    Volt(V)

  • 7/15/2019 Midea 2005 Split Service Manual

    79/358

    212

    8.2.6 Temperature Sensor short/open protection

    When the outdoor condenser pipe temperature T3, outdoor ambient temperature T4, indoor evaporator outlet

    temperature T2B are checked out of range 0.054.95V, it think temperature sensor short/open

    protection. The compressor, four-way valve and outdoor fan motor will stop and send malfunctionsignal to indoor units.

    When the volt is resumed to the range 0.054.95V, then resume signal to indoor units and control

    on-off of the compressor, four-way valve and outdoor fan motor by indoor size.

    8.2.7 Outdoor low temperature protection

    If the outdoor temperature is lower than -15 for 1hour, the compressor and fan motor will stop. And

    any operation is not valid.

    If the outdoor temperature is higher than -12 for 10 minutes and the compressor stops operation

    for 1h, or the outdoor temperature is higher than 5 for 10 minutes, then restart and enter into the

    prior operation mode.If any indoor unit sends out this protection request, the outdoor unit will stop compressor until all

    indoor units have not this protection request.

    8.2.8 Compressor pre-heating function

    When the outdoor temperature is lower than 3 and the compressor stops operation for more than 3

    hours, or the outdoor temperature is lower than 3 and the power is just put on, the compressor

    enters into pre-heating condition.

    8.3 Display function

    8.3.1 Checking function

    The indoor and outdoor operation condition can be examined by check button.

    Normal display Operation mode Capacity request Number of indoor units ambient temp.

    Outdoor pipe temp. Compressor current No.1 PMV opening No.2 PMV opening

    No.3 PMV opening

    8.3.2 Explanation of display function

    1. : Standing-by2. When the compressor is in operation, the compressor operation frequency will be displayed on

    the digital pipe.

    3. : Defrosting

    4. Under standing-by, displaywhen pre-heating and display 11. When pre-heating after

    turning on the AC.

    5. Under malfunction protection:

  • 7/15/2019 Midea 2005 Split Service Manual

    80/358

    213

    Display contents Malfunction or Protection

    0 EEPROM Parameter Malfunction

    No.1 Indoor unit Evaporator outlet temp. sensor malfunction

    No.2 Indoor unit Evaporator outlet temp. sensor malfunction

    No.3 Indoor unit Evaporator outlet temp. sensor malfunction

    Outdoor temp. sensor malfunction

    Compressor volt protection

    Obligate

    7 Outdoor inverter communication malfunction

    0 Top temp. protection

    High-pressure protection

    Low-pressure protection

    Compressor current protection

    Module protection

    Outdoor low-temperature protection

    Condenser high-temperature protection

    7 Obligate

  • 7/15/2019 Midea 2005 Split Service Manual

    81/358

    178

    AC INVERTER SERIES II

    1. Features 179

    2. Specification 180

    3. Dimensions 182

    4. Refrigeration cycle diagram 184

    5. Operation limits 185

    6. Wiring diagram 186

    7. Troubleshooting 189

    8. Electronic function 190

  • 7/15/2019 Midea 2005 Split Service Manual

    82/358

    179

    1.Features

    1.1 Powerful at cooling/heating, 1.3 times and 1.6 times relatively higher than normal same type of

    models.

    1.2 Low voltage start-up function, even at 160 V it can normally start.

    1.3 Anti-icing function at cooling mode.

    1.4 Anti-cold air function at heating mode.

    1.5 Auto-defrosting and heating recovering function at heating mode.

    1.6 Outdoor whole electric current protection

    1.7 Temperature protection of the outdoor compressor top.

    1.8 Restart protection for the compressor.

    1.9 24 hours on/off mode time setting.

    1.10 Error self diagnosis function.

    1.11 Protection against over-load or too-low current inputted through alternating current.

  • 7/15/2019 Midea 2005 Split Service Manual

    83/358

    180

    2. SpecificationModel MSG-09HRI MSG-12HRI

    Power supply Ph-V-Hz 220-240V, 50HZ 220-240V, 50HZ

    Capacity Btu/h 9000(2730-10600) 12000(3070-12300)

    Input W 1080(270-1470) 1260(310-1710)

    Rated current A 6(1.45-7.60) 7.2(1.60-8.80)Cooling

    EER Btu/w.h 8.3 9.52

    Capacity Btu/h 12000(2730-14000) 15000(3070-17060)

    Input W 1350(270-1800) 1790(300-2380)

    Rated current A 7.2(1.45-9.30) 8.4(1.60-12.30)Heating

    COP W/W 2.6 2.5

    Moisture Removal L/h 1 1.2

    Max. input consumption W 2300 2600

    Model 2PV132N7BC02 2PV132N7BC02

    Type Rotary Rotary

    Brand MATSUSHITA MATSUSHITA

    Capacity Btu/h 8900 8900

    Input W 855 855

    Rated current(RLA) A 5.1 5.1

    Locked rotor Amp(LRA) A 16 16

    Thermal protector CS-7LN120 CS-7LN120

    Compressor

    Refrigerant oil ml 350 350

    Model RPG13F RPG20A

    Input W 36.5 35

    Capacitor uF 1.2UF/450VAC 1UF/450VACIndoor fan motor

    Speed(hi/mi/lo) r/min 1100/1000/900 1100/1000/900

    Indoor air flow (Hi/Mi/Lo) m3/h 500 540

    Indoor noise level (Hi/Mi/Lo) dB(A) 36/32/26 38/34/28

    Dimension (W*H*D) mm 750X250X188 875X270X176

    Packing (W*H*D) mm 870X336X280 1000X355X265Indoor unit

    Net/Gross weight Kg 8.5/11 11/14

    Model YDK20-6g YDK25-6-3

    Input W 70 75

    Capacitor uF 2.5 2.5Outdoor fan motor

    Speed r/min 800 900

    Outdoor noise level dB(A) 50 53

    Dimension(W*H*D) mm 780X540X240 780X540X240

    Packing (W*H*D) mm 910X575X335 910X575X335Outdoor unit

    Net/Gross weight Kg 36/39 40/43

    Refrigerant type g 870 1120

    Design pressure MPa 2.6 2.6

    Liquid side/ Vapor side mm(inch) 6.35/9.53 6.35/12.7

    Max. refrigerant pipe length m 10 10Refrigerant piping

    Max. difference in level m 5 5

    Application area m2 18-24 20-30

    1 The noise date is base on hemi-anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient

    condition.

  • 7/15/2019 Midea 2005 Split Service Manual

    84/358

    181

    Model Item MSG-07HRIN2 MSG-09HRIN2 MSG-12HRIN2

    Power source 220-240V~50Hz 220-240V~50Hz 220-240V~50Hz

    Capacity BTU/H 7000(2700~9000) 9000(2730~10600) 12000(3070~12300)

    Input W 820(250~1200) 1080(270~1470) 1400(310~1710)

    Running current A 4.8(1.35~6.2) 6.0(1.45~7.6) 7.5(1.6~8.8)Cooling

    EER BTU/W.H 8.3 8.3 8.6

    Capacity BTU/H 9000(2700~11000) 12000(2730~14000) 14000(3070~17000)

    Input W 1010(250~1300) 1400(270~1800) 1790(300~2380)Heating

    Running current A 5.6(1.35~6.7) 7.2(1.49~9.3) 10.5(1.6~12.3)

    Max. input consumption W 2100 2300 2600

    Model BG130X1C-20FZ BG130X1C-20FZ BG130X1C-20FZ

    Type Rotary Inverter Rotary Inverter Rotary Inverter

    Brand MIDEA TOSHIBA MIDEA TOSHIBA MIDEA TOSHIBA

    Refrigerant oil ml 370 370 370

    Compressor

    Refrigerant oil type R407C R407C R407C

    Refrigerant R407C g 800 800 1150

    Design pressure MPa 2.6 2.6 2.6

    Input W RPG13H 36 RPG13H 36 RPG13C 50

    Capacitor uF 1.2uF/450VAC 1.2uF/450VAC 1.5uF/450VAC

    Speed level 3 3 3

    Hi speed( rpm) 1100 1100 1060

    Mid speed( rpm) 1000 1000 900

    Indoor fan

    motor

    Low speed( rpm) 800 800 800

    High fan m3/h 500 520 560

    Middle fan m3/h 430 430 460Air flow

    (indoor)Low fan m3/h 330 330 380

    Noise level

    (indoor)dB(A) 35/32/26

    36/32/26 36/32/26

    Input W YDK23-6G 63 YDK23-6G 63 YDK23-6G 63Outdoor fan

    motor Capacitor uF 2.5uF/450VAC 2.5uF/450VAC 2.5uF/450VAC

    Noise

    (outdoor)

    High dB(A) 51 51 53

    dimension(W*H*D) 750*250*188 750*250*188 815*280*195

    Packing (W*H*D) 830*336*280 830*336*280 915*360*275Indoor unit

    Net weight kg 8.5 8.5 11

    dimension(W*H*D) 780*520*240 780*520*240 780*520*240

    Packing (W*H*D) 910*575*335 910*575*335 910*575*335Outdoor unit

    Net weight kg 37 37 40

    1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient

    condition.

  • 7/15/2019 Midea 2005 Split Service Manual

    85/358

    182

    3. Dimensions

    3.1 Indoor Unit(MSG-09HRI, MSG-07/09HRIN2)

    3.2 Indoor Unit(MSG-12HR1)

  • 7/15/2019 Midea 2005 Split Service Manual

    86/358

    183

    3.3 Indoor Unit (MSG-12HRIN2)

    3.4 Outdoor Unit

  • 7/15/2019 Midea 2005 Split Service Manual

    87/358

    184

    4. Refrigeration Cycle Diagram

    Indoor unit outdoor unit

    Valve

    Sensor of room temp Heat exchanger

    . 4 way valve

    Sensor

    Heat exchanger Sensor of temp

    Sensor of heat exchanger temp

    . Sensor of heat exchanger temp

    Compressor

    Valve Capillary

  • 7/15/2019 Midea 2005 Split Service Manual

    88/358

    185

    5. Operation Limits

    5.1 Cooling operation

    Outdoor unit air temp.

    60

    50

    40

    30

    20

    10

    10 17 25 30 35 40

    Indoor air temp.

    Note :the chart is the result from the continuous operation under constant air temperature

    conditions. however, excludes the initial pull-down stage.

    5.2 Heating operation

    Indoor air temp.

    30

    20

    10

    5

    -5

    -15

    -15 -5 5 15 25 30

    Outdoor unit air temp.

    Note :the chart is the result from the continuous operation under constant air

    temperature condi