miscellaneous piping types current/csm welcome center/06 mech dwgs.pdf · cv constant volume db...
TRANSCRIPT
F
F/S
S
M
B
A AIR (COMPRESSED)ABV ABOVEA/C AIR CONDITIONINGAC ALTERNATING CURRENT
AIR COMPRESSORACCH AIR COOLED CHILLERACCU AIR COOLED CONDENSING UNITAD ACCESS DOOR
AREA DRAINADJ ADJUSTABLEAF AIR FILTERAFC ABOVE FINISHED CEILINGAFF ABOVE FINISHED FLOORAFG ABOVE FINISHED GRADEAHU AIR HANDLING UNITAL ALUMINUMAMB AMBIENTAP ACCESS PANELAPD AIR PRESSURE DROPARI AMERICAN REFRIGERANT INSTITUTEARCH ARCHITECTAS AIR SEPARATORASHRAE AMERICAN SOCIETY OF HEATING AND REFRIGERATION ENGINEERSASME AMERICAN SOCIETY OF MECHANICAL ENGINEERSASTM AMERICAN SOCIETY OF TESTING AND MATERIALSAV ACID VENT
AIR VENTAVG AVERAGEAW ACID WASTEAWS AMERICAN WELDING SOCIETYAUX AUXILIARY
B BOILERBC BELOW COUNTERB/C BACK OF CURBBFV BUTTERFLY VALVEBH BOX HYDRANTBHP BRAKE HORSEPOWERBLDG BUILDINGBM BENCHMARKBOD BOTTOM OF DUCT (AFF)BOF BOTTOM OF FOOTINGBOS BOTTOM OF STRUCTUREBT BATH TUB
BREAK TANKBTU BRITISH THERMAL UNITBV BALL VALVEBWV BACK WATER VALVE
C CELSIUSCAB CABINETCAV CONSTANT AIR VOLUMECB CATCH BASINCC COOLING COILCD CONDENSATE DRAIN LINECFH CUBIC FEET PER HOURCFM CUBIC FEET PER MINUTECFS CUBIC FEET PER SECONDCI CAST IRONCIRC CIRCULATINGCL CENTERLINECLG CEILINGCLR CLEARCMP CORRIGATED METAL PIPECMU CONCRETE MASONRY UNITCPI CAST IRON PIPE INSTITUTECPVC CHLORINATED POLYVINYL CHLORIDECO CLEANOUTCOL COLUMNCOMB COMBINATIONCOMP COMPRESSORCON CONVERTERCONC CONCRETE
CONCENTRICCOND CONDENSER
CONDENSATECONN CONNECTIONCONT CONTINUOUS
CONTINUATIONCONTR CONTROLLER
CONTRACTORCOP COEFFICIENT OF PERFORMANCECRAC COMPUTER ROOM A/C UNITCRT CATHODE RAY TUBECRU CONDENSATE RETURN UNITCT COOLING TOWERCTR CENTERCU COPPERCW COLD WATERCWP CONDENSER WATER PUMPCWR CONDENSER WATER RETURNCWS CONDENSER WATER SUPPLYCV CONSTANT VOLUME
dB DECIBELDB DRY-BULBDC DOUBLE DUCT CONSTANT VOLUME
DIRECT CURRENTDDC DIRECT DIGITAL CONTROLDESIG DESIGNATIONDEFL DEFLECTIONDTL DETAILDF DRINKING FOUNTAINDIA DIAMETERDIFF DIFFUSERDIM DIMENSIONDISC DISCONNECTDN DOWNDP DISCHARGE PLENUMDPR DAMPERDS DOUNSPOUT
DOUBLE SUCTIONDV DOUBLE DUCT VAVDW DISHWASHERDWG DRAWINGDWH DOMESTIC WATER HEATERDWP DOMESTIC WATER PUMPDX DIRECT EXPANSION
(E) EXISTINGEA EACHEAT ENTERING AIR TEMPERATUREEC ELECTRICAL CONTRACTORECC ECCENTRICEDB ENTERING DRY BULBEDF ELECTRIC DRINKING FOUNTAINEDH ELECTRIC DUCT HEATER
EDR EFFECTIVE DIRECT RADIATIONEER ENERGY EFFICIENCY RATIOEF EXHAUST FANEFF EFFICIENCYEJ EXPANSION JOINTEL ELEVATIONEMRG EMERGENCYENCL ENCLOSUREENGR ENGINEERENT ENTERINGES END SUCTION
EMERGENCY SHOWERESP EXTERNAL STATIC PRESSUREET EXPANSION TANKETR EXISTING TO REMAINEVAP EVAPORATOREWB ENTERING WET BULBEWT ENTERING WATER TEMPERATUREEX EXPLOSION PROOFEXT EXTERNALEXTG EXISTING
F DEGREE FAHRENHEITFBO FURNISHED BY OTHERSFCO FLOOR CLEAN OUTFCS FLOOR CONTROL SWITCHFCU FAN COIL UNITFD FLOOR DRAIN
FIRE DAMPERFDS FIRE DEPARTMENT SIAMESEFDV FIRE DEPARTMENT VALVEFG FIBERGLASSFF FINAL FILTERFH FIRE HYDRANTFHC FIRE HOSE CABINETFHR FIRE HOSE RACKFIXT FIXTUREFLA FULL LOAD AMPSFLEX FLEXIBLEFL FLOW LINESFLR FLOORFP FAN POWERED MIXING BOX
FIRE PUMPFPI FINS PER INCHFPM FEET PER MINUTEFRIC FRICTIONFRZR FREEZERFS FLOW SWITCH
FIRE SPRINKLERFSK FLOOR SINKFT FOOT
FEETFT WC FEET, WATER COLUMNFUT FUTURE
G GASGA GAUGEGAL GALLONGALV GALVANIZEDGC GENERAL CONTRACTORGLV GLOBE VALVEGND GROUNDGPD GALLONS PER DAYGPM GALLONS PER MINUTEGSH GRAND SENSIBLE HEATGV GATE VALVE
HB HOSE BIBBHC HEATING COILHD HEAD
HUB DRAINHF HUMIDIFIERHORIZ HORIZONTALHP HORSEPOWER
HALON PANELHPU HEAT PUMP UNITHKP HOUSEKEEPING PADHSC HORIZONTAL SPLIT CASEHSTAT HUMIDISTATHT HEIGHTHTG HEATINGHTR HEATERHU HUMIDIFIER SECTIONHW HOT WATERHWC HOT WATER CIRCULATORHWP HOT WATER PUMPHWR HOT WATER RETURNHWS HOT WATER SUPPLYHX HEAT EXCHANGERHZ HERTZ
ID INSIDE DIAMTERIE INVERT ELEVATIONIH INFRARED HEATERIN INCHIN WC INCH, WATER COLUMNINSUL INSULATIONINT INTERNAL
INTERIORIW INDIRECT WASTE
JB JUNCTION BOXJP JOCKEY PUMP
KEC KITCHEN EQUIPMENT CONTRACTORKO` KNOCKOUTKVA KILOVOLT AMPSKW KILOWATT
L LENGTHLAT LEAVING AIR TEMPERATURELAV LAVATORYLBS POUNDSLBS/HR POUNDS PER HOURLF LINEAR FEETLP LOW PRESSURELRA LOCKED ROTOR AMPSLVG LEAVINGLVL LEVELLWB LEAVING WET BULBLWCO LOW WATER CUT OFFLWT LEAVING WATER TEMPERATURE
MA MAKE-UP AIRMAT MIXED AIR TEMPERATUREMAX MAXIMUMMBH THOUSAND BTUHMC MECHANICAL CONTRACTORMCA MINIMUM CIRCUIT AMPACITYMCC MOTOR CONTROL CENTERMECH MECHANICALMFR MANUFACTURERMH MANHOLEMI MALLEABLE IRONMIN MINIMUMMOCP MAXIMUM OVER CURRENT PROTECTIONMP MEDIUM PRESSUREMS MOP SINKMTD MOUNTEDMTL METALMU MAKE-UPMUA MAKE-UP AIR UNITMVD MANUAL VOLUME DAMPER
(N) NEWNC NORMALLY CLOSEDNFP NATIONAL FIRE PROTECTION ASSOCIATIONNIC NOT IN CONTRACTNO NORMALLY OPENNO NUMBERNTS NOT TO SCALE
OA OUTSIDE AIROAF OUTSIDE AIR FANOAHU OUTSIDE AIR HANDLING UNITOBD OPPOSED BLADE DAMPEROC ON CENTEROD OUTSIDE DIAMETER
OVERFLOW DRAINOFCU OUTSIDE AIR FAN COIL UNITOPG OPENINGOS&Y OPEN STEM AND YOLK
P PUMPPLUMBING EQUIPMENT
PC PLUMBING CONTRACTORPCR PUMPED CONDENSATE RETURNPD PRESSURE DROP
PLANTER DRAINPF PRE-FILTERPH PHASE
POST HYDRANTPIV POST INDICATOR VALVEPLBG PLUMBINGPNEU PNEUMATICPNL PANELPNTH PENTHOUSEPP POLYPROPYLENEPPM PARTS PER MILLIONPRESS PRESSUREPRI PRIMARYPRS PRIMARY REDUCING STATIONPRV PRESSURE REDUCING VALVEPSF POUNDS PER SQUARE FOOTPSI POUNDS PER SQUARE INCHPSIG POUNDS PER SQUARE INCH, GAUGEPT PLUMBING TRIMPV PLUG VALVEPVC POLYVINYL CHLORIDEPWL SOUND POWER LEVEL
QTY QUANTITY
(R) REMOVERELOCATE
RA RETURN AIRRAD REFRIGERATED AIR DRYERRAF RETURN AIR FANRAG RETURN AIR GRILLERAT RETURN AIR TEMPERATURERCP REFLECTED CEILING PLAN
REINFORCED CONCRETE PIPERD ROOF DRAINRE REFERENCE
REFERRECIRC RECIRCULATERED REDUCERREFR REFRIGERATORREG REGISTERREINF REINFORCINGREQD REQUIREDREV REVISION
REVISERF RETURN FANRH RELATIVE HUMIDITYRHG REFRIGERANT HOT GASRKVA RUNNING KILOVOLT AMPSRKW RUNNING KILOWATTSRL REFRIGERANT LIQUIDRLA RUNNING LOAD AMPSRM ROOM
REFRIGERANT MACHINERPM REVOLUTIONS PER MINUTERS REFRIGERANT SUCTIONRTU ROOFTOP UNITRV RELIEF VALVE
SA SUPPLY AIRSAF SUPPLY AIR FANSAG SUPPLY AIR GRILLESAN SANITARY SEWERSAR SUPPLY AIR REGISTERSCHED SCHEDULESCFM STANDARD AIR CUBIC FEET PER MINUTESCR SILICON CONTROLLED RECTIFIERSD STORM DRAINSE SEWAGE EJECTORSEC SECONDARYSECT SECTIONSENS SENSIBLESF SQUARE FEET
DUCTWORK
T
T
TS
H
HS
PS
CD
CO
S
EXISTING THERMOSTAT
NEW THERMOSTAT
SPACE TEMPERATURE SENSOR
SPACE HUMIDISTAT
SPACE HUMIDITY SENSOR
SPACE PRESSURE SENSOR
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
DUCT MOUNTED SMOKE DETECTOR
(E)
FIRE DAMPER
SMOKE DAMPER
FIRE/SMOKE DAMPER
MOTORIZED DAMPER
BACKDRAFT DAMPER
TRANSITION:RECTANGULAR TO ROUND
ROUND DUCT UP
CONICAL TAP
RECTANGULAR BRANCH TAP
1A101
SIM
TYPELENGTH
SECTION NO.
SECTION VIEWSHEET NO.
DETAILDESIGNATION
POWERED EQUIPMENTDESIGNATION
NON POWERED EQUIPMENTDESIGNATION
BASEBOARD EQUIPMENTDESIGNATION
SHEET KEY NOTES
AHU1.01
VAV1.01
AM1-01
FCU1A-01
INDICATES TYPE OF EQUIPMENT
INDICATES UNIT NUMBER WITHIN AREA
LEVEL
1 - EVENT LEVEL2 - MAIN CONCOURSE3 - PREMIUM LEVEL4 - UPPER CONCOURSE5 - MECHANICAL MEZZANINE6 - ROOF LEVEL INDICATES AREA (A,B,C,D,E,F,G) ETC.
PIPING SYMBOLS
PRESSURE/TEMPERATUREPORT TRAPS
CONCENTRIC REDUCER
ECCENTRIC REDUCER
EXPANSION JOINT
THERMOMETER W/THERMOWELL
UNION
AIR VENT
FLEXIBLE PIPECONNECTOR
FLOW SWITCH
PRESSURE SWITCH
P&T
CR
ER
EJ
U
T
FS
PS
AV
FC
PRESSURE GAUGE W/GAUGE COCK
ELBOW UP
ELBOW DOWN
TEE UP
TEE DOWN
ISOLATION VALVE, RE:SPECS
PG
IV
OUTSIDE STEM ANDYOKE
OS&Y
DRAIN VALVE W/ HOSEEND CONNECTION
DV
PIPE CAP OR PLUG
ABBREVIATIONSYMBOL DESCRIPTION
BALL VALVE W/ HOSECONNECTION
CHECK VALVE WITHINDICATION OF FLOWDIRECTION
PRESSURE REDUCINGVALVE
AUTO FLOW CONTROLVALVE W/ TEST PORTS
CIRCUIT SETTER ORBALANCING VALVE
GLOBE VALVE (STRAIGHTPATTERN)
GLOBE VALVE (ANGLEPATTERN)
BUTTERFLY VALVE
CV
PRV
FCV
GLV
BFV
CS,BV
GLV
BALL VALVE
AUTOMATIC TEMPERATURECONTROL VALVE, 2-WAY
AUTOMATIC TEMPERATURECONTROL VALVE, 3-WAY
BALANCING VALVE
TEMPERATURE/PRESSURERELIEF VALVE
STRAINER W/ BLOW-OFF &CAPPED HOSE ENDCONNECTION
BV
TCV
TCV
BV
TMP
STR
STEAM TRAPST
VALVE IN RISER
PIPING TYPES
CHILLED WATERSUPPLY
CHILLED WATERRETURN
HEATING WATERSUPPLY
HEATING WATERRETURN
CONDENSERWATER RETURN
CONDENSERWATER SUPPLY
CONDENSATEDRAIN
HIGH PRESSURESTEAM SUPPLY
MEDIUM PRESSURESTEAM SUPPLY
LOW PRESSURESTEAM SUPPLY
CHS
CHR
HWS
HWR
CWS
CWR
MPS
LPS
D
HPS
HIGH PRESSURECONDENSATERETURN
MEDIUM PRESSURECONDENSATERETURN
LOW PRESSURECONDENSATERETURNREFRIGERANTSUCTION
REFRIGERANTLIQUID
CONTROL AIR(PNEUMATIC)
CHS
CHR
HWS
HWR
CWS
CWR
MPS
LPS
D
HPS
HPRHPR
MPRMPR
LPRLPR
RSRS
RLRL
AA
BOILER BLOWDOWN
BDBD
BOILER FEEDBFBF
BLOW OFFBOBO
CHEMICAL FEEDERCFCF
PROCESS COOLINGWATERSUPPLY/RETURN
PCS/RPCS/R
HIGH TEMP. HOTWATERSUPPLY/RETURN
HTWS/RHTWS/R
PRIMARY OR DISTRICTHEATING WATERSUPPLY/RETURN
PHWS/RPHWS/R
PRIMARY OR DISTRICTCHILLED WATERSUPPLY/RETURN
PCHS/RPCHS/R
PUMPEDCONDENSATERETURN
PRPR
EXISTING PIPING(E)(E)
EXISTING PIPING TOBE REMOVED
(E)(E)
REFRIGERANTHOT GAS
RHGRHG
SINGLE LINE PIPING(UP TO 2")
DOUBLE LINE PIPING(2" AND ABOVE)
PIPETYPE
MISCELLANEOUS
SUPPLY DIFFUSER-4-WAY THROW
SUPPLY DIFFUSER-3-WAY THROW
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
UC
POINT OFDISCONNECTION
UNDERCUT DOOR(UNDER ARCH. SECTION)
D/L DOOR LOUVER (UNDERARCH. SECTION)
L/D LOUVER DOOR FULLHEIGHT. (UNDER ARCH.SECTION)
ARROW INDICATESDIRECTION OF FLOW
EXTERIOR WALLLOUVER (UNDERARCH. SECTION)
SUPPLY DIFFUSER-2-WAY THROW
SUPPLY DIFFUSER-1-WAY THROW
EQUIPMENT DESIGNATION
EXISTINGDIFFUSER
EXISTINGDUCTWORK TOBE REMOVED
EXISTINGDUCTWORK
POINT OF CONN. (CONN.NEW TO EXISTING)
A SIZECFM
(QTY)
DIFFUSERTYPE
SUPPLYDIFFUSER
ROUND DUCTDOWN
SUPPLY OR OUTSIDEAIR DOWN
NEWDUCTWORK
20"x16"
DUCT DIMENSIONS(WIDTH x HEIGHT)
TURNING VANESSPLITTER DAMPER
TRANSITION-RECT. TORECT. OR ROUND TO
ROUND
CONICAL SPIN-INFITTING W/ MANUAL
VOLUME DAMPER
LOW PRESSUREFLEXIBLE DUCT
SUPPLY SLOTDIFFUSER
RE: #1/M2.0
REFER TO DRAWING #1, SHEET M2.0
UP DN
RETURN DIFFUSER
RISE IN DIRECTIONOF AIRFLOWRETURN OR
RELIEF AIR UP
EXHAUST AIR UP EXHAUST DIFFUSER
DROP IN DIRECTION OFAIRFLOW
RETURN OR RELIEFAIR DN
EXHAUST AIR DN
SFCS SPRINKLER FLOOR CONTROL STATIONSH SHOWERSHT SHEETSIM SIMILARSK SINKSKVA STARTING KILOVOLT AMPSSKW STARTING KILOWATTSSM SHEET METALSP STATIC PRESSURE
SUMP PUMPSPEC SPECIFICATIONSPR SPRINKLERSQ SQUARESS STAINLESS STEEL
SERVICE SINKSSD SUBSURFACE DRAINSSFU SANITARY SEWER FIXTURE UNITSSSSC SOLID STATE SPEED CONTROLSTD STANDARDSTL STEELSTR STRAINERSURF SURFACESUSP SUSPENDSV SANITARY VENTST SOUND TRAP
TC TEMPERATURE CONTROLTD TRENCH DRAINTDH TOTAL DYNAMIC HEADTF TRANSFER FANTG TRANSFER GRILLETH BLK THRUST BLOCKTOD TOP OF DUCT (AFF)TOP TOP OF PIPE (AFF)TP TRAP PRIMERTPD TRAP PRIMER DEVICETSP TOTAL STATIC PRESSURETSTAT THERMOSTATTYP TYPICAL
U URINALU/F UNDERFLOORU/S UNDERSLABUCD UNDERCUT DOORUG UNDERGROUNDUH UNIT HEATERUL UNDERWRITERS LABORATORIESUNO UNLESS NOTED OTHERWISEUTR UP THROUGH ROOF
V VOLT, VENTVA VOLT-AMPEREVAC VACUUMVAV VARIABLE AIR VOLUMEVB VALVE BOX
VACUUM BREAKERVCP VITRIFIED CLAY PIPEVD VOLUME DAMPERVEL VELOCITYVERT VERTICALVFD VARIABLE FREUENCY DRIVEVIB VALVE IN BOXVOV VALVE ON VERTICALVP VACUUM PUMPVR VARIABLE AIR VOLUME REHEATVSD VARIABLE SPEED DRIVEVTR VENT THROUGH ROOF
W WATT, WASTE, WIDTHW/ WITHW/O WITHOUTWB WETBULBWC WATER CLOSETWCO WALL CLEANOUTWF WATER FILTERWH WALL HYDRANTWM WATER METERWP WEATHERPROOFWPD WATER PRESSURE DROPWWF WELDED WIRE FABRICWT WATER TIGHT
WEIGHT
Y YARD HYDRANT
Z ZONE
FITTINGS:
EJ
FS
PS
S SV SOLENOID VALVE
FC
ABBREVIATIONS:ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION
B
A
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
Y
ZAll information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN02/07/14DESIGN DEVELOPMENT04/04/1480% CD SET / PERMIT SET05/02/14100% CD SET
CSM WELCOMECENTER
M0.00
MECHANICALLEGEND
COLORADO SCHOOL OF MINESGOLDEN, CO
1219
DUCTWORK INSTALLATION:
PIPE INSTALLATION:
CONDENSATE DRAINAGE:
LOUVERS:
CUTTING, PATCHING AND DEMOLITION:
ELECTRICAL COORDINATION:
INSTALLATION:
GENERAL MECHANICAL CONTRACT REQUIREMENTS:
GENERAL:
STRUCTURE:
CONSTRUCTION VENTILATION:
FIRE STOPPING:
1. SEAL ALL SEAMS (LONGITUDINAL AND TRANSVERSE) AIR TIGHT WITH SEALANT PERSPECIFICATIONS.
2. DUCT DIMENSIONS ARE INSIDE CLEAR.
3. DIFFUSER NECK SIZE IS SAME AS FLEXIBLE DUCT SIZE.
4. UNLESS OTHERWISE NOTED, ALL CHANGES IN DIRECTION SHALL BE MADE WITH RADIUS ELBOWS WITH RADIUS TO CENTERLINE EQUAL TO 1.5 DUCT WIDTH.
5. WHERE REQUIRED FOR SPACE CONSTRAINTS, PROVIDE MITERED ELBOWS WITH TURNING VANES AS FOLLOWS:
A. FOR DUCT WIDTHS OF 36" OR LESS, PROVIDE MANUFACTURED SINGLE WIDTH TURNING VANES, WITH NO TRAILING EDGES AND SPACING IN ACCORDANCE WITH SMACNA DUCT CONSTRUCTION STANDARDS FOR "STANDARD SPACING".
B. USE DOUBLE THICKNESS (AIRFOIL) BLADES WITHOUT TRAILING EDGES FOR DUCT WIDTHS GREATER THAN 36".
6. ALL FLEXIBLE DUCTS SHALL NOT BE LESS THAN 2', OR MORE THAN 5' IN LENGTH. INSTALL FLEXIBLE DUCTWORK SUCH THAT:
A. MINIMUM OVERALL LENGTH OF 3D, STRAIGHT INTO NECK OF DIFFUSER.
B. MAXIMUM OF 135° OF TOTAL TURNING IN ENTIRE LENGTH OF FLEXIBLE DUCT.
C. MINIMUM TURNING RADIUM OF R = 1.5D.
D. WHERE: * D = FLEXIBLE DUCT DIAMETER * R = RADIUS OF TURN AS MEASURED TO CENTERLINE OF DUCT.
7. RETURN AIR PLENUM: THE HVAC SYSTEM WILL USE THE SPACE ABOVE THE CEILING AS A RETURN AIR PLENUM. CONTRACTOR SHALL CONFORM TO THE REQUIREMENTS OF NFPA AND LOCAL CODE REQUIREMENTS FOR ALL MATERIAL INSTALLED IN THE RETURN AIR PLENUM.
A. IN ADDITION, THE CONTRACTOR SHALL PROVIDE A COMPLETE RETURN AIR PATH BETWEEN ALL RETURN AIR DEVICES (GRILLES ETC.) AND THEIR RESPECTIVE HVAC UNIT. MAXIMUM VELOCITY OF RETURN AIR IN PLENUM SHALL GENERALLY NOT EXCEED 250 FEET PER MINUTE, NOR EXCEED 750 FEET PER MINUTE AT ANY CROSS-SECTION OF THE RETURN AIR PATH.
8. BRANCH LINES:
A. MAKE ALL TAPS TO ROUND DUCTWORK WITH CONICAL TEES.
B. MAKE ALL TAPS TO RECTANGLE DUCTWORK WITH 45° ENTRY OR CONICAL SPIN IN TO ROUND.
C. INCLUDE DAMPERS AT ALL BRANCH LINES.
9. GREASE DUCTS:
A. INSTALL AND SLOPE PER BUILDING CODE REQUIREMENTS. IF PERMITTED BYCODE, PROVIDE COLLECTION RESERVOIRS AS REQUIRED FOR LONGHORIZONTAL RUNS.
B. WRAP IN TWO HOUR RATED FIRE WRAP. COORDINATE WITH ARCHITECTURAL PLANS.
C. WRAP MUST BE RATED FOR 1,900° F AND HAVE A MINIMUM R VALUE OF 10.
D. WRAP MUST BE LISTED FOR ZERO CLEARANCE TO COMBUSTIBLES.
10. DUCT SIZES NOT CALLED OUT SHALL BE DETERMINED BASED ON 0.08" S.P. LOSS OR LESS PER 100 FT. OF LENGTH.
11. ASSUME ROUND OR OVAL DUCTS IN EXPOSED AREAS.
12. INCLUDE DAMPERS AT ALL BRANCH LINES, WHERE SHOWN ON THE DRAWINGS, AND WHERE OTHERWISE REQUIRED FOR BALANCING.
1. ALL PIPING SHALL BE ADEQUATELY SUPPORTED FROM THE BUILDING STRUCTURE TO PREVENT SAGGING, POCKETING, SWAYING OR DISPLACEMENT BY MEANS OF HANGERS AND SUPPORTS. PIPING IS NOT TO BE SUPPORTED BY EQUIPMENT.
2. PROVIDE DIELECTRIC WATERWAY FITTINGS BETWEEN DISSIMILAR MATERIALS.
3. PROVIDE CAPPED HOSE-END DRAINS WITH ISOLATION VALVES AT PIPING HIGH AND LOW POINT. VALVE AT HIGH POINT SHALL BE USED FOR AIR VENTING.
4. WELD PIPE IN ACCORDANCE WITH APPLICABLE CODES AND STANDARDS. WELDERS SHALL BE CERTIFIED FOR TYPE OF WORK BEING PERFORMED.
5. FLUSH OUT PIPING AND REMOVE CONTROL DEVICES BEFORE PERFORMING PRESSURE TEST. DO NOT USE PIPING SYSTEM VALVES TO ISOLATE SECTIONS WHERE TEST PRESSURE EXCEEDS VALVE PRESSURE RATING. PRESSURIZE PIPING AT 100 PSIG. IF LEAKAGE IS OBSERVED OR IF TEMPERATURE COMPENSATED PRESSURE DROP EXCEEDS 1% OF TEST PRESSURE, REPAIR LEAKS AND RETEST. DO NOT USE AIR PRESSURE TO TEST PLASTIC PIPE.
6. PROVIDE SUPPORT UNDER ELBOWS ON PUMP SUCTION AND DISCHARGE LINES.
7. ALL STRAINERS SHALL BE FURNISHED WITH A "ROUGHING" SCREEN AND TWO (2) SCREENS FOR NORMAL OPERATION. INSTALL STRAINER WITH ROUGHING SCREEN AND OPERATE SYSTEM FOR 24 HOURS MINIMUM (RUN DOMESTIC WATER SYSTEMS AT MAX FLOW FOR A MINIMUM OF ONE HALF (1/2) HOUR. REMOVE ROUGHING SCREEN AND INSTALL NORMAL SCREEN, AFTER TWO WEEKS OF NORMAL OPERATION INSTALL NEW NORMAL SCREEN. ALL STRAINERS TO HAVE CAPPED HOSE-END BALL VALVES.
8. PIPING SIZES SHALL BE BASED ON 2' OR LESS HEAD LOSS PER 100 FEET OF LENGTH. VELOCITIES SHALL NOT EXCEED 10 FEET PER SECOND.
9. INSTALL ALL PIPING TO ALLOW FOR EXPANSION AND CONTRACTION WITHIN THEPIPING SYSTEM. ENSURE ALL REQUIRED PIPE EXPANSION WILL OCCUR IN THEPROPER DIRECTION AND SEGMENT OF PIPE. PROPERLY ANCHOR (RE:SPECIFICATIONS) ALL PIPING REQUIRING EXPANSION/CONTRACTION ISOLATION.COORDINATE PIPE EXPANSION/CONTRACTION TO PREVENT DAMAGE TO ANY AND ALLBUILDING COMPONENTS.
10. PROVIDE ISOLATION VALVES AT EVERY HYDRONIC BRANCH LINE.
1. PROVIDE CONDENSATE DRAINAGE FOR ALL COOLING COILS AND OVERFLOW PANS.
2. ROUTE CONDENSATE PIPING, FULL SIZE OF DRIP PAN CONNECTION, TO NEAREST CODE APPROVED RECEPTACLE. INSULATE WHERE LOCATED ABOVE FINISHED CEILINGS.
3. HEAT TRACE CONDENSATE LINES FROM FOOD SERVICE EQUIPMENT.
1. ALL LOUVERS LOCATED ON EXTERIOR WALLS SHALL BE PROVIDED BYARCHITECTURAL DIVISION. ALL OTHER LOUVERS SHALL BE PROVIDED BY DIVISION23. REQUIRED LOUVER FREE AREAS ARE INDICATED ON DIVISION 23 AND 23DRAWINGS. IT IS THE RESPONSIBILITY OF THIS CONTRACTOR TO CONFIRM THAT THEREQUIRED FREE AREA HAS BEEN PROVIDED, PRIOR TO CONNECTION TO THATLOUVER. DIVISION 23 SHALL PROVIDE ALL LOUVER PLENUMS.
1. KEEP DEMOLITION & CUTTING TO MINIMUM REQUIRED FOR PROPER EXECUTION OF WORK.
2. BE RESPONSIBLE FOR ALL CUTTING AND PATCHING NECESSARY FOR THE COMPLETION OF THE WORK.
3. NO CUTTING (NOT SHOWN ON THE CONTRACT DOCUMENTS) SHALL BE DONE WITHOUT THE APPROVAL OF THE ARCHITECT AS TO LOCATIONS, METHOD AND EXTENT OF THE CUTTING.
4. REPAIR ALL ACCIDENTAL OR INTENTIONAL DAMAGE TO MATCH EXISTING CONSTRUCTION WITH NO NOTICEABLE DIFFERENCE IN CONTINUITY, APPEARANCE OR FUNCTION.
5. ALL "CAPPED" SANITARY AND VENT LINES SHALL BE RECONNECTED OR RE- ROUTED AS NECESSARY TO PREVENT "DEAD-ENDS" IN THE PIPING. ALL PIPING SHALL DRAIN TO ACTIVE SANITARY WASTE LINES AND ALL BRANCHES WITH TRAPS SHALL BE ADEQUATELY VENTED.
1. VERIFY THE ELECTRICAL SERVICE PROVIDED BY THE ELECTRICAL CONTRACTOR BEFORE ORDERING ANY MECHANICAL EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS.
2. PROVIDE PREMIUM EFFICIENCY MOTORS WITH 1.15 SERVICE FACTOR ON ALLEQUIPMENT, MOTORS SHALL BE CAPABLE OF OPERATING CONTINUOUSLY AT 105°FUNDER JOBSITE CONDITIONS AND ALTITUDE.
3. UNLESS NOTED OTHERWISE, ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITHHOA SWITCH AND STARTER COMPATIBLE WITH EQUIPMENT AND BMS SYSTEM.STARTERS SHALL BE PROVIDED BY DIVISION 21,22 AND 23 UNLESS IN A MOTORCONTROL CENTER. ALL DISCONNECTS SHALL BE FURNISHED BY DIVISION 26.
4. THE ELECTRICAL POWER FOR CERTAIN EQUIPMENT PROVIDED UNDER DIVISION 21,22AND 23 HAS NOT BEEN SPECIFICALLY INDICATED ON THE ELECTRICAL DRAWINGS ANDMUST BE PROVIDED BY AND FIELD COORDINATED BY THE DIVISION 21,22 AND 23TRADE REQUIRING SUCH POWER.
SUFFICIENT POWER FOR THIS PURPOSE SHALL BE FURNISHED AS "SPARE", DEDICATED CIRCUIT CAPACITY IN DIVISION 26'S PANELBOARDS. ALL WIRING, CONDUIT AND ELECTRICAL DEVICES DOWNSTREAM OF THE PANELBOARDS IS THE RESPONSIBILITY OF THE DIVISION 21,22 AND 23 TRADE REQUIRING THE POWER UNLESS OTHERWISE SHOWN ON THE ELECTRICAL DRAWINGS.
SUCH EQUIPMENT IS HEREBY DEFINED AS:
A. ELECTRICAL HEAT TRACE. REQUIRED HEAT TRACE LOCATIONS, CAPACITIESAND SPECIFICATION ARE SHOWN OR INDICATED ON THE DRAWINGS. REFER TOSPECIFICATIONS FOR ADDITIONAL INFORMATION.
B. FIRE PROTECTION AIR COMPRESSORS, DRY-PIPE CONTROL PANELS ANDVALVES. REQUIRED CONNECTIONS ARE INCLUDED IN THE DIVISION 21 WORK,AND WILL BE SHOWN BY THAT CONTRACTOR'S ENGINEERED SYSTEM DESIGNDRAWINGS.
(1) PRE-ACTION SYSTEM INITIATION SIGNALS (SUCH AS SMOKE DETECTORS, OR GENERAL ALARM CONDITIONS IN A PRE-ACTION ZONE) SHALL BE PROVIDED UNDER DIVISION 28 FIRE-ALARM WORK.
(2) DIVISION 21 SHALL PROVIDE PRE-ACTION CONTROL PANEL AND INTERCONNECTION BETWEEN NEAREST SUITABLE FIRE ALARM PANEL AND LOCATION OF PRE-ACTION VALVE(S).
(3) DIVISION 28 SHALL PROVIDE INTERCONNECTION BETWEEN FIRE COMMAND CENTER ALARM PANEL (PROVIDED UNDER DIVISION 28) AND REMOTE COMMUNICATION FIRE ALARM PANEL (PROVIDED UNDER DIVISION 28).
C. TEMPERATURE CONTROL PANELS, CONTROL AIR COMPRESSORS AND LINE VOLTAGE POWER FOR 24V CONTROL TRANSFORMERS. REQUIRED CONNECTION ARE INCLUDED IN DIVISION 230900 AND WILL BE SHOWN BY THAT CONTRACTOR'S CONTROL SUBMITTAL DRAWINGS.
D. IT IS NOT PERMISSIBLE TO UTILIZE "SPARE" POWER FROM ADJACENT POWER CIRCUITS TO SERVE ANY OF THE ABOVE LOADS. ALL POWER MUST COME FROM DEDICATED CIRCUITS.
5. SMOKE DETECTORS:
FOR AIR HANDLING UNITS AND AIR SYSTEMS WITH A CAPACITY EXCEEDING 2000 CFM, PROVIDE UL LISTED SMOKE DETECTORS IN RETURN AIR SYSTEMS IN ACCORDANCE WITH THE INTERNATIONAL MECHANICAL CODE AND ELSEWHERE AS SHOWN ON THE DRAWINGS.
SMOKE DETECTORS WILL BE FURNISHED AND SET IN PLACE UNDER THIS DIVISION. DETECTORS WILL BE WIRED UNDER DIVISION 28. SMOKE DETECTORS MUST BE OF THE SAME MANUFACTURER, AND COMPATIBLE WITH THE FIRE ALARM SYSTEM PROVIDED UNDER DIVISION 28 (IF APPLICABLE).
CONNECT RELAY(S) TO FAN CONTROL CIRCUIT TO STOP FAN WHEN SMOKE IS DETECTED.
1. SUSPEND EACH TRADE'S WORK SEPARATELY FROM THE STRUCTURE. DUCTWORK SHALL BE HELD TIGHT TO STRUCTURE EXCEPT WHERE OTHERWISE SHOWN.
2. INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS UNLESS SPECIFICALLY INDICATED OTHERWISE OR WHERE LOCAL CODES OR REGULATIONS TAKE PRECEDENCE.
3. PROVIDE MANUFACTURER'S RECOMMENDED SERVICE CLEARANCE AROUND ALL EQUIPMENT REQUIRING SAME.
4. PROVIDE FOR SAFE CONDUCT OF THE WORK, CAREFUL REMOVAL AND DISPOSITION OF MATERIALS AND PROTECTION OF PROPERTY WHICH IS TO REMAIN UNDISTURBED.
5. PROVIDE ACCESS DOORS FOR ALL EQUIPMENT, VALVES, CLEANOUTS, ACTUATORS AND CONTROLS WHICH REQUIRE ACCESS FOR ADJUSTMENT OR SERVICING AND WHICH ARE LOCATED IN OTHERWISE INACCESSIBLE LOCATIONS.
A. FOR EQUIPMENT LOCATED IN "ACCESSIBLE LOCATIONS" SUCH AS LAY-IN CEILINGS: LOCATE EQUIPMENT TO PROVIDE ADEQUATE SERVICE CLEARANCE FOR NORMAL MAINTENANCE WITHOUT REMOVING ARCHITECTURAL, ELECTRICAL OR STRUCTURAL ELEMENTS SUCH AS THE CEILING SUPPORT SYSTEM, ELECTRICAL FIXTURES, ETC. "NORMAL MAINTENANCE" INCLUDES, BUT IS NOT LIMITED TO:FILTER CHANGING; GREASING OF BEARINGS; USING P/T PORTS FOR PRESSURE OR TEMPERATURE MEASUREMENTS; SERVICING CONTROL VALVES AND SERVICING CONTROL PANELS.
6. ISOLATE ALL PRESSURIZED PIPE (WATER, ETC.) AT EACH RISER, BRANCH, PIECE OF EQUIPMENT, AND AREA SERVED.
7. PROVIDE PRIMERS FOR ALL FLOOR DRAINS AND FLOOR SINKS SHOWN ON DRAWINGS. PRIMERS MAY BE CONNECTED TO FLUSH FIXTURES OR BE STAND ALONE. SEE SPECIFICATIONS.
8. NO DOMESTIC WATER, CHILLED WATER, OR HEATING WATER LINES SHALL BE LOCATED EXPOSED IN FINISHED SPACES OR BELOW THE BUILDING SLAB UNLESS SHOWN OTHERWISE ON THE DRAWINGS.
9. NO GAS LINES SHALL BE LOCATED BELOW BUILDING SLAB.
10. ALL CURBS, ROOF JACKS, ROOF THIMBLES, SANITARY VENTS, ROOF DRAINS, ETC. SHALL BE COMPATIBLE WITH ROOFING SYSTEM TO BE PROVIDED. REFERENCE ARCHITECTURAL DIVISION FOR REQUIRED FLASHING DETAILS.
11. MECHANICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL CONCRETE EQUIPMENT PAD DIMENSIONS, BASED ON THE FINAL EQUIPMENT SELECTION, TO THE STRUCTURAL AND GENERAL CONTRACTOR FOR INCLUSION IN THOSE CONTRACTOR'S WORK AS DESCRIBED BY THE GENERAL CONTRACTOR.
12. WARRANTY: AT A MINIMUM, THE ENTIRE MECHANICAL SYSTEM SHALL BE WARRANTED AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE (1) YEAR AFTER ACCEPTANCE OF THE SYSTEM BY THE OWNER. REFER TO INDIVIDUAL SPECIFICATION SECTIONS FOR SPECIFIC WARRANTY REQUIREMENTS.
1. UNLESS OTHERWISE NOTED, THE WORK DESCRIBED ON THE PLANS AND SPECIFICATIONS SHALL INCLUDE THE FURNISHING AND INSTALLATION OF ALL LABOR AND MATERIALS NECESSARY FOR COMPLETE AND OPERATIONAL HVAC, FIRE PROTECTION AND PLUMBING SYSTEMS. CONTRACTOR SHALL FURNISH THESE EVEN IF ITEMS REQUIRED TO ACHIEVE THIS (I.E. OFFSETS, ISOLATION AND BALANCING DEVICES, MAINTENANCE CLEARANCES, ETC.) ARE NOT SPECIFICALLY SHOWN.
2. DATA GIVEN ON THE DRAWINGS IS AS EXACT AS COULD BE SECURED. ABSOLUTE ACCURACY IS NOT GUARANTEED AND THE CONTRACTOR SHALL OBTAIN AND VERIFY EXACT LOCATIONS, MEASUREMENTS, LEVELS, SPACE REQUIREMENTS, POTENTIAL CONFLICTS WITH OTHER TRADES, ETC. AT THE SITE AND SHALL SATISFACTORILY ADAPT HIS WORK TO THE ACTUAL CONDITIONS OF THE JOB.
3. THE DRAWINGS ARE DIAGRAMMATICAL IN NATURE AND SHALL NOT BE SCALED. THEY SHOW CERTAIN PHYSICAL RELATIONSHIPS WHICH MUST BE ESTABLISHED WITHIN THE DIVISION 21,22 AND 23 WORK AND ITS INTERFACE WITH OTHER WORK. ESTABLISHING THIS RELATIONSHIP IN THE FIELD IS THE EXCLUSIVE RESPONSIBILITY OF THE CONTRACTOR. THIS DIVISION SHALL COORDINATE ITS WORK WITH ALL DIVISIONS OF THE WORK AND ADJUST ITS WORK AS REQUIRED BY THE ACTUAL CONDITIONS OF THE PROJECT.
A. THE CONTRACTOR SHALL VISIT THE SITE BEFORE SUBMITTING A BID TO BECOME THOROUGHLY FAMILIAR WITH THE ACTUAL CONDITIONS OF THE PROJECT. NO EXTRAS WILL BE ALLOWED DUE TO LACK OF KNOWLEDGE OF EXISTING CONDITIONS.
B. CERTAIN SYSTEMS REQUIRE ENGINEERING OF INSTALLATION DETAILS BY CONTRACTOR. UNLESS FULLY DETAILED IN THE CONTRACT DOCUMENTS, SUCH ENGINEERING IS THE EXCLUSIVE RESPONSIBILITY OF THE CONTRACTOR.
C. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE WHERE CLEARANCES ARE LIMITED, AND WHERE INSTALLATION DRAWINGS OR SCHEMATICS, "CONSTRUCTION DRAWINGS", OR COORDINATION DRAWINGS MAY BE REQUIRED IN ACCORDANCE WITH, OR IN EXCESS OF, THOSE REQUIRED BY THE SPECIFICATIONS. THE CONTRACTOR SHALL PREPARE ALL SUCH COORDINATION DRAWINGS AS PART OF THE BASE CONTRACT. SUCH DRAWINGS MAY BE SUBMITTED TO THE ARCHITECT/ENGINEER FOR RECORD AND COMMENT (AT THE CONTRACTOR'S OPTION).
4. THESE NOTES ONLY SUPPLEMENT, AND DO NOT REPLACE, THE SPECIFICATIONS.
5. DEFINITIONS AND TERMINOLOGY
A. THE DEFINITIONS OF DIVISION 1 AND THE GENERAL CONDITIONS OF THISSPECIFICATION ALSO APPLY TO THE DIVISION 21,22 AND 23 CONTRACTDOCUMENTS.
B. "CONTRACT DOCUMENTS" CONSTITUTE THE DRAWINGS, SPECIFICATIONS,GENERAL CONDITIONS, PROJECT MANUALS, ETC., PREPARED BY ENGINEER (OROTHER DESIGN PROFESSIONAL IN ASSOCIATION WITH ENGINEER) FORCONTRACTOR'S BID OR CONTRACTOR'S NEGOTIATIONS WITH THE OWNER. THEDIVISION 21,22 AND 23 DRAWINGS AND SPECIFICATIONS PREPARED BY THEENGINEER ARE NOT CONSTRUCTION DOCUMENTS.
C. "CONSTRUCTION DOCUMENTS", "CONSTRUCTION DRAWINGS", AND SIMILAR TERMS FOR DIVISION 21,22 AND 23 WORK REFER TO INSTALLATION DIAGRAMS, SHOP DRAWINGS AND COORDINATION DRAWINGS PREPARED BY THE CONTRACTOR USING THE DESIGN INTENT INDICATED ON THE ENGINEER'S CONTRACT DOCUMENTS. THESE SPECIFICATIONS DETAIL THE CONTRACTOR'S RESPONSIBILITY FOR "ENGINEERING BY CONTRACTOR" AND FOR PREPARATION OF CONSTRUCTION DOCUMENTS.
D. "(N)" INDICATES "NEW" EQUIPMENT TO BE PROVIDED UNDER THIS CONTRACT.
E. "(E)" INDICATES "EXISTING" EQUIPMENT ON SITE WHICH MAY OR MAY NOT NEED TO BE RELOCATED AS A PART OF THIS WORK.
F. "(R)" INDICATES EXISTING EQUIPMENT TO BE RELOCATED AS PART OF THIS WORK.
G. "FURNISH" MEANS TO "SUPPLY" AND USUALLY REFERS TO AN ITEM OF EQUIPMENT.
H. "INSTALL" MEANS TO "SET IN PLACE, CONNECT AND PLACE IN FULL OPERATIONAL ORDER".
I. "PROVIDE" MEANS TO "FURNISH AND INSTALL".
J. "EQUIVALENT" MEANS "MEETS THE SPECIFICATIONS OF THE REFERENCE PRODUCT OR ITEM IN ALL SIGNIFICANT ASPECTS." SIGNIFICANT ASPECTS SHALL BE AS DETERMINED BY THE ARCHITECT/ENGINEER.
K. "WORK BY OTHER(S) DIVISIONS"; "RE: XX DIVISION", AND SIMILAR EXPRESSIONS MEANS WORK TO BE PERFORMED UNDER THE CONTRACT DOCUMENTS, BUT NOT NECESSARILY UNDER THE DIVISION OR SECTION OF THE WORK ON WHICH THE NOTE APPEARS. IT IS THE CONTRACTOR'S SOLE RESPONSIBILITY TO COORDINATE THE WORK OF THE CONTRACT BETWEEN HIS/HER SUPPLIERS, SUBCONTRACTORS AND EMPLOYEES. IF CLARIFICATION IS REQUIRED, CONSULT ARCHITECT/ENGINEER BEFORE SUBMITTING BID.
L. BY INFERENCE, ANY REFERENCE TO A "CONTRACTOR" OR "SUB- CONTRACTOR" MEANS THE ENTITY WHICH HAS CONTRACTED WITH THE OWNER FOR THE WORK OF THE CONTRACT DOCUMENTS.
M. "ENGINEER" MEANS THE DESIGN PROFESSIONAL FIRM WHICH HAS PREPARED THESE CONTRACT DOCUMENTS. ALL QUESTIONS, SUBMITTALS, ETC. OF THIS DIVISION SHALL BE ROUTED THROUGH THE ARCHITECT TO THE ENGINEER (THROUGH PROPER CONTRACTUAL CHANNELS).
1. DO NOT PENETRATE STRUCTURAL MEMBERS. ALL EQUIPMENT SUPPORTS SHALL BE ATTACHED TO THE LOAD BEARING MEMBERS OF STRUCTURAL ELEMENTS. DO NOT OVER-STRESS ANY STRUCTURAL MEMBERS. CONTACT STRUCTURAL ENGINEER FOR ALLOWABLE LOADS FOR SPECIFIC MEMBERS.
2. DO NOT UTILIZE POWER DRIVEN ANCHORS FOR ANY LOCATIONS WHICH REQUIRE THE LOAD TO BE HELD IN TENSION. SEE STRUCTURAL DIVISION FOR ADDITIONAL RESTRICTIONS.
3. SEE ALSO STRUCTURAL DIVISION FOR ACCEPTABLE ANCHORING AND SUPPORT MEANS, METHODS, AND LOCATIONS.
4. PROVIDE FLEXIBLE CONNECTORS, EXPANSION LOOPS, EXPANSION JOINTS, ADDITIONAL FITTINGS OR EQUIVALENT TO ACCOMMODATE THE THERMAL EXPANSION OF THE BUILDING THROUGH STRUCTURAL EXPANSION JOINTS. PROVIDE SUCH FITTING AT EVERY PIPE, DUCT, CONDUIT, ETC. CROSSING OF A STRUCTURAL EXPANSION JOINT.
1. USE OF EXISTING OR NEW MECHANICAL SYSTEMS FOR TEMPORARY VENTILATION SHALL BE APPROVED BY MINES FACILITIES DEPARTMENT PRIOR TO USE.
2. WHERE EXISTING OR NEW MECHANICAL SYSTEMS ARE USED FOR TEMPORARY VENTILATION OR CLIMATE CONTROL, MECHANICAL EQUIPMENT INSTALLER SHALL PROVIDE CONSTRUCTION FILTERS, MAINTAIN EQUIPMENT, AND CLEAN, ADJUST AND PUT IN NEW CONDITION BEFORE BUILDING OCCUPANCY. PARTS AND LABOR WARRANTY SHALL NOT BE CONSIDERED TO START UNTIL ACCEPTANCE OF SYSTEM BY OWNER.
3. PROVIDE CONSTRUCTION FILTERS INSTALLED AT ALL AIR MOVING DEVICES THROUGHOUT THE CONSTRUCTION. REMOVE FILTERS ONLY FOR BALANCING AND FINAL TURNOVER. INSPECT ALL NON-CONSTRUCTION FILTERS AND REPLACE ALL THOSE DEEMED NECESSARY BY THE ENGINEER PRIOR TO ACCEPTANCE OF THE SYSTEM BY THE OWNER.
1. FIRE STOPPING REQUIREMENT: PENETRATIONS THROUGH RATED WALLS AND FLOORS SHALLBE SEALED WITH A MATERIAL CAPABLE OF PREVENTING THE PASSAGE OF FLAMES AND HOTGASSES WHEN SUBJECTED TO THE REQUIREMENTS OF THE TEST STANDARD SPECIFIC FORFIRE STOPS ASTM-E-814. ACCEPTANCE MATERIALS INCLUDE: DOW CORNING RTV FIRE STOPFOAM FOR BARE PIPE, METAL CONDUIT, AND ELECTRICAL CABLE; 3M FIRE DAM 21,22 AND 230CAULK FOR BARE PIPE, METAL CONDUIT, AND BUILDING CONSTRUCTION; GAPS 3M FS-195INTUMESCENT STRIPS FOR INSULATED PIPES, PLASTIC PIPE OR CONDUIT, AND ELECTRICALCABLE.
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN02/07/14DESIGN DEVELOPMENT04/04/1480% CD SET / PERMIT SET05/02/14100% CD SET
CSM WELCOMECENTER
M0.01
MECHANICALNOTES
COLORADO SCHOOL OF MINESGOLDEN, CO
1219
SS
S
S
S
F/S
F/S
20"x16"RA
20"x16"RA
16"x20"SA
B-02FPVAV
B-01FPVAV
12"øSA
16"øSAG 10"X3"100
E 12"X10"400
G 12"X6"285
T
B-01CUH
16"øSA
8"øSA
T
E 10"X10"300
1
1.8
2
3
4
5
7
8
9
D E F
6
10
CA GB
E10"X10"300
G12"X4"150
38"X14"1050 F1
10"X6"150(2) F
12"X12"600F
12"X12"400F
12"øSA
G 12"X6"285
G 12"X6"285
20"x16"SA
38"X14"1050F1
B-01FCU
1010 56"x24"RA
60"x22"SA
26"x
22"S
A36
"x22
"SA
24"x
16"S
A
14"x14"SA
1-02FPVAV
1-01FPVAV
10"ø245A (4)
1-04FPVAV
1-05FPVAV
1-06FPVAV
1-07FPVAV
22"X22"980B
10"øSA
20"x12"SA
22"x18"SA
18"x16"SA
24"x10"RA
22"X22"670B
22"x10"RA
12"x8"SA
E 12"X8"250 (2)
12"x12"SA
8"ø170 A
T
TT
T
16"x14"SA
12"øSA
1-08FPVAV
1-09FPVAV
8"ø130A
8"øSA
22"X22"1200B
22"X22"360B
22"X22"130B
1-10FPVAV
12"ø415A (2)
T
T
T22"X22"2250B
1-11FPVAV
22"X22"300B
22"X22"300B
22"X22"230B
T
1-12FPVAV1-13
FPVAV
1-14FPVAV
1-15FPVAV
10"ø300A
10"ø300A
10"ø230A
T
12"ø390A
8"øSA
12"øSA
22"X22"390B
T
12"ø390 A
22"X22"390 B
8"øSA
10"ø360 A
10"ø350 A
10"ø350 A
12"ø420 A
12"x12"SA
18"x14"SA
22"X22"360 B
T
22"X22"350 B
22"X22"350 B
22"X22"420 B
12"ø400A
8"øSA
12"øSA
22"x10"RA
22"X22"390 B
10"ø240 A
1-01VAV
1-02VAV10"øSA
10"x12"SA
10"ø335A
10"ø335 A
10"ø330 A
1-03VAV
6"ø50A
6"ø100A
6"ø80A
E 22"x6"490
1-04VAV
8"ø125A (2)
22"X22"250B
1-05VAV
8"ø150A (4)
12"x10"SA8"øSA
22"X22"600B
1-06VAV
6"ø100 A
8"ø200 A
T
T
22"X22"200 B
22"X22"100B
T
22"X22"100B
T
T
T
T
22"X22"560B
22"X22"630B
48"X24"2200F (2)
8"X8"250B (2)
16"x
12"S
A
26"x16"SA
1-01TF
12"X12"490F (2)
1-03CUH
20"x10"EA
22"X22"500B
22"X22"500 B
22"X22"500B
8"X6"75F
1-02CUH
1-01CUH
1-01FCU
E 6"X6"50
6"x6"SA
8"X8"240 B
10"ø360A
18"x12"SA
12"øSA
1.8
2
3
4
5
7
8
9
D E F
6
10
CA GB
8"X8"250B (2)
8"x8"EA
10"x10"EA 10"x10"EA
14"x10"EA
10"øSA
1-03FPVAV
22"X22"2200 B
22"X22"980B
24"x10"RA
14"x14"RA
14"x12"SA
10"øSA
10"ø230 A(2) 10"ø
235A (2)
30"x14"SA
14"øSA
10"øSA
48"X30"2630(2) F
42"X24"1960F (2)
10"ø315 A(2)
12"x12"SA
8"øSA
8"ø280 A(2)
TT22"X12"560F (2)
36"X18"1190(2) F
18"x14"SA
30"X16"900(2) F
22"X22"900B
42"x26"RA
36"x22"RA
46"x22"RA
50"x30"RA
10"ø300A (4)
8"ø200A
30"X22"1200(2) F
12"x12"SA
14"X14"130F (2)
14"X14"360F (2)
12"ø420A
14"X14"300(2) F
14"X14"300F (2)
10"øSA
14"X12"390(2) F
14"X14"390(2) F
30"X14"750(2) F
14"X14"350(2) F
14"X14"350(2) F
30"X18"1060(2) F
18"X12"530(2) F
14"X14"400(2) F
68"x20"RA
14"X6"240(2) F
5"øSA
16"x12"SA
E12"x6"430
5"øSA
8"x10"SA
14"X14"100F (2)
14"X14"100F (2)
12"X6"200(2) F
30"X24"1370F (2)
30"X24"1370(2) F
8 8
6
20"x16"SA
20"x14"SA
12"ø440D (5)
12"ø450D (2)
22"x10"RA
22"x10"RA
CDT
CD
CD
CDCD
CD
CD
G 10X350
6"øSA
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN02/07/14DESIGN DEVELOPMENT04/04/1480% CD SET / PERMIT SET05/02/14100% CD SET
CSM WELCOMECENTER
M2.10
BASEMENT ANDFIRST FLOORMECHANICAL PLAN
COLORADO SCHOOL OF MINESGOLDEN, CO
1219
1/8" = 1'-0"1 01 - BASEMENT LEVEL 1/8" MECHANICAL PLAN 1/8" = 1'-0"2 02 - FIRST FLOOR LEVEL 1/8" MECHANICAL PLAN
KEYNOTESKey
Value Keynote Text
5 CAMPUS STEAM AND CHILLED WATERENTRY POINT FROM UTILITY TUNNEL.RE: DRAWING P1.00 AND MECHANICALDIAGRAMS.
6 PROVIDE OPEN ENDED DUCTTHROUGH WALL IN PLENUM WTIHELBOW UP AS INDICATED. PROVIDEWIRE MESH OVER BOTH OPEN DUCTENDS.
8 PROVIDE GRILLES IN PLENUM FORRETURN AIR PATH THROUGH PLENUMWALL.
10 PROVIDE FIRE AND SMOKE DAMPER INVERTICAL DUCT WHERE DUCT EXITSRATED SHAFT.
GENERAL NOTES:1. THE DRAWINGS ARE DIAGRAMMATIC INNATURE. THE CONTRACTOR ISRESPONSIBLE FOR ALL OFFSETS,TRANSITIONS, ELBOWS, ETC. ASREQUIRED IN DUCTWORK, PIPING,SUPPORTS, ETC. TO COMPLETE THEWORK IN A CLEAN FUNCTIONALINSTALLATION THAT IS FULLYCOORDINATED WITH ALL OTHERTRADES. ANY PRICING EFFORT SHALLTAKE THESE FACTORS INTO ACCOUNT.
2. MAINTAIN A MINIMUM OF 25'-0"SEPARATION FROM OUTSIDE AIRINTAKES TO TERMINATIONS OFEXHAUST, COMBUSTION AIR, PLUMBINGVENTS, ETC. AS REQUIRED BY CODE.
3. COORDINATE EQUIPMENTHOUSEKEEPING PAD DIMENSIONS ANDLAYOUT WITH THE GENERALCONTRACTOR BASED ON FINALEQUIPMENT SIZES.
4. PROVIDE MANUAL BALANCE DAMPERSIN ALL SUPPLY DUCT BRANCH TAPSDOWNSTREAM OF VAV BOXES.
5. PROVIDE MANUAL BALANCE DAMPERSIN ALL EXHAUST DUCT BRANCH TAPS.
6. PROVIDE "Z" BOOT TRANSFER DUCTSIN FULL HEIGHT WALLS IN AREAS WHEREA PLENUM RETURN SYSTEM IS UTILIZED.BOOTS SHALL BE SIZED TO MAINTAIN AMAXIMUM OF 400 FPM.
7. COORDINATE SPACE TEMPERATURESENSORS AND THERMOSTATLOCATIONS TO ALIGN VERTICALLY WITHLIGHT SWITCHES. MOUNT AT 60" AFF.
8. TEMPERATURE CONTROLSCONTRACTOR SHALL SUBMIT PLANSINDICATING ALL SPACE TEMPERATURESENSORS, T-STATS, HUMIDITYSENSORS, ETC. AS PART OF SUBMITTALPROCESS FOR A/E REVIEW.
9. PROVIDE REMOTE REGULATORS FORMANUAL BALANCE DAMPERS ABOVEACCESSIBLE CEILINGS.
F/S
F/S
F/S
F/S
F/S
F/S
56"x
18"S
A
32"x
16"S
A
52"x36"RA
T
2-01FPVAV
12"ø480A
22"X22"480B
10"ø360A
10"ø360A
14"x14"SA
12"øSA
T
22"X22"360B
22"X22"360B
2-02FPVAV
22"X22"100B
22"X22"250B
8"ø100A
10"ø250A
10"ø290A
14"x12"SA
22"X22"290B
2-03FPVAV
T
12"ø550A
12"ø550A
12"ø550A
14"x14"SA
18"x14"SA
14"øSA
2-04FPVAV
T
22"X22"1450 B
22"X22"310B
22"X22"260B
10"ø310A
10"ø260A
14"x14"SA
10"øSA
2-05FPVAV
T
22"X22"150B
8"ø150A
E10X10350(2)
14"ø750 A
22"X22"750 B
T
12"ø480 A
12"ø430 A
20"x14"SA
22"X22"430B
22"X22"480B
2-06FPVAV
12"øSA
8"ø150A
10"x8"SA
4"øSA2-04VAV
T
22"X22"150 B
24"x10"RA
6"ø50A
6"ø50A
6"ø60 A
8"ø160A
2-03VAV
T
22"X22"160 B
8"x8"SA
14"x12"SA
E12X10490
18"X12"490(2) F
12"x10"SA 9"øSA
8"ø165A (4)
8"ø170A (2)
T
10"x10"SA
14"x10"SA
14"x14"SA2-02VAV
10"øSA
18"x
14"S
A
22"x
12"S
A
12"ø550 A
12"ø550 A
12"ø550 A
14"x14"SA
18"x14"SA
T
14"øSA
22"X22"1450 B
22"X22"1450B
10"øSA
2-08FPVAV
14"x12"SA
10"ø350 A
10"ø310 A
22"X22"350 B
22"X22"310 B
T
12"ø515 A
12"ø515 A
22"X22"1030 B 24"x10"RA
T
10"øSA
2-09FPVAV
16"x14"SA
30"x
18"S
A30
"x20
"SA
6"øSA
10"øSA
10"x12"SA
8"ø100 A
8"ø140A
8"ø100A
2-01VAV
22"x
16"S
A
2-07FPVAV
T
8"øSA
2-01TF
E 12X10430
8"X8"200 B
8"X8"300B
2-01FCU
6"ø50 A
8"x6"EA
8"X6"100F
12"x10"EA
1.8
2
3
4
5
7
8
9
D E F
6
10
CA GB
12"x10"SA
12"x12"SA
14"x14"SA
14"øSA
8"øSA
40"x24"RA
12"x12"SA10"ø285 A(2)
22"X22"570 B
24"X10"570(2) F
14"X14"360(2) F
14"X14"360(2) F
18"X12"480F (2)
8"øSA
14"X14"100F (2)
14"X14"250F (2)
14"X14"290F (2)
14"øSA
14"X14"310F (2)
14"X14"260(2) F
14"X14"150(2) F
30"X26"1500F (2)
24"X12"430F (2)
24"X12"480(2) F
14"X14"350(2) F
14"X14"310(2) F
30"X18"1030(2) F
12"X8"160(2) F
22"X22"1450B
48"x22"RA
42"X24"1680(2) F
44"X24"2070F (2)
36"X18"1340F (2)
22"X22"1450B
7
8
8 8
22"X22"300B
24"x10"RA24"x10"RA
22"X22"200B
38"X22"1500 FT
2-02TF
38"X22"1500F (2)
CD
CD
CD
38"x
18"S
A
30"x
18"S
A
24"x16"SA
12"ø405A (2)
T
12"ø590A
22"X22"810 B
14"x14"SA
22"X22"590 B
16"øSA
3-05FPVAV
12"ø590A
12"ø350A (2)
22"X22"590 B
22"X22"700 B
14"x14"SA
22"X22"500 B
24"x10"RA
12"ø500 A
12"øSA
8"øSA
3-06FPVAV
T
14"ø650A
12"ø500 A(2)
22"x16"SA
22"X22"650 B
T
3-07FPVAV
10"ø345 A(2)
22"X22"690 B
E10X10350
14"øSA
18"x14"SA
14"x14"SA
12"ø470A
12"ø470A
12"ø470A
3-04FPVAV
T
24"x12"RA 22"X22"1575B
14"x14"SA
12"ø460A
12"ø460A
12"ø470A
T
12"øSA
3-03FPVAV
22"X22"1575B
10"ø310A
10"ø340A
12"ø470A
22"X22"470B
22"X22"340B
22"X22"310B
20"x14"SA
14"øSA
3-02FPVAV
T
22"X22"740B
T
3-01FPVAV
14"x12"SA
12"ø395A (2)
10"øSA
24"x10"RA
22"X22"790B
60"x
40"S
A
38"x
24"S
A
74"x44"RA
T
8"ø190A
12"ø420A
14"x14"SA
10"øSA3-01VAV
T8"ø150A
T
22"X22"500B
24"x10"RA
22"X22"1270 B
3-02VAV
8"ø205A (2)
8"ø205A (4)12"øSA
10"x10"SA18"x14"SA
10"x10"SA
T
3-03VAV
22"X22"1420B
6"ø90 A
6"ø90A
8"ø100A
8"ø100A
7"øSA
10"x10"SA3-04VAV
T
8"ø135A
10"øSA
14"x14"SA
14"x12"SA
10"ø370 A(2)
12"x12"SA8"X8"
200 B
8"X8"200B
8"x8"EA
8"x8"EA
26"x
14"E
A
3-01TF
E 12"X10"530
3-01FCU 8"X8"
150F
8"x8"EA
38"x94"RA
3
4
5
7
8
9
D E F
6
10
C
34"x32"SA44"x24"SA
20"x14"EA
40"x60"RA
62"x36"RA
10"X6"150F (2)
3-01UH
14"X14"310F (2)
14"X14"340F (2)
18"X14"470F (2)
30"X26"1500F (2)
24"X14"590F (2)
24"X14"590F (2)
30"X14"700(2) F
30"X14"650(2) F
30"X14"690(2) F
8"ø165 A
16"x16"SA
24"x10"RA
22"X22"165B
30"x14"RA
10"X6"90(2) F
10"X6"100(2) F
10"X6"90F (2)
10"X6"100F (2)
22"X22"100B
22"X22"90B
22"X22"100 B
22"X22"90B
18"x14"SA
42"x26"RA
48"X30"2790(2) F
42"x26"RA
72"x26"RA
3
4
7
7
7
7
8
4
22"X22"200 B
24"x10"RA
22"X22"200 B
24"x10"RA
38"X22"1500 FT
3-02TF
38"X22"1500F (2)
9
CD
CD CD
CD
111
13
12
18"X10"530(2) F
18"X10"530(2) F
12"x10"RA
16
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN02/07/14DESIGN DEVELOPMENT04/04/1480% CD SET / PERMIT SET05/02/14100% CD SET
CSM WELCOMECENTER
M2.20
SECOND AND THIRDFLOORMECHANICAL PLAN
COLORADO SCHOOL OF MINESGOLDEN, CO
1219
1/8" = 1'-0"1 03 - SECOND FLOOR LEVEL 1/8" MECHANICAL PLAN 1/8" = 1'-0"2 04 - THIRD FLOOR LEVEL 1/8" MECHANICAL PLAN
KEYNOTESKey
Value Keynote Text
1 PROVIDE 90X40 OPENING IN RETURNAIR RISER. PROVIDE WELDED WIREMESH OVER DUCT END.
3 MOUNT BACK-TO-BACK RETURNGRILLES BELOW CEILING AT 7'-4" TOBOTTOM OF GRILLE. PROVIDECONNECTING DUCT IN WALL.
4 MOUNT RETURN DUCT ABOVECEILING. PROVIDE WIRE MESHSCREEN OVER DUCT END.
7 PROVIDE RETURN AIR TRANSFERBOOT THROUGH WALL IN PLENUMWITH ELBOWS UP AS INDICATED.PROVIDE WIRE MESH OVER BOTHOPEN DUCT ENDS.
8 PROVIDE GRILLES IN PLENUM FORRETURN AIR PATH THROUGH PLENUMWALL.
9 MOUNT FAN ABOVE SA DUCT INPLENUM. FAN DISCHARGE SHALL NOTBE DIRECTED AT SUPPLY AIR DUCT.
11 PROVIDE 36X40 OPENING IN RETURNAIR RISER. PROVIDE WELDED WIREMESH OVER DUCT END.
12 PROVIDE 32X36 OPENING IN ROOFSTRUCTURE SUCH THAT AHU ROOFCURB ABOVE IS OPEN TO THE LEVEL 3PLENUM. COORDINATE ROOFOPENING WITH STRUCTURAL.
13 MOUNT GRILLE BELOW RETURN AIRDUCT IN PLENUM.
16 MOUNT BACK-TO-BACK RETURNGRILLES BELOW RETURN AIR DUCT INPLENUM. PROVIDE CONNECTINGDUCT IN WALL.
GENERAL NOTES:1. THE DRAWINGS ARE DIAGRAMMATIC INNATURE. THE CONTRACTOR ISRESPONSIBLE FOR ALL OFFSETS,TRANSITIONS, ELBOWS, ETC. ASREQUIRED IN DUCTWORK, PIPING,SUPPORTS, ETC. TO COMPLETE THEWORK IN A CLEAN FUNCTIONALINSTALLATION THAT IS FULLYCOORDINATED WITH ALL OTHERTRADES. ANY PRICING EFFORT SHALLTAKE THESE FACTORS INTO ACCOUNT.
2. MAINTAIN A MINIMUM OF 25'-0"SEPARATION FROM OUTSIDE AIRINTAKES TO TERMINATIONS OFEXHAUST, COMBUSTION AIR, PLUMBINGVENTS, ETC. AS REQUIRED BY CODE.
3. COORDINATE EQUIPMENTHOUSEKEEPING PAD DIMENSIONS ANDLAYOUT WITH THE GENERALCONTRACTOR BASED ON FINALEQUIPMENT SIZES.
4. PROVIDE MANUAL BALANCE DAMPERSIN ALL SUPPLY DUCT BRANCH TAPSDOWNSTREAM OF VAV BOXES.
5. PROVIDE MANUAL BALANCE DAMPERSIN ALL EXHAUST DUCT BRANCH TAPS.
6. PROVIDE "Z" BOOT TRANSFER DUCTSIN FULL HEIGHT WALLS IN AREAS WHEREA PLENUM RETURN SYSTEM IS UTILIZED.BOOTS SHALL BE SIZED TO MAINTAIN AMAXIMUM OF 400 FPM.
7. COORDINATE SPACE TEMPERATURESENSORS AND THERMOSTATLOCATIONS TO ALIGN VERTICALLY WITHLIGHT SWITCHES. MOUNT AT 60" AFF.
8. TEMPERATURE CONTROLSCONTRACTOR SHALL SUBMIT PLANSINDICATING ALL SPACE TEMPERATURESENSORS, T-STATS, HUMIDITYSENSORS, ETC. AS PART OF SUBMITTALPROCESS FOR A/E REVIEW.
9. PROVIDE REMOTE REGULATORS FORMANUAL BALANCE DAMPERS ABOVEACCESSIBLE CEILINGS.
4-01EF
38"x94"RA
38"x89"SA
3
4
5
7
8
9
D E F
6
10
C GB
4-01AHU
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN02/07/14DESIGN DEVELOPMENT04/04/1480% CD SET / PERMIT SET05/02/14100% CD SET
CSM WELCOMECENTER
M2.30
ROOF LEVELMECHANICAL PLAN
COLORADO SCHOOL OF MINESGOLDEN, CO
1219
1/8" = 1'-0"1 05 - ROOF LEVEL 1/8" MECHANICAL PLAN
KEYNOTESKey
Value Keynote Text
GENERAL NOTES:1. THE DRAWINGS ARE DIAGRAMMATIC INNATURE. THE CONTRACTOR ISRESPONSIBLE FOR ALL OFFSETS,TRANSITIONS, ELBOWS, ETC. ASREQUIRED IN DUCTWORK, PIPING,SUPPORTS, ETC. TO COMPLETE THEWORK IN A CLEAN FUNCTIONALINSTALLATION THAT IS FULLYCOORDINATED WITH ALL OTHERTRADES. ANY PRICING EFFORT SHALLTAKE THESE FACTORS INTO ACCOUNT.
2. MAINTAIN A MINIMUM OF 25'-0"SEPARATION FROM OUTSIDE AIRINTAKES TO TERMINATIONS OFEXHAUST, COMBUSTION AIR, PLUMBINGVENTS, ETC. AS REQUIRED BY CODE.
3. COORDINATE EQUIPMENTHOUSEKEEPING PAD DIMENSIONS ANDLAYOUT WITH THE GENERALCONTRACTOR BASED ON FINALEQUIPMENT SIZES.
4. PROVIDE MANUAL BALANCE DAMPERSIN ALL SUPPLY DUCT BRANCH TAPSDOWNSTREAM OF VAV BOXES.
5. PROVIDE MANUAL BALANCE DAMPERSIN ALL EXHAUST DUCT BRANCH TAPS.
6. PROVIDE "Z" BOOT TRANSFER DUCTSIN FULL HEIGHT WALLS IN AREAS WHEREA PLENUM RETURN SYSTEM IS UTILIZED.BOOTS SHALL BE SIZED TO MAINTAIN AMAXIMUM OF 400 FPM.
7. COORDINATE SPACE TEMPERATURESENSORS AND THERMOSTATLOCATIONS TO ALIGN VERTICALLY WITHLIGHT SWITCHES. MOUNT AT 60" AFF.
8. TEMPERATURE CONTROLSCONTRACTOR SHALL SUBMIT PLANSINDICATING ALL SPACE TEMPERATURESENSORS, T-STATS, HUMIDITYSENSORS, ETC. AS PART OF SUBMITTALPROCESS FOR A/E REVIEW.
9. PROVIDE REMOTE REGULATORS FORMANUAL BALANCE DAMPERS ABOVEACCESSIBLE CEILINGS.
1
1.8
2
3
4
5
7
8
9
D E F
6
10
CA GB
B-02FPVAV
B-01FPVAVT
B-01CUH
T
B-01FCU
5
1 1/4"øHWS4"øHWS4"øHWR
4"øCHS
4"øCHR
3/4"øHWR3/4"øHWS 3/4"øHWR
3/4"øHWS
3/4"øCHR3/4"øCHS
4"øCHR4"øCHS
4"øHWR4"øHWS
3/4"øHWS3/4"øHWR
14
1
1.8
2
3
4
5
7
8
9
D E F
6
10
CA GB
1-02FPVAV
1-01FPVAV
1-04FPVAV
1-05FPVAV
1-06FPVAV
1-07FPVAV
1-08FPVAV
1-09FPVAV
1-10FPVAV
1-11FPVAV
1-12FPVAV
1-13FPVAV
1-14FPVAV
1-15FPVAV
1-03CUH
1-02CUH
1-01CUH
1-01FCU
1-03FPVAV
3/4"øHWR3/4"øHWS
3/4"øHWS3/4"øHWR
3/4"øHWR3/4"øHWS 3/4"øHWR
3/4"øHWS
1"øHWS1"øHWR
3/4"øHWS3/4"øHWR
1 1/2"øHWS1 1/2"øHWR
3/4"øHWS3/4"øHWR
1 1/4"øHWS1 1/4"øHWR
1"øHWS1"øHWR
3/4"øHWS3/4"øHWR
3/4"øHWR3/4"øHWS
2"øHWR
2"øHWS
3/4"øHWS3/4"øHWR
3/4"øHWR3/4"øHWS
3/4"øHWR3/4"øHWS
3/4"øHWR3/4"øHWS
1"øHWS1"øHWR
3/4"øHWS3/4"øHWR 3/4"øHWR
3/4"øHWS
3/4"øHWR3/4"øHWS
3/4"øHWS3/4"øHWR
1 1/4"øHWS1 1/4"øHWR
3/4"øHWS3/4"øHWR
1 1/2"øHWS1 1/2"øHWR
3/4"øHWR3/4"øHWS
1"øCHR1"øCHS
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN02/07/14DESIGN DEVELOPMENT04/04/1480% CD SET / PERMIT SET05/02/14100% CD SET
CSM WELCOMECENTER
M3.10
BASEMENT ANDFIRST FLOORPIPING PLAN
COLORADO SCHOOL OF MINESGOLDEN, CO
1219
1/8" = 1'-0"1 01 - BASEMENT LEVEL 1/8" PIPING PLAN 1/8" = 1'-0"2 02 - FIRST FLOOR LEVEL 1/8" PIPING PLAN
KEYNOTESKey
Value Keynote Text
5 CAMPUS STEAM AND CHILLED WATERENTRY POINT FROM UTILITY TUNNEL.RE: DRAWING P1.00 AND MECHANICALDIAGRAMS.
6 PROVIDE OPEN ENDED DUCTTHROUGH WALL IN PLENUM WTIHELBOW UP AS INDICATED. PROVIDEWIRE MESH OVER BOTH OPEN DUCTENDS.
8 PROVIDE GRILLES IN PLENUM FORRETURN AIR PATH THROUGH PLENUMWALL.
14 PIPING TO ELBOW DOWN BELOWSANITARY LINE. RE: PLUMBINGDRAWINGS.
GENERAL NOTES:1. THE DRAWINGS ARE DIAGRAMMATIC INNATURE. THE CONTRACTOR ISRESPONSIBLE FOR ALL OFFSETS,TRANSITIONS, ELBOWS, ETC. ASREQUIRED IN DUCTWORK, PIPING,SUPPORTS, ETC. TO COMPLETE THEWORK IN A CLEAN FUNCTIONALINSTALLATION THAT IS FULLYCOORDINATED WITH ALL OTHERTRADES. ANY PRICING EFFORT SHALLTAKE THESE FACTORS INTO ACCOUNT.
2. MAINTAIN A MINIMUM OF 25'-0"SEPARATION FROM OUTSIDE AIRINTAKES TO TERMINATIONS OFEXHAUST, COMBUSTION AIR, PLUMBINGVENTS, ETC. AS REQUIRED BY CODE.
3. COORDINATE EQUIPMENTHOUSEKEEPING PAD DIMENSIONS ANDLAYOUT WITH THE GENERALCONTRACTOR BASED ON FINALEQUIPMENT SIZES.
4. PROVIDE MANUAL BALANCE DAMPERSIN ALL SUPPLY DUCT BRANCH TAPSDOWNSTREAM OF VAV BOXES.
5. PROVIDE MANUAL BALANCE DAMPERSIN ALL EXHAUST DUCT BRANCH TAPS.
6. PROVIDE "Z" BOOT TRANSFER DUCTSIN FULL HEIGHT WALLS IN AREAS WHEREA PLENUM RETURN SYSTEM IS UTILIZED.BOOTS SHALL BE SIZED TO MAINTAIN AMAXIMUM OF 400 FPM.
7. COORDINATE SPACE TEMPERATURESENSORS AND THERMOSTATLOCATIONS TO ALIGN VERTICALLY WITHLIGHT SWITCHES. MOUNT AT 60" AFF.
8. TEMPERATURE CONTROLSCONTRACTOR SHALL SUBMIT PLANSINDICATING ALL SPACE TEMPERATURESENSORS, T-STATS, HUMIDITYSENSORS, ETC. AS PART OF SUBMITTALPROCESS FOR A/E REVIEW.
9. PROVIDE REMOTE REGULATORS FORMANUAL BALANCE DAMPERS ABOVEACCESSIBLE CEILINGS.
1.8
2
3
4
5
7
8
9
D E F
6
10
CA GB
2-01FPVAV
2-02FPVAV
2-03FPVAV
2-04FPVAV
2-05FPVAV2-06
FPVAV
2-08FPVAV
2-09FPVAV
2-07FPVAV
2-01FCU
3/4"øHWR3/4"øHWS
3/4"øHWR3/4"øHWS
1"øHWR1"øHWS
3/4"øHWS3/4"øHWR
3/4"øHWR3/4"øHWS3/4"øHWR
3/4"øHWS
3/4"øHWR3/4"øHWS
3/4"øHWS3/4"øHWR
3/4"øHWS 3/4"øHWR
3/4"øHWS3/4"øHWR
1 1/4"øHWR1 1/4"øHWS
1 1/4"øHWR
1 1/4"øHWS
3/4"øHWS3/4"øHWR
1"øCHR1"øCHS
3
4
5
7
8
9
D E F
6
10
C
3-05FPVAV
3-06FPVAV
3-07FPVAV
3-04FPVAV
3-03FPVAV
3-02FPVAV
3-01FPVAV
3-01VAV
3-02VAV
3-03VAV
3-04VAV
3-01FCU
3-01UH
3/4"øHWS3/4"øHWR
3/4"øHWR3/4"øHWS
3/4"øHWS3/4"øHWR
3/4"øHWS3/4"øHWR
3/4"øHWR3/4"øHWS
3/4"øHWS3/4"øHWR
3/4"øHWR3/4"øHWS 3/4"øHWS
3/4"øHWR
1"øHWR1"øHWS
3/4"øHWR3/4"øHWS
3/4"øHWR3/4"øHWS
3/4"øHWS3/4"øHWR
1 1/4"øHWS1 1/4"øHWR
3/4"øHWS3/4"øHWR
3/4"øHWS3/4"øHWR
3/4"øHWS3/4"øHWR
1 1/2"øHWR1 1/2"øHWS
1"øCHR1"øCHS
1 1/2"øHWS1 1/2"øHWR
3/4"øHWS3/4"øHWR
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN02/07/14DESIGN DEVELOPMENT04/04/1480% CD SET / PERMIT SET05/02/14100% CD SET
CSM WELCOMECENTER
M3.20
SECOND AND THIRDFLOOR PIPING PLAN
COLORADO SCHOOL OF MINESGOLDEN, CO
1219
KEYNOTESKey
Value Keynote Text
3 MOUNT BACK-TO-BACK RETURNGRILLES BELOW CEILING AT 7'-4" TOBOTTOM OF GRILLE. PROVIDECONNECTING DUCT IN WALL.
4 MOUNT RETURN DUCT ABOVECEILING. PROVIDE WIRE MESHSCREEN OVER DUCT END.
7 PROVIDE RETURN AIR TRANSFERBOOT THROUGH WALL IN PLENUMWITH ELBOWS UP AS INDICATED.PROVIDE WIRE MESH OVER BOTHOPEN DUCT ENDS.
8 PROVIDE GRILLES IN PLENUM FORRETURN AIR PATH THROUGH PLENUMWALL.
GENERAL NOTES:1. THE DRAWINGS ARE DIAGRAMMATIC INNATURE. THE CONTRACTOR ISRESPONSIBLE FOR ALL OFFSETS,TRANSITIONS, ELBOWS, ETC. ASREQUIRED IN DUCTWORK, PIPING,SUPPORTS, ETC. TO COMPLETE THEWORK IN A CLEAN FUNCTIONALINSTALLATION THAT IS FULLYCOORDINATED WITH ALL OTHERTRADES. ANY PRICING EFFORT SHALLTAKE THESE FACTORS INTO ACCOUNT.
2. MAINTAIN A MINIMUM OF 25'-0"SEPARATION FROM OUTSIDE AIRINTAKES TO TERMINATIONS OFEXHAUST, COMBUSTION AIR, PLUMBINGVENTS, ETC. AS REQUIRED BY CODE.
3. COORDINATE EQUIPMENTHOUSEKEEPING PAD DIMENSIONS ANDLAYOUT WITH THE GENERALCONTRACTOR BASED ON FINALEQUIPMENT SIZES.
4. PROVIDE MANUAL BALANCE DAMPERSIN ALL SUPPLY DUCT BRANCH TAPSDOWNSTREAM OF VAV BOXES.
5. PROVIDE MANUAL BALANCE DAMPERSIN ALL EXHAUST DUCT BRANCH TAPS.
6. PROVIDE "Z" BOOT TRANSFER DUCTSIN FULL HEIGHT WALLS IN AREAS WHEREA PLENUM RETURN SYSTEM IS UTILIZED.BOOTS SHALL BE SIZED TO MAINTAIN AMAXIMUM OF 400 FPM.
7. COORDINATE SPACE TEMPERATURESENSORS AND THERMOSTATLOCATIONS TO ALIGN VERTICALLY WITHLIGHT SWITCHES. MOUNT AT 60" AFF.
8. TEMPERATURE CONTROLSCONTRACTOR SHALL SUBMIT PLANSINDICATING ALL SPACE TEMPERATURESENSORS, T-STATS, HUMIDITYSENSORS, ETC. AS PART OF SUBMITTALPROCESS FOR A/E REVIEW.
9. PROVIDE REMOTE REGULATORS FORMANUAL BALANCE DAMPERS ABOVEACCESSIBLE CEILINGS.
1/8" = 1'-0"1 03 - SECOND FLOOR LEVEL 1/8" PIPING PLAN 1/8" = 1'-0"2 04 - THIRD FLOOR LEVEL 1/8" PIPING PLAN
3
4
5
7
8
9
D E F
6
10
C GB
2
4-01AHU
15
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN02/07/14DESIGN DEVELOPMENT04/04/1480% CD SET / PERMIT SET05/02/14100% CD SET
CSM WELCOMECENTER
M3.30
ROOF LEVEL PIPINGPLAN
COLORADO SCHOOL OF MINESGOLDEN, CO
1219
KEYNOTESKey
Value Keynote Text
2 CWP-3 AND HWP-3 IN AHU PIPE CHASE.REFER TO MECHANICAL DETAILS.
15 ROUTE PIPING FROM BELOWTHROUGH AHU ROOF CURB WALL INTOPIPE CHASE.
GENERAL NOTES:1. THE DRAWINGS ARE DIAGRAMMATIC INNATURE. THE CONTRACTOR ISRESPONSIBLE FOR ALL OFFSETS,TRANSITIONS, ELBOWS, ETC. ASREQUIRED IN DUCTWORK, PIPING,SUPPORTS, ETC. TO COMPLETE THEWORK IN A CLEAN FUNCTIONALINSTALLATION THAT IS FULLYCOORDINATED WITH ALL OTHERTRADES. ANY PRICING EFFORT SHALLTAKE THESE FACTORS INTO ACCOUNT.
2. MAINTAIN A MINIMUM OF 25'-0"SEPARATION FROM OUTSIDE AIRINTAKES TO TERMINATIONS OFEXHAUST, COMBUSTION AIR, PLUMBINGVENTS, ETC. AS REQUIRED BY CODE.
3. COORDINATE EQUIPMENTHOUSEKEEPING PAD DIMENSIONS ANDLAYOUT WITH THE GENERALCONTRACTOR BASED ON FINALEQUIPMENT SIZES.
4. PROVIDE MANUAL BALANCE DAMPERSIN ALL SUPPLY DUCT BRANCH TAPSDOWNSTREAM OF VAV BOXES.
5. PROVIDE MANUAL BALANCE DAMPERSIN ALL EXHAUST DUCT BRANCH TAPS.
6. PROVIDE "Z" BOOT TRANSFER DUCTSIN FULL HEIGHT WALLS IN AREAS WHEREA PLENUM RETURN SYSTEM IS UTILIZED.BOOTS SHALL BE SIZED TO MAINTAIN AMAXIMUM OF 400 FPM.
7. COORDINATE SPACE TEMPERATURESENSORS AND THERMOSTATLOCATIONS TO ALIGN VERTICALLY WITHLIGHT SWITCHES. MOUNT AT 60" AFF.
8. TEMPERATURE CONTROLSCONTRACTOR SHALL SUBMIT PLANSINDICATING ALL SPACE TEMPERATURESENSORS, T-STATS, HUMIDITYSENSORS, ETC. AS PART OF SUBMITTALPROCESS FOR A/E REVIEW.
9. PROVIDE REMOTE REGULATORS FORMANUAL BALANCE DAMPERS ABOVEACCESSIBLE CEILINGS.
1/8" = 1'-0"1 05 - ROOF LEVEL 1/8" PIPING PLAN
SS
S
1.8
2
3
A
2CWP
1CWP
1PHX
1AS
2AS
2HWP
1HWP
1ET
1GP
2ET
2GP
1SHX
5
4CWP
5CWP
2M4.10
3M4.10
01 - BASEMENTLEVEL89' - 0"
02 - FIRST FLOORLEVEL
100' - 0"
AA.9
01 - BASEMENTLEVEL89' - 0"
02 - FIRST FLOORLEVEL
100' - 0"
A
1SHX
1PHX
1CWP
1AS
5CWP
4CWP
01 - BASEMENTLEVEL89' - 0"
02 - FIRST FLOORLEVEL
100' - 0"
23
01 - BASEMENTLEVEL89' - 0"
02 - FIRST FLOORLEVEL
100' - 0"
23
1GP
1ET
1HWP
2AS
2HWP
1CWP
2CWP
1AS
1PHX
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN02/07/14DESIGN DEVELOPMENT04/04/1480% CD SET / PERMIT SET05/02/14100% CD SET
CSM WELCOMECENTER
M4.10
ENLARGEDMECHANICALPLANS
COLORADO SCHOOL OF MINESGOLDEN, CO
1219
1/4" = 1'-0"1 01 - BASEMENT LEVEL 1/4" MECHANICAL PLAN
KEYNOTESKey
Value Keynote Text
5 CAMPUS STEAM ANDCHILLED WATER ENTRYPOINT FROM UTILITYTUNNEL. RE: DRAWINGP1.00 AND MECHANICALDIAGRAMS.
1/4" = 1'-0"2 01- BASEMENT LEVEL 1/4" MECHANICAL SECTION 1
1/4" = 1'-0"3 01- BASEMENT LEVEL 1/4" MECHANICAL SECTION 2
GENERAL NOTE:1. RE: DRAWING M6.01 FOR PIPING LINE SIZES INMECHANICAL ROOM
WALL-MOUNTED FAN COIL UNITS:
MISCELLANEOUS DDC CONTROL:
MISCELLANEOUS NON-DDC CONTROL:
SEQUENCE OF OPERATION GENERAL NOTES:
T
CONTROL LEGEND
3 CABINET/UNIT HEATER CONTROLNONE
2 EXHAUST FAN CONTROL (TEMPERATURE)NONE
1 EXHAUST FAN CONTROL (TYPICAL)NONE
5
WALL MOUNTEDFAN COIL UNIT CONTROLNONE
4 TUNNEL EXHAUST FAN CONTROLNONE
COND
DP
CSEN
DODI
BDD
CD
CHSCHR
CCC
AOAI
DIFFERENTIAL PRESSURE SWITCHDIGITAL OUTPUT
CURRENT SENSORDIGITAL INPUT
CHILLED WATER RETURNCHILLED WATER SUPPLYCONDENSATE OVERFLOW
BACKDRAFT DAMPER
COOLING COILCONTROL DAMPER
CONTROLLER
ANALOG INPUTANALOG OUTPUT
TEMPERATURE TRANSMITTER W/AVERAGING BULB
WET BULB TEMPERATURE TRANSMITTER
MOTORIZED CONTROL
HOT WATER SUPPLYHOT WATER RETURN
PNEUMATIC ELECTRIC SWITCH
INTERLOCK RELAY
PREHEAT COIL
OUTSIDE AIRMINIMUM
M
HWRHWS
FILTER ASSEMBLY
HIGH LIMIT HUMIDITY SWITCHHUMIDITY TRANSMITTER
FLOW TRANSDUCER
FIRE ALARM CONTROL PANEL
HEATING COIL
FREEZESTAT
HT
HCHH
F
FT
FR
FAN COIL UNIT
FLOW SWITCH
FCUFACP
FS
VELOCITY SENSOR
THERMOSTAT
VARIABLE FREQUENCY DRIVE
TEMPERATURE TRANSMITTER
VSWBT
VVFD
T
TTABTT
VALVE
STATIC PRESSURE TRANSMITTERSUPPLY FANSMOKE DETECTOR (BY ELECTRICAL)SUPPLY AIR
RETURN FANRETURN AIR
SPACE TEMPERATURE SENSOR
SWITCHING RELAY
SFSPTSR
SSASD
RARF
P-EPHC
OAMIN
FIREFIGHTER'S SMOKE CONTROL PANELFSCP
DESCRIPTIONABBR DESCRIPTIONABBR DESCRIPTIONABBR
PRESSURE TRANSMITTERPT
TEMPERATURE SENSORTS
FLOW METERFM
BTU BTU METER
IR
HC
S/S
SF
HWSHWR
TEMPERATURE
T
SPACE
SA
THERMOSTAT SHALL CYCLE FAN & OPEN HEATING WATER VALVE OR ENERGIZE ELECTRIC HEAT TO MAINTAINSPACE SETPOINT.
"SUMMER" SWITCH,WHERE APPLICABLE
S
WALL OR UNIT MOUNTEDAS INDICATED
ENERGIZE EXHAUST FAN UPON RISE IN SPACE TEMPERATURE ABOVE SETPOINT.
AI
SPACETEMPERATURE
DO
S/S
CSEN
DI
EA
T
FAN SHALL BE ENERGIZED VIA BMS SCHEDULE. MOTORIZED DAMPER (WHEREAPPLICABLE) SHALL BE INTERLOCKED WITH FAN AND SHALL OPEN WHEN FANIS ENERGIZED. MOTORIZED DAMPER SHALL CLOSE WHEN FAN ISDE-ENERGIZED.
CSEN
S/S
DO
EA
M
DO
MOTORIZED DAMPERWHERE INDICATED INMECHANICAL SCHEDULES
SA
DI
CSEN
SF
CC
AO
CHR
CHS
RA
AI ROOM THERMOSTAT
DO
S/S
FAI OVERFLOW SWITCH
A. OCCUPIED MODE:
1. WHEN THE FCU IS IN THE OCCUPIED MODE, THE SUPPLY FAN SHALL OPERATECONTINUOUSLY AND THE COOLING VALVE SHALL MODULATE TO MAINTAIN SPACESETPOINT.
C. FAN SAFETY CONTROLS:
1. DE-ENERGIZE THE SUPPLY FAN WHENEVER THE OVERFLOW SENSOR HAS TRIPPEDOR THE SUPPLY FAN STATUS INDICATES A FAILURE (AFTER A TWO MINUTE DELAY).
2. ALARM THE BMS WITH AN APPROPRIATE ALARM MESSAGE.
D. ALARMS:
1. ALARM THE TIME, FCU DESIGNATION AND DURATION OF ALL FCU OVER-RIDES.
ENERGIZE EXHAUST FAN UPON RISE IN SPACE TEMPERATURE ABOVE SETPOINT OR A SPACE OXYGEN LEVELDROP BELOW A LOW LIMIT OF 20.2%. ALARM BMS IF SPACE OXYGEN LEVEL DROPS BELOW 19.5%. ALARM BMSAND GENERATE AUDIBLE ALARM AT SPACE OXYGEN LEVEL SENSOR UPON DETECTION OF OXYGEN LEVEL LOWLIMIT.
AI
SPACETEMPERATURE
DO
S/S
CSEN
DI
EA
T
AI
SPACEOXYGEN LEVEL
O2
DI
2. PROVIDE ALARM WHEN FAN IS COMMANDED ON AND THE FAN STATUS IS OFF FOR MORE THAN 30 SECONDS.3. PROVIDE ALARM WHEN SPACE TEMPERATURE RISES ABOVE 80 DEG.
ALARMSCRITICAL ALARM CONDITIONS24/7
ALARMSM-F 7A-7P
ALARMS7A-7P
ALARMSOSAT<45F
JACE IS DOWN
BUILDING LOW TEMP(ANY ZONE <45F)
HIGH WATER ALARM
ELEVATOR, TUNNEL
(1 POINT FOR ANY OF THEFOLLOWING PUMPS) SEWAGE,
AHU FAILURE(1 POINT FOR EITHER OF THE
SUPPLY FAN OR RETURN
FOLLOWING)
FAN FAIL (CMD VS STATUS) ORLOW STATIC PRESSURE
HEATING WATER SYSTEM(1 POINT FOR ANY OF THEFOLLOWING CONDITIONS)
HWP-1 AND HWP-2 FAILURE
HWP-1 OR HWP-2 FAILURE
HWS TEMP - 10F BELOW SETPOINT (WHEN HW SYSTEM ISENABLED
TUNNEL EXHAUST SYSTEMFAN FAILURE (CMD VS STATUS)
X
XX
X
X
XX
X
X
X
A. PUMPS SHALL OPERATE PER OTHER APPLICABLE CONTROL SECTIONS. BMS SHALL MONITORALL PUMPS INCLUDING GLYCOL FEED PUMPS. DOMESTIC HOT WATER RECIRCULATION PUMP(S)ARE EXCLUDED.
B. REFERENCE MECHANICAL EQUIPMENT SCHEDULES (ESPECIALLY "FANS") FOR ADDITIONALCONTROL SEQUENCES.
C. FANS1. PROVIDE START, STOP, AND STATUS FOR ALL FANS U.N.O.2. PROVIDE STATUS ONLY FOR FANS OPERATED VIA LINE VOLTAGE THERMOSTAT.3. RE: SCHEDULES FOR ADDITIONAL REQUIREMENTS.
H. DX SPLIT SYSTEM AND CRAC UNIT CONTROL1. UNITS SHALL OPERATE UNDER THEIR OWN SELF CONTAINED CONTROLS TO MAINTAIN THE
SPACE TEMPERATURE AND HUMIDITY SETPOINTS.2. THE BMS SHALL INTERFACE WITH THE UNIT CONTROLS TO MONITOR SPACE TEMPERATURE,
EQUIPMENT STATUS AND EQUIPMENT FAILURE ALARMS.
J. EXHAUST AND INTAKE DAMPERS1. RELIEF AND INTAKE LOCATIONS THAT CONTAIN MOTORIZED DAMPERS SHALL INTERLOCK THE
POSITION OF THE DAMPER WITH THE OPERATION OF ITS ASSOCIATED EQUIPMENT: WHEN THEEQUIPMENT IS ENABLED, THE DAMPER SHALL BE OPEN, WHEN THE EQUIPMENT IS DISABLED,THE DAMPER SHALL BE CLOSED. ALL DAMPERS TO BE FAST-ACTING OR AN EQUIPMENTDELAY SHALL BE PROVIDED TO PREVENT FULL AIRFLOW PRIOR TO DAMPER REACHING FULLOPEN POSITION. FOR INTAKE DAMPERS SERVING MULTIPLE FAN COILS, ANY FAN COILENERGIZED ON COMMON DUCT RUN SHALL OPEN OR CLOSE DAMPER.
K. HIGH LEVEL ALARMS1. PROVIDE HIGH LEVEL ALARMS IN SUMPS FOR THE FOLLOWING:
1.1. BUILDING SEWAGE SUMP1.2. BUILDING ELEVATOR SUMP1.3. TUNNEL SUMP
L. EXTERIOR LIGHTING1. PROVIDE DDC CONTROL OF EXTERIOR LIGHTING INCLUDING PHOTOCELL CONTROL.
M. ENERGY DEMAND AND CONSUMPTION1. PROVIDE DDC MONITORING AND TRENDING OF THE FOLLOWING:
1.1. BUILDING ELECTRICITY DEMAND AND CONSUMPTION.1.2. BUILDING CHILLED WATER DEMAND AND CONSUMPTION.1.3. BUILDING STEAM DEMAND AND CONSUMPTION.
2. PROVIDE TRENDING OF ENERGY CONSUMPTION FOR EACH UTILITY INCLUDING DATASTORAGE FOR A MINIMUM OF THREE YEARS.
N. CRITICAL ALARMS1. ALL ANALOG VALUES SHALL GENERATE AN ALARM AT THE BMS IF THEY ARE OUTSIDE OF
ACCEPTABLE CONTROL RANGE. FOR EXAMPLE, AHU SUPPLY AIR TEMPERATURE +/-10 DEG FFOR 15 MINUTES, DUCT STATIC PRESSURE +/-0.25 INCHES WC FOR 15 MINUTES, SPACETEMPERATURE +/-4 DEG F OF HEATING AND COOLING SETPOINTS, ETC. ALL SETPOINTSSHALL BE ADJUSTABLE.
2. THE OPERATION OF OPERATION OF MECHANICAL SYSTEMS IS DEEMED CRITICAL TO THEOPERATION OF THE BUILDING. IN THE EVENT OF A CRITICAL SYSTEM FAILURE, TELEPHONEDIALERS ARE EMPLOYED TO NOTIFY CSM PERSONNEL OF SPECIFIC FAILURES. CERTAINCRITICAL ALARMS CALL OUT 24/7,OTHERS CALL OUT DURING SCHEDULED TIMES OF DAY, ANDOTHERS CALL OUT BASED ON OUTSIDE AIR TEMPERATURE OR OTHER CONDITIONS.
3. TELEPHONE DIALERS ARE LOCATED IN THE HEATING PLANT BUILDING. THE TEMPERATURECONTROLS CONTRACTOR IS RESPONSIBLE FOR PROGRAMMING THE LOGIC REQUIRED TOIDENTIFY THESE SYSTEM FAILURES. LINKING OF THESE CRITICAL ALARMS TO THE LOGIC INTHE HEATING PLANT JACE AS WELL AS MODIFICATIONS TO THE CRITICAL ALARM GRAPHICPAGE WILL ALSO BE REQUIRED. CSM WILL PROVIDE NEW DIALERS IF REQUIRED AND ALLHARDWARE NECESSARY FOR ACTIVATION OF THE INDIVIDUAL DIALER INPUTS. CSMPERSONNEL WILL PROVIDE SETUP OF THE DIALERS INCLUDING INDIVIDUAL DIALERMESSAGES AND TELEPHONE LIST PROGRAMMING. THE TEMPERATURE CONTROLSCONTRACTOR SHALL WORK WITH CSM PERSONNEL TO ACCOMPLISH CRITICAL ALARMPROGRAMMING.
4. REFER TO CRITICAL ALARM CONDITIONS TABLE FOR REQUIRED ALARMS.
A. CHEMICAL TREATMENT: PROVIDE REQUIRED FIELD WIRING INTERLOCKS
B. MISCELLANEOUS PUMPS: PUMPS SHALL OPERATE PER SCHEDULE AND DRAWINGS. FOREXAMPLE, RECIRCULATION PUMPS CYCLE TO MAINTAIN DHW TEMPERATURE.
GENERAL:
A. BMS CONTRACTOR SHALL COORDINATE ALL INTERFACE REQUIREMENTS.
B. ALTHOUGH EACH SEPARATE CONTROL DIAGRAM INDICATES AN OUTDOOR AIR TEMPERATURESENSOR AND OUTDOOR AIR HUMIDITY SENSOR, TC CONTRACTOR MAY UTILIZE ONE OF EACHSENSOR AS A COMMON INPUT TO THE SYSTEM. COORDINATE LOCATION WITHARCHITECT/ENGINEER PRIOR TO INSTALLATION.
C. PROVIDE INDIVIDUAL INPUTS OR OUTPUTS FOR EACH POINT LISTED IN THE POINTS LISTS.PROVIDE ANY ADDITIONAL POINTS NOT LISTED IN THE POINTS LIST, BUT REQUIRED TO MEETTHE SEQUENCES OF OPERATION, AT NO ADDITIONAL COST TO THE OWNER. ALL ANALOGOUTPUTS SHALL BE 4-20MA, 0-10VDC OR 0-20VDC UNLESS OTHERWISE INDICATED. AO=ANALOGOUTPUT, AI=ANALOG INPUT, DO=DIGITAL (BINARY) OUTPUT, DI=DIGITAL (BINARY) INPUT.
E. ALL SETPOINTS SHALL BE FULLY ADJUSTABLE AT THE OPERATOR WORKSTATION.
F. PROVIDE OVERRIDE CONTROL OF ALL POINTS AT THE OPERATOR WORKSTATION.
G. PROVIDE ZERO TO THREE HOUR (ADJ.) TIMED OVERRIDE IN A CENTRAL LOCATION TO PROVIDEAFTER-HOURS OVERRIDE OF THE AIR HANDLING UNIT AND VAV BOXES.
H. BMS/ATC CONTRACTOR IS RESPONSIBLE FOR UNDERSTANDING ALL LOCAL GOVERNMENTSTANDARDS. ANY MODIFICATIONS REQUIRED IN ORDER TO MEET THE LOCAL GOVERNMENTSTANDARDS AT A LATER DATE SHALL BE DONE AT NO ADDITIONAL COST TO THE OWNER OR THEPROJECT.
I. REFER TO THE SPECIFICATIONS FOR OPERATOR WORKSTATION REQUIREMENTS.
J. IN THE EVENT OF A POWER OUTAGE OR OTHER MALFUNCTION, THE CURRENTLY ENABLEDCONTROLS SEQUENCES SHALL BE MAINTAINED- RE: SPECIFICATIONS. IN ADDITION, CHILLEDWATER VALVES SHALL FAIL CLOSED AND HEATING WATER VALVES SHALL FAIL OPEN.
OCCUPANCY SCHEDULES:
K. THE FOLLOWING SPECIAL OCCUPANCY SCHEDULE TYPES ARE HEREBY DEFINED:
1. EVENT OCCUPANCY: BASED ON EVENTS SCHEDULED BY THE OPERATOR.
2. FULL OCCUPANCY: BASED ON DAYS WHEN THE FULL FACILITY WILL BE IN USE.
3. ANY COMBINATION OF THE ABOVE
L. ANY DEVICE UTILIZING ON/OFF CONTROL OR SCHEDULING SHALL BE CAPABLE OFBEING PROGRAMMED TO CONFORM TO ANY OF THESE SCHEDULES.
M. THE BMS SHALL STAGE AIR HANDLERS TO/FROM OCCUPIED MODE TO MINIMIZE SUDDENCHANGES IN SYSTEM FLOW REQUIREMENTS.
N. ALL SETPOINTS SHALL BE FULLY ADJUSTABLE AT THE OPERATOR WORKSTATION.
O. PROVIDE OVERRIDE CONTROL OF ALL POINTS AT THE OPERATOR WORKSTATION.
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN02/07/14DESIGN DEVELOPMENT04/04/1480% CD SET / PERMIT SET05/02/14100% CD SET
CSM WELCOMECENTER
M6.00
MECHANICALSCHEMATICS ANDCONTROLDIAGRAMS
COLORADO SCHOOL OF MINESGOLDEN, CO
1219
TS
AI DP
DICSEN
LOW LEVELALARM
DI
TS
DO
VFD
AO
DI
AIDI
CSEN
DO
VFD
AO
DI
AIDI
CSEN
AI
PT
FM
DIDO
DI
FS
AI
TT
AI
TT
TT
AI DP
LOWLEVELALARM
DI
AI
TT
FM
AI
FM
AI
DIDO
AI
TT
AI
TT
DO
VFD
AO
DI
AIDI
CSEN
DO
VFD
AO
DI
AIDI
CSEN
AI - CONDENSATE FLOW
FM
AI
TT
TS
TS
AI - FLOW MEASUREMENT
BTU
AI - SUPPLY TEMPERATUREAI - RETURN TEMPERATUREAI - ENERGY DEMANDAI - TOTALIZED ENERGY CONSUMPTION
PULSE - TOTALIZED CONDENSATE FLOW
DO
VFD
AO
DI
AIDI
CSEN
DO
VFD
AO
DI
AIDI
CSEN
AIAO
PT
AI
PT
AI
AIAO
AIAO
DI
DP
AI
PT
AI
AI - FLOW MEASUREMENT
BTU
AI - SUPPLY TEMPERATUREAI - RETURN TEMPERATUREAI - ENERGY DEMANDAI - TOTALIZED ENERGY CONSUMPTION
HWP2
HWP1
SHX1
PHX1
CHP1
CHP2
CHP4
CHP5
2 HEATING WATER PIPING SCHEMATIC/CONTROL DIAGRAMNO SCALE
1 CHILLED WATER PIPING SCHEMATIC/CONTROL DIAGRAMNO SCALE
2A HEATING WATER SYSTEM SEQUENCE OF OPERATIONSNO SCALE1A CHILLED WATER SYSTEM SEQUENCE OF OPERATIONS
NO SCALE
1
2
3
4
5
4
4
2
5
1
3
HWS
HWR
TO GLYCOLFILL ASSEMBLYRE:DETAIL
CONNECT TOSIDE OF PIPING
TO EXPANSIONTANKSRE:DETAIL
HIGH CAPACITYAUTOMATIC AIRVENT B&G MODEL 107 A
AIR SEPARATOR
PIPE FULL SIZETO NEARESTFLOOR DRAIN
4"
4"
CHEMICAL POTFEEDER
COIL
100 GPM100 GPM
MPS
MPR
200 GPM140/180F
2147 LBS/HR85 PSIG
4"
4"
2"
3"
CHS
CHR
TO GLYCOLFILL ASSEMBLYRE:DETAIL
CONNECT TOSIDE OF PIPING
TO EXPANSIONTANKSRE:DETAIL
HIGH CAPACITYAUTOMATIC AIRVENT B&G MODEL 107 A
AIR SEPARATOR
PIPE FULL SIZETO NEARESTFLOOR DRAIN
CHEMICAL POTFEEDER
COIL
PCHS
PCHR
BUILDING MECHANICAL ROOMCAMPUS TUNNEL
200 GPM57/44F
260 GPM42/52F
4"
4"
4"
4"
100 GPM
4"4"
100 GPM
4"
3" 3" 3" 3"
BUILDING MECHANICAL ROOMCAMPUS TUNNEL
(85 PSIG)
VERTICAL FLOODEDSTEAM HEATEXCHANGER SKID
FLANGED
3" 3" 3" 3"
GLYCOL TANK.
PRESSURE RELIEF VALVESET AT 90 PSI PIPE TO
GLYCOL TANK.
PRESSURE RELIEF VALVESET AT 60 PSI PIPE TO
FLANGE TO HWS MAIN. RE:
1-1/4" STABILIZING LINE.MINIMUM 30' LENGTH FROM
MANUFACTURER'S INSTALLATIONRECOMMENDATIONS.
1"
3/4"
DIAGRAM KEY NOTES:
HEAT EXCHANGER PACKAGE BY MANUFACTURER. INSTALL UNDER DIVISION 23.
1/2" AIR VENT FURNISHED BY HEAT EXCHANGER MANUFACTURER. INSTALLUNDER DIVISION 23.
CONDENSATE MIXING UNIT WITH INTEGRAL CHECK VALVE AND UNIONS FURNISHEDBY HEAT EXCHANGER MANUFACTURER. INSTALL UNDER DIVISION 23.
3/4" STEAM TRAP FURNISHED BY HEAT EXCHANGER MANUFACTURER. INSTALLUNDER DIVISION 23.
1/2" MNPT X 3/8" FNPT VACUUM BREAKER FURNISHED BY HEAT EXCHANGERMANUFACTURER. INSTALL UNDER DIVISION 23.
DIAGRAM GENERAL NOTES:
1. UNLESS NOTED OTHERWISE, ALL PIPING, VALVES, AND SPECIALTIES SHALL BE FURNISHEDAND INSTALLED BY DIVISION 23.
3/4"
PIPE TO DRAIN1/2"
2"
3"
PRESSURE GAUGEWITH PIGTAIL
CONNECTION (TYP.)
PIPE TO DRAIN
1/2"
3/8"
3"
CHILLED WATER BTU METER.RE: SPECIFICATIONS.
STEAM CONDENSATE FLOW METER.RE: SPECIFICATIONS.
MIN
IMU
M 9
6"
130 GPM 130 GPM
4" 4" 4" 4"
4"
4"
4"
PRIMARY (COLD-SIDE) PUMPS SECONDARY (HOT-SIDE) PUMPS
PRIMARY (COLD-SIDE)CONTROL VALVE
SECONDARY (HOT-SIDE)ISOLATION VALVE
2" BYPASS
DIFFERENIALPRESSUREGAUGE
DIFFERENIALPRESSUREGAUGE
4"
4"
SECODARY WATERFLOW INDICATION
PRESSURE TRANSMITTERMOUNTED IN STEAM MAINDOWNSTREAM OF STEAMCONTROL VALVES
CONDUCTIVITYSENSOR
2. ADDITIONAL CONTROL POINTS REQUIRED FOR SKID MOUNTED DEVICES BY HEAT EXCHANGERMANUFACTURER INCLUDE: A. STABILIZING PUMP START/STOP (DO) B. STABILIZING PUMP CSEN (DI) B. CONDENSATE CONTROL VALVE (AO) B. STEAM STARTUP CONTROL VALVE (DO) B. STEAM PRIMARY CONTROL VALVE (DO) B. STEAM PRIMARY CONTROL VALVE (DO)
HEATING HOT WATER BTU METER.RE: SPECIFICATIONS.
h. OPERATE THE LEAD HOT WATER PUMP THROUGH ITS VARIABLE FREQUENCYDRIVE TO MAINTAIN THE MINIMUM DIFFERENTIAL STATIC PRESSURE SETPOINT ASMEASURED AT THE END OF THE HEATING HOT WATER MAINS. IF DIFFERENTIALSTATIC PRESSURE SETPOINT IS NOT MET AFTER 5 MINUTES OF LEAD HOT WATERPUMP OPERATION, THE SECOND HOT WATER PUMP SHALL START.
i. MODULATE THE BYPASS CONTROL VALVE TO MAINTAIN A MINIMUM OF 15% OFTHE DESIGN HEATING HOT WATER FLOW WHENEVER ANY PRIMARY STEAMCONTROL VALVE IS OPEN.
4. WHEN THE HEATING PLANT IS DISABLED, THE SYSTEM CONTROL SHALL:
a. CLOSE THE CONDENSATE CONTROL VALVE.b. WHEN THE HEATING HOT WATER SUPPLY TEMPERATURE IS +/- 1 DEG F FROM THE
HEATING WATER RETURN TEMPERATURE FOR 30 CONSECUTIVE SECONDS,CLOSE THE PRIMARY STEAM CONTROL VALVE.
c. STOP STABILIZING PUMP.d. STOP LEAD AND LAG HEATING HOT WATER PUMPS.
5. HEAT EXCHANGER ALARMS:a. UPON HEATING HOT WATER SUPPLY TEMPERATURE EXCEEDING 20 DEG F ABOVE
CURRENT SETPOINT, STEAM INLET CONTROL VALVES SHALL CLOSE AND THE BMSSHALL GENERATE AN ALARM. WHEN THE HEATING HOT WATER SUPPLYTEMPERATURE FALLS TO 5 DEG F ABOVE CURRENT SETPOINT, THE ALARM SHALLBE DISABLED AND STEAM INLET CONTROL VALVES SHALL RESUME NORMALOPERATION.
b. UPON HEATING HOT WATER SUPPLY TEMPERATURE EXCEEDING 15 DEG FBELOW CURRENT SETPOINT, THE BMS SHALL GENERATE AN ALARM. WHEN THEHEATING HOT WATER SUPPLY TEMPERATURE RISES TO 10 DEG F BELOWCURRENT SETPOINT, THE ALARM SHALL BE DISABLED.
c. UPON CONDENSATE CONDUCTIVITY REACHING ITS HIGH LIMIT SETPOINT, THEBMS SHALL GENERATE AN ALARM AND THE SYSTEM SHALL INITIATE THE SHUTDOWN SESQUENCE.
d. UPON HEATING HOT WATER FLOW NOT PROVEN FOR MORE THAN 5 SECONDS(ADJ), THE BMS SHALL GENERATE AN ALARM AND THE SYSTEM SHALL INITIATETHE SHUT DOWN SEQUENCE. MANUAL RESET IS REQUIRED TO RESTART THESYSTEM.
e. UPON LOST SIGNAL FROM THE HEATING HOT WATER SUPPLY OR RETURNTEMPERATURE SENSORS OR WHEN EITHER OF THE HEATING HOT WATER SUPPLYOR RETURN TEMPERATURE SENSORS READ OUT OF RANGE, THE STEAM INLETCONTROL VALVES SHALL CLOSE, THE CONDENSATE CONTROL VALVE SHALLCLOSE, AND THE BMS SHALL GENERATE AN ALARM. MANUAL RESET IS REQUIREDTO RESTART THE SYSTEM.
5. PUMP FAILURE: UPON SENSING A PUMP FAILURE, THE BMS SHALL LOCKOUT AND ALARMTHE FAILED PUMP. IMMEDIATELY, THE FOLLOWING PUMP SHALL BE ENERGIZED (IF NOTALREADY OPERATING). AUTOMATIC ISOLATION VALVES SHALL MAINTAIN HEATEXCHANGER OPERATION WITH THE FOLLOWING PUMP.
6. PUMP ROTATION: AUTOMATIC ROTATION OF PUMP OPERATION SHALL EQUALIZERUNTIME. ROTATION SHALL BE INITIATED BY THE FOLLOWING OPERATOR SELECTABLEMETHODS:
a. REAL TIME: BASED ON DAY INTERVALS.b. RUN TIME: ACTUAL RUN TIMES.c. MANUAL OR FORCED.
A. REFER TO CONTROLS SPECIFICATION FOR ADDITIONAL REQUIREMENTS.
B. THE DESIGN INTENT IS FOR THE BMS TO CONTROL THE STEAM TO HOT WATER HEAT EXCHANGERINCLUDING ALL NECESSARY POINTS AND CONTROL FUNCTIONS TO PERFORM THE SEQUENCEDEFINED BELOW. THE SEQUENCE BELOW IS INTENDED TO OUTLINE THE OVERALL CONTROLFUNCTIONALITY OF THE HEATING HOT WATER SYSTEM, AND THE SEQUENCE REFERENCESCONTROL FUNCTIONS TO BE PERFORMED BY BOTH SKID MOUNTED COMPONENTS ANDCOMPONENTS PROVIDED BY THE TEMPERATURE CONTROLS CONTRACTOR. IT IS THERESPONSIBILITY OF THE TEMPERATURE CONTROLS CONTRACTOR TO PROVIDE ALL ADDITIONALCOMPONENTS, POINTS, CONNECTIONS, AND CONTROL LOGIC REQUIRED FOR A FULLYFUNCTIONAL HEATING HOT WATER SYSTEM. SYSTEM SHALL BE INSTALLED AND CONTROLLEDPER MANUFACTURER'S RECOMMENDATIONS.
C. THE BMS SHALL PERFORM THE FOLLOWING CONTROL SEQUENCES AND PROVIDE THE POINTSAS LISTED ON THE POINTS LIST.
1. ENABLE/DISABLE THE STEAM TO WATER HEAT EXCHANGER AND SEQUENCE HEATINGWATER PUMPS.
2. HEAT EXCHANGER'S SUPPLY AND RETURN WATER TEMPERATURES SHALL BE MONITOREDAND ALARMED.
C. HEAT EXCHANGER SHALL MODULATE TO MAINTAIN THE HWS TEMPERATURE AND PROVIDE ALLSAFETY INTERLOCKS. THE BMS SHALL RECEIVE THE GENERAL HEAT EXCHANGER ALARMS ANDALARM THE OPERATOR'S WORKSTATION.
D. THE HEATING PLANT SEQUENCING SOFTWARE SHALL PERFORM THE FOLLOWING CONTROLSEQUENCE AND PROVIDE THE CONTROL POINTS LISTED.
1. THE HEATING PLANT SHALL START IN RESPONSE TO AN OUTSIDE AIR TEMPERATURE OF 50F(ADJ.).
2. HEATING PLANT SEQUENCING SOFTWARE SHALL START AND STOP THE SYSTEM WATERPUMPS AND ENABLE HEAT EXCHANGER BASED UPON THE SYSTEM LOAD.
3. WHEN THE HEATING PLANT IS ENABLED, THE SYSTEM CONTROL SHALL:
a. OPEN THE SECONDARY (HEATING HOT WATER) ISOLATION VALVE AND START THELEAD HOT WATER PUMP.
b. START THE STABILIZING PUMP.c. VERIFY SECONDARY WATER FLOW IN HEAT EXCHANGER VIA DIFFERENTIAL
PRESSURE TRANSMITTER.d. ONCE SECONDARY WATER FLOW IS PROVEN, OPEN THE PRIMARY (CAMPUS
STEAM) STARTUP CONTROL VALVE AT THE HEAT EXCHANGER.e. ONCE THE HEAT EXCHANGER IS COMPLETELY FLOODED, STEAM PRESSURE WILL
AUTOMATICALLY INCREASE UNTIL FULL AVAILABLE STEAM PRESSURE ISREACHED.
f. ONCE FULL AVAILABLE STEAM PRESSURE IS REACHED AS INDICATED VIAPRESSURE TRANSMITTER MOUNTED DOWNSTREAM OF THE STEAM CONTROLVALVES, OPEN THE MAIN PRIMARY STEAM CONTROL VALVE AND CLOSE THESTARTUP STEAM CONTROL VALVE.
g. MODULATE THE CONDENSATE CONTROL VALVE TO ACHIEVE HEATING HOTWATER SUPPLY TEMPERATURE. THE HEATING HOT WATER SUPPLYTEMPERATURE SETPOINT SHALL BE RAMPED FROM THE RETURN HEATING HOTWATER TEMPERATURE UP TO THE REQUIRED SUPPLY TEMPERATURE AT A RATEOF 5 DEG F PER MINUTE TO AVOID THERMAL SHOCK. THE HEATING HOT WATERSUPPLY TEMPERATURE SHALL NEVER BE MORE THAN 20 DEG F (ADJ) ABOVE THERETURN WATER TEMPERATURE. ANY ADJUSTMENTS IN HEATING HOT WATERSUPPLY TEMPERATURE SETPOINTS SHALL BE PERFORMED AT A RATE OF 5 DEG FOF ADJUSTMENT PER MINUTE MAXIMUM.
1" BYPASS WITH ISOLATIONVALVE FOR SYSTEM FLUSHING
1" BYPASS WITH ISOLATIONVALVE FOR SYSTEM FLUSHING
4. HEAT EXCHANGER FAILURE: UPON SENSING A HEAT EXCHANGER FAILURE THE BMSSHALL ALARM AND LOCKOUT THE HEAT EXCHANGER.
5. PUMP FAILURE: UPON SENSING A PUMP FAILURE, THE BMS SHALL LOCKOUT AND ALARMTHE FAILED PUMP. IMMEDIATELY, THE FOLLOWING PUMP SHALL BE ENERGIZED (IF NOTALREADY OPERATING). AUTOMATIC ISOLATION VALVES SHALL MAINTAIN HEATEXCHANGER OPERATION WITH THE FOLLOWING PUMP.
6. PUMP HIGH PRESSURE LIMIT: UPON SENSING DISCHARGE PRESSURE AT ANY PUMP OF125 PSIG OR HIGHER, THE PUMP SHALL BE DISABLED AND THE BMS SHALL GENERATE AHIGH PRESSURE LIMIT ALARM.
7. PUMP ROTATION: AUTOMATIC ROTATION OF PUMP OPERATION SHALL EQUALIZERUNTIME. ROTATION SHALL BE INITIATED BY THE FOLLOWING OPERATOR SELECTABLEMETHODS:
a. REAL TIME: BASED ON DAY INTERVALS.b. RUN TIME: ACTUAL RUN TIMES.c. MANUAL OR FORCED.
E. UPON A DROP IN PRIMARY CHILLED WATER RETURN TEMPERATURE TO 50F, THE SECONDARYCHILLED WATER SUPPLY TEMPERATURE SHALL BE RESET IN INCREMENTS OF 1 DEGREE TO AMAXIMUM OF 48F UNTIL THE PRIMARY CHILLED WATER RETURN TEMPERATURE RISES TO 52F.SECONDARY CHILLED WATER SUPPLY TEMPERATURE SHALL BE RESET IN INCREMENTS OF 30MINUTES.
A. REFER TO CONTROLS SPECIFICATION FOR ADDITIONAL REQUIREMENTS.
B. THE BMS SHALL PERFORM THE FOLLOWING CONTROL SEQUENCES AND PROVIDE THE POINTS ASLISTED ON THE POINTS LIST.
1. ENABLE/DISABLE THE WATER TO WATER HEAT EXCHANGER AND SEQUENCE CHILLEDWATER PUMPS.
2. HEAT EXCHANGER'S SUPPLY AND RETURN WATER TEMPERATURES SHALL BE MONITOREDAND ALARMED.
C. HEAT EXCHANGER SHALL MODULATE TO MAINTAIN THE CHS TEMPERATURE AND PROVIDE ALLSAFETY INTERLOCKS. THE BMS SHALL RECEIVE THE GENERAL HEAT EXCHANGER ALARMS ANDALARM THE OPERATOR'S WORKSTATION.
D. THE CHILLED WATER PLANT SEQUENCING SOFTWARE SHALL PERFORM THE FOLLOWINGCONTROL SEQUENCE AND PROVIDE THE CONTROL POINTS LISTED.
1. THE CHILLED WATER PLANT SHALL START IN RESPONSE TO A CALL FOR COOLING FROMANY AIR HANDLING UNIT OR FAN COIL UNIT AND WHEN OUTSIDE AIR TEMPERATURE ISABOVE 65 DEG F (ADJ).
2. CHILLED WATER PLANT SEQUENCING SOFTWARE SHALL START AND STOP THE SYSTEMWATER PUMPS AND ENABLE HEAT EXCHANGER BASED UPON THE SYSTEM LOAD.
3. WHEN THE CHILLED WATER PLANT IS ENABLED, THE SYSTEM CONTROL SHALL:
a. OPERATE THE PRIMARY (COLD-SIDE) CHILLED WATER PUMPS THROUGH THEIRVARIABLE FREQUENCY DRIVES TO MAINTAIN PRIMARY RETURN WATERTEMPERATURE OF 55 DEG F (ADJ).
b. OPEN THE SECONDARY (HOT-SIDE) ISOLATION VALVE AND THE PRIMARY(COLD-SIDE) CONTROL VALVE AT THE HEAT EXCHANGER.
c. START THE LEAD SECONDARY CHILLED WATER PUMP AFTER WATER FLOWS HAVEBEEN PROVEN.
d. OPERATE THE LEAD SECONDARY CHILLED WATER PUMP THROUGH ITS VARIABLEFREQUENCY DRIVE TO MAINTAIN THE MINIMUM DIFFERENTIAL STATIC PRESSURESETPOINT AS MEASURED AT THE END OF THE CHILLED WATER MAINS. IFDIFFERENTIAL STATIC PRESSURE SETPOINT IS NOT MET AFTER 5 MINUTES OFLEAD CHILLED WATER PUMP OPERATION, THE SECOND CHILLED WATER PUMPSHALL START.
e. MODULATE THE HEAT EXCHANGER PRIMARY CONTROL VALVE TO MAINTAIN ASECONDARY SUPPLY WATER TEMPERATURE OF 44F (ADJ.).
f. MODULATE THE BYPASS CONTROL VALVE TO MAINTAIN A MINIMUM OF 15% OFTHE DESIGN CHILLED WATER FLOW WHENEVER THE CHILLED WATER PLANT ISENABLED.
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN02/07/14DESIGN DEVELOPMENT04/04/1480% CD SET / PERMIT SET05/02/14100% CD SET
CSM WELCOMECENTER
M6.01
MECHANICALSCHEMATICS ANDCONTROLDIAGRAMS
COLORADO SCHOOL OF MINESGOLDEN, CO
1219
PARALLEL FAN POWERED VARIABLE AIR VOLUME (VAV) HWREHEAT UNITS:
SHUTOFF VARIABLE AIR VOLUME (VAV) HW REHEAT UNITS:
VAV BOX CONTROL SEQUENCE (SHUT OFF VAV):
VAV AIR HANDLING UNIT WITH RETURN FAN (CONFIGURATIONII):
T
HTT
T
T
CD
CD
CD
2
SHUTOFF VAV BOX WITHHW REHEAT CONTROLNONE
3 SHUTOFF VAV BOX CONTROLNONE
1 VAV AIR HANDLING UNIT WITH RETURN FAN CONTROLNONE
4
PARALLEL FAN POWERED VAVBOX WITH HW REHEAT CONTROLNONE
DI
CONTROLLERDEDICATED
SA
TUBING
ROOM
M
DO LANDO OR AO
SAVS
AI
HYDRONIC RH COIL
HWSHWR AI
V
TT
HI LOW
AO
DI (TIME OVERRIDE)
F
DP
A0
OA
M
M
AO
EA
CSEN
DI
DI
AI
VFD DOAO
A0
M
SATTTTLOCATE 2/3 DOWNDUCTWORK.SUBMIT LOCATIONFOR REVIEW.
HWS
HWR
AOHC CC
DI
AI
SF
VFD DOAO
SPT
AI
HUMIDITYOUTDOOR
AI
T
DI
FR
HTTT
AI AI
CSEN
DI
SPT
AIAI
TT SD
DI
CO2 SENSOR
AI
SD
RA
DI
AI
AIROUTSIDE
AI AI
SPACE
S
CD
CD
CD
SPT
AI
SPT
AI
DI
AI
SPT
AI
RA
AI
TOA
AI
OACFM
CHR
CHS
AODI
CONTROLLERDEDICATED
SA
TUBING
ROOM
M
DO LANDO OR AO
SAVS
AI
HYDRONIC RH COIL
HWSHWR
AI
V
TT
HI LOW
AO
SF
CSEN
DI
S/S
DO
PLENUM RA
DI
CONTROLLERDEDICATED
SA
TUBING
ROOM
M
DO LANDO OR AO
SAVS
AI
AI
TT
HI LOW
DI
ROOM (SELECT LOCATIONSAI
ONLY) RE: PLANS.
DI
ROOM (SELECT LOCATIONSAI
ONLY) RE: PLANS.
DI
ROOM (SELECT LOCATIONSAI
ONLY) RE: PLANS.
A. OCCUPIED MODE:
1. ON A RISE IN SPACE TEMPERATURE ABOVE THE COOLING SETPOINT, THE UNITCONTROL DAMPER SHALL MODULATE UP TO ITS MAXIMUM SUPPLY AIR CFM TOMAINTAIN SETPOINT. AS SPACE TEMPERATURE DECREASES, THE UNIT CONTROLDAMPER SHALL MODULATE DOWN TO ITS MINIMUM COOLING CFM TO MAINTAINSETPOINT. UPON A FURTHER DECREASE IN SPACE TEMPERATURE, THE UNITCONTROL DAMPER SHALL MODULATE TO ITS FIXED HEATING MINIMUM CFM AND THEUNIT FAN SHALL ENERGIZE. UPON A FURTHER DECREASE IN SPACE TEMPERATURE,THE UNIT CONTROL DAMPER SHALL REMAIN AT ITS FIXED HEATING MINIMUM CFM, THEUNIT FAN SHALL REMAIN ENERGIZED, AND THE HEATING CONTROL VALVE SHALLMODULATE OPEN TO MAINTAIN HEATING SETPOINT.
2. FOR UNITS SERVING SPACES EQUIPPED WITH CO2 DETECTORS, ON A RISE IN SPACECO2 LEVEL ABOVE THE SETPOINT, THE UNIT SHALL MODULATE UP TO ITS MAXIMUMCFM. THE UNIT FAN SHALL ENERGIZE, AND THE HEATING CONTROL VALVE SHALLMODULATE TO MAINTAIN SPACE TEMPERATURE SETPOINT. UNIT SHALL RETURN TONORMAL OCCUPIED MODE WHEN CO2 SETPOINT IS SATISFIED.
B. UNOCCUPIED MODE:
1. UNIT'S CONTROL DAMPER SHALL BE FULLY CLOSED. UNIT FAN SHALL BEDE-ENERGIZED.
C. NIGHT SETBACK MODE:
1. REF. AHU CONTROL.
D. ALARMS:
1. ALARM THE BMS IN THE EVENT OF A UNIT FAN FAILURE.
A. OCCUPIED MODE:
1. ON A RISE IN SPACE TEMPERATURE ABOVE THE COOLING SETPOINT, THE UNIT SHALLMODULATE UP TO ITS MAXIMUM CFM TO MAINTAIN SETPOINT. AS SPACETEMPERATURE DECREASES, THE UNIT SHALL MODULATE DOWN TO ITS MINIMUMCOOLING CFM TO MAINTAIN SETPOINT. UPON A FURTHER DECREASE IN SPACETEMPERATURE, THE UNIT SHALL MODULATE TO ITS FIXED HEATING MINIMUM CFM ANDTHE HEATING COIL SHALL MAINTAIN HEATING SETPOINT.
2. FOR UNITS SERVING SPACES EQUIPPED WITH CO2 DETECTORS, ON A RISE IN SPACECO2 LEVEL ABOVE THE SETPOINT, THE UNIT SHALL MODULATE UP TO ITS MAXIMUMCFM. THE HEATING COIL SHALL THEN MODULATE TO MAINTAIN SPACE TEMPERATURESETPOINT. UNIT SHALL RETURN TO NORMAL OCCUPIED MODE WHEN CO2 SETPOINT ISSATISFIED.
B. UNOCCUPIED MODE:
1. UNIT'S VOLUME DAMPER SHALL BE FULLY CLOSED.
C. NIGHT SETBACK MODE:
1. REF. AHU CONTROL.
A. OCCUPIED MODE:
1. UPON A RISE IN SPACE TEMPERATURE, THE UNIT SHALL MODULATE TO PROVIDE UPTO ITS MAXIMUM CFM TO MAINTAIN SPACE SETPOINT. UPON A DECREASE IN SPACETEMPERATURE, THE UNIT SHALL MODULATE DOWN TO ITS MINIMUM COOLING CFM TOMAINTAIN SPACE SETPOINT.
2. FOR UNITS SERVING SPACES EQUIPPED WITH CO2 DETECTORS, ON A RISE IN SPACECO2 LEVEL ABOVE THE SETPOINT, THE UNIT SHALL MODULATE UP TO ITS MAXIMUMCFM. THE HEATING COIL SHALL THEN MODULATE TO MAINTAIN SPACE TEMPERATURESETPOINT. UNIT SHALL RETURN TO NORMAL OCCUPIED MODE WHEN CO2 SETPOINT ISSATISFIED.
B. UNOCCUPIED MODE:
1. UNIT'S VOLUME DAMPER SHALL BE FULLY CLOSED.
C. NIGHT SETBACK MODE:
1. REF. AHU CONTROL.
H. OUTSIDE AIR CONTROL:1. PROVIDE CO2 SENSOR IN RETURN AIR DUCTWORK TO MONITOR CO2 LEVEL.2. UPON A DROP IN RETURN AIR CO2 LEVEL BELOW 1000 PPM, MODULATE OA DAMPER BELOW
DESIGN MINIMUM POSITION TO A LOWER LIMIT EQUAL TO 50% OF THE DESIGN MINIMUMOUTSIDE AIRFLOW. OA DAMPER SHALL MODULATE BETWEEN DESIGN MINIMUM AND LOWERLIMIT TO MAINTAIN RETURN AIR CO2 LEVEL BELOW 1000 PPM.
3. MONITOR THE MIXED AIR TEMPERATURE AND DAT AND OVERRIDE THE OA CONTROL IF MATEMP FALLS BELOW 45F (ADJ.) OR DAT EXCEEDS 60F (ADJ.). ALARM THE BMS IF EITHEROCCURS.
4. MONITOR RETURN AIR CO2 LEVEL AND ALARM THE BMS IF CO2 LEVEL IS ABOVE 1000 PPM FOR5 MINUTES (ADJ.).
5. OA DAMPERS ARE CLOSED IN UNOCCUPIED MODE.
I. ECONOMIZER CONTROL:1. WHEN THE OUTSIDE AIR ENTHALPY IS LESS THAN THE RETURN AIR ENTHALPY, AND COOLING
IS REQUIRED, THE ECONOMIZER CONTROL SHALL BE ENABLED. THE ECONOMIZER DAMPERSSHALL MODULATE BETWEEN THE ADJUSTABLE MINIMUM POSITION AND FULL OPEN TOMAINTAIN THE DISCHARGE AIR TEMPERATURE. COOLING SHALL BE ENABLED WITH THEOUTSIDE AIR DAMPERS FULLY OPEN AS LONG AS OUTSIDE AIR ENTHALPY IS LESS THANRETURN AIR ENTHALPY. HEATING SHALL BE LOCKED OUT UNTIL THE ECONOMIZER DAMPERSHAVE RETURNED TO THE MINIMUM VENTILATION POSITION. WHEN OUTSIDE AIR ENTHALPYEXCEEDS RETURN AIR ENTHALPY, ECONOMIZER CONTROL SHALL BE DISABLED AND THEDAMPERS SHALL MODULATE TO MAINTAIN MINIMUM AIRFLOW AND CO2 LEVELS. EXHAUSTDAMPER TO MODULATE BETWEEN THE ADJUSTABLE MINIMUM POSITION AND FULL OPEN TOMAINTAIN BUILDING STATIC PRESSURE SETPOINT.
J. DISCHARGE AIR TEMPERATURE:1. MAINTAIN DESIGN DAT OF 55F (ADJ.).2. PROVIDE A DISCHARGE AIR TEMPERATURE RESET ALGORITHM TO RESET THE DISCHARGE AIR
TEMPERATURE (UP TO A HIGH LIMIT OF 65F (ADJ.)) SO THAT AT LEAST ONE VAV BOX ORPARALLEL FAN-POWERED VAV BOX IS ABOVE ITS SCHEDULED MINIMUM POSITION AND NO VAVBOXES OR PARALLEL FAN-POWERED VAV BOXES ARE MORE THAN 90% OPEN. MODULATE DATSETPOINT BETWEEN DESIGN DAT AND HIGH LIMIT DAT AS NECESSARY TO SATISFY BOTHCONDITIONS. HEATING SHALL BE LOCKED OUT DURING DAT RESET.
3. IF RETURN AIR HUMIDITY RISES ABOVE 55% (ADJ.), RESET ALGORITHM SHALL BE DISABLEDAND DAT SHALL RETURN TO DESIGN DAT SETPOINT FOR MINIMUM OF 15 MINUTES (ADJ.).
K. FREEZE PROTECTION: FREEZE STAT SHALL BE HARD WIRED TO ACCOMPLISH THE FOLLOWING:1. A MANUAL RESET HEATING COIL DISCHARGE AIR LOW LIMIT SHALL INITIATE FREEZE
PROTECTION MODE IF ANY 12-INCHES OF ITS SENSING ELEMENT IS BELOW ITS SETPOINT (35ADJ.).
2. FANS SHALL DE-ENERGIZE.3. THE OA AND EA DAMPERS SHALL CLOSE.5. THE COOLING COIL FREEZE PROTECTION PUMP SHALL ENERGIZE.6. THE HEATING VALVE SHALL OPEN TO 75% OPEN POSITION.7. THE HEATING VALVE SHALL REMAIN AT 75% OPEN IF THE MIXED AIR TEMPERATURE IS BELOW
40F (ADJ.) WHEN THE FANS ARE OFF.6. THE HEATING COIL FREEZE PROTECTION PUMP SHALL ENERGIZE.7. A LOW LIMIT TEMPERATURE ALARM SHALL BE GENERATED AT THE BMS.
L. TIMED OVERRIDE:1. PROVIDE A 0-3 HOUR OVERRIDE TIMER IN A CENTRAL LOCATION TO PROVIDE AFTER-HOURS
OVERRIDE OF THE AIR HANDLING SYSTEM AND VAV BOXES. THE 0-3 HOUR OVERRIDE TIMERSHALL RETURN THE AHU AND ALL ASSOCIATED VAV BOXES AND PARALLEL FAN-POWEREDVAV BOXES TO OCCUPIED MODE FOR THE TIME PERIOD SELECTED.
M. HEATING VALVE CONTROL:1. THE HEATING VALVES SHALL MODULATE TO MAINTAIN THE DESIGN DAT (ADJ.). THE HEATING
VALVES SHALL BE FULLY CLOSED IF THE FANS ARE OFF. THE HEATING VALVES SHALL BEFULLY CLOSED WHEN DAT SETPOINT IS RESET UP FROM DESIGN DAT.
N. COOLING VALVE CONTROL:1. THE COOLING VALVES SHALL MODULATE TO MAINTAIN THE DAT (ADJ.). THE COOLING VALVES
SHALL BE FULLY CLOSED IF THE FANS ARE OFF.
A. SPECIFIC AHU CONFIGURATION, RE: SCHEDULE
B. OCCUPIED MODE:1. WHEN THE AHU IS IN THE OCCUPIED MODE, THE SUPPLY AND RETURN FANS SHALL OPERATE
CONTINUOUSLY. THE SUPPLY FAN VFD SHALL MODULATE TO MAINTAIN THE DUCT STATICPRESSURE. THE RETURN FAN VFD SHALL MODULATE TO MAINTAIN EXHAUST PLENUM STATICPRESSURE OF 0.1" WG (ADJ.). COOLING VALVES, HEATING VALVES AND ECONOMIZERDAMPERS SHALL MODULATE IN SEQUENCE TO MAINTAIN DISCHARGE AIR TEMPERATURE (DAT)OF 55F (ADJ.).
C. UNOCCUPIED MODE:1. WHEN THE AHU IS IN THE UNOCCUPIED MODE THE SUPPLY AND RETURN FAN SHALL BE OFF,
COOLING SHALL BE DISABLED AND THE OUTSIDE AIR DAMPER AND THE HEATING VALVE SHALLBE CLOSED UNLESS THE FREEZE STAT OR NIGHT SETBACK OVERRIDES THE VALVE POSITION.THE EA DAMPER IS CLOSED AND THE RA DAMPER IS OPEN ASSOCIATED VAV BOXES TO BECLOSED.
D. NIGHT SETBACK MODE:1. NIGHT SETBACK OFFSETS: MAINTAIN A 6F (ADJ.) OFFSET TO OCCUPIED MODE HEATING AND
COOLING SETPOINTS.2. UPON A RISE IN SPACE TEMPERATURE ABOVE THE NIGHT SETBACK COOLING OFFSET IN ANY
ZONE , CYCLE SUPPLY AND RETURN FANS AND MODULATE ASSOCIATED VAV BOXES ANDPARALLEL FAN-POWERED VAV BOXES TO MAINTAIN OFFSET TEMPERATURE OF WARMESTSPACE T-STAT.
3. UPON A DROP IN SPACE TEMPERATURE BELOW THE NIGHT SETBACK HEATING OFFSET IN ANYZONE SERVED BY A VAV BOX, CYCLE SUPPLY AND RETURN FANS AND FULLY OPEN HEATINGVALVE TO MAINTAIN OFFSET TEMPERATURE OF COLDEST SPACE T-STAT. FULLY OPEN ALLVAV BOX CONTROL DAMPERS AND OPEN PARALLEL FAN-POWERED BOX CONTROL DAMPERSTO THEIR FIXED HEATING MINIMUM CFM.
4. UPON A DROP IN SPACE TEMPERATURE BELOW THE NIGHT SETBACK HEATING OFFSET IN AZONE SERVED BY A PARALLEL FAN-POWERED VAV BOX, ENERGIZE THE ASSOCIATEDPARALLEL FAN-POWERED BOX FAN AND MODULATE THE HEATING CONTROL VALVE TOMAINTAIN OFFSET TEMPERATURE IN THE ZONE. PARALLEL FAN-POWERED VAV BOX ZONESSHALL BE ALLOWED TO CYCLE ON INDIVIDUALLY BY ZONE TO MEET HEATING OFFSETTEMPERATURE.
5. UPON CYCLING ON SUPPLY AND RETURN FANS DURING NIGHT SETBACK MODE, THEFOLLOWING SHALL OCCUR:
5.1. OA DAMPERS SHALL BE CLOSED. EA DAMPERS SHALL BE CLOSED. RETURN AIRDAMPERS SHALL BE OPEN.
5.2. COOLING SHALL BE LOCKED OUT.6. UPON ALL SPACE T-STATS REACHING OFFSET SETPOINT, AHU TO RETURN TO UNOCCUPIED
MODE. VAV HEATING TO REMAIN CLOSED DURING NIGHT SETBACK MODE.
E. WARM-UP MODE:1. SUPPLY AND RETURN FANS SHALL RUN CONTINUOUSLY AND BE ENERGIZED ONE HOUR (ADJ.)
PRIOR TO SCHEDULED OCCUPIED MODE START. MODULATE HEATING VALVE TO WARM-UPSPACE TO OCCUPIED SETPOINT OF ALL SPACE STATS.
2. OA DAMPERS SHALL BE CLOSED. EA DAMPERS SHALL BE CLOSED. RA DAMPERS SHALL BEOPEN.
3. COOLING SHALL BE LOCKED OUT.4.REVERT TO OCCUPIED MODE WHEN ALL SPACE STATS HAVE REACHED OCCUPIED HEATING
SETPOINT. ALLOW HEATING VALVE TO CLOSE AND THE DISCHARGE AIR TEMPERATURE TODROP TO WITHIN 2 DEG F (ADJ.) OF MIXED AIR TEMPERATURE BEFORE OPENING OUTSIDE AIRDAMPERS.
F. FAN SAFETY CONTROLS:1. DE-ENERGIZE THE SUPPLY AND RETURN FANS WHENEVER THE FREEZE STAT IS TRIPPED,
EITHER SMOKE DETECTOR HAS TRIPPED OR A FAN STATUS INDICATES A FAILURE (AFTER ATWO-MINUTE DELAY). THE SMOKE DETECTORS, FREEZE STAT AND THE FAN FAILURESREQUIRE A MANUAL RESET.
2. DE-ENERGIZE THE SUPPLY AND RETURN FANS WHEN THE DISCHARGE STATIC PRESSUREHIGH-LIMIT REACHES 4.0 INCHES WC (ADJ.).
3.DE-ENERGIZE THE SUPPLY AND RETURN FAN WHEN THE RETURN FAN DISCHARGE STATICPRESSURE HIGH-LIMIT REACHES 2.0 INCHES WC (ADJ.).
4.PROVIDE SUCTION STATIC PRESSURE SWITCH AT INLET OF SUPPLY FAN. SWITCH TO BE TIEDTO SUPPLY FAN START CIRCUIT. DE-ENERGIZE SUPPLY AND RETURN FAN WHEN SUCTIONSUPPLY FAN STATIC PRESSURE HIGH-LIMIT REACHES 2.0 INCHES WC (ADJ.)
5. PROVIDE DDC MONITORING OF EACH FAN IN BOTH SUPPLY AND RETURN FAN ARRAYS. ALARMTHE BMS WITH A FAN FAILURE ALARM WHEN ANY OVERLOAD IS OPEN.
5.ALARM THE BMS WITH THE APPROPRIATE ALARM MESSAGE.
G. VFD CONTROL:1. WHEN THE SUPPLY AND RETURN FANS ARE TURNED ON, THE VFD SHALL SLOWLY RAMP UP
TO SETPOINT AND MODULATE TO MAINTAIN THE PROPER DUCT STATIC PRESSURES. THESTATIC PRESSURE SENSORS SHALL BE LOCATED BY THIS DIVISION.
2. SUBMIT SENSOR LOCATIONS TO ENGINEER FOR REVIEW.3. SENSING DEVICE SHALL BE MULTIPLE POINT, NON-PULSATING STATIC SENSING SECTION WITH
SELF AVERAGING MANIFOLD.
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN02/07/14DESIGN DEVELOPMENT04/04/1480% CD SET / PERMIT SET05/02/14100% CD SET
CSM WELCOMECENTER
M6.02
MECHANICALSCHEMATICS ANDCONTROLDIAGRAMS
COLORADO SCHOOL OF MINESGOLDEN, CO
1219
A ROUND DUCT BRANCH TAKE-OFF DETAILSNO SCALE
B ROOF MOUNTED EXHAUST FAN DETAILNO SCALE
C BRANCH DUCT TAKE-OFF DETAILNO SCALE
D CEILING DIFFUSER DETAILNO SCALE
H LINEAR DIFFUSER CONNECTION DETAILNO SCALE
F FLEX DUCT/SPIN IN FITTING DETAILNO SCALE
I PARALLEL FAN POWERED VAV BOX DETAILNO SCALE
L VAV BOX WITH COIL DETAILNO SCALE
O RECTANGULAR DUCT FITTINGS AND TAKE-OFFS DETAILNO SCALE
E RETURN AIR BOOT DETAILNO SCALE
G DUCT LINER DETAILNO SCALE
M FIRE DAMPER INSTALLATION DETAILNO SCALE
J COMBINATION FIRE/SMOKE DAMPER DETAILNO SCALE
N FLEXIBLE DUCT SUPPORTNO SCALE
K RETURN AIR TRANSFER BOOT DETAILNO SCALE
1"
GENERAL NOTES:
45 DEGREE ENTRY BRANCH TAKE-OFF
NOTES:
RADIUS ELBOW
SQUARE ELBOW
TRANSFER AIR DUCT
RETURN AIR TRANSFER BOOT
HWS
#10x3/4" SELF TAPPING CADMIUM PLATED INSULATED SHEET
BELL-MOUTH SPIN-IN FITTING
BALANCE DAMPER WITH
WRAP ALL RIGID DUCT W/FOILFACED 1-1/2" FIBERGLASS
SHEET METAL SCREWS. ALL STRAPS TO BETIGHT AGAINST DUCT AND SUPPORT MEMBERS
FASTEN RIGID DUCT TO SPIN-INFITTING WITH SHEET METAL SCREWS
HANGER STRAPS
NO POP RIVETS ALLOWED
(TYP)
DUCT WRAP
METAL DUCT
LOCKING QUADRANT
ROUND RIGID DUCT
INACCESIBLEDAMPER ISOPERATOR WHEREREMOTE CEILING
AIR FLOW
W
THAN TWO DUCT WIDTHSBE INSTALLED CLOSERDAMPERS SHOULD NOT
INTERSECTIONSTO ELBOWS OR
NOTE:
45
L
CEILING DAMPERREGULATOR
PROVIDE CONCEALEDVOLUME DAMPER
L=1/4 W (4" MIN.)NOTE:
RETURNAIR GRILLE
CEILING
W L
L
W
SHEET METAL DUCTWORKWITH 1" DUCT LINING
2X5.
W
USING TAPE.
FACE STYLE PER SCHEDULE
OF STANDARD LENGTHFACTORY SEAL AT END
FABRICATE END SEALIF REQUIRED, FIELD
WITH SEALERSEAL METAL JOINTS
BAND CLAMP
PROVE A MIN. OF 3 DUCTDIAMETERS (D) STRAIGHTDUCT UPSTREAM OF
BE A MIN. OFr= 1.5D. PROVIDEA MAXIMUM OF 135^TOTAL TURN IN FLEX
INSULATION
CEILING
BAND CLAMP
BARRIERWITH VAPOR
FIBERGLASS
DUCT.
DIFFUSER
CL
FLEXDUCT
DIFFUSER NECK
WITH MANUAL LOCKINGCONICAL SPIN-IN DUCT FITTING
ALL TURNS SHALL
1-1/2 TIMES DUCT DIA.MAKE RADIUS BEND MIN.
QUADRANT.
r
DUCT
TRUNK
DUCT
TRUNK
DUCT
TRUNK
DUCT
TRUNK
TRUNK DUCT
AIR FLOW
DIRECTION OF
AIR FLOW
DIRECTION OF
AIR FLOW
DIRECTION OF
AIR FLOW
DIRECTION OF
AIR FLOWDIRECTION OF
BRANCH DUCT
BRANCH DUCT
BRANCH DUCT
BRANCH DUCTBRANCH DUCT
90^ CONICAL TEE90^ STRAIGHT TEE
90^ ELONGATED TEE
2-WAY 45^ Y
45^ Y TEE
INSULATE DIFFUSER
PLANS FOR SIZE.DUCTWORK. SEE FLOORLINED LOW PRESSURE
FLEXIBLE CONNECTION
PRESSURE DUCT. SEE FLOOR PLANSEXTERNALLY INSULATED MEDIUM
FILTER TRACK AND1" FILTER. PROVIDE
CONNECTION DETAIL.SEE TYPICAL COILHOT WATER COIL.
AND CONTROL PANEL.
HOUSING.
ELECTRICAL CONNECTION
SIZE AS UNIT OPENING.LINED ELBOW, SAME
FOR SIZE.
D
FAN
3'-0" MIN.SERVICE
CLEARANCEHWR
PROVIDE 3XD STRAIGHTDUCT INTO BOX INLET
1. COORDINATE FLASHING REQUIREMENTS AND CURBINSTALLATION WITH ROOFING CONTRACTOR ANDARCHITECTURAL ROOF REQUIREMENTS.
FLEXIBLE CONNECTION
BIRDSCREEN
TRANSITION TO DUCT SIZE
6" O.C. FOR TIGHT JOINTSMETAL SCREWS NOT OVER
AND RIGID INSULATION
SECURE FAN & DUCT W/SHEET
INDICATED ON PLANS
SOUND LINER
DUCT SIZE PER PLANS
CURB AND CANT.COORDINATE WITHROOFING CONTRACTOR.
GRAVITY BACKDRAFT
ROOF CURB, MIN. 14" HIGH
ROOF
DAMPER
EXHAUST FANROOF MOUNTED
STRUCTURE WITH 20 GA.SUPPORT DIFFUSER FROM
CONTINUOUS SHEET
EXTERNAL INSULATIONMETAL PLENUM WITH
STRAPS
LINEARDIFFUSER
CEILING
DUCT INSULATION
TAKE OFF. SEAL PLATE AIRPLATE TO COVER ZONE DUCT
STAINLESS STEELBAND
TIGHT.
VD
DIFFUSER NECKDUCT UPSTREAM OFDIAMETERS (D) STRAIGHTPROVE A MIN. OF 3 DUCT
INSULATED FLEXIBLEDUCT. MAX. 5'
2. FITTINGS TO BE 2 GAGES HEAVIER THAN CONNECTED DUCT.
1. REFER TO DRAWING NOTES AND SPECS FOR TURNING VANEREQUIREMENTS. PROVIDE ACCESS DOORS AT TURNING VANES.
MINIMUM R = 1W (WHERE SPACE PROHIBITS 1.5W)
TURNING VANES
0.5W MINIMUM
MANUAL DAMPER
W
45°
MINIMUM
0.25 X WOR 4"
W
SEE NOTE 1
R
AIRFLOW
DOUBLE RADIUSTURNING VANES
FLOWAIR
SQUARE ELBOWS SHALLONLY BE USED IF SPACECONSTRAINTS DO NOTPERMIT USE OF RADIUSELBOWS.
ACCESS DOOR
R = 1.5W
ACCESS DOOR
AIRFLOW
SQUARE ELBOW SHOWN. SQUAREELBOWS SHALL ONLY BE USED IFSPACE CONSTRAINTS DO NOTPERMIT USE OF RADIUS ELBOWS.
ANGLE STEEL SUPPORT
MEDIUM PRESSUREDUCTWORK WITHEXTERNAL INSULATION
30° MAX.
MEDIUM PRESSURE TAP
FABRIC CONNECTOR.TO VAV BOX FLEXIBLE
HARD CONNECT
HANGER ROD
MIN18"
STRAIGHTDUCT
VAV BOX
30° MAX
12X12 ACCESSDOOR
(TYP.)PIPE HANGER
NOTE: DUCT CONNECTIONS ARE THE SAME FOR ALL VAV BOXES WITH AND WITHOUT COIL.
SEE TYPICAL COILHOT WATER COIL
CONNECTION DETAIL
METAL FASTENERS12" O.C. MAX.(TYP.)
DUCT LINER
TOP AND BOTTOMSECTION OFLINER SHALLOVERLAP THESIDES
DUCTLINER
LINER TO BEADHERED TODUCT WITH100% ADHESIVE
ALL ENDS OF LINERTO BE COATED WITHADHESIVE. ENDS OFLINER SHALL BE BUTTEDFIRMLY TOGETHERAND TAPED OVER.
NOT MORE THAN2" FROM EDGEOF LINER
GALV. SHT.METAL DUCT
DUCT1" THICK LINED
GRILL (TYP.)TRANSFER AIR
1" THICK LINED
SEALANT AT EXPOSED EDGES (TYP)SHT. MTL. NOSING OR APPROVED
WALL PENETRATION (TYP.)CAULK CONTINUOUS AT
DUCT
SHEET METAL
1. SUPPORTS AT 3' MAX.
DUCT SADDLE
NOTE:
1" WIDE SHEET METALALL AROUND
FLEXIBLE DUCT
(TYP)
BUILDINGSTRUCTURE
SECURE TO
WIRE HANGER(TYP)
BLADES OUT OF MINERAL FIBER.
FIRE DAMPER
AIR STREAM
1-1/2"X1-1/2"X1/8"
SIDES OF WALLALL AROUND BOTHRETAINING ANGLES
TYPE, TURN ASSEMBLY 90
VERTICAL TYPE FIRE DAMPER
AND PROVIDE W/SPRING
SHOWN. FOR HORIZONTAL
NEGATOR EXTENSION.
NOTE:
FASTENERS 8" O. C.
SLEEVE ONLYSECURE TO STEEL
ACCESS DOOR
BREAKAWAY JOINT
DAMPER SLEEVEBOTH SIDES OF
MAINTAIN CLEARANCE INACCORDANCE WITH MFR.
PACK WITH FIREPROOFINSTRUCTIONS AND NFPA 90A.
16 GAUGESTEEL SLEEVE
6" MAX (TYP ALL SIDES)1-1/2"x1-1/2" ANGLESUPPORTS (TYP ALLSIDES) DO NOT ATTACH
10 GA SLEEVE (TYP)
INSULATION WHERENOTED
1/4" MINCLEARANCE
1" MINOVERLAPACCESS DOOR
OPERATOR/ACTUATOR
AUXIARY OPERATINGJACK SHAFTFUSIBLE LINK WITH LOCK
FUSABLE ROD
NEGATOR SPRING
TO WALL
24V OR 120V
MINERAL FIBER.
MAINTAIN CLEARANCE INACCORDANCE WITH MFR.
PACK WITH FIREPROOFINSTRUCTIONS AND NFPA 90A.
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN02/07/14DESIGN DEVELOPMENT04/04/1480% CD SET / PERMIT SET05/02/14100% CD SET
CSM WELCOMECENTER
M8.01
MECHANICALDETAILS
COLORADO SCHOOL OF MINESGOLDEN, CO
1219
B TYP. WATER COIL CONNECTION (2-WAY)NO SCALE
C TYP. WATER COIL CONNECTION (3-WAY)NO SCALE
D AHU COIL CONNECTION WITH COIL PUMPNO SCALE
I DRAIN AND TRAP FROM AIR HANDLING UNITNO SCALE
E INLINE PUMP CONNECTION DETAILNO SCALE
A END OF MAIN STEAM TRAP ASSEMBLYNO SCALE
G PLATE TYPE HEAT EXCHANGER DETAILNO SCALE
F END SUCTION PUMP DETAILNO SCALE
J EXPANSION TANK DETAILNO SCALE
K AIR SEPARATOR MOUNTINGNO SCALE
H DRAIN VALVE CONNECTIONNO SCALE
N GLYCOL FEED ASSEMBLY DETAILNO SCALE
O CHEMICAL POT FEEDERNO SCALE
L AUTOMATIC AIR VENT DETAILNO SCALE
M ROOFTOP MECH. UNIT MOUNTINGNO SCALE
P PARTITION RETURN AIR BOOT DETAILNO SCALE
NOTE:
COIL
s" DRAIN VALVE WITH HOSEFITTING AND CAP.
AIR VENT
T & P TAP
UNION
T & P TAP
SHUTOFFVALVE (TYP.)
STRAINER
VALVE2- WAY CONTROL
BALANCING VALVE
RETURN
SUPPLY
VALVE (TYP.)
UNION
BALANCING VALVE
BALL
3- WAY CONTROLVALVE
T & P TAP
AIR VENT
MAY BE DELETED IF BALANCINGVALVE IS RATED FOR BUBBLE-
s" DRAIN VALVE WITH HOSE
NOTE: SHUTOFF VALVE ON RETURN
T & P TAP
STRAINER
TIGHT SHUT OFF.
FITTING AND CAP.
COIL
RETURN
SUPPLY
OPEN TO ATMOSPHERE
TO
FLOOR SINKRECEPTOR OR
2"A
B1"
2. 2" MINIMUM.1. STATIC PRESSURE OF AIR HANDLING UNIT PLUS 1".
NOTES:
DRAIN PAN
AIR HANDLING UNIT
OPEN DRAIN
TOWARD DRAINPITCH DOWN
THE NIPPLE ON THE DRAIN PANLEAST THE SAME SIZE ASDRAIN LINE SHALL BE AT
B A
SEE NOTE 2 SEE NOTE 1SEE NOTE 2SEE NOTE 1
BA
BLOW THROUGH COILDRAW THROUGH COIL
CHECK VALVEBALANCING VALVE
LIFTING EYES
NOTE:UNISTRUT SUPPORTS FROMPROVIDE ANGLE IRON OR
W/LEVER HANDLE.
SMALLER PUMPS MAY BEPUMPS 7 HP & LARGER.
ISOLATORS.
ABOVE. PUMPS MUST BE
PT PLUG
SUPPORTED WITH VIBRATION
SUPPORTED FROM STRUCTURE
HOSE END DRAINVALVE
STRAINER
FLOOR FOR ALL INLINE
BUTTERFLY VALVE (3" AND LARGER)BALL VALVE (2" AND SMALLER
INLINE PUMP
COIL
s" DRAIN VALVE WITH HOSEFITTING AND CAP.
AIR VENT
T & P TAP
UNION
T & P TAP
SHUTOFFVALVE (TYP.)
STRAINER
VALVE2- WAY CONTROL
BALANCING VALVE
RETURN
SUPPLYINTERLOCKED WITH PUMP2- WAY SOLENOID VALVE
INLINE COIL PUMP
CHECK VALVE (TYP.)
1-1/2" FREEZE PROTECTION PIPING
LINE SIZE SUPPLY PIPING. RE: PLANS.
1-1/2" FREEZE PROTECTIONBYPASS LINE
1-1/2" FREEZE PROTECTION PIPING
LINE SIZE SUPPLY PIPING. RE: PLANS.
HPSPITCH DN
SWING CHECK VALVE
TRAP ISOLATION BALLVALVE, TYP.
COLLECTING LEG
CONTINUES WHEREEND-OF-MAIN ISAT A LIFT
MAIN LINE SIZE
PITCH DOWN
PITCH DOWN
PITCH DOWN
CURB SECURED TO ROOF
PRE-FABRICATEDCURB
SEE ARCH. DRAWINGWITH BLOCKING,RIGID INSULATION
DUCT DOWN
FACTORY SUPPLIEDWOOD NAILER
LEVELED ROOFSEE ARCH. DRAWING
UNIT BASE, SECURE
COUNTER FLASHING
SUPPLIED WITH CURBNEOPRENE GASKET
FLASHING SEE ARCH. DRAWING
TO CURB
UNIT
SEE STRUCTURAL DWG.FOR ANCHORAGE DETAIL,
AIRVENT
DRAIN VALVEHOSE END
TO OTHEREXPANSION
ANTI-THERMOSYPHONLOOP, 12" MIN. DROP.
LOCK SHIELDTYPE SHUT-OFF
TANKS
VALVE
OF SYSTEM PIPINGCONNECT TO SIDE
HOUSE KEEPING PAD
WITH 1/4" APOLLO CONBRACOPRESSURE GAUGE
EXPANSIONTANK
BALL VALVE
TO FLOORDRAIN
CW MAKE UP
REDUCED PRESSUREBACKFLOW PREVENTER
SYSTEM PIPING
PRV VALVE SET AT 35 PSIG.AUTOMATIC MAKE-UP WATER
TO CHILLER LOOP
PRESSURE GAUGE& TEMP. GAUGE
AIR VENT
BUTTERFLY VALVEP/T PLUG
PCH
WR
SCH
WS PC
HW
R
SCH
WR
FROM BUILDINGFROM CHILLER LOOP
FROM BUILDING
HEAT EXCHANGER
DRAIN VALVE
4" CONCRETE PAD
POSITIVE DISPLACEMENTPUMP 1/3HP, 120V/1~
PRESSURE RELIEF VALVE
PRESSURE SWITCH
CLOSED RECIRCULATING
LOW LEVEL CONTROLLER
TANK WITH PREMIXED GLYCOL
BALL VALVE WITHHOSE END FITTING
SYSTEM
PRESSURE GAUGE
SOLUTION RE: FLOOR PLANSFOR SIZE OF TANK
CONTROL PANEL WITHLOW LEVEL ALARM, PUMPSTARTER AND HOA SWITCH
120 VOLT POWER
NOTE:
1.GLYCOL FEEDER SHALL BE A PACKAGED SYSTEM PROVIDEDBY THE WATER TREATMENT SUPPLIER. H.O.H. OR EQUIVALENT.
CHECK) VALVE
FOR FLOW MEASUREMENTPRESSURE SENSING TAP
FLEX CONNECTOR. RE: SPECIFICATIONS
INERTIA BASE
BRAIDED STAINLESS STEEL
PRESSURE GAUGE
\"
PRESSURE SENSING TAP
GAUGE ISOLATION VALVE
COUPLING GUARD
FOR FLOW MEASUREMENT
4" HOUSEKEEPINGPAD
VALVEBALL OR BUTTERFLY
SUCTION DIFFUSERWITH STRAINER
MULTI-PURPOSE (BALANCING, SHUT-OFF,
SHEET METAL DUCTWORKWITH 1" DUCT LINING
L
W
3W
X
WITH 90^ ORIENTATION.CEILING BOOT IS SIMILAR
PARTITION WALL
1.
3 XW
SUPPORT TO STRUCTURE WITH METALSTRIP IN ATLEAST 2 PLACES MAX 16"CENTER TO CENTER
L
W
FOR AIR VENT LINE. SECURE
SIZE TO CONNECTION ON AIRWITH COPPER CLIPS 18" O.C.
3/8" HARD DRAWN COPPER
1/4" APOLLO OCNBRACO BALL VALVEUP 5'-0" FROM FLOOR
OR AS DIRECTEDTO FLOOR DRAIN
WATER PIPING
HIGH POINTS INWATER MAINS
INSTALL AIR VENT AT ALLHIGH POINTS AND WHERESHOWN ON THE DRAWINGS
AIR CHAMBERSPECIFIED
CHAMBER
AND/OR PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS
PROVIDE DRAIN VALVES AT LOW POINTS OF WATER SYSTEM.
2.
NOTES:
1.
WELDED PIPINGELEVATION
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
3/4" BALL VALVE
ADAPTER TO 3/4" HOSE THREADPROVIDE HOSE CAP NUT
THREADED PIPINGELEVATION
4" CONCRETE PAD
SUPPORT RING
TO DRAIN
HEADERTO RETURN
MANUAL AIR VENT
FLOW CONTROLNEEDLE VALVE FOR
WITH GOOSNECK FITTING
FROM SUPPLY HEADER
3/4"
UNION (TYP.)
3/4"
FILLING FUNNEL WITHSHUT OFF VALVE
TO FLOOR SINKDRAIN PIPING
AIR VENTHIGH CAPACITY
SUPPORT PER SPEC. SEC. 15050
STEEL FRAME BRACINGAT 4 SIDESSTEEL BASE PLATE BOLTEDTO CONCRETE PAD
LOCATIONSFRAME AT 4
CLIP WELDED TOSTEEL ANGLE
ELEVATION
AIR SEPARATOR
4" HIGH CONCRETEHOUSEKEEPING PAD
6"
WELDED CONSTRUCTIONSTRUCT. STEEL FRAME
ANGLE CLIP
CONNECTING BOLT
AIR SEPARATOR
STRUCTURAL STEEL FRAME
TANK WALLDRAINTO FLOOR
WATER CONN.MAKE UP
AIR SEPARATOR
DETAIL `A'DETAIL 'A'
CONTINUOUS WELD
SHIMLEVELING
PLAN
d" THICK BASE PLATE
ANCHOR BOLTS
STRAINER WITHBLOWDOWN VALVE
UNION
BALL VALVE
(75 PSIG)
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN02/07/14DESIGN DEVELOPMENT04/04/1480% CD SET / PERMIT SET05/02/14100% CD SET
CSM WELCOMECENTER
M8.02
MECHANICALDETAILS
COLORADO SCHOOL OF MINESGOLDEN, CO
1219
~ ~
C PIPE THRU STUD WALL DETAILNO SCALE
E RISER ISOLATION SUPPORTNO SCALE
B PIPE THRU FLOOR SLAB DETAILNO SCALE
A VIBRATION ISOLATION HANGER DETAILNO SCALE
D TYPICAL WATER PIPE HANGER DETAILNO SCALE
F INLINE FAN DETAILNO SCALE
F PIPE THROUGH EXTERIOR WALL DETAILNO SCALE
WHERE DIRECTEDWATER STOP CURB
PIPE CLAMP
PIPE RISER
OVER PIPE CLAMPSPECIFIED INSULATION
ENDS WITH MASTIC,SEALANT AND SEALW/APPROVED FIREPACK VOID TIGHTLY
ON EXPOSED PIPESESCUTCHEON PLATECHROME PLATED
FOR MIN 1/2" ANNULUSIPS PIPE SLEEVE SIZED
SLEEVEDIA. TACK WELD TOLARGER THAN SLEEVE1/4" THICK SPOKE, 4"
SEE SPEC.
16 GAGE PIPE SLEEVE
SPECIFIED INSULATION
PIPE
PLATED ESCUTCHEON PLATESPOSITIVE ACTING CHROME
NOTE: OMIT ESCUTCHEON PLATES
STUD WALL
FRAME AROUNDMETAL STUD CHANNEL
FOR CONCEALED PIPES.
FINISH FLOOR
SECTION A-A
SIDE OF CLAMP ONLYWELD PLATE TO ONE
3/16
TAC WELD TO STEEL PLATE
TYPE 'NP' NEOPRENEISOLATOR PAD
PLATE (WELD TO CLAMP)3/8" THICK LOAD BEARING
SIZED FOR LOADSHEAVY DUTY PIPE CLAMP
SECURE TO PIPE
RISER PIPE
A
A
PIPES ONLY)
STRIP BETWEEN BEARING AREA OF\" CLOSED CELL FOAM INSULATION(N) 1" SCRIM FACED FIBERGLASS OR
PIPE AND PIPE HANGER (BARE
PIPE HANGERS
WATER) PIPEBARE METAL (I.E. CONDENSER
INSTALL CALCIUM SILICATE INSERT WHEREPIPING IS INSULATED. RE: SECTION 15140.
RE: SECTION 15240SHEAR VIBRATION ISOLATORSPRING AND NEOPRENE IN(N) ADJUSTABLE, 30^ SWING
NEOPRENE ELEMENTDOUBLE DEFLECTION STD
BELOW WASHER TO ALLOW SPRINGAFTER INSULATION, RELEASE NUT
TO ACT FREELY
STD NEOPRENE GROMMET
FULL PIPE BORNE BY HANGER)FOR 1" DEFLECTION AT WEIGHT OFSPRING (SELECT ISOLATOR SIZE
THREADED ROD
AS SPECIFIED.80^ INSERT
STRUCTURAL ENGINEER FOR
OR CLAMP ACCORDING
INSULATION SHIELDS
12" LONG MIN. NOTE 2
TO SPECIFICATION
(1) 360^ OR (2) 180^20 GA GALVANIZED
PER SPECIFICATION
GALVANIZED U-BOLT
(TYPICAL ALL HGRS)
REQUIREMENTS ON SUPPORTS.
RATED NYLON. 2 PCS EACH. BE BANDED. USE SS OR PLENUM
3. SEE SPECIFICATION FOR PAINT
2. 180^ INSULATION SHIELDS MUST
TO STRUCTURE
APPROVAL.
1. SUBMIT ANCHORING METHOD TONOTES:
THREADED SUPPORTRODS. FOR SIZE SEE
ISOLATORS IN
NUT & WASHER
STEEL ANGLE
TOP & BOTTOM
VIBRATION
WATER AND DOMESTIC WATER, TYPICAL.HANGER OR CLAMP FOR CHILLEDCONTINUOUS VAPOR BARRIER INSIDE
CLEVIS TYPE HANGERAS SPECIFIED. FACTORY
180^ INSULATION SHIELD. NOTE 2.20 GA. GALVANIZED 12" LONG MIN.
360^ INSERT AT CLAMP AS SPECIFIED.
PAINTED.
IN MECH. ROOMS AND ASVIBRATION ISOLATORS
SPECIFIED.
TO STRUCTURE
HANGER RODSSEE SPECS.
TYPICAL
MECH ROOMS.
TABLE 1 ABOVE.
TYPICAL
RESILIENTWATERPROOF
WELD
CAULKING
1/4" STEEL PLATE
ANCHOR COLLARWATER STOP AND
IN SLEEVEPIPE CENTERED
INSULATION
END SEAL 2"
INTERIOR SIDEOF WALL
PENETRATION SEALLINK-SEAL MODEL-T
PIPE SLEEVEBLACK STEELSTANDARD WEIGHT
CONCRETE WALL
TO 2" AFF.EXTEND PIPE SLEEVE
AND ALL PARTS FOR PROPER AIR MOVEMENT AS RECOMMENDEDINSTALL FAN WITH PROPER SERVICE CLEARANCE TO MOTOR
TRANSITION WHERE REQUIRED.
30° MAXIMUM.
INTAKE DUCT.
BY THE MANUFACTURER.
NOTE:
FLEXIBLE CONNECTION.
BACKDRAFT DAMPER
ALLOW DOOR TO BE COMPLETELYOPENED.
ACCESS DOOR. INSTALL FAN TO
30° MAXIMUM
DISCHARGE DUCT.
SPRING ISOLATORS
TRANSITION WHERE
FLEXIBLE CONNECTION.
ABOVE, TYPICALHANGER RODS TO STRUCTURE
REQUIRED.
PER 15240, TYPICAL.
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN02/07/14DESIGN DEVELOPMENT04/04/1480% CD SET / PERMIT SET05/02/14100% CD SET
CSM WELCOMECENTER
M8.03
MECHANICALDETAILS
COLORADO SCHOOL OF MINESGOLDEN, CO
1219
ENVIRONMENTAL FAN SCHEDULE
CODE
EF-4-01
TF-1-01TF-2-01TF-2-02TF-3-01TF-3-02
EF-T-01
GENERAL NOTES:1. DRIVE TYPE: B = BELT-PROVIDE ADJUSTABLE SHEAVE UNLESS OTHERWISE NOTED.2. ALL CURBS SHALL BE FACTORY MADE, 14 INCH HIGH INSULATED UNLESS OTHERWISE NOTED.3. SCHEDULED FAN VALUES (CFM, SP AND HP) ARE ACTUAL AT ALTITUDE. JOB SITE ELEVATION = 5700 FT.4. PROVIDE MAGNETIC STARTER WITH AUXILARY CONTACTS AND HOA SWITCH ON ALL THREE PHASE UNITS EXCEPT WHEN SERVED FROM MOTOR CONTROL CENTER.5. PROVIDE MANUFACTURER'S STANDARD BELT TENSIONER FOR ALL BELT DRIVE FANS.
MOUNTING (MTG):1. PROVIDE WITH FACTORY MANUFACTURED ROOF CURB SUITABLE FOR ROOFING SYSTEM BEING USED. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.2. INSTALL FAN WITH FLEXIBLE CONNECTIONS AT DUCT INLET AND OUTLET AND WITH HANGING VIBRATION ISOLATORS.
CONTROL (CTRL):I. ENERGIZE VIA SCHEDULE THROUGH BMS SYSTEM.II. CONTROL VIA WALL SENSOR-ENERGIZE AT 75°F (ADJUSTABLE).III. ENERGIZE VIA WALL TEMPERATURE SENSOR AT 80°F OR ABOVE OR VIA WALL OXYGEN SENSOR AT MINIMUM OXYGEN CONCENTRATION. RE: CONTROLS DRAWINGS.IV. UPON CALL FOR HEATING AT AHU, ENERGIZE FAN TO MAINTAIN 80°F (ADJUSTABLE).
REMARKS:A. PROVIDE MOTORIZED DAMPER INTERLOCKED WITH FAN.B. PROVIDE SPEED CONTROL SWITCH.C. PROVIDE MANUFACTURER'S STEEL GRILLE.D. REAR INLET WITH WIRE MESH OVER OPEN FAN END.
MANUFACTURER/MODEL NO.
COOK / 195 ACEB
COOK / GC 720COOK / GC 720COOK / GN 1000COOK / GC 720COOK / GN 1000
COOK / 135CIC
SERVICE
RESTROOMS, CUSTODIAL
ELEC ROOMELEC ROOM
SOUTH SOLAR WALLELEC ROOM
SOUTH SOLAR WALL
TUNNEL EXHAUST
LOCATION
ROOF
LEVEL 1LEVEL 2LEVEL 2LEVEL 3LEVEL 2
TUNNEL
TYPE
DOWNBLAST
INLINEINLINEINLINEINLINEINLINE
INLINE
CFM
2,465
430430
1,500430
1,500
5,000
ESP"W.C.(ALT.)
1.00
0.500.500.500.500.50
0.75
DRIVE
B
DDDDD
B
ELECTRICAL
HP/W
3/4
134 W134 W
0.5134 W
1/2
5
VOLT
480
120120480120120
208
PH
3
11311
3
FLA
1.6
1.11.1
1.19.8
17.5
DISC.
30A/3P
$TO$TO
$TO$TO
30A/3P
FUSE
5A FRS-R
N/AN/A
N/AN/A
30A FRS-R
FEEDER
(3#12,1#12G)3/4"C
(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C
(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C
(3#10,1#10G)3/4"C
MTG
1
2222
2
CTRL
I
IIIIIVII
III
REMARKS
A
B, CB, CB, DB, CB, D
A
AIR HANDLING UNIT SCHEDULE (MODULAR OR CUSTOM)
CODE(AHU)
4-01
GENERAL NOTES1. PROVIDE HIGH EFFICIENCY MOTORS (RELIANCE E+ OR EQUIVALENT)2. PROVIDE FACTORY MOUNTED VFD FOR ALL SUPPLY AND RETURN FANS. PROVIDE OVERLOAD PROTECTION FOR EACH INDIVIDUAL FAN AND AUXILIARY CONTACTS ON EACH OVERLOAD FOR INTERFACE WITH DDC SYSTEM.3. INSTALL UNITS WITH ADEQUATE CLEARANCE FOR COIL PULL , FILTER REPLACEMENT AND TO FULLY OPEN ACCESS DOORS. PROVIDE A MINIMUM OF 3 FEET CLEARANCE IN FRONT OF DISCONNECTS SWITCHES AND CONTROL PANELS. COMPLY FULLY WITH NEC.4. UNIT STATIC PRESSURE CAPABILITY SHALL INCLUDE SCHEDULED EXTERNAL STATIC PRESSURE PLUS ALL SCHEDULED INTERNAL PRESSURE DROPS. INCLUDE VALUES FOR WETTED COILS AND DIRTY FILTERS.5. SCHEDULED FAN VALUES (CFM, SP AND HP) ARE AT 5700 FT.6. CHILLED WATER: EWT = 44F, LWT = 57F, 20% PG.7. HEATING WATER: EWT = 180F, LWT = 160F, 30% PG.8. PROVIDE DUCT SMOKE DETECTORS IN THE SUPPLY AND RETURN AIR OF ALL UNITS 2000 CFM OR GREATER. RE: SPECIFICATIONS.9. PROVIDE FREEZE STAT DOWNSTREAM OF HEATING COIL.10. MERV 8 PREFILTER, MERV 13 FINAL FILTER.11. REFER TO PLANS FOR DETERMINATION OF ALL AHU COIL CONNECTION SIDES.
REMARK NOTESA. REFER TO CONTROL DIAGRAMS FOR CONTROL REQUIREMENTS.B. PROVIDE FACTORY INSTALLED AND WIRED MARINE LIGHTS IN FAN AND ACCESS SECTIONS. WIRE TO AN EXTERIOR MOUNTED SWITCH, 120V POWER CONNECTION BY DIVISION 26.C. PROVIDE WINDOWS IN ACCESS DOORS OF FAN, FILTER/MIXING, AND ACCESS SECTIONS.D. MOUNT UNIT ON ROOF WITH MANUFACTURER'S CURB.E. PROVIDE INTERNAL VIBRATION ISOLATION.F. PROVIDE AN AIRFLOW MEASURING SENSOR IN THE OUTSIDE AIR DUCTWORK; SENSOR SHALL BE USED TO MAINTAIN THE MINIMUM OA AIRFLOW OVER THE ENTIRE RANGE OF SUPPLY AIR OPERATING RATES.G. PROVIDE 2-WAY HEATING (PREHEAT AND REHEAT) AND COOLING CONTROL VALVES.H. PROVIDE 48" PIPE CHASE EXTERNAL TO UNIT BY UNIT MANUFACTURER. RE: PLANS FOR LOCATION. PIPING TO BE ROUTED THROUGH UNIT CURB INTO PIPE CHASE. COORDINATE OPENING IN UNIT CURB TO ALLOWBUILDING AIR TO HEAT PIPE CHASE. COIL FREEZE PROTECTION PUMPS SHALL BE MOUNTED INSIDE UNIT PIPE CHASE. RE: MECHANICAL DETAILS.I. PROVIDE 24" ROOF CURB WITH 48"X10" OPENING THROUGH CURB WALL INTO PIPE CHASE. PIPING TO BE ROUTED FROM BELOW UNIT THROUGH ROOF CURB INTO PIPE CHASE.
CONFIGURATIONI. OUTDOOR HORIZONTAL DRAW THRU UNIT WITH EXHAUST FAN, MIXING BOX, PRE-FILTER/FINAL FILTER SECTION, PRE HEAT HEATING COIL, ACCESS SECTION, COOLING COIL, SUPPLY FAN, DISCHARGE PLENUM. 100% ECONOMIZER.
AREASERVED
WELCOME CENTER
LOCATION
ROOF
MANUFACTURER/MODEL NO.
TRANE PCC
SUPPLY FAN
CFM
42,000
TYPE
CENTRIFUGAL
DRIVE
DIRECT
TSP"W.C.
6.0
ESP"W.C.
2.5
MIN.OSA
10,000
RETURN/EXHAUST FAN
CFM
40,000
TYPE
CENTRIFUGAL
DRIVE
DIRECT
TSP"W.C.
3.7
ESP"W.C.
1.5
COOLING COIL CAPACITYEAT (F)
DB
81
WB
56
LAT (F)DB
55
WB
55
TOTALMBH
968
SENSMBH
968
GPM
156
WPD(FT)
5.5
APD"W.C.
0.3
PRE-HEAT HEATING COILEAT(F)
45
LAT(F)
96
CAPMBH
1909
GPM
200
WPD(FT)
9.3
APD"W.C.
0.1
FILTER SECTIONAPD ("W.C)MID LIFE
1.48
CODE(AHU)
1
ELECTRICALSUPPLY FAN
HP
(4) 15
ELECTRICALRETURN/EXHAUST FAN
HP
(4) 10
VOLT
460
VOLT
460
PH
3
PH
3
MCA
100
MCA
81.25
FUSE
175A FRS-R
FUSE
125A FRS-R
DISC
200A/3P
DISC
200A/3P
FEEDER
RE: ONE-LINE
FEEDER
RE: ONE-LINE
AHUCONFIG.
I
DIMENSIONSL
(IN.)
438
W(IN.)
142
H(IN.)
126
WT.(LBS.)
24,000
REMARKS
A,B,C,D,E,F,G,H,I
CABINET/UNIT HEATER SCHEDULE (HYDRONIC)
CODE
CUH-B-01
CUH-1-01CUH-1-02CUH-1-03
UH-3-01
GENERAL NOTES1. HEATING WATER: EWT = 180F, LWT = 160F, 30% PROPYLENE GLYCOL.2. JOBSITE ELEVATION = 5300 FT.3. PROVIDE 1" TYPE A FILTER
REMARK NOTESA. PROVIDE UNIT MOUNTED LINE VOLTAGE THERMOSTAT WITH SPEED CONTROL SWITCH. MONITOR VIA BMS.B. PROVIDE FRONT STAMPED LOUVER OUTLET AND BOTTOM STAMPED LOUVER INLET.C. PROVIDE 2-WAY VALVE AND COIL CONNECTION.
MANUFACTURER/MODEL NO.
TRANE FFBB08
TRANE FFBB08TRANE FFBB04TRANE FFBB08
TRANE UHSBA08
AREASERVED
WEST STAIR
NORTH VESTIBULEWEST VESTIBULE
SOUTH STAIR
CUSTODIAL
CONFIG
VERTICAL FLOOR MOUNT
VERTICAL FLOOR MOUNTVERTICAL FLOOR MOUNTVERTICAL FLOOR MOUNT
HORIZONTAL
CAP.(MBH)
30
301530
8
CFM
700
700350700
245
GPM
3.3
3.31.73.3
0.9
ELECTRICALW
135
13595135
16
VOLT
120
120120120
120
PH
1
111
1
FLA
1.5
1.51.51.5
1.5
DISC
$TO
$TO$TO$TO
$TO
FUSE
N/A
N/AN/AN/A
N/A
FEEDER
(2#12,1#12G)3/4"C
(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C
(2#12,1#12G)3/4"C
REMARKS
A,B,C
A,B,CA,B,CA,B,C
A,C
WALL MOUNTED FAN COIL SCHEDULE (HYDRONIC)
CODE(FCU)
B-011-012-013-01
GENERAL NOTES:1. CHILLED WATER: EWT = 42°F, 20% PROPYLENE GLYCOL.2. PROVIDE 1" TYPE A FILTERS.3. JOB SITE ELEVATION = 5700 FT4. PROVIDE PREMIUM EFFICIENCY MOTORS FOR MOTORS 1 HP AND OVER PER MENA STANDARD MG1-2003, TABLES 12-12 AND 12-13.
REMARK NOTES:A. PROVIDE WALL MOUNTED CONTROLLER.B. PROVIDE DUCT SMOKE DETECTORS PER CODE FOR ALL UNITS 2000 CFM OR GREATER.
MANUFACTURER/MODEL NO.
MULTIAQUA / MHWW-9MULTIAQUA / MHWW-24MULTIAQUA / MHWW-24MULTIAQUA / MHWW-24
AREA SERVED
ELEV CONTROLTELETELETELE
FAN
CFM
270600600600
ESP(IN.)
0000
COOLING COILEAT (°F)
DB
80808080
WB
67676767
TOTALMBH
10.322.522.522.5
SENSMBH
7.715.715.715.7
GPM
1.95.15.15.1
ROW
2222
WPD(FT)
3.68.38.38.3
ELECTRICAL
HP
1/601/201/201/20
VOLT
120120120120
PH
1111
FLA
1111
DISC
$TO$TO$TO$TO
FUSE
N/AN/AN/AN/A
FEEDER
(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C
REMARKS
AAAA
AIR SEPARATOR SCHEDULE
CODE(AS)
AS-1AS-2
GENERAL NOTES:1. TRANSITION PIPING TO INLET AND OUTLET AS REQUIRED.
SERVICE
CHILLED WATERHEATING HOT WATER
LOCATION
BASEMENTBASEMENT
DESIGN PARAMETERSSYSTEM
FLOW(GPM)
200200
PIPESIZE(IN.)
44
MAX PD(FT. HD.)
11
MANUFACTURER/MODEL NO.
SPIROTHERM/VSR500SPIROTHERM/VSR500
DIMENSIONS
DIAMETER(IN.)
12.812.8
HEIGHT(IN.)
30.630.6
WEIGHT(LBS.)
200200
REMARKS
EXPANSION TANK SCHEDULE
CODE(ET)
ET-1ET-2
GENERAL NOTES:1. TYPE: B=FULL BLADDER. D=PARTIAL DIAPHRAGM.2. LOCATE MAKE UP WATER CONNECTION AT EXPANSION TANK CONNECTION TO HYDRONIC SYSTEM.
REMARKS:A. TANK AND APPURTENANCES SHALL BE COMPATIBLE WITH PROPYLENE GLYCOL.
MANUFACTURER/MODEL NO.
EXTROL/200-LEXTROL/300-L
SERVICE
CHILLED WATERHEATING HOT WATER
LOCATION
BASEMENTBASEMENT
DESIGN PARAMETERSSYSTEMVOLUME
8001200
FLUID
20% PG30% PG
MIN.TEMP (°F)
4040
MAXTEMP (°F)
85190
OPERATING PARAMETERSMAX OPERATINGPRESSURE (PSIG)
6060
CW MU PRVREQ'T (PSIG)
3535
CONFIG
VERTICALVERTICAL
TYPE
BB
MIN. ACCEPT.(GAL)
5080
PRECHARGE(PSIG)
3535
REMARKS
AA
PLATE TYPE HEAT EXCHANGER SCHEDULE
CODE
PHX-1
MANUFACTURER/MODEL NO.
ALFA LAVAL/TL10B-FG
SERVICE
CHILLED WATER
HOT SIDE
FLUID
20% PG
GPM
200
EWT(F)
57
LWT(F)
44
WPD(FT)
14
FOULFACT
0.0005
COLD SIDE
FLUID
20%PG
GPM
260
EWT(F)
42
LWT(F)
52
WPD(FT)
22.8
FOULFACT
0.0005
WEIGHT(LBS)
1900
PUMP SCHEDULE
CODE
CWP-1,2CWP-3
CWP-4,5HWP-1,2HWP-3GP-1GP-2
GENERAL NOTES1. PROVIDE VFD WITHOUT BYPASS ON ALL THREE PHASE MOTORS.2. PROVIDE PREMIUM EFFICIENCY MOTORS FOR MOTORS 1 HP AND OVER PER MENA STANDARD MG1-2003, TABLES 12-12 AND 12-13.3. FOR PARALLEL PUMP APPLICATIONS MANUFACTURER SHALL REVIEW SINGLE PUMP OPERATON SUCH THAT PUMP CAN OPERATE AND NOT EXCEED THE END OPERATION POINT ON THE PUMP CURVE AND MOTOR HP IS PROPERLY SLELCTED TO PREVENT OVERLOADING.4. NPSHR AT SCHEDULED OPERATING POINT SHALL NOT EXCEED 0.8*NPSHA.5. REFER TO DRAWINGS TO DETERMINE REQUIRED PUMP ROTATION. COORDINATE WITH MECHANICAL CONTRACTOR PRIOR TO ORDERING.6. CHILLED AND HEATING WATER PUMPS OPERATE AS PART OF VARIABLE PRIMARY FLOW SYSTEMS.7. JOBSITE ELEVATION = 5700FT.
REMARK NOTESA. PROVIDE WITH VARIABLE FREQUENCY DRIVE WITH INTEGRAL OVER-CURRENT PROTECTION AND GROUND FAULT PROTECTION PER NEC 430.B. 50% CAPACITY (PARALLEL PUMP APPLICATION).C. FLUID CONTAINS 30% PROPYLENE GLYCOL. ALL PUMP COMPONENTS IN CONTACT WITH THE FLUID SHALL BE COMPATIBLE WITH GLYCOL. ADJUST STANDARD CATALOG PERFORMANCE TO ACCOUNT FOR USE OF GLYCOL. ASSUME FLUID TEMPERATURE OF 150 F(HWP) FOR PUMP ADJUSTMENT.D. FLUID CONTAINS 20% PROPYLENE GLYCOL. ALL PUMP COMPONENTS IN CONTACT WITH THE FLUID SHALL BE COMPATIBLE WITH GLYCOL. ADJUST STANDARD CATALOG PERFORMANCE TO ACCOUNT FOR USE OF GLYCOL. ASSUME FLUID TEMPERATURE OF 40 F (CHWP) FOR PUMP ADJUSTMENT.E. ELECTRICAL CONNECTION TO 120V WALL OUTLET.F. PROVIDE INTERLOCKED SOLENOID VALVE. REFER TO MECHANICAL DETAILS.G. PROVIDE 1-1/2" FLANGED INLET AND OULET CONNECTIONS.
MANUFACTURER/MODEL NO.
TACO/FI1509TACO/IL0014TACO/FI1507TACO/FI1509TACO/IL0014
HOH/G-50HOH/G-50
SERVICE
SECONDARY CHILLED WATERCHILLED WATER COIL PUMPPRIMARY CHILLED WATER
HEATING HOT WATERHEATING HOT WATER COIL PUMP
CHILLED WATER GLYCOLHEATING HOT WATER GLYCOL
LOCATION
BASEMENTROOF
BASEMENTBASEMENT
ROOFBASEMENTBASEMENT
PUMPTYPE
BASE MTD.INLINE
BASE MTD.BASE MTD.
INLINEPOSITIVE DISPLACEMENTPOSITIVE DISPLACEMENT
GPM
1002013010020----
HEAD(FT)
70540705----
NPSHR(FT)
5.7--5
5.7------
ELECTRICALHP
30.12
33
0.120.50.5
VOLT
480120480480120120120
PH
3133111
FLA
4.83
4.84.83
9.89.8
FUSE
10A FRS-RN/A
10A FRS-R10A FRS-R
N/AN/AN/A
DISC
30A/3P$TO
30A/3P30A/3P
$TO$TO$TO
FEEDER
(3#12,1#12G)3/4"C(2#12,1#12G)3/4"C(3#12,1#12G)3/4"C(3#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C
REMARKS
A, B, DD, F, GA, B, DA, B, CC, F, G
D, EC, E
VERTICAL FLOODED HEAT EXCHANGER SCHEDULE (STEAM)
CODE
SHX-1
NOTES:A. PROVIDE HEAT EXCHANGER PACKAGE INCLUDING ALL STEAM TRAPS, CONDENSATE MIXERS, AIR VENTS, AND VACUUM BREAKERSINDICATED ON DRAWING M6.01 AND ANY ADDITIONAL ACCESSORIES REQUIRED FOR A FULLY FUNCTIONAL SYSTEM.
MANUFACTURER/MODEL NO.
MAXI-THERM/MCU-200G-20F-85P
SERVICE
HEATING HOT WATER
TUBE SIDE
FLUID
30% PG
GPM
200
EWT(F)
160
LWT(F)
180
WPD(PSI)
2
FOULINGFACTOR
0.0005
SHELL SIDESTEAM
PRESS(PSIG)
85
FLOWLB/HR
1790
TEMP(F)
327.8
REMARKS
A
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN02/07/14DESIGN DEVELOPMENT04/04/1480% CD SET / PERMIT SET05/02/14100% CD SET
CSM WELCOMECENTER
MEP0.01
MECHANICALSCHEDULES
COLORADO SCHOOL OF MINESGOLDEN, CO
1219
FAN POWERED VAV BOX SCHEDULE (HYDRONIC)
CODE(FPVAV)
B-01B-02
1-011-021-031-041-051-061-071-081-091-101-111-121-131-141-15
2-012-022-032-042-052-062-072-082-09
3-013-023-033-043-053-063-07
GENERAL NOTES:1. EWT = 180ºF, LWT=160ºF, % PROPYLENE GLYCOL = 30%.2. PROVIDE 1" TA FILTERS ON FAN INLET.3. FAN PERFORMANCE BASED ON MEDIUM SPEED UNLESS OTHERWISE NOTED.4. PRIMARY AIR S.P. IS MAXIMUM ALLOWABLE FOR MAXIMUM AIR FLOW LISTED.5. CONTROLS PROVIDED BY TEMPERATURE CONTROL CONTRACTOR. SEE SPECIFICATIONS.6. PROVIDE FLEXIBLE CONNECTION ON INLET AND DISCHARGE.7. ATC CONTRACTOR TO PROVIDE 2- WAY CONTROL VALVE PACKAGE UNLESS NOTED OTHERWISE (SEE REMARKS)8. MOUNT WITH 3 STRAIGHT DUCT DIAMETERS UPSTREAM OF THE BOX.9. PROVIDE RETURN AIR SMOKE DETECOTR FOR BOX EXCEEDING 2000 CFM.
REMARK NOTES:A. ATC CONTRACTOR TO PROVIDE 2-WAY CONTROL VALVE PACKAGEB. PROVIDE HOT WATER COIL AT INDUCTION AIR INLET.
MANUFACTURER /MODEL NO.
TITUS / DTQP 05TITUS / DTQP 03
TITUS / DTQP 03TITUS / DTQP 03TITUS / DTQP 06TITUS / DTQP 03TITUS / DTQP 03TITUS / DTQP 02TITUS / DTQP 02TITUS / DTQP 05TITUS / DTQP 02TITUS / DTQP 05TITUS / DTQP 03TITUS / DTQP 02TITUS / DTQP 02TITUS / DTQP 05TITUS / DTQP 02
TITUS / DTQP 02TITUS / DTQP 05TITUS / DTQP 02TITUS / DTQP 05TITUS / DTQP 05TITUS / DTQP 05TITUS / DTQP 05TITUS / DTQP 02TITUS / DTQP 05
TITUS / DTQP 03TITUS / DTQP 05TITUS / DTQP 05TITUS / DTQP 05TITUS / DTQP 06TITUS / DTQP 02TITUS / DTQP 06
AREA SERVEDMAIN MECH, MAIN ELEC, FACT STOR
STORAGE, HALL
LARGE MEETING ALARGE MEETING B
LOBBY 107HERITAGE LOUNGE
LOBBY 100TOUR WAITING
TOUR PRESENTATIONHALL,CONFERENCE
OFFICE 124,126OPEN OFFICE (EXTERIOR)
OFFICE 138,140,142OFFICE 144OFFICE 146
OFFICE 148,150,152,154CONFERENCE 158
SHELL 200OFFICE 216,218
OFFICE 222,224,226OPEN OFFICE (EAST EXTERIOR)
OFFICE 240,242
OFFICE 250,252OPEN OFFICE (WEST EXTERIOR)
OFFICE 266,268MEETING 270
WORK RM/CONFOFFICE 316, 318,322,324
HALL C315HALL C315,GRAPHIC WALL
OFFICE 348,352, 354,356CONFERENCE 360
OFFICE 362,OPEN OFFICE, OFFICE 366
INLET(DIA.)
1210
101014101088128121088128
8128141012141010
1014121416814
DESIGN AIRMIN.CFM440400
395395880270360255225560200500335160160595160
230480260660430665660265415
3207455607051080200940
MAX.CFM1100100021009809802200670900630560140049012508303903901480400
13550570120064016501070166016506601030101307901860139017602690500234011330
S.P."W.C.
0.50.5
0.50.50.50.50.50.50.50.50.50.50.50.50.50.50.5
0.50.50.50.50.50.50.50.50.5
0.50.50.50.50.50.50.5
CAPACITYMIN.CFM325230
230230450230230145145325145325230145145325145
145325145450230325450145230
230450450450580145450
MAX.CFM20001400
140014003000140014009009002000900200014009009002000900
900200090030001400200030009001400
140030003000300040009003000
FAN SECTION
CFM660600
5855851320400540375335840290750495230230885240
340720380990640995990395615
4701115830105516103001400
S.P."W.C.0.350.39
0.390.390.440.350.380.350.350.370.350.360.370.320.320.380.35
0.320.350.350.390.340.390.390.350.35
0.370.410.370.40.590.350.45
ELECTRICAL
HP1/31/4
1/41/43/41/41/41/61/61/31/61/31/41/61/61/31/6
1/61/31/61/31/31/31/31/61/3
1/41/31/31/33/41/63/4
VOLT277277
277277277277277277277277277277277277277277277
277277277277277277277277277
277277277277277277277
PH11
111111111111111
111111111
1111111
MCA4
2.8
2.82.86.92.82.81.61.64
1.64
2.81.61.64
1.6
1.63.61.64
3.63.64
1.64
2.8444
6.91.66.9
DISC$TO$TO
$TO$TO$TO$TO$TO$TO$TO$TO$TO$TO$TO$TO$TO$TO$TO
$TO$TO$TO$TO$TO$TO$TO$TO$TO
$TO$TO$TO$TO$TO$TO$TO
FUSE----
------------------------------
------------------
--------------
FEEDER(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C
(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C
(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C
(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C(2#12,1#12G)3/4"C
E POWER?(Y/N)
HEATING COILCOILEAT65.065.0
65.065.065.065.065.065.065.065.065.065.065.065.065.065.065.0
65.065.065.065.065.065.065.065.065.0
65.065.065.065.065.065.065.0
COILCFM660.0600.0
585.0585.01320.0400.0540.0375.0335.0840.0290.0750.0495.0230.0230.0885.0240.0
340.0720.0380.0990.0640.0995.0990.0395.0615.0
470.01115.0830.01055.01610.0300.01400.0
CAP.MBH28.425.8
25.325.356.817.323.316.314.536.212.732.321.510.110.138.310.3
14.731.016.642.627.742.942.617.126.6
20.448.136.045.569.512.960.5
GPM0.91.5
1.21.23.50.91.20.93.91.52.41.31.11.21.21.71.224.40.71.20.92.01.12.12.00.91.0
1.02.51.52.32.52.44.0
APD"W.C.0.040.09
0.090.090.140.050.080.040.020.060.010.050.070.010.010.070.01
0.040.050.040.080.040.080.080.050.04
0.060.10.060.090.280.010.15
WPDFT0.40.89
0.420.427.040.380.640.382.781.451.091.060.520.280.281.720.28
0.210.950.382.510.722.582.510.380.68
0.463.81.453.132.091.089.16
MAXN.C.3137
373736343635353432323631313531
353236363136363631
35373437383437
REMARKSA,BA,B
A,BA,BA,BA,BA,BA,BA,BA,BA,BA,BA,BA,BA,BA,BA,B
A,BA,BA,BA,BA,BA,BA,BA,BA,B
A,BA,BA,BA,BA,BA,BA,B
GRILLE REGISTER DIFFUSER SCHEDULE
CODE
ABCDEFF1G
GENERAL NOTES:1. SEE PLANS FOR CFM AND NECK SIZE.2. MAXIMUM NOISE CRITERIA (NC) SHALL BE 30 UNLESS OTHERWISE NOTED.3. COLOR TO BE COORDINATED WITH ARCHITECT PRIOR TO ORDERING. FIELD PAINT AS REQUIRED.4. MATERIAL IS STEEL UNLESS OTHERWISE NOTED.5. PROVIDE BALANCING DEVICE FOR ALL GRD'S UNLESS OTHERWISE NOTED.6. BORDER TYPES LISTED ARE FOR REFERENCE ONLY. CONTRACTOR SHALL VERIFY CEILING SYSTEMS AND PROVIDE APPROPRIATE FRAME AND BORDER TYPE AS REQUIRED.
REMARK NOTES:A. PROVIDE CONTINUOUS DIFFUSER FACE FOR LENGTH OF DIFFUSER.B. PROVIDE INTEGRAL AIR SCOOP BALANCING DAMPER.C. PROVIDE INTEGRAL BALANCING DAMPER.D. NO BALANCING DAMPER
MANUFACTURER/MODEL NO.
TITUS / TMSTITUS / PARTITUS / PAS
TITUS / TBDI-80TITUS / 272FL
TITUS / 3FLTITUS / 3FL
TITUS / S300FL
SERVICE
SUPPLYRETURN / EXHAUSTRETURN / EXHAUST
SUPPLYSUPPLY
EXHAUST/RETURNEXHAUST/RETURN
SUPPLY
TYPE
LOUVEREDPERFORATEDPERFORATED
LINEARSIDEWALLSIDEWALLSIDEWALLSIDEWALL
ACCESSORIES
LAY-IN CEILING FRAMELAY-IN CEILING FRAMELAY-IN CEILING FRAME
1" 4-SLOT CONTINUOUS FACE W/ INSULATED PLENUM BOX45 DEGREE DEFLECTION0 DEGREE DEFLECTION0 DEGREE DEFLECTION45 DEGREE DEFLECTION
FACE SIZE
24X2424X2424X2448X8
SEE PLANSSEE PLANSSEE PLANSSEE PLANS
REMARKS
ACDCB
VAV BOX SCHEDULE
CODE
1-011-021-031-041-051-06
2-012-022-032-04
3-013-023-033-04
GENERAL NOTES1. CONTROLS SHALL BE BY MANUFACTURER OR BY CONTROL MANUFACTURER (SEE SPECIFICATIONS).2. MOUNT WITH 5 STRAIGHT DUCT DIAMETERS UPSTREAM OF THE BOX.3. MAXIMUM INLET S.P.= 0.75.4. MAXIMUM NC LEVELS ARE RADIATED SOUND DATA AND BASED ON THE MAXIMUM BOX CFM LISTED AND AT A PRESSURE DROP ACROSS THE BOX OF 2.0".5. EWT= 180°f, %PROPYLENE GLYCOL= 30%.
REMARK NOTESA. PROVIDE 2-WAY CONTROL VALVES.
AREA SERVED
CATERING KITCHENOPEN OFFICE (CENTER)
OFFICE 151, ELEC 131, STORAGE 129, HALL C120WAITING 122
OPEN OFFICE 135COPY/MAIL 149, BREAK 133
HALL C200, HALL C210, OPEN OFFICE 223, HALL C205OPEN OFFICE 231
COPY 253, BREAK 241, ELEC 241A, UA STORAGE 243, FA STORAGE 251CONFERENCE 246
HALL C310, WAITING 325, OPEN OFFICE 364CONFERENCE 361OPEN OFFICE 331
WORK RM 355, COPY 341, COPY 355A, BREAK 343
MANUFACTURER/MODEL NO.
TITUS DESV 5TITUS DESV 10TITUS DESV 9TITUS DESV 5TITUS DESV 8TITUS DESV 5
TITUS DESV 6TITUS DESV 10TITUS DESV 9TITUS DESV 4
TITUS DESV 10TITUS DESV 4TITUS DESV 12TITUS DESV 7
DESIGN CFMCOOLING
MAX
240100072025060025030603401050810150235091015012303802670
HEATINGMAX
753002207518075
10531524560
27545370115
DESIGNMIN
753002207518075
10531524560
27545370115
CAPACITY (CFM)
MAX.
35014001050350900350
50014001050225
14002252000650
MIN.
632211676313263
6622116750
2215030499
HEATING COILCAP.MBH
------------
--------
9.81.613.24.1
GPM
------------
--------
10.51.10.5
APD"W.C.
------------
--------
0.160.020.160.07
WPDFT
------------
--------
0.160.150.250.15
MAX. NC @DESIGN MAX.
353635353435
3136
33
23333837
INLETSIZE
5109585
61094
104127
OUTLETSIZE
12 X 814 x 12.514 X 12.5
12 X 812 X 1012 X 8
12 X 814 x 12.514 X 12.5
12 X 8
14 x 12.512 X 816 X 1512 X 10
REMARKS
AAAA
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN02/07/14DESIGN DEVELOPMENT04/04/1480% CD SET / PERMIT SET05/02/14100% CD SET
CSM WELCOMECENTER
MEP0.02
MECHANICALSCHEDULES
COLORADO SCHOOL OF MINESGOLDEN, CO
1219
M
1
1.8
2
A
PROVIDE MPS PIPE GUIDE AT 6'MAXIMUM FROM (N) EXPANSIONJOINT.
PROVIDE MPS PIPE GUIDE AT 6'MAXIMUM FROM ANCHOREDELBOW.
MPS PIPE GUIDE AT 30'INTERVAL FROM (N)EXPANSION JOINT.
PROVIDE MPR PIPEGUIDE AT 3' MAXIMUMFROM (N) EXPANSIONJOINT.
MPR PIPE GUIDE AT 15'INTERVAL FROM (N)EXPANSION JOINT.
PROVIDE CHS AND CHR PIPEGUIDES AT 12' MAXIMUM FROM (N)EXPANSION JOINT.
PROVIDE CHS AND CHR PIPEGUIDES AT 40' INTERVAL FROM (N)EXPANSION JOINT.
MPR PIPE GUIDE AT 15'INTERVAL FROM (N)EXPANSION JOINT.
MPR PIPE GUIDE AT 15'INTERVAL FROM (N)EXPANSION JOINT.
RE: MP3.00 FOR EXPANSION JOINTAND ANCHOR REQUIREMENTS ATCORNER.
RE: MP3.01 FOR EXPANSION JOINTAND ANCHOR REQUIREMENTS ATTUNNEL TERMINATION.
PROVIDE MPR PIPE GUIDE AT 3'MAXIMUM FROM ANCHOREDELBOW.
MPS PIPE GUIDE AT 30'INTERVAL FROM ANCHOREDELBOW.
MPS PIPE GUIDE AT 30'INTERVAL FROM ANCHOREDELBOW.
MPR PIPE GUIDE AT 15' INTERVALFROM ANCHORED ELBOW.
MPR PIPE GUIDE AT 15' INTERVALFROM ANCHORED ELBOW.
MPR PIPE GUIDE AT 15' INTERVALFROM ANCHORED ELBOW.
MPR PIPE GUIDE AT 15' INTERVALFROM ANCHORED ELBOW.
MPR PIPE GUIDE AT 15' INTERVALFROM ANCHORED ELBOW.
MPR PIPE GUIDE AT 15' INTERVALFROM ANCHORED ELBOW.
MPS PIPE GUIDE AT 30'INTERVAL FROM ANCHOREDELBOW.
MPS PIPE GUIDE AT 30'INTERVAL FROM ANCHOREDELBOW.
MPS PIPE GUIDE AT 30'INTERVAL FROM ANCHOREDELBOW.
PROVIDE CHS AND CHR PIPE GUIDES AT12' MAXIMUM FROM ANCHORED ELBOW.
CHS AND CHR PIPE GUIDES AT75' INTERVAL FROMANCHORED ELBOW.
CHS PIPE GUIDE AT 4' FROM45 DEGREE ELBOW.
CHR PIPE GUIDE AT 75' FROMANCHORED ELBOW.
(E) TUNNEL PIPING
(N) TUNNEL PIPING
PROVIDE WATSON MCDANIEL MODELWD600 STEAM TRAP. 250 LBS/HR, 1/2",125PSIG INLET PRESSURE, 0PSIG OUTLETPRESSURE. RE: SPECIFICATIONS ANDDETAILS FOR END OF MAIN STEAM TRAPREQUIREMENTS.
RE: MP3.00 FOR EXPANSION JOINTAND ANCHOR REQUIREMENTS ATCORNER.
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
I.E. 5780'
I.E. 5781'
DIRECT BURIED 4" CHS/RFROM CAMPUS TUNNEL TOBASEMENT MECHANICALROOM
DIRECT BURIED 3" MPSAND 2" MPR FROM CAMPUSTUNNEL TO BASEMENTMECHANICAL ROOM
DIRECT BURIED 6" EMPTY SDR 35PVC PIPE FROM CAMPUS TUNNELTO BASEMENT MECHANICALROOM
PROVIDE EPANSIONLOOPS FOR DIRECTBURIED MPS AND MPR
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN
02/07/14DESIGN DEVELOPMENT
04/04/1480% CD SET / PERMIT SET
05/02/14100% CD SET
WELCOME CENTER
MP2.00
TUNNEL PIPING
PLAN
COLORADO SCHOOL OF MINES
GOLDEN, CO
1219
1/8" = 1'-0"1
MECHANCIAL AND PLUMBING TUNNEL PLAN
GENERAL NOTES:
KEY NOTES:
1
(SOME KEY NOTES MAY
NOT APPLY TO THIS SHEET)
SANITARY PIPING UP
SANITARY PIPING DN
SANITARY PIPING UP & DN
GW PIPING UP
GW PIPING DN
GW PIPING UP & DN
SANITARY VENT UP
SANITARY VENT DN
SANITARY VENT UP & DN
CW PIPING UP
CW PIPING DN
CW PIPING UP & DN
HW PIPING UP
HW PIPING DN
HW PIPING UP & DN
HWC PIPING UP
HWC PIPING DN
HWC PIPING UP & DN
CW & HW PIPING UP
CW & HW PIPING DN
DOMESTIC WATER METER
3" DOMESTIC WATER BACKFLOWPREVENTER
DOMESTIC WATER PRESSUREREDUCING STATION
4" FIRE BACKFLOW PREVENTER
FIRE SERVICE PRESSUREREDUCING STATION
4" FROM FIRE DEPARTMENTCONNECTION, CONNECT TO FIREPROTECTION SYSTEM
PIPING UP TO FLOOR SINK/DRAIN
STORM PIPING UP
STORM PIPING DN
STORM PIPING UP & DN
OVERFLOW PIPING UP
OVERFLOW PIPING DN
OVERFLOW PIPING UP &DN
OVERFLOW PIPING DOWN ANDTHRU WALL TO DOWNSPOUTNOZZLE +12" AFG
SANITARY PIPING UP TOPLUMBING FIXTURES
PIPING UP TO CLEANOUT
CW HEADER
HW HEADER
CW & HW HEADER
1/2" CW & HW TO EACH LAV/SK
1. REQUIRED PIPE SIZES ARE SHOWNNEXT TO KEY NOTE.
2.PROVIDE BALL VALVE SHUTOFF AND12"X12" ACCESS PANEL AT EACHSHOCK ABSORBER (SA). PANELLOCATION TO BE VERIFIED ANDCOORDINATED WITH ARCHITECT.
3. PROVIDE 12"X12" ACCESS PANEL ATALL TRAP PRIMER VALVES.COORDINATE WITH ARCHITECT. IFPOSSIBLE, LOCATE TRAP PRIMERVALVES NEAR SHOCK ABSORBERSFOR USE WITH (1) ACCESS PANEL.
4. ALL FLOOR DRAINS ARE 2" FD-1UNLESS NOTED OTHERWISE.
5. ALL FLOOR SINKS ARE 3" FS-1 WITH3/4" GRATE UNLESS NOTEDOTHERWISE.
6. MOUNT HOSE BIBBS IN MECHANICALROOM AT 42" ABOVE FLOOR.
7. ALL INVERT ELEVATIONS (IE) SHALLBE FIELD VERIFIED BEFORE ANYPIPING IS INSTALLED.
8. ALL CIRCUIT SETTERS SHALL BESET AT 1.0 GPM UNLESS NOTEDOTHERWISE.
9. ALL FIRE PROTECTION DESIGNDOWNSTREAM OF THE BACKFLOWPREVENTER IS BY THE FIREPROTECTION CONTRACTOR.
10. PROVIDE WALL CLEANOUT ATBASE OF ALL STORM AND SANITARYRISERS AND AS REQUIRED BY CODE.
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
KEYNOTESKey
Value Keynote Text
M
A TUNNEL PIPING SUPPORT DETAIL
NO SCALE
UNISTRUT SUPPORT SYSTEM.
RE: SPECIFICATIONS. (TYP.)
SECURE TO CEILING WITH 1/4" PLATE (TYP.)
STEEL ANGLE REINFORCING
PER MANUFACTURER'S
RECOMMENDATIONS (TYP.)
SECURE TO FLOOR WITH 1/4" PLATE(TYP.)
STRUCTURAL BOX CULVERT. RE:
STRUCTURAL AND CIVIL DRAWINGS. (TYP.)
PIPE ROLLER SECURED TO
UNISTRUT SYSTEM (TYP.)
PIPE SADDLE WELDED TO PIPE WITH
INSULATION INSERTS TO MATCH EXTERIOR
PIPE INSULATION THICKNESS (TYP.)
SPACERS AS REQUIRED TO ALLOW
MINIMUM 1/2" CLEARANCE BELOW
PIPE ROLLER. (TYP.)
7'-0"
6'-0"
14" CHR
6" MPS
3" MPR
14" CHS
SECURE TO WALL WITH ANGLE
STEEL SUPPORT (TYP.)
(E) TUNNEL PIPING
(N) TUNNEL PIPING
(E) BRANCH PIPING
(N) TUNNEL PIPING STACKEDVERTICALLY6" MPS3" MPR
(E) SLIP EXPANSION JOINTS
(E) PIPE ANCHORS
(E) TUNNEL PIPING STACKEDVERTICALLY14" CHR14" CHS6" MPS3" MPR
(E) ISOLATION VALVES
PROVIDE SLIP EXPANSION JOINTS:6" MPS - ATS MODEL TP2F-131-4-350H-BRZ-B3" MPR - ATS MODEL TP2F-131-4-350H-BRZ-B
PROVIDE PIPE ANCHORS AT ELBOW FOREACH OF CHR, CHS, MPS, AND MPR.
PROVIDE PIPE SUPPORT RACKS AT10' ON CENTER. RE: DETAIL A.
GENERAL NOTE:RE: MP2.00 FOR PIPE GUIDE LOCATIONSAND SPACING REQUIREMENTS.
T-01
EF
36"x12"EA
24"x12"EA
PROVIDE 24"X12" EA PLENUM ANDCONNECT TO EXISTING OPENING IN TUNNELCEILING. PROVIDE NEW MOTORIZEDDAMPER AND INTERLOCK WITH FAN. RE:MEP SCHEDULES.
CLOSE AND LOCKOUT (E) CHS/RBYPASS.
RE: MECHANICAL DETAILS
(N) TUNNEL PIPING STACKEDVERTICALLY14" CHR14" CHS
PROVIDE PIPE ANCHORS AT ELBOW FOREACH OF CHR, CHS, MPS, AND MPR.
PROVIDE SLIP EXPANSION JOINTS:14" CHR - ATS MODEL TP2F-121-4-350H-BRZ-B14" CHS - ATS MODEL TP2F-121-4-350H-BRZ-B
PROVIDE 2" CHS/R BYPASS WITHISOLATION VALVE FOR SYSTEMFLUSHING RE: SPECIFICATIONSECTION 232113 HYDRONIC PIPING
ROUTE CHWS/R LINES ACROSS TUNNELSOUTH OF EXISTING MANHOLE. DO NOTBLOCK EXISTING MANHOLE.
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN
02/07/14DESIGN DEVELOPMENT
04/04/1480% CD SET / PERMIT SET
05/02/14100% CD SET
WELCOME CENTER
MP3.00
TUNNEL ENLARGED
PLANS
COLORADO SCHOOL OF MINES
GOLDEN, CO
1219
1/4" = 1'-0"1
ENLARGED MECHANICAL AND PLUMBING TUNNEL PLAN 1
A TUNNEL PIPING SUPPORT DETAIL
NO SCALE
UNISTRUT SUPPORT SYSTEM.
RE: SPECIFICATIONS. (TYP.)
SECURE TO CEILING WITH 1/4" PLATE (TYP.)
STEEL ANGLE REINFORCING
PER MANUFACTURER'S
RECOMMENDATIONS (TYP.)
SECURE TO FLOOR WITH 1/4" PLATE(TYP.)
STRUCTURAL BOX CULVERT. RE:
STRUCTURAL AND CIVIL DRAWINGS. (TYP.)
PIPE ROLLER SECURED TO
UNISTRUT SYSTEM (TYP.)
PIPE SADDLE WELDED TO PIPE WITH
INSULATION INSERTS TO MATCH EXTERIOR
PIPE INSULATION THICKNESS (TYP.)
SPACERS AS REQUIRED TO ALLOW
MINIMUM 1/2" CLEARANCE BELOW
PIPE ROLLER. (TYP.)
7'-0"
6'-0"
14" CHR
6" MPS
3" MPR
14" CHS
SECURE TO WALL WITH ANGLE
STEEL SUPPORT (TYP.)
PROVIDE CHS PIPING OFFSET DOWN INTUNNEL TO ALLOW EXISTING SANITARY LINETO PASS THROUGH TUNNEL WALLS. RE: CIVILDRAWINGS.
GENERAL NOTE:RE: MP2.00 FOR PIPE GUIDE LOCATIONSAND SPACING REQUIREMENTS.
(E) SANITARY LINE
TERMINATE 14" CHR, 14" CHS, 6" MPS,AND 3" MPR WITH ISOLATION VALVE FORFUTURE CONNECTION.
4" CHR, 4" CHS, 3" MPS, AND 2" MPR TAPSTO WELCOME CENTER. PROVIDEISOLATION VALVES IN TUNNEL WITHFLEXIBLE METAL HOSE CONNECTION ONBUILDING-SIDE OF ISOLATION VALVE.
DIRECT BURIED CHILLED WATERAND STEAM TO BUILDING.
PROVIDE SLIP EXPANSION JOINTS WITH ANCHOR:14" CHR - ATS MODEL TP2F-122-4-350H-BRZ-B14" CHS - ATS MODEL TP2F-122-4-350H-BRZ-B6" MPS - ATS MODEL TP2F-132-8-350H-BRZ-B3" MPR - ATS MODEL TP2F-132-4-350H-BRZ-B
PROVIDE PIPE SUPPORT RACKS AT10' ON CENTER. RE: DETAIL A
(N) TUNNEL PIPING STACKEDVERTICALLY14" CHR14" CHS
PROVIDE 2" CHS/R BYPASSWITH ISOLATION VALVE ANDBALANCING VALVE. RE:SPECIFICATION SECTION232113 HYDRONIC PIPINGFOR FLUSHINGREQUIREMENTS.
PROVIDE WATSON MCDANIEL MODEL WD600STEAM TRAP. 250 LBS/HR, 1/2", 125PSIGINLET PRESSURE, 0PSIG OUTLET PRESSURE.RE: SPECIFICATIONS AND DETAILS FOR ENDOF MAIN STEAM TRAP REQUIREMENTS.
(N) TUNNEL PIPING STACKEDVERTICALLY6" MPS3" MPR
6" EMPTY SDR 35 PVC PIPE
PROVIDE 1" CHS/R BYPASS WITHISOLATION VALVE FOR SYSTEMFLUSHING. RE: SPECIFICATION SECTION232113 HYDRONIC PIPING
All information appearing herein shall not be duplicated, discharged orotherwise used without the written consent of Sink Combs Dethlefs
Issues/Revisions: Date:
SCD Project No.:
10/16/13SCHEMATIC DESIGN
02/07/14DESIGN DEVELOPMENT
04/04/1480% CD SET / PERMIT SET
05/02/14100% CD SET
WELCOME CENTER
MP3.01
TUNNEL ENLARGED
PLANS
COLORADO SCHOOL OF MINES
GOLDEN, CO
1219
1/4" = 1'-0"1
ENLARGED MECHANICAL AND PLUMBING TUNNEL PLAN 2