    1.Outline of operation

    This control equipment is consisted of combinedcontrols of the proportional position control and

    the on/o control. Namely, during the burner isburning, detecting the boiler steam pressure, thecombustion rate can be continuously regulated,according to the signal value of the pressureconverter, which is used as a controlling despatch

    device or when the steam pressure is raised to anupper limit value, the burner can be automaticallye!tinguished by means of pressure switch or whendropped to a lower limit value, the burner can beautomatically ignited.

  • 8/9/2019 Mithun,Mike,Kiru

    3/24

    The following safeguard devices are provided " no voltage of power circuit low water level of boiler decrease of oil temperature overload of forced draft fan #ame failure during combustion low oil pressure of fuel oil.

    $hen any of the above safeguard devices hasdetected abnormal condition, the burner is to beautomatically e!tinguished, and even if the startingswitch has turned to the start, the burner cannot beignited again, unless the abnormal conditionchanges into the normal operational condition.

  • 8/9/2019 Mithun,Mike,Kiru

    4/24

    %. &lassi'cation into bloc( units

    This equipment is classi'ed into the followingbloc(s"

    Timer )nit*gnition )nit+lame etecting )nit-roportional positon controlling )nitwitch and pilot lamp )nit

  • 8/9/2019 Mithun,Mike,Kiru

    5/24

    . -rocedure of operation

    +irst, it should be con'rmed that everydamaging factors in the piping arrangementhas been perfectly removed by #ashing it.

    The voltage and the frequency, etc. of theelectric source should be chec(ed that theyhave been correctly connected with theequipment.

  • 8/9/2019 Mithun,Mike,Kiru

    6/24

    .1 T0 T

    2 +irst it should be con'rmed that the electricsource pilot lamps, -31 and -3% are being lighted.

    2 tarting the oil pump and the oil heater, the oilheated to the preset temperature, should becirculated through the equipment.

    2$hen the oil thermometer has shown the presettemperature, the start switch , *4 , should be

    turned to start2*t should be con'rmed that the low oil temperaturepilot lamp, -3% , is not being lighted

    2The fan will be started and the gas in the furnacewill be purged.

  • 8/9/2019 Mithun,Mike,Kiru

    7/24

    20fter 56 secs the fuel oil valve %17 will beopened and the burner will #ame up.This valveis being opened during 6 secs , from 56895secs.

    2 ince the #ame detecting device , + willdetect it , and then the continuous combustionwill be begun and primary air damper open.0fter the #ame present pilot lamp -39 hasbeen lighted , the automatic combustion willbe performed, increasing or decreasing thecombustion rate by means of the signal from

    the pressure converter or the boiler steampressure.2The conditions of each switches and pilot lamps duringnormal combustion are as follow8The timer , 5: ,is stopped at ;; seconds position.

    8The electric source pilot lamps , -31 and -3% and the #amepresence pilot lamp , -39 are lighted.

    8The by

  • 8/9/2019 Mithun,Mike,Kiru

    8/24

    .% TO-2The position of the start switch *4 is to bechanged over to the stop

    2Then the fuel oil valve, %17, will be closedimmediately, and stops the combustion.

    2The +. . fan will purge for 95 seconds beforestopping.

    2-ilot lamps -31 and -3% are lighted.

    2Timer 5: is set to =ero. 0nd the proportional

    control device to low combustion rate.

  • 8/9/2019 Mithun,Mike,Kiru

    9/24

    . &ase of +lame +ailure during

    combustion"

    2+uel valve %17 to changed to &irculatingposition, after purging for 95 secs, the ignitionprocedure is performed again.

    2*f it does not get ignited, it is put into 3oc(out-osition, -35 is ignited and bu>>er is sounded.

    2The gas in the burner is purged for 9?seconds, and burner is stopped.

    2 The burner cant start from this position

    unless the reset button is pressed.

  • 8/9/2019 Mithun,Mike,Kiru

    10/24

    .5 &ase of 3ow Oil Temperature during

    &ombustion"

    2*f the thermostat senses low oil temperature

    than the set pressure, the relay 5 is activatedalong with -3 and bu>>er is sounded.

    2The furnace is purged for 95 seconds and thenthe burner is stopped.

  • 8/9/2019 Mithun,Mike,Kiru

    11/24

    .9 &ase of Overload of forced draft fan"

    2 The fuel valve %17 is closed and the oil pathis set to circulation.

    2+lame is e!tinguished and the -35 is ignitedwith a bu>>er.

    2The timer is set bac( to =ero.

    2 eset is required for @lectro magnetic switchand the burner reset button.

  • 8/9/2019 Mithun,Mike,Kiru

    12/24

    .;&ase of boiler high and low water level"

    2*f the water level is low than the preset valuethen -3; and alarm are activated.

    24urner is stopped if the low level further

    reduces.

    2 The burner is restarted again after purging.

  • 8/9/2019 Mithun,Mike,Kiru

    13/24

    5. ign and &ounter -lan for failure"

    The equipment cannot start, even if the startswitch has turned to AstartB

    @quipment can start, but it cannot be ignited.

    @quipment is spontaneously stopped duringcombustion.

    @ven if the start switch *4 is in stop position,the equipment is not stopped.

  • 8/9/2019 Mithun,Mike,Kiru

    14/24

    5.1 The equipment cannot start, even if

    the start switch has turned to AstartB

    2+irst, ascertain the lights out of the low oil temperature

    pilot lamp -3 .20scertain the normal level of the boiler water.2*t should be ascertain that the boiler steam pressure isnot at the upper limit, that is at which the burner ise!tinguished automatically by means of on/o controlby the steam pressure gauge.

    20scertain the light of the electric source pilot lamps-31 and -3%.20scertain the perfectness of every fuses. $hen thefuel is cut o , the pilot lamp -3% 'tted on the upper partof the panel does not light.2Try to push the reset button.

  • 8/9/2019 Mithun,Mike,Kiru

    15/24

    20fter the above described ascertainments have beencompleted, the circuit of the outer interloc( connections aretried to short circuit.

    *f the equipment start at this time, some of theapparatus connected to the outer interloc( connection are ina failure

    The % 7 contacts are to be short circuited. *f the equipmentstarts at this time, the oil temperature regulating thermostatis in a wrong condition, and therefore it should be readCustedor e!changed. 2$hen it does not start by the short circuit of

    % 7 and 9+4 contacts should be short circuited. *f it isstarted by this, the 4 contact of the relay 9+ is wrong, andtherefore it should be inspected and adCusted or e!changed.

    2The 4 contact of the outer interloc( contact are performed inthe same inspection method, and the contact of the timer,the by8pass switch and the start switch *4 should beinspected and e!changed respectively.

    2$hen it is not started by the above inspection method, therelay coil 5 and the circuit line will be cut o or theircontacts will be wrong and so it is necessary to repair ore!change these parts.

  • 8/9/2019 Mithun,Mike,Kiru

    16/24

    5.% @quipment can start, but it cannot beignited.

    20scertain that the spar( is being produced.

    2+or D.@. igniter, refer the e!planation note, 'led in the rear.

    2$hen this spar( discharge of D.@. igniter have beencon'rmed, it may be decided that cause of failure is in themain burner.

    2The oil temperature should be chec(ed, whether it is at thepredetermine value by means of the thermometer 'tted onthe header outlet or the actual measurement. *f theindication of the thermometer is wrong, it should bereadCusted or e!changed.

    20scertain the operation of the fuel oil valve solenoid%17.0fter 56 sec from start, the sound AbangB is heard and thesolenoid is to wor( so as to open the fuel oil valve.

  • 8/9/2019 Mithun,Mike,Kiru

    17/24

    2*f the solenoid does not wor(, inspect the circuit if thecircuit is bro(en, e!change it. :oreover this solenoid isthe standard one of the ma(er.

    20fter this solenoid has been e!changed or repaired,ascertain that it is in a relative position such as conditionthat the valve arm is being fully pushed into the attractedpiece, being fully contacted with the '!ed piece.

    2*f there is a roar or an e!traordinary generation of heat,they are the sign that the relative position is slipped downfrom regular position.

    2The dirtiness of the atomi>er and the position of the burneretc should be ascertained and inspected.

    2$hen the con'rmation and repair of the above descriptionhave been completed and the fuel oil valve wor(s, thereis no clogging in the oil pipelines and no lea(age in thepipe arrangement and valves etc. $hen the [email protected] been ignited and the valves have been opened, the

    fuel oil being sprayed should ignite the burner.

  • 8/9/2019 Mithun,Mike,Kiru

    18/24

    5. @quipment is spontaneously stoppedduring combustion.

    2$hen the #ame is e!tinguished and the equipment isstopped, they may be caused by the factors above E5.1and 5.%F

    2*t should be ascertain that the stop is not caused by thepressure switch owing to the boiler steam pressure raisedup to the set upper limit.

    20scertain that the water level in the boiler is in normalcondition.

    20scertain than the fan is running.

    2 *f the oil temperature is lowered the burner stops.2$hen the equipment is stopped in spite of the #ame is

    burning, it should be run opening the front door of thecontrol panel and switching on the bypass switch,immediately after the main burner has been ignited. *f itcan be run at this time, the ignition detection devices +and + are incorrect.

  • 8/9/2019 Mithun,Mike,Kiru

    19/24

    2The detection part should be withdrawn and the lens glassetc should be cleaned, and wiped.

    2The contact of the pin part of the relay unit should also beinspected.

    2:oreover, the characteristics and the speci'cation of the&ds should be referred to the appended 'gures.

    2*t should be ascertained whether the settlement of the trip

    percentage is good or not.

    2*n order to see whether the overload relay the electro8magnetic switch for the +. . fan motor is wor(ing or not,push the reset.

    2@ven if the front glass, section of the &ds is being bro(en,there is no bad in#uence upon the wor( now.

  • 8/9/2019 Mithun,Mike,Kiru

    20/24

    5.5 @ven if the start switch *4 is in stopposition, the equipment is not stopped.

    2Opening the door of the control panel, try tocut o the connection of either 14 switch.

    2$hen the equipment stops in this case, thestart switch *4 will be failed, and therefore

    inspection and adCustment or renewal of theswitch should be done.

  • 8/9/2019 Mithun,Mike,Kiru

    21/24

    9. 0bout the equipment 'tted with manualoperation switch.

    9.1. $hen the start switch *4 has been setto stop, the following steps can beoperated by the manual switch"

    2 tart and stop of fan G5 89%+H

    2 tart and stop of spar( G5 < * )H

    2Opening and closing of fuel oil valve G5 8% 7H The obCective of this handling is to con'rm the wor(or to use for the sa(e of an e!traordinary occasion,and therefore it is desirable not to use in normalcondition.

  • 8/9/2019 Mithun,Mike,Kiru

    22/24

    team 4low &ircuit"0 steam device is installed in order to blow residual oil

    out of the sprayer body.

    &onditions" The heavy oil pump operates and the oil pressure is 1I to%1 Jg at circulation.Gif the oil pressure is not applied to the control valve,steam may blow into the oil side.H

    Operation"$hen the steam blow switch on the panel is set atAblowB, at e!tinction Gincl. O due to boiler pressureincrease, intentional stoppage, accidents, etc.H andmis'ring, the cam timer rotates after ;; sec. 0nd thesteam solenoid valve opens 6% sec. 3ater, then steamenters into the sprayer body to purge the residual oil.G etting time is about 1K sec.H The D@ ignitor alsooperates on activation of the solenoid valve.ubsequently, after8purge is done and the fan stops 1%K

    sec. 3ater.

  • 8/9/2019 Mithun,Mike,Kiru

    23/24

    election of blow circuit"

    *t can be considered that the burner is turned on o at all timesduring anchorage, it is practical to set the blow circuit switch atAO++B during anchorage.

    team is not blown but after8purge is done after ;; sec.$hen predicted that automatic additional burning is requiredduring navigation, set the steam blow changeover switch atA43O$B, then the above steam blow will be done.$hen heavy oil 0 is used, steam blow is necessary.

    :aintenance"

    *n case of steam lea(age through solenoid valve, completelytighten up the chec( valve.team solenoid valve and reverse drain solenoid valve,completely tighten up the chec( valve.team solenoid valve and reverse drain solenoid screwed chec(valve, completely close the chec( valve to stop inCection of oilfrom the drain solenoid valve outlet.