mjt 314 updated - 3.imimg.com · overcurrent & earthfault protection key features of mjt 314 b...
TRANSCRIPT
DescriptionThe MJT 314 B (Self powered numerical overcurrent protection)
& MJT 314 C (Self powered with series trip numerical overcurrent
protection) relay combines the power and flexibility of
microprocessor technology with decades of experience in the
field of protection. A wide range of protection elements and
characteristics are supplemented by advance features such as
metering, fault recorder and communication.
MJT 314 (B&C) offers inverse time and definite time over current
protection for phase fault and earth fault with communication.
DesignThe MJT Protection unit consists of the following modules within
its dimensions.
• Input Module
• Power Supply and Output Relay module
• Measuring Module & communication interface
• Front Fascia
• Status input module
The four modules viz. Input, Power supply, Measuring and status
input modules are plugged into the Front fascia which houses
switches, LEDs and LCD display for the human machine
interface. All PCB s are well protected from one another and from
external environment with best shielding for better
electromagnetic compatibility and housed in the enclosed
chassis, which is withdrawable from the outer case.
The draw-out case is provided with the required CT shorting
contacts.
Applications• Distribution feeders
• Transmission lines
• AC machines
• Capacitor banks
• Transformers
• Used in Compact MV Switch Boards with CB
• Where Auxillary Voltage is not available or guaranteed
Genesis Range
MJT 314 B&C
e3
Ele
gant
Easy to Use
Efficient
Numerical Self PoweredOvercurrent & EarthfaultProtection
Key Features of MJT 314 B(Self Powered Numerical Over Current Protection)
• Charged capacitor output is available to actuate low energy
magnetic actuator in the Breaker(12-24V DC output-
0.25 joules)
• In absence of low energy magnetic actuator, the breaker
can be tripped using power from external power pack. For
the same one N/O contact is available in the relay
Key Features of MJT 314 C(Self Powered with Series Trip Numerical Over Current
Protection)
• This relay comes with two boxes, One with main Relay and
other with series Trip element .
• Output of the main relay has been modified suitably to
energize, special B33 type of series trip element three
numbers(coils are connected in series). The break contacts
of this will be used to divert the C.T current to the series
trip coils of the breaker.
Numerical Overcurrent &Earthfault Protection - MJT 314 (B&C)
Common Features for MJT 314
(B&C)
• Two group settings
• Storage of two fault records
• Internal real time clock
• Suitable for flashing faults
• Gets power from the C.T input itself. (No auxiliary D.C
supply necessary)
• The current measurement on relay is available when current
flows more than 400mA on all the three phases
• The Back light of the LCD will glow when current flows
more than 750mA
• To set the relay or read the fault records (in absence of
current input ) a separate battery box with inbuilt battery
charger is available, external to the relay. (order to be placed
separately for this)
• Wide range of current settings
• Self diagnostics feature
• Currents-Ir,Iy,Ib,Ie
• Readable human machine interface with Backlit LCD
display
• LED indications
• Push buttons for viewing/editing the settings and resetting
• Data communication using IEC 60870-5-103 Protocol
• RS485 communication electrical terminals at rear
Protection• IDMTL / DTL phase fault overcurrent ( 50 / 51 )
• IDMTL / DTL earth fault overcurrent ( 50N /51N)
• Dual DC transient free highsets for phase fault & earth fault
• True RMS measurement
• Six characteristics
ControlThe relay has the following output contacts
MJT 314 B
• Normally Open 1 N/O
• Capacitor Charged Outputs 1 N/O
MJT 314 C
• Capacitor Charged Outputs 1 N/O
Typical Wiring Diagram for MJT314 B
Typical Wiring Diagram for MJT314 C
Wiring Diagrams
Technical InformationCT Input Rating 1A & 5A
Frequency 50Hz
Auxiliary Supply
Self Powered from CT input
Protection Settings
Phase Fault 0.5xIn to 2xIn Δ 0.01 In
Earth Fault 0.2xIn to 0.8xIn Δ 0.01 In
Highset1 Phase Fault 4xIn to 20xIn Δ 0.5 In, off
Highset1 Earth Fault 0.5xIn to 12xIn Δ 0.5 In, off
Highset2 Phase Fault 4xIn to 20xIn Δ 0.5 In, off
Highset2 Earth Fault 0.5xIn to 12xIn Δ 0.5 In, off
P/F Time Multiplier 0.025 to 1.6 Δ 0.001
E/F Time Multiplier 0.025 to 1.6 Δ 0.001
P/F DTL 0 Secs to 20 Secs Δ 0.01 Secs
E/F DTL 0 Secs to 20 Secs Δ 0.01 Secs
P/F Highset1 DTL 0 Secs to 20 Secs Δ 0.01 Secs
E/F Highset1 DTL 0 Secs to 20 Secs Δ 0.01 Secs
Highset2 Instantaneous
Reset Time 0 to 60 Secs Δ 1 sec
Inverse Characteristics
Operating time can be calculated as follows:
where
I=fault current
Is=current setting
Tm=time multiplier
Si3 - k =0.14, a= 0.02
SI1 - k =0.0613, a= 0.02
VI - k =13.5, a= 1.0
EI - k =80.0, a= 2.0
LTI - k =120.0, a= 1.0
Contact Rating
Carry continuously 5A AC rms or DC
Make & Carry 20A for 0.2sec
Break Resistive 75W DC
Inductive 50W DC
@L/R#40msec
with a maximum of 300V DC
Resistive 1250 VA AC
Inductive 250 VA @ PF #0.4
Indication
Green LED Protection healthy
Orange LED Starter
Red LED Trip
Red LED (3mm) Submenu
16x2 Alphanumeric LCD display for settings, metering and fault
data
Burden
AC Current Input
5 A Rating #15 VA
1 A Rating #3 VA
Auxiliary input
Quiescent (typical) 5 W (DC)
12VA (AC)
Environmental
Temperature IEC 60068-2-1/2
Operating range -10° C to +55°C
Storage range -25° C to +70°C
Humidity IEC 60068-2-3
4 days at 40°C and 93%RH
Transient Overvoltage IEC 60255-5
5KV, 1.2/50Fs, 0.5J between all terminals and earth or between
any two terminals without damage or flashover
Insulation IEC 60255-5
2.0 KVrms for 1 min between all terminals and earth
2.0 KVrms for 1 min between independent circuits
1.0 KVrms for 1 min across normally open contacts
High frequency Disturbance IEC 60255-22-1 Class III
2.5 KV Common (Longitudinal) mode #3%
1.0 KV Series (Transverse) mode #3%
Electrostatic Discharge IEC 60255-22 -2 Class III
6 KV Contact Discharge #5%
8 KV Air Discharge #5%
Radio Frequency Interference IEC 60255-22-3 Class III
20 MHz to 1000 MHz, 10V/m #3%
Fast Transient
2 KV, 5/50 ns, 2.5 kHz repetitive IEC 60255-22-4 Class III #3%
Vibration (Sinusoidal) IEC 60255-21-1 Class I
Shock and Bump IEC 60255-21-2 Class I
Mechanical Classification6Durability in excess of 10 operations
The policy of EASUN REYROLLE is one of continuous improvement and development. The company therefore reserves the right to supply equipment which may differ slightly
from that described and illustrated in the publication.
ERL
ERL Group Corporate Office#389, “Rasukumaki”, Hulimavu, Begur Hobli, Bannerghatta Road, Bangalore – 560 076, IndiaTel: +91 80 6717 7000 / 7001 Fax: +91 80 6717 7002 Email: [email protected]
Global Marketing OfficesGermany, Canada, Hong Kong, Thailand, South Africa, UAE, Brazil, Peru & USA
Global Manufacturing CentersIndia, Canada & Germany
Global Technology CentersIndia, Canada & Germany
Marketing Offices in IndiaBangaloreTel: +91 80 6717 7000/01Fax: +91 80 6717 7002Email: [email protected]
BhopalFax: +91 755 2684221Email: [email protected]
ChennaiTel: +91 44 2434 6425/7608Fax: +91 44 2434 6435Email: [email protected]
KolkataTel: +91 33 2284 8320Fax: +91 33 2284 8326Email: [email protected]
MumbaiTel: +91 22 2285 5415/ 2202 2270Fax: +91 22 2285 5703Email: [email protected]
NoidaTel: +91 120 2405 741/42/43Fax: +91 120 2405 744Email: [email protected]
SecunderabadTelfax: +91 40 2781 7847Email: [email protected]
FA
CT/M
JT3
14
B&
C /0
1-1
1/R
EV 3
.0.
www.easunreyrolle.com
MODULAR CASES: SIZES 6
SIZE 6 CASE
A B C
155 151 130.5
Note:1. All dimensions are in mm2. All dimensions are measured equidistant from centre line3. Maximum depth of equipment inside panel : 200mm
Ordering InformationBattery sourceMJT 314 B or MJT 314 CCT Rating 1 Amp or 5 Amps
QualificationISO 9001-2008
Cutout Details