    ZAWTIKA DEVELOPMENT PROJECT PHASE 1A

    EPCIC OF ZAWTIKA ONSHORE PIPELINE

    CONTRACT NO. : IMO-EMP-CT-10-0018

    LIGHTING CALCULATION FOR ZOC

    C2 05-Feb-13 LH Issued for Purchase GB WQL HJ SB

    B1 22-Feb-12 LH Issued for Approval GB WQL HJ SB

    A2 09-Jan-12 LH Issued for Review GB WQL HJ SB

    A1 09-Dec -11 LH Issued for Review GB WQL HJ SB

    REV DATE BY DESCRIPTION

    CHECK APPR. CHECK APPR.

    CPPAPPROVAL

    COMPANYAPPROVAL

    REVISION CODE: A = Issued for Review (IFR); B = Issued for Approval (IFA); C = Approved for Construction (AFC)

    TOTAL OR PARTIAL AND / OR UTILIZATION OF THIS DOCUMENT ARE FORBIDDEN WITHOUT PRIOR WRITTENAUTHORIZATION OF THE COMPANY

    PTTEP INTERNATIONAL LIMITED

    CPP

    ZAWTIKA DEVELOPMENT PROJECT PHASE 1A

    EPCIC OF ZAWTIKA ONSHORE PIPELINE

    MM-ZTK-1A-ZOC-ELE-CAL-5002REV CLASS

    C2 1

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    2/419

    PTTEP International Limited Page 2/11

    Zawtika Development Project Phase 1A Document : MM-ZTK-1A-ZOC-ELE-CAL-5002

    EPCIC of the Zawtika Onshore PipelineRevision : C2

    Date :05-Feb -132

    Table of Contents1.0 SCOPE............................................................................................................................................................ 3

    2.0 REFERENCE DOCUMENTS......................................................................................................................... 3

    3.0 CODES AND STANDARDS.......................................................................................................................... 4

    4.0 SITE AND ENVIRONMENTAL CONDITIONS............................................................................................. 4

    5.0 LIGHTING SYSTEM....................................................................................................................................... 4

    5.1 LIGHTING SYSTEM CONFIGURATION.............................................................................................................................. 4

    5.2 ILLUMINATION LEVELS................................................................................................................................................ 4

    5.3 TYPE OF LAMP AND LUMINAIRE.................................................................................................................................... 5

    6.0 ASSUMPTION OF CALCULATION............................................................................................................ 6

    6.1 SOFTWARE TO BE USED............................................................................................................................................. 6

    6.2 CALCULATION METHOD............................................................................................................................................. 6

    6.2.1 General ......................................................................................................................................................... 6

    6.2.2 Formula used for indoor lighting calculation ............................................................................................... 7

    6.2.3 Formula used for outdoor lighting calculation: ............................................................................................ 7

    6.3 INPUT DATA............................................................................................................................................................ 7

    6.4 CHARACTERISTICS OF CONSTRUCTION........................................................................................................................... 8

    7.0 CONCLUSION................................................................................................................................................ 8

    8.0 ATTACHMENT............................................................................................................................................. 11

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    3/419

    PTTEP International Limited Page 3/11

    Zawtika Development Project Phase 1A Document : MM-ZTK-1A-ZOC-ELE-CAL-5002

    EPCIC of the Zawtika Onshore PipelineRevision : C2

    Date :05-Feb -132

    1.0 SCOPE

    This report covers the illumination calculation for lighting system which shall be installed inZOC.

    This report sets out the minimum principle calculation for design. The final detailed calculationreport shall be confirmed by selected Vendor according to technical parameter of hisproduction.

    2.0 REFERENCE DOCUMENTS

    This calculation report shall be on the basis of the following documents referenced herein

    MM-ZTK-1A-ONEP-ELE-SPE-5011 Specification For Electrical Guidelines

    MM-ZTK-1A-ONEP-ELE-SPE-5009 Specification For Electrical Bulk Material

    MM-ZTK-1A-ZOC -CIV-DWG-5003 ZOC Administration Building Architectural Plans AndElevations

    MM-ZTK-1A-ZOC -CIV-DWG-5007 ZOC Catering Building Architectural Plans

    MM-ZTK-1A-ZOC -CIV-DWG-5012 ZOC Staff Dormitory Junior BldgArchitectural

    Plans

    MM-ZTK-1A-ZOC -CIV-DWG-5017 ZOC Staff DormitorySenior BldgArchitectural

    Plans

    MM-ZTK-1A-ZOC -CIV-DWG-5022 ZOC Control Building Architectural Plans

    MM-ZTK-1A-ZOC -CIV-DWG-5027 ZOC Workshop Architectural Plans And Elevations

    MM-ZTK-1A-ZOC -CIV-DWG-5010 ZOC Plot Plan

    MM-ZTK-1A-ZOC -CIV-DWG-5040 ZOC Car Parking Shelter Architectural Plans AndSection

    MM-ZTK-1A-ZOC -CIV-DWG-5031 ZOC GarageArchitectural Plans And Section

    MM-ZTK-1A-ZOC -CIV-DWG-5041 ZOC MOGE Gas Pressure Regulation And Meeting

    System ShelterArchitectural Plans And Section

    MM-ZTK-1A-ZOC -CIV-DWG-5039 ZOC WarehouseArchitectural Plans And Section

    MM-ZTK-1A-ONEP-CIV-DWG-5005 Typical For gas engine generator ShelterArchitectural Plans And Sections

    MM-ZTK-1A- ONEP-CIV-DWG-5026 Typical For diesel generator Shelter Layout AndSections

    MM-ZTK-1A-ONEP-CIV-DWG-5012 Typical For fire water pump Shelter ArchitecturalElevation

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    4/419

    PTTEP International Limited Page 4/11

    Zawtika Development Project Phase 1A Document : MM-ZTK-1A-ZOC-ELE-CAL-5002

    EPCIC of the Zawtika Onshore PipelineRevision : C2

    Date :05-Feb -132

    MM-ZTK-1A- ONEP -CIV-DWG-5014 Typical for Water Treatment Architectural Plans, andSections

    MM-ZTK-1A-ONEP-CIV-DWG-5009 Typical for Drain/Condensate Sump Shelter

    Architectural Plans , Elevations And Sections

    MM-ZTK-1A-ONEP-CIV-DWG-5008 Typical for Fuel Gas Knockout Drum AndSuperheater Shelter Architectural Plans ,ElevationsAnd Sections

    MM-ZTK-1A-ONEP-CIV-DWG-5025 Typical for Petrol Filling Station Plans AndElevations

    3.0 CODES AND STANDARDS

    The latest revisions of the following Codes and Standards shall be considered as part of thisSpecification:

    CIE

    4.0 SITE AND ENVIRONMENTAL CONDITIONS

    The site is located in a humid, tropical environment.

    Maximum ambient temperature : 45 C

    Minimum ambient temperature : 18 C

    Seismic Zone : 2B

    Maximum relative humidity at 40 C : 100%

    5.0 LIGHTING SYSTEM

    5.1 Lighting system configuration

    Normal lighting system shall be provided in the following area:

    Internal building

    Shelter for process facilities

    Perimeter

    Street

    Normal lighting system shall feed from the gas generator. At the same time,emergency lighting shall be envisaged and feed from the diesel generator.

    5.2 Illumination levels

    The normal illumination levels requested in specification No. MM-ZTK-1A-ONEP-ELE-SPE-5011 are the following:

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    5/419

    PTTEP International Limited Page 5/11

    Zawtika Development Project Phase 1A Document : MM-ZTK-1A-ZOC-ELE-CAL-5002

    EPCIC of the Zawtika Onshore PipelineRevision : C2

    Date :05-Feb -132

    Location Illumination Level (lux) Working Plane

    General Process and Utility

    areas50 At grade

    Process and Utility areas

    - Pump, Compressor etc.

    - Operating Area

    100

    200

    At grade

    At 1.5 m level

    Storage area

    - General area

    - Tank (ladder, gauge

    area)

    10 At grade

    Loading Area 100 At gradeMuster Area 100 At grade

    Control Panel 300 At 1.5m level

    E&I Room 300 Floor

    Parking area 5 Floor

    Fence lighting 10 At grade

    Street Lighting 10 At grade

    Offices(administration) 500 Floor+0.8m

    Central Control Room 500 Floor

    Warehouses 50 At grade

    Generator Shelter 200 Floor

    Workshops 300 Floor+0.8m

    First Aid Room 700 Floor+0.8m

    Lavatory 100 Floor

    Cafeteria 300 Floor+0.8m

    Entrance gate, Inspection 150 Floor

    Emergency average exit path illumination to be 10 lux with minimum 1 lux at any point.And illumination level of emergency lighting shall be maintained along egress paths tomuster point and plant gate for safely evacuation.

    5.3 Type of lamp and luminaire

    Lamps suitable for operating condition shall be reduced in sizing according to theirpower. They are resistant to voltage and temperature change. Power factor of lampshall be equal to 0.9.

    The type of lamp shall be indicated in the table.

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    6/419

    PTTEP International Limited Page 6/11

    Zawtika Development Project Phase 1A Document : MM-ZTK-1A-ZOC-ELE-CAL-5002

    EPCIC of the Zawtika Onshore PipelineRevision : C2

    Date :05-Feb -132

    No. Location Lamp type Power Application

    1 Indoor building Fluorescent 3x14W General room

    2 Indoor building Fluorescent 4x14W General room

    3 Indoor building Fluorescent 1x18W Lavatory (above mirror)

    4 Indoor building Compactfluorescent

    1x32W/1x18W1x26W

    Corridor, Toilet ,walkway ,Gatehouse

    5 Indoor building Fluorescent 2x36W, 1x36W, Workshop ,warehouse

    6 Guard House Metal Halide 1x70W Parking trucks

    6 Shelter Metal HalideFluorescent

    1x70W,1x150W1x100W,2x36W,

    Industrial plant

    7 Outdoor High pressure

    sodium

    1x150W General (street lighting)

    8 Outdoor fence High pressuresodium

    2x250W General (floodlighting)

    Notes :

    1) For outdoor lighting, the explosion-proof fitting shall be selected in the hazardousarea. In the non-hazardous area , the IP56 industry fitting shall be foreseen.

    2) Fluorescent fitting with IP44 shall be used in the high humidity area (e.g. outdoorwalkway, toilet, kitchen.)

    6.0 ASSUMPTION OF CALCULATION

    6.1 Software to Be Used

    - DIALUX version 4.9 is used for illumination calculation in internal building.

    - LUXICON version 2.5 is used for illumination calculation in outdoor area andshelter.

    6.2 Calculation Method

    6.2.1 General

    Compute program shall be used for illumination level calculation. The basictechnical parameter shall be chosen from database of the Philips or CopperCrouse-hinds.

    It determines the illumination level in the calculation area with the lamp andluminaries selected previously. The illumination levels in the grids points arethe result of every luminary contribution.

    Lumen method is utilized for indoor lighting calculation and pointby-pointmethod is utilized for outdoor lighting calculation.

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    7/419

    PTTEP International Limited Page 7/11

    Zawtika Development Project Phase 1A Document : MM-ZTK-1A-ZOC-ELE-CAL-5002

    EPCIC of the Zawtika Onshore PipelineRevision : C2

    Date :05-Feb -132

    6.2.2 Formula used for indoor lighting calculation

    S

    NuKEav

    Where:

    Eav = average luminous flux

    N = quantities of lamp

    = luminous per lamp

    S = area

    K= lighting loss factor

    u = coefficient of utilization

    Cavity ratios for ceiling, room and floor using formula:

    LxW

    WLxHccCCR )(5

    LxW

    WLcxHRCR

    R )(5

    LxW

    WLcxHFCR

    F )(5

    Where:

    HCC= Height from ceiling plane to luminaire plane

    HCR= Height from luminous plane to work plane

    HFC= Height from work plane to ground plane

    6.2.3 Formula used for outdoor lighting calculation:

    Where:

    E= Illumination in the horizontal flux

    I = Candela value per 1000 lumen

    =Angle from the downward vertical

    h= Flood lighting mounted height

    K= lighting loss factor

    6.3 Input Data

    The input data are the following:

    - Calculation grids dimensions

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    8/419

    PTTEP International Limited Page 8/11

    Zawtika Development Project Phase 1A Document : MM-ZTK-1A-ZOC-ELE-CAL-5002

    EPCIC of the Zawtika Onshore PipelineRevision : C2

    Date :05-Feb -132

    - Lamp and luminaries selected

    - Maintenance factor of 0.8

    - Luminaries position and orientation

    6.4 Characteristics of Construction

    Calculation grids dimension shall be defined in accordance with the building and

    shelter of plant. The detailed characteristic of building and shelter is indicated in the

    architectural plan drawing indicated in para. 2.0.

    The following lighting fitting in the internal building shall be selected:

    - Philips TBS869 3xTL5-14W/840 HFP114 D8H

    - Philips TBS869 4xTL5-14W/840 HFP114 D8H

    - Philips FBS271 1xPL-T/4P32W HFP M- Philips FBS271 1xPL-T/4P18W HFP M

    - Philips 4 IS120 2XTL-D36W HFPAC

    - Philips XWC120 1xSOX-E18W

    - Philips FWG251 2xPL-T/4P26W HF

    The following lighting fitting in the shelter shall be selected for process facilities:

    - VMV 70W/100W/150W MHT

    - ELLK 92036_36 2x36W

    - Philips 4 IS120 2XTL-D36W HFP AC

    The following lighting fitting shall be selected for the outdoor lighting:

    - 12-meter high pole with lighting fitting 2xFDL 250WHPS lamp for fence lighting

    - 8-meter high pole with lighting fitting 1xVMV 150W or 1XOVY 150W HPS lamp for

    street lighting

    7.0 CONCLUSION

    The normal target illuminance is defined in para.5.2. In general, 20% of lighting fittings in the

    room shall be served as emergency lighting. But the only one lighting fitting in the room exceptstaff dormitory shall be served as emergency lighting.

    The final calculate value in the building via computer software Dialux utilizing the lumenmethod shall be listed as follows:

    Building tag Name of room Heightof ceiling(m)

    Mountingheight(m)

    TargetIlluminance(Lux)

    CalculatedIlluminance (N)(Lux)

    CalculatedIlluminance (E)(Lux)

    AdministrationBuilding

    Office 1 2.8 2.8 500 686 348

    Office 2 2.8 2.8 500 559 281

    Office 3 2.8 2.8 500 559 281

    Office 4 2.8 2.8 500 559 281

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    9/419

    PTTEP International Limited Page 9/11

    Zawtika Development Project Phase 1A Document : MM-ZTK-1A-ZOC-ELE-CAL-5002

    EPCIC of the Zawtika Onshore PipelineRevision : C2

    Date :05-Feb -132

    AdministrationBuilding

    Copier area 2.8 2.8 500 503 281

    Elec. room 2.8 2.8 300 329 329

    Janitor room 2.8 2.8 300 287 287

    Female WC. room 2.8 2.8 100 224 100

    Male WC. room 2.8 2.8 100 218 100

    Pantry room 2.8 2.8 200 329 329

    Medical room 2.8 2.8 500 660 227

    Meeting room 2.8 2.8 500 583 292

    Staff area 2.8 2.8 500 652 325

    Praying room 2.8 2.8 500 632 318

    Walkway 3.2 3.2 10 30 30

    CateringBuilding

    Laundry room 2.8 2.8 200 231 115

    Kitchen room 2.8 2.8 300 367 124

    Camp boss room 2.8 2.8 500 652 326

    Elec. room 2.8 2.8 200 267 267

    GYM room 2.8 2.8 300 337 169

    Recreation room 2.8 2.8 300 371 169

    Seating room 2.8 2.8 300 362 149Male WC. room 2.8 2.8 100 160 80

    Female WC. room 2.8 2.8 100 163 80

    Janitor 2.8 2.8 200 251 251

    Walkway 3.2 3.2 10 23 23

    Junior Building Bedroom 2.8 2.8 150 232 -

    WC room 2.8 2.8 50 134 -

    Balcony 2.8 2.8 50 332 -

    Elec. room 2.8 2.8 200 201 201

    Corridor 2.8 2.8 100 102 102

    Walkway 3.0 3.0 10 34 34

    SeniorBuilding

    Bedroom 2.8 2.8 150 232 -

    WC room 2.8 2.8 50 100 -Balcony 2.8 2.8 50 332 -

    Elec. room 2.8 2.8 200 248 248

    Corridor 2.8 2.8 100 110 110

    Walkway 3.0 3.0 10 33 33

    ControlBuilding

    Battery room 2.8 2.8 200 222 100

    Control room 2.8 2.8 500 617 617

    Switchgear room 2.8 2.8 300 315 179

    Instrument/Telecom.Equipment room

    2.8 2.8 300 327 132

    Pantry room 2.8 2.8 200 219 219

    Emergency

    respond team

    2.8 2.8 500 523 264

    Male WC. room 2.8 2.8 100 166 90

    Female WC. room 2.8 2.8 100 203 100

    AHU room 2.8 2.8 300 316 158

    Janitor room 2.6 2.7 200 256 256

    Corridor 2.8 2.9 100 241 150

    Walkway 3.5 3.5 10 24 24

    Warehouse Cool room 2.8 2.8 50 97 49

    Staff room 2.8 2.8 500 475 230

    Office room 2.8 2.8 500 602 277

    WC room 2.8 2.8 100 196 90

    Warehouse 9.8 5.0 50 128 64

    Dangerous goods 3.0 3.0 50 53 53

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    10/419

    PTTEP International Limited Page 10/11

    Zawtika Development Project Phase 1A Document : MM-ZTK-1A-ZOC-ELE-CAL-5002

    EPCIC of the Zawtika Onshore PipelineRevision : C2

    Date :05-Feb -132

    Painting storage 3.0 3.0 50 82 82

    Spare area 3.0 3.0 50 84 84

    Walkway 3.5 3.5 10 18 18

    Workshop Instrumentationstorage room

    3.0 3.0 50 119 119

    Instrumentworkshop

    3.0 3.0 300 368 136

    Chemical &oilstorage room

    4.4 4.4 50 68 68

    Storage room 4.4 4.4 50 61 61

    WC room 2.8 2.8 100 246 100

    Office room 3.0 3.0 500 527 265

    Walkway 4.4 4.4 10 17 17

    Cold workshoproom

    5.0 4.4 300 325 113

    Hot workshoproom

    5.0 4.4 300 321 112

    Walkway 3.5 3.5 10 18 18

    Notes:1) N: Normal lighting2) E: Emergency lighting

    The final calculate value in the shelter via computer software provided by Crouse-Hindutilizing the lumen method shall be listed as follows:

    Shelter Description Heightofshelter

    Mountingheight (m)

    TargetIlluminance(Lux)

    CalculatedIlluminance (N)(Lux)

    CalculatedIlluminance (E)(Lux)

    ZOC Garage Car ParkingShelter

    5.5 3.5 50 71 30

    MOGE Gas PressureRegulation And MeetingSystem Shelter

    5.8 4.5 100 149.21 61.34

    Flow Control Valve andhigh Integrity PressureProtection System

    5.8 4.5 100 122.8 40.95

    Fiscal Ultrasonic MeteringSystem Shelter

    5.8 4.5 100 138.7 48.15

    The typical shelters shall be located at ZMS and ZOC , The final calculate value shall be listedas follows:

    Shelter Description Height(m)

    Mountingheight(m)

    TargetIlluminance(Lux)

    CalculatedIlluminance(N)(Lux)

    CalculatedIlluminance (E)(Lux)

    Gas Engine GeneratorShelter

    6.3 4.5 200 236 49.77

    Diesel GeneratorShelter

    4.4 3.5 200 217

    Fire water pumpShelter

    5.5 4.0 100 114 45

    Water Treatment 5.2 4.0 100 144 57

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    11/419

    PTTEP International Limited Page 11/11

    Zawtika Development Project Phase 1A Document : MM-ZTK-1A-ZOC-ELE-CAL-5002

    EPCIC of the Zawtika Onshore PipelineRevision : C2

    Date :05-Feb -132

    Shelter

    Drain/CondensateSump Shelter

    4.5 3.5 100 104 29.8

    Petrol Filling Station 5.2 4 100 126 57.98

    Fuel Gas KnockoutDrum And SuperheaterShelter

    5.8 4.5 100 104 46.52

    The typical buildings shall be located at ZMS and ZOC , The final calculate value shall belisted as follows:

    Building tag Name of room Heightof ceiling(m)

    Mountingheight

    (m)

    TargetIlluminance(Lux)

    CalculatedIlluminance (N)(Lux)

    CalculatedIlluminance (E)(Lux)

    Guard

    house

    Fire fighting

    room

    2.6 2.6 100 134 134

    Chief room 2.4 2.4 500 499 346

    Staff room 2.4 2.4 500 621 336

    WC room 2.5 2.635 100 175 50

    Standby room 2.4 2.4 200 243 243

    Corridor 2.5 2.6 100 276 50

    Walkway 3.0 3.0 10 26 26

    Parking for firefighting trucks

    4.9 3 10 77 40

    Gatehouse

    Gate room 2.8 2.8 100 99 99

    The average illuminance of fence and street is 24lux. The 8-meter high pole with lighting fitting1XEVZ150RD 150W or 1XOVY150W HPS lamp shall be installed adjacent to the street.Maximum distance between pole is not greater than 40m.

    The 12-meter high pole with lighting fitting 2xFDL 250W HPSlamp shall be installed adjacentto the fence . Maximum distance between pole is not greater than 45m.

    8.0 ATTACHMENT

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    12/419

    ZOC Control Building

    Date: 21.09.2012Operator: GuoBin

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    13/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    PHILIPS TBS869 3xTL5-14W/840 HFP114 D8H / Luminaire Data Sheet

    See our luminaire catalog for an image of theluminaire.

    Luminous emittance 1:

    200

    300

    400

    500

    cd/klm 77%C0 - C180 C90 - C270

    0 15 30

    45

    60

    75

    90

    105105

    90

    75

    60

    45

    30 15 0

    Luminaire classification according to CIE: 100CIE flux code: 73 98 100 100 77

    Luminous emittance 1:

    Glare Evaluation According to UGR

    Ceiling 70 70 50 50 30 70 70 50 50 30

    Walls 50 30 50 30 30 50 30 50 30 30

    Floor 20 20 20 20 20 20 20 20 20 20

    Room SizeX Y

    Viewing direction at right anglesto lamp axis

    Viewing direction parallelto lamp axis

    2H 2H 11.7 12.7 12.0 12.9 13.1 16.1 17.1 16.4 17.3 17.5

    3H 11.6 12.5 11.9 12.7 12.9 16.1 16.9 16.4 17.2 17.4

    4H 11.5 12.3 11.8 12.6 12.9 16.0 16.8 16.3 17.1 17.3

    6H 11.5 12.2 11.8 12.5 12.8 15.9 16.7 16.3 16.9 17.2

    8H 11.4 12.1 11.8 12.4 12.7 15.9 16.6 16.2 16.9 17.2

    12H 11.4 12.0 11.7 12.4 12.7 15.9 16.5 16.2 16.8 17.1

    4H 2H 11.9 12.7 12.2 12.9 13.2 15.9 16.7 16.3 17.0 17.3

    3H 11.7 12.4 12.1 12.7 13.0 15.9 16.5 16.2 16.9 17.2

    4H 11.7 12.2 12.0 12.6 12.9 15.8 16.4 16.2 16.7 17.1

    6H 11.6 12.1 12.0 12.4 12.8 15.8 16.2 16.2 16.6 17.0

    8H 11.5 12.0 12.0 12.4 12.8 15.7 16.2 16.1 16.5 16.9

    12H 11.5 11.9 11.9 12.3 12.7 15.7 16.1 16.1 16.5 16.9

    8H 4H 11.6 12.0 12.0 12.4 12.8 15.7 16.2 16.1 16.5 16.9

    6H 11.5 11.8 11.9 12.2 12.7 15.6 16.0 16.1 16.4 16.9

    8H 11.4 11.7 11.9 12.2 12.6 15.6 15.9 16.1 16.3 16.8

    12H 11.4 11.6 11.9 12.1 12.6 15.5 15.8 16.0 16.3 16.8

    12H 4H 11.5 11.9 12.0 12.3 12.7 15.7 16.1 16.1 16.5 16.96H 11.4 11.7 11.9 12.2 12.6 15.6 15.9 16.1 16.3 16.8

    8H 11.4 11.6 11.9 12.1 12.6 15.5 15.8 16.0 16.3 16.8

    Variation of the observer position for the luminaire distances S

    S = 1.0H +2.7 / -12.5 +0.7 / -0.9

    S = 1.5H +4.1 / -20.2 +1.7 / -4.4

    S = 2.0H +5.7 / -23.0 +3.7 / -12.4

    Standard table BK00 BK00

    CorrectionSummand

    -7.6 -3.3

    Corrected Glare Indices referring to 3600lm Total Luminous Flux

    Page 2

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    14/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    PHILIPS TBS869 4xTL5-14W/840 HFP114 D8H / Luminaire Data Sheet

    See our luminaire catalog for an image of theluminaire.

    Luminous emittance 1:

    200

    300

    400

    500

    cd/klm 78%C0 - C180 C90 - C270

    0 15 30

    45

    60

    75

    90

    105105

    90

    75

    60

    45

    30 15 0

    Luminaire classification according to CIE: 100CIE flux code: 75 99 100 100 78

    Luminous emittance 1:

    Glare Evaluation According to UGR

    Ceiling 70 70 50 50 30 70 70 50 50 30

    Walls 50 30 50 30 30 50 30 50 30 30

    Floor 20 20 20 20 20 20 20 20 20 20

    Room SizeX Y

    Viewing direction at right anglesto lamp axis

    Viewing direction parallelto lamp axis

    2H 2H 12.0 13.0 12.3 13.2 13.4 17.2 18.1 17.4 18.3 18.5

    3H 11.9 12.7 12.2 13.0 13.2 17.1 17.9 17.4 18.2 18.4

    4H 11.8 12.6 12.1 12.9 13.1 17.0 17.8 17.3 18.1 18.3

    6H 11.8 12.5 12.1 12.8 13.0 17.0 17.7 17.3 18.0 18.2

    8H 11.7 12.4 12.1 12.7 13.0 16.9 17.6 17.3 17.9 18.2

    12H 11.7 12.3 12.0 12.6 13.0 16.9 17.5 17.2 17.8 18.2

    4H 2H 12.2 12.9 12.5 13.2 13.5 17.0 17.7 17.3 18.0 18.3

    3H 12.0 12.7 12.4 13.0 13.3 16.9 17.5 17.3 17.9 18.2

    4H 12.0 12.5 12.3 12.9 13.2 16.8 17.4 17.2 17.7 18.1

    6H 11.9 12.4 12.3 12.7 13.1 16.8 17.2 17.2 17.6 18.0

    8H 11.8 12.3 12.3 12.7 13.1 16.7 17.2 17.1 17.5 17.9

    12H 11.8 12.2 12.2 12.6 13.0 16.7 17.1 17.1 17.5 17.9

    8H 4H 11.8 12.3 12.3 12.7 13.1 16.7 17.2 17.1 17.5 17.9

    6H 11.8 12.1 12.2 12.5 13.0 16.6 17.0 17.1 17.4 17.9

    8H 11.7 12.0 12.2 12.5 12.9 16.6 16.9 17.1 17.3 17.8

    12H 11.7 11.9 12.2 12.4 12.9 16.5 16.8 17.0 17.3 17.8

    12H 4H 11.8 12.2 12.2 12.6 13.0 16.7 17.1 17.1 17.5 17.96H 11.7 12.0 12.2 12.5 12.9 16.6 16.9 17.1 17.3 17.8

    8H 11.7 11.9 12.2 12.4 12.9 16.5 16.8 17.0 17.3 17.8

    Variation of the observer position for the luminaire distances S

    S = 1.0H +3.1 / -13.1 +0.7 / -0.9

    S = 1.5H +4.5 / -20.1 +2.0 / -4.7

    S = 2.0H +6.2 / -22.9 +3.9 / -12.9

    Standard table BK00 BK00

    CorrectionSummand

    -7.3 -2.3

    Corrected Glare Indices referring to 4800lm Total Luminous Flux

    Page 3

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    15/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    PHILIPS TBS869 4xTL5-14W/840 HFP114 D8H / Luminaire Data Sheet

    See our luminaire catalog for an image of theluminaire.

    Luminous emittance 1:

    200

    300

    400

    500

    cd/klm 78%C0 - C180 C90 - C270

    0 15 30

    45

    60

    75

    90

    105105

    90

    75

    60

    45

    30 15 0

    Luminaire classification according to CIE: 100CIE flux code: 75 99 100 100 78

    Luminous emittance 1:

    Glare Evaluation According to UGR

    Ceiling 70 70 50 50 30 70 70 50 50 30

    Walls 50 30 50 30 30 50 30 50 30 30

    Floor 20 20 20 20 20 20 20 20 20 20

    Room SizeX Y

    Viewing direction at right anglesto lamp axis

    Viewing direction parallelto lamp axis

    2H 2H 12.0 13.0 12.3 13.2 13.4 17.2 18.1 17.4 18.3 18.5

    3H 11.9 12.7 12.2 13.0 13.2 17.1 17.9 17.4 18.2 18.4

    4H 11.8 12.6 12.1 12.9 13.1 17.0 17.8 17.3 18.1 18.3

    6H 11.8 12.5 12.1 12.8 13.0 17.0 17.7 17.3 18.0 18.2

    8H 11.7 12.4 12.1 12.7 13.0 16.9 17.6 17.3 17.9 18.2

    12H 11.7 12.3 12.0 12.6 13.0 16.9 17.5 17.2 17.8 18.2

    4H 2H 12.2 12.9 12.5 13.2 13.5 17.0 17.7 17.3 18.0 18.3

    3H 12.0 12.7 12.4 13.0 13.3 16.9 17.5 17.3 17.9 18.2

    4H 12.0 12.5 12.3 12.9 13.2 16.8 17.4 17.2 17.7 18.1

    6H 11.9 12.4 12.3 12.7 13.1 16.8 17.2 17.2 17.6 18.0

    8H 11.8 12.3 12.3 12.7 13.1 16.7 17.2 17.1 17.5 17.9

    12H 11.8 12.2 12.2 12.6 13.0 16.7 17.1 17.1 17.5 17.9

    8H 4H 11.8 12.3 12.3 12.7 13.1 16.7 17.2 17.1 17.5 17.9

    6H 11.8 12.1 12.2 12.5 13.0 16.6 17.0 17.1 17.4 17.9

    8H 11.7 12.0 12.2 12.5 12.9 16.6 16.9 17.1 17.3 17.8

    12H 11.7 11.9 12.2 12.4 12.9 16.5 16.8 17.0 17.3 17.8

    12H 4H 11.8 12.2 12.2 12.6 13.0 16.7 17.1 17.1 17.5 17.96H 11.7 12.0 12.2 12.5 12.9 16.6 16.9 17.1 17.3 17.8

    8H 11.7 11.9 12.2 12.4 12.9 16.5 16.8 17.0 17.3 17.8

    Variation of the observer position for the luminaire distances S

    S = 1.0H +3.1 / -13.1 +0.7 / -0.9

    S = 1.5H +4.5 / -20.1 +2.0 / -4.7

    S = 2.0H +6.2 / -22.9 +3.9 / -12.9

    Standard table BK00 BK00

    CorrectionSummand

    -7.3 -2.3

    Corrected Glare Indices referring to 4800lm Total Luminous Flux

    Page 5

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    16/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Philips FBS271 1xPL-T/4P32W HFP M / Luminaire Data Sheet

    Luminous emittance 1:

    200

    300

    400

    500

    600

    cd/klm 72%C0 - C180 C90 - C270

    0 15 30

    45

    60

    75

    90

    105105

    90

    75

    60

    45

    30 15 0

    Luminaire classification according to CIE: 100CIE flux code: 74 100 100 100 73

    Fugato performance in a new light

    The Fugato range of fixed downlights for general lighting consists of FugatoCompact (cut-out 175 mm), Fugato Performance (cut-out 225 mm), FugatoPower (cut-out 275 mm) and Fugato Full Metal (both 175 and 225 mm),which have all been designed for optimum performance both optical and

    thermal with compact fluorescent lamps.

    Optical variation is provided by Fugatosdual optic concept. The top

    optic is made of high-gloss aluminum. The lower polymer optic can beordered in a high-gloss, matt-satin or white finish. The high-gloss (C) versioncomplies with the UGRr19 norm (in accordance with EN12464-1, Lm < 1000cd/m2 at > 65o) when used with the innovative round louver. A wide rangeof accessories is available for the CFL versions of both Fugato and FugatoFull Metal.

    Luminous emittance 1:

    Glare Evaluation According to UGR

    Ceiling 70 70 50 50 30 70 70 50 50 30

    Walls 50 30 50 30 30 50 30 50 30 30

    Floor 20 20 20 20 20 20 20 20 20 20

    Room SizeX Y

    Viewing direction at right anglesto lamp axis

    Viewing direction parallelto lamp axis

    2H 2H 20.1 21.0 20.4 21.2 21.5 19.5 20.5 19.8 20.7 20.9

    3H 19.9 20.8 20.2 21.0 21.3 19.4 20.2 19.7 20.5 20.7

    4H 19.9 20.7 20.2 20.9 21.2 19.3 20.1 19.6 20.4 20.6

    6H 19.8 20.5 20.1 20.8 21.1 19.2 20.0 19.6 20.2 20.5

    8H 19.8 20.5 20.1 20.7 21.1 19.2 19.9 19.5 20.2 20.5

    12H 19.7 20.4 20.1 20.7 21.0 19.2 19.8 19.5 20.1 20.4

    4H 2H 20.0 20.8 20.3 21.1 21.3 19.5 20.2 19.8 20.5 20.8

    3H 19.9 20.5 20.2 20.8 21.2 19.3 20.0 19.7 20.3 20.6

    4H 19.8 20.4 20.2 20.7 21.1 19.3 19.8 19.6 20.2 20.5

    6H 19.7 20.2 20.1 20.6 21.0 19.2 19.7 19.6 20.0 20.4

    8H 19.7 20.1 20.1 20.5 20.9 19.1 19.6 19.6 20.0 20.4

    12H 19.7 20.0 20.1 20.4 20.9 19.1 19.5 19.5 19.9 20.3

    8H 4H 19.7 20.1 20.1 20.5 20.9 19.1 19.6 19.6 20.0 20.4

    6H 19.6 20.0 20.1 20.4 20.8 19.1 19.4 19.5 19.8 20.3

    8H 19.6 19.9 20.0 20.3 20.8 19.0 19.3 19.5 19.8 20.2

    12H 19.5 19.8 20.0 20.2 20.7 19.0 19.2 19.5 19.7 20.2

    12H 4H 19.7 20.0 20.1 20.4 20.9 19.1 19.5 19.5 19.9 20.36H 19.6 19.9 20.0 20.3 20.8 19.0 19.3 19.5 19.8 20.2

    8H 19.5 19.8 20.0 20.2 20.7 19.0 19.2 19.5 19.7 20.2

    Variation of the observer position for the luminaire distances S

    S = 1.0H +1.2 / -2.5 +0.9 / -1.8

    S = 1.5H +2.9 / -14.4 +2.0 / -8.9

    S = 2.0H +4.8 / -26.7 +3.6 / -24.0

    Standard table BK00 BK00

    CorrectionSummand

    0.4 -0.1

    Corrected Glare Indices referring to 2400lm Total Luminous Flux

    Page 6

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    17/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Switchgear RM / Summary

    280

    280

    280

    350350

    350 350

    350

    350

    350

    350

    350

    350350

    350

    350

    350 350350

    350

    350350

    350350 350

    350350

    350 350

    10.00 m0.00 2.50 5.82

    24.00 m

    0.00

    3.60

    5.09

    6.28

    7.68

    9.0810.48

    11.88

    13.28

    14.65

    15.80

    17.30

    18.88

    20.09

    Height of Room: 2.800 m, Mounting Height: 2.800 m, Light loss factor:

    0.80

    Values in Lux, Scale 1:309

    Surface [%] Eav[lx] Emin[lx] Emax[lx] u0

    Workplane / 315 96 428 0.305

    Floor 27 288 7.89 428 0.027

    Ceiling 78 90 63 256 0.701

    Walls (4) 78 119 20 215 /

    Workplane:Height: 0.000 mGrid: 128 x 128 PointsBoundary Zone: 0.000 m

    Luminaire Parts List

    Specific connected load: 6.30 W/m = 2.00 W/m/100 lx (Ground area: 240.00 m)

    No. Pieces Designation (Correction Factor) [lm] P [W]

    1 24 PHILIPS TBS869 4xTL5-14W/840 HFP114 D8H (1.000) 4800 63.0

    Total: 115200 1512.0

    Page 7

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    18/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Switchgear RM / Luminaire parts list

    24 Pieces PHILIPS TBS869 4xTL5-14W/840 HFP114 D8HArticle No.:Luminaire Luminous Flux: 4800 lmLuminaire Wattage: 63.0 WLuminaire classification according to CIE: 100CIE flux code: 75 99 100 100 78Fitting: 4 x TL5-14W/840 (Correction Factor1.000).

    See our luminairecatalog for an image of

    the luminaire.

    Page 8

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    19/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Switchgear RM / Workplane / Value Chart (E)

    203

    268

    303

    256

    242

    284

    312

    274

    241

    267

    312

    289

    245

    256

    307

    300

    253

    248

    298

    312268

    247

    287

    308

    253

    256

    344

    360

    281

    376

    334

    265

    356

    385

    330

    388

    343

    307

    254

    280

    309

    269

    238

    265

    306

    282

    242

    254

    302

    297

    251

    246

    291

    308265

    262

    353

    386

    307

    359

    389

    317

    336

    318

    371

    404

    356

    313

    347

    399

    370

    316

    333

    392

    386

    327

    321

    379

    400345

    272

    362

    385

    332

    377

    402

    328

    245

    338

    395

    363

    323

    354

    408

    384

    329

    340

    399

    402

    262

    350

    371

    338

    322

    374

    381

    297

    247

    338

    395

    364

    324

    355

    409

    384

    331

    341

    401

    403

    330

    287

    309

    337

    348

    271

    365

    401

    350

    334

    387

    391

    303

    310

    346

    402

    377

    323

    343

    403

    398

    338

    332

    391

    410

    314

    299

    347

    381

    325

    219

    296

    325

    289

    263

    302

    327

    263

    309

    267

    258

    299

    325

    282

    257

    288

    327

    10.00 m0.00 1.53 5.82

    24.00 m

    0.00

    3.60

    5.09

    6.28

    7.68

    9.08

    10.48

    11.88

    13.28

    14.0514.72

    15.55

    16.30

    17.30

    18.28

    19.25

    20.09

    Values in Lux, Scale 1 : 188Not all calculated values could be displayed.

    Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)

    Grid: 128 x 128 Points

    Eav

    [lx] Emin

    [lx] Emax

    [lx] u0 Emin/ Emax

    315 96 428 0.305 0.224

    Page 10

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    20/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    AHU RM / Summary

    240

    240

    240

    240

    240

    300

    300

    300

    300

    300

    300300

    300

    300

    300

    300

    300

    300

    300

    300

    360

    360 360

    360

    360

    360

    360

    360360

    360360

    360 360

    360

    360

    360

    360

    360

    420

    420 420

    420

    420

    420

    420

    420420

    420

    420 420

    420

    420

    420420

    420

    10.00 m0.00

    4.00 m

    0.00

    Height of Room: 2.800 m, Mounting Height: 2.800 m, Light loss factor:0.80

    Values in Lux, Scale 1:72

    Surface [%] Eav[lx] Emin[lx] Emax[lx] u0

    Workplane / 316 178 446 0.564

    Floor 27 304 163 446 0.535

    Ceiling 78 90 69 102 0.765

    Walls (4) 78 130 71 292 /

    Workplane:Height: 0.000 mGrid: 64 x 32 PointsBoundary Zone: 0.200 m

    UGR Lengthways- Across to luminaire axisLeft Wall 12 17Lower Wall 12 17(CIE, SHR = 0.25.)

    Luminaire Parts List

    Specific connected load: 6.30 W/m = 1.99 W/m/100 lx (Ground area: 40.00 m)

    No. Pieces Designation (Correction Factor) [lm] P [W]

    1 4 PHILIPS TBS869 4xTL5-14W/840 HFP114 D8H (1.000) 4800 63.0

    Total: 19200 252.0

    Page 11

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    21/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    AHU RM / Luminaire parts list

    4 Pieces PHILIPS TBS869 4xTL5-14W/840 HFP114 D8HArticle No.:Luminaire Luminous Flux: 4800 lmLuminaire Wattage: 63.0 WLuminaire classification according to CIE: 100CIE flux code: 75 99 100 100 78Fitting: 4 x TL5-14W/840 (Correction Factor1.000).

    See our luminairecatalog for an image of

    the luminaire.

    Page 12

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    22/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    AHU RM / Workplane / Value Chart (E)

    190 220 266 312 338 346 330 294 256 227 215 219 244 281 319 342 345 322 285 232 199201 232 278 326 358 367 346 311 267 244 228 232 262 296 334 364 366 337 297 247 211

    215 252 305 359 394 403 382 341 291 264 245 251 285 323 367 400 403 372 326 269 227

    236 270 328 387 426 435 410 368 314 285 265 271 308 348 397 429 433 402 350 288 244

    240 274 334 395 434 444 418 375 322 292 273 279 315 355 405 438 442 410 357 294 248

    243 276 337 398 436 446 421 379 325 294 275 282 317 358 409 440 444 413 360 296 251

    238 272 332 392 431 440 415 372 320 290 271 277 313 352 402 434 437 407 354 291 247

    231 265 321 380 418 427 403 360 308 279 259 265 301 341 389 424 427 394 344 283 239

    211 246 296 348 382 392 371 332 284 259 241 246 278 315 357 389 391 361 316 262 222

    198 227 274 322 352 360 343 306 266 242 226 231 259 291 331 356 359 333 293 241 209

    10.00 m0.00

    4.00 m

    0.00

    Values in Lux, Scale 1 : 72Not all calculated values could be displayed.

    Position of surface in room:Working plane with 0.200 mBoundary ZoneMarked point:

    (0.200 m, 0.200 m, 0.000 m)

    Grid: 64 x 32 Points

    Eav

    [lx] Emin

    [lx] Emax

    [lx] u0 Emin/ Emax316 178 446 0.564 0.399

    Page 14

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    23/419

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    24/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Control RM / Luminaire parts list

    16 Pieces PHILIPS TBS869 4xTL5-14W/840 HFP114 D8HArticle No.:Luminaire Luminous Flux: 4800 lmLuminaire Wattage: 63.0 WLuminaire classification according to CIE: 100CIE flux code: 75 99 100 100 78Fitting: 4 x TL5-14W/840 (Correction Factor1.000).

    See our luminairecatalog for an image of

    the luminaire.

    Page 16

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    25/419

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    26/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Instrument Equipment&Telecom Equipment RM / Summary

    240

    240

    320

    320

    320

    320

    320320

    320

    400

    400 400

    400

    400

    400

    400400400

    400

    10.00 m0.00 2.50 4.10 5.70 8.10

    10.00 m

    0.00

    3.79

    4.59

    5.60

    6.40

    8.20

    9.00

    Height of Room: 2.800 m, Mounting Height: 2.800 m, Light loss factor:

    0.80

    Values in Lux, Scale 1:129

    Surface [%] Eav[lx] Emin[lx] Emax[lx] u0

    Workplane / 327 84 454 0.257

    Floor 47 280 12 454 0.042

    Ceiling 78 152 105 216 0.686

    Walls (4) 78 217 101 754 /

    Workplane:Height: 0.000 mGrid: 128 x 128 PointsBoundary Zone: 0.000 m

    Luminaire Parts List

    Specific connected load: 7.20 W/m = 2.20 W/m/100 lx (Ground area: 100.00 m)

    No. Pieces Designation (Correction Factor) [lm] P [W]

    1 15 PHILIPS TBS869 3xTL5-14W/840 HFP114 D8H (1.000) 3600 48.0

    Total: 54000 720.0

    Page 19

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    27/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Instrument Equipment&Telecom Equipment RM / Luminaire parts list

    15 Pieces PHILIPS TBS869 3xTL5-14W/840 HFP114 D8HArticle No.:Luminaire Luminous Flux: 3600 lmLuminaire Wattage: 48.0 WLuminaire classification according to CIE: 100CIE flux code: 73 98 100 100 77Fitting: 3 x TL5-14W/840 (Correction Factor1.000).

    See our luminairecatalog for an image of

    the luminaire.

    Page 20

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    28/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Instrument Equipment&Telecom Equipment RM / Workplane / Value Chart (E)

    286

    290

    316

    321

    325

    328

    323

    323

    321

    314

    309

    307

    304

    295

    290

    297286

    279

    254

    245

    239

    259

    290

    273

    242

    339

    342

    366

    369

    373

    375

    368

    367

    362

    361

    356

    353

    351

    343

    337

    335328

    321

    302

    274

    249

    228

    221

    263

    263

    357

    377

    402

    406

    410

    414

    408

    406

    399

    396

    388

    391

    388

    367

    360

    353351

    347

    333

    301

    278

    267

    276

    375

    398

    422

    427

    431

    434

    426

    423

    417

    414

    409

    413

    399

    372

    333

    355

    339

    305

    278

    290

    368

    389

    415

    421

    426

    427

    415

    410

    402

    402

    398

    397

    370

    340

    297

    305

    309

    283

    272

    282

    356

    375

    400

    408

    412

    409

    390

    380

    365

    364

    367

    378

    352

    304

    268

    278

    282

    264

    254

    265

    357

    376

    403

    411

    415

    411

    389

    374

    351

    341

    345

    375

    345

    299

    270

    280

    284

    261

    255

    266

    376

    398

    421

    428

    430

    429

    394

    373

    341

    316

    314

    283

    298

    302

    283

    268

    282

    390

    413

    438

    443

    445

    446

    410

    386

    354

    309

    332

    295

    313

    318

    301

    282

    297

    390

    414

    442

    445

    446

    447

    409

    382

    344

    253

    334

    294

    312

    317

    307

    287

    301

    377

    399

    424

    429

    431

    431

    389

    363

    325

    241

    301

    281

    298

    302

    287

    277

    286

    356

    375

    402

    408

    410

    407

    368

    343

    306

    224

    274

    268

    281

    285

    263

    259

    268

    353

    372

    397

    404

    405

    403

    363

    338

    302

    220

    271

    263

    277

    281

    260

    256

    263

    360

    380

    407

    411

    413

    410

    371

    346

    308

    228

    286

    280

    285

    290

    269

    264

    273

    372

    394

    415

    419

    420

    420

    379

    353

    317

    237

    310

    293

    300

    304

    289

    275

    284

    358

    378

    401

    406

    407

    406

    367

    342

    309

    231

    305

    278

    291

    295

    286

    267

    274

    330

    337

    371

    377

    378

    373

    344

    322

    289

    252

    281

    265

    270

    274

    265

    257

    259

    224

    170

    219

    162

    205

    179

    277

    283

    311

    318

    322

    317

    284

    270

    233

    228

    218

    194

    213

    222

    215

    226

    225

    236

    10.00 m0.00 0.90 2.50 4.10 5.70 8.10 8.91

    10.00 m

    0.00

    3.79

    4.59

    5.60

    6.40

    8.20

    9.00

    Values in Lux, Scale 1 : 79Not all calculated values could be displayed.

    Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)

    Grid: 128 x 128 Points

    Eav

    [lx] Emin

    [lx] Emax

    [lx] u0 Emin/ Emax

    327 84 454 0.257 0.185

    Page 22

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    29/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Pantry RM / Summary

    160

    160

    160

    160

    160

    160

    200

    200200

    200

    200

    200

    200

    240

    240

    240

    240

    240

    240

    240

    240

    240

    280

    280

    280 280

    280

    280

    280

    280

    280

    280

    280

    5.00 m0.00

    3.00 m

    0.00

    0.20

    2.80

    Height of Room: 2.800 m, Mounting Height: 2.800 m, Light loss factor:

    0.80

    Values in Lux, Scale 1:39

    Surface [%] Eav[lx] Emin[lx] Emax[lx] u0

    Workplane / 219 114 313 0.520

    Floor 47 206 99 311 0.480

    Ceiling 78 84 64 99 0.763

    Walls (4) 78 107 63 252 /

    Workplane:Height: 0.000 mGrid: 32 x 32 PointsBoundary Zone: 0.200 m

    Luminaire Parts List

    Specific connected load: 4.20 W/m = 1.92 W/m/100 lx (Ground area: 15.00 m)

    No. Pieces Designation (Correction Factor) [lm] P [W]

    1 1 PHILIPS TBS869 4xTL5-14W/840 HFP114 D8H (1.000) 4800 63.0

    Total: 4800 63.0

    Page 23

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    30/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Pantry RM / Luminaire parts list

    1 Pieces PHILIPS TBS869 4xTL5-14W/840 HFP114 D8HArticle No.:Luminaire Luminous Flux: 4800 lmLuminaire Wattage: 63.0 WLuminaire classification according to CIE: 100CIE flux code: 75 99 100 100 78Fitting: 4 x TL5-14W/840 (Correction Factor1.000).

    See our luminairecatalog for an image of

    the luminaire.

    Page 24

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    31/419

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    32/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Emergency Respond Team / Summary

    480

    480480

    480

    480

    600

    600

    600600

    600

    600

    600

    600

    600

    600

    600

    600

    600600

    600

    600

    600 600

    600

    5.00 m0.00 0.37 0.97 1.43 2.03 2.42 4.23 4.61

    4.00 m

    0.00

    0.20

    0.400.58

    0.79

    0.99

    1.20

    1.59

    2.20

    2.66

    3.01

    3.63

    Height of Room: 2.800 m, Mounting Height: 2.800 m, Light loss factor:

    0.80

    Values in Lux, Scale 1:52

    Surface [%] Eav[lx] Emin[lx] Emax[lx] u0

    Workplane / 523 86 643 0.164

    Floor 64 333 35 518 0.104

    Ceiling 78 219 171 259 0.779

    Walls (4) 78 248 5.54 392 /

    Workplane:Height: 0.800 mGrid: 128 x 128 PointsBoundary Zone: 0.200 m

    Luminaire Parts List

    Specific connected load: 9.60 W/m = 1.83 W/m/100 lx (Ground area: 20.00 m)

    No. Pieces Designation (Correction Factor) [lm] P [W]

    1 4 PHILIPS TBS869 3xTL5-14W/840 HFP114 D8H (1.000) 3600 48.0

    Total: 14400 192.0

    Page 27

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    33/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Emergency Respond Team / Luminaire parts list

    4 Pieces PHILIPS TBS869 3xTL5-14W/840 HFP114 D8HArticle No.:Luminaire Luminous Flux: 3600 lmLuminaire Wattage: 48.0 WLuminaire classification according to CIE: 100CIE flux code: 73 98 100 100 77Fitting: 3 x TL5-14W/840 (Correction Factor1.000).

    See our luminairecatalog for an image of

    the luminaire.

    Page 28

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    34/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Emergency Respond Team / Workplane / Value Chart (E)

    391415458482488497485464456447461482488495484458438405

    399426472497504511497475468450477494508504483469427

    408438486513520527512489481464491509524520498483438

    422458510538545553537513507501519535551549525508460

    426486524551567557548523513513520545562560553518471431

    433542560577590574557541537553572588584560541490

    448550578603594584559548548563582598593568550497381

    455559595604621605580574569585603619613587568516490

    469567602611623608583576575590606621610584565519 514474578614624637623597591586596620629580529490

    519639620476581617627641626601594589599624633583559523

    505643624453577613623637623598592588598625633586558522

    503634616414573608617631616592585582592618627580554518

    504626609565598606619604580574570580606616571543508

    484614598503576598609603578563559563578605563535501

    476604595494560579589582557541537541557584564519488

    468578571483543562573566545529515534558549496462

    450563560463522539550544523508491509527510455

    531540428451509524536529509495479534514467

    479510518

    405424475492508502485472462511495470444415 465483505397415475494511505490476468513504487447

    413 456

    5.00 m0.00 0.37 0.97 1.43 2.03 2.42 4.23 4.53

    4.00 m

    0.00

    0.20

    0.35

    0.51

    0.79

    0.92

    1.09

    1.25

    1.59

    2.20

    2.37

    2.66

    2.83

    3.01

    3.17

    3.63

    3.80

    Values in Lux, Scale 1 : 36Not all calculated values could be displayed.

    Position of surface in room:Working plane with 0.200 mBoundary Zone

    Marked point:(0.200 m, 0.200 m, 0.800 m)

    Grid: 128 x 128 Points

    Eav

    [lx] Emin

    [lx] Emax

    [lx] u0 Emin/ Emax523 86 643 0.164 0.133

    Page 30

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    35/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Male WC RM / Summary

    120

    120

    120

    120

    160

    160

    160

    160160

    160

    200

    200

    200

    200

    200

    200

    3.00 m0.00 1.10 2.10

    4.00 m

    0.00

    0.20

    1.80

    3.80

    Height of Room: 2.600 m, Mounting Height: 2.735 m, Light loss factor:

    0.80

    Values in Lux, Scale 1:52

    Surface [%] Eav[lx] Emin[lx] Emax[lx] u0

    Workplane / 166 76 233 0.459

    Floor 20 150 14 233 0.095

    Ceiling 70 35 17 92 0.470

    Walls (4) 50 82 20 913 /

    Workplane:Height: 0.000 mGrid: 32 x 32 PointsBoundary Zone: 0.200 m

    Luminaire Parts List

    Specific connected load: 11.67 W/m = 7.05 W/m/100 lx (Ground area: 12.00 m)

    No. Pieces Designation (Correction Factor) [lm] P [W]

    1 4 Philips FBS271 1xPL-T/4P32W HFP M (1.000) 2400 35.0

    Total: 9600 140.0

    Page 31

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    36/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Male WC RM / Luminaire parts list

    4 Pieces Philips FBS271 1xPL-T/4P32W HFP MArticle No.:Luminaire Luminous Flux: 2400 lmLuminaire Wattage: 35.0 WLuminaire classification according to CIE: 100CIE flux code: 74 100 100 100 73Fitting: 1 x PL-T/4P32W/840 (Correction Factor1.000).

    Page 32

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    37/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Male WC RM / Workplane / Value Chart (E)

    109125143161174180176165151142

    112130158180195201197184167155

    113126154189203209207195177164

    114127146185211219217205186174

    109122140160207224223211196183

    105115131148160225223214202192

    100109121136144166222219212204

    9199107118123126187221221216

    213232227166165159164165

    203232229173172166168172

    168227225176175170171175

    167218216178175167168168

    161195202169165156159157

    145166182151148140141140

    129140156128125119119119

    3.00 m0.00 1.10 2.10

    4.00 m

    0.00

    0.20

    1.80

    3.80

    Values in Lux, Scale 1 : 32Not all calculated values could be displayed.

    Position of surface in room:Working plane with 0.200 mBoundary ZoneMarked point:(0.200 m, 0.200 m, 0.000 m)

    Grid: 32 x 32 Points

    Eav

    [lx] Emin

    [lx] Emax

    [lx] u0 Emin/ Emax

    166 76 233 0.459 0.326

    Page 34

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    38/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Female WC RM / Summary

    150

    180

    180

    210

    210

    210

    210

    210

    210210

    210

    210

    210

    210

    240

    240

    240

    3.00 m0.00 1.45

    2.60 m

    0.00

    0.20

    1.25

    2.40

    Height of Room: 2.600 m, Mounting Height: 2.735 m, Light loss factor:

    0.80

    Values in Lux, Scale 1:34

    Surface [%] Eav[lx] Emin[lx] Emax[lx] u0

    Workplane / 203 138 247 0.682

    Floor 64 184 54 239 0.293

    Ceiling 78 73 43 113 0.587

    Walls (4) 78 136 42 381 /

    Workplane:Height: 0.000 mGrid: 32 x 32 PointsBoundary Zone: 0.200 m

    Luminaire Parts List

    Specific connected load: 13.46 W/m = 6.64 W/m/100 lx (Ground area: 7.80 m)

    No. Pieces Designation (Correction Factor) [lm] P [W]

    1 3 Philips FBS271 1xPL-T/4P32W HFP M (1.000) 2400 35.0

    Total: 7200 105.0

    Page 35

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    39/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Female WC RM / Luminaire parts list

    3 Pieces Philips FBS271 1xPL-T/4P32W HFP MArticle No.:Luminaire Luminous Flux: 2400 lmLuminaire Wattage: 35.0 WLuminaire classification according to CIE: 100CIE flux code: 74 100 100 100 73Fitting: 1 x PL-T/4P32W/840 (Correction Factor1.000).

    Page 36

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    40/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Female WC RM / Workplane / Value Chart (E)

    155 158 153 154 148 147 143 197 199 214 221 232 231 235

    165 169 165 166 160 159 154 201 205 220 226 237 236 241

    170 176 172 174 167 165 161 199 204 217 222 233 232 238

    180 188 185 188 181 178 173 202 205 218 223 234 233 239

    191 201 198 202 195 190 185 192 196 209 214 225 224 230

    199 209 207 211 204 199 194 188 192 204 210 222 221 225

    205 216 213 216 209 206 202 181 186 200 207 214 214 215

    208 220 217 219 212 210 205

    209 221 218 220 214 211 207 178 184 196 204 212 212 214

    208 219 216 219 212 210 206 181 186 199 206 215 215 215

    205 216 214 217 209 206 201 189 193 205 211 223 221 225

    199 210 208 212 204 200 195 194 198 210 215 226 225 230

    189 198 197 201 195 191 184 203 206 219 225 236 235 240

    180 188 185 188 182 179 173 200 205 219 224 236 234 240

    173 179 177 179 175 173 167 203 207 223 228 239 238 243

    3.00 m0.00 0.20 1.45 2.80

    2.60 m

    0.00

    0.20

    1.25

    1.35

    2.40

    Values in Lux, Scale 1 : 22Not all calculated values could be displayed.

    Position of surface in room:

    Working plane with 0.200 mBoundary ZoneMarked point:(0.200 m, 0.200 m, 0.000 m)

    Grid: 32 x 32 Points

    Eav

    [lx] Emin

    [lx] Emax

    [lx] u0 Emin/ Emax203 138 247 0.682 0.560

    Page 38

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    41/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Janitor RM / Summary

    210 210

    210210

    210210

    240

    240240

    240240

    270

    270

    270

    270270

    270

    270

    270

    1.50 m0.00

    2.60 m

    0.00

    Height of Room: 2.600 m, Mounting Height: 2.735 m, Light loss factor:

    0.80

    Values in Lux, Scale 1:34

    Surface [%] Eav[lx] Emin[lx] Emax[lx] u0

    Workplane / 256 192 301 0.749

    Floor 64 256 195 301 0.760

    Ceiling 78 144 114 163 0.791

    Walls (4) 78 194 110 428 /

    Workplane:Height: 0.000 mGrid: 32 x 32 PointsBoundary Zone: 0.000 m

    Luminaire Parts List

    Specific connected load: 8.97 W/m = 3.51 W/m/100 lx (Ground area: 3.90 m)

    No. Pieces Designation (Correction Factor) [lm] P [W]

    1 1 Philips FBS271 1xPL-T/4P32W HFP M (1.000) 2400 35.0

    Total: 2400 35.0

    Page 39

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    42/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Janitor RM / Luminaire parts list

    1 Pieces Philips FBS271 1xPL-T/4P32W HFP MArticle No.:Luminaire Luminous Flux: 2400 lmLuminaire Wattage: 35.0 WLuminaire classification according to CIE: 100CIE flux code: 74 100 100 100 73Fitting: 1 x PL-T/4P32W/840 (Correction Factor1.000).

    Page 40

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    43/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Janitor RM / Workplane / Value Chart (E)

    220

    199

    212

    222

    236

    248

    253

    257

    259

    257

    254

    248

    231

    220

    206

    195

    237

    210

    226

    237

    255

    265

    272

    276

    279

    277

    272

    263

    248

    237

    218

    211

    236

    211

    227

    240

    259

    270

    278

    283

    285

    283

    278

    268

    251

    238

    218

    211

    247

    217

    235

    249

    272

    284

    291

    296

    298

    296

    292

    283

    262

    248

    227

    220

    245

    216

    235

    250

    274

    287

    292

    296

    299

    297

    294

    286

    266

    250

    228

    221

    235

    212

    233

    250

    275

    289

    293

    297

    300

    298

    296

    288

    267

    250

    229

    221

    231

    209

    233

    249

    275

    288

    292

    296

    300

    297

    295

    287

    266

    250

    228

    221

    230

    208

    232

    247

    273

    285

    291

    296

    299

    297

    294

    285

    264

    249

    228

    221

    219

    200

    223

    237

    260

    272

    279

    284

    288

    285

    280

    270

    253

    239

    219

    212

    215

    198

    216

    231

    251

    262

    269

    275

    278

    275

    271

    261

    244

    231

    213

    202

    1.50 m0.00

    2.60 m

    0.00

    Values in Lux, Scale 1 : 21Not all calculated values could be displayed.

    Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)

    Grid: 32 x 32 Points

    Eav

    [lx] Emin

    [lx] Emax

    [lx] u0 Emin/ Emax256 192 301 0.749 0.637

    Page 42

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    44/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Corridor / Summary

    160

    160 160

    200

    240

    240

    240

    240

    240

    240

    240

    240

    280280

    280

    280

    280280

    280

    280

    280 280

    280

    5.00 m0.00 2.50

    13.00 m

    0.00

    2.50

    Height of Room: 2.800 m, Mounting Height: 2.935 m, Light loss factor:

    0.80

    Values in Lux, Scale 1:167

    Surface [%] Eav[lx] Emin[lx] Emax[lx] u0

    Workplane / 241 127 314 0.529

    Floor 64 241 132 315 0.547

    Ceiling 78 140 97 170 0.690

    Walls (7) 78 152 92 226 /

    Workplane:Height: 0.000 mGrid: 128 x 64 PointsBoundary Zone: 0.000 m

    Luminaire Parts List

    Specific connected load: 4.17 W/m = 1.73 W/m/100 lx (Ground area: 58.75 m)

    No. Pieces Designation (Correction Factor) [lm] P [W]

    1 7 Philips FBS271 1xPL-T/4P32W HFP M (1.000) 2400 35.0

    Total: 16800 245.0

    Page 43

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    45/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Corridor / Luminaire parts list

    7 Pieces Philips FBS271 1xPL-T/4P32W HFP MArticle No.:Luminaire Luminous Flux: 2400 lmLuminaire Wattage: 35.0 WLuminaire classification according to CIE: 100CIE flux code: 74 100 100 100 73Fitting: 1 x PL-T/4P32W/840 (Correction Factor1.000).

    Page 44

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    46/419

    ZOC Control Building

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Corridor / Workplane / Value Chart (E)

    164

    190

    219

    229

    223

    213

    210

    216

    232

    242

    234

    221

    212

    212

    222

    233

    231

    218

    201

    192197

    206

    203

    191

    158

    190

    227

    268

    279

    266

    241

    233

    249

    280

    293

    283

    256

    234

    238

    262

    283

    280

    256

    222

    209222

    245

    243

    224

    176

    208

    244

    285

    300

    286

    262

    255

    269

    300

    314

    303

    276

    256

    259

    280

    301

    296

    270

    237

    216226

    246

    245

    222

    179

    212

    243

    275

    288

    279

    265

    262

    272

    293

    304

    295

    277

    264

    263

    276

    289

    284

    264

    236

    208

    203

    241

    281

    296

    282

    257

    250

    264

    296

    312

    301

    273

    252

    254

    274

    295

    289

    261

    223

    183

    182

    218

    261

    274

    262

    237

    228

    243

    275

    289

    281

    252

    230

    231

    252

    273

    267

    239

    200

    152

    159

    182

    211

    222

    221

    211

    211

    215

    229

    238

    230

    218

    207

    206

    213

    223

    217

    198

    167

    143

    5.00 m0.00 2.50

    13.00 m

    0.00

    2.50

    Values in Lux, Scale 1 : 102Not all calculated values could be displayed.

    Position of surface in room:Marked point:(0.000 m, 0.000 m, 0.000 m)

    Grid: 128 x 64 Points

    Eav

    [lx] Emin

    [lx] Emax

    [lx] u0 Emin/ Emax

    241 127 314 0.529 0.405

    Page 46

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    47/419

    Battery Room

    Calculation Grid: Battery Room GridHorizontal Illuminance

    rid Name:

    rid Type:

    rid Units:

    Battery Room Grid

    Horizontal Illuminance

    Lux

    Grid Origin:

    Grid Orient:

    Grid Elev.:

    (0.00, 0.00)

    0.80

    Grid Surface:

    Grid Hinge:

    Grid Azimuth:

    n/a

    0

    0

    tatistical Area Summary

    tat. Area Ave Max Min Ave/Min Max/Min Std. Dev.

    attery Room Grid 222.2 409.0 72.8 3.0 5.6 99.0

    alculation Grid

    0.25 0.75 1.25 1.75 2.25 2.75 3.25 3.75 4.25 4.75

    75

    25

    75

    25

    75

    25

    75

    25

    75

    25

    85.7

    127.6

    181.9

    236.7

    269.1

    261.1

    217.4

    160.4

    110.2

    73.3

    97.7

    149.6

    218.4

    289.0

    331.2

    320.7

    264.0

    191.0

    127.8

    82.8

    107.9

    166.1

    243.3

    322.3

    369.0

    357.5

    294.2

    212.5

    141.5

    91.1

    115.2

    177.1

    258.8

    341.6

    390.6

    378.3

    312.0

    226.0

    150.8

    97.0

    118.8

    184.4

    270.3

    357.2

    408.2

    395.3

    325.8

    235.5

    156.2

    99.4

    118.9

    184.7

    270.9

    358.0

    409.0

    395.8

    325.9

    235.4

    156.0

    99.3

    115.8

    178.2

    260.4

    343.6

    392.2

    379.1

    312.0

    225.7

    150.4

    96.7

    108.8

    167.6

    245.5

    324.7

    370.7

    357.9

    293.6

    211.7

    140.8

    90.7

    98.7

    151.3

    220.6

    291.3

    332.5

    320.6

    263.0

    189.9

    127.0

    82.3

    86.6

    129.0

    183.7

    238.4

    269.9

    260.7

    216.3

    159.3

    109.3

    72.8

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    48/419

    Battery Room

    1. Crouse-Hinds ELLK92036_36 72W Linear Fluorescent

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    49/419

    ZOC Control Building(EMERGENCY)

    Date: 21.09.2012Operator: GuoBin

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    50/419

    ZOC Control Building(EMERGENCY)

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Switchgear RM.(EMERGENCY) / Summary

    80

    80

    160

    240

    240

    240

    240

    240

    240

    320

    320

    320

    320

    320

    320

    320

    320

    10.00 m0.00 2.50 5.10

    24.00 m

    0.00

    3.60

    5.09

    6.28

    7.68

    9.0810.48

    11.70

    12.89

    14.10

    16.08

    17.30

    18.88

    20.09

    Height of Room: 2.800 m, Mounting Height: 2.800 m, Light loss factor:

    0.80

    Values in Lux, Scale 1:309

    Surface [%] Eav[lx] Emin[lx] Emax[lx] u0

    Workplane / 179 7.05 389 0.039

    Floor 27 145 1.10 388 0.008

    Ceiling 78 40 5.50 218 0.136

    Walls (4) 78 33 4.16 149 /

    Workplane:Height: 0.000 mGrid: 128 x 128 PointsBoundary Zone: 0.500 m

    Luminaire Parts List

    Specific connected load: 3.15 W/m = 1.76 W/m/100 lx (Ground area: 240.00 m)

    No. Pieces Designation (Correction Factor) [lm] P [W]

    1 12 PHILIPS TBS869 4xTL5-14W/840 HFP114 D8H (1.000) 4800 63.0

    Total: 57600 756.0

    Page 2

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    51/419

    ZOC Control Building(EMERGENCY)

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Switchgear RM.(EMERGENCY) / Workplane / Value Chart (E)

    42

    44

    45

    46

    4648

    48

    46

    46

    46

    46

    45

    44

    43

    45

    4542

    42

    47

    47

    45

    44

    44

    45

    44

    143

    173

    166

    147

    152175

    179

    157

    145

    164

    180

    166

    144

    150

    173

    170136

    122

    166

    181

    164

    141

    153

    173

    164

    244

    303

    287

    245

    254304

    313

    263

    229

    257

    291

    259

    216

    230

    273

    277208

    230

    290

    265

    274

    316

    301

    169

    253

    297

    366

    350

    264

    303371

    380

    325

    294

    351

    315

    363

    342

    265

    303

    272

    224

    236

    292

    258

    255

    304

    328

    281

    234

    292

    277

    236

    246297

    305

    256

    229

    301

    227

    260

    295

    261

    125

    152

    146

    127

    151

    132

    10.00 m0.00 1.53 4.52 6.60

    24.00 m

    0.00

    3.60

    5.09

    6.28

    7.68

    9.08

    9.88

    10.80

    11.70

    12.6013.28

    14.10

    16.08

    16.7917.48

    18.28

    19.25

    20.09

    Values in Lux, Scale 1 : 188Not all calculated values could be displayed.

    Position of surface in room:Working plane with 0.500 mBoundary ZoneMarked point:(0.500 m, 0.500 m, 0.000 m)

    Grid: 128 x 128 Points

    Eav

    [lx] Emin

    [lx] Emax

    [lx] u0 Emin/ Emax

    179 7.05 389 0.039 0.018

    Page 3

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    52/419

    ZOC Control Building(EMERGENCY)

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    AHU RM.(EMERGENCY) / Summary

    100

    100

    100

    100

    150

    150150

    150

    150

    150

    200

    200

    200 200

    200

    200

    200200

    200

    200

    200 200

    200

    200

    200

    250

    250250

    250

    250

    250

    250

    250

    250

    250250 250

    250

    250

    250250

    10.00 m0.00

    4.00 m

    0.00

    Height of Room: 2.800 m, Mounting Height: 2.800 m, Light loss factor:0.80

    Values in Lux, Scale 1:72

    Surface [%] Eav[lx] Emin[lx] Emax[lx] u0

    Workplane / 158 47 287 0.301

    Floor 27 152 41 289 0.271

    Ceiling 78 45 34 56 0.745

    Walls (4) 78 65 34 246 /

    Workplane:Height: 0.000 mGrid: 64 x 32 PointsBoundary Zone: 0.200 m

    UGR Lengthways- Across to luminaire axisLeft Wall 12 17Lower Wall 12 17(CIE, SHR = 0.25.)

    Luminaire Parts List

    Specific connected load: 3.15 W/m = 2.00 W/m/100 lx (Ground area: 40.00 m)

    No. Pieces Designation (Correction Factor) [lm] P [W]

    1 2 PHILIPS TBS869 4xTL5-14W/840 HFP114 D8H (1.000) 4800 63.0

    Total: 9600 126.0

    Page 4

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    53/419

    ZOC Control Building(EMERGENCY)

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    AHU RM.(EMERGENCY) / Workplane / Value Chart (E)

    51 52 56 62 63 65 65 63 60 58 57 57 59 62 64 65 64 62 60 53 5259 63 71 79 83 85 83 79 73 69 66 68 72 77 82 85 84 80 74 65 62

    72 81 94 108 116 119 114 106 96 88 84 86 93 102 112 118 117 111 100 85 76

    93 105 125 146 158 162 154 141 124 113 108 110 120 134 150 160 160 151 133 111 98

    109 124 150 176 192 197 186 168 146 132 125 128 140 160 181 194 195 183 160 132 114

    124 143 174 205 225 230 217 194 168 149 141 145 161 185 210 227 229 213 186 153 129

    135 154 190 226 250 255 239 213 182 161 151 156 175 201 231 251 254 235 203 166 139

    144 166 204 244 272 278 259 229 195 170 160 165 186 217 249 273 277 255 219 178 146

    147 170 210 250 279 285 266 233 198 172 163 168 189 221 255 281 285 261 225 183 148

    144 168 208 250 278 284 266 233 197 172 161 168 188 221 255 280 285 260 224 180 146

    10.00 m0.00

    4.00 m

    0.00

    Values in Lux, Scale 1 : 72Not all calculated values could be displayed.

    Position of surface in room:Working plane with 0.200 mBoundary ZoneMarked point:

    (0.200 m, 0.200 m, 0.000 m)

    Grid: 64 x 32 Points

    Eav

    [lx] Emin

    [lx] Emax

    [lx] u0 Emin/ Emax158 47 287 0.301 0.166

    Page 5

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    54/419

    ZOC Control Building(EMERGENCY)

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Instrument Equipment&Telecom Equipment RM.(EMERGENCY) / Summary

    180

    180

    180180

    180

    180

    180

    180

    180

    180180

    180

    180180

    360

    540

    540

    540

    720

    720

    720

    720

    720

    10.00 m0.00 1.30 2.49 3.70 4.89 6.10 7.29 8.50

    10.00 m

    0.00

    3.79

    4.59

    5.60

    6.40

    8.20

    9.00

    Height of Room: 2.800 m, Mounting Height: 2.800 m, Light loss factor:

    0.80

    Values in Lux, Scale 1:129

    Surface [%] Eav[lx] Emin[lx] Emax[lx] u0

    Workplane / 132 13 875 0.097

    Floor 47 86 3.45 311 0.040

    Ceiling 78 58 17 379 0.294

    Walls (4) 78 50 11 352 /

    Workplane:Height: 1.500 mGrid: 128 x 128 PointsBoundary Zone: 0.000 m

    Luminaire Parts List

    Specific connected load: 2.40 W/m = 1.83 W/m/100 lx (Ground area: 100.00 m)

    No. Pieces Designation (Correction Factor) [lm] P [W]

    1 5 PHILIPS TBS869 3xTL5-14W/840 HFP114 D8H (1.000) 3600 48.0

    Total: 18000 240.0

    Page 6

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    55/419

    ZOC Control Building(EMERGENCY)

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Instrument Equipment&Telecom Equipment RM.(EMERGENCY) / Workplane / Value

    Chart (E)

    36

    31

    33

    34

    34

    34

    34

    34

    33

    33

    30

    29

    30

    27

    25

    26

    2525

    24

    21

    22

    20

    18

    18

    19

    31

    31

    31

    32

    32

    32

    32

    32

    31

    31

    30

    29

    29

    26

    25

    25

    2323

    23

    18

    18

    16

    16

    16

    18

    36

    32

    35

    35

    35

    36

    35

    35

    34

    34

    33

    32

    32

    26

    24

    24

    2626

    25

    21

    21

    17

    20

    36

    32

    35

    35

    35

    36

    35

    35

    35

    35

    33

    32

    32

    26

    26

    26

    26

    21

    17

    20

    41

    36

    40

    40

    40

    41

    41

    41

    40

    40

    39

    37

    37

    31

    32

    30

    30

    23

    22

    25

    47

    43

    46

    47

    47

    49

    48

    48

    48

    48

    47

    46

    45

    40

    40

    42

    42

    35

    29

    33

    73

    72

    78

    80

    79

    82

    83

    84

    84

    83

    82

    85

    83

    75

    76

    83

    84

    67

    59

    70

    200

    270

    320

    302

    268

    264

    299

    325

    287

    214

    100

    213

    304

    302

    286

    332

    315

    210

    255

    243

    410

    581

    700

    644

    537

    524

    631

    706

    623

    647

    699

    635

    726

    657

    412

    556

    515

    472

    682

    823

    749

    615

    598

    728

    835

    733

    744

    825

    739

    853

    762

    470

    652

    600

    328

    458

    548

    510

    435

    425

    500

    552

    490

    490

    530

    483

    558

    517

    333

    489

    378

    129

    154

    178

    173

    159

    158

    174

    180

    162

    151

    178

    159

    188

    184

    135

    161

    140

    55

    51

    55

    55

    57

    59

    55

    54

    50

    33

    50

    45

    53

    54

    48

    44

    47

    45

    41

    44

    45

    45

    46

    42

    41

    37

    22

    30

    32

    37

    37

    33

    29

    32

    37

    34

    37

    38

    38

    38

    33

    33

    30

    13

    20

    24

    25

    25

    21

    20

    24

    33

    30

    32

    33

    33

    33

    28

    28

    25

    13

    20

    21

    21

    21

    19

    16

    18

    29

    26

    29

    30

    30

    29

    26

    26

    23

    14

    14

    16

    16

    16

    14

    13

    14

    23

    19

    16

    16

    16

    16

    28

    24

    27

    27

    27

    26

    25

    25

    23

    18

    18

    18

    18

    18

    16

    14

    14

    15

    10.00 m0.00 0.90 1.69 2.49 3.29 4.09 4.89 5.69 6.49 7.29 8.09 8.89

    10.00 m

    0.00

    3.79

    4.59

    5.60

    6.40

    8.20

    9.00

    Values in Lux, Scale 1 : 79Not all calculated values could be displayed.

    Position of surface in room:Marked point:(0.000 m, 0.000 m, 1.500 m)

    Grid: 128 x 128 Points

    Eav[lx] Emin[lx] Emax[lx] u0 Emin/ Emax132 13 875 0.097 0.015

    Page 7

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    56/419

    ZOC Control Building(EMERGENCY)

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Emergency Respond Team.(EMERGENCY) / Summary

    9090

    180 180 180

    270270 270

    270

    270

    360

    360

    360360

    450

    450

    450450

    450450

    450

    5.00 m0.00 0.37 0.97 1.43 2.03 2.42 4.23 4.61

    4.00 m

    0.00

    0.20

    0.400.58

    0.79

    0.99

    1.20

    1.59

    2.20

    2.66

    3.01

    3.63

    Height of Room: 2.800 m, Mounting Height: 2.800 m, Light loss factor:

    0.80

    Values in Lux, Scale 1:52

    Surface [%] Eav[lx] Emin[lx] Emax[lx] u0

    Workplane / 264 37 461 0.140

    Floor 64 162 17 332 0.107

    Ceiling 78 110 72 144 0.652

    Walls (4) 78 124 2.68 299 /

    Workplane:Height: 0.800 mGrid: 128 x 128 PointsBoundary Zone: 0.200 m

    Luminaire Parts List

    Specific connected load: 4.80 W/m = 1.82 W/m/100 lx (Ground area: 20.00 m)

    No. Pieces Designation (Correction Factor) [lm] P [W]

    1 2 PHILIPS TBS869 3xTL5-14W/840 HFP114 D8H (1.000) 3600 48.0

    Total: 7200 96.0

    Page 8

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    57/419

    ZOC Control Building(EMERGENCY)

    21.09.2012

    Operator GuoBinTelephone

    Faxe-Mail [email protected]

    Emergency Respond Team.(EMERGENCY) / Workplane / Value Chart (E)

    311344382406413415402382374365377396401409399374356323

    323358397423431432416395387374397411425425405389349

    330369409438446446429407398386410424440440419402359

    336375421450459458441416409404422436454456433414368

    335398423450460449440417407408415437455456448414372333

    312416429445449433418403401416430446446426407364

    316409429444434426403393394408423438438418400358228

    300374402409415402382377375387399412412394377340326

    290354378385389378360356355366375387384368352319 305266321343349354345330326323329343348320291268

    289333323255304323329335327313309306312325329303293274

    246308298219258273278285280269266265269279283260250236

    229261252212236249253261256247245244247256259238228216

    190236228186195198207205199197197199205207190182175

    156183177144169174183182178176176176178183168162159

    122161157112132134143143140139139139140143136129130

    10911911592108109119119119119115116119113103105

    811071037388889999991009695939386

    9392686882829293939389888881

    858686

    6060707182838384828277777478 82858860607375878888888786818178

    83 86

    5.00 m0.00 0.37 0.97 1.43 2.03 2.42 4.23 4.53

    4.00 m

    0.00

    0.20

    0.35

    0.51

    0.79

    0.92

    1.09

    1.25

    1.59

    2.20

    2.37

    2.66

    2.83

    3.01

    3.17

    3.63

    3.80

    Values in Lux, Scale 1 : 36Not all calculated values could be displayed.

    Position of surface in room:Working plane with 0.200 mBoundary Zone

    Marked point:(0.200 m, 0.200 m, 0.800 m)

    Grid: 128 x 128 Points

    Eav

    [lx] Emin

    [lx] Emax

    [lx] u0 Emin/ Emax264 37 461 0.140 0.080

    Page 9

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    58/419

    ZOC

    25.12.2011

    OperatorTelephone

    Faxe-Mail

    Philips XWC120 1xSOX-E18W / Luminaire Data Sheet

    Luminous emittance 1:

    80

    120

    160

    cd/klm 78%C0 - C180 C90 - C270

    0 15 30 45

    60

    75

    90

    105

    120

    135150165180165150135

    120

    105

    90

    75

    60

    45 30 15 0

    Luminaire classification according to CIE: 88CIE flux code: 35 65 86 88 78

    FWC110/120/121 and FCC110/120? for low-level lighting

    FWC110/120/121 (wall-mounted) and FCC110/120 (ceiling-mounted) areattractive, low-energy luminaires for all-night security and amenity lighting.The high-reflectance white plate and translucent bowl with prismatic controlproduce excellent light distribution for low-level lighting of walls, corridorsand surroundings.

    Due to missing symmetry properties, no UGR tablecan be displayed for this luminaire.

    Page 1

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    59/419

    ZOC

    25.12.2011

    OperatorTelephone

    Faxe-Mail

    Control Room walkway / Planning data

    47.80 m24.45

    10.70 m

    -25.49

    Maintenance factor: 0.80, ULR (Upward Light Ratio): 1.5% Scale 1:336

    Luminaire Parts List

    No. Pieces Designation (Correction Factor) [lm] P [W]

    1 22 Philips XWC120 1xSOX-E18W (1.000) 1800 25.0

    Total: 39600 550.0

    Page 2

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    60/419

    ZOC

    25.12.2011

    OperatorTelephone

    Faxe-Mail

    Control Room walkway / Copy of Ground Element 1 / Surface 2 / Value Chart (E)

    1.65 m0.00

    0.04 m

    Values in Lux, Scale 1 : 12Not all calculated values could be displayed.

    Position of surface in external scene:Marked point:(26.100 m, -25.450 m, 0.000 m)

    Grid: 128 x 16 Points

    Eav[lx] Emin[lx] Emax[lx] u0 Emin/ Emax24 22 26 0.907 0.845

    Page 3

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    61/419

    ZOC

    25.12.2011

    OperatorTelephone

    Faxe-Mail

    Control Room walkway / Copy of Ground Element 1 / Surface 2 / Value Chart (E)

    24

    26

    30

    32

    33

    33

    29

    28

    30

    31

    28

    27

    31

    31

    27

    28

    31

    30

    27

    28

    30

    26

    19

    19

    1.65 m

    34.46 m

    0.00

    33.03

    Values in Lux, Scale 1 : 270Not all calculated values could be displayed.

    Position of surface in external scene:Marked point:(24.500 m, 9.075 m, 0.000 m)

    Grid: 128 x 16 Points

    Eav[lx] Emin[lx] Emax[lx] u0 Emin/ Emax

    26 2.41 34 0.092 0.070

    Page 4

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    62/419

    ZOC

    25.12.2011

    OperatorTelephone

    Faxe-Mail

    Control Room walkway / Copy of Ground Element 1 / Surface 1 / Value Chart (E)

    26 29 28 26 26 30 30 27 27 30 30 27 26 28 29 27 24 24

    25 30 29 26 27 30 31 28 27 30 31 28 26 28 30 27 24 25

    21.77 m0.00 1.60

    1.50 m

    0.00

    Values in Lux, Scale 1 : 156Not all calculated values could be displayed.

    Position of surface in external scene:Marked point:

    (24.500 m, 9.075 m, 0.000 m)

    Grid: 128 x 16 Points

    Eav[lx] Emin[lx] Emax[lx] u0 Emin/ Emax26 4.29 32 0.164 0.135

    Page 5

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    63/419

    ZOC

    25.12.2011

    OperatorTelephone

    Faxe-Mail

    Control Room walkway / Copy of Ground Element 1 / Surface 1 / Value Chart (E)

    0.03 m

    1.50 m

    0.00

    Values in Lux, Scale 1 : 12Not all calculated values could be displayed.

    Position of surface in external scene:Marked point:(47.769 m, 10.575 m, 0.000 m)

    Grid: 128 x 16 Points

    Eav[lx] Emin[lx] Emax[lx] u0 Emin/ Emax

    21 21 22 0.977 0.959

    Page 6

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    64/419

    ZOC

    25.12.2011

    OperatorTelephone

    Faxe-Mail

    Control Room walkway / Copy of Copy of Ground Element 1 / Surface 1 / Value Chart

    (E)

    28

    19

    12

    19

    27

    29

    27

    28

    31

    29

    27

    31

    32

    28

    28

    31

    30

    28

    3034

    33

    30

    25

    15

    1.50 m

    36.00 m

    0.00

    1.43

    34.45

    Values in Lux, Scale 1 : 282Not all calculated values could be displayed.

    Position of surface in external scene:Marked point:(46.269 m, 9.075 m, 0.000 m)

    Grid: 128 x 16 Points

    Eav[lx] Emin[lx] Emax[lx] u0 Emin/ Emax25 1.75 34 0.069 0.051

    Page 7

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    65/419

    ZOC

    25.12.2011

    OperatorTelephone

    Faxe-Mail

    Control Room walkway / Copy of Copy of Ground Element 1 / Surface 1 / Value Chart

    (E)

    24

    25

    25

    25

    24

    23

    25

    24

    28

    28

    29

    29

    27

    26

    27

    26

    30

    29

    30

    29

    27

    26

    27

    26

    30

    29

    30

    29

    26

    26

    27

    26

    28

    28

    28

    29

    23.30 m0.00 1.65

    1.50 m

    0.00

    Values in Lux, Scale 1 : 167Not all calculated values could be displayed.

    Position of surface in external scene:

    Marked point:(26.100 m, -25.450 m, 0.000 m)

    Grid: 16 x 128 Points

    Eav

    [lx] Emin

    [lx] Emax

    [lx] u0 Emin/ Emax26 3.50 32 0.134 0.111

    Page 8

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    66/419

    ZOC CATERING BUILDING

    Partner for Contact:

    Order No.:Company:Customer No.:

    Date: 21.09.2012Operator:

  • 7/27/2019 Mm Ztk 1a Zoc Ele Cal 5002 Rev c2_in

    67/419

    ZOC CATERING BUILDING

    21.09.2012

    OperatorTelephone

    Faxe-Mail

    PHILIPS TBS869 4xTL5-14W/840 HFP114 D8H / Luminaire Data Sheet

    See our luminaire catalog for an image of theluminaire.

    Luminous emittance 1:

    200

    300

    400

    500

    cd/klm 78%C0 - C180 C90 - C270

    0 15 30

    45

    60

    75

    90

    105105

    90

    75

    60

    45

    30 15 0

    Luminaire classification according to CIE: 100CIE flux code: 75 99 100 100 78

    Luminous emittance 1:

    Glare Evaluation According to UGR

    Ceiling 70 70 50 50 30 70 70 50 50 30

    Walls 50 30 50 30 30 50 30 50 30 30

    Floor 20 20 20 20 20 20 20 20 20 20

    Room SizeX Y

    Viewing direction at right anglesto lamp axis

    Viewing direction parallelto lamp axis

    2H 2H 12.0 13.0 12.3 13.2 13.4 17.2 18.1 17.4 18.3 18.5

    3H 11.9 12.7 12.2 13.0 13.2 17.1 17.9 17.4 18.2 18.4

    4H 11.8 12.6 12.1 12.9 13.1 17.0 17.8 17.3 18.1 18.3

    6H 11.8 12.5 12.1 12.8 13.0 17.0 17.7 17.3 18.0 18.2

    8H 11.7 12.4 12.1 12.7 13.0 16.9 17.6 17.3 17.9 18.2

    12H 11.7 12.3 12.0 12.6 13.0 16.9 17.5 17.2 17.8 18.2

    4H 2H 12.2 12.9 12.5 13.2 13.5 17.0 17.7 17.3 18.0 18.3

    3H 12.0 12.7 12.4 13.0 13.3 16.9 17.5 17.3 17.9 18.2

    4H 12.0 12.5