Publication 2727-IN010A-EN-P - May 2004 Installation Instructions MobileView Junction Box (Catalog Number 2727-MRJB2) English The MobileView Junction Box (2727-MRJB2) integrates the following terminals into the control system: MobileView Guard G750 MobileView Machine Terminal MT750 The Junction Box can be used either inside or outside a control cabinet based on its IP65 rating. The cables that connect the MobileView terminal to the Junction Box are available as separate catalog numbers. MobileView Connection Cable (Catalog Numbers 2727-MRTxx) connects the MobileView terminal to the Junction Box. The Connection Cable is available in 5, 10, 15, 20 meter (16.4, 32.8, 49.2, 65.6 foot) lengths. MobileView Junction Box Cable (2727-MREY1) connects the Junction Box to the MobileView Connection Cable when the Junction Box is mounted inside a cabinet. The cable is 2 meters (6.56 feet) long. Inside. . . Junction Box Dimensions and Connections ...................................................................... 2 Mounting the Junction Box on a DIN Rail ......................................................................... 3 Connecting the MobileView Terminal to the Junction Box ............................................... 5 Junction Box Pinout and Wiring ........................................................................................ 6 Specifications .................................................................................................................... 7

Upload: others

Post on 09-Jun-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MobileView Junction Box - RockwellAutomation.com › idc › ... · Use the dimensions below for drilling the holes to mount the MobileView Junction Box to a wall. Use the manufacturer’s

Installation Instructions

MobileView Junction Box(Catalog Number 2727-MRJB2)

English

The MobileView Junction Box (2727-MRJB2) integrates the following terminals into the control system:

• MobileView Guard G750

• MobileView Machine Terminal MT750

The Junction Box can be used either inside or outside a control cabinet based on its IP65 rating.

The cables that connect the MobileView terminal to the Junction Box are available as separate catalog numbers.

• MobileView Connection Cable (Catalog Numbers 2727-MRTxx) connects the MobileView terminal to the Junction Box. The Connection Cable is available in 5, 10, 15, 20 meter (16.4, 32.8, 49.2, 65.6 foot) lengths.

• MobileView Junction Box Cable (2727-MREY1) connects the Junction Box to the MobileView Connection Cable when the Junction Box is mounted inside a cabinet. The cable is 2 meters (6.56 feet) long.

Inside. . .

Junction Box Dimensions and Connections ...................................................................... 2

Mounting the Junction Box on a DIN Rail ......................................................................... 3

Connecting the MobileView Terminal to the Junction Box ............................................... 5

Junction Box Pinout and Wiring ........................................................................................ 6

Specifications .................................................................................................................... 7

Publication 2727-IN010A-EN-P - May 2004

Page 2: MobileView Junction Box - RockwellAutomation.com › idc › ... · Use the dimensions below for drilling the holes to mount the MobileView Junction Box to a wall. Use the manufacturer’s

2 MobileView Junction Box

Junction Box Dimensions and Connections

K1

X1 X3

1 101 6

SHIELD

140

mm

(5

.52

in)

165 mm (6.50 in)

70 m

m

(2.7

6 in

)

K1 17-pin female connector for connection cable

X1 Terminal block for power and control lines

X3 Terminal block for data lines

SHIELD Cable shield clamp with connection surface for shield of data lines (not used for strain-relief of the cable)

The Junction Box and the MobileView terminal meet the safety class III in accordance with EN 61131-2 and EN 50178. When connecting the MobileView terminal, make sure all voltages connected to the terminal are safety low voltages and isolated from the low voltage supply system by a safety transformer or a similar safety component.

ATTENTION

Publication 2727-IN010A-EN-P - May 2004

Page 3: MobileView Junction Box - RockwellAutomation.com › idc › ... · Use the dimensions below for drilling the holes to mount the MobileView Junction Box to a wall. Use the manufacturer’s

MobileView Junction Box 3

Mounting the Junction Box on a DIN RailMount the Junction Box on a DIN rail inside the enclosure.

Attach DIN Rail Adapter to MobileView Terminal

Attach the DIN Rail Adapter to the back of the Junction Box using the screws provided.

To install the Junction Box on a DIN rail:

1. Mount the DIN rail.

2. Hook the top slot of the adapter over the DIN rail.

3. While pressing the Junction Box against the DIN rail, snap the Junction Box into position.

Publication 2727-IN010A-EN-P - May 2004

Page 4: MobileView Junction Box - RockwellAutomation.com › idc › ... · Use the dimensions below for drilling the holes to mount the MobileView Junction Box to a wall. Use the manufacturer’s

4 MobileView Junction Box

To remove the Junction Box from the DIN rail:

1. Place a screwdriver in the adapter latch at the bottom of the Junction Box.

2. Holding the Junction Box, pry downward on the latch until the Junction Box is released from the DIN rail.

Mounting Junction Box to a WallUse the dimensions below for drilling the holes to mount the MobileView Junction Box to a wall. Use the manufacturer’s recommendation for hole size based on the screw type and mounting surface.

40 mm (1.58 in)

155 mm (6.10 in)

10.2

mm

(0

.40i

n)

64.8

mm

(2

.55

in)

Publication 2727-IN010A-EN-P - May 2004

Page 5: MobileView Junction Box - RockwellAutomation.com › idc › ... · Use the dimensions below for drilling the holes to mount the MobileView Junction Box to a wall. Use the manufacturer’s

MobileView Junction Box 5

Connecting the MobileView Terminal to the Junction Box

7 8 9

4 5 6

1 2 3

. 0 -

ESC

KE TOP

Run

Error

Control CabinetJunction Box

maximum wall thickness 5 mm (0.2 in)

Dust Cover

Junction Box Cable

K1K1

Server

10 Base-T Connection to Ethernet Network

MobileView Connection Cable

Connector Cutout

Power Supply, E-Stop, enabling switch

25 ± 0.1 mm (1.0 ± 0.0039 in)

25 ±

0.1

mm

(1

.0 ±

0.0

039

in)

MobileView Terminal

Cable Clearance

Minimum 130 mm (5.118 in) Minimum 100 mm (3.937 in)Required minimum distance outside and inside the control cabinet

Publication 2727-IN010A-EN-P - May 2004

Page 6: MobileView Junction Box - RockwellAutomation.com › idc › ... · Use the dimensions below for drilling the holes to mount the MobileView Junction Box to a wall. Use the manufacturer’s

6 MobileView Junction Box

Junction Box Pinout and Wiring

24V DCGND_INE-Stop, circuit 1, pos.*E-Stop, circuit 1, neg.*E-Stop, circuit 2, pos.*E-Stop, circuit 2, neg.*Enbl. sw. circ. 1, pos*Enbl. sw. circ. 1, neg*Enbl. sw. circ. 2, pos*Enbl. sw. circ. 2, neg*Not usedNot used

pinkblack

green-brownwhite-green

grey-pinkred-bluebrownyellowgreengreyviolet

bluewhite

orangered

MobileViewConnection Cable

MobileViewJunction Box Cable Junction BoxMobileView

pinkblack

green-brownwhite-green

grey-pinkred-bluebrownyellowgreengreyviolet

bluewhite

orange

red

+24VGNDES1+ES1-ES2+ES2-ED1+ED1-ED2+ED2-

K1S19

K2S4

K1K2 X1K3

K1K2

12345678

12

9

4

6

9

21

3

5

87

101117

* Junction Box connections are for connection to MobileView Guard G750 Terminals only.

131415

123

6

X3

TD+

RD+RD-

SHLD

45 TD-

16

5

1

34

6

812

911

2

7

17

5

10

876

9101112345

123

6

13141516

Refer to the MobileView Guard User Manual (Publication 2727-UM002) for important information on wiring and implementing into machine safety systems.

ATTENTION

Publication 2727-IN010A-EN-P - May 2004

Page 7: MobileView Junction Box - RockwellAutomation.com › idc › ... · Use the dimensions below for drilling the holes to mount the MobileView Junction Box to a wall. Use the manufacturer’s

MobileView Junction Box 7

Specifications

Electrical Specifications

24V dc Power Supply Use a 24V dc Safety Extra Low Voltage power supply. Supply Voltage Range: 18V dc to 32V dc Current Consumption: 450mA at 24V dc, 600mA at 18V dc (with MobileView Terminal attached) Peak Inrush Current: 5.6a maximum

Environment Specifications

Operating Temperature +0°C to +50°C (+32°F to +122°F)

Storage Temperature -20°C to +70°C (-4°F to +158°F)

Relative Humidity (non-condensing) 5% to 95%

Vibration resistance (operation) 5≤ f < 9 Hz 7mm 9 ≤ f ≤ 150 Hz 2g

Shock Resistance (operation) 15g / 11 ms

Housing

Construction Double-walled ABS housing withstands grease, oil, lubricants, alcohol, etc.

Flammability Class UL 94-V0

Dimensions (W x H x D) 160 mm x 140 mm x 70 mm (6.3 in x 5.5 in x 2.76 in)

NEMA Rating IP65

The device meets the safety class III in accordance with EN 61131-2 and EN 50178. The 24V power supply for the equipment must provide appropriate isolation between the safety-extra-low-voltage circuits and dangerous-contact voltage circuits (for example, by safety transformers).

The power supply circuit must be protected by a 3.5A fuse.

The nominal supply voltage of the MobileView terminal without the connection cable is 24V dc (supply voltage range: 18 -32V dc.

When planning the power supply, consider the voltage drop in the connection cable. Specifications of the power supply lines in the cable are:

• Cross section: AWG24 (0.24mm2)

• Material: zinc-coated copper strand

• Line resistance: <90 Ohm/km (<145 Ohm/mile)

ATTENTION

Publication 2727-IN010A-EN-P - May 2004

Page 8: MobileView Junction Box - RockwellAutomation.com › idc › ... · Use the dimensions below for drilling the holes to mount the MobileView Junction Box to a wall. Use the manufacturer’s

Publication 2727-IN010A-EN-P - May 2004 PN 41061-351-01(1)Supersedes Publication XXXX-X.X.X - Month Year Copyright © 2004 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.