Modbus Gateway ME30-24/E4(M)
Thank you for choosing Commercial Air Conditioners, please read this owner’s manual carefully before operation and retain it for future reference.
Commercial Air ConditionersOwner's Manual
User NoticesPlease read this manual carefully before installation and operation and strictly observe the
installation and operation instructions covered in this manual. In addition, careful attention shall be drawn to the following two symbols.
WARNING
It indicates, if operated improperly, it would lead to bodily injury or severe damage.
The installation shall be done by the skilled serviceman; otherwise it would lead to a fire hazard or electric shock.
Be sure the power plug is inserted into the socket only after it is dried and cleaned.
Do not touch the gateway before its power supply is cut off.
Do not touch the gateway with wet hands; otherwise it would lead to electric shock.
installation is in poor condition.
Be sure the power supply is connected in the correct sequence and the power supply is
damaged.
Place the gateway inside an indoor electric cabinet which is inaccessible and locked.
Do not locate the gateway where it would be subject to electromagnetic interference or dust.
CAUTION
It indicates, if operated improperly, the equipment would be damaged.
Be sure proper power supply is provided, otherwise the gateway will fail to work or even be damaged.
Be sure all devices are placed correctly, otherwise communication would go abnormally.
Be sure the communication line is connected to the correct port, otherwise communication would go abnormally.The connected communication line should be protected with the insulating tape against oxidation and short circuit.Normal working conditions: 1) temperature: -20~+70o
location: inside an indoor electric cabinet, not subject to direct sunlight, rain and snow etc.
Contents
1 General ............................................................................................................1
2 Check before Installation ................................................................................. 1
...................................................................................... 2
.................................................................................................. 2
.......................................................................................... 4
............................................................................................ 4
4 Applications ..................................................................................................... 7
............................... 7
.......................................................................................................... 7
.................................................................................
......................................................................................................9
.................. 9
...................................................................................... 10
................................................
... 19
.......... 22
C-1 Debug the cooling system ..................................................................... 22
C-2 Communication debugging of Modbus gateway and air conditioning units ...
...............................................
C-4 Communicaiton debugging of Modbus gateway and remote monitoring system .......... 24
1
1 GeneralModbus gateways for the central air conditioning system are used to bridge the internal
and is enabled to take the real-time monitoring and the long-distance control to the air conditioning
Modbus gateway will stop the air conditioning system immediately).
2 Check before InstallationPlease check for the items listed below prior to installation.
Modbus Gateway 1
Installation and Operation Manual 1
2
CAN Interface,to the air conditioning system
RS485-1 Interface,to Web-based Remote
Monitoring and Control System/BMS
Digital Input
Digital Output
Power Input
POWER INPUT
WARNING
Do not touch the input port of the power supply when the gateway is energized.
CAN Interface: it is connected to the air conditioning system through twisted pairs so as to get through the communication between the Modbus gateway and the air conditioning system.
RS485-1 Interface: It is connected to Web-based Remote Monitoring and Control
RS485-2 Interface: it is reserved .
DI1...DI5Digital inputs: binary (0/1) digital signals, applicable to passive inputs.DI 1
signal “1”, which indicates that the Modbus gateway will stop the whole air conditioning system at
will resume the normal operation.DI2...DI5
it is opened.
K5 K4 K3 K2 K1
Fire signal
DO1...DO5Digital outputs: relay outputs, normally open contacts.
input the binary signal “0”, its two contacts will be opened.
4
Power Supply
CANRX
the air conditioning system).
TXconditioning system).
RX
TX
RX It is reserved.
TX It is reserved.
RX It is reserved.
TX It is reserved.
POWER It lights on when the Modbus gateway is powered normally.
RUN
It is reserved.
CAUTION
The DIP switches shall be set prior to operation of the gateway.
This Modbus gateway includes two kinds of DIP switches, address DIP switch and function DIP switch.
The address DIP switch is intended to set the address of the Modbus gateway, which should
address of the same Modbus bus is not allowed to be repeated, otherwise communication would fail.
CAUTION
The master outdoor unit of air conditioning system or the gateway located at either end of the CAN2 bus
communication would fail.
The eighth position of this function DIP switch is used to set the matched resistance of the CAN2 bus.
When the Modbus gateway is located at either end of the CAN2 bus, it shall be coupled with a matched resistance and the eighth position should be set to “0”.
When the Modbus gateway is located at neither end of the CAN2 bus, no matched resistance is required the eighth position should be set to “1”.
CAN2 Bus
Master outdoor unit of system 1
Master outdoor unit of system 2
Master outdoor unit of system n
Matched resistance
required Matched resistance required not
Matched resistance required not
Matched resistance required
n
The seventh position of this function DIP switch is used to set the matched resistance for the
transmission line.In application of the Modbus gateway, an upper unit as the terminal unit is usually coupled
resistance.When the Modbus gateway is required to be set with a matched resistance, the seventh
position of this DIP switch should be set to "0" and the gateway should be located at the end of the
7
4.3, each indoor unit has an
When the indoor unit number is beyond the range defined by the gateway, it should be
4 ApplicationsThe Modbus gateway is generally applied in the following two systems.
The Modbus gateway is applicable to be used to integrate the air conditioning system, including
Indoor unitIndoor unit
Master outdoor unit
Master outdoor unit
Mater outdoor unit
Slave outdoor unit
Slave outdoor unit Slave outdoor unit Slave outdoor unit
Slave outdoor unit Slave outdoor unit
Master outdoor unit
Slave outdoor unit
Slave outdoor unit
System 1 .
Either Web-based Remote Monitoring and Control System or BMS
CAN2 Network 1
CAN2 Network 2
To the next system
To the next system
To the next system
To next Modbus gateway
L1
L1
L2
L2
L2
L2L1
R1
L3
L3
L3
L3
System 16.
System 1 .
System 2.
CAN2 bus
CAN2 bus
CAN2 bus
Modbus bus
Mod
bus
bus
CAN
2 bu
sC
AN2
bus
Mod
bus
bus
System 1.
L2
L2
Internet
Web-based Remote Monitoring and Control System
(client side)
Web-based Remote Monitoring and Control System
(server side)
BMS
Other device Lighting Fire Vent Lift Electricity
RS232-RS485
Modbus gateway 1
Modbus gateway 2
Modbus gateway 3
Modbus gateway 255
Indoor unitIndoor unit
Indoor unitIndoor unit Indoor unitIndoor unit
Indoor unitIndoor unit Indoor unit
Indoor unitIndoor unit Indoor unit Indoor unit
Master outdoor unit
Converter
9
Modbus busCAN2 bus
master outdoor unit. CAN2 network
indoor units are allowed. If exceeded, the CAN2 network should be divided into two.Air conditioning system: one air conditioning system consists of at most four outdoor units
Allowable number accessible to the gateway: one Modbus gateway can support at most
CAN2 Network 2.
296mm
177mm
56mm
98.5mm
10
The Modbus gateway should be located inside the electric cabinet, hung up with the front side
for reference).
Address
Function
Address
Function
Address
Function
WARNING
Power lines and communication lines of the Modbus gateway should be routed separately; otherwise the Modbus gateway would fail to work.
The Modbus gateway works to get through the communication
Type Remarks
twisted pairs24AWG
An optoelectrical repeater is required when the communication distance is
Type 2) Remarks
copper twisted pairs The allowable
maximum length is
11
CAUTION
Only serial connection is allowed for all communication lines of the Modbus gateway. The star connection is prohibited
Web-based Remote Monitoring and Control System/BMS
Web-based Remote Monitoring and Control System/BMS
Master outdoor unit of system 1
Master outdoor unit of system 2
Master outdoor unit of system n
12
Master outdoor unit of system 1
Master outdoor unit of system 1
Master outdoor unit of system 2
Master outdoor unit of system 2
Master outdoor unit of system n
Master outdoor unit of system n
Step 1:
) .Step 2:
).Step 3: )
Step1: 5.2.2.
) .
Step 2: connect the Modbus gateway's CAN interface G1 and G2 to the interface G1 and G2 at ) .
Step 3:
and ) .
Step 1: 3.3.2 for the address setting of the Modbus gateway. Step 2: 3.3.3-3.3.4 for the matched resistance setting of the Modbus gateway.
tep 3: 3.3.5
14
Notes:
30 Modbus gateways at most is allowed between two repeaters.
The total communication distance of at most 800m is allowed between two repeaters.
of the CAN2 bus should be coupled with a matched resistance. The example listed below shows
12
ON
SA8
Master Outdoor Unit
Matched resistance
D1 D2 G1 G2
D1 D2 G1G2
Address DIPAdd
Address DIPAdd
1 2 4 7 1 2 4 7
0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
1 0 0 0 0 0 0 0 1 1 0 0 0 0 1 0 0
0 1 0 0 0 0 0 0 2 0 1 0 0 0 1 0 0
1 1 0 0 0 0 0 0 1 1 0 0 0 1 0 0
0 0 1 0 0 0 0 0 4 0 0 1 0 0 1 0 0
1 0 1 0 0 0 0 0 1 0 1 0 0 1 0 0
0 1 1 0 0 0 0 0 0 1 1 0 0 1 0 0
1 1 1 0 0 0 0 0 7 1 1 1 0 0 1 0 0
0 0 0 1 0 0 0 0 0 0 0 1 0 1 0 0 40
1 0 0 1 0 0 0 0 9 1 0 0 1 0 1 0 0 41
0 1 0 1 0 0 0 0 10 0 1 0 1 0 1 0 0 42
1 1 0 1 0 0 0 0 11 1 1 0 1 0 1 0 0
0 0 1 1 0 0 0 0 12 0 0 1 1 0 1 0 0 44
1 0 1 1 0 0 0 0 1 0 1 1 0 1 0 0
0 1 1 1 0 0 0 0 14 0 1 1 1 0 1 0 0
1 1 1 1 0 0 0 0 1 1 1 1 0 1 0 0 47
0 0 0 0 1 0 0 0 0 0 0 0 1 1 0 0
1 0 0 0 1 0 0 0 17 1 0 0 0 1 1 0 0 49
0 1 0 0 1 0 0 0 0 1 0 0 1 1 0 0
1 1 0 0 1 0 0 0 19 1 1 0 0 1 1 0 0
0 0 1 0 1 0 0 0 20 0 0 1 0 1 1 0 0
1 0 1 0 1 0 0 0 21 1 0 1 0 1 1 0 0
0 1 1 0 1 0 0 0 22 0 1 1 0 1 1 0 0
1 1 1 0 1 0 0 0 1 1 1 0 1 1 0 0
0 0 0 1 1 0 0 0 24 0 0 0 1 1 1 0 0
1 0 0 1 1 0 0 0 1 0 0 1 1 1 0 0
0 1 0 1 1 0 0 0 0 1 0 1 1 1 0 0
1 1 0 1 1 0 0 0 27 1 1 0 1 1 1 0 0
0 0 1 1 1 0 0 0 0 0 1 1 1 1 0 0
1 0 1 1 1 0 0 0 29 1 0 1 1 1 1 0 0
0 1 1 1 1 0 0 0 0 1 1 1 1 1 0 0
1 1 1 1 1 0 0 0 1 1 1 1 1 1 0 0
Address DIPAdd
Address DIPAdd
1 2 4 7 1 2 4 7
0 0 0 0 0 0 1 0 0 0 0 0 0 1 1 0
1 0 0 0 0 0 1 0 1 0 0 0 0 1 1 0 97
0 1 0 0 0 0 1 0 0 1 0 0 0 1 1 0
1 1 0 0 0 0 1 0 1 1 0 0 0 1 1 0 99
0 0 1 0 0 0 1 0 0 0 1 0 0 1 1 0 100
1 0 1 0 0 0 1 0 1 0 1 0 0 1 1 0 101
0 1 1 0 0 0 1 0 70 0 1 1 0 0 1 1 0 102
1 1 1 0 0 0 1 0 71 1 1 1 0 0 1 1 0
0 0 0 1 0 0 1 0 72 0 0 0 1 0 1 1 0 104
1 0 0 1 0 0 1 0 1 0 0 1 0 1 1 0
0 1 0 1 0 0 1 0 74 0 1 0 1 0 1 1 0
1 1 0 1 0 0 1 0 1 1 0 1 0 1 1 0 107
0 0 1 1 0 0 1 0 0 0 1 1 0 1 1 0
1 0 1 1 0 0 1 0 77 1 0 1 1 0 1 1 0 109
0 1 1 1 0 0 1 0 0 1 1 1 0 1 1 0 110
1 1 1 1 0 0 1 0 79 1 1 1 1 0 1 1 0 111
0 0 0 0 1 0 1 0 0 0 0 0 1 1 1 0 112
1 0 0 0 1 0 1 0 1 0 0 0 1 1 1 0
0 1 0 0 1 0 1 0 0 1 0 0 1 1 1 0 114
1 1 0 0 1 0 1 0 1 1 0 0 1 1 1 0
0 0 1 0 1 0 1 0 0 0 1 0 1 1 1 0
1 0 1 0 1 0 1 0 1 0 1 0 1 1 1 0 117
0 1 1 0 1 0 1 0 0 1 1 0 1 1 1 0
1 1 1 0 1 0 1 0 1 1 1 0 1 1 1 0 119
0 0 0 1 1 0 1 0 0 0 0 1 1 1 1 0 120
1 0 0 1 1 0 1 0 1 0 0 1 1 1 1 0 121
0 1 0 1 1 0 1 0 90 0 1 0 1 1 1 1 0 122
1 1 0 1 1 0 1 0 91 1 1 0 1 1 1 1 0
0 0 1 1 1 0 1 0 92 0 0 1 1 1 1 1 0 124
1 0 1 1 1 0 1 0 1 0 1 1 1 1 1 0
0 1 1 1 1 0 1 0 94 0 1 1 1 1 1 1 0
1 1 1 1 1 0 1 0 1 1 1 1 1 1 1 0 127
17
Address DIPAdd
Address DIPAdd
1 2 4 7 1 2 4 7
0 0 0 0 0 0 0 1 0 0 0 0 0 1 0 1
1 0 0 0 0 0 0 1 129 1 0 0 0 0 1 0 1
0 1 0 0 0 0 0 1 0 1 0 0 0 1 0 1
1 1 0 0 0 0 0 1 1 1 0 0 0 1 0 1
0 0 1 0 0 0 0 1 0 0 1 0 0 1 0 1
1 0 1 0 0 0 0 1 1 0 1 0 0 1 0 1
0 1 1 0 0 0 0 1 0 1 1 0 0 1 0 1
1 1 1 0 0 0 0 1 1 1 1 0 0 1 0 1
0 0 0 1 0 0 0 1 0 0 0 1 0 1 0 1
1 0 0 1 0 0 0 1 1 0 0 1 0 1 0 1
0 1 0 1 0 0 0 1 0 1 0 1 0 1 0 1 170
1 1 0 1 0 0 0 1 1 1 0 1 0 1 0 1 171
0 0 1 1 0 0 0 1 140 0 0 1 1 0 1 0 1 172
1 0 1 1 0 0 0 1 141 1 0 1 1 0 1 0 1
0 1 1 1 0 0 0 1 142 0 1 1 1 0 1 0 1 174
1 1 1 1 0 0 0 1 1 1 1 1 0 1 0 1
0 0 0 0 1 0 0 1 144 0 0 0 0 1 1 0 1
1 0 0 0 1 0 0 1 1 0 0 0 1 1 0 1 177
0 1 0 0 1 0 0 1 0 1 0 0 1 1 0 1
1 1 0 0 1 0 0 1 147 1 1 0 0 1 1 0 1 179
0 0 1 0 1 0 0 1 0 0 1 0 1 1 0 1
1 0 1 0 1 0 0 1 149 1 0 1 0 1 1 0 1
0 1 1 0 1 0 0 1 0 1 1 0 1 1 0 1
1 1 1 0 1 0 0 1 1 1 1 0 1 1 0 1
0 0 0 1 1 0 0 1 0 0 0 1 1 1 0 1
1 0 0 1 1 0 0 1 1 0 0 1 1 1 0 1
0 1 0 1 1 0 0 1 0 1 0 1 1 1 0 1
1 1 0 1 1 0 0 1 1 1 0 1 1 1 0 1
0 0 1 1 1 0 0 1 0 0 1 1 1 1 0 1
1 0 1 1 1 0 0 1 1 0 1 1 1 1 0 1
0 1 1 1 1 0 0 1 0 1 1 1 1 1 0 1 190
1 1 1 1 1 0 0 1 1 1 1 1 1 1 0 1 191
Address DIPAdd
Address DIPAdd
1 2 4 7 1 2 4 7
0 0 0 0 0 0 1 1 192 0 0 0 0 0 1 1 1 224
1 0 0 0 0 0 1 1 1 0 0 0 0 1 1 1
0 1 0 0 0 0 1 1 194 0 1 0 0 0 1 1 1
1 1 0 0 0 0 1 1 1 1 0 0 0 1 1 1 227
0 0 1 0 0 0 1 1 0 0 1 0 0 1 1 1
1 0 1 0 0 0 1 1 197 1 0 1 0 0 1 1 1 229
0 1 1 0 0 0 1 1 0 1 1 0 0 1 1 1
1 1 1 0 0 0 1 1 199 1 1 1 0 0 1 1 1
0 0 0 1 0 0 1 1 200 0 0 0 1 0 1 1 1
1 0 0 1 0 0 1 1 201 1 0 0 1 0 1 1 1
0 1 0 1 0 0 1 1 202 0 1 0 1 0 1 1 1
1 1 0 1 0 0 1 1 1 1 0 1 0 1 1 1
0 0 1 1 0 0 1 1 204 0 0 1 1 0 1 1 1
1 0 1 1 0 0 1 1 1 0 1 1 0 1 1 1
0 1 1 1 0 0 1 1 0 1 1 1 0 1 1 1
1 1 1 1 0 0 1 1 207 1 1 1 1 0 1 1 1
0 0 0 0 1 0 1 1 0 0 0 0 1 1 1 1 240
1 0 0 0 1 0 1 1 209 1 0 0 0 1 1 1 1 241
0 1 0 0 1 0 1 1 210 0 1 0 0 1 1 1 1 242
1 1 0 0 1 0 1 1 211 1 1 0 0 1 1 1 1
0 0 1 0 1 0 1 1 212 0 0 1 0 1 1 1 1 244
1 0 1 0 1 0 1 1 1 0 1 0 1 1 1 1
0 1 1 0 1 0 1 1 214 0 1 1 0 1 1 1 1
1 1 1 0 1 0 1 1 1 1 1 0 1 1 1 1 247
0 0 0 1 1 0 1 1 0 0 0 1 1 1 1 1
1 0 0 1 1 0 1 1 217 1 0 0 1 1 1 1 1 249
0 1 0 1 1 0 1 1 0 1 0 1 1 1 1 1
1 1 0 1 1 0 1 1 219 1 1 0 1 1 1 1 1
0 0 1 1 1 0 1 1 220 0 0 1 1 1 1 1 1
1 0 1 1 1 0 1 1 221 1 0 1 1 1 1 1 1
0 1 1 1 1 0 1 1 222 0 1 1 1 1 1 1 1
1 1 1 1 1 0 1 1 1 1 1 1 1 1 1 1
19
cooling systems
among different cooling systems. In such case, reset the project no. of each system and then follow the methods described below:
When there is central control among different cooling systems, if the project numbers of any
transfer in modes or operate functionally. The entire unit can’t be started up until error is eliminated. The Debugger software displays as below:
20
1)
operation. Display is as show below:
21
2)
controllers or remote controllers for the operation details. This method is not available when the IDU is under project debugging status.
Auto deviation setting of project no. in ODU’s main board:Auto deviation of IDU project numbers can be realized through the main board of outdoor unit.
will be in the standby status for function selection, as shown below:
Display way Current progress Display way Current status Display way
A7 blink 00 blink 00 blink
blink 00 blink 00 blink
A2 blink 00 blink 00 blink
blink 00 blink 00 blink
n0 blink 01 blink 00 blink
n1 blink 00 blink 00 blink
n2 blink 00 blink 00 blink
blink 00 blink 00 blink
n4 blink 00 blink 00 blink
blink 00 blink 00 blink
Display way Current progress Display way Current status Display way
00 Blink OC Blink
Display way Display way Current status Display way
00 OC
system will function as normal.
address is “00000”.)Remark: This handling method may change the project numbers of other normal units and it is
22
our
After the communication system is properly installed and connected, please follow the steps below to debug the communication system.
C-1 Debug the cooling systemBefore debugging the remote monitoring system, make sure the relevant settings of the air
Step 1: The setting of master unit in a single system and the central control address setting in multiple systems
service manual for the operation details).If multiple cooling systems are connected, make sure the central control address code of each
Step 2: Deviation setting of IDU project numbers
system will be in the standby status for function selection and master unit will display as below.Default display is “A7”. Display of the master unit is:
Display way Current progress Display way Current status Display way
A7 blink 00 blink 00 blink
is as below:
Display way Current progress Display way Current status Display way
lit up 00 blink 00 blink
deviation status of project numbers. Display is as below:
Display way Current progress Display way Current status Display way
lit up 00 lit up 00 lit up
At that time, all project numbers of indoor units will be automatically deviated. After about 1min,
unit whose central control address is 0.)
for it is faster and easier. But this handling method may change the project numbers of other normal
C-2 Communication debugging of Modbus gateway and air conditioning unitsStep 1: CAN2 matched resistance setting
CAN2 Bus
Master outdoor unit of system 1
Master outdoor unit of system 2
Master outdoor unit of system n
Matched resistance
required Matched resistance required not
Matched resistance required not
Matched resistance required
n
As shown here, the master outdoor unit at the front end and back end of the CAN2 bus and the Modbus gateway need to be set with matched resistance.
the instruction manual to see how to add matched resistance to the Modbus gateway.The way to add matched resistance to system’s master outdoor units:
12
ON
SA8
Master Outdoor Unit
Matched resistance
D1 D2 G1 G2
D1 D2 G1G2
Step 2: Disconnect and then connect power for the air conditioning equipment and Modbus gateway.
Step 3: Check the status of communication indicators Check the CAN_RX indicator of Modbus gateway. If it blinks, then communication is ok.
TX is blinking or lit up. If the light is not lit up, please check the connection of communication cords and the setting of DIP switch.
Step 1:Please refer to section “3.3.2 Address DIP Switch” in the instruction manual to set the
address of Modbus gateway. Make sure the address codes of gateways on the same Modbus are
Step 2:
24
According to the range of IDU project number related to gateway, set the project number of indoor unit that’s at the beginning of gateway to be 1 or 129. Please refer to section 3.3.5 in the instruction manual for the operation method.
C-4 Communicaiton debugging of Modbus gateway and remote monitoring system
After the software of remote monitoring system is successfully installed, please follow the steps below.
Step 1:
Step 2:
“open”.
b.
service will be energized.
Step 3:
Step 4:
27
After the detection, the detected equipment will be shown below the Net tree. Communication debugging is completed.
_______________________________________________________________________________________
WWW.ALPICAIR.COM