Model UT513OPERATING MANUAL
Title Page
Model UT513: OPERATING MANUAL
1
Table of Contents
IntroductionUnpacking the MeterSafety InformationInternational Electrical SymbolsBattery Saver (Sleep Mode)Battery IndicationThe Meter StructureDisplayKey FunctionsMeasurement Operation A. Measuring Voltages B. Measuring Insulation Resistance a) Continuous Measurement b) Timed Measurement c) Polarization Index (PI) Measurement d) Compare FunctionThe Use of Power Adaptor
556888912141717192020212223
2
242525262727272828292930
Model UT513: OPERATING MANUAL
Title Page
USB InterfaceMaintenance A. General Service B. Replacing the BatterySpecificationsSafety and CompliancesPhysical SpecificationsGeneral SpecificationsFeature SummaryDetailed Accuracy Specifications A. Voltage Measurement B. Insulation Resistance Measurement
3
Model UT513: OPERATING MANUAL
Table Title Page
1. Unpacking Inspection2. International Electrical Symbols3. Battery Indication4. Meter Front Description5. Meter Side Description6. Display Description7. Key Description
58810111314
List of Tables
4
Model UT513: OPERATING MANUAL
Figure Title Page
1. The Meter Front Structure2. The Meter Side Structure3. Display4. Voltages Measurement5. Insulation Resistance Measurement6. The Use of Power Adaptor7. USB Interface Connection8. Battery Replacement
911121719232426
List of Figures
5
Model UT513: OPERATING MANUAL
IntroductionUni-Trend Model UT513 insulation resistance tester(hereafter, ìthe Meterî) is a handheld instrumentdesigned primarily to make resistance/ insulationresistance measurement.
Unpacking the MeterThe Meter includes the following items:
Table 1. Unpacking Inspection
Item12
3
4
56789
DescriptionEnglish Operating ManualOne plug test lead to one alligatorclip (Black colour)One plug test lead to one alligatorclip (Green colour)Two plugs test lead to onealligator clip (Red colour)1.5V Battery (LR14)Tool BoxUSB Interface CableSoftwarePower adaptor (input voltage230V, 50/60Hz, 75mA, outputDC14V, 1.0A)(optionally, availableat extra cost)
Qty1 piece1 piece
1 piece
1 piece
8 pieces1 piece1 piece1 piece1 piece
In the event you find any missing or damage, pleasecontact your dealer immediately.
6
Model UT513: OPERATING MANUAL
Safety InformationThis Meter complies with the standards IEC61010 safetymeasurement requirement: in pollution degree 2,overvoltage category (CAT. III 600V) and doubleinsulation.
CAT II: Local level, appliance, PORTABLE EQUIPMENTetc., with smaller transient voltage overvoltages thanCAT. III
Use the Meter only as specified in this operating manual,otherwise the protection provided by the Meter may beimpaired.
Danger identifies conditions and actions that posehazard(s) to the user.Warning identifies avoiding electric shock.Caution identifies conditions and actions that maydamage the Meter and carrying out accuratemeasurement.
Danger
Use of instrument in a manual not specifed by themanufactuer may impair safety features/protectionprovided by the equipment. Read the followingsafety information carefully before using orservicing the instrument.
Do not apply more than 600V.Do not use the Meter around explosive gas,vapor or dust.Do not use the Meter in a wet environment.When using the test leads, keep your figuresaway from the lead contacts. Keep yourfigures behind the finger guards on the leads.Do not use the Meter with any parts or coverremoved.
International electrical symbols used on the Meter andin this Operating Manual are explained on page 8.
Operating Caution identifies conditions that userneeds to take extra care during operating the Meter
7
Model UT513: OPERATING MANUAL
Warning
Do not use the Meter if it is damaged or metalpart is exposed. Look for cracks or missingplastic.Be careful when working above 33V rms, 46.7Vac rms or 70V DC. Such voltages pose a shockhazard.Discharge all loading of circuit under test aftermeasuring high voltage.Do not change battery when the Meter is inwet environment.Place test leads in proper input terminals.Make sure all the test leads are firmlyconnected to the Meterís input terminals.Make sure the Meter is turned off whenopening the battery compartment.
Caution
When performing resistance tests, remove allpower from the circuit to be measured anddischarge all the power.When servicing the Meter, use only the samemodel number or identical electricalspecifications of test leads and power adaptor.Do not use the Meter if the battery indicator( ) shows a battery empty condition. Takethe battery out from the Meter if it is not usedfor a long time.Do not use or store the Meter in anenvironment of high temperature, humidity,explosive, inflammable and strong magneticfield. The performance of the Meter maydeteriorate after dampened.Soft cloth and mild detergent should be usedto clean the surface of the Meter whenservicing. No abrasive and solvent should beused to prevent the surface of the Meter fromcorrosion, damage and accident.Dry the Meter before storing if it is wet.
When carrying out insulation measurement,do not contact the circuit under test.
Risk of electric shockEquipment protected by double orreinforced insulation.DC MeasurementAC MeasurementGroundingSee ManualEmpty of Built-In BatteryConforms to Standards of European Union
8
Model UT513: OPERATING MANUAL
International Electrical SymbolsInternational symbols on the Meter and in this manualare explained in Table 2.
Table 2. International Electrical Symbols
Battery Saver (Sleep Mode)The Meter enters the Sleep Mode and blanks the displayif there is no button press for 15 minutes. This is doneto conserve battery power. The Meter comes out ofSleep Mode when ON/OFF button is pressed and holdfor 1 second.
Battery IndicationThere is a battery indicator shows on the display upperleft hand corner. Below Table 3 is the explanation:
Battery Voltage
10V or less. It means the battery isempty, donít use the Meter as it cannotguarantee accuracy.10V~10.5V. It means the battery isnearly empty, replacing battery isnecessary. At this status, the Meter canstill do 500V and 1000V outputmeasurement, accuracy will not beaffected.10.6V~11.5V11.6V or more
Table 3. Battery Indication
BatteryIndicator
9
Model UT513: OPERATING MANUAL
The Meter Structure
Below Figure 1 and Table 4 shows the Meter frontstructure and description
Figure 1. The Meter Front Structure
Green Black Red
10
Model UT513: OPERATING MANUAL
12345678910111213141516
Table 4. Meter Front Description
LCD Scroll Button
Emergency StopData Clear the Display Backlight Button
Down ButtonOn/Off ButtonCompare ButtonInsulation Resistance ButtonDC Voltages measurement ButtonTimer Button.AC Voltages measurement ButtonTest ButtonUSB ButtonData Store Button.Data Recall Button
Scroll Button
1718
19
20
21
22
Up ButtonLINE: High Voltage output input terminal(two plugs red test lead to one alligator clip)High voltage line shielding input terminal(two plugs red test lead to one alligator clip)GUARD: Grounding protection input terminal(one plug black test lead to one alligator clip)EARTH: High resistance measurement inputterminal (one plug green test lead to onealligator clip)Testing leads:Two plugs red test lead to one alligator clip.One plug black test lead to one alligator clip.One plug green test lead to one alligatorclip.
11
Model UT513: OPERATING MANUAL
Below Figure 2 and Table 5 shows the Meter sidestructure and description
Figure 2. The Meter Side Structure
Table 5. Meter Side Description
1 Safety Shutter2 Power adaptor Input Terminal3 USB Port
12
Model UT513: OPERATING MANUAL
Display
Table 6 and Figure 3 describe the display.
Figure 3. Display
13
Model UT513: OPERATING MANUAL
Table 6. Display Description
Number1234567891011
MeaningIndicator for DC voltageIndicator for data store fullIndicator for clearingIndicator for AC voltageIndicator for timerStep symbolIndicates selected pass/fail compare valueIndicates for negative readingTimer 1 symbolTimer 2 symbolData store is on
Number12131415161718192021
MeaningData recall is onIndicator for polarization indexUnit symbolsThe continuity buzzer is onCompare feature passAnalogue bar graphRisk of electric shockCompare feature failIndicator for power adaptorBattery life indicator
14
Model UT513: OPERATING MANUAL
Table 7. Key Description
Turn on or off the Meter. Press andhold the button for 1 second to turn theMeter on. Press again to turn off theMeter.The Meter default range is 500Vinsulation resistance continuousmeasurement when turning on.Emergency stop button. Press thisbutton when the Meter is hang andcannot turn off the power.Press to turn on or off the displaybacklightPress and hold to clear the stored dataPress to store the current measurementvalue. The maximum number of storedreading is 18. When the stored readingsmemory is full, the Meter shows FULLand stop storing. Press and holdCLEAR / to clear the stored valuein order to store the next measurement
value.LOAD
Key Functions
ON/OFF
E-STOP
CLEAR /
SAVE
Press once to recall the first storedvalue.Press again to exit Load feature.Load feature can only be used whenthere is no high voltage output.When the insulation resistancemeasurement has no testing voltageoutput, press to select one voltagerange up.Under load mode: press to recall theprevious stored value.When the insulation resistancemeasurement has no testing voltageoutput, press to select one voltagerange down.Under load mode: press to recall thenext stored value.
15
Model UT513: OPERATING MANUAL
Table 7. Key Description
When set the timer duration for themeasurement of insulation resistanceor polarization index, press todecrement the time. The maximumlength of time is 15 minutes and 30seconds, the Meter will automaticallycarry out measurement.When compare feature measuringinsulation resistance, press todecrement a resistance comparingvalue.After polarization indexmeasurement, press to displaypolarization index, TIME 2 insulationresistance value and TIME 1insulation resistance value insequence.When set the timer duration for themeasurement of insulation resistanceor polarization index, press to
increment the time. The maximumlength of time is 30 minutes and 30seconds, the Meter will automaticallycarry out measurement.When use the compare featuremeasuring insulation resistance,press to increment a resistancecomparing value.After polarization indexmeasurement, press to displaypolarization index, TIME 2 insulationresistance value and TIME 1insulation resistance value insequence.Press once to start the datatransferring to the computer via USB,USB symbol shows on the display.Press again to stop the datatransferring to the computer via USB,USB symbol disappears.
USB
16
Model UT513: OPERATING MANUAL
Table 7. Key Description
Set a pass / fail limit for insulation tests.The default value is 10MPres to step through continuousmeasurement, timed measurement andpolarization index measurement insequence.Press to stop or start an insulationresistance testPress to initiate insulation resistancemeasurementPress to initiate DC voltagemeasurementPres to initiate AC voltagemeasurement
COMP
TIME
TEST
IR
DCV
ACV
17
Model UT513: OPERATING MANUAL
Measurement Operation A. Measuring Voltages
Figure 4. Voltages Measurement
Below section explains how to make measurements.
Press and hold ON/OFF to turn on the Meter, pressagain to turn off the Meter. The Meter default range is500V insulation resistance continuous measurementwhen turning on.
Red
Green
18
Model UT513: OPERATING MANUAL
To avoid harms to you or damages to the Meter,please do not attempt to measure voltageshigher than 600V or 600V rms, althoughreadings may be obtained.Special care should be taken when measuringhigh voltage.
Operating Catuion
To measure voltages, set up the Meter as Figure 4 anddo the following:
Press DCV or ACV button to select DC voltage orAC voltage measurementInsert the red and green test lead into the testedcircuit.When measuring DC voltage, if the red test lead isnegative voltage, ì-ì symbol will show on the display.
1.
2.
3.
When voltage measurement has been completed,disconnect the connection between the testingleads and the circuit under test and remove testingleads away from the input terminals of the Meter.
Note
19
Model UT513: OPERATING MANUAL
Black
Red
B. Measuring Insulation Resistance
Figure 5. Insulation Resistance Measurement
Operating Caution
When performing insulation resistance tests,remove all power from the circuit to bemeasured and discharge all the power.Operating the Meter must be very careful as itoutputs dangerous voltage duringmeasurement. Must make sure the tested objectis firmed clipped, hands are away from theclips, then press TEST button to put highvoltage.Do not short circuit the testing leads duringhigh voltages output or test insulationresistance after high voltages output. This kindof incorrect operating may cause sparking andfire, which damages the Meter and harms toyou.Do not measure over 10 seconds when:500V measure resistance lower than 2M1000V measure resistance lower than 5M2500V measure resistance lower than 10M5000V measure resistance lower than 20M
Green
Groud
20
Model UT513: OPERATING MANUAL
To measure insulation resistance, set up the Meter asFigure 5 and do the following:
Press IR button to select insulation resistancemeasurement.When there is no testing voltage output, press and button to select voltages of 500V, 1000V,2500V or 5000V.When performing insulation resistance tests, removeall power from the circuit to be measured anddischarged all the power.Insert the red test lead into the LINE input terminaland the black test lead into GUARD input terminal.Connect the red and black alligator clip to the circuitto be measured, negative voltage output from LINEterminal.Choose below insulation resistance measurementmode.
1.
2.
3.
4.
5.
6.
Press TIME button to select continuousmeasurement mode, there is no timer icon on theLCD.Press and hold TEST button for 1 second tocarry out continuous measurement. Outputinsulation resistance testing voltage, TEST buttonlight up, blinks on every 0.5 seconds.Press TEST button to close the insulation resistancemeasurement voltage when measurement iscompleted. TEST button lights off, disappears.The LCD shows the current insulation resistancemeasurement value.
Press TIME button to select timed measurementmode, the LCD displays TIME 1 and symbols.Press and buttons to set the time (00:10~15:00).Within 1 minute, the time increment or decrementby every 5 seconds. Afterward, the time incrementor decrement by every 30 seconds.
21
Model UT513: OPERATING MANUAL
Then press and hold TEST button for 2 second tocarry out timed measurement. TIME 1 and aredisplayed and blinked on the LCD on every 0.5seconds.When the set time is reached, the insulationresistance measurement voltage will be closedand the measurement will be automatically stopped.The LCD displays the insulation resistance reading.
Press TIME button to select timed measurementmode, the LCD displays TIME 1 and symbols.Press and buttons to set the time (00:10~15:00).Within 1 minute, the time increment or decrementby every 5 seconds. Afterward, the time incrementor decrement by every 30 seconds.Press TIME button again. TIME 2, PI and symbolsappear on the LCD.Press and buttons to set the time (00:15~15:30).Within 1 minute, the time increment or decrementby every 10 seconds. Afterward, the time increment
or decrement by every 30 seconds.Then press and hold TEST button for 2 seconds tocarry out timed measurement.TIME 1 and are displayed and blinked on theLCD on every 0.5 seconds before TIME 1 set timeis reached.TIME 2 and are displayed and blinked on theLCD on every 0.5 seconds before TIME 2 set timeis reached.When the two set time are reached, the insulationresistance measurement voltage will be closed andthe measurement will be automatically stopped.The LCD displays the polarization index reading.Press , to set through the polarization index,TIME 2 insulation resistance reading and TIME 2insulation resistance reading.
Information:PI = 3 minutes ~10 minutes reading / 30 seconds ~1minute reading
PIStandard
4 or moreThe best
4~2Good
2.0~1.0Warning
1.0 or lessBad
22
Model UT513: OPERATING MANUAL
Press COMP button to select compare feature.COMP symbol displays on the LCD..Press and buttons to set the compare valueBelow is the list in sequence of the compare value:10M , 20M , 30M , 40M , 50M , 60M , 70M ,80M , 90M ,100M , 200M , 300M , 400M ,500M , 600M , 700M , 800M , 900M ,1G ,2G , 3G , 4G , 5G , 6G , 7G , 8G , 9G ,10G ,20G , 330G , 40G , 50G , 60G , 70G ,80G , 90G , 100G ,200G , 300G , 400G ,500G , 600G , 700G , 800G , 900GPress and hold TEST button for 2 seconds to carryout the measurement.The NG symbol will display if the insulationresistance value is smaller than resistance value.Otherwise GOOD symbol will be displayed.
The Use of Power Adaptor
23
Model UT513: OPERATING MANUAL
The use of power adaptor, see figure 6
Open the side safey shutter, then you will see thereis a power adaptor input terminal.Make sure the Meter is power off and insert theUT513 power adaptor to the input terminal.It is highly recommeded to take out all the batterieswhen you are using the power adaptor.Make sure the Meter is power off when youdisconnect the UT513 power adaptor from the Meter.It is highly recommeded to use Uni-Trend suppliedUT513 power adaptor to avoid dangerous.
1.
2.
3.
4.
5.
Figure 6. The Use of Power Adaptor
24
Model UT513: OPERATING MANUAL
USB InterfaceConnecting the USB interface, see figure 7
Figure 7. USB Interface Connection
Install the included software, the installation guidecan be seen from the CD.Open the side safety shutter, then you will see thereis a USB port.Insert the included USB cable to the Meterís USBport and the other end to the computer.
1.
2.
3.
25
Model UT513: OPERATING MANUAL
MaintenanceThis section provides basic maintenance informationincluding battery replacement instruction.
Warning
Do not attempt to repair or service your Meter unlessyou are qualified to do so and have the relevantcalibration, performance test, and serviceinformation.
A. General Service
Periodically wipe the case with a damp cloth andmild detergent. Do not use abrasives or solvents.To clean the terminals with cotton bar with detergent,as dirt or moisture in the terminals can affectreadings.Turn the Meter to OFF when it is not in use.Take out the battery when it is not using for a longtime.Do not use or store the Meter in a place of humidity,high temperature, explosive, inflammable and strongmagnetic field.
If the Meter is wet, dry it before use.
26
Model UT513: OPERATING MANUAL
B. Replacing the Battery
Warning
To avoid electric shock, remove all the test leadsfrom the Meter when replacing the batteries.
Operating Caution
Donít mix to use old and new batteries.Be careful the polarity is correct when installingbatteries.Do not use the Meter if the battery indicator( ) shows a battery empty condition.Do you carry out measuring during the batterycompartment is open.
Figure 8. Battery Replacement
Follow Figure 8 and proceed as follows to replace thebattery:
Turn the Meter to OFF and remove all connectionsfrom the terminals.Remove the screw from the battery compartment,and separate the battery compartment from the casebottom.Replace with 8pcs of new 1.5V (LR14) batteries.Rejoin the case bottom and battery compartment,and reinstall the screw.
27
Model UT513: OPERATING MANUAL
Specifications
Safety and Compliances
CertificationCompliances IEC 61010 CAT.III 600V overvoltage and double insulation standard
Physical SpecificationsDisplay (LCD)
Operating TemperatureStorage TemperatureRelative Humidity
Battery Type
Dimensions (HxW xL)Weight
Digital: 9999 countsAnalog bar graph.-10 ~40 (14 ~104 )-20 ~60 (-4 ~152 )
85% @ -10 ~40 below; 90% @ -20 ~60 :
8pcs of 1.5V (LR14) batteries or power adaptor (input voltage 230V, 50/60Hz,75mA, input DC14V, 1.0A).Power adaptor is optionally at extra cost.202 x 155 x 94 mmApprox. 2kg (including battery)
28
Model UT513: OPERATING MANUAL
General SpecificationsRangeOverloadingBattery IndicatorIcon DisplayCurrent Consumption
AutoDisplay OL on insulation resistance rangeDisplayEquips with function and battery indicator icons.Maximum: around 1.0AAverage: around 20mA
Feature SummaryDisplay BacklightComputer connectionData Logging and RecallAutorangeWarningVoltageCOMP Measurement
PI Measurement
TIME
Bright backlight for clear readings in poorly lighted areas.Via USB interface.18The Meter automatically selects best range
and red light will on.Auto release voltageUse the Compare function to set a pass/fail compare level for the insulationmeasurements.Polarization Index is the ratio of insulation resistance. You can pre-set twopoint of times and automatically carry out the measurement.To carry out measurement by setting a specified time within 15 minutes.
Measurement RangeResolutionAccuracy
DC Voltage30 ~ 600V
29
Model UT513: OPERATING MANUAL
Detailed Accuracy SpecificationsAccuracy: ([% of reading] + [number of least significant digits), guarantee for 1 year.Operating temperature: 18 ~28Relative humidity: 45~75%RH
A. Voltage Measurement
AC Voltage30V~600V (50/60Hz)
1V(2%+5) Among them 30~100V(50/60Hz) (2%+8)
30
Model UT513: OPERATING MANUAL
Output VoltageDisplay RangeOpen Circuit VoltageTest Current
Accuracy
B. Insulation Resistance Measurement
500V0.5M ~20GDC 500V 0%~+ 20%1mA~1.2mA @ 500k
1000V2M ~40GDC1000V 0%~+ 20%1mA~1.2mA @ 1M
2500V5M ~100GDC 2500V 0%~+ 20%1mA~1.2mA @ 2.5M
5000V10M ~1000GDC5000V 0%~+ 20%1mA~1.2mA @ 5M
10.0M ~29.9M : (Forreference only)30.0M ~99.9M : (3%+5)100M ~9.99G : (5%+5)10.0G ~99.9G : (10%+5)Above 100G : [ (20%+5) Humidity:Below 50%]
0.50M ~99.9M : (3%+5)
100M ~9.99G : (5%+5)
10.0G ~20.0G : (10%+5)
Short Circuit
At any output voltage, when the tested resistance is les than 10M , the testing time cannot exceed 10seconds continuously.
Operating Caution
2.0M ~99.9M : (3%+5)
100M ~9.99G : (5%+5)
10.0G ~40.0G : (10%+5)
5.0M ~99.9M : (3%+5)
100M ~9.99G : (5%+5)
10.0G ~100G : (10%+5)
Less than 2.0mA
31
Model UT513: OPERATING MANUAL
This operating manual is subject to change without notice.
*END*