MPSS Modular Power System Simulator Technical Teaching Equipment Worlddidac Quality Charter Certificate Worlddidac Member ISO 9001:2000 Certificate of Approval European Union Certificate Certificates ISO 14001: 2004 and ECO-Management and Audit Scheme (environmental management) Worlddidac Member The “MPSS” is a modular Power System Simulator specially designed for Technicians at Technical and Vocational level. Manual operation or in combination with SCADA system. The simulator will include the main parts of a Power System as: ! Generation. ! Transformation. ! Transport. ! Distribution. ! Consumption. It will include important and key elements that play a very important roll in a Power System control and protection, as: - Automatic voltage regulator. - Automatic frequency control. - All the main protection relays involved. - Automatic and Manual synchronization. The simulator includes the following modules: - EGMG/P. Generation Group. - BUS03. Busbar model 3 (Coupling). - AVR/P. Automatic Voltage Regulator. - BUS04. Busbar model 4 (Consumption). - VVCA/MP. AC Motors Speed Controller. - ALI01. Power Supply. - TRANS/3A. Step-up Transformer. - IND05. Synchronims Module. - TRANS/3B. Step-down Transformer. - INX20/P. Generator Protection Module. - AE1. Transmission Lines Simulation Unit. - ERP-PGC. Generators Protection and Control Device Unit. - AE11. Energy Consumption Module. - ERP-PD. Distance Protection Relay Unit. - BUS01. Busbar model 1 (Generation). - ERP-PDF. Differential Protection Relay Unit. - BUS02. Busbar model 2 (Transport). - ERP-MF. Fault Injection Module. - BUS05. Busbar model 5 (Transport). GENERAL DESCRIPTION Page 1

Upload: lamtram

Post on 05-Mar-2019

219 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Modular Power System Simulator MPSS - Alat peraga pendidikan · The “MPSS” is a modular Power System Simulator specially designed for Technicians at Technical and Vocational level

MPSSModular Power System Simulator

Technical Teaching Equipment

Worlddidac Quality Charter Certificate

WorlddidacMember

ISO 9001:2000Certificate of Approval

European Union Certificate Certificates ISO 14001: 2004 andECO-Management and Audit Scheme

(environmental management) Worlddidac Member

The “MPSS” is a modular Power System Simulator specially designed for Technicians at Technical and Vocational level.

Manual operation or in combination with SCADA system.

The simulator will include the main parts of a Power System as:

� Generation.

� Transformation.

� Transport.

� Distribution.

� Consumption.

It will include important and key elements that play a very important roll in a Power System control and protection, as:

- Automatic voltage regulator. - Automatic frequency control.

- All the main protection relays involved. - Automatic and Manual synchronization.

The simulator includes the following modules:

- EGMG/P. Generation Group. - BUS03. Busbar model 3 (Coupling).

- AVR/P. Automatic Voltage Regulator. - BUS04. Busbar model 4 (Consumption).

- VVCA/MP. AC Motors Speed Controller. - ALI01. Power Supply.

- TRANS/3A. Step-up Transformer. - IND05. Synchronims Module.

- TRANS/3B. Step-down Transformer. - INX20/P. Generator Protection Module.

- AE1. Transmission Lines Simulation Unit. - ERP-PGC. Generators Protection and Control Device Unit.

- AE11. Energy Consumption Module. - ERP-PD. Distance Protection Relay Unit.

- BUS01. Busbar model 1 (Generation). - ERP-PDF. Differential Protection Relay Unit.

- BUS02. Busbar model 2 (Transport). - ERP-MF. Fault Injection Module.

- BUS05. Busbar model 5 (Transport).

GENERAL DESCRIPTION

Page 1

Page 2: Modular Power System Simulator MPSS - Alat peraga pendidikan · The “MPSS” is a modular Power System Simulator specially designed for Technicians at Technical and Vocational level

Consumption

AE11.Energy Consumption Module

ERP-PGC. Generators Protection and Control Device Unit ERP-PD. Distance Protection Relay UnitERP-PDF. Differential Protection Relay Unit

ERP-MF. Fault Injection Module

D ”“SCA A

AVR/P. Automatic Voltage RegulatorVVCA/MP. AC Motors Speed Controller

AE1.Transmission Lines Simulation Unit

TRANS/3B.Step-down Transformer

EGMG/P. Generation Group

Generation Transformation Transport/Lines

Busbars Control and Protections

Faults

MODULES IN DETAIL

TRANS/3A.Step-up Transformer

www.edibon.com

-ALI01. Power Supply. -BUS02. Busbar model 2 (Transport).-INX20/P. Generator Protection Module. -BUS05. Busbar model 5 (Transport).-IND05. Synchronims Module. -BUS03. Busbar model 3 (Coupling).-BUS01. Busbar model 1 (Generation). -BUS04. Busbar model 4 (Consumption).

Page 2

Page 3: Modular Power System Simulator MPSS - Alat peraga pendidikan · The “MPSS” is a modular Power System Simulator specially designed for Technicians at Technical and Vocational level

www.edibon.comPage 3

SPECIFICATIONS

ALI01. Power Supply

This module has the followings elements:One three-phase power supply output connector.One three-phase power supply output with red, yellow and green connectors.Two single-phase power supply output. One single-phase standard type power supply output.Ground terminal.One security key.One emergency stop switch.Module state indicators.

A removable key 6 with two positions (ON and OFF) acts as main switch.

www.edibon.com

This group has the followings elements:1.One three-phase AC squirrel cage induction motor acting as generation prime mover.2.One three-phase Synchronous generator with DC field excitation.

The induction motor is controlled from the VVCA/MP. AC Motors Speed Controller.

EGMG/P. Generation Group

SPECIFICATIONS

INX20/P. Generator Protection Module

SPECIFICATIONS

Page 4: Modular Power System Simulator MPSS - Alat peraga pendidikan · The “MPSS” is a modular Power System Simulator specially designed for Technicians at Technical and Vocational level

Page 4

VVCA/MP. AC Motors Speed Controller

The VVCA/MP is an AC motor speed regulator.The numerous inputs and outputs allow you to use the VVCA/MP for power supply standard asynchronous ac motor for simulation of prime mover of generation system.Each part of the VVCA/MP is correctly identified in order to facilitate the operation and fast identification.Elements of the AVR/P:

Ground protection connector.Three-Phase power output supply connectors.Control enable/disable switch.Remote/Local mode switch.Local control set-point slider.Input/Output CPR01 signal connector.Input/Output AVR signal connector.Power supply Switch.

The capacity range of VVCA/MP is for 3 ph 400 V supply from 0.4 kW to 7 kW. The overload capacity of VVCA/MP is 150% for 1 min and 200% for 3s (in High Duty mode). The inverters with capacities of 5.5 kW and above can be used in dual rating; this means that the same inverter can be used for next higher capacity (in Low Duty mode). For example a 5.5 kW inverter can be used for a 7.5 kW motor; in this case the overload is 120% for 1 min. The braking transistor is included as standard. The braking resistor is included as standard up to 7.5 kW units. The main features of VVCA/MP are:

Safety enables input (compliant to EN954-1 category 3).Built-in EMC filter for all capacities (compliant to EN 61800-3, category C3).Sensorless vector control mode (100% torque at 0 Hz).Advanced PID functions (dancer control).Brake control function.Logic gates for logic combination of input and output functions and delay timer (10steps). Positioning function (when encoder option is used).3 slots for 3 different options at the same time (encoder, fieldbus, I/O expansion).Removable control terminals (cage clamp type).

SPECIFICATIONS

www.edibon.com

SPECIFICATIONS

AVR/P. Automatic Voltage Regulator

The AVR/P is an Automatic Voltage Regulator that works in conjunction with the ERP-PGC. Generators Protection and Control Device Unit.The numerous inputs and outputs allow you to use the AVR/P for voltage, reactive power and power factor regulation of generation system.Each part of the AVR/P is correctly identified in order to facilitate the operation and fast identification.Elements of the AVR/P:

Ground protection connector.Generator output voltage measurement connectors.Generator Field excitation output supply connectors.Voltage Control enable/disable switch.Remote/Local mode switch.Input/Output signal connector.Local control set-point slider.Serial Port connector( Software HMI is optional product).Power supply Switch.

The AVR/P is an automatic voltage regulator of the latest design for synchronous generators and synchronous motors. The unit contains the most advanced microprocessor technology together with IGBT semiconductor technology (Insulated Gate Bipolar Transistor).This advanced-design automatic voltage regulator is used for the excitation of indirectly excited synchronous machines. This unit is only suitable for this one area of application.The regulator can also be switched over to function as a reactive power, power factor and field current regulator.

Page 5: Modular Power System Simulator MPSS - Alat peraga pendidikan · The “MPSS” is a modular Power System Simulator specially designed for Technicians at Technical and Vocational level

IND05. Synchronims Module

This module has the followings elements:Phase Synchronization Lamps.Phase RST sequences test connectors.

SPECIFICATIONS

Page 5 www.edibon.com

Three-phase power transformer with group connection YyN0, 400/400V, 2kVA, 50-60Hz.This unit simulates the STEP-UP transformer located in the transmission substation.

TRANS/3A. Step-up Transformer

SPECIFICATIONS

Three-phase power transformer with group connection YyN0, 400/230V, 2kVA, 50-60Hz.This unit simulates the STEP-DOWN transformer located in the distribution substation.

TRANS/3B. Step-down Transformer

SPECIFICATIONS

Page 6: Modular Power System Simulator MPSS - Alat peraga pendidikan · The “MPSS” is a modular Power System Simulator specially designed for Technicians at Technical and Vocational level

SPECIFICATIONS

BUS01. Busbar model 1(Generation)

The finality of these modules is to represent the generation, transmission, distribution and subtransmission substations busbars and it included the main commutation elements as power circuit breaker, isolating switches, double busbar. With the aid of these modules is possible to coupling or decoupling all necessary elements of the power system simulator.

Basically the busbars modules have similar elements, as:

- Input/Outputs double BusBar power connectors.

- Single-phase power supply input.

- 89L-1 and 89L-2 isolators open/close selectors.

- 52L circuit breaker open/close selector.

- 89L-3 isolator open/close selector.

- Manual/Remote operation enable switch.

- Input/Output signals control connector.

BUS03. Busbar model 3(Coupling)

BUS02. Busbar model 2(Transport)

www.edibon.com

BUS04. Busbar model 4(Consumption)

Page 6

BUS05. Busbar model 5(Transport)

www.edibon.com

Busbars

Page 7: Modular Power System Simulator MPSS - Alat peraga pendidikan · The “MPSS” is a modular Power System Simulator specially designed for Technicians at Technical and Vocational level

SPECIFICATIONS

This unit represents basic concepts of the Electric Energy high-voltage three-phase transmission lines operation. It simulates a value modifying concentrated parameter line that allows different configurations and consists on three conductorline (R, S, T) and a Neutral or return line (N).

Each of the phases is represented, following the concentrated parameters theoretical model, through a resistance series association and inductance, along with a parallel association between each one of them in a capacitance effect.

A way to reduce the earth short circuit current is to have impedance in the neutral-to-ground connections. This impedance has no repercussion in the normal functioning of the network but they introduce a repercussion in the increase of 3x Z (impedance on the zero sequence component), o

which reduces the short circuit current.

The return line is simulated through small value impedance that has a resistive-indicative characteristic. To simplify the effect, being a despicable inductance, it will be simulated with a pure 10 resistance.

The phases have two terminals at the input and two at the output, and they are connected at the interior. Through one of them the module will be supplied. Through the last one the natural circuit will continue to the load module, the bar module, the transformer, etc. The two terminals left en every phase is left for assembly of protection relay or other parallel configurations.

The supply of this unit will be done through line terminals (R, S, and T) and the neutral (N) through a 400V three-phase supply and it will be controlled by an interrupter-circuit breaker of 4 poles placed between the supply and the lines module.

In the phases we can distinguish different resistance and inductance values, being able to simulate different length transport lines.

The resistive part is formed by two resistance values of 15 and 33 , with the possibility of making parallel-series connections between them, obtaining two additions resistive values of 10.31 and 48 .

The inductive part consists on a multistage coil of despicable resistance. In which it is possible to choose one of the following values:

33 mH, 78 mH, 140 mH, 193 mH, 236 mH

The capacitive part will be divided into capacitance between conductors and capacitance between line and ground.

The capacitance between conductors is simulated with a pair of capacitors at the beginning and at the end of the line with different values: 0.5 F and 1 F for each conductor.

The capacitance between conductor and ground is 1 F and 2 F, also at the beginning and at the end of the line.

With all this values it is possible to simulate a great number of line configurations, beginning with different line distances with different types of conductor, through the unbalanced lines with different conductors groups (Simplex, Duplex, Triplex and Cuadruplex). At the same time it is possible to simulate transient state with different short-circuits injection using a fault injection module.

The unit is protected with a grounding connection that comes from the metallic caging and that is accessible through a terminal in the front of the module.

AE1. Transmission Lines Simulation Unit

Page 7 www.edibon.com

Page 8: Modular Power System Simulator MPSS - Alat peraga pendidikan · The “MPSS” is a modular Power System Simulator specially designed for Technicians at Technical and Vocational level

SPECIFICATIONS

With this module is possible to simulate any proper consumption in the power system or we can test any element of the power system separately under different load conditions.

It has differentiated part on resistive, inductive and capacitive zones and it allows all types of combinations between them, so we can simulate pure resistive, inductive and capacitive load as well as different series-parallel combination of them.

AE11. Energy Consumption Module

Page 8 www.edibon.com

Page 9: Modular Power System Simulator MPSS - Alat peraga pendidikan · The “MPSS” is a modular Power System Simulator specially designed for Technicians at Technical and Vocational level

The ERP-PGC is a control unit for engine-generator simulator system.

The numerous inputs and outputs, along with a modular software structure, allow you to use the ERP-PGC for a wide range of applications with only a single part number. This includes stand-by, AMF (automatic mains failure), peak shaving, import-export or distributed generation, among others.

Also the ERP-PGC is compatible for island, island parallel, mains parallel and multiple unit mains parallel operations.

Each part of the ERP-PGC is correctly identified in order to facilitate the operation and fast identification.

All the adjustments are executed with the management software from a PC.

Elements of the ERP-PGC:

Power input/output connectors.

Multifunction control and protection device.

Generator group control inputs and outputs connector.

Generator rotor to ground protection Relay.

Isolated operation connector(52GT state and 52G trip command).

Functions:

Prime mover control.

Engine, mains and generator protection.

Engine data measurement :

Oil pressure and temperature, coolant temperature, battery voltage, speed, service hours, etc.

Generator and mains data measurement:

Voltage, current, power, kVar, kW, kWh, etc.

Load/Var sharing for up to 32 participants.

Load-dependent start/stop.

Automatic, Manual, and Stop operating modes.

Application modes:

1.No CB (Circuit Breaker) operation.

2.Open GCB (Generator Circuit Breaker).

3.Open/close GCB.

4.Open/close GCB/MCB (Generator CB/Main Circuit Breaker).

Logics Manager for processing measured values, discrete inputs, and internal states.

Engine starter sequencing.

Alarm display with circuit breaker trip and engine shutdown.

AMF (automatic mains failure) standby genset control, with automatic engine start on mains failure detection and open transition breaker control.

Critical mode operation.

Synchronizing (phase matching and slip frequency) and mains parallel operation.

External frequency, voltage, power, and power factor set point control via analogue input or interface.

FIFO (First Input First Output) event history with 300 entries.

ECU data visualization via J1939.

CAN bus communication to engine controllers, plant management systems, expansion boards, and Toolkit configuration and visualization software.

RS-485 Modbus communication with plant management systems.

RS-232 Modbus communication with plant management systems.

SPECIFICATIONS

ERP-PGC. Generators Protection and Control Device Unit

Page 9 www.edibon.com

Page 10: Modular Power System Simulator MPSS - Alat peraga pendidikan · The “MPSS” is a modular Power System Simulator specially designed for Technicians at Technical and Vocational level

SPECIFICATIONS

The ERP-PD is a transmission line protection device.The numerous inputs and outputs, along with a modular software structure, allow you to use the ERP-PD for study and analyze the performance of different transmission line protection system.Each part of the ERP-PD is correctly identified in order to facilitate the operation and fast identification.All the adjustments are executed with the management software from a PC.Elements of the ERP-PD:

Power input/output connectors.Protection device.Outputs connector for trip command.

Functions:Protection:Optimize line protection with a system of sensitive, secure, and dependable three-pole trip relay elements.Monitoring: Simplify fault and system disturbance analyses with event reports and Sequential Events Recorder.Fault Locator: Isolate line problems, and restore service faster.Automation.Remote communications capabilities and elimination of external control elements.

ERP-PD. Distance Protection Relay Unit

Page 10 www.edibon.com

SPECIFICATIONS

The ERP-PDF is a differential protection device.The numerous inputs and outputs, along with a modular software structure, allow you to use the ERP-PDF for study and analyze the performance of different differential protection system.Each part of the ERP-PDF is correctly identified in order to facilitate the operation and fast identification.All the adjustments are executed with the management software from a PC.Elements of the ERP-PDF:

Power input/output connectors.Protection device.Outputs connector for trip command.

Functions:It provides current differential protection plus two complete groups of overcurrent elements in one compact package. The relay measures high- and low-side currents, differential operate and restraint quantities, as well as second and fifth harmonics of the applied currents. The unit provides two optoisolated inputs, four programmable output contacts, and one alarm output contact.This relay can protect two-winding power transformers, reactors, generators, large motors, and other two-terminal power apparatus. The relay settings permit you to use wye or delta connected high- and low-side current transformers. The relay compensates for various equipment and CT connections to derive appropriate differential operating quantities.The ERP-PDF provides three differential elements with dual slope characteristics. The second slope provides security against CT saturation for heavy through faults.

ERP-PDF. Differential Protection Relay Unit

Page 11: Modular Power System Simulator MPSS - Alat peraga pendidikan · The “MPSS” is a modular Power System Simulator specially designed for Technicians at Technical and Vocational level

SPECIFICATIONS

The fault injection module have the possibility to inject different kind of short-circuits, in any point of the power system simulator including line module, directly or through a pure resistive element.

Employing this element we can analyze line performance during transient state as well as analyze the line protection elements functionality.

The short-circuit injection possibility are:

Three-pole short-circuit.

Two-pole short-circuit.

Two-pole-ground short-circuit.

Single-pole-ground short-circuit.

ERP-MF. Fault Injection Module

Page 11 www.edibon.com

Page 12: Modular Power System Simulator MPSS - Alat peraga pendidikan · The “MPSS” is a modular Power System Simulator specially designed for Technicians at Technical and Vocational level

Some Practical Possibilities:

14.- Study of generator armature reaction when feeding isolated capacitive loads through transmission line with automatic frequency control and without voltage control.

15.- Study of generator armature reaction when feeding isolated mixed RCL loads through transmission line with automatic frequency control and without voltage control.

16.- Study of generator armature reaction when feeding isolated unbalanced loads through transmission line with automatic frequency control and without voltage control.

17.- Study of generation unit connected to the network through different transmission lines, operating at constant active power and variable field current.

18.- Study of generation unit connected to the network through different transmission lines, operating at variable active power and constant field current.

19.- Calculation of the line parameters.

20.- No laad transmission line operation and voltage regulation.

21.- Pure resistive load transmission line operation and voltage regulation.

22.- Pure inductive load transmission line operation and voltageregulation.

23.- Pure capacitive load transmission line operation and voltage regulation.

24.- Mixed R-L load transmission line operation and voltage regulation.

25.- Mixed R-C load transmission line operation and voltage regulation.

26.- Mixed L-C load transmission line operation and voltage regulation.

27.- Mixed R-L-C load transmission line operation and voltage regulation.

28.- Unbalanced load transmission line operation and voltage regulation.

29.- Verification of generator rotor to ground protection functionality.

30.- Verification of differential protection functionality.13.- Study of generator armature reaction when feeding isolated

31.- Verification of line distance protection functionality.inductive loads through transmission line with automatic frequency control and without voltage control.

1.- Power System Simulator Components recognition and operation introduction.

2.- Study of generation unit feeding isolated resistive loads through a medium transmission line with automatic frequency control and voltage adjustment at remote distribution substation busbar.

3.- Study of generation unit feeding isolated inductive loads through a medium transmission line with automatic frequency control and voltage adjustment at remote distribution substation busbar.

4.- Study of generation unit feeding isolated capacitive loads through a medium transmission line with automatic frequency control and voltage adjustment at remote distribution substation busbar.

5.- Study of generation unit feeding isolated mixed loads through a medium transmission line with automatic frequency control and voltage adjustment at remote distribution substation busbar.

6.- Study of generation unit feeding isolated unbalanced resistive loads through a transmission line with automatic frequency control and voltage adjustment at remote distribution substation busbar.

7.- Study of unit feeding isolated resistive loads through transmission line with automatic frequency control and voltage adjustment at transmission substation busbars.

8.- Study of unit feeding isolated inductive loads through transmission line with automatic frequency control and voltage adjustment at transmission substation busbars.

9.- Study of unit feeding isolated capacitive loads through transmission line with automatic frequency control and voltage adjustment at transmission substation busbars.

10.-Study of unit feeding isolated mixed RLC loads through transmission line with automatic frequency control and voltage adjustment at transmission substation busbars.

11.-Study of generation unit feeding isolated unbalanced resistive loads through a transmission line with automatic frequency control and voltage adjustment at transmission substation busbar.

12.- Study of generator armature reaction when feeding isolated resistive loads through transmission line with automatic frequency control and without voltage control.

EXERCISES AND PRACTICAL POSSIBILITIES

*