mta manual

Upload: andres-grisales

Post on 25-Feb-2018

248 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/25/2019 MTA Manual

    1/98

    Users Manual

    MTA for Windows

    Baker Instrument Company

    4812 McMurry Ave. Suite 100

    Fort Collins, CO 80525(970) 282-1200

    (970) 282-1010 (FAX)

    800-752-8272 (USA Only)

    [email protected]

    Baker Instrument Company assumes no liability for damages consequent to the

    use of this product. Any and all parameters preset in the software for test and

    analysis are suggested values to initiate quick and productive use of this product.

    No responsibility or liability is assumed for these preset parameters asrepresenting authorized standards of test or analysis.

    Baker is a registered trademark of Baker Instrument Company.

    Copyright 2005, Baker Instrument Company, 4812 McMurry Avenue, Fort

    Collins, CO 80525.

    1

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    2/98

    Software License Agreement

    Baker Instrument Company (hereafter known as Baker) provides an executable

    and supporting programs on the express condition that you agree to this softwarelicense. By using any of the enclosed diskette(s), you agree to the following

    conditions. If you do not agree with these terms & conditions, please return the

    products to your Baker representative within three days after purchase and yourpurchase price will be refunded in full.

    1) This software and the diskettes on which it is contained (the Licensed

    Software) are licensed to you, the end user, for your own internal use. You donot obtain title to the licensed software or any copyrights or property rights in

    the licensed software. You may not sublicense, rent, lease, convey, modify,

    translate, convert to any programming language de-compile or disassemble the

    licensed software for any purpose whatsoever.

    2) The driver software is licensed solely on a as-is basis. All warranties and

    representation of any kind with regard to the licensed software are hereby

    disclaimed, including the implied warranties of merchantability and fitness for a

    particular purpose. Under no circumstances will the manufacturer or developerof the licensed software be liable for any consequential, incidental, special or

    exemplary damages even if apprised of the likelihood of such damagesoccurring. Some states do not allow the limitation or exclusion of liability for

    incidental or consequential damages, so the above limitation or exclusion may

    not apply to you.

    3. Site licenses are available to use the program on multiple computers at a

    single plant facility. Please contact Baker should you require furtherinformation about the site license opportunity.

    2

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    3/98

    Warranty Information

    All products manufactured by Baker Instrument Company are warranted against

    defective materials and workmanship for a period of one year from the date ofdelivery to the original purchaser. Any product that is found to be defective

    with the warranty period will, at the option of Baker Instrument Company, be

    repaired or replaced. This warranty does not apply to products damaged byimproper use. The Purchaser shall assume all responsibilities and expense for

    removal, reinstallation, freight or On-Site service charges in connection with

    the foregoing remedies.

    Companys liability to purchaser relating to the product whether in contract or intort arising out of warranties, representations, instructions, installations, or

    defects from any cause, shall be limited exclusively to correcting the product

    and under the conditions as aforesaid.

    Components of MTA for Windows are covered by Baker Instrument Company.

    Any component not manufactured by Baker Instrument Company are covered

    by the respective manufactured warranties and NO additional warranty from

    Baker Instrument Company is offered or implied. Enclosed materials from themanufacturer and source of these items describe the only warranty pertaining to

    these items.

    IN ITS COMMITMENT TO SERVICE EXCELLENCE, BAKER

    INSTRUMENT COMPANY WILL HELP FACILITATE OBTAINING

    NECESSARY WARRANTY SERVICE, FROM THE RESPECTIVE

    MANUFACTURER, NEEDED FOR PRODUCTS NOT

    MANUFACTURED BY BUT RESOLD THROUGH BAKER

    INSTRUMENT COMPANY. IT SHOULD BE NOTED THAT THIS MAY

    ADD ADDITIONAL TIME TO THE TIME REQUIRED FOR SERVICE

    WHEN DEALING DIRECT WITH THE MANUFACTURER, AND THAT

    BAKER INSTRUMENT COMPANY ASSUMES NO RESPONSIBILITY

    TO CONTROL THE LEVEL OF OR TIME NEEDED FOR OTHERMANUFACTURERS TO PROVIDE THEIR WARRANTY OR OTHER

    SERVICES.

    3

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    4/98

    4

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    5/98

    Users Manual.............................................................................................. 1

    CHAPTER 1: MTA INSTALLATION........................................................... 7

    MTA for Windows Compatible Operating Systems......................................9Minimum Computer Requirements...............................................................9Configuring the PCs Parallel Port .............................................................9

    Computer Bios Settings............................................................................ 9Installing MTA for Windows 98/ME/2000/XP ...........................................10

    CHAPTER 2: GETTING STARTED ............................................................11

    THE BIG IDEA .................................................................................................13STARTING MTA SOFTWARE ...........................................................................13

    Finding Motors ..........................................................................................14The Explore Tab.........................................................................................15The Motor ID Tab ......................................................................................15The Route Tab ............................................................................................16

    Adding a Route ......................................................................................16Renaming a Route.................................................................................. 17Deleting a Route.....................................................................................17Editing Motor IDs on an existing Route ...............................................17

    Viewing Data.............................................................................................. 18The Data Tab..........................................................................................18Data Tab, Nameplate View:................................................................... 19Adding a New Motor .............................................................................20Updating an Existing Motors Nameplate Information..........................20Deleting an Existing Motor from the Database......................................21Data Tab, Application View: .................................................................21Data Tab, Results Summary...................................................................22Data Tab, Surge Views: .........................................................................23Data Tab, PI View..................................................................................24

    The Tests Tab .............................................................................................24Test Configuration .................................................................................26

    Temperature/Resistance Configuration/ Data Acquisition Dialog.........26Megohm/PI/HiPot Configuration/Data Acquisition Dialog.......................29

    Surge Configuration/Data Acquisition Dialog.......................................30The Trending Tab.......................................................................................33

    Resistance .................................................................................................. 33Insulation Resistance/Megohm..............................................................34HiPot ......................................................................................................35PI............................................................................................................35Relative Humidity..................................................................................35Special Software Trending Features.......................................................35

    5

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    6/98

    CHAPTER 3: EXAMPLE TEST.................................................................... 37

    CREATING A MOTOR ID.................................................................................. 39CREATING A TEST ID......................................................................................41

    Configure Temperature/Resistance............................................................43Configure Megohm/PI/HiPot Tests............................................................45Configure Surge Test .................................................................................46

    Generic Test IDs versus Specific Test IDs............................................... 47RUNNING A REAL-TIME TEST SEQUENCE .......................................................47

    Saving Data................................................................................................54Reviewing Test Results/Data......................................................................54

    CHAPTER 4: DATABASE MANAGEMENT ............................................. 65

    DATABASE MANAGEMENT .............................................................................67Consequences of Not Organizing Data......................................................67

    Motor ID Field ...........................................................................................68Motor Location Fields ...............................................................................68Multiple Databases .................................................................................... 69Opening a Database................................................................................... 69Creating a New Database ..........................................................................70

    DATA TRANSFER.............................................................................................70Transferring Motor and Test Result Data...............................................71Transferring Test IDs................................................................................ 74

    Archiving a Database.................................................................................75Restoring a Database................................................................................. 77

    CONVERTING AN OLDER DATABASE...............................................................79Converting the Data...................................................................................80

    APPENDIX I: FIRMWARE..........................................................................83

    CHECKING FIRMWARE VERSION .....................................................................85Firmware Version 3.+................................................................................85

    APPENDIX II: INSTALLING FIRMWARE............................................... 87

    INSTALLATION

    INSTRUCTIONS FOR

    MTA FIRMWARE

    .....................................89INDEX...............................................................................................................95

    6

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    7/98

    CHAPTER 1: MTA INSTALLATION

    Inside..

    Installation

    MTA for Windows Compatible Operating Systems

    Configuring the PCs Parallel Port

    Computer Bios Settings

    Installing MTA for Windows 98/ME/2000/XP

    7

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    8/98

    8

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    9/98

    Installation

    If installing version 2.2 or greater over an installation of MTA for Windows

    versions 2.1.4 or older, uninstall the older version first, before installing the

    newer version. Uninstall by clicking on the Start Settings Control Panel,then by clicking on the Add/Remove Programsicon. Select Digital MTA to

    uninstall. This will delete only the program files and icons associated with theMTA software and will not delete any data. However, it is always important to

    make backups of your data as unforeseen events do occur.

    MTA for Windows Compatible Operating Systems

    Windows 98/ME

    Windows 2000/XP (Recommended)

    Must have Internet 5.0 or higher

    Must be able to install the MDAC 2.5sp3 or higher (Installs the Jet

    Engine 4.0, for the Access Database)

    Minimum Computer Requirements

    Pentium II

    400 MHz

    64 MB memory

    20 MB Hard Drive Space

    ECP-Parallel Port

    Configuring the PCs Parallel Port

    Note: Most new computers have ECP set as default. Re-configure port only if

    communication with tester does not work or if the port is not set to ECP.

    Computer Bios SettingsThe parallel port on the PC used with MTA for Windows must be set up inorder for MTA to acquire data. The parallel port must be configured as an

    ECP parallel port in the computers BIOS or on the parallel port card.Consult the PCs manuals for instructions on how to configure parallel

    ports.

    Rebooting the computer is necessary for BIOS setting modification. Using

    the computer specific keystroke from your PCs manual, check the BIOS

    settings prior to Windows operating system restarting. This specifickeystroke enables the BIOS program, which is used to setup the parallel

    9

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    10/98

    port. This keystroke varies from one computer to another. Many computers

    use Del, Esc, or the F10 key. Most computers in use today use the

    BIOS written by Award or Phoenix Technologies. Modification instructions

    for BIOS settings can be obtained from their associated web sites. They

    can be reached at www.award.comand www.phoenix.com.

    Installing MTA for Windows 98/ME/2000/XP

    To install MTA for Windows, insert the install CD into the computers CD-

    ROM drive, the install process should start automatically. If computer does not

    have the auto-run feature enabled for the CD drive, run setup.exe from the CD.

    The install program self guides through the installation process. The filesinstalled include the MTA.exe, dynamic link libraries (.dll) from Microsoft that

    allow MTA for Windows to run, Microsoft Jet Database Engine dlls, and a

    folder for saving test data. The Dlls are Microsofts and only install if non-existent or an older version is found.

    Note Windows 2000/XP installs: Baker has written a kernel driver based on

    the Microsofts parallel.sys driver. The MTA for Windows installation program

    automatically installs the Baker driver in the c:\winnt\system32\drivers folder.The driver is called BICParallel.sys. It is loaded upon booting the computer. In

    order for this driver to install the profile used must have administrative rights.

    10

    Doc #: 71-009-001 Rev 1

    http://www.award.com/http://www.phoenix.com/http://www.phoenix.com/http://www.award.com/
  • 7/25/2019 MTA Manual

    11/98

    CHAPTER 2: GETTING STARTED

    Inside

    The Big Idea

    Starting MTA Software

    Finding Motors

    The Explore Tab

    The Motor ID Tab

    The Route Tab

    Adding a Route

    Renaming a Route

    Deleting a Route

    Editing Motor IDs on an Existing Route

    The Data Tab

    Nameplate View

    Application View

    Results Grid View

    Surge View

    PI View

    The Tests Tab

    Temperature/Resistance Test Screen

    Megohm/PI/HIPOT Test Screen

    Surge Test Screen

    The Trending Tab

    Resistance

    Insulation Resistance/Megohm HiPot

    PI

    Relative Humidity

    11

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    12/98

    12

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    13/98

    The Big Idea

    The MTA software works by performing pre-configured tests on pre-configuredmotors. The pre-configured tests are called Test IDs. A pre-configured motor is

    called a Motor ID. The Motor ID is stored in the MTAs database along with the

    Test ID to be used when testing that motor. Additional information about themotor such as the manufacturer, serial number, horsepower rating, frame size,

    speed, operating voltage and current is also stored in the Motor ID. New motors

    can be entered into the database or existing motors can be updated.

    To view test results for a given motor or to perform a test on a motor, it mustfirst be selected from all the other motors in the MTAs database. The left of the

    display is used to find and select a motor. The right of the screen is used to view

    test result data and run tests.

    The Test ID consists of all test parameters to be used when performing tests on a

    motor. Details such as test voltages, pass or fail criteria, and test times are

    contained in a Test ID. These Test IDs are named and defined by the user.

    There are already several Test IDs created by Baker Instrument Company forseveral different machines. Usually, the most important parts of a Test ID are

    the test voltages. Therefore, a Test ID is named after the operating voltage of the

    motor. Several motors can share a single Test ID. For example, all 480 volt

    motors can use the same Test ID.

    Starting MTA Software

    To start MTA, locate and

    double click the MTA

    icon on the computers

    desktop. The MTAsoftware will start and

    present a window givingthe opportunity to create anew database, select the

    most recently used

    databases, or browse formore databases.

    Fig 2.1: Selected Database

    13

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    14/98

    After selecting a database, the following window appears:

    The main MTA window is split into two panes. The left pane contains threedifferent tabs that facilitate browsing through the motors in the database: the

    Explore Tab, the Motor ID Tab, and the Route Tab. The right pane contains

    three more tabs, which allow the viewing of test results and acquisition of test

    data.

    Finding Motors

    The left side of the opening screen is used to navigate through the motors within

    the opened database. Three methods areprovided: an Explore Tab where the motor

    location is shown in a three level Tree View,

    a Motor ID Tab where a alphabetical list of

    Motor IDs can be used to locate a motor by

    typing the first few characters of the Motor ID, and a Route Tab whereredefined lists of motors can be used, such as in predictive maintenance.p

    Fig 2.2: Selected Database

    Fig 2-3: Finding Motors

    14

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    15/98

    Fig 2-4: Explore Tab

    The Explore Tab

    rnd

    ,

    plus sign or contract a location by clicking on the

    the

    to

    n the letters

    le

    ted

    the Displaybutton to select the desired

    otor ID.Fig 2-5: Motor ID Tab

    The Explore tab offers a tree structure to assist

    selection of a particular Motor ID. The two uppelevels of the tree correspond to the location a

    building that the physical motor is housed.

    Location and Building are the default tree labels

    but are changeable labels for the motor location

    fields. The lowest level is the Motor ID. Forexample, in the view below the selected Motor ID

    CnVyr23BLine2-22R, is at the Willow Ridge

    plant, Unit 22R. By clicking on a Motor ID, thatmotors data is recalled and becomes the current

    motor. Expand a motor location by clicking on the

    minus sign.

    The Motor ID TabThe Motor ID list box contains all motors from

    database in alphabetical order. In the edit box,

    located above the list, will be the currently selectedMotor ID. Location of a Motor ID can be done in

    two ways within this tab. The first method allows

    the operator to begin typing the needed Motor IDin the edit box. The list will automatically scroll

    the nearest Motor ID that begins with the typed

    characters. For example by typing i

    Cn, in the example to the left the

    Cnvyr23Bline2-22R Motor ID would behighlighted. If this is the needed Motor ID doub

    click on that Motor ID (or click the Display

    button) and it would become the currently selecmotor. The second method is to simply scroll

    down in the list until the Motor ID is found.

    Double click on the Motor ID or highlight the MotorID and click

    M

    15

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    16/98

    The Route Tab

    The Route tab allows construction of individual lists of Motor IDs for routing

    purposes. As seen in the example to the left the Spring Outage list is selected.This list has four motors associated with it. The electrical technician does not

    have to search the whole database for the four motors to be tested during the

    spring outage.

    This tab also allows editing and printing of the routes. Click on the Edit Routebutton to evoke the editor. The editor allows Add, Rename, and Delete of

    routes. It also allows add, remove and change the order of the Motor IDs on alist. See example dialog box Fig 2-7.

    Adding a Route

    Spring Outage is the currentlyselected Route.

    Fig 2.6 Route Tab

    1. To add a new route, click onthe Addbutton at the top of

    the dialog. The Route IDs

    edit box will be blanked out

    allowing a new Route ID to

    be entered. After enteringthe new ID, start adding

    Motor IDs from the

    16

    Doc #: 71-009-001 Rev 1

    Fig 2.7: Route

  • 7/25/2019 MTA Manual

    17/98

    Available Motorslist box on the right to the Route Motorslist box on the

    left.

    2. To add a motor, select the Motor ID on the right and click on the

  • 7/25/2019 MTA Manual

    18/98

    IDs will be remove from the Route Motor list and added back to the

    Available Motorslist.

    4. To change the order of the Motor IDs in the Route Motorslist, select the

    motor or group of motors to move and click on the Move Up or MoveDownbuttons at the bottom of the list.

    5. When finished editing a route click on the Save Listbutton to save changes.

    Fig 2.8: Data Tab

    Viewing Data

    The Data Tab

    The right pane has threetabs at the top of the

    screen. They are Data,

    Testsand Trendingtabs.

    The Data tab contains twowindows one above the

    other. The top window

    shows the date and timefor the test result data and

    whether or not the motor

    passed the specific test.

    By clicking on a

    date/time, view test resultdata for that specific date

    within the Application,

    Surge, or PI, tabs in thelower window. The lower

    windows view changes

    depending on which tab at

    the bottom of the panel isselected: a Nameplateview, an

    Applicationview, a Results

    SummaryView, a Surgeview, a PIview, and a Step Voltage Test view. If a

    Step Voltage Test was performed on an AWA, the test data can be reviewed on

    the MTA software.

    Fig 2-8: Data Tab

    18

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    19/98

    Data Tab, Nameplate View:

    The Nameplateview contains the nameplate data on each motor in the database.

    The first field is the Motor ID, which is used by the MTA program to uniquely

    identify the motor. Required fields are the Motor ID, and the two motor locationfields. In the example to the right, the location fields are Plantand Unit. The

    labels of these two fields are user definable. The default values are Locationand Building. To change the field descriptions do so by selecting theView-

    Options-Changeable Labelsmenu item. The location fields are used in the

    Exploretab to help locate a motor. All other fields in the Nameplateview are

    optional.

    Note: Several of Bakers industrial customers have found having all fields filled

    in greatly helps in their preventive maintenance programs by providing one

    place where their plants motor data is kept. Likewise, Bakers motor shopcustomers find recording the complete nameplate information is a required taskwhen working with their customers motors.

    The Nameplateview allows for the adding of new motors, updating existingmotors and deleting motors from the database.

    Fig 2-9: Data Tab, Nameplate View

    19

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    20/98

    Adding a New Motor

    1. Click on the Add button The motor ID and the serial number field is

    cleared. All other fields will stay populated with the previous motors

    information. This is to assist in entering motors with like nameplateinformation. Click on the clear button to erase all fields.

    2. Enter the new Motor ID by filling in the location fields. For a choice of

    existing locations, click on the down arrow of the location boxes and as

    listing of existing locations will appear. See example Fig.2-10. All Plant(location field 1) locations in the database are available to choose from. If

    entering a new Plant location then simply type the new name in the field.

    3. Enter any other information to be tracked. When finished click on the Savebutton. When the Voltage Class restriction is enabled, entering the

    appropriate voltage class is required.

    Fi 2-10: Location

    4. Enter the Test ID to be used when testing the new motor.

    5. Note: Clicking the Reset button will redisplay the previously displayed

    motor and no motor will be added.

    Updating an Existing Motors Nameplate Information

    1. Make sure the Motor ID is selected and move the cursor to the field to

    update. Make the desired changes. The Savebutton will be enabled as soon

    as changes are started.

    2. When finished, click on the Save button and your changes will be

    committed to the database. If the changes are not wanted, click on theReset button instead of the Save button. All fields will reset and no

    changes will take effect.

    20

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    21/98

    Deleting an Existing Motor from the Database

    1. Make sure the Motor ID is selected and click on the Deletebutton.

    2. A dialog will be display asking if that is what is wanted. Click Yesand the

    motor and all of its test results will be deleted.

    Data Tab, Application View:

    The Application View

    provides a place to enter

    data about a particular test.

    Such information as who

    did the test, who the testwas done for, which MCC

    the test was performed

    from, and a general memo

    are fields that can be filledout at the time of testing or

    at a later date. The memofield is a good place to put

    such information as

    noticeable vibration of the

    motor before it was tested,

    etc. Using the scroll bars

    at the right of the viewscroll the view down and

    more fields appear.

    Note:The Tester Types

    stamped on this record, to

    indicate what type of digitaltester performed the test.

    Add new application records (which add a empty test record), update existing

    information, and delete test results from this view. To change what test result is

    being displayed, click on the date/time in the top window of the Datatab andthis will change the Applicationview to the selected data/times information.

    Fig 2-11 Data Tab Application View

    21

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    22/98

    Data Tab, Results Summary

    The Results Summary view displays the test results data summarized in a grid orcolumn is the Date and Time the test was performed. If all tests performed were

    passed, then the Date/Time will be displayed as a green cell. If one or more

    tests fail, theDate/Time will be

    displayed in a red

    cell. If no testswere performed

    then the cell will be

    gray. Use the scroll

    bars to the right and

    bottom to scrollthrough the results

    for each test

    category. The side-by-side nature of

    his view allows

    comparisons to be

    easily madebetween test

    results, by allowing

    all test results for a

    motor.

    To print a copy of

    this view right

    mouse button clickany of the gird and

    a dialog will appear

    to choose a printer

    and print the grid.

    Fig 2-12: Data Tab, Results Summary

    22

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    23/98

    Data Tab, Surge Views:

    The Surge view displays the surge waveforms for the selected test results. The

    surge waveforms can be viewed in two ways. The smaller of the two views

    displays the waveforms as a comparison of each lead superimposed on each

    other. The second surge view is an enlarged view which can be seen by clicking

    on the Enlargebutton on the Surge Tab view. This view offers a much largerpicture of the waveform allowing the waveforms to be displayed by lead and

    Nested (waveforms for each lead at the 1/3, 2/3 and full voltage aresuperimposed). Additionally, if the test failed, the previous to fail and the

    failed waveform will be displayed.

    Fig 2-13: Data Tab, Surge Results

    The Surge view not only displays the surge waveforms for all leads but also

    renders a view of the Pulse-to-Pulse Error Area Ratios (EAR).Click on the P-P EARbutton to view the Pulse-to-Pulse EAR graph. The graph

    displays the EAR percent between successive pulses per test lead and the

    tolerance used during the test. Also displayed at the right is the maximumpulse-to-pulse EAR per lead.

    23

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    24/98

    Fig 2-14: Pulse-to-Pulse EAR

    Data Tab, PI View

    Pressing the PI tab displays the PI

    View (Fig. 2-15) which contains thePI/DA graph and the data table.

    The PI graph charts the current vs.time and the Megohm reading vs.

    time. Under the PI graph are

    selected data points that are used in

    the graph. On the right side findthe following: PASS/FAIL, Test

    Voltage, DA/PI ratios, and 4 check

    boxes. Choose to have the graph

    plot Megohm/Current data in onesecond or one minute increments.

    The Tests Tab

    Pressing the Teststab displays a screen in Fig. 2-16 this Tests View. Each of

    the possible tests performed by the digital tester is indicated.

    Fig 2-15: Data Tab, PI View

    24

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    25/98

    Fig 2-16: Test Tab

    On the left are On/Off radio buttons that show what tests are selected to beperformed. Click on the radio button to turn the test on or off.

    In the center is a column of buttons that can be pressed to change test parametersor acquire real-time data from the digital tester. If one of these buttons is

    pressed, the test configuration screen pops up. Each tests configuration screen

    will be described below.

    After a test has been performed a right column of indicators will be displayed

    (not shown above). Green means a passed test, red is a failure and cyan

    indicates a test where the software could not determine a pass or fail. If a failure

    occurs, the reason why will be displayed on the red indicator.

    To acquire a stored record from the tester, click the Acquire Stored Records

    button. The selected Test ID will be used to indicate pass/fail of the stored

    record.

    To edit Test IDs click on the Edit Test IDcheck box. A prompt for a password

    will appear. If this is the first time to edit a Test ID since the softwareinstallation, press the Change Passwordbutton and enter a password then press

    the Set Passwordbutton. If this is not the first time to edits Test IDs, simply

    enter the password and press OK. Three new buttons will appear below the Test

    ID. Use the Savebutton to save changes that are made to the selected Test ID.

    Use the Addbutton to add a new blank Test ID or to copy the selected Test ID.Us the Deletebutton to delete the selected Test ID. When finished editing Test

    IDs click on the Edit Test IDcheck box to disable the editing of Test IDs.

    25

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    26/98

    Note: Leaving the Testsview will also disable the editing of Test IDs and all

    changes will be lost if they have not been updated.

    Test Configuration

    The three major setup screens for configuring tests parameters will be describedbelow. The specific choices made in the test setup screens define the Test ID.

    Before editing test parameters make sure to check the Edit Test ID box andenter the password. This allows saving of changes when finished editing.

    Temperature/Resistance Configuration/ Data Acquisition Dialog

    Clicking the temperature/resistance test Config/Acquire Databutton causes the

    Temperature/Resistance Test dialog to be displayed. The temperature and

    resistance are combined into one and are shown in Fig. 4-17. This screen is

    used to setup the temperature and resistance test parameters. It is also used toupload resistance data from the DR series or it can be used to manually enter

    Fig 2-17: Temperature Resistance Test

    26

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    27/98

    resistance data. To turn on Temperature or Resistance test parameters click on

    the respective rounded check boxes on the left side of the window.

    The Temperature Test provides a place where temperature can be entered

    manually. Temperature can be entered in either C or F. Entered at test time, itis used to temperature correct coil resistance values per IEEE 118 and insulation

    resistance values per IEEE 43/95.

    he Resistance Test has several options associated with it. The motor may have

    g

    y Checking the Max Delta R (%)box, the resistance values will have their

    The acquired resistance values may be temperature corrected by checking the

    Fig 2-18: Resistance Enable

    T

    Wye or Delta winding configurations. The Wye or Delta configuration is

    entered in the Nameplatewindow. The resistance values may be uploadinfrom Baker tester (DR series only) or acquired by some other means and

    manually entered into the software.

    Bpercent spread calculated at the end of the test. If the percent spread is outside

    the number entered in the edit box, the resistance test will show a DELTA R

    failure.

    Temperature Enablecheck box.

    Fig 2-19: Temperature Enable

    27

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    28/98

    Corrected to temperature is set to the IEEE 118 recommendation of 25C

    however, it can be changed. The constant used to correct resistances is known

    as the IEEE 118 constant and is 235.4 for copper or 224.1 for aluminum.

    Note: A Temperature must be entered in order to get corrected resistances.

    A motor that does not have a resistance reading within a Target Resistance range

    may also be failed by checking the Target Corrected Resistance check box andentering appropriate resistances. The application will compare corrected

    resistance readings to the Target Corrected Resistanceat the end of the test,

    determining if the resistances are within tolerance.

    Note:Only temperature corrected values will be used in determining if values

    are within the specific tolerance.

    The lower portion of the Temperature/Resistancedialog consists of threecolumns. The first is measured resistance values, the second is temperature

    corrected resistance values, and the third column is calculated coil resistance.

    The DR series tester acquires resistance data by hooking the tester to a computer

    with the MTA for Windows software installed. Perform the resistance test withthe tester. When testing is completed, leave the tester in the resistance screen

    and click on the Up Loadbutton on the Temperature/Resistance Dialog. The

    MTA for Windows will acquire the resistance data for all leads, calculate thetemperature corrected values (if temperature was entered) and calculate the coil

    resistance.

    Note: The data to be uploaded must be present on the testers resistance screen.

    Measurements merely present on the screen and not yet saved to memory are tobe acquired by pressing the Up Loadbutton. To acquire data saved to memory

    use the Acquire Stored Recordsbutton on the Test View.

    Fig 2-20: Test Results

    28

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    29/98

    If using a non-R series digital tester or have other equipment that takes the

    resistance measurement, it can be manually entered. If temperature

    compensation is needed enter the temperature and click the ANALYZEbutton

    to calculate the corrected resistance values and coil resistance. This will alsocalculate the delta resistance percent which is the maximum value minus the

    minimum divided by the average.

    Regardless of how the resistance measurements were acquired, once the

    measurements are obtained, the software will calculate the temperature corrected

    resistances and display them. The individual coil resistances will be calculated,

    if possible. If not possible, the software will display a message indicating asolution to the coil resistance could not be found

    Megohm/PI/HiPot Configuration/Data Acquisition Dialog

    Clicking the DC tests Config/Acquire Databutton on the Tests view causes the

    DC Tests dialog to be displayed. The dialog in fig. 2-21- is used to acquire real-

    Fig 2-21: Megohm/PI/HiPot Config

    29

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    30/98

    time megohm, PI and HiPot data. All three of these tests should be thought of a

    single type of test. The Megohm test is the first test to be run, followed

    immediately by a PI test, and continuing into a HiPot test. Therefore, a single

    set up screen for these three tests is used to configure each test.

    This dialog is used to setup test parameters and to acquire real-time data. In the

    upper left corner of the dialog is where test enable, test voltages, minimum

    Megohm readings, and test times are entered. In addition to DC test parameters,the temperature can be enabled and entered without having to enter the

    resistance screen when not taking resistance values.

    Each test may be run individually by pressing the appropriate test button locatedin the upper center of the dialog, or all selected tests can be run by pressing the

    Run Selected Testsbutton.

    The right side of the screen is a display of the real time voltage, current, and theinsulation resistance reading during the DC tests. The voltage and current will

    be displayed as slider bars. Below the slider bars are real time numerical

    outputs of the voltage and current.

    Surge Configuration/Data Acquisition Dialog

    Clicking the Surge testsConfig/Acquire Databutton on the TestsviewcausestheSurge Data Acquisitiondialog to appear.

    Target Voltageis located in the

    upper left corner.The surge targetvoltage is

    traditionally set

    to twice theoperating voltage

    plus 1000.The top center of

    the screen shows

    a series ofcheckboxes that

    determine

    Pass/Fail criteria

    for the surge test.The L-L EAR

    (%) checkbox

    30

    Doc #: 71-009-001 Rev 1

    Fig 2-22: Surge Test Dialog

  • 7/25/2019 MTA Manual

    31/98

    sets the maximum Lead-to-Lead Error Area Ratio (EAR) that is allowed

    between the different leads. This is set to 10% as a default. This option should

    not be turned on if testing a motor with a rotorinstalled. If it is absolutely

    necessary to use the L-L EAR with the rotor installed, increase the tolerance to

    avoid nuisance trips. The increase in EAR tolerance with installed rotors makesthe use of this feature a poor detector of a turn-to-turn insulation problem.

    L3) will show real time numbers for the specific lead while the test is running.

    These numbers will bec p number will indicate

    the current P-P EAR and the bottom number is the maximum P-P EAR percent.When P-P EAR (%) is turned on, voltage should be ramped slowly and

    he Test-Ref EAR (%) edit box is used to set a pass/fail criteria when

    ference

    he 4 buttons on the right side of the screen will run a

    if each

    Fig 2-24: Run Surge

    The P-P EAR (%) sets the maximum Pulse-to-Pulse Error Area Ratio that will

    be allowed for the test. This parameter helps identify turn-to-turn faults. If the

    pulse-to-pulse EAR % is greater than the entered tolerance, the MTA forWindows will flag a PPEAR error. The remaining three columns (L1, L2, and

    controlled.

    Fig 2-23: Surge Test Setup

    ome visible during the test. To

    T

    comparing the surge waveforms from the test to a previously stored ReTest.

    T

    surge test if pressed. Clicking the Lead 1button willstart the acquisition of the surge waveform on lead 1

    only, likewise for the Lead 2and the Lead 3buttons.The Surge All Leadsbutton will automatically

    sequence through Lead 1, Lead 2, and Lead 3 as

    button was pressed individually.

    31

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    32/98

    The peak voltage reached for each lead tested is displayed on the middle right of

    the screen. The L-L EAR values shown correspond to the measured Lead-to-

    Lead Error Area Ration between the three leads during the test.

    The surge waveform graph is shown below. The vertical or y-axis shows a

    voltage while the horizontal or x-axis shows time. The surge waveform is a plot

    of the voltage across a coil versus time.

    Fig 2-25: Peak Voltage & EAR

    Display

    Fig 2-26: Surge Waveform Graph

    32

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    33/98

    The Trending Tab

    Pressing the Trendingtab brings up a trending graph that charts acquired data.Information such as resistance, megohm values (temperature corrected and

    uncorrected), and HiPot leakage currents can be graphed over time in order to

    get an idea of the long term status of a motors insulation.

    Resistance

    There are three different types of Resistance data that can be trended, Balance,Line-to-Line, and Coil. Selecting one will bring up a graph similar to Fig 2-40.

    Resistance measurements are against time and show very little variation over thetest interval. Each of the three leads is shown in its own color. Each data point is

    indicated by a square, diamond or triangle marker. Hovering the mouse pointer

    over any of the data point symbols will display the value, test date and time for

    that point to popup. This feature allows for easy identification of the test record

    Fig 2-27: Resistance Trend Graph

    33

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    34/98

    for that point. By clicking the Markerscheckbox the markers can be hidden or

    unhidden.

    Insulation Resistance/MegohmBy checking the Megohmbutton, the megohm data is graphed. In the example

    shown below the Megohm reading fluctuates between 1246 and 1275 Mohms

    acceptable values, while the current remains constant. Hovering the mousepointer over any of the data points brings up a box indicating the value of the

    point and test date/time for the corresponding test record in the database.

    Note:When trending Megohm values, the temperature corrected values shouldbe used and not the uncorrected values. Both values are available to the

    software. Sometimes it is not possible to acquire the temperature of a motor

    when testing due to inaccessibility of the motor.

    Fig 2-28: Megohm Trending Screen

    34

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    35/98

    HiPot

    Pressing the HiPotbutton brings up a graph of the HiPot leakage current data

    and has the same features as the Megohm trending graph.

    PI

    Pressing the PIbutton displays the graph trending the PI ratio versus time and

    has similar features to the other trending graphs.

    Relative Humidity

    Checking Relative Humidity will cause the tool tips to display the RH% entered

    at test time. Hover over a data point will cause the tool tip to display Time/Date

    Stamp value of the point and RH%.

    Special Software Trending Features

    There are occasionswhen only a certain

    time period of data isdesired to be

    displayed or some

    invalid points need to

    be thrown out.

    There are two way

    which to select datapoints. The first

    method is when the

    trending graph is

    displayed. Hold the

    left mouse button anddrag and draw a box

    around the points to be displayed. See Fig. 2-29. When the left button isreleased, the graph will automatically re-scale and display the points inside of

    the drawn box. To reset the graph click on the Reset button and all p

    s in

    oints will

    be displayed.

    Fig 2-29: Megohm Trend

    35

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    36/98

    The second method is to choose points from a list of all test dates/times. By

    pressing the Select Datesbutton, a window pops up showing the entire test dates

    and times as well as a spreadsheet style view of the data. All of the data can be

    selected or just specific tests selected. Most often this feature will be used to

    exclude a test that contains known bad data that might be, for example, acquired

    in a test that was aborted. To select or deselect dates, use the same type ofselection techniques used to select files in Windows Explorer: left click to select

    a single record; left click the first record, press the shift key and click on the last

    record to select a range; within a selected range, press the ctrl-key and click to

    remove a unwanted record from the selection.

    Additionally, all of the records on this window can be exported to a comma-delimited file for later importing into a spread sheet. In this manner, data can be

    analyzed using the customers tools in any way desired. To create the commadelimited file, select the test date/time to be exported or select none and all will

    be exported, then click on thePrint to Filebutton, enter a file name and the

    application will create a comma delimited file that can later be imported to a

    spreadsheet. This dialog will also print out all the data in the list box to aprinter. Click on Print Listto print all selected data.

    Fig 2-30: Trending-Select Dates Screen

    36

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    37/98

    CHAPTER 3: EXAMPLE TEST

    Inside

    Creating a Motor ID

    Creating a Test ID

    Configure Temperature/Resistance

    Configure Megohm/PO/HiPot

    Configure Surge

    Running a Real Time Test Sequence

    Saving Data

    Reviewing Test Results / Data

    Printing Reports

    37

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    38/98

    38

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    39/98

  • 7/25/2019 MTA Manual

    40/98

    Fig 3.1: Test ID's

    Note:There are more data fieldsavailable than are contained on the

    nameplate. Only those items that

    are on the nameplate are filled in.

    Enter a unique identifier for the Motor ID. For this example use Delco-B-95-22L as the Motor ID. Plant location is Willow Ridge and Unit location is

    Unit 22L. Fill in the rest of the fields from the nameplate data previously

    given. After all data is entered click on the Savebutton to add the new MotorID to the database.

    After the Savebutton is clicked, a Select Test IDdialog will appear. At thistime you will need to assign a Test ID to the newly created motor. In this

    40

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    41/98

    example, we will select the 480V/woPITest ID next we will create a new Test

    ID and assign the new Test ID to this Motor ID.

    Once the Test ID is selected, click on the OKbutton. The new Motor ID,

    Delco-B-95-22L, is displayed in the tree to the left along with all the othermotors.

    At this point the Motor ID, Delco-B-95-22L, has been created. The next step isto create a Test ID and assign it to this motor.

    Creating a Test ID

    Fig 3-2: Creating a Test ID

    Press the Teststab. Notice there is already a Test ID assigned in theTest ID

    drop down box. For this example, we will add a new Test ID.

    To add a blank Test ID:

    1. On the Tests Tab, check the .

    41

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    42/98

    2. Enter the password. (Note: If this is the first time to edit Test IDs you

    will need to set the password by clicking on the Change Password

    button and entering a password then click on Set Password.) Click

    OK, once the application has accepted your password, the Save, Add,

    and Deletebuttons will appear and the voltage class dropdown list willbe enabled.

    3. Click on the Addbutton, the Create New Test IDdialog box appears.

    4. Click on the Add Blank Test IDradio button.

    5. Enter the Test ID, Delco_460/wPI, for this example.

    Fig 3-3: Test ID Input

    6. Using the dropdown box select a Target Motor Voltage Class. Forthis example, choose the existing voltage class of 460. If it does not

    exist you can create a new one by typing 460 in the edit box of thedropdown list.

    7. If you entered a new voltage class type, in a description and click onAdd Voltage Classbutton. You will be asked if you want to create a

    new voltage class, click OK.

    8. Click OK; this will close the Create New Test ID dialog.

    42

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    43/98

    Fig 3-4: Test Screen

    9. The new Test ID will be displayed and all tests are turned off.

    10. Turn on all of the tests by clicking the left most column of ON/OFF

    radiobuttons. The Tests view will resemble Fig. 5-4.

    11. Proceed to the next section,Configure Temperature/ Resistance.

    Configure Temperature/Resistance

    1. The Temperature and Resistance Tests share the same setup screen.

    Click on Config/Aquire Databutton under Temperature/ResistanceTestsheading. The Temperature/Resistance Testdialog will be

    displayed.

    43

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    44/98

    Fig 3-5: Temperature/Resistance Test Parameters

    2. Click on the Temperature Enablecheck box. MTA for Windows will

    accept a temperature range of range of -32C to 250C.

    3. Click on the Resistance Enablecheck box to turn on the resistancetest. The Delco motor in this example is wye wound, which is

    indicated on the screen and can be changed on the motors Nameplate

    Tab.

    4. Check the Max Delta R (%)check box, setting it to 10%. If the spread

    of resistance readings are more then 10% MTA for Windows will failthe motor.

    5. Since temperature is enabled, the Correct tocheck box is checked and

    defaults to 25C and the coppers IEEE 118 constant.

    6. Target Corrected Resistanceis another tool which further refines thepass/fail criteria. If checked, the MTA software will fail a motor if the

    readings are not within the tolerances. For the example motor its

    resistance reading, using a DVM, is 3.1 ohms. So it would be possible

    44

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    45/98

    to check the Target Corrected Resistancecheck box and enter the

    value of 3.1 +/- 10%. Enabling target corrected resistance makes this

    Test ID specific to the example motor. If resistance data is not

    available, do not enable this.

    7. Click on theClosebutton.

    Configure Megohm/PI/HiPot Tests

    1. To configure the Megohm/PI/HiPot tests, press Config/Acquire Data

    button under the DC Tests heading to bring up the DC Testsscreen. Forthis motor, the Megohm and PI tests will be run at 500V while the HiPot

    test will be run at 2000V. Consult IEEE 43/95 or another appropriate

    standard to determine test voltages.

    Fig 3-6: DC Test Parameters

    2. Since this is a small motor, the PI test will be ran as a DA test only by

    selecting the DA Onlyfrom the middle combo box.

    This motor has newer insulation doing a full PI test will not yield any usefulinformation.

    The other option, DA If IR>5000 @1m, sets up MTA for Windows to

    automatically skip the PI test in favor of the DA test, at 3 minutes if theinsulation resistance (IR) is greater than 5000 megohms at 1 minute. Insulation

    45

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    46/98

    resistance readings 5000 megohms or greater at 1minute is the generally

    accepted criteria for aborting the PI test. Once the DC Tests are configured as

    shown above, press the Closebutton to return to the main test screen.

    Configure Surge Test

    1. Press theConfig/Acquire Databuttonunder the Surge heading.

    Fig 3-7: Surge Test Parameters

    2. Configure the surge test as shown. Select the Target Voltageto be 2000V

    which is approximately 2*V + 1000.

    3. The L-L EAR(Lead-to-Lead EAR) has been turned off since this motorwill be tested with the rotor installed. If this option were left selected, a

    nuisance trip would almost certainly occur as the rotor coupling is different

    for each phase winding.

    4. TheP-P EAR(Pulse-to-Pulse EAR) is set to 10%. This means a pulse-to-

    pulse EAR value greater than 10% will cause the MTA for Windows to flag

    a failure.

    5. The Test-Ref EAR(%)is set to 10% which means that if a test is run, and a

    reference test exists, the reference waveforms will be compared to the

    acquired waveforms. Should the EAR values between reference waveforms

    and acquired waveforms be greater than the value shown, the MTA forWindows will fail the motor. If this option is not checked and is grayed out,

    no reference waverform is associated with this test.

    6. Press the Closebutton in the upper right corner of the Surge Data

    Acquisitionscreen to return to the Testsview.

    7. On the Testsview click on the Savebutton to save the Test ID to the

    database. From this point on the Test ID called Delco_460V/wPI will be

    46

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    47/98

    used to test the Delco motor or any other motor that has this Test ID

    assigned to it.

    Generic Test IDs versus Specific Test IDs

    The Test ID just created above is specific to the Delco 460 V motor of this

    example. This Test ID should not be used for another 460 V motor such as a 100hp/460 V motor. The reason is that we entered a Target Resistance value of

    3.1(ohms) which it is specific to this 3 hp Delco motor. If this Test ID were

    used to test a 100 hp motor, the resistance test would fail because the 100 hp

    motor will have a much lower winding resistance than 3.1(ohms). Therefore,

    if a Test ID is to be used for many motors, the Target Corrected Resistance

    option should not be used. Without a Target Corrected Resistance, there is nospecific or unique information that ties the Test ID to a specific motor. Baker

    has already provided several Test IDs based on machine voltage in thedatabase. These are generic Test IDs. (Target Corrected Resistance checking is

    disabled.)

    Running a Real-Time Test Sequence

    Once a new Motor ID has been created, and a new Test ID for this motor has

    been created, a real-time test can be run. The following sequence is

    recommended:

    1. Temperature

    2. Resistance3. Megohm

    4. PI

    5. HiPot

    6. Surge

    At the end of the sequence, you will need to click on the yellow Save Results

    button to save all test results in the same record. You may save after eachindividual test, however each test results will be save in a different record.

    Example Test ID:

    Temperature Enabled

    Resistance Enabled Max Delta %Megohm Enabled Test Voltage 500, Min Meg 10, Time 60s

    PI Enabled Test Voltage 500, Min Meg 10, Time 600

    HiPot Enabled Test Voltage 2000, Min Meg 10, Time 60s

    Surge Enabled Test Voltage 2000, P-P EAR, 10%

    47

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    48/98

    Using the example Test ID: follow the instructions below to acquire tests results.

    1. Make sure that the parallel port cable is plugged in to the computers

    parallel port and in to the testers printer/parallel port. The testers do havean Aux port; do not use this port for communication with the computer.

    2. Select the Motor ID of the motor to test.

    3. Click Teststab.

    Acquire Temperature and Resistance: Click Config/Acquire Databutton forTemperature and Resistance.

    Fig 3-8: Acquire Temp & Resistance Data

    48

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    49/98

    DR Series only1. Hook the resistance leads to the motor to test. Perform the resistance test

    for all leads, using the procedure for the tester. Leave the tester in the

    resistance screen.

    2. Enter Temperature of the motor, in the temperature field on the

    Temperature/Resistance Dialog.

    3. Click the Up Loadbutton. The MTA gets the resistance data from the

    tester, displays it along with the corrected resistance and coil resistance.

    OR

    Digital Series without Resistance

    1. Enter Temperature of the motor, in the temperature field on theTemperature/Resistance Dialog.

    2. Manually enter resistances data that was gathered with some other

    instrument.3. Click the ANALYZEbutton to temperature correct the resistance, to

    calculate coil resistance and to calculate the delta R %.

    4. Click the Closebutton to continue to the next test.

    Acquire Megohm/PI/HiPot: Click Config/Acquire Databutton for DC Tests.

    Fig 3-9: Acquire Megohm/PI/HiPot Data

    49

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    50/98

    The DC tests can be treated as one continuous test. Starting with the Megohm

    test using a low voltage held typical for 1 minute. Next is the Polarization Index

    (PI) test held at the same voltage as Megohm for 10 minutes the first minute

    being the Megohm test. Or the Dielectric Absorption (DA) test which is a 3minute PI giving a ratio of the 30 second reading to the 3 minute, instead of the

    1 minute reading to the 10 minute reading. The final test is the HiPot in which

    the voltage is increased to a higher target voltage and held for 1 minute. ConsultIEEE 43 and IEEE 95 for the appropriate test voltages.

    1. Set the knobs as instructed in your Digital Testers manual.

    2. Click the Run Selected Testsbutton. The software will instruct you to

    push the Test button on the digital tester. Push the test button on the

    tester. You have 4-5 seconds to push the test button on the tester before

    it times out.

    3. Slowly increase the voltage output on the tester. The voltage and

    current will be displayed as blue and red bars on the screen of thecompu release the

    Test bu a slight delay inresponse due to the communication between the tester and computer.

    voltage line appears on the voltage slider bar. When you reach the

    target voltage a message in yellow will appear.

    st button

    on the tester. A DA test was requested to be performed, at the end of

    ting megohm values at each minute and current values at

    each second.

    ter. If these bars do not appear after 5-6 seconds,

    tton and repeat the step above. Note there is

    4. Increase voltage to the test voltage specified by the Test ID; a target

    5. Adjust -Amps/div knob on the tester to best match the leakage currentof the motor being tested.

    6. Hold the Test button on the tester for the amount of time entered in theTest ID for the Megohm test. One minute is the standard time for a

    megohm test. A timer on the computer screen will count down the

    remaining time.

    7. At the end of the Megohm test continue to hold down the Te

    one minute the time remaining will reset to 2 minutes remaining for the

    DA test. (Since 1 minute has passed for the megohm and DA is 3minutes in total) After a few seconds the DA/PI dialog will be

    displayed, plot

    50

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    51/98

    8. Once the DA test has concluded, you will be prompted to increase

    voltage to the HiPot target voltage. Before increasing the voltage,

    change the -Amps/div knob to the 100 -Amps/div to avoid an ove

    current trip. Increase the voltage to the Test IDs test voltage for HiPo

    for this example that is 2000 volts. A message will be display when

    the

    r

    t,

    you hit the target voltage.

    9.

    onsult IEEE 43 and IEEE 95 forrecommended HiPot test times.

    11. on

    ey to respond to commands. During this time the

    computer is still communicating with the tester. You will get a

    12. the

    13. e Surge Test

    Not

    the compproperly

    screen o

    At target voltage re-adjust the -Amps/div to best match the leakagecurrent.

    10. Remain holding the test button as the computers time remaining counts

    down the specified time. C

    At the end of the test you will be prompted to release the PTT button

    the tester. A few seconds after the PTT button has been released; thcomputer will be read

    message on the CRT screen of the tester that indicates an error in thetransmission has occurred. This is normal.

    If satisfied with the test results press the Closebutton and return to

    Tests View.

    Continue to th

    e: Keep your main attention on the Digital tester. Occasionally glance at

    uters screen to insure that the data logging process in proceedingand to check test time remaining. The clock displayed on the CRT

    f the tester will not be accurate while communicating with the computer.

    51

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    52/98

    Acquire

    Tests.

    Real-Time Surge: Click Config/Acquire Databutton for Surge

    Fig 3-10: Acquire Real Time Surge

    Real time surge will acquire data from the tester to the computer after each surge

    pulse is applied to the motor under test. As a waveform is acquired, it will bedisplayed as nested waveforms. The waveforms at 1/3-Target voltage, 2/3-

    Target Voltage and Full Target Voltage will be saved as the test for each leadprogress. If the pulse-to-pulse EAR is turned on, as the voltage reaches 1000

    volts a smaller graph will appear in the lower right corner of the surge graph

    displaying the pulse-to-pulse EAR values from one pulse to another. If a turn-to-turn short is detected the software will flag a failure and you will need to

    release the test button on the tester.

    1. Set knobs and selector switch to Lead 1 as described in the Testsmanual.

    52

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    53/98

    e

    displayed.

    3. Quickly press testers Test button. You will have about 10 secondsbetween pressing the Surge Lead button and pressing the Test button on

    the Digital tester. When the computer begins acquiring data a red

    Testing Lead 1 message will replace the green Ready Lead 1message.

    4. Slowly increase the output voltage until the desired test voltage is

    reached. While increasing the voltage, watch the surge waveformdisplay, looking for indications of a turn-to-turn short. See the Digital

    Testers manual for information on identifying turn-to-turn shorts.

    5. Release the PTT button when the Target Voltage is reached or a failureis detected. A message will be displayed on the computer screen in

    either case.

    6. The Surge Data Acquisition Dialogwill show the final display of the

    waveforms.

    7. If the Seconds/div knob or Volts/div knob need to be changed to fully

    display the surge wave, make any adjustments then repeat procedureabove for capturing data.

    8. Repeat the same procedures for Leads 2 and 3. After all three leads

    have been tested; the lead-to-lead Error Area Ratio (EAR) values willthe right side of the surge window. The

    peak voltage from each leads test will also be displayed.

    1,ll

    2. Click Surge Lead 1button. A green Ready Lead 1 message will b

    be calculated and displayed on

    9. If the test results are satisfactory, press the Closebutton to return to the

    Testsview.

    Note: The Surge All Leadsbutton will automatically sequence through LeadLead 2 and Lead 3 as if each button was pressed individually. The operator wi

    only have to operate the tester.

    53

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    54/98

    Saving Data

    Fig

    nc ldata

    why failed, if the test failed at least one of

    he Save Res with the

    ote: Test resu st be saved prior to viewing them in the Datatab views

    ata

    After the test results have been saved to the database, they can be reviewed

    using the Datatab on the right hand pane of the MTA for Windows main

    window. The Results Summarytab shows aDate/Timewindow on the top part

    of the screen and a spreadsheet style view of the data on the bottom.

    3-11: Saving Data

    O e al tests has been completed return to the Testsview. All tests that haveacquired will display one of the following flags:

    Green Pass flag, if the test passed all parameters

    Red failure flag and reason

    the parameters

    Cyan Tested flag, if the data was acquired but it could not be

    determined that it pass/failed or did not have any parameters set.

    ultsbutton will be highlighted. Click it, when finishT

    sequence of tests.

    lts muNsuch as, ResultsSummary, Surgeor PI.

    Reviewing Test Results/D

    54

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    55/98

    The Date/TimeWindow shows a quick summary of the time and date of tests

    and whether the tests passed or failed. Double click on a test date and time to

    move to a new record.

    The spreadsheet style of

    results view shows the actual

    test data as acquired. The test

    date and time is shown acrossthe top of the window and the

    specific measurement results

    n.

    will

    alon i

    current a ings

    gath

    PI voltagtio are d

    are shown in each colum

    The PI test can be reviewed by

    pressing the PItab. PI view

    Fig 3-12: Date/Time Results Summary

    display the PI/DA graph

    g w th a table of the

    nd megohm read

    ered at specific times. The

    e, DA ratio and PIisplayed on the rightra

    side.

    Fig 3-13: Test Results Spreadsheet

    55

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    56/98

    Fig 3-14: PI Test Results View

    56

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    57/98

    The surge test data can be reviewed by pressing the Surgetab.

    Printing Reports

    MTA for Windows comes with a complete set of report generation features to

    facilitate the requirement that test results be made available to managers,owners, and repair personnel. Reports containing test data, nameplate data,

    application data, etc., ca r can be printed to a

    Microsoft Word 2000/X

    he following are three ways to invoke the Report Generator, shown above,

    clicking on the File Printmenu item, holding down the control key and

    pressing the P key, or pressing the printer icon on the upper left of the mainscreen. The top section of the Report Generator, called Select Filter(s), contains

    the filters by which you can choose what test results to print. You can select the

    current motor and test result, or use any combination of the other filters, such as,

    a date range and all motors that fail any test during that given test range. The

    bottom section of the Report Generator dialog is called Select Reports. Thissection is where you choose what reports you wish to print.

    Fig 3-15: Surge Test Data View1

    n be printed to a physical printer o

    P/2003 file.

    T

    57

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    58/98

    Fig3-16 Report Generator

    The Report Generator can look a bit intimidating, especially when you only

    want to print out the test result you have just been reviewing.

    This is the simplest case. The motor and test result that is selected in the main

    program will appear to the right of the checkbox titled Current Motor/Test

    Fig 3-17: Print Filter

    Resultsas seen in Fig 5-18. Click on that box and select which report is to beprinted in the lower part of the window and press the Printbutton. You will b

    asked which printer to use and the selected report will be sen

    e

    t to that printer. In

    ig 5-19 the Results Summary with Surge Summaryhas been selected.F

    58

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    59/98

    If several motors data need to be printed, instead of selecting one motors test

    results, then selecting the next motor and the appropriate record to be printed,

    and repeating this for all necessary reports, one at a time, the software provides a

    more elegant solution. The Report Generator can select all records that match acertain criteria. Those items used to filter the data are the Motors location

    fields, date range, or pass/fail criteria. Different combinations of the above

    options can be used, such as any motor at a given location within a given daterange that failed a Surge test can be printed.

    Once you have determined what test results to select, there are several choices

    fo ate, Application, Summary, Surge, or PI Testre election Filter (top part of the dialog) along with

    the Selected Reports section (bottom part of the dialog) to create reports. For

    stance, if you have the filters set to select all test records that failed the PI, but

    are selecting onnd what you want to see. You can easily set up the filters to select many test

    Consider the situation where an electrician tests many different motors duringthe day and needs to print reports for those motors that failed before going

    home. In this case the Report Generator should be configured as shown in Fi 5-of the window has the Date Rangeselected and

    ith

    Surge Summaryis selected. When the Printbutton is pressed, the Report

    Fig 3-18: Print Select Reports

    r what reports to print. Nameplports can be chosen. Use the S

    in

    you print only one of the surge reports, you will probably not get the

    information you are need. It is important to think out what youa

    results, but this may not be what you want or have time to print.

    g20. The Select Filter(s)section

    set both dates as 4/29/2005. This will cause the application to look for all test

    results that took place on 4/29/2005. Next filter selected is the Pass/Fail. Select

    the FAILradio button. This will cause the application to print results for

    motors that have failed one or more tests on this date. Tests that passed will notbe printed. In the bottom Select Reportssection, the Results Summary w

    59

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    60/98

    Generator will go thru the entire database, looking for any failed tests that

    occurred on 4/29/2005. Once it is done searching a dialog box will appear

    informing you of how many records were selected. You can either choose to

    cancel or continue and print the selected reports.

    Fig 3-19: Report Generation Example

    Note:The Report Generator can be set up so that a large number of reports are

    reated. Printing out a large number of reports can be very time consumc ing,

    a

    especially when going to Microsoft Word . The Report Generator will informyou of how many test results are chosen, this is not the number of pages that will

    be printed. That depends on the number of reports chosen.

    The program can also print reports to Microsoft Word, (see Fig 5-21) if it is

    installed on the desktop computer running the software. This feature provides away to annotate reports by adding text to the Word Document as required. For

    example, a comment regarding the vibration level of the motor before it was

    turned off can be added to the Word document. This feature should also be usedwith caution because printing reports to MS Word takes some time selecting

    60

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    61/98

    lot of records to print means the system will be tied up for a long period of ti

    before all records can be transferred to the Word document.

    A typical Word report looks like the figure below

    me

    . Each of the sections is a

    Word table, except the surge waveform hich is a bitmap. The reports can bemodified by adding text between the tables or the data tables can be cut and

    pasted into other documents. See the next three pages for a sample report.

    w

    61

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    62/98

    Sample Report

    62

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    63/98

    63

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    64/98

    Fig 3-20: Sample Report

    64

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    65/98

    65

    Doc #: 71-009-001 Rev 1

    CHAPTER 4: DATABASE

    MANAGEMENT

    Inside.

    Motor ID Field Motor Location Fields

    Multiple Databases

    Opening Databases

    Creating a New Database

    Data Transfer

    Transferring Motor and Test Data

    Transferring Test IDs

    Archiving a Database

    Restoring a Database

    Converting Older Databases

  • 7/25/2019 MTA Manual

    66/98

    66

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    67/98

    Database Management

    Database management is a highly important feature of a good predictivemaintenance-testing program. It facilitates organization of periodic maintenance

    data. The database section of the MTA for Windows software allows the entry

    of identifications to help clarify the location of specific motors, along with theuse of multiple databases to help organize overall program maintenance. You

    will need to develop a best practice in keeping the data collected, easily

    accessible and meaningful. The discussion in this chapter will be about the tools

    the Analyzer Software provides to aid you in database management. The

    following will be discussed:

    Motor ID

    Motor Location Fields

    Multiple Databases

    Data Transfer

    Archive

    Restore

    Conversion of Older Databases

    Consequences of Not Organizing Data

    It is recommended to establish a structure that is to be used by all persons

    performing tests. Consider the following example: A maintenance program isestablished to test motors at seven plastics production plants, each in a remote

    location. Each plant has nearly 1000 motors that are identified as needing

    periodic testing. All works well for several months until a motor that waspreviously tested fails. The maintenance manager wants to see all the test data.

    When the project supervisor looks at the data, he finds nearly 7000 tests, all in

    one large database, and in a random order. He spends about an hour looking forthe last test performed and gives up. Upon investigation he finds that each of the

    technicians using the equipment has been entering the data based upon what

    made sense to him at the time. Because of the disorganization, important testdata has been lost or at best difficult to locate.

    The database structure is designed to facilitate data organization and to be

    flexible enough to allow you to uniquely plan for your needs. The Motor ID,

    two location fields, and the multi-database abilities are the tools for you to use toorganize the data so that the above scenario does not happen to you.

    67

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    68/98

    68

    Doc #: 71-009-001 Rev 1

    locations. Take steps at the start to ensure that the

    duplicate processes, it makes databasen se two motors can be uniquely identified. One way to

    s to include in the Motor ID the process ID as in the

    lo e Motor ID for Process 1 could be Intake Pump P1 while the

    t ake Pump P2.

    In the example Exploretab to the right,

    motors have been organized by location

    Fig 4-1: MTA Database Tree

    otor ID FieldMThe records that are stored are linked to each other hierarchically. The principle

    field, which serves as the base for linking associated records, is the Motor ID.

    The Motor ID is also the main means of locating and interacting with a motorsdata. Therefore it is important to develop a naming scheme that will facilitate

    location and retrieval of information. Case in point, it is not uncommon for aplant to have duplicate processes, with identically named motors in each process

    (ex: Intake Pump) . This can cause confusion, since the motors have the sameMotor ID, but are in different

    t l be unique!Mo or IDs wil

    is present inExample: If Intake Pumpif thema agement easier

    blem isolve this pro

    fol wing: Th

    Mo or ID for Process 2 could be Int

    Motor Location Fields

    The Motor ID is the primary identifier

    of a motor by which it can be located.There are two other fields that are used

    to help in locating a motor in the

    database. The location fields havedefault field names of Location and

    Building. If these labels do not make

    sense for your situation then you canchange them. (ChooseView-Options-

    Changeable Labelsmenu item from

    the AWA software.) For instance, for a

    plant maintenance program with severallants, the label of the location fieldsp

    may be renamed to Plant and Unit.

    These location fields along with the

    Motor ID are entered as part of thenameplate record and are used to make

    up the tree structure of the Exploretab.

  • 7/25/2019 MTA Manual

    69/98

    in Plants and Units. North Platt and South Branch are Plants and Unit 23,

    nit45A, Unit 17C are all units.

    ultiple Databases

    is important to establish your best practices for database organization early

    ing

    s. Proceed with

    aution when manipulating data always backup a database before deletingtabase in any way.

    ion under the Filemenu or click on the

    U

    M

    The MTA for Windows software allows the use of multiple databases. You may

    split the data between different databases, grouping motors in whatever way thatis beneficial to you. For example, motor shops might want to use different

    databases for each of their customers. A preventive maintenance departmentcould use a different database for each part of their plant. You may need to keep

    the data in a centrally located database on a network and have databases locallyon other computers, which are used to update the main database.

    It

    and maintain adherence to the establish practices to avoid loss of data or datafrom the same motor being in several different places.

    Note: Manipulation of the database may be useful for management and audit

    purposes. Do not delete records associated with Motor ID

    crecords or manipulating the da

    Opening a Database

    To open a database, select theOpenopt

    open database icon on the toolb

    allow the selection of a database to u

    Fig 6-2: S

    ar. An open file dialog box will pop up and

    se as shown below. It will default to the

    elect Database

    69

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    70/98

    folder that has been selected in View-Option-File Locationsmenu item. I

    case above the default folder is MT

    n the

    AData. By selecting a database (.mdb) and

    licking the Openbutton or by double clicking the desired database the AWA

    atabase.

    w

    c

    application will open the d

    Creating a New Database

    To create a new database, select the Newfrom the Filemenu item or the ne

    database icon on the toolbar. The Create New Databasedialog will be

    displayed, as seen below. The Save infolder is the default folder, you can

    Fig 6-3: Create New Database

    navigate to another folder if desire, enter the name of the new database in the

    box next to the File Name:and click on the Savebutton. A database will becreated and opened that has one default motor and the Baker default Test IDs.

    At this point you can begin entering new motors using theData-Nameplatetab.

    Data Transfer

    The Data Transfer tool allows you to transfer motor and test information from

    one database (source) to a second database (destination). The transferredinformation is not deleted from the sourcedatabase, it is only copied to the

    destinationdatabase. The Data Transfer can be used to combine two existing

    databases into one centrally lo used to re-organizecated database. It can also be

    70

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    71/98

    exiting database into more convenient groupings. Anytime you need to move

    motor data or Test IDs the Data Transfer provides this functionality.

    Transferring Motor and Test Result Data

    tion, test result data and Test IDs, two

    atabases need to be open. A sourcedatabase, the database to transfer

    information to. Both databases must exist before beginning the transfer. To

    n thetoolbar.

    There are two ways in which to start the Data Transfer. The first method is tochoose theDatabase-Data Transfermenu item from the software menu, or

    click on the Data Transfer button on the toolbar.

    In order to transfer motor informa

    dinformation from, and a destinationdatabase, the database to transfer

    transfer to a new destination database, create it before beginning the Data

    Transfer, by selectingFile-Newmenu item or clicking on the new button o

    Once the Dwill present an open source file

    xample3 database is open in the

    Dataed, the open

    urce file dialog defaults to the

    Fig 4-1: Data Transfer Buttons

    or

    ata Transfer is started it

    dialog box and default to the folder

    in which the currently opendatabase resides. For example, in

    the above screen shot theE

    main program. When theTransfer button is click

    so

    MTAData folder with the

    Example.mdb for theFile name.

    Fig4-2: Select Source AWA Database

    71

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    72/98

    The option to pick the default database or choose another database to transfer

    data from is available.. This is the sourcedatabase.

    Once the source database is chosen, click the Openbutton. The following dialog

    ill be displayed, with the source database opened on the left side. Notice the

    splayed, click on the destination database

    open the destination database.

    wfamiliar Motor ID tree structure.

    After the Data Transfer dialog is di

    Browsebutton, in order to

    Fig 4-3: Data Transfer Select Screen

    72

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    73/98

    Presented will be a destination file open dialog. It will default to the same folder

    s was used to open the source database. Choose a destination database to open

    When both the sourceand destinationdatabases are open the Add Alland the

    Add buttons are enabled. The application is ready to select motors from the

    source database to be added to the Transfer List. The Transfer Listis the listof motors that will be transferred when the Transferbutton is pushed. The Add

    Allbutton adds all the motors in the source database to the Transfer List. The

    following gives two ways to add selected motors to the list.

    1) Highlight the motor to add, and press the Addbutton.

    a

    and press the Openbutton. At this point the software returns to the Data

    Transfer dialog with both databases open.

    If either database is not the desired database, choose the appropriate databases

    by clicking on the Browsebutton next to the wrong database and chooseanother.

    Fig 5-4: Data Transfer Destination Database

    Fig 4-4: Data Transfer Destination Database

    73

    Doc #: 71-009-001 Rev 1

  • 7/25/2019 MTA Manual

    74/98

    ove

    he Removebutton. When theransfer Listis finalized, press the Transferbutton.

    llows.Transfer runs through the Transfer Listadding the motor

    ameplate) information if the motor does not exist in the destination database.

    If the motor does exist, no motor information will be added. Next, the Data

    Transfer adds any test records that do not exist in the destination database. Itcompares the time/date stamp with existing test result records and if the source

    time/date equals a test result record in the destination database it does not

    transfer the record. If the application does not find any matching time/date then

    it adds the source test result record to the destination database.

    The Data Transfer creates a log during the transfer process. Information logged

    is source/destination database names, Motors IDs added, and number of recordsupdated. If the transfer encountered any problems, it also logs the Motors ID

    and reason the transfer failed. Print this log by clicking on the Print Logbutton.

    Transferring Test IDs

    NOTE: Test IDs are transferred separately from the Motor IDs.

    To transf ransferring Motor

    and Test Result Data section on how to open a source and destination database.

    The source and destination database both must be open before any transfer canbe performed. Once both databases are open, theTransfer Test IDs button

    w alog below.

    e dialog displays all Test IDs in the source database, as well as the Test IDs

    2) Double click on the motor to add.

    If there are motors on the Transfer Listthat are not to be transferred, rem

    them by selecting a motor(s) and pressing tT

    The method the Data Transfer a