MULTI-PURPOSE FOR 2|4 PIPE SYSTEMS
IPOLUY .1402. 4724311_01
USER MANUAL
EN
MULTIPURPOSE UNIT
CONTENT
1. USERINTERFACE(PGD1) ............................................................................................................. 4
2. REMOTETERMINAL(PGD1) ........................................................................................................ 5
3. USEOPERATIONALPROCEDURES ............................................................................................. 6
4. MENUSTRUCTUREANDNAVIGATION ...................................................................................... 7
5. DISPLAYS-SWITCHINGUNITON ............................................................................................... 9
6. MAINDISPLAY ............................................................................................................................ 10
7. IN/OUT MENU ........................................................................................................................... 14
8. ON/OFF MENU ........................................................................................................................... 18
9. PLANT(2PIPES) ......................................................................................................................... 19
10. RECOVERYMENU(2PIPES)....................................................................................................... 22
11. COOLMENU(4PIPES) ................................................................................................................ 23
12. HEATMENU(4PIPES) ................................................................................................................ 24
13. CLOCK MENU ............................................................................................................................. 25
14. ALARMS MENU .......................................................................................................................... 27
15. ALARMSLOGMENU .................................................................................................................. 28
16. ALARMS LIST .............................................................................................................................. 29
17. INPUTS/OUTPUTS LIST .............................................................................................................. 31
4IPOLUY .1402. 4724311_01
KEY FUNCTION
���
���
���
���
ALARMS KEYDisplaysthelistofalarmsandthealarmslog;
���
���
���
���
MENU ACTIVATION KEY•Pressingthiskeyactivatesnavigationamongthemenus;
���
���
���
���MENU EXIT KEY•Pressingthiskeyleadstothedisplayofthepreviouswindow;
���
���
���
���
NAVIGATION KEY (+)•Pressing this keyduringnavigation through themenus/parameters,allowstopasstothenextmenu/parameter;•Pressingthiskeyduringparametermodification,increasesthevalueoftheparametermodified;
���
���
���
���
NAVIGATION KEY (ENTER)•Pressingthiskeyduringnavigationthroughthemenus,allowstoentertheselectedmenu;•Pressingthiskeyduringnavigationthroughtheparameters,allowstoselecttheparameterdisplayedandenterthemodificationmode;•Pressingthiskeyduringparametermodification,confirmsthemodifi-cationtothevalueoftheparameterselected;
���
���
���
���
NAVIGATION KEY (-)•Pressingthiskeyduringnavigationthroughthemenus/parameters,allowstopasstothepreviousmenu/parameter;•Pressingthiskeyduringparametermodification,decreasesthevalueoftheparametermodified;
1. USERINTERFACE(pGD1)
Thecontrolpanelallowsquicksettingofthema-chinefunctioningparametersandtheirdisplay.
Thedisplay ismadeup froma graphicalmatrixwith132x64pixelinordertosignalthetypeoffunctioning, displaying set parameters and anyalarmsthathaveintervened.
All default settings and any modifications arememorisedintheboard.
With the installation of the PGD1 remote panel, all of the functions and settings available on the machine can be replicated at a distance.
Afterapowercut,theunitcanre-startautomati-callykeepingtheoriginalsettings.
Theuserinterfaceisrepresentedbyagraphicdis-playwithsixkeysfornavigation.Thedisplaysareorganisedviaamenuhierarchy,whichcanbeactivatedbypressingthenavigationkeys. The default for displaying thesemenus isrepresentedbythemainmenu.
Navigationbetweenthevariousparameterstakesplaceusingthearrowkeyspositionedontherightside of the panel. These keys are also used tomodifytheparametersselected.
���
���
���
���
INTERFACE CONTROL KEYSControlkeys Controlkeys
WARNING Tampering of parameters contained in the assistance and the manufacturer menu can cause unit mal-functioning. It is therefore recommended that these parameters are modified only by authorised staff.
�
� ATTENTION The 2-pipe NRP is set up for the production of cooled water, hot water and Domestic Hot Water (D.H.W.).- No Anti-legionella Cycle is included
The 4-pipe NRP is set up for the production of cooled water and hot water.
5IPOLIUY .1402. 4724311_01
Theterminalcanberemote-controlledupto50musingatelephonecable,whileusingashieldedtwincable,aTCONN6J000andaseparatepowersupplyitcanberemote-controlledasfaras500m.
� ATTENTIONThe cable must always be shielded for domestic use of the terminal.
� ATTENTIONFor further information concerning installation of the remote terminal, see the instructions inside the accessory.
AddressconfigurationIftwopGD1terminalsareconnectedtothesameboard,thesecondterminalmustbeassignedwithadifferentaddressthanthefirst(whichis32).1.PowerthepGD1withthetelephoneconnector.2.Pressi↓↑Entersimultaneouslyforatleast5seconds.3Tomodifytheterminaladdress(displayaddresssetting)pressEnteronce:thecursorwillmoveontotheaddressfield(nn).4Usethe↓↑keystoselectthedesiredvalueandconfirmbypressingEnter.
2. REMOTE TERMINAL (pGD1)
6IPOLUY .1402. 4724311_01
3. USE OPERATIONAL PROCEDURES
TomanageormodifytheNRPunitoperationalparameters,thecontrolboardinterfaceonthemachinemustbeused.Thefundamentaloperationsthattheusermustbeabletoperformforcorrectuseoftheunitare:
(1)Topassfromonemenutoanother;
(2)Toselectandmodifyaparameter;
1To pass from one menu to another
(a) Inorder to scroll thevariousmenus (theorderwithwhich themenusaredisplayed is represented in thepreviouspage) it is firstnecessarytoenterthemenuselectionmode,pressingthe( ���
���
)key;
(b)Once themenu selectionmodehasbeenentered, thesecanbescrolledusing thearrowkeys: the (
���
���
) key topass to thepreviousmenuandthe(
���
��� )keytopasstothenextmenu;
previousmenu
subsequentmenu
(c)Whenthedesiredmenuisdisplayed,pressthe(���
���
)keytoenterthemenu.Toexit themenuandgoback tomenu selectionmode,pressthe(
���
��� )key;
Toexitamenu
Enter inamenu
2To select and modify a parameter
(a)Oncetheselectedmenuhasbeenentered(followingtheproce-dure( 1 )itispossibletoscrollthewindowsthatmakeitup,usingthearrowkeys,usingthe(
���
���
)keytopasstothepreviousparameterandthe(
���
��� )keytopasstothenextparameter;
previousparameter
subsequentparameter
(c)Whenthedesiredparameterisdisplayed,pressthe(���
���
)keytoentertheparameter.Toexittheparameterandgobacktoparam-etersselectionmode,pressthe(
���
��� )key;
ATTENTION: Onceaparameterhasbeen selected,press the (���
���
) key toauto-maticallyenterthemodificationmodeofthatparameter.Fromthismodeitispossibletosetthedesiredvaluesfortheparameters,fol-lowingtheprocedurebelow:(1)bypressingthe(���
���
)key,aflashingcursorwillappearnearthefirstmodifiablefieldoftheparameter(iffieldsthatcanbemodifieddonotappear,nocursorwillappear);(2)bypressingthe(
���
���
)keyorthe(
���
��� )keythevalueinthefieldwillbeincreasedordecreased;(3)bypressingthe(���
���
)key,themodificationstothefieldvaluewillbeconfirmed,savinginthememory;
On the basis of the type of the type of parameter selected, the number of fields that can be modified could vary;
Toexitaparam-eter
Toenteraparameter� ATTENTION
To adjust display contrast, press Alarm + Prg simulta-neously and use the keys to increase or decrease contrast.
7IPOLIUY .1402. 4724311_01
4. MENU STRUCTURE AND NAVIGATIONMenudisplayisorganisedbyrotationoftheiconsrepresentingthem.Havingselectedthedesiredicon,youenterthechosenmenu,allowingyoutoviewormodifytheparametersmakingitup.Theprocedurefornavigatingthemenusormodifyingtheparametersisexplainedindetailinthechapter"Useoperationalprocedures".Seeitforfurtherinformation.
Index Icon Menu Menu function
A P1
P1
IN/OUTContainstheinformation(tempera-ture, pressure, etc.) of the systemcomponents.
B P1
P1
ON/OFFSwitchestheunitonandoffandsetsitsfunctioningmode(summer/winter)andeventualtimeperiods.
2-PIPE VERSION
C P1
P1
SYSTEMManagementofthechillerparam-eters,standard/energysavingworkset-point.
D P1
P1
RECOVERYDHWmanagementparameters(set-point,consent,temperature,timeperiods,etc...).
MAIN SCREEN VISIBLE FOR USER
A
B
C
DE
F
G
Manufacturer Menu protected by password
Assistance Menu protected by password
MAIN SCREEN VISIBLE FOR USER
Index Icon Menu Menu function
E P1
P1
CLOCKManagesallparameterslinkedtothesystemtime(hour,date,etc....).
F P1
P1
AFTER-SALESASSISTANCE
Protectstheafter-salesassistancemenuwithpasswordrequest.
G
E - C
R - E
E V C N
R E
1 2
1 2
F
F
LT
HT
MANUFACTURER Protectsthemanufacturermenuwithpasswordrequest.
4-PIPE VERSION
C P1
P1
COLD
Management of the chillerparameters, standard/energysaving work set-point whenfunctioningincoolingmode.
D HOT
Management of the chillerparameters, standard/energysaving work set-point whenfunctioninginheatingmode.
User Menu
8IPOLUY .1402. 4724311_01
Assistance Menu protected by password
ASSISTANCE MENU MAIN SCREEN(parameters can be modified by authorised personnel alone)
Assistance Menu (protected by password)
MultipurposeUnit-UserMenu-MenuStructureandNavigation
Index Icon Menu Menu function
A LANGUAGE Selectingtheuserinterfacelanguage
B INFO Informationregardingthesoftware
C2 PIPES
AssistanceparametersforthechillerCHILLER4 PIPES
AssistanceparametersincoolingmodeCOLD
D
2 PIPESAssistanceparametersfortheDHW
RECOVERY
4 PIPESAssistanceparametersinheatingmode
HOT
EVENTILAT. Ventilationassistanceparameters
Geothermalside Serviceparametersofgeothermalpump
F PUMPS Pumpsassistanceparameters
G TIMER Devicesworkinghourstimer
H MANUAL Manualcontrolsforcing
I ACCESSORIES Enablingofaccessoriesmodules
L C.SYSTEM Definitionofsystemfeatures
M VARIOUS Settingassistanceparameters
N IN/OUT Inputandoutputstates
B
C
D
E
FG
H
I
L
M
NA
ASSISTANCE MENU MAIN SCREEN
(parameters can be modified by authorised personnel alone)
9IPOLIUY .1402. 4724311_01
5. DISPLAYS - SWITCHING UNIT ON
Displays - Switching Unit on
Unitdisplay Index Display/Parameter
Thefollowingtableshowsthewindowsvisiblefortheuserwhentheunitispowered.
WARNINGtampering of parameters contained in the assistance and the manufacturer menu can cause unit malfunc-tioning. It is therefore recommended that these parameters are modified only by authorised staff.
�
L a n g u a g eL a n g u a g e E N G L I S H
E N T E R f o r c h a n g eE S C t o c o n f i r m
T i m e s h o w m a s k 20
W a i t p l e a s e 6s
A
A
Introductorywindow,visible30secondsafterunit isswitchedon.
The seconds remaining before passing on to the languagechoicemenuareindicatedatthebottomright.
B
Indicatesthepossibilityofchoosingthedesiredlanguage.
The seconds remainingbeforepassingon to themain screenareindicatedatthebottomright.
After20secondshaveelapsed,itwillnolongerbepossibletomodifythelanguageuntilthenexttimetheboardisrestarted.
� The language can be modified by qualified personnel alone, using the ASSISTANCE MENU.
10IPOLUY .1402. 4724311_01
Icon Meaning
E - C
R - E
E V C N
R E
1 2
1 2
F
F
LT
HTIndicatesthattheoutletlowtemperatureantifreezepreven-tionisactive.Switchescompressorsoff.
E - C
R - E
E V C N
R E
1 2
1 2
F
F
LT
HT Indicatesthattheoutlethightemperaturepreventionisactive.Switchesthecompressors/modechangeoff.
B IndicatesthestatesinwhichthecircuitcanbefoundIndicatesthestatusinwhichtheunitcanbefound.
E - C
R - E
E V C N
R E
1 2
1 2
F
F
LT
HT
E - C
R - E
E V C N
R E
1 2
1 2
F
F
LT
HT1 2
3 4
Indicatescompressorstatus:disabled(1),off(2),on(3),inalarm(4).
6. MAIN DISPLAY
Duringnormal functioningof theunit, thePGD1 panel display shows the main win-dow.Thiswindowcontainstheinformationon the system status and this informationwillallowtheusertohaveaclearindicationregarding functioning of the NRP unit aswellastosupplyanyerrorand/ormalfunc-tioningmessages.
Dependingonthefunctioningmode,differ-ent informationcanbedisplayedconcern-ingthecurrentstatusoftheunit,userset-tings,etc.
Tohavea clear interpretationof the iconspresent in the main window, refer to thetablebelow.
E - C R - E15.0 °c
CH+R CH+R
40.2 °c
c40.1°c19.3Aermec Tue 14:29
°
MAIN WINDOW DISPLAY
A
B
Icon Meaning
A Indicatesthedayoftheweekandthetime.
E - C
R - E
E V C N
R E
1 2
1 2
F
F
LT
HT
E - C
R - E
E V C N
R E
1 2
1 2
F
F
LT
HT
Indicateswaterinletandoutlettemperature(evaporator in summer and condenser inwinter).
E - C
R - E
E V C N
R E
1 2
1 2
F
F
LT
HT
IndicateswaterinletandoutlettemperatureofDHWsideheatexchanger(recovery).
E - C
R - E
E V C N
R E
1 2
1 2
F
F
LT
HTIndicatesthepercentageofwaterrequest-edbythemachineintendedforthesystemorforrecovery.
P1 2
Indicateswhichpumpisrunning.Theiconontheleftreferstothepumponthesystemside,ontherighttotheheatrecoverypump.Thenumberbelowshowswhichpumpison
E - C
R - E
E V C N
R E
1 2
1 2
F
F
LT
HTNRP Indicatesthattheanti-freeze
resistanceisactive.
NXP Optionnotpresent
E - C
R - E
E V C N
R E
1 2
1 2
F
F
LT
HT
Indicatesthattheflowswitchisopen.Ifitremainsopentoolongthecompressorsswitchoff.Thepumpswillreleasetheflowswitch.
Description of icons displayed on main window
11IPOLIUY .1402. 4724311_01
State MeaningC1 C2 ThesystemisactiveandrunningCH ChillerfunctioningCH+R Chiller+totalrecoveryfunctioningPC HeatpumpfunctioningREC TotalrecoveryDEFR DefrostactiveWAIT ThecircuitisinstandbybecauseconfigurationischangingLC Lowload:IndicateslowwatercontentorlowthermalloadOK Setpointachieved
Description of the status in which the circuit can be found
MultipurposeUnit-UserManual-MainDisplay
State MeaningEnabled Thesystemisactiveandrunning
Offbyalarm Thereisaseriousalarmwhichstopsthesystem(checkthelistofalarms,belowthealarmkey)
GeneralOff ThesystemisswitchedOFFbytheterminal;checktheON/OFFscreenOffbysupervisor(BMS) Thesupervisionsystemhaspreventedunitstart-upOffbyclock Lefasceorarieimpostateimpongonol’OFFdelinterosistemaOffbydigitalinput L’ingressodigitale(ID8)èchiusoeponeilsistemainOFFOffbydisplay L’impiantoe’inOFFdaterminale.Controllarelaschermata IMPIANTO
OffbyPlant-side/ColdsideNRP Plant-side/Coldsidedisable/off:Recovery/HeatsidenotworkingNXP Optionnotpresent
Anti-freezeNRP Azionediprevenzionegeloall’’internodegliscambiatorid’acquaNXP Optionnotpresent
ManualMode Thecompressorsorpumpsareforcedtomanually
A t t e n z i o n e
F u n z i o n en o n p r e s e n t e
Function not present
Ifafunctionisnotpresentthefolowingscreenwillbeshown.
ToreturntothemainscreenpressESC.
Description of the status in which the circuit can be found
NRP 2 PIPESO n / O f f U n i t u 3
P l a n t s i d eE n a b l e d
R e c o v e r y s i d eE n a b l e d
G e n e r a l e n a b l e :
Y E S
NRP 4 PIPESO n / O f f U n i t u 3
C o l d s i d eE n a b l e d
H e a t s i d eE n a b l e d
G e n e r a l e n a b l e
Y E S
EnabledOffbyalarmOffGeneralOffBMSOfftoclockOffinp.dig.OffdisplayOfffromplantAntifreezer
EnabledOffbyalarmOffGeneralOffBMSOfftoclockOffinp.dig.OffdisplayOfffromplantAntifreezer
EnabledOffbyalarmOffGeneralOffbyBMSOffbyclockOffinp.dig.
Offbydisplay
EnabledOffbyalarmOffGeneralOffbyBMSOffbyclock
OffbydigitalinputOffbydisplay
ATTENTIONNRP 2-pipe system - Deactivated system /Off: also the recovery side is excludedNRP 4-pipe system - Deactivated Cool Side /Off: also the heating side is excluded*for NRP units
12IPOLUY .1402. 4724311_01
MultipurposeUnit-UserManual-MainDisplay
NRP 2 PIPESBy pressing the
���
���
���
���
���
���
���
��� keys it is possible to access other displays of the main window
Main window - Information on system side heat exchanger
Unit display Index Display/Parameter
Fromthiswindowitispossibletoviewtheinformationrelatingtotheheatexchangeronthesystemside
A Currentworkset-point
B Evaporatorinlettemperature
C Indicatestheheatdropvalue
D Temperatureatwhichmachineisadjusted
E Percentageofproportionalfactor(ifactivatedPID)
F Percentageofintegralfactor(ifactivatedPID)
G Percentagerequestedbysystem
H Theactualpowerpercentageused
P l a n t s i d eS e t p o i n t
7.0°CDiff. 5.0°CTemp.Outlet: 8.5%Ep 30% Ei 9.0%Req. 39% Active 2.9%
A
B
CD
E
G H
F
Main window - Information on circuits 1 - 2
Unit display Index Display/Parameter
A Showsthecircuitdemand
B Showsthecircuitstatus
C Showswhichcompressorwillstart/stop
C i r c u i t sTotal require 60%
Cirucit 1: 58% CH + RecCircuit 2: 58% Rec
Next ON 2 Circ.1 83sNext Off 1 Circ.1
BA
C
Main window - Information on DHW side heat exchanger
Unit display Index Display/Parameter
FromthiswindowitispossibletoviewtheinformationrelatingtotheheatexchangerontheDHWside
A Currentworkset-point
B Heatexchangeroutlettemperature
C Indicatestheheatdropvalue
D Temperatureatwhichmachineisadjusted
E Percentagerequestedbysystem
F Theactualpowerpercentageused
R e c o v e r y s i d eS e t p o i n t
45.0°CDiff. 5.0°CTemp.Outlet 8.5%Req. 39% Active 2.9%
A
B
CD
E
F
Main window - Information on DHW side heat exchanger
Unit display Index Display/Parameter
A Leavingdomestichotwatertemperature
B Temperaturewithinstoragetank
CIndicatesdomestichotwaterdemand(instepsof0to10)
D
Isshownwhentheheatrecoverypumpison.Thenum-berbelowshowswhichpumpison.Ifheatrecoveryanddomestichotwaterisenabledthepumpwillstartifthereisademandfordomestichotwater.
AR e c o v e r y s i d e
T e m p . P r o d T a n k .4 2 . 4 ° C 1 0 . 5 ° C
S e t 4 5 . 0 ° CD i f f 5 . 0 ° CR e q . 6 4 %A c t i v e 5 8 %
C
D
B
13IPOLIUY .1402. 4724311_01
MultipurposeUnit-UserManual-MainDisplay
NRP 4 PIPESBy pressing the
���
���
���
���
���
���
���
��� keys it is possible to access other displays of the main window
Main window - Information on cooling side heat exchanger
Unit display Index Display/Parameter
Fromthiswindowitispossibletoviewtheinformationrelatingtotheheatexchangeronthesystemside
A Currentworkset-point
B Evaporatorinlettemperature
C Indicatestheheatdropvalue
D Temperatureatwhichmachineisadjusted
E Percentageofproportionalfactor(ifactivatedPID)
F Percentageofintegralfactor(ifactivatedPID)
G Percentagerequestedbysystem
H Theactualpowerpercentageused
C o l d s i d eS e t p o i n t
7.0°CDiff. 5.0°CTemp.Outlet: 8.5%Ep 30% Ei 9.0%Req. 39% Active 2.9%
H
F
G
A
B
CD
E
Main window - Information on heating side heat exchanger
Unit display Index Display/Parameter
Fromthiswindowitispossibletoviewtheinformationrelatingtotheheatexchangeronthesystemside
A Currentworkset-point
B Heatexchangeroutlettemperature
C Indicatestheheatdropvalue
D Temperatureatwhichmachineisadjusted
E Percentagerequestedbysystem
F Theactualpowerpercentageused
H e a t s i d eS e t p o i n t
50.0°CDiff. 5.0°CTemp.Outlet: 8.5%Ep 30% Ei 9.0%Req. 39% Active 2.9%
F
B
CD
E
A
Main window - Information on circuits 1 - 2
Unit display Index Display/Parameter
A Showsthecircuitdemand
B Showsthecircuitstatus
C Showswhichcompressorwillstart/stop
C i r c u i t sTotal require 60%
Cirucit 1: 58% CH + RecCircuit 2: 58% Rec
Next ON 2 Circ.1 83sNext Off 1 Circ.1
BA
C
Main window - Information on DHW side heat exchanger
Unit display Index Display/Parameter
A Leavingdomestichotwatertemperature
B Temperaturewithinstoragetank
CIndicatesdomestichotwaterdemand(instepsof0to10)
D
Isshownwhentheheatrecoverypumpison.Thenum-berbelowshowswhichpumpison.Ifheatrecoveryanddomestichotwaterisenabledthepumpwillstartifthereisademandfordomestichotwater.
BH e a t s i d e
T e m p . P r o d T a n k .4 2 . 4 ° C 1 0 . 5 ° C
S e t 4 5 . 0 ° CD i f f 5 . 0 ° CR e q . 6 4 %A c t i v e 5 8 %
C
D
A
14IPOLUY .1402. 4724311_01
IN/OUT menu - Information regarding external temperature
Unit display Index Display/Parameter
7. IN/OUT MENU P1
P1
Menu IN/OUT - Information on circuit status and capacity
Display shown on the unit Index Display/Parameter
A
B
C
Temp.Min
Temp.Max
O u t d o o r t e m p .
5.7°C
Today 5.7°C 5.7°CYester 0.0°C 5.7°C
D
C i r c u i t 1Chiller + RecPros.change mode 163s
Req. 58% Active: 58%Compr.1:Compr.2:
E
AB
C
D
AExternaltemperature:thiswindowdisplaysthedatarelativetotheexternaltemperature.
BToday:indicatestheMINandMAXtemperaturerecordeddur-ingtheday.
CYesterday: indicatestheMINandMAXtemperaturerecordedthepreviousday.
DExternaltemperature:Indicatestheexternaltemperaturecur-rentlydetectedbytheoutdoorairprobe.
A
Shows the circuit operating status
• Off• Chilleronly• Chiller+Rec• Heatpump• Heatrecoveryonly• Awaitpartload• Modeselected• Defroststart
• AwaitinversionVIC• Defrost• Awaitexitdefrost• Turnonfanexitdefrost• Exitdefrost• NodefrostSystem• NodefrostRecovery
B Showshowmanysecondsuntilthenextchangeofoperation
C Showsthecircuitdemand
D
Shows the compressor status
Compressoroff
Compressoron
Min.On Compressoronandinminimumruntimer,rightwhenthiswillfinish
Min.Off Compressoronandinminimumstoptimer,rightwhenthiswillfinish
Offalarm Compressoroffduetoalarm,seeAlarmkey
E Showsthecircuitactivecapacity
15IPOLIUY .1402. 4724311_01
IN/OUT menu - Information on status of fans
Unitdisplay Index Display/Parameter
MultipurposeUnit-UserManual-IN/OUTMenu
F a n 2S p e e d
1 0 0 %S e t 1 2 . 0 b a r D i f f 5 . 0 b a rC 1 F o r z a a l m a x 5 . 0 b a rC 2 C h i l l e r + R e c
F a n 1S p e e d
1 0 0 %S e t 1 2 . 0 b a r D i f f 5 . 0 b a rC 1 F o r c e 5 . 0 b a rC 2 F o r c e 5 . 2 b a r
B
C
A
D
A
Thiswindowdisplaysthedatarelativetofanoperation.Ventilation 1: the screen is displayed if the two circuits have thesameventilation.Ventilation 2: thescreenisdisplayedifthetwocircuitshavesepa-rateventilation.
B Indicatesthespeedpercentageatwhichthefanisrotating.
C Indicatesthecurrentsetting.
D
Indicates the status in which the circuit can be found (seeMainDisplaychapter)TheMaxForcemode isactivated if the fansareoperating incon-densationandtheoutdoortemperaturedropsbelowthesetvalue(assistance/fansmenu).
C1Off Circuitoff
C1Press.Cond Fanscontroltohighpressure(condensing)
C1Chiller+RecFansoffbecauseunitisoperatinginwater/watermode
C1ForcedtoMaxFansareforcedtomaximumbecausetheexternaltemperatureishigherthan30°C
C1Press.Evap Fanscontroltolowpressure
*for NRP units
Menu IN/OUT – Informations about geothermal pump’s conditions
A Input and output temperature on geothermal side
B Speed percentage of geothermal pump
C High pressure circuit 1 and circuit 2
D Workings mode C1 and C2
PROParameters are visible only if PID is selected
INT
A
B
CD
*for NRP units
C i r c u i t 2I n . W a t e r G e o 30.7°CO u t . W a t e r G e o 30.7°C
1 0 0 %P r o . I n tC 1 E v a p . P r e s s . H P 1 2 5 . 2C 2 C h i l l e r + R e c H P 2
16IPOLUY .1402. 4724311_01
IN/OUT menu - Information on defrosting status
Unit display Index Display/Parameter
Description of defrosting statesStates Description
No SBR NodefrostOff Circuitofffromdisplaypanel,ortimeclock,ordigitalinputSbr.Attivo Defrostactive(theunitcondensesintheventilatedcoil)On Smart DefroststartedduetodropOn Min LP DefroststartedduetolowpressurereachedOn Reboot DefroststartedafterpowerlossOn Force DefroststartedforcedfromthedisplaypanelorforcedbyanotherdefrostcycleOn TGP DefroststartedduetohighdischargetemperatureEnd Liq.T DefroststoppedduetohighliquidtemperatureEnd Tempo DefroststoppedaftermaximumtimereachedEnd Force DefroststoppedforcedfromdisplaypanelStartup Cmp DefrostinhibitedduetotimeaftercompressorstartAlta P.Evap DefrostinhibitedduetohighevaporatingpressureAlta T.Ext DefrostinhibitedduetohighexternaltemperatureT.Bw Sbr DefrostinhibitedduetodelaytimerbetweentwodefrostcyclesAllarmi CircuitinalarmOn da Alarm Defroststartedduetoreturntoalarm
A
B
D e f r o s tC i r c u i t 1 A l a r m sO f fL P 5 . 4 b a r D e l t a 0 . 0
C i r c u i t 2 A l a r m sO f fL P 5 . 4 b a r D e l t a 0 . 0
C
D
MultipurposeUnit-UserManual-IN/OUTMenu
AShowsthedefroststatusofcircuits1and2see(1) Description of defrost status
BShowsifthedefrostmodeisoperating
C
Shows the circuit operating status
• Off• Chilleronly• Chiller+Rec• Heatpump• Heatrecoveryonly• Awaitpartload• Modeselected• Defroststart
• AwaitinversionVIC• Defrost• Awaitexitdefrost• Turnonfanexitdefrost• Exitdefrost• NodefrostSystem• NodefrostRecovery
D
Showsactualsetpointvalue.The Delta value shows the drop in pressurewith time.When thislevelisreachedthedefrostoperatingcycleisstarted
17IPOLIUY .1402. 4724311_01
IN/OUT menu - Indicates the status of the circuit 1 and circuit 2 valves
Unit display Index Display/Parameter
A
Thiswindowdisplaysthedatarelativetocircuitpressuresandvalvestatus.
B Displays the status of the compressors (disabled - on - off -alarm).
C Indicatesthehighandlowpressurevaluesofthecircuit.
D
Indicatestherefrigerantliquid(LiqT)andpressinggas(Tgp)temperature.
E
Indicatesthevalvestatus:VIC-CycleReversingValve.VIR-RecoveryReversingValve.
F
vs1:liquidintercept.solenoidvalve.v1a:liquidintercept.solenoidvalve.vsB:batterysolenoidvalve.vsR:recoverysolenoidvalve.vsE:evaporatorsolenoidvalve.By:defrostspillingvalve.
GIndicatesspeedpercentageatwhichthefanworks.
ON OFF
ON OFF
MultipurposeUnit-UserManual-IN/OUTMenu
C i r c u i t 2C H
H P 2 6 . 7 b a r F a n 8 8 %L P 2 . 4 b a rL i q T 4 0 . 7 ° C v i c v i r
v s 1 v 1 a v s B v s R v s E B y
C i r c u i t 1C H
H P 2 6 . 7 b a r F a n 8 8 %L P 2 . 4 b a rL i q T 4 0 . 7 ° C v i c v i r
v s 1 v 1 a v s B v s R v s E B y
A GE
B
D
C
F
18IPOLUY .1402. 4724311_01
ON/OFF menu - Unit switch-on/off and settings on the functioning mode
Unit display Index Display/Parameter
A Unit On/Off:thedatarelativetothestatusoftheunitanditsfunctioningmodearesetinthiswindow.
BFORthedescriptionoftheunitstatusseeCHAPTER 6 - Main Display - Description of the status in which the unit can be found.
C General ON/Offstatus,enabledbyuser.
ON/OFF menu - Unit switch-on/off and settings on the functioning mode
Unit display Index Display/Parameter
A Unit On/Off:thedatarelativetothestatusoftheunitanditsfunctioningmodearesetinthiswindow.
BFORthedescriptionoftheunitstatusseeCHAPTER 6 - Main Display - Description of the status in which the unit can be found.
C General ON/Offstatus,enabledbyuser.
8. ON/OFF MENU P1
P1NRP 2 PIPES
NRP 4 PIPES
O n / O f f U n i tP l a n t s i d e
O f f t o c l o c kR e c o v e r y s i d e
O f f t o c l o c k
G e n e r a l e a b l e : Y E S
A
C
B
O n / O f f U n i tC o l d s i d e
O f f f o r A l a r mH e a t s i d e
O f f f o r A l a r m
G e n e r a l e n a b l e : Y E S
B
A
C
ATTENTIONNRP 2-pipe system - Deactivated system /Off: also the recovery side is excludedNRP 4-pipe system - Deactivated Cool Side /Off: also the heating side is excluded
19IPOLIUY .1402. 4724311_01
9. PLANT (2 PIPES)SYSTEM menu - System set-point display
Unit display Index Display/Parameter
A Displays the current settings of the chiller.
B
NO:Thesystemdoesnotproducecold/hotwater,recoveryismanagedseparately. Yes:theunitisrunningandthesystemisadjustedatthedefaultset-point.Yes with set2: theunitisrunningandthesystemisadjust-edatthesecondset-point.BY CLOCK: thesystemisadjustedbythesettimeperiods,whenactive.
C
MODE selection:BY SUPERV:theunitismanagedbyremotecontrolviatheBMSsystem.BY DIG INPUT: ifthedigitalcontact(auxiliarydevice)closes,theheatingmodeisactivated.BY EXT TEMP.:coolingorheatingmodeisselecteddepend-ingontheexternaltemperature.BY CALENDAR: theunitproduceshotwaterdependingontheperiodset.HEATING: theunitproduceshotwater.COOLING: theunitproducescoldwater.
P1
P1
SYSTEM menu - System set-point display
Unit display Index Display/Parameter
A Displaysset-point2(onlyifenabled)
B Indicatestheset-pointsforproductionofcoldwater.
C Indicatestheset-pointsforproductionofhotwater.
SYSTEM menu - System set-point display
Unit display Index Display/Parameter
A Displaysthecurrentsettingsofthechiller.
B Indicatesthecoldwaterproductionset-point.
C Indicatesthehotwaterproductionset-point.
P l a n t s i d e
S e t p o i n t 1
7 . 0 ° C4 5 . 0 ° C
A
B
C
I m p i a n t o
O F F t o c l o c k
S w i t c h O N :B Y C L O C K
M O D E S E L E C T I O NB Y C A L E N D A R
A
B
C
P l a n t s i d e
S e t p o i n t 2
1 2 . 0 ° C4 0 . 0 ° C
A
B
C
20IPOLUY .1402. 4724311_01
SYSTEM menu - Enabling: BY CLOCK
Unit display Index Display/Parameter
A Indicatesthedayoftheweek.
BIndicateswhethertheunitisonoroff.
C
Indicatesthetimeperiodsofthedayandcansetunitswitch-onandswitch-off.SEL - ITispossibletoselect,fortherelativetimeperiod,whethertoleavetheunitOFForON,usingthedefaultset-pointorthesecondset-point(Set2).
D Indicatesthedaywiththesettingstobecopied.
E
Indicatesthedaywherethesettingsmustbecopied.Thesettingsmaybecopiedonasingledayoronalldays.No=disablesthedaysettingcopyfunctionYes=enablesthedaysettingcopyfunction
ATTENTION: Each program has 8 days and each day is divided into 4 time periods at which the recov-ery switch-on and switch-off time, set-point2 or switch-on/switch-off can be set. ATTENTION: outside of the 4 time periods the program will switch the system off.
�
MultipurposeUnit-UserManual-SystemMenu(2pipes)
ON (SET 1) ON (SET 1)SET 2 SET 2
a-ON a-OFF b-ON b-OFF c-ON c-OFF d-ON d-OFF00:00 24:00
P l a n t s i d e
D A Y M O N D A Y
O N O F F S E L
c : 0 : 0 0 : 0 S e t 2
d : 0 : 0 0 : 0 O N
P l a n t s i d e
D A Y M O N D A Y
O N O F F S E L
a : 8 : 0 1 2 : 0 O F F
b : 1 6 : 0 2 2 : 0 O N
CB
A
P l a n t s i d e
T i m e z o n e
D A Y M O N D A Y
C o p y t o A L L N o
D
E
21IPOLIUY .1402. 4724311_01
SYSTEM menu - Mode Selection: EXTERNAL TEMPERATURE
Unit display Index Display/Parameter
ASetstheexternaltemperatureatwhichtheunitmustbeacti-vatedincoolingmode.
BSetstheexternaltemperatureatwhichtheunitmustbeacti-vatedinheatingmode.
SYSTEM menu - Mode Selection: BY CALENDAR
Unit display Index Display/Parameter
ASetsthestartingdateoftheperiodatwhichtheheatingunitcanbeactivated.
BSetsthefinaldateoftheperiodatwhichtheheatingunitcanbedeactivated.
MultipurposeUnit-UserManual-SystemMenu(2pipes)
C o o l i n g / H e a t i n g
S e l e c t C o o l / H e a t w i t hC a l e n d a r
S t a r t H e a t i n g 0 / - - -F i n i s h H e a t i n g 0 / - - -
A
B
C o o l i n g / H e a t i n g
S e l e c t C o o l / H e a t w i t hE x t e r n a l T e m p e r a t u r e
S e t O N H e a t i n g 2 6 ° CS e t O N C o o l i n g 0 7 . 0 ° C
A
B
22IPOLUY .1402. 4724311_01
RECOVERY menu - Recovery set-point display
Unit display Index Display/Parameter
A Displays the current settings of the heat exchanger.
B
YES:theunitdoesnotproducehotwaterforDHWuse.NO:theunitisrunningandthesystemisadjustedatthedefaultset-point.BY CLOCK: thesystemisadjustedbythesettimeperiods,whenactive.Yes with set2: theunitisrunningandthesystemisadjustedatthesecondset-point.
E - C
R - E
E V C N
R E
1 2
1 2
F
F
LT
HTRECOVERY menu - Recovery set-point display
Unit display Index Display/Parameter
A Displaysthecurrentsettingsofthechiller.
BDisplaystheheatexchangeroutletwatertemperatureatthedefaultset-point.
CDisplaystheheatexchangeroutletwatertemperatureatthesecondset-point.
10. RECOVERY MENU (2 PIPES)
WARNING
− The NRP - 2-pipe unit è is set up for production of Domestic Hot Water (D.H.W.).− No Anti-legionella Cycle is included.
�
R e c o v e r y s i d e
O f f t o c l o c kE x t e r n a l t e m p e r a t u r e
E n a b l e :S I
A
B
R e c o v e r y s i d e
S e t p o i n t 1 : 4 5 . 0 ° CS e t p o i n t 2 : 4 5 . 0 ° C
A
B
C
23IPOLIUY .1402. 4724311_01
COOLING menu - Display of cooling side heat exchanger set-point
Unit display Index Display/Parameter
A Displaysthecurrentsettingsofthechiller.
B Indicatesthatthesystemdefaultset-pointisactive.
C Indicatesthecoolingset-pointtemperature.
COOLING menu - Display of cooling side heat exchanger set-point
Unit display Index Display/Parameter
A Displays the current settings of the chiller.
B
NO:thesystemdoesnotproducecold/hotwaterYes: the unit is running and the system is adjusted at thedefaultset-pointYes WITH SET2: theunitisrunningandthesystemisadjust-edatthesecondset-pointBY CLOCK: the system is adjustedby the set timeperiods,whenactive.
WARNING To set the time periods, see the chapter relative to system menu (2 pipes)enabling: by clock.
�
Menù FREDDO - Visualizzazione set point scambiatore lato freddo
Visualizzazione sul display dell’unità Indice Visualizzazione/Parametro
A Displaysthecurrentsettingsofthechiller.
B Indicatesthatthesystemdefaultset-pointisactive.
C Indicatesthecoolingset-pointtemperature.
11. COOL MENU (4PIPES) P1
P1
C o l d s i d eO F F f o r A l a r m
E n a b l e :B Y C L O C K
A
B
C
C o l d s i d eS e t p o i n t 1
7 . 0 ° C
A
B
C
A
C o l d s i d eS e t p o i n t 2
1 2 . 0 ° CB
C
24IPOLUY .1402. 4724311_01
12. HEAT MENU (4 PIPES)
HEATING menu - Display of heating side set-point
Unit display Index Display/Parameter
A Displays the current settings of the heat exchanger.
B
NO:theunitdoesnotproducehotwateronsystemside.YES:theunitisrunningandthesystemisadjustedatthedefaultset-point.BY CLOCK: thesystemisadjustedbythesettimeperiods,whenactive.Yes with set2: the unit is running and the system isadjustedatthesecondset-point.
RECOVERY menu - Display of heating side set-point
Unit display Index Display/Parameter
A Displaysthecurrentsettingsofthechiller.
BDisplaystheheatexchangeroutletwatertemperatureatthedefaultset-point.
CDisplaystheheatexchangeroutletwatertemperatureatthesecondset-point.
ATTENTION The NRP - 4-pipe unit is set up for production of Domestic Hot Water (D.H.W.).�
A
B
H e a t s i d e
O f f t o C l o c kE x t e r n a l T e m p e r a t u r e
S w i t c h O n :Y E S
H e a t s i d e
S e t p o i n t 1 : 4 5 . 0 ° CS e t p o i n t 2 : 4 5 . 0 ° C
A
C
B
25IPOLIUY .1402. 4724311_01
Clock Menu - System time and date settings
Unit display Index Display/Parameter
ADisplaysthedayoftheweek(itcannotbechangedfromthiswindow).
B THEdateofthesystemcanbemodified.
C THEtimeofthesystemcanbemodified.
Clock Menu - Daylight saving time settings
Unit display Index Display/Parameter
AClock: thedaylightsavingtimesettingsaredisplayedinthiswindow.
BDay-light saving time: thisparameterindicateswhethertoenableadjustmentofsystemtimebasedonthedate,accordingtothesubsequentsettings.
C
Transition time: Thisparameterindicateshowmuchthesystemtimemustbeincreasedordecreasedbasedontimechange(dependingonwhetheritisthestartorfinishofday-lightsavingstime).
D
Start of daylight saving time use: thisparameterindicateswhichdayofthemonthyoumuststarttousedaylightsavingtime;inordertospecifythis,youmustsettwopartsofthesameparameter,thefirstindicatingtheweek(first,second,thirdorlast),thesecondindicatingthedayoftheweek.
EStart month: thisparameterindicatesthemonthinwhichtostarttousethedaylightsavingtimesetting.
FStart time: thisparameterindicatesthetimeinwhichtostarttousethedaylightsavingtimesetting.
G
End of daylight saving time use: thisparameterindicateswhichdayofthemonthyoumustquitusingdaylightsavingtime;inordertospecifythis,youmustsettwopartsofthesameparameter,thefirstindicatingtheweek(first,second,thirdorlast),thesecondindicatingthedayoftheweek.
HEnd month: thisparameterindicatesthemonthinwhichtoquitusingthedaylightsavingtimesetting.
IEnd hour: thisparameterindicatesthetimeinwhichtoquitusingthedaylightsavingtimesetting.
13. CLOCK MENU
E - C
R - E
E V C N
R E
1 2
1 2
F
F
LT
HT
C l o c kA u t o m a t i c c h a n g eH o u r s o l a r / l e g a l Y E STr a n s i t i o n T i m e : 1 hS t a r t : L A S T S U N D AYi n M A R C H a t 0 2 . 0 0E n d : L A S T S U N D AYi n O C T O B E R a t 0 3 . 0 0
CDE F
IGH
B
A
C l o c k
D a y : T u e s d a y
T i m e : 3 M a y . 2 0 1 1
H o u r : 1 4 : 0 4
A
B
C
26IPOLUY .1402. 4724311_01
CLOCK menu - Setting the calendar function
Unit display Index Display/Parameter
MultipurposeUnit-UserManual-ClockMenu
C a l e n d a rS t a r t F i n i s h A c t i o n0 1 / J A N . 0 6 / F E B O F F0 5 / J A N . 0 8 / F E B H O L . 0 / - - - 0 / - - - - - - 0 / - - - 0 / - - - - - - 0 / - - - 0 / - - - - - -
B
E
C DA
F G
A
Calendar: thiswindowsetstheactionstobecarriedoutinthecal-endarfunction;thisfunctionallowsyoutoset5periods,specifyingthelengthindays,andtoconnectaspecificactiontobecarriedouttoeachoneofthem.
B Start: Indicatesthestartdateforthe5periodsthatcanbeset.
C End: Indicatestheenddateforthe5periodsthatcanbeset.
DAction: indicates the action to be carried out for each of the 5periodssetinthecalendar.
ETime periods start date: theseparametersspecifythestartingdate(day/month)foreachperiod;ifyouset00/00asthestartandendvalue,thisperiodwillbedisabled.
FTime periods end date: these parameters specify the end date(day/month)foreachperiod;ifyouset00/00asthestartandendvalue,thisperiodwillbedisabled.
G
Actions set for the time periods: these parameters specify theaction to be carried out corresponding to the set periods; theactionscanbe:•Off(unitswitch-offduringtheperiodselected);•Fest(foreachdayoftheperiodselected,settingsrelativetothetimeperiodsspecifiedforthe"HOLIDAY"willbecarriedout);•---(noaction).
27IPOLIUY .1402. 4724311_01
ALARMS Menu
Unit display Index Display
14. ALARMS MENUEverytimeanalarmisgenerated,itissavedinanareaofmemorycalled “alarms log”,whichcontains the last 100 alarms recorded in theunit.Foreveryalarmsaved,different informa-tionisrecordedregardingtheunitsituationatthat time (work temperatures and pressures),so that the technicalafter-salesstaffcanhaveaclearviewoftheunitwhenagivenalarmoc-
curs.Toaccessthealarmslog:(a)pressthekey(
���
���
)andenterthealarmsdis-play;(b) if they are present, scroll all active alarmsusingthe(���
���
)keyandreachtheiconthatindi-catestheactivationofthealarmslog;(3)pressthekey(���
���
)toenterthealarmslog;
(4)toexitthealarmslog,press( ���
���
)or(
���
��� ).���
���
���
���
���
���
���
���
���
���
A l a r m A L 0 5H i g h p r e s s u r e s e n s o rc i r c u i t 1b r o k e n o r n o t c o n n e c t
A c t i v e a l a r m s : 1 5
A
B
DC
A Alarm code:thisparameterindicatesthealarmcode.Thiscodecanbefoundinthepreviouspages(alarmssummarytable).
B Alarm description: thisparameter indicatesthedescriptionofthealarmsaved.
CAlarm number: this value indicates the progressive numberassignedtothealarm;thisvaluegoesfrom0(firstalarrecorded)to99(lastalarmrecorded).
D Indicatesthepossibilityofscrollingthedisplaysofthevariousactivealarmssignalledbypressingthekeys.
28IPOLUY .1402. 4724311_01
�
ATTENTION: the alarms log display always starts from the latest alarm generated. To navigate through the alarms saved, use the (
���
���
) and (���
��� ) arrow keys.
THE ALARMS LOG CANNOT BE RESET and as the memory available is suitable to contain 100 alarms, once the index has reached the value of 99, its increase will start from 00 again (over-writing the oldest alarm).
15. ALARMS LOG MENU
E - C
R - E
E V C N
R E
1 2
1 2
F
F
LT
HT
ALARMS Menu - Alarms LogUnit display Index Display/Parameter
AByusingthekeys
���
���
���
���
���
���
���
��� toscrollinsidethealarmsmenu,youaccesstheindicatedscreenfromwhenceit ispossibletoenterthealarmslogMENU.
B
Thefollowingdescriptionsarepossibleforeachalarm:-Dateandtimeoftriggering-Natureofalarm-Systemsideinput/outputtemperature:-Recoveryinput/outputtemperature-Statusofcompressors-Lowpressure-Statusofunit-Statusofcompressors-Statusofpumps-Highpressure
TYPE OF REARMINGAUTO= automatic, the alarm is rearmed automatically as the event which generated it ceases.
SEMI = semiautomatic, the alarm is rearmed automatically, but if the event that generated it repeats itself more than 3 times in one hour, it must be rearmed manually.
MAN = manual, the alarm is only rearmed by means of the manual control.
� ATTENTION: keep the
���
���
button pressed to rearm the alarm manually.
B
A l a r m
P u s h k e y E N T E Rt o g o H I S T O R Y a l a r m
8 : 2 2 2 9 / 3 / 1 1 N ° 0 0 3
A L 3 3 R e c o v e r y anti-freezeTe m p O u t l e t I n O u tP l a n t 1 5 . 7 ° C 2 4 . 5 ° CR e c o v. 0 . 0 ° C 0 . 0 ° C
C 1 : O F FC 2 : O F F
8 : 2 2 2 9 / 3 / 1 1 N ° 0 0 3
A L 7 6 H i g h t e m p .T G Pc i r c u i t 2 L P b a r H P b a rC i r c 1 8 . 3 1 2 . 5C I r c 2 4 . 0 1 4 . 7P l a n t 1 0 0 %R e c o v. 7 0 %
A
29IPOLIUY .1402. 4724311_01
16. ALARMS LISTCode Log Text Note Delay Manual Reset
AL01 Clockbatterydischargederror Yes
AL02 Flashmemoryerror Yes
AL03 ID8phasemonitor
AL04 Automaticrestartafterpowersupplycutoff notalarm
AL05 Circ1highpressurebrokenordisconnected B1 30s
AL06 Circ2highpressurebrokenordisconnected B6 30s
AL07 Circ1lowpressurebrokenordisconnected B2 30s
AL08 Circ2lowpressurebrokenordisconnected B7 30s
AL09 EvapIn.Temp.brokenordisconnected B4 30s
AL10 EvapOut.Temp.brokenordisconnected B3 30s
AL11 EvapOut.Temp.brokenordisconnected B3uPC 30s
AL12 Rec.In.Temp.brokenordisconnected B1uPC 30s
AL13 Rec.1Out.Temp.brokenordisconnected B2uPC 30s
AL14 Rec.2Out.Temp.brokenordisconnected B6uPC 30s
AL15 Com.Out.Rec.Temp.brokenordisconnected B4uPC 30s
AL16 ExternalAirTempbrokenordisconnected B9 30s
AL17 NRP Circ1LiquidTempbrokenordisconnected 30s
AL17 NXP Geothermalinput’stemperatureprobeisbrokenornotconnected 30s
AL18 NRP Circ2LiquidTempbrokenordisconnected 30s
AL18 NXP Geothermalinput’stemperatureprobeisbrokenornotconnected 30s
AL19 Circuit1Comp.1maintenance Yes
AL21 Circuit1Pump1Rec.maintenance Yes
AL22 Circuit1Pump1systemmaintenance Yes
AL23 Circuit1Compres.1overload Yes
AL24 ID13Pump1systemoverload ID6 Yes
AL25 ID14Pump2systemoverload Yes
AL26 Pump1rec.overload Yes
AL27 Pump2rec.overload Yes
AL28 NRP ID15Fan1overload Yes
AL28 NXP Geothermalinput’stemperatureprobeisbrokenornotconnected Yes
AL29 ID16Fan2overload Yes
AL30 Circuit1LP1pressureswitch 180s+3s“M48” Semiautomatic
AL31 Lowpressureprobe Semiautomatic
AL32 HP1pressureswitchbydigitalinput Yes
AL33 Highpressure1byprobe Yes
AL34 Lowpressure1byprobe(serious) Yes
AL35 Lowpressure2byprobe(serious) Yes
AL36 Circ1preventionbyprobe ---
AL37 Circ2preventionbyprobe ---
AL38 Syst.flowmeter Semiautomatic
AL39 Rec.flowswitch Semiautomatic
AL40 Evap.outputtempsystemanti-freeze 3°C“Ma9”
AL41 Evap.outputtempcom.systemanti-freeze 3°C“Ma9”
AL42 Outputtemprecovery1anti-freeze 3°C“Ma12”
30IPOLUY .1402. 4724311_01
MultipurposeUnit-UserManual-AlarmsList
Code Log Text Note Delay Manual Reset
AL43 Outputtemprecovery2anti-freeze 3°C“Ma12”
AL44 Outputtempcom.rec.anti-freeze 3°C“Ma12”
AL45 ExpansionIO(uPC)OffLine 20s
AL46 ExpansionIO(pCOe)OffLine 20s
AL48 Circ.1highdischargetemperaturebrokenordisconnected 30s
AL49 Circ.2highdischargetemperaturebrokenordisconnected 30s
AL50 Automaticrestartafterpowersupplycutoff notalarm
AL51 Circuit1Comp.2maintenance Displayonly “W18”
AL52 Circuit1Comp.3maintenance Displayonly W18”
AL53 Circuit2Comp.1maintenance Displayonly W18”
AL54 Circuit2Comp.2maintenance Displayonly W18”
AL55 Circuit2Comp.3maintenance Displayonly W18”
AL56 Circuit2Fanmaintenance Displayonly W18”
AL57 Circuit1Pump2Rec.maintenance Displayonly W18”
AL58 Circuit1Pump2syst.maintenance Displayonly W18”
AL59 Circuit1Compres.2overload Yes
AL60 Circuit1Compres.3overload Yes
AL61 Circuit2Compres.1overload Yes
AL62 Circuit2Compres.2overload Yes
AL63 Circuit2Compres.3overload Yes
AL64 LP2pressureswitch 180s+3s“M48” Semiautomatic
AL65 Lowpressure2byprobe Semiautomatic
AL66 Highpressure2bypressureswitch Yes
AL67 Highpressure2byprobe Yes
AL68 Circ.1lowpressureprevention
AL69 Circ.2lowpressureprevention
AL70 ---
AL71 NRP Recovery2outputanti-freeze 3°C“Ma12”
AL71 NXP Forcingoffrecovery2
AL72 NRP Rec.commonoutputanti-freeze 3°C“Ma12”
AL72 NXP Forcingoffcommonrecovery
AL73 Circuit1TGPprevention “Ma39”
AL74 Circuit2TGPprevention “Ma39”
AL75 Circ.1highdischargetemperature “Ma54”
AL76 Circ.2highdischargetemperature “Ma54”
AL78 Defrostonsystemnotavailable
AL79 Defrostonrecoverynotavailable
AL80 AlarmOfflineMasterboarddisconnected
AL81 AlarmOfflineNRP2boarddisconnected
AL82 AlarmOfflineNRP3boarddisconnected
AL83 AlarmOfflineNRP4boarddisconnected
AL84 Alarmhightemperature-Systeminlet Semiautomatic
AL85 Alarmhightemperature-Recoveryinlet Semiautomatic
AL86 Forzaturaoffcaldocircuito1 Semiautomatico
AL87 Forzaturaoffcaldocircuito2 Semiautomatico
AL88 Forzaturaofffreddocircuito1 Semiautomatico
AL89 Forzaturaofffreddocircuito2 Semiautomatico
AL90
AL91 Allarmeflussostatogeotermico
AL92 Allarmeantigelogeotermico
31IPOLIUY .1402. 4724311_01
17. INPUTS/OUTPUTS LIST
DIGITAL OUTPUTS MASTER
NO1 CP1(compressor)circuit1(CC1)
NO2 CP2(compressor)circuit1(CC1A)
NO3 CP1(compressor)circuit2(CC2)
NO4 CP2(compressor)circuit2(CC2A)
NO5 VS1(liquidinterceptionsolenoidvalve)circuit1
NO6 VS2(liquidinterceptionsolenoidvalve)circuit1
NO7(exchange) Evaporatorpump1
NO8 Seriousalarm
NO9 Evaporatorpump2
NO10 Condenserfan1
NO10 Geothermalpump
NO11 Condenserfan2
NO12 VIC1(cyclereversingvalve)
NO13 VIR1(recoveryreversingvalve)
NO14 VIC2(cyclereversingvalve)
NO15 VIR2(recoveryreversingvalve)
NO16 Anti-freezeresistance
NO17 VS1(liquidinterceptionsolenoidvalve)circuit2
NO18 VS2(liquidinterceptionsolenoidvalve)circuit2
DIGITAL INPUTS MASTER
ID1 Highpressurecircuit1
ID2 Lowpressurecircuit1
ID3 RemoteOn-Off
ID4 Remoteheating/cooling
ID5 Evaporatorflowswitch
ID6 Circuit1circuitbreakerCP1(MT1)
ID7 Circuit1circuitbreakerCP2(MT1A)
ID8 Phasemonitoralarm
ID9 Highpressurecircuit2
ID10 Lowpressurecircuit2
ID11 Circuit2circuitbreakerCP1(MT2)
ID12 Circuit2circuitbreakerCP2(MT2A)
ID13 Evaporativepump1circuitbreaker
ID14 Evaporativepump2circuitbreaker
ID15 Fan1circuitbreaker
ID15 Circuitbreakerofgeothermalpump
ID16 Fan2circuitbreaker
ID17 Geothermalflowswitch
ID18 Multi-functioninputenabling
17.1. INPUTS/OUTPUTS LIST - PCO3 LARGE BOARD
32IPOLUY .1402. 4724311_01
ANALOGUE OUTPUTS MASTER
Y1(0-10V)
Y2(0-10V) Evaporatormodulatingpump
Y3(0-10V) NRP Modulating1fan
Y3(0-10V) NXP Geothermal modulating pump
Y4(0-10V) Modulating2fan
ANALOGUE INPUTS MASTER
B1 Highpressurecircuit1
B2 Lowpressurecircuit1
B3 Evaporatorwateroutlettemperature
B4 Evaporatorwaterinlettemperature
B5 Pressinglinegastemperature(PT1000)Circuit1
B6 Highpressurecircuit2
B7 Lowpressurecircuit2
B8 Multi-functioninput
B9 Externalairtemperature
B10 Pressinglinegastemperature(PT1000)Circuit2
MultipurposeUnit-UserManual-Inputs/OutputsList-pCO3LARGEBOARD
� ATTENTION: The basic configuration includes a pCO3 large board. In addition a series of accessories can be managed through a µPC board.
pCO3 LARGE BOARD
Rx-/
Tx-
Rx+
/Tx+
GN
D C1
NO
1
NO
2
NO
3
C1 C4
NO
4
NO
5
NO
6
C4 C7
NO
7
C7
NO
8
C8
NC8
G G0
B1 B2 B3 GND
+V
DC
+V te
rm
GND
+5
VREF
B4 BC4
B5 BC5
VG VG0
Y1 Y2 Y3 Y4 ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
J1 J24 J2 J3 J4 J5
J14J11
J10J9
J13J12 J15
�eld card serial cardinput: 24 V / ; 50 to 60 Hzmax. power: 40 VA /15W
33IPOLIUY .1402. 4724311_01
DIGITAL OUTPUTS Master
NO1 Recoverypump1
NO2 Recoverypump2
NO3 CP3circuit1(CC1B)
NO4 CP3circuit2(CC2B)
NO5 VS-R(recoverysolenoidvalve)circuit1
NO6 VS-R(recoverysolenoidvalve)circuit2
NO7(exchange) VS-B(batterysolenoidvalve)circuit1
NO8 VS-B(batterysolenoidvalve)circuit2
NO9 VS-E(evaporatorsolenoidvalve)circuit1
NO10 VS-E(evaporatorsolenoidvalve)circuit2
NO11 VBY(bypasssolenoidvalve)circuit1
NO12 VBY(bypasssolenoidvalve)circuit2
DIGITAL INPUTS
ID1 Recoveryflowswitch
ID2 Recoverypump1circuitbreaker
ID3 Recoverypump2circuitbreaker
ID4 Circuit1circuitbreakerCP3(MT1B)
ID5 Circuit2circuitbreakerCP3(MT2B)
ID6 On/Off remote D.H.W. /Hot water
ID7 Qualify according to setpoint D.H.W.
ID8
ID9
ID10
ANALOGUE OUTPUTS
Y1(0-10V)
Y2(0-10V)
Y3(0-10V)
Y4(0-10V)
ANALOGUE INPUTS
B1(NTC) Recoveryinletwatertemperature
B2(NTC) Recovery1outletwatertemperature
B3(NTC) Evaporatorcommonoutletwatertemperature(Master/Slave)
B4(NTC) Recoverycommonoutletwatertemperature(Master/Slave)
B5(NTC;NTCHT;0-1V;4-20mA)
B6(NTC) Recovery2outletwatertemperature
B7(NTC) NXP Liquidtemperature(defrostend)Circuit1
B7(NTC) NXP Geothermal’s input water temperature (end of defrosting) Circuit 1
B8(NTC)
B9(NTC;NTCHT;)
B10(NTC) NRP Liquidtemperature(defrostend)Circuit2
B10(NTC) NXP Geothermal’s output water temperature
B11(0-5V)
B12(0-5V)
17.2. µPC BOARD
MultipurposeUnit-UserManual-Inputs/OutputsList-µPCBOARD
34IPOLUY .1402. 4724311_01
MultipurposeUnit-UserManual-Inputs/OutputsList-µPCBOARD
C4
NO8
NO9
NO10
NO11
NO12
RX-/TX-RX+/TX+GND
VoutRX-/TX-RX+/TX+GND
C1
NO1
NO2
NO3
C2
NO4
NO5
NO6
NO7
C3
NC7
G
G0
B1
B2
B3
B4
B5
B6
B7
GND
+Vdc
+Vdc
GND
+5 Vref
GND
Y1
Y2
Y3
Y4
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DIC1
B8
B9
B10
B11
B12
GND
ID8
ID9
ID10
IDC2
J2 - probe supply
J3 - analog input
J4 - digital input
J5 - analog output
J18 - analog input
J17 - valve 2
J16 - digital input
J6
J7
J8
J9
J10
J11
J12 - group 1
J13 - group 1
J14 - group 2
J15 - group 3
J1 - power supply
µPC BOARD
35IPOLIUY .1402. 4724311_01
carta riciclatarecycled paperpapier recyclérecycled Papier