BUILDING DESIGN AND ENGINEERING APPROACHES TO AIRBORNE INFECTION CONTROL AUGUST 3 – 14, 2009 – Harvard School of Public Health Natural Ventilation for Infection Control in Health Care Settings: Mixed Mode Hal Levin Building Ecology Research Group Santa Cruz, California 1

Upload: builien

Post on 28-Aug-2018

238 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

BUILDING DESIGN AND ENGINEERING APPROACHESTO AIRBORNE INFECTION CONTROL

AUGUST 3 – 14, 2009 – Harvard School of Public Health

Natural Ventilation for Infection Control in Health Care

Settings:

Mixed Mode

Hal LevinBuilding Ecology Research Group

Santa Cruz, California 1

Page 2: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

22

IEA Annex 35 -- HybVent Buildings

Page 3: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

3

Shares of Non-ResidentialBuilding Energy Use

0% 5% 10% 15% 20% 25%

Percent of non-residential total

Office

Warehouse/Storage

Mercantile

Education

Public Assembly

Lodging

Service

Health Care

Food Service

Public Order/Safety

Food Sales

Vacant

Other

Primary Energy Use

Total Floorspace

Healthcare

Page 4: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

44

Natural and Mixed Mode Ventilation Mechanisms

Courtesy of Martin Liddament via Yuguo Li

Mixed Mode Ventilation

Sketch of school systemSketch of B&O Building

Natural Ventilation

Cross Flow Wind

Mixed Mode Ventilation

Wind Tower Stack (Flue) Stack (Atrium)

Fan Assisted Stack

heated/cooledpipes

heated/cooledceiling void

Top Down Ventilation

chilled pipes

Buried Pipes

Page 5: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

5

Main Hybrid Ventilation Principles

• Natural and mechanicalventilation

• Fan-assisted natural ventilation

• Stack and wind-assisted mechanical ventilation

Page 6: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

6

Ventilation for Indoor Air Quality Control

• When optimizing ventilation for indoor air quality control, the challenge is to achieve an optimal equilibrium between indoor air quality, thermal comfort, energy use and environmental impact during periods of heating and cooling demands.

Page 7: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

7

Pollutant concentration as a function of outdoor air exchange rate

0

1

2

3

4

5

6

7

8

0 1 2 3 4 5Ventilation air changes per hour (ach)

Con

cent

ratio

n (µ

g/m

3 )

EF = 1 µg/m2•hr

EF = 5 µg/m2•hr

EF = 10 µg/m2•hr

Page 8: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

The relationship between infection risk, and the ventilation rate and the quanta generation. The unit of quanta generation is quanta per hour

Qian et al, 2010, Building and Environment 45: 559–565

8

Page 9: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

9

Impact of ventilation rate on infection rate(Nardell et al, 1991, Am Rev Resp Dis)

Page 10: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

1010

Decay of droplet nuclei concentration in an isolation room for different ventilation rates and duration of time

Ventilation rate Time (minutes)

6 ACH 9 ACH 12 ACH 15 ACH 18 ACH 21 ACH 24 ACH

0 100.00% 100.00% 100.00% 100.00% 100.00% 100.00% 100.00%

5 60.65% 47.24% 36.79% 28.65% 22.31% 17.38% 13.53%

10 36.79% 22.31% 13.53% 8.21% 4.98% 3.02% 1.83%

15 22.31% 10.54% 4.98% 2.35% 1.11% 0.52% 0.25%

20 13.53% 4.98% 1.83% 0.67% 0.25% 0.09% 0.03%

25 8.21% 2.35% 0.67% 0.19% 0.06% 0.02% 0.00%

30 4.98% 1.11% 0.25% 0.06% 0.01% 0.00% 0.00%

35 3.02% 0.52% 0.09% 0.02% 0.00% 0.00% 0.00%

40 1.83% 0.25% 0.03% 0.00% 0.00% 0.00% 0.00%

45 1.11% 0.12% 0.01% 0.00% 0.00% 0.00% 0.00%

50 0.67% 0.06% 0.00% 0.00% 0.00% 0.00% 0.00%

60 0.25% 0.01% 0.00% 0.00% 0.00% 0.00% 0.00%

Page 11: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

Conclusions(Qian et al, Building and Environment, 2010)

11

“… field measurement study …performance of natural ventilation in a TB hospital and an outpatient clinic…possibility of using natural ventilation for infection control. …measured ventilation rate …found to be much higher than the CDC recommended 12 ACH for isolation rooms. However, when all …openings are open, …pressure difference between …corridor and …ward and …between …ward and outdoor << 1 Pa, and cannot be measured by conventional equipment. … observed airflow direction through an open door or window can be unstable during the measurement when the wind is weak.[M]echanical exhaust fans installed can create negative pressure. When all …openings were closed and fans …turned on, …ventilation rate was as high as 12.6 ACH and pressure difference between ward and corridor was also high. [M]easured results indicate NatVentilated ward may be converted to an isolation room by installing exhaust fans when natural forces are not sufficiently strong. [C]onfirmed: natural ventilation could provide a high ventilation rate, especially when all the openings in the ward were fully open. The high ventilation rate is expected to reduce the risk of cross-infection.

Page 12: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

12

IAQ-Energy Trade-off

Page 13: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

1313

Local ventilation - exhaust

Design Drawing Prototype in the test room

Page 14: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

14

ACH can be misleading?

V=10 m3 V=10 m3

V=30 m3

V=10 m3

q=30m3/h

q=1 ach

q=30m3/h

q=1 ach

Page 15: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

15

Ventilation for Temperature Control

• When optimizing ventilation as a natural cooling strategy, the challenge is to achieve an optimal equilibrium between cooling capacity, cooling load, thermal mass and thermal comfort.

Page 16: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

16

ASHRAE Std. 55-2004Adaptive vs. Static Comfort Model: Offices

Comparison of adaptive models’ predicted indoor comfort temperatures with predictions by the “static” PMV model.

buildings with natural ventilation

20

21

22

23

24

25

26

27

-5 0 5 10 15 20 25 30 35

mean outdoor effective temperature (oC)

com

fort

tem

pera

ture

(o C)

RP-884 adaptive model"static" model (PMV)

buildings with centralized HVAC

20

21

22

23

24

25

26

27

-5 0 5 10 15 20 25 30 35

mean outdoor effective temperature (oC)

com

fort

tem

pera

ture

(o C)

RP-884 adaptive model with semantics

"static" model (PMV)

CENTRALLY-CONTROLLED HVAC SYSTEMS

NATURALLY VENTILATED BUILDINGS

Page 17: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

17

Adaptive Model Research (offices):Brager and de Dear

Page 18: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

18

Low Energy Cooling Technologies

• Night cooling (natural ventilation)• Night cooling (mechanical ventilation)• Slab cooling (air)• Slab cooling (water)• Evaporative cooling (direct and indirect)• Desiccant and evaporative cooling• Chilled ceilings/beams• Displacement ventilation• Ground cooling (air)• Aquifer• Sea/river/lake water cooling

Page 19: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

19

Types of HybVent Components

• There are no real hybrid ventilation components as such.

• In nearly all cases hybrid ventilation systems consist of a combination of components, which can be used in purely natural systems or in purely mechanical systems.

• However, the availability of appropriate components is essential for the successful design and operation of a hybrid ventilation system.

Page 20: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

20

Ventilation SystemsAll houses need ventilation, while traditionally this is done bypassive trickle vents above windows, often some form of mechanical ventilation may be needed. Simple bathroom extracts can be driven from the lighting circuit, but these simply throw away the warm air. Heat Recovery Ventilation Units extract the heat from the extract air and use this to warmthe incoming fresh air saving energy.

Natural or Passive Ventilation schemesSome houses employ Natural Ventilation techniques, using the buoyancy of warm air to create the “stack effect”, enhancing ventilation through a wind tower. Such schemes employ automatic opening windows or vents at low and high level, which must be inhibited during high winds, etc.

Typically, our solution will feature:a small “smart Box” panel with the smart Module near to the motorised windows a weather station with wind speed and direction can inhibit the opening of windows under certain conditions a rain sensor may also be fitted

http://www.smartkontrols.co.uk/cooling_overview.htm

SmartKontrols technology

Page 21: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

21

To combine natural and mechanical forces in the air distribution system, components can include:

• Low-pressure ductwork (size, surface, angles)• Low-pressure fans with advanced control mechanisms such as frequency control, air flow control, etc…• Low-pressure static heat exchangers and air filters (filter s.p. relates to filter efficiency, e.s.)• Wind towers, solar chimneys or atria for exhaust.• Underground ducts, culverts or plenums to pre-condition supply air.

Page 22: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

22

For control of thermal comfort, indoor air quality and air flow, components can include:

• Manually operated and/or motorized windows, vents or special ventilation openings in the facade- and in internal walls,

• Room temperature, CO2 and/or air flow sensors,• A control system with weather station

Page 23: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

23

Local air movement fans

Page 24: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

24

BRE – Environmental OfficeWatford, UK

Not in handout materials (copyright limitation)

Page 25: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

25

BRE Environmental Office (1997)

Page 26: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

26

BRE’s Environmental Office Building

• Low energy fans for use on still air days

• Glass for solar heating of thermal chimney

Page 27: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

27

BRE Environmental Office Building: Ventilation and Cooling

Page 28: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

28

Wind floor 18F

Memorial Hall

Entrance Hall

Lecture Rooms

Graduate School

Offices

Library Car Parking

Roof Garden

119.5m

Heat Storage TankRain Water Tank

Canteen

Roof Garden

Wind floor on 18FWind floor on 18F

The 1st Hybrid Vent. for High rise Bldgs in JapanThe 1st Hybrid Vent. for High rise Bldgs in Japan

Page 29: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

29

Wind floor 18F

Memorial Hall

Entrance Hall

Lecture Rooms

Graduate School

Offices

Library Car Parking

Roof Garden

119.5m

Heat Storage TankRain Water Tank

Canteen

Roof Garden

Entrance Hall on 1FEntrance Hall on 1F

Page 30: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

30

Wind floor 18F

Memorial Hall

Entrance Hall

Lecture Rooms

Graduate School

Offices

Library Car Parking

Roof Garden

119.5m

Heat Storage TankRain Water Tank

Canteen

Roof Garden

Memorial Hall on 23FMemorial Hall on 23F

Memorial Hall on 23F

Page 31: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

31

Wind floor 18F

Memorial Hall

Entrance Hall

Lecture Rooms

Graduate School

Offices

Library Car Parking

Roof Garden

119.5m

Heat Storage TankRain Water Tank

Canteen

Roof Garden

Graduate School on 19-22FGraduate School on 19-22F

Graduate School on 19 - 22F

Page 32: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

32

Wind floor 18F

Memorial Hall

Entrance Hall

Lecture Rooms

Graduate School

Offices

Library Car Parking

Roof Garden

119.5m

Heat Storage TankRain Water Tank

Canteen

Roof Garden

Natural Ventilation Shafts for 19-22FNatural Ventilation Shafts for 19-22F

Page 33: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

33

Wind floor 18F

Memorial Hall

Entrance Hall

Lecture Rooms

Graduate School

Offices

Library Car Parking

Roof Garden

119.5m

Heat Storage TankRain Water Tank

Canteen

Roof Garden

Canteen on 17FCanteen on 17F

Page 34: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

34

Wind floor 18F

Memorial Hall

Entrance Hall

Lecture Rooms

Graduate School

Offices

Library Car Parking

Roof Garden

119.5m

Heat Storage TankRain Water Tank

Canteen

Roof Garden

Lecture Rooms on 6-16F & B1-3FLecture Rooms on 6-16F & B1-3F

Page 35: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

35

Typical lecture room floorTypical lecture room floor

Lecture Rooms

Escalator

Refresh SpaceWC WC

M/RM/R

Wind is exhausted at the top of Wind is exhausted at the top of Escalator (Wind floor on 18th level)Escalator (Wind floor on 18th level)

Page 36: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

36

Wind floor 18F

Memorial Hall

Entrance Hall

Lecture Rooms

Graduate School

Offices

Library Car Parking

Roof Garden

119.5m

Heat Storage TankRain Water Tank

Canteen

Roof Garden

Gymnasium on B3FGymnasium on B3F

Page 37: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

37

Wind floor 18F

Memorial Hall

Entrance Hall

Lecture Rooms

Graduate School

Offices

Library Car Parking

Roof Garden

119.5m

Heat Storage TankRain Water Tank

Canteen

Roof Garden

Library B3-1FLibrary B3-1F Day-lighting even on B3F

Page 38: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

38

Library B3-1FLibrary B3-1F Day-lighting even on B3F

Page 39: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

39

To improve Indoor Air Quality and Save Energy

To improve Indoor Air Quality and Save Energy

- Automatically controlled natural ventilation windows and wind floor (18F) design. - Night-purge of VOCs and Internal heat- Variable fresh air intake using CO2 sensor - BEMS

Page 40: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

40

Hybrid Ventilation SystemHybrid Ventilation System

VAV

Air Handling Unit(Middle season:all fresh air conditioner)

Lecture Room

NaturalVentilation Conditioned Air

To each Class RoomReturned Air

EscalatorHall

Fresh Air

Exhausted AirFrom each Class Room

To Wind Floor (18th level)

Motor Damper

Page 41: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

41

SensorsSensors

Anemometer,State of natural ventilation window (open or close),Integrated time while windows are open

T H

T

T

HOutdoor

Solar radiationRainfall

Wind speed at exhaust openingThermometer

T

H Hygrometer

VAnemometer

Wind speed & direction

V

V

VV

VCOdensity

2

T

These data (total 2000 points) are recorded automatically every 10 minutes

Page 42: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

42

0

200

400

600

800

1,000

1,200

1,400

1,600

1,800B3F

B1F

2F

4F

6F

8F

10F

12F

14F

16F

18F

20F

22F

23F

時間

/年

2000/3

2000/2

2000/1

1999/12

1999/11

1999/10

1999/9

1999/8

1999/7

1999/6

1999/5

1999/4

Ventilation windows were opened for 1100 hours per year

Ventilation windows were opened for 1100 hours per year

Page 43: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

43

Apr.1999-Mar.2000

Hybrid Ventilation System reduced Space Cooling Energy by 17%

Hybrid Ventilation System reduced Space Cooling Energy by 17%

0102030405060708090

Apr May Jun Jul Aug Sep Oct Nov

Prim

ary

Ener

gy C

onsu

mpt

ion

for

Spac

e C

oolin

g(M

J/m

2)

Reduced by Natural VentilationAir-handlingChilling

Page 44: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

44

Operation Energy was reduced by 40%Operation Energy was reduced by 40%

0

500

1000

1500

2000

2500

3000

Reference Case Study Actual

Pri

mary

Energ

y C

om

sum

pti

on[M

J/a/m

2]

Cooking

Escalator

Elevator

Electr ic Applances

Lighting

Air Handling

HeatSource(Others)

Heat Source(Storage)

1,5831,647

2,696 Apr. 1999 – Mar. 2000

Page 45: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

45

LCCO2 will be reduced by 40%LCCO2 will be reduced by 40%

0 50 100 150 200 250

Case Study

Reference

Design Intial ConstructionRe-construction RepairRenovation MaintenanceOperating Energy DemolitionRelease of HCFCs

-37%kg-CO2/a/m2

127.9

202.1

Page 46: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

46

Other Loads will be reducedOther Loads will be reduced

0 0.2 0.4 0.6 0.8

Case Study

Reference

Formed Insulation RefrigerantFire extingusher Electric Isolator

-95%

g-CFC11/a/m2

0.036

0.669

0 100 200 300 400

Case Study

Reference

Design Intial ConstructionRe-construction RepairRenovation MaintenanceOperating Energy DemolitionRelease of HCFCs

-26%g-SO2/a/m2

276.5

372.3

0 100 200 300 400 500 600

Case Study

Reference

Design Intial ConstructionRe-construction RepairRenovation MaintenanceOperating Energy DemolitionRelease of HCFCs

-26%g-SO2/a/m2

414.8

558.1

0 1000 2000 3000 4000

Case Study

Reference

Design Intial ConstructionRe-construction RepairRenovation MaintenanceOperating Energy DemolitionRelease of HCFCs

-34%MJ/a/m2

2422.5

3679.9

Depletion of Ozone LayerDepletion of Ozone Layer AcidificationAcidification

Health Damage (Air)Health Damage (Air) Depletion of Fossil FuelDepletion of Fossil Fuel

Page 47: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

47

Eco-Economic AnalysisEco-Economic AnalysisInitial cost(Million

Yen)

Energycostreduction(MillionYen/year)

CostPaybacktime(Year)

CO2Reduction

(t-CO2

/Year)

Intial costper unit CO2Reduction(1000 yen/(t-CO2/year))

CO2 cont. for Fresh air Intake 13.5 10.4 1.3 1038 13Day Lithting Hf lamp 31.4 19.6 1.6 981 32CO cont. for Parking Vent. 54.1 18.0 3.0 966 56Variable Air Volume 66.9 17.2 3.9 956 70Thermal Heat Strage 0 5.4 0.0 595 0Escalator control 2.9 5.9 0.5 290 10Variable Water Volume 9.4 9.4 1.0 154 61Natural Ventilation 56.5 2.9 19.2 57 1000Total 234.7 88.8 2.6 5037 47

1999, 2000

234.7 / 20000 Million Yen= + 1.2%

Page 48: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

48

Additional Initial Cost {Yen/(t-CO2/a)}

47,000JPY/(t-CO2/a)

Photo Voltaics

Eco-Economic AnalysisEco-Economic Analysis

4,000,000JPY/(t-CO2/a)

234.7 / 20000 Million JPY = + 1.2%

Meiji University

Page 49: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

49

Official Annex 35 report summarizes initial working phase of the project.

• Ventilation technologies• Control strategies and algorithms• Analysis methods• Examples of existing systems• Solutions to problems in different

climates.

• Available at http://hybvent.civil.auc.dk/puplications/sotar.pdf

(135 pages)

Page 50: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

50

Annex 35 HybVent Publications are available for download at http://hybvent.civil.auc.dk/

Page 51: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

51

Weather conditions and ventilation modeArmoury Tower – Shanghai, China

Not in handout materials (copyright limitation)

Page 52: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

52

Armoury Tower, Shanghai

Not in handout materials (copyright limitation)

Page 53: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

53Not in handout materials (copyright limitation)

Page 54: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

54Not in handout materials (copyright limitation)

Page 55: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

55

Queen’s College, de Montefort University, Leicester, UK

Not in handout materials (copyright limitation)

Page 56: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

56Not in handout materials (copyright limitation)

Page 57: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

57

Umno Tower - Penang, Malaysia

Not in handout materials (copyright limitation)

Page 58: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

58

Wind flow around building – air pressure contoursUmno Tower - Penang, Malaysia

Vertical section Level 12

Not in handout materials (copyright limitation)

Page 59: Natural Ventilation for Infection Control in Health …€¦ · Natural Ventilation for Infection Control in Health Care ... outdoor air exchange rate 0 1 2 3 4 5 6 7 8 ... NATURALLY

59

Wind pressure diagramsUmno Tower - Penang, Malaysia

Not in handout materials (copyright limitation)