ncb series application drawings - blueridge...

17
These drawing are intended as a guide only and not as a replacement for professionally engineered project drawings. These concept system drawings do not imply compliance with local building codes. Actual installations may vary depending on installation location & parameters and it must be done in accordance with all local building codes. Verify with local building officials before commencement of system installations. Guide Only NCB Series Application Drawings 20 Goodyear Irvine, CA 92618 800-519-8794 www.NavienAmerica.com T Check Valve Circulator Pressure Relief Valve Expansion Tank Aquastat Full-port Ball Valve Mixing Valve DHW Circulator w/Aquastat & Check Valve Backflow Preventor Air Elimination NCB-180ASME H Gas Domestic Heating S R C NCB-210ASME H Gas Domestic Heating S R C NCB-240ASME H Gas Domestic Heating S R C

Upload: lydang

Post on 11-Mar-2018

217 views

Category:

Documents


2 download

TRANSCRIPT

These drawing are intended as a guide only and not as a replacement for professionally engineered project drawings. These concept system drawings do not imply compliance with local building codes. Actual installations may vary depending on installation location & parameters and it must be done in accordance with all local building codes. Verify with local building o�cials before commencement of system installations.

Guide Only

NCB Series Application Drawings

20 GoodyearIrvine, CA 92618

800-519-8794www.NavienAmerica.com

T

Check Valve Circulator

PressureReliefValve

ExpansionTank

Aquastat

Full-portBall Valve

MixingValve

DHW Circulatorw/Aquastat & Check Valve

BackflowPreventor

AirElimination

NCB-180ASME

HGas D

omes

tic

Hea

ting

S R C

NCB-210ASME

HGas D

omes

tic

Hea

ting

S R C

NCB-240ASME

HGas D

omes

tic

Hea

ting

S R C

20 Goodyear

Irvine, CA 92618

800-519-8794

www.navienamerica.com

T

Check Valve Circulator

Drawn By: B. Fenske November 1, 2013

Pressure

Relief

ValveExpansion

Tank

Aquastat

Full-port

Ball Valve

Mixing

Valve

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Backflow

PreventorNCB-AHU-BF01

Air Elimination

Zone Valve

H

Gas

Hydronic

Feed

Water

Domestic Hot Water

Domestic Cold Water

Condensate

Ga

s Do

me

stic

He

atin

g

S R C

AIRFLOW

Opt. AC COIL

NCB Series Combi-Boiler

Installation Notes:

1. 25' Total Maximum Boiler-Side

Piping Connection Length Allowed.

2. Boiler-Side Pipe Length Exceeding

25' Total or a 50MBTUH Coil Output or

More Requires Primary/Secondary

Piping Configuration with Separate

System Circulator.

3. Air Handlers with Internal or External

Circulator Requires Crossover Pipe at

A/H Unit or CH Unit to Complete

Primary/Secondary Configuration*.

* See Drawing NCB-AHU-P-BF01

Navien CH Combi Boiler Application

with Air Handler - Direct Connection

20 Goodyear

Irvine, CA 92618

800-519-8794

www.navienamerica.com

T

Check Valve Circulator

Drawn By: B. Fenske November 1, 2013

Pressure

Relief

ValveExpansion

Tank

Aquastat

Full-port

Ball Valve

Mixing

Valve

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Backflow

PreventorNCB-AHU-P-BF01

Air Elimination

Zone Valve

H

Gas

Hydronic

Feed

Water

Domestic Hot Water

Domestic Cold Water

Condensate

Ga

s Do

me

stic

He

atin

g

S R C

AIRFLOW

Opt. AC COIL

Navien NCB Combi-Boiler Application

Air Handler with Internal/External Pump

NCB Series Combi-Boiler

Installation Notes:

1. 100' Total Maximum Boiler-Side

Piping Connection Length Allowed.

2. Boiler-Side Pipe Length Exceeding

100' Total or a 50MBTUH Coil Output

or More Requires Primary/Secondary

Piping Configuration (A) with A/H

connection the tertiary secondary.

(A)

Optional

Circulator

Location

20 Goodyear

Irvine, CA 92618

800-519-8794

www.navienamerica.com

T

Check Valve Circulator

Drawn By: B. Fenske November 1, 2013

Pressure

Relief

ValveExpansion

Tank

Aquastat

Full-port

Ball Valve

Mixing

Valve

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Backflow

PreventorNCB-NCBQuik4-BF01

Air Elimination

Zone ValveNavien NCB Combi Boiler

With CH Quik-Install Manifold Kit

Single System Circulator with AHU Shown

NCB Series Combi-Boiler

H

Gas

Hydronic

Feed

Water

Domestic Hot Water

Domestic Cold Water

Condensate

Ga

s Do

me

stic

He

atin

g

S R C

Field Supplied Circulator Zone Panel

Shall have Dry Contacts Closed On Heat

Calls Wired to Navien CH Unit “T & T”

Terminals To Activate Heat Mode

DIP Sw 7 of 8 Down (OFF) on PCBT

Circ

Panel

AIRFLOW

Opt. AC COIL

20 Goodyear

Irvine, CA 92618

800-519-8794

www.navienamerica.com

T

Check Valve Circulator

Drawn By: B. Fenske November 1, 2013

Pressure

Relief

ValveExpansion

Tank

Aquastat

Full-port

Ball Valve

Mixing

Valve

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Backflow

PreventorNCB-NCBQuik1-BF01

Air Elimination

Zone ValveNavien NCB Combi Boiler

With CH Quik-Install Manifold Kit

Single System Circulator Shown

NCB Series Combi-Boiler

H

Gas

Hydronic

Feed

Water

Domestic Hot Water

Domestic Cold Water

Condensate

Ga

s Do

me

stic

He

atin

g

S R C

Field Supplied Circulator Zone Panel

Shall have Dry Contacts Closed On Heat

Calls Wired to Navien CH Unit “T & T”

Terminals To Activate Heat Mode

DIP Sw 7 of 8 Down (OFF) on PCB

T

Circ

Panel

System Return

20 Goodyear

Irvine, CA 92618

800-519-8794

www.navienamerica.com

Check Valve Circulator

Drawn By: B. Fenske November 1, 2013

Pressure

Relief

ValveExpansion

Tank

Full-port

Ball Valve

Mixing

Valve

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Backflow

PreventorNCB-1P-BF01

Air Elimination

Zone Valve

NCB Series Combi-Boiler

Navien NCB Combi-Boiler Application

Single Circulator Zone ApplicationPurge

Valve

H

Gas

Hydronic

Feed

Water

Domestic Hot Water

Domestic Cold Water

Condensate

Ga

s Do

me

stic

He

atin

g

S R C

6" Min

12" Max

Field Supplied Circulator Zone Panel

Shall have Dry Contacts Closed On Heat

Calls Wired to Navien CH Unit “T & T”

Terminals To Activate Heat Mode

DIP Sw 7 of 8 Down (OFF) on PCB

T

Circ

Panel

System Return

20 Goodyear

Irvine, CA 92618

800-519-8794

www.navienamerica.com

T

Check Valve Circulator

Drawn By: B. Fenske November 1, 2013

Pressure

Relief

ValveExpansion

Tank

Aquastat

Full-port

Ball Valve

Mixing

Valve

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Backflow

PreventorNCB-NCBQuik3-BF01

Air Elimination

Zone ValveNavien NCB Combi Boiler

With CH Quik-Install Manifold Kit

Multiple System Zone Valves Shown

NCB Series Combi-Boiler

H

Gas

Hydronic

Feed

Water

Domestic Hot Water

Domestic Cold Water

Condensate

Ga

s Do

me

stic

He

atin

g

S R C

Field Supplied Circulator Zone Panel

Shall have Dry Contacts Closed On Heat

Calls Wired to Navien CH Unit “T & T”

Terminals To Activate Heat Mode

DIP Sw 7 of 8 Down (OFF) on PCB

Circ

Panel

T T T

120 to 24VAC

Transformer

System Return

20 Goodyear

Irvine, CA 92618

800-519-8794

www.navienamerica.com

Check Valve Circulator

Drawn By: B. Fenske November 1, 2013

Pressure

Relief

ValveExpansion

Tank

Full-port

Ball Valve

Mixing

Valve

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Backflow

PreventorNCB-3P-BF01

Air Elimination

Zone Valve

NCB Series Combi-Boiler

Navien NCB Combi-Boiler Application

Single Circulator with Multiple Zone Valves ShownPurge

Valve

H

Gas

Hydronic

Feed

Water

Domestic Hot Water

Domestic Cold Water

Condensate

Ga

s Do

me

stic

He

atin

g

S R C

6" Min

12" Max

Field Supplied Circulator Zone Panel

Shall have Dry Contacts Closed On Heat

Calls Wired to Navien CH Unit “T & T”

Terminals To Activate Heat Mode

DIP Sw 7 of 8 Down (OFF) on PCB

Circ

Panel

T T T

120 to 24VAC

Transformer

System Return

20 Goodyear

Irvine, CA 92618

800-519-8794

www.navienamerica.com

T

Check Valve Circulator

Drawn By: B. Fenske November 1, 2013

Pressure

Relief

ValveExpansion

Tank

Aquastat

Full-port

Ball Valve

Mixing

Valve

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Backflow

PreventorNCB-NCBQuik2-BF01

Air Elimination

Zone ValveNavien NCB Combi Boiler

With CH Quik-Install Manifold Kit

Multiple System Circulators Shown

NCB Series Combi-Boiler

H

Gas

Hydronic

Feed

Water

Domestic Hot Water

Domestic Cold Water

Condensate

Ga

s Do

me

stic

He

atin

g

S R C

Circ Zone

Panel

T T TField Supplied Circulator Zone Panel

Shall have Dry Contacts Closed On Heat

Calls Wired to Navien CH Unit “T & T”

Terminals To Activate Heat Mode

DIP Sw 7 of 8 Down (OFF) on PCB

System Return

20 Goodyear

Irvine, CA 92618

800-519-8794

www.navienamerica.com

Check Valve Circulator

Drawn By: B. Fenske November 1, 2013

Pressure

Relief

ValveExpansion

Tank

Purge

Valve

Full-port

Ball Valve

Mixing

Valve

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Backflow

PreventorNCB-3P-BF01

Air Elimination

Zone Valve

NCB Series Combi-Boiler

Navien NCB Combi-Boiler Application

Multiple Zone Circulators Shown

H

Gas

Hydronic

Feed

Water

Domestic Hot Water

Domestic Cold Water

Condensate

Ga

s Do

me

stic

He

atin

g

S R C

6" Min

12" Max

Circ Zone

Panel

T T T

Field Supplied Circulator Zone Panel

Shall have Dry Contacts Closed On Heat

Calls Wired to Navien CH Unit “T & T”

Terminals To Activate Heat Mode

DIP Sw 7 of 8 Down (OFF) on PCB

System Return

20 Goodyear

Irvine, CA 92618

800-519-8794

www.navienamerica.com

Check Valve Circulator

Drawn By: B. Fenske November 1, 2013

Pressure

Relief

ValveExpansion

Tank

Purge

Valve

Full-port

Ball Valve

Mixing

Valve

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Backflow

PreventorNCB-3P-1LT-BF01

Air Elimination

Zone Valve

NCB Series Combi-Boiler

Navien NCB Combi-Boiler Application

Multiple Zone Circulators

Low Temperature Zone Shown

Field Supplied Circulator Zone Panel

Shall have Dry Contacts Closed On Heat

Calls Wired to Navien CH Unit “T & T”

Terminals To Activate Heat Mode

DIP Sw 7 of 8 Down (OFF) on PCB

H

Gas

Hydronic

Feed

Water

Domestic Hot Water

Domestic Cold Water

Condensate

Ga

s Do

me

stic

He

atin

g

S R C

6" Min

12" Max

Circ Zone

Panel

T T T

20 Goodyear

Irvine, CA 92618

800-519-8794

www.navienamerica.com

Check Valve Circulator

Drawn By: B. Fenske November 1, 2013

Pressure

Relief

ValveExpansion

Tank

Wye Strainer

Full-port

Ball Valve

Mixing

Valve

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Backflow

PreventorNCB-CI-2P-DR-BF01

Air Elimination

Dirt Separator

NCB Series Combi-Boiler

Navien NCB Combi-Boiler Application

Two-Pipe Direct Return

H

Gas

Hydronic

Feed

Water

Domestic Hot Water

Domestic Cold Water

Condensate

Ga

s Do

me

stic

He

atin

g

S R C

6" Min

12" Max

Field Supplied Circulator Zone Panel

Shall have Dry Contacts Closed On Heat Calls

Wired to Navien CH Unit “T & T” Terminals To

Activate Heat Mode

DIP Sw 7 of 8 Down (OFF) on PCB

T

Circ

Panel

or

Cast Iron Baseboard

Cast Iron Fin Tube

Cast Iron Radiators

or

Proper dirt separation must be used when applying the Navien NCB combi-boiler with

systems that contain ferrous or ferric materials.

Installation requires proper means of cleaning and flushing system piping prior to

start-up to avoid potentiality subjecting the NCB combi boiler to system contaminants.

Proper air elimination & system maintenance is required to maintain Navien warranties.

Dirt SeparatorWYE Strainer w/

Blowdown

20 Goodyear

Irvine, CA 92618

800-519-8794

www.navienamerica.com

Check Valve Circulator

Drawn By: B. Fenske November 1, 2013

Pressure

Relief

ValveExpansion

Tank

Wye Strainer

Full-port

Ball Valve

Mixing

Valve

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Backflow

PreventorNCB-CI-2P-RR-BF01

Air Elimination

Dirt Separator

NCB Series Combi-Boiler

Navien NCB Combi-Boiler Application

Two-Pipe Reverse Return

Field Supplied Circulator Zone Panel

Shall have Dry Contacts Closed On Heat Calls

Wired to Navien CH Unit “T & T” Terminals To

Activate Heat Mode

DIP Sw 7 of 8 Down (OFF) on PCB

Proper dirt separation must be used when applying the Navien NCB combi-boiler with

systems that contain ferrous or ferric materials.

Installation requires proper means of cleaning and flushing system piping prior to

start-up to avoid potentiality subjecting the NCB combi boiler to system contaminants.

Proper air elimination & system maintenance is required to maintain Navien warranties.

Dirt SeparatorWYE Strainer w/

Blowdown

H

Gas

Hydronic

Feed

Water

Domestic Hot Water

Domestic Cold Water

Condensate

Ga

s Do

me

stic

He

atin

g

S R C

6" Min

12" Max

T

Circ

Panel

or

Cast Iron Baseboard

Cast Iron Fin Tube

Cast Iron Radiators

or

20 Goodyear

Irvine, CA 92618

800-519-8794

www.navienamerica.com

Check Valve Circulator

Drawn By: B. Fenske November 1, 2013

Pressure

Relief

ValveExpansion

Tank

Wye Strainer

Full-port

Ball Valve

Monoflo

Tee

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Backflow

PreventorNCB-CI-MONO-BF01

Air Elimination

Dirt Separator

NCB Series Combi-Boiler

Navien NCB Combi-Boiler Application

One-Pipe (Monoflo) Distribution System

H

Gas

Hydronic

Feed

Water

Domestic Hot Water

Domestic Cold Water

Condensate

Ga

s Do

me

stic

He

atin

g

S R C

6" Min

12" Max

Field Supplied Circulator Zone Panel

Shall have Dry Contacts Closed On Heat Calls

Wired to Navien CH Unit “T & T” Terminals To

Activate Heat Mode

DIP Sw 7 of 8 Down (OFF) on PCB

T

Circ

Panel

or

Cast Iron Baseboard

Cast Iron Fin Tube

Cast Iron Radiators

or

Proper dirt separation must be used when applying the Navien NCB combi-boiler with

systems that contain ferrous or ferric materials.

Installation requires proper means of cleaning and flushing system piping prior to

start-up to avoid potentiality subjecting the NCB combi boiler to system contaminants.

Proper air elimination & system maintenance is required to maintain Navien warranties.

Dirt SeparatorWYE Strainer w/

Blowdown

20 Goodyear

Irvine, CA 92618

800-519-8794

www.navienamerica.com

Check Valve Circulator

Drawn By: B. Fenske November 1, 2013

Pressure

Relief

ValveExpansion

Tank

Full-port

Ball Valve

Mixing

Valve

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Backflow

PreventorNCB-DHWR-BF01

Air Elimination

Solenoid

Valve

NCB Series Combi-Boiler

Navien NCB Combi-Boiler Application

DHW Recirculation Shown

S

H

Gas

Hydronic

Feed

Water

Domestic Hot Water

Domestic Cold Water

Condensate

Ga

s Do

me

stic

He

atin

g

S R C

6" Min

12" Max

*

System Return

DHW Circulator Requirements:

1. S.S. or Bronze Body & Impeller

* DHW Side 2.5 PSI Pressure drop @ 2 GPM

2. > 0.5 GPM to Activate Burner

3. Maximum 2 GPM

4. Programmable Timer

5. Selectable Aquastat

* Set minimum 5°F below NCB DHW Setpoint

Purge

Valve

20 Goodyear

Irvine, CA 92618

800-519-8794

www.navienamerica.com

T

Check Valve Circulator

Drawn By: B. Fenske November 1, 2013

Pressure

Relief

ValveExpansion

Tank

Aquastat

Full-port

Ball Valve

Mixing

Valve

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Backflow

PreventorNCB-NPE-BF01

Air Elimination

Solenoid

Valve

NCB Series Combi-Boiler & NPE (A/S) Series Tankless

Navien NCB Combi-Boiler Application

With NPE-A or S Tankless Water Heater

S

H

Gas

Hydronic

Feed

Water

Domestic Cold Water

Condensate

Ga

s Do

me

stic

He

atin

g

S R C

6" Min

12" Max

CH

Domestic Hot Water

Communication

Cable

Ga

s

Opt. DHW Recirculation – “A” Model

S

20 Goodyear

Irvine, CA 92618

800-519-8794

www.navienamerica.com

T

Check Valve Circulator

Drawn By: B. Fenske November 1, 2013

Pressure

Relief

ValveExpansion

Tank

Aquastat

Full-port

Ball Valve

Mixing

Valve

DHW Circulator

w/Aquastat & Check Valve

This drawing is intended only as a guide and not as a replacement for professionally engineered project drawings.

This concept system drawing does not imply compliance with local building codes. Actual installation may vary

depending on installation location & parameters and it must be done in accordance to all local building codes.

Verify with local building officials before commencement of system installation.

Backflow

PreventorNCB-2NPE-BF01

Air Elimination

Solenoid

Valve

NCB Series Combi-Boiler & NPE (A/S) Series Tankless

Navien NCB Combi-Boiler Application

With Two NPE-A or S Tankless Water Heater

S

H

Gas

Hydronic

Feed

Water

Domestic Cold Water

Condensate

Ga

s Do

me

stic

He

atin

g

S R C

6" Min

12" Max

CH

Communication

Cable

Ga

s

S

CH

Domestic Hot Water

Ga

s

Opt. DHW Recirculation

NPE– “A” Models

Communication

Cable