netpro operation manual 2k0 4k0 va

20
NetPro Uninterruptible Power Supply 2000 - 4000 VA Manufactured by: GE Digital Energy General Electric Company Telephone +41 (0)91 / 850 51 51 CH – 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www.gedigitalenergy.com GE Digital Energy Technology for the Digital World. ver 4.0 - GB NetPro UPS g

Upload: danny-dan

Post on 21-Jan-2016

678 views

Category:

Documents


96 download

DESCRIPTION

ups user guide

TRANSCRIPT

Page 1: Netpro Operation Manual 2k0 4k0 Va

NetProUninterruptible Power Supply2000 - 4000 VA

Manufactured by:

GE Digital EnergyGeneral Electric Company Telephone +41 (0)91 / 850 51 51CH – 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44Switzerland Website www.gedigitalenergy.com

GE Digital Energy

Technology for the Digital World. ver 4.0 - GBNetPro UPS

g

Page 2: Netpro Operation Manual 2k0 4k0 Va

O

GE Digital Energy gUSER MANUAL

PK

©c

GB

PM_NPE_XXX_2K0_4K0_1GB_V040 1 NetPro 2000-4000: user manual 4.0 (GB)

NetProUninterruptible Power SupplyUninterruptible Power SupplyUninterruptible Power SupplyUninterruptible Power Supply

2000 - 4000 VA2000 - 4000 VA2000 - 4000 VA2000 - 4000 VA

lease read these instructions carefully before installation and start-up of the NetPro UPS.eep this manual in a safe place for future reference.

CONTENTS

1 INTRODUCTION............................................................................................................ 21.1 Introduction1.2 Safety Rules1.3 Transport / Storage

2 INSTALLATION .............................................................................................................. 22.1 Installation Rules2.2 Installation Procedure

3 OPERATION................................................................................................................... 43.1 Description of Front Panel3.2 Start-up

3.2.1 Start-up, mains available3.2.2 Start-up, mains not available (‘battery start’)3.2.3 Start-up with programmed runtime (autonomy time)

3.3 Use: Normal Operation3.3.1 Normal operation conditions3.3.2 Normal operation indications3.3.3 Auto-off (no-load shutdown)3.3.4 Automatic bypass switch3.3.5 Switching off

3.4 Use: Screen Menus3.4.1 Default menu3.4.2 Status messages and alarm messages

3.4.2.1 Status messages3.4.2.2 Low priority alarm messages3.4.2.3 High priority alarm messages

3.4.3 Setup menu3.5 Runtime: calculation and indication3.6 Other Features

3.6.1 Shutdown3.6.2 Programmed shutdown3.6.3 Front panel test3.6.4 Quick battery test3.6.5 Battery calibration test3.6.6 Deep battery test

4 COMMUNICATION ......................................................................................................164.1 RS232 Port4.2 Relay Interface Card (option)4.3 SNMP Interface Card (option)

5 OPTIONAL FEATURES...............................................................................................175.1 Extended Runtime (NetPro 2000/3000)5.2 Isolation Transformer (NetPro +)5.3 PowerFLAG SerVICe Box for Modem Connection

6 MAINTENANCE............................................................................................................176.1 General6.2 Batteries

7 TROUBLESHOOTING .................................................................................................18

8 SPECIFICATIONS........................................................................................................19

General Electric Digital Energy. All rights reserved; reproduction without permission prohibited. This manual may be subject tohange; no liability can be accepted for any error or omission.

Page 3: Netpro Operation Manual 2k0 4k0 Va

OPM_NPE_XXX_2K0_4K0_1GB_V040 2 NetPro 2000-4000: user manual 4.0 (GB)

GE Digital Energy g

1.1 Introduction

The GE (General Electric) Digital Energy NetPro UPS, a truly on-line uninterruptible power supply,protects your equipment from all forms of power interference, including complete power failures.

1.2 Safety Rules

! CAUTION: RISK OF ELECTRICAL SHOCK. The UPS contains batteries. The applianceoutlets may be electrically live, even when the UPS is disconnected from the mains.

! The UPS contains potentially hazardous voltages. Do not open the UPS, there are no userserviceable parts inside.

! All maintenance and service work, including replacement of the batteries, should beperformed by qualified service personnel.

1.3 Transport / Storage

! No liability can be accepted for any transport damage when the equipment is shipped in non-original packaging.

! Store the UPS in a dry location with the batteries in a fully charged state. Storage temperaturemust be within -20 +45 "C. If the unit is stored for a period exceeding 3 months, optimal batterylifetime is obtained if the storage temperature does not exceed 25°C.

! If the unit is stored for an extended period of time, the batteries must be recharged periodically.Connect the unit to a wall outlet and recharge the batteries for 24 hours:- if the storage temperature is within -20 and +30°C: every 3 months,- if the storage temperature is within -20 and +45°C: every month.

The shipping box contains a NetPro UPS, two IEC male-female power cords, a data cable, a CD ROMand this manual. Inspect the UPS for damage after unpacking. If any damage is present pleaseimmediately notify the carrier and place of purchase.

IMPORTANT:Before making any connection and switching on the NetPro UPS, please check the followingconditions:

! your mains supply is 220 - 240 Volts and 50 (if the mains frequency is 60Hz, the output frequencyof the UPS can be changed, see section 3.4), and

! the total power demand of the connected equipment does not exceed the rated output power ofthe NetPro UPS (indicated on the rating label) (6, fig. 1).

WARNINGConnecting the UPS output to neutral or ground will result in a malfunctioning UPS, unless yourunit is a "NetPro+", i.e. equipped with an isolation transformer.

2.1 Installation Rules

! The UPS is intended to be used in normal domestic and office situations.! Protect the UPS, according to the wiring rules, with a 16A (NP 2000/3000VA) or 25A

(NP 4000VA) D-type fuse.! The UPS must be powered from a single phase wall outlet equipped with protective earth. Do not

use extension cords.! Avoid locations that are excessively humid, near water, near heat sources or in direct sunlight.! The ambient temperature should not exceed 40"C. Optimal battery lifetime is obtained if the

ambient temperature does not exceed 30"C.! It is important that ventilation air can move freely around and through the unit. Do not block the air

vents.! Do not plug appliances such as electric heaters, toasters and vacuum cleaners into the UPS.! Be careful when connecting laser printers: be sure that the demanded power does not exceed the

capacity of the UPS.! The sum of the leakage currents of the UPS and the connected loads should not exceed 3.5mA.

1 - Introduction

2 - Installation

Page 4: Netpro Operation Manual 2k0 4k0 Va

OPM_NPE_XXX_2K0_4K0_1GB_V040 3 NetPro 2000-4000: user manual 4.0 (GB)

GE Digital Energy g2.2 Installation Procedure

1 Switch off your computer, and unplug it from thesocket-outlet.

2 NetPro 2000: Disconnect the power cord from thecomputer (rating 250Vac/10A) and connect this cordto the mains input socket (2, fig. 1) of the UPS. Seefig. 2.NetPro 3000/4000 models are equipped with a fixedpower cord (11, fig. 1).

3 Using the output cords provided, connect thecomputer equipment to the appliance outlets (4, fig. 1)of the unit. Spread the loads over the appliance outletsas equally as possible. If you use a distribution box toconnect more than one appliance per outlet, pleasenote that the maximum AC-current rating of eachappliance outlet is 10A. See fig. 3.Output 4a is programmable: see 3.4.3.

If your UPS is a 4000VA model please proceed withstep 5.

NetPro 2000/3000 only.4 Battery extension pack(s) can be installed to

increase the battery runtime. Connect the DCconnector of the battery pack (9, fig. 1/4) to the DCsocket of the UPS (7, fig. 1/4). You will hear a clickwhen the cable is properly installed. Block the DCconnector: install the small locking plate (9a, fig. 4)that came with the battery pack, and fasten it withthe screw provided. Using the DC connector of thebattery pack (10, fig. 1) you can install a second,third, etc. pack. See 5.1 for more information.

5 Make sure the on/off switch (12, fig. 1) at the rear of the UPS is off, i.e. in position ‘0’, and connectthe mains cord of the UPS to a working, AC wall socket outlet equipped with a protective earthconnection. The fans start rotating: mains power is available and the batteries are charging.

6 For best results, allow the UPS to recharge the batteries during a period of approx. 12 hours. It isacceptable to use the UPS without first charging the battery, but the runtime may be reduced.

7 For advanced communication possibilities, the RS232 interface port (3, fig. 1) can be connectedto a computer system and/or optional interface cards (5, fig. 1) can be added. See chapter 4.

Batt. extension pack NetPro 2000VA NetPro 3000/4000VA

fig. 2

fig. 3

fig. 4

9a7

9

68

2 4

6

10

1 3

11

5

1 6

12 4a 3

79 7

RESET

OK

12 4

3000 VA

fig. 1

Page 5: Netpro Operation Manual 2k0 4k0 Va

OPM_NPE_XXX_2K0_4K0_1GB_V04

GE Digital Energy g

3.1 Description of Front Panel

13 Green LED 'operation'The UPS operates and supplies the load.

14 Red LED 'alarm'High priority alarm situation. See 3.4.2.3.

15 Yellow LED 'progr. shutdown'(= programmed shutdown)See 3.6.2.

16 Yellow LED 'weak mains'See 3.4.2.2.

17 LCD screen2x16 characters, shows UPS system data, statusmessages, alarm messages, settings. The languageis selectable: English (default), German, French,Italian, Spanish. Section 3.4.3 describes theselection procedure.

18-20 Push-buttonsWith the button keypads '####' (18) and '$$$$' (20) you canscroll through the several screens, with keypad 'OK'(19) a selection is confirmed. Keypad activity isaccompanied by a beeping buzzer. If there is nokeypad activity during 20 seconds the LCD screenwill return to a default screen.

3.2 Start-up

3.2.1 Start-up, mains available1 As soon as the power cord is plugged into a working wall outlet, the battery charger is active: the

batteries are being charged.2 Switch on the UPS with the 'on/off' switch (12, fig. 1) at the rear of the unit; the green LED

'operation' will illuminate.3 The equipment connected to the UPS can now be switched on. (The 'soft start' capability of the

UPS allows that the on/off switch of the UPS can be used as a 'master switch': all equipmentprotected by the UPS can be switched on by simply switching on the UPS. The simultaneouslyoccuring inrush currents of the loads do not immediately cause bypass operation.)

3.2.2 Start-up, mains not available (battery start)If the mains input is absent (power cord not connected, or mains failure):

1 Turn the on/off switch (12, fig 1) into position 'I'. The following screen will appear:

If the 'OK' key (19, fig. 5) ifig. 5), or waiting 5 seconddischarges the batteries. Thunless the mains input is av

fig. 5 Front panel

3 - Operation

20

19

17

16

15

18

1413

!"##$%&'(#"%#')*+''''''''''&$(

0 4 NetPro 2000-4000: user manual 4.0 (GB)

s pressed within 5 seconds, the UPS will start. Pressing key $$$$ (20,s, will abort the start-up attempt. The UPS operates on battery: ite UPS will stop delivering output power at the end of the runtimeailable by that time

Page 6: Netpro Operation Manual 2k0 4k0 Va

OPM_NPE_XXX_2K0_4K0_1GB_V04

GE Digital Energy g3.2.3 Start-up with programmed runtime (autonomy time)

If a start-up runtime has been programmed (see section 3.4.3 Setup menu) and the batteries do notcontain sufficient energy to provide this runtime at the moment of start-up, the following screen willappear:

If 'OK' (19, fig. 5) is pressed the meUPS will wait until the batteries haveonly then start up. Calculation of thload.

This feature is not active during a 'b

3.3 Use: Normal Operatio

3.3.1 Normal operation conditio! the mains supply is pres! the UPS is on,! the load does not excee! the operating temperatu

3.3.2 Normal operation indicati! the green LED 'operation! LEDs 'weak mains', 'pro! the beeper is silent and! the liquid crystal display

3.3.3 Auto-off (no-load shutdowIf this function is activated,than 5% of the maximum lThe unit will automatically tuno-load shutdown function i

3.3.4 Automatic bypass switchThe UPS is equipped with load to the mains if the UPovertemperature. The UPSremoved or the temperatureIf a power failure occurs deventually, when the batteoverload or overtemperaturThe bypass function can be

3.3.5 Switching off1 Turn the 'on/off' switch (12,

the output will always be aable to reboot.

2 If electric isolation is require

The unit can be switched of

",#+*-'#++'.+/'''''(#"%#')

0 5 NetPro 2000-4000: user manual 4.0 (GB)

ssage is ignored and the UPS will start up. If no key is pressed, the been sufficiently charged to guarantee the programmed runtime, and

e runtime is based on the assumption that the UPS supplies a 100%

attery start' (see above).

n

ns:ent,

d the capacity of the UPS andre is below alarm level

ons:' is continuously on,

gr. shutdown' and 'alarm' are out,

(LCD) shows a default screen (see 3.4.1)

n) the UPS will switch off during a mains failure when the load is lessoad. In this way unnecessary discharging of the batteries is avoided.rn on again when mains power is restored. The default setting of the

s: activated. Changing of the setting is described in 3.4.3.

an automatic bypass switch. This switch automatically transfers theS is unable to deliver the demanded output power due to overload or will switch back to normal operation when the overload has been has dropped below alarm level.

uring bypass operation, the UPS will switch to battery operation andries are depleted, output power is lost. If the UPS functions undere conditions it may not be able to protect the load. See also 3.4.2.3. disabled: see 3.4.3.

fig. 1) at the rear of the unit into position ‘0’. If the UPS is switched offbsent for a few seconds to ensure that the connected equipment is

d, unplug the power cord from the wall outlet.

f in a programmed way: see section 3.6.2.

Page 7: Netpro Operation Manual 2k0 4k0 Va

O

GE Digital Energy g3.4 Use: Screen MenusOperation of the NetPro UPS is done via the push-buttons and the LCD screen on the front panel. Inaddition 4 LEDs inform the user about operating conditions.

Furthermore some functions of the UPS can be programmed via the RS232 communication port. Formore information see section 3.6 and chapter 4.

The messages displayed on the LCD screen can be divided into three menus:• Default menu• Status and alarm menu• Setup menu

If the UPS operates under normal conditions, the LCD shows the standard menu. The message showndepends on the operating mode of the UPS. From any menu, the LCD screen will always return to thestandard menu after a push-button inactivity time-out of 20 seconds.If the operating conditions change, e.g. by a mains failure or rise of temperature, a ! mark will appear inthe right lower corner of the display. With key #### (18) you can enter the status and alarm screens.The setup menu allows you to program the UPS. To enter the menu press #### (18) until the menu isreached. You can scroll through the individual setup screens with $$$$ (20) and #### (18).

3.4.1 Default menu

Under normal operating conditions (see 3.3.1), the LCD shows a default screen (the mentioned valuesare examples):

230V = the true RMS input voltage12 = time until sleep in minutes, if activated23min = the calculated available runtime, at present load. The

*

I

*

I

0123''40'''0156748023"''''''940/

calculation is based on two figures: the capacity of thebattery set and the energy consumption of the actualload. If the load increases, the runtime will decrease andthe runtime figure in the display will be refreshed within asecond.

1520VA = actual output power of the UPS* in VA912W = actual output power of the UPS* in W

Display will only show the output power if it exceeds 25VA.

f the NetPro UPS operates on battery, the screen shows:

- - -V = The input voltage is too low to be measured12 = time until sleep in minutes, if activated23min = the calculated available runtime, at present load. The

0123''40'''0156748023"''''''940/

calculation is based on two figures: the capacity of thebattery set and the energy consumption of the actualload. If the load increases, the runtime will decrease andthe runtime figure in the display will be refreshed within asecond.

1520VA = actual output power of the UPS* in VA912W = actual output power of the UPS* in W! = blinking signal in case of status change or new alarm

Press #### (18) to display the accompanying message(s),see 3.4.2. The ! sign will disappear from the display, untilthe next status change or new alarm.

Display will only show the output power if it exceeds 25VA.

f the NetPro UPS operates on bypass the default screen will change into:

225V = the true RMS bypass input voltageBypass = operating mode: bypass operation

0083''40''!&:"((;

PM_NPE_XXX_2K0_4K0_1GB_V040 6 NetPro 2000-4000: user manual 4.0 (GB)

Page 8: Netpro Operation Manual 2k0 4k0 Va

OPM_NPE_XXX_2K0_4K0_1GB_V040 7 NetPro 2000-4000: user manual 4.0 (GB)

GE Digital Energy g3.4.2 Status messages and alarm messages

The NetPro UPS alerts the user with a blinking ! signal on the LCD that the status has changed or that analarm situation occurs. The accompanying screen messages appear after the push-buttons $$$$ or #### havebeen pressed. The blinking ! signal will disappear from the display (see also 3.4.1).

3 kinds of messages can be displayed on the LCD:

- status indications indicate the UPS operating mode(3.4.2.1)

- low priority alarms indicate abnormal operating situations; the screen message is accompa- (3.4.2.2) nied by a 1x per 8 secs. sounding buzzer. The buzzer is resettable with the

OK button (19), but only after the default screen is displayed again.In case of 'weak mains' the yellow LED (16) on the front panel illuminatesand the buzzer remains silent.

- high priority alarms indicate situations in which the connected load is at risk as a proper output (3.4.2.3) voltage of the UPS is no longer guaranteed; immediate action should be

taken. The screen message is accompanied by a red LED 'alarm' and a 1xper second sounding buzzer. The buzzer is resettable with the OK button(19).

Table 1 shows an overview of all messages

Message text Kind of message

Status indication High priorityalarm

Low priorityalarm

On line !

On battery ! !

On bypass ! !

Error !

Battery low !

Fan error (NetPro 3/4k) !

Overload !

Output error !

High temperature !

Input converter error !

Charger error (NetPro 2k) !

Charger error (NetPro 3/4k) !

Temperature !

Replace battery !

Bypass error !

Progr.outlet off (NetPro 3/4k) !

Input error !

Weak mains !

Table 1: NetPro screen messages

Page 9: Netpro Operation Manual 2k0 4k0 Va

O

GE Digital Energy g3.4.2.1 Status messages

Normal operating mode: the mains input voltage is present.

3

+7<=67>

During a power failure, i.e. whenever the mains input voltage is outsidethe input voltage range, the UPS uses the energy stored in its internal

+7'?@AA>BC

battery. The remaining runtime, displayed in the default screen, countsdown until either the mains returns or the batteries are empty. See also3.5.

Bypass mode: the load is directly connected to the mains supply. See

+7'?CD@EE also 3.3.4

.4.2.2 Low priority alarm messages

First line: ‘error’

$BBFB Second line: specified as indicated below

The battery voltage exceeds 13.8Vdc/battery. If this is not caused by anexternal battery charger, contact your dealer.

$BBFB

GH@BI>B'>BBFB

The operating temperature can rise intolerably as a result of:! extreme environmental temperature! lack of proper ventilation

$BBFB#>5D>B@AJB>

! overloadWhen the alarm 'temperature' is generated (low priority, red LED 'alarm'is out), check these conditions to avoid a further rising of thetemperature which might result in a transfer to bypass, a UPS shut downor damage to the UPS.

Either the batteries are almost chemically worn out or the battery wiring,including the battery fuse, is faulty. If the batteries are aged, they mustbe replaced as soon as possible to ensure full protection for your

$BBFB%>D=@K>'?@AA>BC

equipment (see section 6.2). Perhaps the 'replace battery' alarm occursafter a manual test which you started immediately after installation orafter a power failure. In this case the alarm may be incorrect as thebatteries have been (partly) discharged during transport/storage orduring the power failure. Allow the UPS to recharge the batteries.

The mains voltage or mains frequency are outside bypass inputtolerance but inside UPS input tolerance (see chapter 8). Bypassoperation is inhibited: if for whatever reason the UPS is not able to

$BBFB!CD@EE'>BBFB

deliver the required output, output power is lost. If the input frequency isoften out of tolerance – during which bypass operation is inhibited andan alarm is generated – it may be useful to disable the bypass functionafter which the unit operates as a UPS without automatic bypass switch.

NetPro 3000/4000 only: The programmable outlet (4a, fig. 1) isswitched off. For more information see section 3.4.3 'PROG. OUTLET'.

$BBFB:BFI-'FJADJA'FLL

The input voltage is out of tolerance (see chapter 8)

$BBFBM7DJA'>BBFB

The UPS is still on-line but the incoming mains voltage dropped(instantaneously) below 187Vac. The alarm will only occur at loads lessthan 100%, as at full load the UPS switches to battery operation if the

$BBFB/>@N'5@67E

PM_NPE_XXX_2K0_4K0_1GB_V040 8 NetPro 2000-4000: user manual 4.0 (GB)

incoming mains voltage drops below 187Vac (see chapter 8 'inputspecifications'). The alarm lasts at least 15 seconds, regardless theduration of the alarm situation. This alarm is not supported by thebuzzer.

Page 10: Netpro Operation Manual 2k0 4k0 Va

O

GE Digital Energy g3.4.2.3 High priority alarm messages

First line: ‘error’Second line: specified as indicated below

$BBFB

The batteries are nearly discharged. Controlled shutdown of anycomputer equipment is absolutely necessary at this point.If the NetPro UPS is operating at 100% load, the shut-down procedure

$BBFB!@AA>BC'=FO

should be completed within 2 minutes after the 'battery low' alarmstarted. If only part of the output capacity of the UPS is used this periodcan be longer, with aged batteries this period can be shorter.When the batteries are fully discharged, the UPS is no longer able topower the connected equipment.

NetPro 3000/4000 only: fan is blocked or defective.

$BBFBP@7'>BBFB

The demanded power of the equipment exceeds the normal capacity ofthe UPS. The message is displayed when the load is > 100%. If the loadexceeds 150% the UPS will immediately switch to bypass, assuming

$BBFB+Q>B=F@R

that the conditions for a transfer to bypass are fulfilled. If an overloadsituation between 100-150% persists, the UPS can eventually alsoswitch to bypass operation. If a transfer to bypass is inhibited (due tovoltage or frequency errors of the mains supply), or if the bypassfunction has been disabled (see 3.4.3) the UPS may automaticallyswitch off within a few seconds (load dependent). Output power is lost atthat moment.To avoid these problems, be absolutely certain that the power demandsof the protected equipment are within the limits of the UPS.

The output voltage drops below 207Vac. This situation can occur duringan overload, with either the bypass disabled or during battery operation.

$BBFB+JADJA'>BBFB

If during a 'temperature' alarm the operating temperature of the UPS isallowed to increase further, a high priority alarm will follow: the screenmessage changes and red LED 'alarm' on the front panel illuminates. If

$BBFBS6IH'A>5D>B@AJB>

the UPS operates in 'on line' mode, it will switch to bypass mode (ifallowed, see explanation in section 'overload' above) until thetemperature is normal again*. If however the UPS operates 'on battery',a shutdown will occur and output power is lost.

* If the UPS is equipped with an isolation transformer (NetPro+), thetemperature of the transformer may rise to an intolerable level duringbypass operation. In this case the UPS will shut down, too.

Input converter defective. Please contact your dealer.

$BBFBM7DJA'KF7Q>BA>B

PM_NPE_XXX_2K0_4K0_1GB_V040 9 NetPro 2000-4000: user manual 4.0 (GB)

Page 11: Netpro Operation Manual 2k0 4k0 Va

O

GE Digital Energy g3.4.3 Setup Menu

The 'setup screens' allow you to program the NetPro UPS, to read several operating parameters and totest parts of the system. To enter the setup screens from a default screen, press the #### key (18) until thefirst of the setup screens appears (the mentioned values are examples):

NetPro 3000 = UPS type,V06 = software version numbersecond line = serial number

P

Pf

CUc(O

BPd

Pb

T

*

*>A:BF'1222''32T*:12"2UV9W08:24U

ressing #### (18) displays the second setup screen:

80% = the available battery capacity, as % of:14.2Ah = the battery capacity, either the set capacity

or the result of a deep battery test (see 3.6.6)

!@AA>BC'K@D@K6ACX2Y'''''''4U-0"H

ressing #### (18) displays the third setup screen. The upper line of the screen shows a programmable UPSunction; the lower line shows its actual setting.

hanging settings:sing $$$$ (20) and #### (18) you can scroll through the several setup screens; OK (19) confirms a screenhoice. Subsequently '+' and '-' are displayed, and a proper setting for the function can be selected with $$$$20) and #### (18), and stored with OK (19). If a setting is stored, '+' and '-' will disappear.ne of the default screens will appear after 20 seconds of no key activity,

locking settings:ressing OK (19) and #### (18) simultaneously in a default screen during at least 2 seconds blocks theisplay of all setup screens described below. The display shows during 5 seconds:

($##M*Z(.+G[$\

ressing OK (19) and #### (18) simultaneously in a default screen during 2 seconds again releases thelocking of the setup screens. The display shows during 5 seconds:

($##M*Z(,*.+G[$\

PM_NPE_XXX_2K0_4K0_1GB_V040 10 NetPro 2000-4000: user manual 4.0 (GB)

able 2 gives an overview of all programmable functions, ranges and settings:

Screen text Range Default

NP 3000/4000 only:Prog. outletIf set 'AUTO': Off auton. time

ON/OFF/AUTO

0 - 60 min.

ON

0

Fr.tracking rate 2 Hz/sec or 10 Hz/sec 10 Hz/sec

Start auton. time 0 - 60 min. 0 min.

Buzzer delay 0 - 60 sec. 8 sec.

Language English, German, French,Spanish, Italian

English

No-load shutdown ON/OFF OFF

Battery capacity*(display shows no text, just a figure 4- 250)

4 - 250 Ah 7Ah

Bypass enable YES/NO YES

Output voltage* 220 / 230 / 240V 230V

Output frequency* 50 / 60 Hz 50 Hz

Restore defaults*

Restore defaults: restores the default settings except the settings marked with *

Page 12: Netpro Operation Manual 2k0 4k0 Va

OPM_NPE_XXX_2K0_4K0_1GB_V040 11 NetPro 2000-4000: user manual 4.0 (GB)

GE Digital Energy g

NetPro 3000/4000 only:One of the applicance outlets (4a, fig. 1) is programmable. Three settings are possible:

! ON! OFF! AUTO

When the UPS is started the outlet is always switched ON, but it can be switched off either manually orautomatically.With the default setting 'ON', the outlet functions similar to the other appliance outlets: it delivers outputpower as long as the output converter does. When 'OFF' is selected, the outlet switches off. When theoption 'AUTO' is selected, the system asks for the 'Off autonomy time': the remaining runtime (in minutes)at which, during a mains failure, the programmable output is automatically switched off until the mainsreturns. This way less critical equipment (e.g. screens, printer) can be switched off automatically in orderto lengthen the remaining runtime.Figure 6 shows an example. The total predicted runtime is 15 minutes, and the 'off autonomy time' hasbeen set on 5 minutes: the outlet switches off 5 minutes before the predicted end of autonomy.

As the load decreases when the outlet switchesoff, the actual remaining autonomy at the 'outletoff' moment (which was predicted at presentload) will be longer than the programmed 5-minute period.In configurations with small loads and largebattery capacities, i.e. very long runtimes, thestep size with which the runtime is counteddown can be longer than the programmed 'offautonomy time' (see section 3.5). In this casethe programmable outlet will be switched offwhen the remaining runtime is one step fromzero.

Example: suppose the runtime is counted down with 10 minute steps, and the 'off autonomy time' is setas mentioned above. Despite of the 5-minute setting, the outlet will be switched off 10 minutes (= onestep) before end of autonomy.If the step size does not exceed the 'off autonomy time', the programmable outlet will be switched off atthe programmed moment although the accuracies may not match. Example: 'off autonomy time' set at 14minutes while the step size is 10 minutes, the outlet will indeed be switched off 14 minutes before the endof the autonomy.If the option 'AUTO' is selected the programmable outlet can still be switched off manually using the frontpanel keys.Each time the mains returns, the programmable outlet will always be switched on. Therefore do not usethis outlet to switch off equipment that should permanently remain off.

The frequency tracking rate is the maximum rate at which the UPS adjusts its output frequency tofluctuations of the input frequency. If the UPS is not connected to a generator set the default setting maybe too high. Note that a change of the frequency tracking rate is coupled with a change of the trackingrange (see chapter 8, bypass).

The runtime, below which the UPS is inhibited to start up, can be set here. The UPS will first recharge itsbatteries and start up as soon as the 'start up autonomy' is available. The setting can be bypassed (seealso 3.2.3). Calculation of the 'start up autonomy' is based on the assumption that the UPS supplies 100%load.

:BFI-'FJA=>A

PB-AB@KN67I'B@A>

(A@BA'@JAF7-A65>

������������������������������������������������������������������������

15 05

mainsfailure

remaining autonomy (minutes)

outputoff

end ofautonomy

'Off autonomy time'

I4D211-9

fig. 6 Off autonomy time

Page 13: Netpro Operation Manual 2k0 4k0 Va

O

GE Digital Energy g

In case of low priority alarms (see 3.4.2.2) the buzzer will not immediately sound but only after a certaindelay in order to avoid frequent buzzer activity during momentary alarm situations (e.g. overload,temperature, weak mains). The buzzer delay time does not affect buzzer operation during alarms withhigh priority.

CS

Sloc

Inco

IftobfuIfw

T

TNfrloT

!J]]>B'R>=@C

.@7IJ@I>$7I=6EH

hanges the language of the screen messages: you can select English (default), German, French,panish, Italian.

etting ‘ON’ means that the function is activated: the UPS will switch off during a mains failure when thead is < 5% of the maximum load. Be careful with very small loads: e.g. a fax machine in stand-by modeould be recognised by the UPS as a no-load situation.

*F'=F@R'EHJARFO7

!@AA>BC'K@D@K6AC'''''''''''''W"H

order to generate reliable runtime predictions the UPS needs to be informed about the total batteryapacity. The Ah value shown in the display is the programmed capacity and should indicate the capacityf the standard internal battery plus the capacity of the battery extension pack(s).

!CD@EE'>7@?=>'''''&$(

the NetPro is supplied by a generator set, and the generator's frequency is often out of the UPS's inputlerances, frequently occurring 'bypass error' alarms (see 3.4.2.2) will be the result. During these alarmsypass operation is inhibited. To avoid this situation the bypass function can be disabled: the UPSnctions as a UPS without automatic bypass switch.

NO is selected, i.e. if the bypass function is disabled, the default screen alternates every 10 secondsith the following message, displayed during 2 seconds:

/"%*M*Z!CD@EE'R6E@?=>R

+JADJA'QF=A@I>'''''0123

he output voltage can be set to 220/230/240 Vac.

+JADJA'LB>^J>7KC'''''82S]

PM_NPE_XXX_2K0_4K0_1GB_V040 12 NetPro 2000-4000: user manual 4.0 (GB)

he output frequency can be set to 50/60 Hz.OTE: The unit can be used as a frequency converter: the input frequency range is 45-66Hz, the outputequency is selectable 50/60Hz. If the unit is used as a frequency converter, the bypass function is nonger available. As a result an audible alarm will be generated continuously (see 3.4.2.2 ‘Bypass error’).o avoid this, we advise to disable the bypass (see above).

WARNING:Changing of the output frequency can cause severe damage of equipment connected tothe appliance outlets of the UPS: Be sure that the new frequency is suitable for theconnected equipment!

Page 14: Netpro Operation Manual 2k0 4k0 Va

O

GE Digital Energy g3.5 Runtime: calculation and indicationThe available runtime is displayed in the default screen, and is counted down during battery operationuntil either the mains returns or the batteries are empty.

Normally, i.e. if the runtime is less than 100 minutes, the runtime is calculated in minutes, and the stepsize of the changes is one minute. In case of small loads and/or battery extension packs the availableruntime can be substantially longer. The accuracy of the runtime calculations however is limited: approx1% of the initial runtime.For this reason the measuring unit and step size will change at longer runtimes: if for example the runtimeis between 200 and 500 minutes the step size is 5 minutes; if the runtime is > 5000 minutes the runtime iscalculated in hours and the step size is 2 hrs. The following table gives an overview:

Runtime Rt, in minutes Unit Step size

Rt < 100 minutes 1 minute

100 ≤ Rt < 200 minutes 2 minutes

200 ≤ Rt < 500 minutes 5 minutes

500 ≤ Rt < 1000 minutes 10 minutes

1000 ≤ Rt < 2000 minutes 20 minutes

2000 ≤ Rt < 5000 hours 1 hr

Rt ≥ 5000 hours 2 hrs

Please note that unit and step size do not change during countdown: the initial units and step sizesremain unaltered, until eventually the batteries are empty.If during battery operation the available runtime becomes less than the step size it will be shown as '< S',where S is the step size. If for example the initial autonomy was 1200 minutes, i.e. between 1000 and2000, the countdown occurs with steps of 20 minutes each, and during the last 20 minutes before thebatteries are empty the runtime will be displayed as '< 20 min'.

3.6 Other Features

3.6.1 Shutdown

Using communication capabilities, the computer can direct the UPS to turn itself off following controlledshutdown of the system. Subsequently the UPS will remain off for at least 30 seconds. LED 'operation' willgo out. The unit will start up again as soon as the mains returns (and, if activated, the start-up runitme isavailable).

3.6.2 Programmed shutdown

The UPS monitoring software allows you to program a 'sleep period' of the UPS by sending twocommands to the UPS:

- shut down after # minutes, and subsequently:- shut down during # hours.

The first command indicates the period of time after which the UPS should 'fall asleep', the secondindicates the duration of the sleep period. After the first command LED 'prog shutdown' starts blinking andthe standard screen shows the time until sleep (see 3.4.1). In the 'sleep'-mode LED 'operation' is off, LED'progr. shutdown' is on, and the LCD shows the remaining sleep time:

Dsdpa

Tc

#65>'J7A6='O@N>_SS_``_((

PM_NPE_XXX_2K0_4K0_1GB_V040 13 NetPro 2000-4000: user manual 4.0 (GB)

uring the 'sleep period' the UPS is not completely switched off as it has to keep track of the remainingleep time. However, if a mains failure occurs during the sleep period and the battery capacity eventuallyrops below 80% of the normal capacity, the UPS will automatically switch off in order to save batteryower. When the mains returns the UPS will start up automatically (as soon as the start-up runtime isvailable, if this feature is activated). The programmed sleep time however is lost.

he programmed shutdown in progress can be cancelled: press the OK button during 10 seconds toancel shutdown and switch the UPS on.

Page 15: Netpro Operation Manual 2k0 4k0 Va

O

GE Digital Energy g3.6.3 Front panel test

Proper functioning of all indicators on the front panel can be tested. From a default screen, press the $$$$key (20) until the display shows

Key OK (19) confirms the selection. Subsequently all LEDs will blink, the buzzer will sound intermittently,and all characters in the LCD will illuminate and gradually disappear: the upper row from the right, thelower row from the left.After succesful completion of the front panel test the LCD screen should display

3

Aat

M

F

(pP

T

BVBVT

N

IgNgt

PBF7AD@7>='A>EA

PBF7AD@7>='A>EAA>EA'+[

.6.4 Quick battery test

utomatic test: The NetPro UPS conducts periodic automatic battery tests to ensure that the batteriesnd the wiring are healthy and able to support power failures. The tests do not cause any interruption in

he function of the unit and are conducted at the following times:· 5 hours after manual switch-on· 5 hours after return of mains following any power failure, and· 30 days from the last battery test.

anual test: A manual quick battery test can be activated- either through an interface kit, via the RS232 Interface Port (please refer to the manual of your

interface package), or- via the front panel with the push-buttons ####, OK and $$$$. The procedure is as follows:

rom a default screen, press push-button $$$$ (20) until the display shows

!@AA>BC'A>EA

If no test has been performed since switch-on, the second line of this screen shows 'NO RESULT' untilush-button 'OK' is pressed).ush-button OK (19) confirms the selection, and the screen shows:

!@AA>BC'A>EA!JEC'A>EA67I

PM_NPE_XXX_2K0_4K0_1GB_V040 14 NetPro 2000-4000: user manual 4.0 (GB)

he test status (indicated by the second line) can be:

USY TESTING = testing OUTPUT TOO LOW = output voltage too low for succesful completion of the testAD BATTERY = the batteries should be replaced BATT TOO LOW = battery voltage too low to start the testEST OK = battery has been tested with positive result

OTE: the test only gives a reliable result if- the load exceeds >30% of the rated output power,- the batteries are > 95% charged.

f the batteries are dangerously close to being worn out, a low priority alarm 'replace battery' will beenerated (see 3.4.2.2). The batteries must be replaced as soon as possible (see section 6.2).OTE: If the manual test is started immediately after installation or after a power failure, the UPS mayenerate a false 'replace battery' alarm as the batteries have been (partly) discharged during

ransport/storage or during the power failure.

Page 16: Netpro Operation Manual 2k0 4k0 Va

O

GE Digital Energy g3.6.5 Battery calibration test

From a default screen, press the $$$$ key (20) until the display shows

ThhtIb

D33c

3

TP

G@=6?B@A>'?@AA+[

PM_NPE_XXX_2K0_4K0_1GB_V040 15 NetPro 2000-4000: user manual 4.0 (GB)

he default setting of the capacity normally results in a reliable runtime prediction. Local circumstancesowever (e.g. low ambient temperature) may cause the prediction to be unreliable. In this case you canave the UPS to recalculate the battery capacity. The predicted runtime shown in the display is 10% lower

han calculated in order to balance out small changes in load, ambient temperature and battery condition.n order to keep track of the capacity deterioration due to aging of the batteries, we advise to perform aattery calibration test at least once per year.

uring a battery calibration test the batteries will be discharged to 'battery low' alarm level (see section.4.2.3 'battery low'). The test will result in a new capacity indication in the second setup screen (see.4.3) and, after complete recharge, new runtime predictions. Please note that immediately after a batteryalibration test the expected runtime time is very short: allow the UPS to recharge its batteries.

.6.6 Deep battery test

his test, initiated by UPS monitoring software, is identical to a 'battery calibration test' (see above).lease refer to the manual of the appropriate monitoring software package for more information.

Page 17: Netpro Operation Manual 2k0 4k0 Va

OPM_NPE_XXX_2K0_4K0_1GB_V040 16 NetPro 2000-4000: user manual 4.0 (GB)

GE Digital Energy g

4.1 RS232 Port (fig. 7)

The RS 232 Port is a plug-in interface port (9-pin, Sub-D, male) which enables advanced communicationbetween the UPS and the computer (UPS software required). The interface port is operative as soon asthe mains power cord is plugged into a live wall outlet, even if the UPS is switched off.We strongly recommend to use only original GE Digital Energy software products in combination withthe interface port.

Pin # Function 1 RS232 input (UPS shutdown) 2 RS232 output 3 General alarm1)

4 Plug and Play 5 Common 6 Bypass active 7 Battery low 8 UPS connected 9 Mains failure

1) Active if the output voltage of the UPS is no longer guaranteed due to other circumstances thanalready indicated by pin 6-7-9:

- Output converter overload- Overtemperature (pre-)alarm- Battery failure- Fan failure- High charger voltage- Bypass out of limits- Inverter shutdown (due to inverter failure or batt. failure)

4.2 Relay Interface Card (option)

The card is equipped with potential free change-over contacts for the following alarms:• mains failure• general alarm• battery low• bypass active

For more information please refer to the user manual that comes with the interface card.

4.3 SNMP Interface Card (option)

This card allows the data interface to be connected directly to an Ethernet network.For more information please refer to the user manual that comes with the interface card.

fig. 7

RS232

DCUPS

DATA TO UPS

DATA FROM

MAX: +48V 100mA

BYPASS ACTIVE

BATTERY LOW

GENERAL ALARM

MAINS FAILURE

REMOTE UPSSHUT DOWN

RS232PORT

5 = COMMON8 = UPS CONNECTED

RS232

DC

RS232

2

6

5

1

7

3

849

DCPnP

4 - Communication

Page 18: Netpro Operation Manual 2k0 4k0 Va

OPM_NPE_XXX_2K0_4K0_1GB_V040 17 NetPro 2000-4000: user manual 4.0 (GB)

GE Digital Energy g

Apart from the options described in 4.2 and 4.3 the following options are possible:

5.1 Extended Runtime (NetPro 2000/3000)Extended runtime can be obtained by connecting a separate battery extension pack to the UPS. In thiscase the UPS must be informed about the new total battery capacity to allow a reliable recalculation of theavailable runtime (see section 3.4.3). Dependent of the charge condition of the new batteries the newruntime calculations may temporarily be unreliable.The additional batteries increase the runtime and recharging time for the unit, all other operationalinformation is the same as for standard models. It is not allowed to connect an external charger to theUPS!

5.2 Isolation Transformer (NetPro 2000/3000)Units equipped with a temperature protected isolation transformer ("NetPro +") are housed in a largercabinet than the standard unit. The isolation transformer allows the output neutral to be connected to

- protective earth (default setting)- the input neutral

or be isolated. Please contact your dealer.

5.3 PowerFLAG SerVICe Box for Modem ConnectionIf you connect the PowerFLAG SerVICe Box between the communication port of the UPS and a modem,a programmed number can be dialed in case of a UPS alarm. It also allows service personnel to dial inand check the status of the UPS to perform remote diagnostics. This way service costs, specially inremote areas, can be reduced considerably.

6.1 GeneralThe UPS is virtually maintenance free: take care of proper environmental conditions and keep airinlets/outlets free of dust. Please read 2.1.

6.2 BatteriesThe service life of the battery is from 3 to 6 years, depending on the operating temperature and on thenumber of discharge cycles.

As a healthy battery is critical to the performance of the UPS, an automatic quick battery test is performedregularly to ensure failsafe operation (see section 3.6.4). When the condition of the battery is critical, a'replace battery' alarm will be activated (see 3.4.2.2). Have your dealer replace the batteries as soon aspossible.

NOTE: under certain circumstances a manual battery test can result in a false alarm: please see 3.6.4'quick battery test'.

Regular deep battery tests are advised in order to re-calibrate the capacity of aging batteries. Sections3.4.3 'battery capacity' and 3.6.5 give more information.

5 - Optional Features

6 - Maintenance

Page 19: Netpro Operation Manual 2k0 4k0 Va

OPM_NPE_XXX_2K0_4K0_1GB_V040 18 NetPro 2000-4000: user manual 4.0 (GB)

GE Digital Energy g

Whenever a malfunction occurs, first check external factors (e.g connections, temperature, humidity orload) to determine whether the problem is caused by the unit itself or by its environment. Subsequentlycheck the thermal circuit breaker: it may be tripped. If so: reset it (see 1, fig.1) and be sure that the UPS isnot overloaded.The following chart is a simple troubleshooting checklist only. If the suggested solution does not succeed,or if the information is insufficient to solve the problem, please contact your dealer or consultwww.gedigitalenergy.com.

PROBLEM POSSIBLE CAUSE SOLUTION

UPS overload Reduce load, reset TCB(1, fig. 1)

Thermal Circuit Breaker (TCB)tripped

System failure Contact your dealer or consultwww.gedigitalenergy.com

Most probably an overload See 3.4.2.3, reduce the loadLCD message 'on bypass'

Overtemperature See 3.4.2.3Allow the UPS to cool down

Line cord not connected Read 2.2Connect line cord

Batteries not connected Contact your dealer or consultwww.gedigitalenergy.com

Dead wall socket outlet, ormains voltage out of limits

Contact qualified electrician

UPS overtemperature See 3.4.2.3Allow UPS to cool down

Runtime too low to start up See 3.2.3, wait or press OK

UPS will not switch on (withoutusing 'battery start')and the output has been off fora few secs.

Tripped Thermal Circuit Breaker See above

UPS switched off automatically UPS overtemperature See 3.4.2.3Allow UPS to cool down

Mains failure, batterydischarged

Wait until mains returns

Programmed shutdown inprogress

See 3.6.2

UPS received shut downcommand from computer duringmains failure

See 3.6.1

The load is < 5% of the max.load and no mains power ispresent.(No-load shutdown function isactive, see 3.3.3)

Wait until mains returns

LCD message ‘replace battery’ Battery test just after installationor mains failure

Allow the UPS to recharge thebatteries

Battery test shows weak battery Read 6.2, replace batteries

7 - Troubleshooting

Page 20: Netpro Operation Manual 2k0 4k0 Va

OPM_NPE_XXX_2K0_4K0_1GB_V040 19 NetPro 2000-4000: user manual 4.0 (GB)

GE Digital Energy g

NetPro model : 2000 3000 4000

RatingsVoltage Amperes (VA) : 2000 3000 4000with computer type loadWatts (W) : 1200 1800 2400with resistive loadInput thermal circuit breaker (A) : 10 14 16

Input converterAC input voltage : 220 - 240 VAC input voltage range : 100% load: 187 - 264 V

60% load: 160 - 264 V 30% load: 125 - 264 V

Maximum start-up AC voltage : 255 V (at any load)Minimum start-up AC voltage : 187 V (at any load)Input current waveform : sinusoidalInput power factor : 1Input frequency range : 50 or 60 Hz ± 10%Input current (A) : 6.6 10.0 13.5

Output converterAC output voltage : 220/230/240 V (selectable)AC output voltage tolerance : ± 1%Output frequency : 50 or 60 Hz ± 0.15% unless synchronized to the mainsOutput waveform : sine waveHarmonic distortion : < 2% (typical 1.5%) with linear loadPower factor : 0.6Crest factor (peak to RMS current) : up to 6:1Capacity appliance outlets : max. 10 A per outlet

BypassAC input voltage range : 187 - 264 VFrequency tracking rate : max. 2 or 10 Hz/sec.(selectable, factory setting 10Hz/sec)Frequency tracking rate : 2 Hz/sec 10 Hz/secFrequency tracking range : nominal ± 2% nominal ± 10%Phase difference : < 7° < 10°Transfer time : < 1 msec.

Overload capabilityThe UPS is fully protected against overloadOverload behaviour:on-line operation, bypass enabled : 110% during 5 minutes, 150% during 2 secondson-line operation, bypass disabled : 110% during 110 secondsbattery operation, NP2000 : 110% during 5 minutes, >135% during 110 secondsbattery operation, NP3000/4000 : >110% during 110 secondsbypass operation : depends on rating of thermal circuit breaker; typical

: 105% of TCB value: no trip135% of TCB value: trip within 1 hour200% of TCB value: for 2 - 30 secs300% of TCB value: for 0.8 - 4 secs.

Batteries (ratings given for 25°C)Nominal voltage (V) : 72 108 120Number of 7 Ah batteries : 6 9 10Type : sealed and maintenance freeService life : 3 - 6 years (depending on use)Battery recharge current : 1.5 ABattery recharge time : 2 - 6 hours for 80% capacity, std. batteryAutomatic battery test : see 3.6.4Runtime in minutesat typical load (75%) : 7 7 7 Watts

60 190 270 310120 117 165 185240 60 95 105360 38 63 72600 21 35 40900 13 22 25

1200 9 15 181800 - 9 10

GeneralWeight (kg) : 27 38 42Dimensions (hxwxd, mm) : 293x220x557Enclosure / protection : steel-plastic / IP20

EnvironmentSafety : EN 50091-1-1; EN 60950; IEC 950Electromagnetic compatibility : EN 50091-2; EN 50081-1 + EN 50082-1; IEC 801-5: 6kVAmbient temperature : -10 to +40°CAudible noise at 1 meter : 45 dB(A)

The audible noise is load and temperature dependentMax. relative humidity : 95% (non-condensing)

8 - Specifications