TRANSCRIPT

Page 1: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Pro

fessio

na

l |

Dis

cip

lin

ed

| R

ele

ntl

ess |

Se

rvic

e

NEW TRENDSin

AC & LIGHTNING MITIGATION

Clay Brelsford

Bass Engineering Company

54th SIEO/NACE Winter Symposium

Sun Valley, ID

January 10, 2019

Page 2: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

AC Interference

Co-Location

Pipelines

HVAC Power Systems

Creates Complex,

Electro-magnetic Interaction

Page 3: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Capacitive Coupling

Electric Field Influence

Page 4: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

AC Power

Induced AC

Inductive Coupling

Magnetic Field Influence

Page 5: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Resistive Coupling

Fault or “Short-Circuit” HVAC ConditionsLightning

Shared Conductive Path

Page 6: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

AC Interference = Risk

• Personnel• Step-Step Potential• Step-Touch Potential

• Pipeline Equipment• Metering• Electrical Isolation

• CP System• ICCP/GCP Damage

• Pipeline• AC Corrosion

Page 7: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Resistive CouplingFault or “Short-Circuit” HVAC Conditions

Page 8: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

AC Corrosion Morphology

Coating Deformation

Tubercle Pits Within Pits

Page 9: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

ACCD AC Corrosion Risk

< 20 A/M2 Low Risk

20-100 A/M2 Medium Likelihood

> 100 A/M2 Very High Likelihood

Technical Service | Installation | Material Sales

AC Corrosion & AC Current Density

Expressed as a Function of AC Voltage & Soil Resistivity

Page 10: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Risk Factors

Multiple

Dynamic

Interactive

Geezzzz…Can I Get Some Help Here?

Page 11: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Federal Law

• 49 CFR 192.467 (f)• External Corrosion Control; Electrical Isolation

• 49 CFR 195.575 (e)• External Corrosion Control; Electrical Isolation

• 29 CFR 1910

• 29 CFR 1926

Yea…Not Really What I was Looking for….

Page 12: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

NACE• NACE SP0177-2014

• Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems

• NACE SP21424-2018• Alternating Current Corrosion on Cathodically Protected Pipelines:

Risk Assessment, Mitigation, and Monitoring

• AC Corrosion State-of-the-Art Report: Corrosion Rate, Mechanism, & Mitigation Requirements #35110

• NACE SP0104-2014• The Use of Coupons for Cathodic Protection Monitoring

• Technical Report on the Application & Interpretation of Data from External Coupons Used in the Evaluation of Cathodically Protected Metallic Structures #35201

Page 13: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Other• Canadian Standard

• CAN/CSA – C22.3 No. 6-13• Principles and Practices of Electrical Coordination Between Pipelines and Electric

Supply Lines

• European Standard• BS EN 15280:2013

• Evaluation of AC Corrosion Likelihood of Buried Pipelines Applicable to Cathodically Protected Pipelines

• Interstate Natural Gas Association of America (INGAA)• Criteria for Pipelines Co-existing with Electric Power Lines; 2015-04 Final

Report

• National Electric Code (NEC), Article 250• Grounding & Bonding

• Institute of Electrical & Electronic Engineers (IEEE)• PRCI

• On-going Research; EC 6-2, EC 6-4

Page 14: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Confused?

Page 15: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

AC Interference Threat Risk Assessment

RECEPTOR

LOCATION

MECHANISM

THREAT

An object impacted by an abnormal event or failure.Personnel, PL Assets, CP Systems

A position or site marked by some distinguishing feature.Aboveground appurtenances, station numbers

A natural or established process by which something takes place or is brought about.

Capacitive, Inductive & Resistive Coupling

An indication of something impending.Elevated AC potentials, elevated AC current density,

step/touch potentials

Something that actively contributes to the production of a result.

Lateral separation distance, co-location length, crossing angle, soil resistivity, HVAC current, etc.

FACTORApply Industry Risk Concepts

Page 16: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Threat Risk Assessment; Resistive Coupling

RECEPTOR

LOCATION

MECHANISM

THREAT

PersonnelElectrical Isolation

Valve setting; ID by station #

Resistive Coupling

Elevated AC potentialsStep-touch potentials

Lateral separation distanceSoil resistivity

FACTOR

Page 17: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

AC Threat Risk Factors

Geospatial

Relationship

Collocation Length*

Lateral Separation Distance*

Crossing Angle*

1Environmental

Conditions

Soil Resistivity*

AC Current Density

3Pipeline

Design

Cased Crossings

Aboveground Appurtenances

Coating Resistance

4HVAC System

Operating

Parameters

HVAC Current*

HVAC Voltage

2

Fault Current Load

*

Page 18: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Over 7,000 miles of

transmission PL and

large diameter

distribution mains

serving several rural and

major metropolitan areas

Assets spread over six

environmental

geographies

Wide ranging pipe

design and operating

parameters

Identify & Prioritize

Page 19: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Analyze HVAC Data

Obtained 41,322 miles of

HVAC centerline and

operational data from Platts,

PennWell, & RexTag

Converted Rated Voltage

to AC Current

70-138 kV

0-69 kV

138-230 kV

231-345 kV

346-500 kV

Page 20: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Geospatial Analysis; PL & HVAC System

Utilize GIS tools to determine

•Lateral separation distance

•Co-location length

•Co-location angle

•Crossing angle

Page 21: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Geospatial Analysis; Soil Resistivity

Vast pipeline system

spread across 6

geographical regions

Acquired USGS

SSURGO soils data

Utilize UGIS tools to

determine soil resistivity

for co-location

Page 22: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

AC Threat Risk Analysis

Import GIS Data into RIPL

Separation Distance

Co-location Length

Co-location Angle

Crossing Angle

HVAC Voltage

HVAC Current

Soil Resistivity

Combined with Existing:

Pipe Coating Resistance

Create Threat Ranking

Analysis dynamically segmenting and

ranking PL based on specific factors

combined into a threat score

Page 23: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Engineered Field Analysis

• Differentiate above & below ground assets• Design gradient control mats

• Identify electrical isolation locations• Design decoupler installations

• Design engineered grounding system locations• Incorporate “natural” grounding

• Address lightning mitigation

• Address safe arc distance• Substations, guy anchors, etc.

• Incorporate AC mitigation system monitoring

Page 24: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

AC & Lightning Mitigation Tools

• Engineering Controls

• Decoupling Devices

• Engineered Grounding Systems

• Gradient Control Mats

• Coupon Test Stations

Page 25: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Signage

Page 26: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Dead Front Test Stations

Page 27: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Decoupling Devices

Polarization Cell

Solid State Decoupler

(SSD)

Polarization Cell Replacement (PCR)

Zinc Anode Pair

Page 28: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Engineered Grounding Systems

Deep Vertical Point Ground (DVPG)

PCR

Pipeline

Page 29: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Engineered Grounding Systems

PCRLinear Ground Linear Array

PCR

Page 30: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Engineered Grounding Systems

Natural Grounds

Pipeline Casing

Page 31: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Gradient Control Mats

Magnesium Anode

Page 32: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Gradient Control Mat Assembly

Exothermically Welded @ Seams on 18” Centers

Page 33: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Lead Length is Critical!

Pin Brazed Connections

Page 34: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Monitoring

• Measure PL AC & DC P/S Potentials

• Measure AC & DC Current

• Calculate PL AC & DC Current Density

Page 35: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Remote Monitoring w/ CTS

Page 36: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

The Complete Package

• AC Threat Risk Analysis• Prioritize pipeline assets at risk

• Engineered Field Analysis• Gather critical field data

• Soil resistance

• Electrical isolation locations

• Aboveground assets/security dimensions

• Cased crossings

• HVAC guyed anchors

Page 37: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Summary• AC Interference is Complex

• Influenced by Design & Operating Conditions…Dynamic!

• Design Protocol• AC Threat Risk Analysis w/ Engineered Field Design

• Integrated ACLM Solution Using Multiple AC Mitigation Tools

• Monitor!!

Page 38: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

Technical Service | Installation | Material Sales

Clay Brelsford

Bass Engineering Company

[email protected]

903-759-1633

Page 39: NEW TRENDS in AC & LIGHTNING MITIGATION...•Mitigation of Alternating Current and Lightning Effects on Metallic Structures and Corrosion Control Systems •NACE SP21424-2018 •Alternating

All copyrightable text, photography and graphics, arrangement, and

presentation of all materials, and the overall design of this presentation are ©

Bass Corrosion Services, Inc. d/b/a Bass Engineering Company. All rights

reserved. Other product names, logos and brands are property of their

respective owners.

Permission is granted to download and print materials from this presentation

for the purpose of viewing, reading, and retaining for reference. Any other

copying, distribution, retransmission, or modification of information or materials

in this presentation, whether in electronic or hard copy form, without the

express prior written permission of Bass Engineering Company is strictly

prohibited.