AHT-17-02-C NORSEMAN AURA CONFIGURATION #1 MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTS INSTALLED WITH MAXIHEAT STANDARD IRONBARK DEFAULT FLUE KIT WITH DOUBLE SHIELDS Floor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal conductivity not greater 0.33W/m°K. The top surface of the floor protector must be no less than 40mm above the floor, whether solid or with an air space beneath. Appliance Base Width = 1190 mm (1071) 1190 min 375 to heater body 175 1205 400 to front of Appliance Base 400 to front of Appliance Base 75 75 1221 905 10 1210 1221 With heater body in centre of bench With heater body to side of bench 910 400 to front of Appliance Base 1221 616 616 (355) 300 MXTHCNRBLK2/GRY2 (548) (484) (621) 300 MXTHCNRBLK2/GRY2

Upload: others

Post on 03-Oct-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

AHT-17-02-C

NORSEMAN AURA

CONFIGURATION #1MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTS INSTALLED WITH

MAXIHEAT STANDARD IRONBARK DEFAULT FLUE KIT WITH DOUBLE SHIELDS

Floor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and athermal conductivity not greater 0.33W/m°K. The top surface of the floor protector must be

no less than 40mm above the floor, whether solid or with an air space beneath.

Appliance BaseWidth = 1190 mm

(1071)

1190 min

375to heater

body

175

1205

400to front of

Appliance Base

400to front of

Appliance Base

7575

1221

905

10

12101221

With heater bodyin centre of bench

With heater bodyto side of bench

910400

to front ofAppliance Base

1221

616

616

(355)

300

MXTHCNRBLK2/GRY2

(548)

(484)(621)

300

MXTHCNRBLK2/GRY2

Page 2: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

AHT-17-02-C

NORSEMAN AURA

CONFIGURATION #2MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTS INSTALLED WITH

MAXIHEAT DECROMESH DEFAULT FLUE KIT WITH INNER & OUTER SHIELDS

Floor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and athermal conductivity not greater 0.33W/m°K. The top surface of the floor protector must be

no less than 40mm above the floor, whether solid or with an air space beneath.

Appliance BaseWidth = 1190 mm

With heater bodyin centre of bench

With heater bodyto side of bench

(548)

MXTHCNRBLK2/GRY2

300

905

1221

75 75

400to front of

Appliance Base

1205

MXTHCNRBLK2/GRY2

300

(621)(484)

400to front of

Appliance Base910

12211210

10

(380)

616

616

1221

400to front of

Appliance Base

200

350to heater

body

1190 min

(1096)

Page 3: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

AHT-16-21.1-C

NORSEMAN ECLIPSE

CONFIGURATION #1 MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTS

INSTALLED WITH MAXIHEAT STANDARD BLACK DEFAULT FLUE KIT (NO SHIELDS)

Floor Protector Minimum Requirement: 7.5 mm thick fibre cementsheet with a thermal conductivity not greater than 0.33 Wm°K

250

425

800 min

280to front of

Appliance Base

(970)

280to front of

Appliance Base

1035

275275

1221

735

Appliance BaseWidth = 598 mm

Please note: 280 mm to front ofAppliance Base is equivalent to300 mm to Firebox Door opening

1000

1000

(475)MXTH1BLK2/GRY2

300

(532)

MXTHCNRBLK2/GRY2

Page 4: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

AHT-16-21.1-C

NORSEMAN ECLIPSE

CONFIGURATION #2 MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTS

INSTALLED WITH MAXIHEAT STANDARD BLACK DEFAULT FLUE KIT WITH DOUBLE SHIELDS

Floor Protector Minimum Requirement: 7.5 mm thick fibre cementsheet with a thermal conductivity not greater than 0.33 Wm°K

MXTH1BLK2/GRY2 (475)

1000

1000

(795)

280to front of

Appliance Base

800 min

400

75

(532)

300

560

1221

860

280to front of

Appliance Base

Appliance BaseWidth = 598 mm

Please note: 280 mm to front ofAppliance Base is equivalent to300 mm to Firebox Door opening

MXTHCNRBLK2/GRY2

100 100

Page 5: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

0AM1500

NORSEMAN FORESTER

CONFIGURATION #1MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTS

INSTALLED WITH FLUE PIPE

800

356to front of

Appliance Base

356to front of

Appliance Base

845 min

1435

1221

525 525

1135

475(641)

1200 nominal

1200nominal

(86)

Appliance BaseWidth = 550 mm

Please note: 356 mm to front ofAppliance Base is equivalent to300 mm to Firebox Door opening

MXTH12BLK2/GRY2 orMXFSH12LGRY/DBLK

This hearth sits 86 mmaway from rear wall to meet

the minimum requirementfor the front hearth.

300

(214)

MXTHCNRBLK2/GRY2

This hearth sits 214 mmaway from the wall to meetthe minimum requirementfor the front hearth.

(826)

Page 6: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

0AM1500

NORSEMAN FORESTER

CONFIGURATION #2MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTS

INSTALLED WITH FLUE PIPE AND SINGLE SHIELD

Appliance BaseWidth = 550 mm

Please note: 356 mm to front ofAppliance Base is equivalent to300 mm to Firebox Door opening

(826)

MXTHCNRBLK2/GRY2

This hearth sits 214 mmaway from the wall to meetthe minimum requirementfor the front hearth.

(214)

300

1135

525525

1221

1435

356to front of

Appliance Base

(1061)

MXTH12BLK2/GRY2 orMXFSH12LGRY/DBLK

1200nominal

1200 nominal

(416)250

845 min

356to front of

Appliance Base

800

Page 7: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

0AM1500

NORSEMAN FORESTER

CONFIGURATION #3MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTS

INSTALLED WITH FLUE PIPE AND DOUBLE SHIELD

MXTH1BLK2/GRY2

800

356to front of

Appliance Base

845 min

150

(316)

1000

1000(961)

MXTHCNRBLK2/GRY2

This hearth sits 214 mmaway from the wall to meetthe minimum requirementfor the front hearth.

356to front of

Appliance Base

1435

1221

525 525

1135

300

(214)

(826)

Appliance BaseWidth = 550 mm

Please note: 356 mm to front ofAppliance Base is equivalent to300 mm to Firebox Door opening

Page 8: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

0AM1500

NORSEMAN FORESTER

CONFIGURATION #4MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTS

INSTALLED WITH FLUE PIPE AND SINGLE LENGTH DECROMESH/SHIELD

MXTH12BLK2/GRY2 orMXFSH12LGRY/DBLK

800

356to front of

Appliance Base

845 min

250(416)

1200 nominal

1200nominal

MXTHCNRBLK2/GRY2

This hearth sits 214 mmaway from the wall to meetthe minimum requirementfor the front hearth.

356to front of

Appliance Base

1435

1221

525 525

1135

300

(214)

(826)

(1061)

Appliance BaseWidth = 550 mm

Please note: 356 mm to front ofAppliance Base is equivalent to300 mm to Firebox Door opening

Page 9: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

HCMG/16/043 & HCMG/16/044

Appliance BaseWidth = 565 mm

130

350

545to front of

Appliance Base

896 min

545to front of

Appliance Base

55551115 1221

815

NORSEMAN GEN IIWITH PEDESTAL CONFIGURATION #1MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTS INSTALLEDWITH MAXIHEAT DECROMESH DEFAULT FLUE KIT WITH INNER SHIELD Floor Protector Minimum Requirement: 9 mm thick fibre cementsheet with a thermal resistance value of 0.1 m²K/W per 9 mm thick sheet

1077min

1200nominal

1200 nominal

(289)

300

MXTH12BLK2/GRY2 orMXFSH12LGRY/DBLK

MXTHCNRBLK2/GRY2

(369)

Page 10: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

HCMG/16/043 & HCMG/16/044

Appliance BaseWidth = 565 mm

NORSEMAN GEN IIWITH PEDESTAL CONFIGURATION #2MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTS INSTALLEDWITH MAXIHEAT STANDARD IRONBARK DEFAULT FLUE KIT WITH DOUBLE SHIELDS Floor Protector Minimum Requirement: 9 mm thick fibre cementsheet with a thermal resistance value of 0.1 m²K/W per 9 mm thick sheet

MXTH12BLK2/GRY2 orMXFSH12LGRY/DBLK

(209)

1200 nominal

1200nominal

1022min

896 min

545to front of

Appliance Base

375

50

300

965

12211265

205 205

545to front of

Appliance Base

(44)

MXTHCNRBLK2/GRY2

This hearth sits 44 mmaway from the wall to meetthe minimum requirementfor the front hearth.

(519)

Page 11: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

HCMG/16/043 & HCMG/16/044

Appliance BaseWidth = 625 mm

NORSEMAN GEN IIWITH LEGS CONFIGURATION #1MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTS INSTALLEDWITH MAXIHEAT DECROMESH DEFAULT FLUE KIT WITH INNER SHIELD Floor Protector Minimum Requirement: 9 mm thick fibre cementsheet with a thermal resistance value of 0.1 m²K/W per 9 mm thick sheet

600to front of

Appliance Legs

1077min

896 min

350

130

1221

1221

MXTH12BLK2/GRY2

55 55

(369)

600to front of

Appliance LegsMXTHCNRBLK2/GRY2870

300

1170 1221

(289)

Page 12: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

HCMG/16/043 & HCMG/16/044

Appliance BaseWidth = 625 mm

NORSEMAN GEN IIWITH LEGS CONFIGURATION #2MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTS INSTALLEDWITH MAXIHEAT STANDARD IRONBARK DEFAULT FLUE KIT WITH DOUBLE SHIELDS Floor Protector Minimum Requirement: 9 mm thick fibre cementsheet with a thermal resistance value of 0.1 m²K/W per 9 mm thick sheet

(209)

1200nominal

1200 nominal50

375

896 min

1077min

600to front of

Appliance Legs

1320

300

1020600

to front ofAppliance Legs

(519)

205205

MXTH12BLK2/GRY2 orMXFSH12LGRY/DBLK

1221

(99)

MXTHCNRBLK2/GRY2

This hearth sits 99 mmaway from the wall to meetthe minimum requirementfor the front hearth.

Page 13: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

8AM1166

NORSEMAN LEGEND

CONFIGURATION #1MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTS

INSTALLED WITH FLUE PIPE

400

310to front of

Appliance Base

310to front of

Appliance Base

250 250

845 min

12211221

400

1200 nominal

1200nominal

(572)MXTH12BLK2/GRY2 orMXFSH12LGRY/DBLK

This hearth sits 17 mmaway from rear wall to meet

the minimum requirementfor the front hearth

Appliance BaseWidth = 618 mm

Please note: 310 mm to front ofAppliance Base is equivalent to300 mm to Firebox Door opening

(613)

MXTHCNRBLK2/GRY2

(17)

Page 14: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

8AM1166

NORSEMAN LEGEND

CONFIGURATION #2MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTSINSTALLED WITH FLUE PIPE, SINGLE SHIELD AND LOCATING RING

MXTH1BLK2/GRY2

This hearth sits 17 mmaway from rear wall to meet

the minimum requirementfor the front hearth

(372)

1000

1000

200

845 min

310to front of

Appliance Base

400

MXTHCNRBLK2/GRY2

(488)

12211095

125125

310to front of

Appliance Base795

300

Appliance BaseWidth = 618 mm

Please note: 310 mm to front ofAppliance Base is equivalent to300 mm to Firebox Door opening

(17)

Page 15: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

8AM1166

NORSEMAN LEGEND

CONFIGURATION #3MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTSINSTALLED WITH FLUE PIPE, DOUBLE SHIELD AND LOCATING RING

Appliance BaseWidth = 618 mm

Please note: 310 mm to front ofAppliance Base is equivalent to300 mm to Firebox Door opening

300

795 MXTHCNRBLK2/GRY2

310to front of

Appliance Base

125 125

10951221

(488)

MXTH1BLK2/GRY2

400

310to front of

Appliance Base

845 min

90

1000

1000

(262)

Page 16: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

8AM1166

NORSEMAN LEGEND

CONFIGURATION #4MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTS

INSTALLED WITH FLUE PIPE AND SINGLE LENGTH DECROMESH/SHIELD

Appliance BaseWidth = 618 mm

Please note: 310 mm to front ofAppliance Base is equivalent to300 mm to Firebox Door opening

MXTH1BLK2/GRY2

This hearth sits 17 mmaway from rear wall to meet

the minimum requirementfor the front hearth

400

310to front of

Appliance Base

845 min

200

1000

1000

(372)

300

795 MXTHCNRBLK2/GRY2

310to front of

Appliance Base

125 125

10951221

(488)

(17)

Page 17: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

8AM1163

NORSEMAN NEVADA

CONFIGURATION #1MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTS

INSTALLED WITH FLUE PIPE

305to front of

Appliance Base

400

425

(1142)

845 min

225 225

305to front of

Appliance Base

1105 1221

805

1200 nominal

1200nominal

(597)

Appliance BaseWidth = 618 mm

Please note: 305 mm to front ofAppliance Base is equivalent to300 mm to Firebox Door opening

300

(566)

MXTH12BLK2/GRY2 orMXFSH12LGRY/DBLK

MXTHCNRBLK2/GRY2

Page 18: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

8AM1163

NORSEMAN NEVADA

CONFIGURATION #2MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTSINSTALLED WITH FLUE PIPE, SINGLE SHIELD AND LOCATING RING

Appliance BaseWidth = 618 mm

Please note: 305 mm to front ofAppliance Base is equivalent to300 mm to Firebox Door opening

MXTH1BLK2/GRY2(347)

1000

1000

845 min

(892)

175

400

305to front of

Appliance Base

MXTHCNRBLK2/GRY2

(516)

300

755

1221

1055

305to front of

Appliance Base

175175

Page 19: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

8AM1163

NORSEMAN NEVADA

CONFIGURATION #3MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTSINSTALLED WITH FLUE PIPE, DOUBLE SHIELD AND LOCATING RING

Appliance BaseWidth = 618 mm

Please note: 305 mm to front ofAppliance Base is equivalent to300 mm to Firebox Door opening

MXTH1BLK2/GRY2

305to front of

Appliance Base

400

100

(817)

845 min

1000

1000

(272)

MXTHCNRBLK2/GRY2

175 175

305to front of

Appliance Base

1055

1221

755

300

(516)

Page 20: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

8AM1163

NORSEMAN NEVADA

CONFIGURATION #4MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTS

INSTALLED WITH FLUE PIPE AND SINGLE DECROMESH/SHIELD

Appliance BaseWidth = 618 mm

Please note: 305 mm to front ofAppliance Base is equivalent to300 mm to Firebox Door opening

MXTH1BLK2/GRY2

305to front of

Appliance Base

400

175

(892)

845 min

1000

1000

(347)

MXTHCNRBLK2/GRY2

175 175

305to front of

Appliance Base

1055

1221

755

300

(516)

Page 21: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

AHT-15-18-C

NORSEMAN SILHOUETTE GL

MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTSINSTALLED WITH A MAXIHEAT DECROMESH DEFAULT FLUE KIT

Floor Protector Minimum Requirement: 15 mm thick fibre cement

sheet with a thermal conductivity not greater than 0.33 Wm°K

335to front of

Appliance Base

100

275

855

1155 12217575

335to front of

Appliance Base

980 min

950min

Appliance BaseWidth = 690 mm

Please note: 335 mm to front ofAppliance Base is equivalent to350 mm to Firebox Door opening

(273)

1200 nominal

1200nominal

MXTH12BLK2/GRY2 orMXFSH12LGRY/DBLK

300

(476)

MXTHCNRBLK2/GRY2

Page 22: NORSEMAN AURA CONFIGURATION #1 MINIMUM ...ezorder.bbqgalore.com.au/Spares/Norseman.pdfFloor Protector Minimum Requirement: no less than 7.5mm thick fibre cement sheet, and a thermal

HCMG/02/005

Appliance BaseWidth = 730 mm

NORSEMAN SILHOUETTE GLX

MINIMUM CLEARANCES AND FLOOR PROTECTOR REQUIREMENTSINSTALLED WITH A MAXI-HEAT DEFAULT FLUE KIT, WITH DECROMESH PLUS

HEAT SHIELD ON THE OUTSIDE (back) OF DECROMESH

Floor Protector Minimum Requirement: 4.5 mm thick cement fibre sheet

300to front of

Appliance Base

350

75

50501180 1221

880 300to front of

Appliance Base

1020 min

1200 nominal

1200nominal

(1046)

(262)

300

MXTH12BLK2/GRY2 orMXFSH12LGRY/DBLK

MXTHCNRBLK2/GRY2

(475)