Noţiuni dimensionare instalaţie solară
Determinarea componentelor unei instalaţii solare
|
© Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as
copying and passing on to third parties.
226.04.06 RBRO | AD-8004 | Echipamente solare Junkers.ppt
TT
Noţiuni dimensionare instalaţie solară
• Componente principale instalaţie solară - acm
• Componente principale instalaţie solară - piscină
alegere boiler bivalent (deteminare volum) panouri solare (nr.) conducte sistem solar (diamentru) izolaţie conducte solar vas expansiune volum Tyfocor instalaţie alegere automatizare
panouri solare (nr.) schimbător căldură în plăci alegere automatizare
|
© Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as
copying and passing on to third parties.
326.04.06 RBRO | AD-8004 | Echipamente solare Junkers.ppt
TT
Noţiuni dimensionare instalaţie solară
• Componente principale instalaţie solară - acm
Schema de principiu a unei instalaţii solare pentru producere de acm
|
© Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as
copying and passing on to third parties.
426.04.06 RBRO | AD-8004 | Echipamente solare Junkers.ppt
TT
Noţiuni dimensionare instalaţie solară
alegere boiler bivalent (deteminare volum)
Exemplu de calcul:
• 4 persoane• temperatura punct consum: 45 oC• necesar acm / persoană / zi: 50 l• temperatură stocare acm: 60 oC• temperatură intrare apă rece: 10 oC
Volum boiler bivalent?
Volumul total al boilerului bivalent = 1,5 (2) x necesarul zilnic de acm (45 oC)Observaţie: temperatura de stocare acm: 60 oC
Vboiler bivalent = ( )( )10-60
10454502 −××× = 280 L
Junkers SK 300-1 Solar
|
© Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as
copying and passing on to third parties.
526.04.06 RBRO | AD-8004 | Echipamente solare Junkers.ppt
TT
Noţiuni dimensionare instalaţie solară
consum acm (litri / zi)
sup
rafa
ţă p
an
ou
ri s
ola
re (
m2 )
volum boiler bivalent (litri )
Panouri solare plane
Panouri solare cu tu
buri vidate
nr. panouri solare f(volum boiler bivalent)
|
© Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as
copying and passing on to third parties.
626.04.06 RBRO | AD-8004 | Echipamente solare Junkers.ppt
TT
Noţiuni dimensionare instalaţie solară
• f1 – factor de corecţie pentru abaterea faţă de axa S• a-abatere către V faţă de axa S• b-abatere către E faţă de axa S
Abaterea faţă de axa S
Exemplu de calcul:
• necesar acm / zi: 200 l• boiler ales: SK 300-1 Solar• suprafaţă necesară (diagramă): 5 m2 panouri solare plane• orientare panouri solare: SV, 50 o
Suprafaţă corectă?
Factor de corecţie:
• f1 (50 o, SV) = 1,1
Suprafaţă panouri: 5 m2 x 1,1 = 5,5 m2
V E
|
© Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as
copying and passing on to third parties.
726.04.06 RBRO | AD-8004 | Echipamente solare Junkers.ppt
TT
Noţiuni dimensionare instalaţie solară
•f2 – factor de corecţie pentru înclinaţie (numai pentru producere de acm)•g-înclinaţia faţă de orizontală
Abaterea faţă înclinaţia optimă faţă de orizontală (45 o)
Exemplu de calcul:
• necesar acm / zi: 200 l• boiler ales: SK 300-1 Solar• suprafaţă necesară (corectată): 5,5 m2 panouri solare plane• înclinaţie: g = 25 o
Suprafaţă corectă?
Factor de corecţie:
• f2 (g = 25 o) = 1,05
Suprafaţă panouri: 5,5 m2 x 1,05 = 5,78 m2
|
© Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as
copying and passing on to third parties.
826.04.06 RBRO | AD-8004 | Echipamente solare Junkers.ppt
TT
Noţiuni dimensionare instalaţie solară
pentru 1 m2 panou solar -> 0,2-0,35 m2 serpentină solar
Numărul maxim de panouri al instalaţiei solare pentru producere de acm depinde de suprafaţa maximă a serpentinei solare a boilerului bivalent!!
Exemplu de calcul:
• boiler bivalent SK 300-1 Solar • suprafaţa serpentinei solare (inferioare): 1,45 m2
Suprafaţa maximă de panouri solare? Spanouri max = 0,245,1 = 7,25 m2
nr. maxim de panouri solare / boiler bivalent
|
© Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as
copying and passing on to third parties.
926.04.06 RBRO | AD-8004 | Echipamente solare Junkers.ppt
TT
Noţiuni dimensionare instalaţie solară
conducte sistem solar (diametru)
• conducte din Cu, rezistente la 150-170 oC• îmbinare prin lipire tare sau fitinguri cu presare (rezistente la amestec apă/propilenglicol)• viteza de curgere prin conducte: min. 0,4 m/s – max. 1,17 m/s
Efecte supradimensionare conducte instalaţie solară:• zgomote în instalaţie• nu se atinge debitul necesar pentru transportarea cantităţii optime de căldură de la panouri la boiler
Dimensionarea conductelor de solar:w = 0,7 m/s (viteza maximă de curgere)• v = debitul de circulaţie în panou (50 l/(m2*h) – de ex. FKT)• V = debit de circulaţie câmp panouri solare (m2): v x A• A = suprafaţa câmpului de panouri solare (m2)• Dinterior = diametrul interior al conductelor (mm)
|
© Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as
copying and passing on to third parties.
1026.04.06 RBRO | AD-8004 | Echipamente solare Junkers.ppt
TT
Noţiuni dimensionare instalaţie solară
Exemplu de calcul:
• nr. panouri: 4 FKT• suprafaţă panouri solare (absorber): A = 8,92 m2
• w = 0,7 m/s• v = 50 l / (m2*h)
Diametrul conductelor de solar?
• V = v x A = 50 l/(m2*h) x 8,92 m2 = 446 l/h = 0,446 m3/3600 s
• Dinterior = = = = 0,015 m = 15 mm
v
V4
×π×
sm
7,014,3
s3600m446,0
43
×
×2m000225343,0
Teavă Cu (diametrul exterior x grosimea peretelui)
Diametrul interior (mm)
Cu 10 x 1 8 Cu 12 x 1 10 Cu 15 x 1 13 Cu 18 x 1 16 Cu 22 x 1 20 Cu 28 x 1,5 25
Se alege ţeavă de Cu 18 x 1
|
© Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as
copying and passing on to third parties.
1126.04.06 RBRO | AD-8004 | Echipamente solare Junkers.ppt
TT
Noţiuni dimensionare instalaţie solară
Viteza de curgere şi pierderea de presiune pe m liniar, în funcţie de viteza de curgere şi diametrul ţevii
|
© Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as
copying and passing on to third parties.
1226.04.06 RBRO | AD-8004 | Echipamente solare Junkers.ppt
TT
Noţiuni dimensionare instalaţie solară
izolaţie conducte solar
• conductele din Cu se vor izola întotdeauna cu izolaţie termică, astfel încât pierderile de căldură să fie minime; fitingurile nu se izolează• izolaţia trebuie să fie rezistentă la temperaturi înalte (max. 170 oC), la UV, precum şi la factorii de mediu extern (ploaie, soare, vânt)• izolaţia cu vată minerală nu se va folosi la exterior, deoarece vata îmbibată cu apă îşi pierde proprietăţile izolatoare
|
© Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as
copying and passing on to third parties.
1326.04.06 RBRO | AD-8004 | Echipamente solare Junkers.ppt
TT
Noţiuni dimensionare instalaţie solară
vas expansiune
• depinde de volumul de tyfocor care se poate evapora în cazul opririi instalaţiei, numărul de panouri şi diametrul conductelor instalaţiei solare• în funcţie de necesar se pot lega mai multe vase de expansiune în paralel
Nr. de panouri solare Volum vas expansiune (l)
1 – 3 18 4 – 5 25 6 – 9 35 10 50
Condiţii limită:• înălţimea statică maximă a instalaţiei solare: 10 m• lungimea maximă a conductelor solare (numai un fir): 20 m• pentru 10 panouri, varianta de legare va fi 2 campuri (panouri înseriate), legate în paralel (în caz contrar, pompa solară din AGS 3 este prea mică!!); diametrul conductelor de solar în acest caz este Ø = 35 mm
|
© Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as
copying and passing on to third parties.
1426.04.06 RBRO | AD-8004 | Echipamente solare Junkers.ppt
TT
Noţiuni dimensionare instalaţie solară
volum Tyfocor instalaţie
• volumul total de tyfocor din instalaţie = volum panouri + volum vas expansiune + volum conducte instalaţie + alte elemente (serpentină boiler, schimbător de căldură în plăci etc.)
Volum Tyfocor panouri:- nr. panouri x volum absorber/panouVolum conducte instalaţie:- lungime ţevi (m) x conţinut tyfocor/ml (l/m)Volum Tyfocor vas expansiune:- 40-60% din volumul vasului de expansiuneVolum schimbător de căldură în plăci, serpentină solar etc. = date de producător
|
© Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as
copying and passing on to third parties.
1526.04.06 RBRO | AD-8004 | Echipamente solare Junkers.ppt
TT
Noţiuni dimensionare instalaţie solară
Temperaturi• pentru piscinele din aer liber: 22-25 oC; pentru cele acoperite 26-30 oC• temperatura aerului din incintele cu piscine: + 1-3 oC faţă de cea a apei din bazin
Pierderile de căldură• temperatura apei din piscină: cu cât este mai mare -> pierderi mai mari (evaporare)• temperatura aerului: cu cât este mai mică faţă de cea a apei -> pierderi mai mari • umiditatea relativă a aerului: cu cât este mai uscat aerul -> pierderi mai mari (evaporare); umiditate normală: 55-65%• suprafaţa piscinei
Convecţie 12%
Pierdere căldură prin pereţi 5%
Radiaţie căldură 17%
Evaporare 66%
|
© Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as
copying and passing on to third parties.
1626.04.06 RBRO | AD-8004 | Echipamente solare Junkers.ppt
TT
Noţiuni dimensionare instalaţie solară
nr. panouri solare
Piscină acoperită cu bazin protejat (acoperit)
• nr. de panouri N = f(suprafaţă piscină A(m2), temperatura dorită Tw (oC))• temperatură calcul Tw = 24 oC• factor de suprafaţă fA (m2)
FKT-1 FKC-1 factor de suprafaţă fA (1/m2) 0,16 0,2
FKT-1 FKC-1 nr. suplimentar de panouri pentru creşterea temperaturii cu 1oC peste 24 oC
1 1,3
|
© Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as
copying and passing on to third parties.
1726.04.06 RBRO | AD-8004 | Echipamente solare Junkers.ppt
TT
Noţiuni dimensionare instalaţie solară
Exemplu de calcul:
• piscină acoperită, cu bazin protejat• suprafaţă piscină: A = 32 m2
• temperatura dorită a apei din bazin: Tw = 25 oC
Nr. de panouri FKT-1 pentru încălzirea apei din bazin?
Calcul
pentru FKT-1, fA = 0,16 (Tw = 24 oC)
N = fA x A = 0,16 x 32 = 5,12
pentru creşterea temperaturii cu 1oC -> N = 5,12 + 1 = 6 panouri FKT-1
|
© Robert Bosch GmbH reserves all rights even in the event of industrial property rights. We reserve all rights of disposal such as
copying and passing on to third parties.
1826.04.06 RBRO | AD-8004 | Echipamente solare Junkers.ppt
TT
Noţiuni dimensionare instalaţie solară
Piscină acoperită cu bazin neprotejat (neacoperit) sau pisicină în aer liber protejată
• nr. de panouri N = f(suprafaţă piscină A(m2), temperatura dorită Tw (oC))• temperatură calcul Tw = 24 oC• factor de suprafaţă fA (m2)• suprafaţa panourilor solare = 0,5 x suprafaţa piscinei A
FKT-1 FKC-1 factor de suprafaţă fA (1/m2) 0,24 0,3
Piscină în aer liber neprotejată
• nr. de panouri N = f(suprafaţă piscină A(m2), temperatura dorită Tw (oC))• temperatură calcul Tw = 24 oC• factor de suprafaţă fA (m2)• suprafaţa panourilor solare = 1 x suprafaţa piscinei A
FKT-1 FKC-1 factor de suprafaţă fA (1/m2) 0,48 0,6