nsol v4_6 manual

Upload: daniel-ayosa

Post on 05-Apr-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/31/2019 NSol V4_6 Manual

    1/41

  • 7/31/2019 NSol V4_6 Manual

    2/41

    PV System Sizing Program

    2

    NSol!PV SYSTEM SIZING PROGRAM

    Version 4.6

    Contents1 Introduction ........................................................................................................................................... 5

    2 Installation............................................................................................................................................. 7

    2.1 Installation File ............................................................................................................................. 7

    2.2 Registration and Activation .......................................................................................................... 7

    2.2.1 Purchase ................................................................................................................................ 72.2.2 Registration ........................................................................................................................... 7

    2.2.3 Activation .............................................................................................................................. 7

    2.2.4 Updates ................................................................................................................................. 8

    2.2.5 Demo Version ....................................................................................................................... 8

    2.3 Borland BDE Database Configuration .......................................................................................... 8

    2.3.1 Background ........................................................................................................................... 8

    2.3.2 Manual Configuration ........................................................................................................... 8

    2.3.3 Rebuild NSol4 Config ........................................................................................................... 9

    3 Program Overview .............................................................................................................................. 10

    3.1 Overview ..................................................................................................................................... 10

    3.2 Starting the Program ................................................................................................................... 10

    3.3 Opening a File ............................................................................................................ ................. 10

    3.4 Navigating the Notebook ............................................................................................................ 10

    3.5 Printing a Report ......................................................................................................................... 11

    3.6 Saving the File ............................................................................................................................ 11

    3.7 Closing the Program.................................................................................................................... 11

    4 Data Entry ........................................................................................................................................... 12

    4.1 Overview ..................................................................................................................................... 12

    4.2 Data Entry Page .......................................................................................................................... 12

    4.3 Site Data ...................................................................................................................................... 12

    4.4 Insolation /Temperature Data ...................................................................................................... 12

    4.5 Insolation Database ..................................................................................................................... 12

    4.5.1 Navigating the Database ..................................................................................................... 13

  • 7/31/2019 NSol V4_6 Manual

    3/41

    PV System Sizing Program

    3

    4.5.2 Search City .......................................................................................................................... 13

    4.5.3 Search State/Region ............................................................................................................ 13

    4.5.4 Search Country .................................................................................................................... 13

    4.5.5 Search Latitude / Longitude ................................................................................................ 13

    4.6 Editing the Database ................................................................................................................... 144.7 System Data ................................................................................................................................ 14

    4.8 Component Data ......................................................................................................................... 14

    4.8.1 Battery ................................................................................................................................. 14

    4.8.2 PV Modules ........................................................................................................................ 15

    4.8.3 Hybrid Components ............................................................................................................ 15

    4.8.4 Inverter ................................................................................................................................ 16

    4.9 Load Data .................................................................................................................................... 16

    4.9.1 Load Summary Report ........................................................................................................ 17

    5 Array Tilt Calculation ......................................................................................................................... 18

    5.1 Overview ..................................................................................................................................... 18

    5.2 Array Tilt .................................................................................................................................... 18

    5.3 Tracking Options ........................................................................................................................ 19

    5.4 Optimization ............................................................................................................................... 19

    5.5 Array Insolation Report .............................................................................................................. 19

    6 System Sizing Standalone PV .......................................................................................................... 20

    6.1 Overview ..................................................................................................................................... 20

    6.2 Selecting Components................................................................................................................. 20

    6.3 Setting Array Tilt ........................................................................................................................ 20

    6.4 ALR Method ............................................................................................................................... 20

    6.4.1 MPPT vs. Non MPPT Controller ........................................................................................ 22

    6.5 LOLP Method ............................................................................................................................. 23

    6.5.1 LOLP Page .......................................................................................................................... 23

    6.5.2 BSOC Page ......................................................................................................................... 24

    6.5.3 Note on Calculations ........................................................................................................... 25

    6.6 LOLP Methodology .................................................................................................................... 25

    6.7 IV Curve Analysis ....................................................................................................................... 266.8 Reports ........................................................................................................................................ 26

    6.8.1 System Sizing Report .......................................................................................................... 26

    6.8.2 System Availability (LOLP) Report .................................................................................. 26

    6.8.3 Battery SOC Report ............................................................................................................ 27

    6.8.4 Standalone System Summary Report .................................................................................. 27

  • 7/31/2019 NSol V4_6 Manual

    4/41

    PV System Sizing Program

    4

    7 System Sizing - Hybrid ....................................................................................................................... 28

    7.1 Overview ..................................................................................................................................... 28

    7.2 Selecting Components................................................................................................................. 28

    7.3 Setting Array Tilt ........................................................................................................................ 28

    7.4 Hybrid System Analysis.............................................................................................................. 287.5 Hybrid System Analysis Screen .................................................................................................. 29

    7.6 Hybrid Sizing Report .................................................................................................................. 30

    8 System Sizing Grid Systems ............................................................................................................ 31

    8.1 Overview ..................................................................................................................................... 31

    8.2 Selecting Components................................................................................................................. 31

    8.3 Setting Array Tilt ........................................................................................................................ 31

    8.4 Grid System Analysis ................................................................................................................. 31

    8.5 Grid System Screens ................................................................................................................... 32

    8.6 Grid System Report ..................................................................................................................... 32

    9 Reports and Exporting Data ................................................................................................................ 33

    9.1 Report Summary ......................................................................................................................... 33

    9.2 Printing Reports .......................................................................................................................... 33

    9.2.1 Printing ................................................................................................................................ 33

    9.2.2 Page Setup ........................................................................................................................... 33

    9.2.3 PDF Files ............................................................................................................................ 33

    9.3 Printing Charts ............................................................................................................................ 33

    9.4 Exporting Charts ......................................................................................................................... 33

    9.5 Exporting ASCII Data for Spreadsheets ..................................................................................... 33

    9.6 Exporting Grid Data for Spreadsheets ........................................................................................ 33

    APPENDIX 1 - SAMPLE REPORTS ...................................................................................................................

    APPENDIX 2 - GLOSSARY OF TERMS .............................................................................................................

    APPENDIX 3 - LIST OF SIZING REFERENCES ................................................................................................

    For more information or technical support, contact:

    FearTheSkunk

    Web: www.nsolpv.com

    Email: [email protected]

  • 7/31/2019 NSol V4_6 Manual

    5/41

  • 7/31/2019 NSol V4_6 Manual

    6/41

    PV System Sizing Program

    6

    NREL solar insolation databases, and has

    the ability to search for specific sites by city,

    state,

    country or latitude / longitude. This databaseis user-modifiable.

    Advanced statistical system performanceanalysis. NSol!uses a proprietary LOLP

    algorithm developed by Professor L. L.

    Bucciarelli of the Massachusetts Institute of

    Technology. Based on the concept of

    "Markov Transition Matrices," this

    algorithm calculates the statistical

    performance of the solar insolation resource,

    then applies this to the battery-based PV

    system. The result is a "Loss-ofLoad

    Probability" which gives a concise estimate

    of system reliability.

    Hybrid System Analysis Basicperformance calculations for PV-Battery-Generator hybrids

    Grid System Analysis Basic performancecalculations for utility-tied PV systems

    Laser Quality Printouts - summary anddetailed printouts are ready for inclusion

    directly into your proposals.

    A graphic "Tool-Bar" -- icon-basedshortcuts to common file functions

    NSol!is easy enough to use that a new user can just

    jump right in without reading the manual. For a

    quick overview of the program, Section 3 contains asummary of program operation.

  • 7/31/2019 NSol V4_6 Manual

    7/41

  • 7/31/2019 NSol V4_6 Manual

    8/41

    PV System Sizing Program

    8

    2.2.4 UpdatesPeriodically, we will issue updates to the program.

    Users will receive an email with instructions on how

    to download / install the updates.

    2.2.5 DemoVersionA demo version is available from the website. This

    has the full set of design features of the main

    program with three exceptions:

    1) Saving is disabled.2) Printed reports will have a Demo Version

    watermark.

    3) The Company name and address cannot bechanged.

    2.3 BorlandBDEDatabaseConfiguration

    2.3.1 Background databases are managed using the Borland

    Database Engine. Installation of this software is

    automatic in most cases; however, because of the

    widely disparate requirements of Windows operating

    systems, manual intervention may be required in

    some cases.

    Known cases involve 64 bit operating systems,

    installation on a non-C drive, and some issues with

    XP permissions.In 64 bit system, the operating software will install

    the program in a folder called C:\Program

    Files (x86)\nsol! instead of the

    c:\program files\nsol! folder. The

    BDE is looking in the latter folder so it needs to be

    manually changed.

    A similar situation applies when the program is

    installed on a non-C drive.

    You will know if this is the situation if you try to

    open one of the database tabs you will get some

    sort of message (depending on the system) aboutmissing BDE configurations.

    If this occurs, you can manually set the BDE

    configuration using the following steps.

    2.3.2 ManualConfiguration1. Open the Control Panel and start the BDE

    Administration program (bdeadmin.exe), using

    administrator privileges in Visa or Windows 7.

    Note -- The actual program is found in

    c:\program files\common

    files\borland shared\bde.)

    2. Click on the [Databases Tab] and then select

    NSol46. Click on the [Path] field on the righthand side and set the path to the proper value,

    using the [] to open a file browser. The

    program is typically installed in \program

    files\nsol! on one of the drives, but this

    will be \program files

    (x86)\nsol!

    3. Next, click on the [Configuration] tab. Expandthe Configuration property, then Drivers, then

    Native, then click on Paradox, which will

    bring up the following screen:

  • 7/31/2019 NSol V4_6 Manual

    9/41

    PV System Sizing Program

    9

    4. Change the NET DIR path to beC:\Program Files\Common

    Files\bdeshare

    5. Note on some XP systems, this may not bepossible. If so, set the path to c:\.

    6. Close the program, saving the data as prompted.

    2.3.3 RebuildNSol4ConfigOn some XP systems, it may not be possible to savethe BDE configuration file because of strange

    system permissions restriction. If this occurs, please

    use the following steps to fix the problem:

    1. Delete the NSol4 database by clicking on theX of right clicking and selecting Delete.

    2. Type Ctrl-N to insert a new database, choosingStandard when prompted.

    3. Rename it NSol46Properties should be Standard, PARADOX

    and False (under enable BCD)

    4. Set the path as described above (Step 2).

    5. Click on the configuration tab and set up as per3. and 4. above.

    6. Close and save.

    If there are other problems, please contact us at

    [email protected] . Please include your operatingsystem (XP, Vista, Windows 7, 32 bit or 64 bit) and

    your installation location. Windows is a funny thing

    we have most of the situations covered, but I

    would not be surprised to see some new variation.

  • 7/31/2019 NSol V4_6 Manual

    10/41

    PV System Sizing Program

    10

    3 ProgramOverview3.1 OverviewNSol!is a project-based approach to sizing PV

    systems. Each system is stored in a separate file with

    the PV5 extension. The PV5 file opens to showthe summary page of a notebook with separate

    pages for each of the major sizing functions.

    Clicking on a component on the summary page

    opens a data or load data entry form.

    Multiple documents can be open at the same time,

    allowing comparisons between different system

    options.

    The program also produces a variety of reports, and

    data export capabilities.

    3.2 StartingtheProgramThe program is opened by double-clicking on the

    program icon, or its shortcut. Shortcuts can be

    installed on the desktop, Start menu, or toolbar.

    3.3 OpeningaFileOnce the program has started, it offers three choices:

    The first option starts a new project using the data

    stored in default.PV5 and names it new.PV5.

    (Note -- The default file can be edited to include the

    users most common module, battery, location, or

    system parameters so that these will appear

    automatically when a new file is started.)

    The second option allows the user to open an

    existing file via a standard file dialog box.

    The third option allows the user to start a new file,

    using an existing file as the initial data. This isuseful for analyzing one system design at multiple

    locations, or for looking at multiple options for a

    single site (e.g. hybrid vs. standalone).

    3.4 NavigatingtheNotebookThe notebook contains four or five pages, depending

    on the system configuration.

    The pages are selected by clicking on tabs at the topof the project notebook.

    The first page is the summary page, which isused to enter site information, loads and

    components.

    The second page is the Array Tilt page, usedfor calculated the insolation on the tilted /

    tracking array surface.

  • 7/31/2019 NSol V4_6 Manual

    11/41

    PV System Sizing Program

    11

    Standalone PV systems include the Sizing(ALR) page, the LOLP Analysis page, and

    the BSOC page.

    Hybrid systems include the Sizing (ALR)and Hybrid Sizing pages.

    Grid connect systems include the GridSystem and Grid Typ Day pages.

    3.5 PrintingaReportReports can be can be printed in three ways:

    Clicking on the Printer speed button willprint a report appropriate for the active page,

    if it is available.

    Choosing File _Print from the main menuaccomplishes the same thing.

    Choosing File_PrintAll from the mainmenu allows the user to choose a set of

    reports to print with a single command.

    3.6 SavingtheFileOnce the project is designed, it can be saved either

    via a speed button in the top toolbar, or via a menu

    command.

    The menu also includes File _SaveAs which

    allows the file to be saved under a different name.

    If the file is new, the program will suggest a name

    based on the city name.

    3.7 ClosingtheProgramAn individual project can be closed via a speed

    button, a menu command, or the X in the upper

    right corner of the project screen. The entire

    program can be closed in the same ways.

    If the open projects have not been saved, the

    program will prompt the user for an appropriate

    action.

  • 7/31/2019 NSol V4_6 Manual

    12/41

    PV System Sizing Program

    12

    4 DataEntry4.1 OverviewIn order to properly size a PV or hybrid power

    system, information about the site, loads, and

    components must be specified. In NSol!, this is donevia the Summary page of the project notebook.

    4.2 DataEntryPageClicking on the corresponding symbol on the

    Summary page accesses the appropriate data entry

    form. For example, clicking on the PV Array will

    bring up the PV page of the components dialog.

    The site and component data is either entered

    directly into the form, or selected from a database

    (PV modules, batteries and Site Insolation only).

    Loads are entered by clicking on the Load symbolat the right of the page (PV and hybrid only). Up to

    ten distinct loads can be entered.

    4.3 SiteDataTo enter site data, click on the site summary table on

    the Summary screen. This will bring up the data

    entry dialog box. This form includes pages for the

    site data and system factors, as well as each of the

    major components.

    The following data is used for the site: Site Name City Region / State Country Latitude (decimal degrees North is

    positive, South is negative)

    Longitude (decimal degrees East ispositive, West is negative)

    Elevation (meters) Comments / References

    Insolation data is also entered from this page.

    4.4 Insolation/TemperatureDataTo enter insolation data, click on the Sun in the

    upper left of the Summary Page. This will bring up

    the site data page in the data entry dialog.

    The following data specifies the solar resources and

    temperature at the site:

    GH Insol Average Global Horizontalinsolation for each month of the year.

    Avg temp Average daily temperature atthe site for each month of the year (degrees

    Celsius)

    Temp Swing the average number ofdegrees between the average temperature

    and the high or low temperature. Typically 5

    to 8 deg C. Example average is 18C,

    variation is 5C, so average high is 23C,

    average low is 13C.)

    Reflectance typically 0.2 (20%). Canrange from 0.02 (2%) for loose, dark soil or

    asphalt, to 0.8 (80%) for smooth snow.

    Each of these factors can be entered by month.

    4.5 InsolationDatabaseNSol!includes an insolation / site database to

    facilitate data entry. All data is public domain data,

    primarily from NREL (for us sites) and the

    University of Lowell (for international sites). Note

    that version 4.6 includes an additional NASA

    satellite database, which covers the entire globe at 1

    degree latitude / longitude intervals. Since this data

    does not include city, state or country information, it

    can only be accessed via a Latitude / Longitude

    search.

  • 7/31/2019 NSol V4_6 Manual

    13/41

    PV System Sizing Program

    13

    To access the database, click on the InsolDatabase

    button in the lower right of the site entry page.

    This will bring up a form that allows access to the

    entire NSol!Insolation database.

    4.5.1 NavigatingtheDatabaseTo move through the database, use the four buttons

    located below the search buttons. These buttons have

    the following functions:

    The left button (left arrow with bar) movesto the beginning of the database.

    The left arrow moves back one record. The right arrow moves forward one record. The right arrow with bar moves to the last

    record in the database.

    4.5.2 SearchCityTo search the database by city, click on the search

    city button, enter the city name in the Seach City

    field, and click on Okay. This will sort the database

    by city name, and find the nearest match. Note that it

    is not necessary to enter the entire name, just the

    first few letters.

    4.5.3 SearchState/RegionThis button sorts the database by region, and finds

    the nearest match. Most of the international sites do

    not have a region entered, so this is primarily useful

    for custom sites, or for US sites.

    4.5.4 SearchCountryThis button sorts the database by country, and finds

    the nearest match. This is useful when looking for a

    site in a particular country.

    4.5.5 SearchLatitude/LongitudeThis button filters the database so that it only

    includes sites within the search criteria specified by

    the search dialog box:

    The user can then use the navigation buttons to

    scroll through this data and find an appropriate site.

  • 7/31/2019 NSol V4_6 Manual

    14/41

    PV System Sizing Program

    14

    4.6 EditingtheDatabaseThe insolation database has standard user-editing

    capabilities. These are accessed by clicking on the

    Edit DB button just below the navigation bar.

    This changes the database from read only to

    modifiable and adds six editing buttons to the

    navigation tool bar. From left to right they are:

    Plus -- Add new record Minus -- Delete record Up Arrow Edit Record Check Post record (save to database) X Cancel Edit Circle Arrow Refresh data

    Please remember to keep a backup copy of the

    database and all index files if you plan on editing the

    database. In a default installation, the database files

    are in a folder called DB under Program Files /OEC / NSol. If you chose a different folder during

    installation, try searching for ns4ins.db.

    4.7 SystemDataThe system tab opens a page which contains the

    basic system sizing background data. These fields

    include:

    Battery Voltage Maximum Battery Depth-of-Discharge

    Average Battery Volts/cell

    AC Operating Voltage

    Target ALR Target Battery Days System Losses (with seasonal loss option)

    4.8 ComponentDataThe next four tabs contain the specific component

    information:

    Batteries PV Modules / Array

    Grid InverterHybrid Info (generator, rectifier, battery charge

    setpoints)

    4.8.1 BatteryThis dialog page allows the user to specify the

    battery used in the system design.

    The user has the choice of entering the data directly

    or choosing a module from a pre-designed database.

    The user can edit the database using the same

    techniques as with the insolation database.

    Battery parameters are:

    Battery Manufacturer Battery Model - Name of the battery. Cell Amp-hr -- Rate amp-hour capacity of

    the battery at the C/100 rate.

    Unit Volts -- voltage of the battery unit. Forindividual battery cells, this is two volts. For

    monoblocs (pre-packaged groups of cells),

    this may be 4, 6, 8 or 12 volts.

    # Series -- The number of cells or blocks in

    series # Parallel -- The number of parallel strings Auto Series -- If this block is selected, the

    program will automatically calculate the

    proper number of cells or blocks in series.

    This should only be overridden with great

    care.

    Monobloc -- This box determines thebehavior of the battery sizing controls on the

  • 7/31/2019 NSol V4_6 Manual

    15/41

    PV System Sizing Program

    15

    "Sizing (ALR)" page. If the box is not

    selected, the program will simply increase or

    decrease the number of amp-hour in

    response to the up and down arrows. If

    monobloc" is selected, the program will

    leave the Ah capacity alone, and increase or

    decrease the number of parallel strings.

    4.8.2 PVModulesPV module information can be entered directly or

    selected from a database.

    The user can edit the database using the sametechniques as with the insolation database.

    The data fields are as follows:

    PV Module Mfgr - Name of the PV module

    manufacturer. PV Module Model - Name of the PV

    module.

    Module W(p) - Rated power of the module.This is used in the system specifications and

    BOM only.

    Vmpp, or Vtyp - Module max power voltage Impp, or Ityp - Module max power current Voc - Module open circuit voltage Isc - module open circuit current V Temp Comp % - Voltage temperature

    compensation for PV modules, expressed as

    percent of open circuit voltage per degree Cabove/below 25 deg C. (Example value of

    -0.4 means -0.004 * Voc per deg C)

    I Temp Comp % - Current temperaturecompensation for PV modules, expressed as

    percent of short circuit current per degree C

    above/below 25 deg C. (Example value of

    0.035 means 0.00035 * Isc per deg C)

    # Series - This is the total number ofmodules in a single series string.

    # Parallel - This is the total number ofstrings in parallel.

    Auto Series - If this box is checked, theprogram will calculate the number of

    modules in series automatically, with onemodule per 12V of nominal capacity. This

    should typically be checked for systems up

    to 48V. For 120 V systems, a careful

    designer might be able to use only 9

    modules in series, especially in colder

    climates.

    If the "# Parallel" field is initially left blank,the program will automatically calculate the

    size of the array to meet the "Target ALR"

    specified previously. This then forms a

    starting point for sizing the system.

    This dialog box can also be used later to change the

    system size or configuration.

    4.8.3 HybridComponents

    The user must enter the following generator and

    battery charger information:

    Generator Manufacturer Generator Model Genset Power Rating Power in kilowatts

    Genset Power Factor Rating Rating ofAlternator typically either 0.8 or 1.0 Full Load Fuel Consumption (FLFC) Fuel

    use at full load either liters per hour

    (diesel) or kg per hour (LPG)

    Quarter Load Fuel Consumption (QLFC) Fuel use at 25% load (quarter load) in L/hr

    or kg/hr

  • 7/31/2019 NSol V4_6 Manual

    16/41

    PV System Sizing Program

    16

    Generator Maintenance Oil ChangeInterval in hours, typically between 100 and

    500 hours

    Generator Maintenance Decoke Interval inhours, typically 500-1500 hours for

    decarbonization (also called top end

    overhaul) Generator Maintenance Overhaul Interval

    in hours, full overhaul of engine, typically at

    6,000-10,000 hours

    Generator Maintenance Generator Life,ranged between 1,000 hours for a small

    gas/petrol engine to 20,000-40,000 for a

    well maintained diesel engine

    Battery Charger Current primary rating forbattery charger determines load on

    engine/generator

    Battery Charger Power Factor used to sizealternator

    Battery Charger Efficiency used todetermine AC power requirement of battery

    charger as seen by the generator

    In addition, the data input screen allows thefollowing control setpoint inputs:

    Generator Start Battery State of Charge typically 20-50% SOC

    Generator Stop BSOC (normal charge) typically 80-90% SOC

    Normal Charge Coloumbic (Amp-hr)Efficiency typically 90-95% for non-

    equalization charging

    Equalization Frequency typically one tofour times per month

    4.8.4 Inverter

    The user must enter the following inverter

    information:

    Inverter Manufacturer Inverter Model number Inverter rating in kW

    Average efficiencyIn addition, the Type and Configuration need to beset using the radio buttons.

    NOTE At this time, the inverter efficiency

    number is used only for reporting. The actual

    efficiency should be set under loads as described

    in the next section.

    4.9 LoadDataLoad information can be entered via the Load Input

    dialog box. This is accessed by clicking on the

    "Radio Tower" on the System Summary page, or via

    the System Load menu. Up to ten different loads canbe entered.

    The load dialog box consists of four data fields,

    along with three "radio-button" selection fields and a

    "Check Box". The load is specified by the load size,

    load hours, load type (amps / amp-hrs / watts), AC /

    DC, conversion efficiency and load profile. The load

    size, load hours, and conversion efficiency are

    entered via data fields. The other choices -- amps vs.

    Ah vs. watt, AC vs. DC, and load profile are enteredvia "Radio buttons."

  • 7/31/2019 NSol V4_6 Manual

    17/41

    PV System Sizing Program

    17

    If "Seasonal Loads" are selected, the loads can be set

    by month via a separate dialog input.

    The data is entered as follows:

    Load Description - a brief description of the

    equipment which is being powered, e.g."Streetlights," "Microwave Transmitter,"

    "Refrigerator."

    Load Size - The magnitude of the load,either in watts, amps or amp-hours. This is

    entered as a real number.

    Choose Amps, Amp-Hrs or Watts to matchthe design load by selecting one of the

    "radio" buttons.

    AC vs. DC - This choice is also made via"radio" buttons.

    Conversion Efficiency - this is entered as an

    integer percent, e.g. 80% is entered as "80".Typical inverters have efficiencies ranging

    from 70% through 95%. DC to DC

    converters used in many telecom systems

    have efficiencies of 80 to 90%.

    Load Hours - hours per day that the loadoperates, entered as a real number, with aminimum of 0.1 and a maximum of 24.0.

    Load Profile - Selected from six choices via"radio" buttons on the right side of the

    dialog box. The choices range from"Daytime only" though "Day/Night" (50%

    each), on to "Night Only." The Dusk toDawn operation will automatically

    calculate the number of hours between

    sunset and sunrise and enter deratings under

    seasonal load. (See Below.) This

    information is used by the statistical LOLP

    calculations. A system which has night loads

    will have a higher LOLP (worse reliability)

    than a system which is more closely

    matched to the solar resource.

    Seasonal Loads -- Clicking on this boxallows the user to specify the loads by

    month. This can be useful for specifying

    lighting loads which vary over the year, or

    loads such as air-conditioners, which onlyoperate in one season. Note that the

    maximum load is 100%. This means you

    must specify the maximum design load, then

    vary it as a percentage of the maximum.

    When you are done entering the data, clickon the "OK" button or press [Enter] on the

    keyboard. If you want to exit without saving

    changes, click on the Cancel" button or

    press [Esc] on the keyboard. To enter

    another load, click on the Next arrow.

    This will bring you to another load entry

    page. You can enter up to ten separate loads.If there are more than ten loads, you must

    group them into similar categories

    ("Lighting", "Telecom Equipment", etc.) and

    enter the conglomerate data.

    4.9.1 LoadSummaryReportThe Load Summary Report lists all of the details for

    the loads which were entered, including: Load

    Description, Load Size, Power Type, Conversion

    Efficiency, Load Hours, Load Profile, and seasonal

    loads. This information can be used to verify proper

    load input.

    A sample Load Summary Report is included in the

    Appendix.

  • 7/31/2019 NSol V4_6 Manual

    18/41

    PV System Sizing Program

    18

    5 ArrayTiltCalculation5.1 OverviewThe first step in the sizing process is to calculate the

    average insolation on the tilted array. This step is

    done using the "Tilt Analysis" page which isselected by clicking on the "Array Tilt" tab at the top

    of the notebook, or by choosing Sizing, then Array

    Tilt from the main menu.

    5.2 ArrayTiltThe basic window is shown below.

    The display consists of three sections - the control

    buttons, the insolation graph or chart, and the

    summary information.

    The controls along the right side of the page control

    the actions available. There are three types of

    controls: Array Tilt and Azimuth using "spin

    buttons", a box for selecting tracking items, and

    program / display control (Text / Graph, Print, and

    To Clipboard).

    To change the array tilt and orientation, simply click

    on the up and down arrows next to the tilt and

    azimuth options, or enter a value directly.

    In the northern hemisphere, an array with a positive

    tilt points towards the equator, and in the southernhemisphere, an array with a negative tilt points

    towards the equator.

    Since the calculations do not do "time of day"

    effects, the azimuth is simply the direction in

    degrees either east or west of due north/south.

    The "Text / Graph" button toggles the display

    between the graphic display and a text chart of the

    same data.

    In the "text" mode, the display switches to tabular

    data, as shown below.

    The column labeled "Horiz" represents the global

    horizontal insolation as entered previously. The

    values are kilowatt hours per square meter per day,

    or kWh/m2/d. The "Clearness" values are the ratio

    between the measured insolation and the

    extraterrestrial insolation. The "TiltFactor" is the

    calculated ratio between the horizontal and tilted

    insolation. The column labeled "Array" is themonthly average insolation on the array, also in

    kWh/m2/d.

    Two speed buttons control output of this

    information:

    Print - This button will print the Array Tilt Analysis

    report to the active printer.

    To Clipboard - This button will copy a bitmap of

    either the graph or the chart to the clipboard. It can

    then be pasted into a word processing document.

    Note that since this is a bitmap, the resolution is not

    especially good.Once you have finalized the tilt, you can choose

    Print to print a single page report (see Section 9.1),

    or click on the "Sizing (ALR)" tab at the top of the

    notebook to move on to the next step.

  • 7/31/2019 NSol V4_6 Manual

    19/41

    PV System Sizing Program

    19

    5.3 TrackingOptionsThe tracking buttons provide four choices for

    tracking arrays:

    The baseline choice is a fixed flat plate array.

    Vertical is for single axis vertical axis tracking. Theazimuth input has no effect on this calculation, since

    it assumes that the array is rotated from east to west

    using a vertical axis.

    Polar is for single axis polar tracking. The azimuth

    input has no effect on this calculation, since it

    assumes that the array is aligned north-south at the

    specified tilt

    Two Axis tracking assumes an array than can fully

    track the sun while it is above the horizon.

    5.4 OptimizationWhen optimizing the array tilt, the orientation of thearray is entered first, using the Azmith control box.

    The array is then tilted used the array tilt control

    button. When in Graph mode, the array insolation is

    plotted along with the horizontal insolation. The

    minimum and average insolation values are also

    displayed on the bottom center of the page.

    For standalone PV systems, the array is typically

    tilted to maximize the worst month insolation. For

    hybrid systems, the array tilt is often optimized for

    annual average insolation.

    5.5 ArrayInsolationReportThe Array Insolation Report shows both horizontal

    and tilted / array data in both tabular and graphic

    forms. The report also shows the average

    temperature and Clearness Index.

    A sample Array Insolation Report is included in the

    Appendix.

  • 7/31/2019 NSol V4_6 Manual

    20/41

  • 7/31/2019 NSol V4_6 Manual

    21/41

  • 7/31/2019 NSol V4_6 Manual

    22/41

    PV System Sizing Program

    22

    The system summary section at the bottom of the

    screen gives values for the PV array (# of modules,

    array kW and array amps), and the battery (# of

    days, battery kW, battery Ah, and battery volts).

    6.4.1 MPPTvs.NonMPPTControllerOne of the new features ofNSol!V4.6 is the optionto specify a Max Power Point Tracking (MPPT)

    controller.

    With a standard (non-MPPT) controller, the system

    treats the array as a current source, that is a

    constant current device. The current is set to the

    maximum power current of the module, derated

    properly for temperature. This tends to be slightly

    on the conservative side, as long as the module as

    sufficient voltage to so that it does not drop over

    the knee of the IV curve. This can be checked by

    clicking on the [IV Check] button.

    The user can specify an MPTT controller on the

    [Summary] tab of the Inputs dialog. There is a

    checkbox just below the System Voltage selection

    box.

    When an MPPT controller is selected, there is a

    flag on the summary page just below the controller

    symbol, as shown in the following screenshot:

    When this feature is selected, the system determines

    the array output by calculating the maximum power

    of the array at each point over a typical day for

    each month (15 minute intervals). This value is

    derated for temperature, and the battery chargecurrent is calculated by dividing the power by the

    battery charge voltage (average system voltage plus

    0.2 volts per cell).

    This value is then multiplied by 97% to account for

    losses in the controller. To approximate a change in

    this value, adjust the system losses value up or

    down.

    Note that this method does not check whether the

    array voltage is properly configured to operate

    with the controller. It is up to the system designer

    to ensure that the array is properly configured

    according to the controller manufacturerspecifications.

    Typically, MPPT controllers use a step down

    controller, so the array voltage is higher than would

    normally be used. To do this, uncheck the Auto

    Series box on the PV Module page of the inputs

    dialog, and set the number of series modules

    manually.

  • 7/31/2019 NSol V4_6 Manual

    23/41

    PV System Sizing Program

    23

    6.5 LOLPMethodOccasionally, the system designer needs to consider

    factors other than a simple energy balance in a

    system. For example, in high reliability

    telecommunications systems, the customer will often

    specify that the system must have an availability of99.9%, or a minimum battery state of charge of 50%

    under worst case conditions. If the sun always shone

    with the average value, then these would be easy

    calculations. However, the solar insolation varies

    day by day as well as month by month, meaning that

    you must have additional information to perform

    these calculations. The program provides the system

    designer with a powerful statistical tool called

    "Loss-Of-Load-Probability" (LOLP) calculations to

    estimate these advanced parameters using the same

    input data as in the ALR calculations described in

    Section 6.4.

    This section describes the screens used to display the

    results of these advanced calculations; the next

    section gives an overview of the LOLP calculation

    methodology.

    This analysis is done within the "LOLP Analysis"

    and "BSOC Reports" pages of the project notebook.

    The LOLP Analysis page can be accessed by

    clicking on the appropriate tab at the top of the

    notebook, or by choosing Sizing, then LOLP from

    the main menu.

    6.5.1LOLP

    Page

    The basic LOLP Analysis notebook page is shown

    below.

    This page has three sections -- the Graph / Chart,

    summary sizing information, and one control button:

    Text / Graph -- This button switches thedisplay between the LOLP graph and the

    data tables with detailed statistical

    information. (Shown below, with an

    explanation of the terms in the tableimmediately following)

    Terms in the LOLP Analysis table:

    The column labeled "Variability (%)" givesthe tilted insolation variability, which is

    defined as the standard deviation of the

    monthly insolation values divided by the

    average monthly insolation. The variabilityis an indication of how "steadily" the sun

    shines. A site with a low "variability" with

    have very consistent weather, while a site

    with a higher variability with have a greater

    mix of sunny and cloudy days.

    The column labeled "Correlation (%)" givesthe day-to-day correlation of the solar

    insolation. The correlation is the probability

    that one day will be like the next (e.g. that a

    sunny day will follow a sunny day). In

    general a higher correlation means more

    steady weather. The column labeled "Array/Load Ratio" is

    simply the ALR from the previous section,

    repeated here for information's sake.

    The "BSOC Avg (%)" column gives themonthly average battery state-of-charge of

    the battery. Note that this is never 100%,

    since the load is never perfectly matched

    with the array, and the battery is usually

  • 7/31/2019 NSol V4_6 Manual

    24/41

    PV System Sizing Program

    24

    discharging at night. However, this gives a

    good indication of the ability of the system

    to maintain the health of the battery.

    The "LOLP %" column gives the "Loss-OfLoad-Probability" (LOLP) for that

    month. The LOLP is the statistical

    probability that the system will not havesufficient energy to supply the load on one

    of the days during that month. The value is

    given as a percentage of days that will

    encounter an LOLP event. (For example, an

    LOLP value of 1.0 percent in October means

    that the system will "go down" one day out

    of every 100 "October days," or about once

    every three years since October has 31 days.

    An LOLP of 3.0 percent means

    approximately one outage per month, while

    an LOLP of 0.3 percent means

    approximately one outage every 10 years.) The SEP % page shows the Surplus

    Energy Probability, which is analogous to

    the LOLP, except at the top end of the

    battery. This is the probability that the

    battery will be fully charged and will require

    regulation on any given day.

    6.5.2 BSOCPageThe "BSOC" page shows the LOLP data in a

    somewhat different format, as shown below. It

    concentrates on the part of the analysis that shows

    the probability of the battery being at differentstates-of-charge during different months of the year.

    This page displays a choice of two graphs or a

    tabular report.

    The default choice displays a graph showing the

    average Battery SOC for each month.

    The second graph and the table show the percentage

    of time that the battery will spend in each state-of-

    charge during each month. The battery is divided up

    into ten segments. This means that if the maximum

    battery DOD is 80%, the segments will be 8% SOC.

    Likewise with 100% max DOD, the segments will

    be 10% and with 50% max DOD, the segments will

    be 5%.

    The third graph is in the form of a three-dimensional

    bar chart, with the higher states of charge towards

    the rear of the graph. If the chart looks like a steep

    green cliff with a flat sea in front (as shownabove), the system is fine.

    If the blue segments of the chart are level or taller

  • 7/31/2019 NSol V4_6 Manual

    25/41

    PV System Sizing Program

    25

    than the green in any month, this is an indication of

    a problem. An example is shown below:

    6.5.3 NoteonCalculationsThe LOLP calculations are very "math intensive"

    and take quite a while, even on powerful computers,

    so a status window appears to indicate which month

    is being analyzed. In general, systems with larger

    batteries take longer to analyze. This used to be a big

    problem (when NSol!first came out, the

    recalculation could take up to three minutes) but

    now, most computers are fast enough so that a

    manual recalculation feature has been removed from

    the program.

    Note - occasionally, the statistical model will notwork for a specific set of data. This does not imply

    that the system is not reliable during that month, it

    merely means that the model cannot find a

    mathematically valid solution. When this occurs, the

    program will print out a set of three asterisks (***)

    in the place of the Variability, correlation, average

    BSOC, and LOLP.

    The user must then use engineering judgment as to

    whether the system is reliable for that month. For

    example, if the array to load ratio is greater than 2.0

    and there is sufficient battery storage and the months

    on either side of the asterisks are valid, you canassume that the system is reliable. Alternatively, you

    can try changing the solar insolation data slightly to

    see if the model will work.

    Once you have finished examining the LOLP

    screens, you can click on the Print speed button to

    print a single page "Availability Analysis" report.

    6.6 LOLPMethodologyOne of the functions of the NSol!program is to

    reduce the complexity of the statistical

    calculations to a useful format. The purpose of this

    section is to elaborate a little on the actual

    calculations used.Two cautions apply:

    First, this discussion is not for the fainthearted

    when it comes to math. Even the simplified

    discussion cannot avoid some complexity.

    Second, this is not a rigorous presentation of the

    exact methodology. The algorithm was adapted from

    existing published papers, using techniques

    proprietary to Orion Energy Corporation. Professor

    L. L. Bucciarelli of the MIT School of Engineering

    developed the actual algorithm under contract to

    Orion Energy Corporation. There is a list oftechnical papers in the appendix, which themathematically inquisitive reader can reference for

    more details.

    There are two basic parts of the LOLP algorithm -

    determination of the insolation variability incident

    upon the photovoltaic array, and determination ofthe probability distribution for the Battery SOC (its

    stationary states) and subsequent LOLP.

    The first part is an adaptation of the concept of the

    use of Markov Transition Matrices in determining

    solar insolation variability, as presented by Aguiar,

    Collares-Pereira and Conde in their paper SimpleProcedure for Generating Sequences of Daily

    Radiation Values Using a Library of Markov

    Transition Matrices (Solar Energy, Vol 40. No. 3

    pp. 269-279, 1988). Their paper presents the

    methodology for using Markov Transition Matrices

    (MTMs) to generate radiation sequences for

    simulation models.

    An MTM is a matrix which gives estimates for the

    probability that the insolation value for the next day

    will be at level "j" given that it was at level "i"

    today. Aguiar et. al, and we, take the

    month as the fundamental period during which the

    statistical analysis applies. They, as do we, break the

    range of possible insolation values into ten discrete

    steps and use the clearness index as its measure. For

    example, if one day during the month has a clearness

    of 45%, the matrix then gives the probabilities of the

    next day being at 40%, 35%, 50, 55%, 60%, etc.

    These day to day transition matrices can be used to

  • 7/31/2019 NSol V4_6 Manual

    26/41

    PV System Sizing Program

    26

    calculate the probability distribution for the daily,

    global horizontal insolation for any month. Each

    transition matrix has associated with it a mean

    clearness index and a variance. Knowing the

    monthly values for the mean clearness index at a

    particular site, we can judiciously choose an

    appropriate MTM from the set constructed byAguiar et. al. A day-to-day correlation coefficient is

    also computed for each transition matrix.

    The major limitation of this method is that the

    MTMs in the paper apply only to global horizontal

    (GH) insolation data. Previous work by various

    authors has shown that the variability of the tilted

    insolation is significantly different from that of the

    horizontal insolation, primarily because of the

    effects of direct and reflected radiation. The

    technique used by NSol!converts the MTMs for the

    GH insolation into equivalent matrices for the tilted

    insolation, using GH to

    array insolation conversions for each insolation level

    of the original MTM. The result is an MTM that

    describes the behavior of the insolation resource on

    the tilted array, as well as its probability distribution

    and a measure of day-to-day correlation. Unlike

    other statistical methods which use table-lookups to

    approximate these values based on standard tilts and

    latitudes, this method calculates the values for the

    exact tilt and latitude of the system.

    The next step is to apply this data to the system

    specifications (array/load ratio and battery size) inorder to determine the statistical performance - the

    stationary states for the battery state of charge - of

    the proposed PV system. This section of the

    algorithm is based on previous work by Bucciarelli

    (ref L. L. Bucciarelli Jr., Estimating Loss-Of-Power

    Probabilities of Stand-Alone Photovoltaic Solar

    Energy Systems, Solar Energy Vol 32, pp. 205-209,

    1984) but adapted and generalized to use the

    transition matrices derived in the first steps. These

    are combined with the system loads, array/load ratio,

    and battery size to calculate a battery transition

    matrix showing the probability of the battery beingat any given SOC on any day during that month.

    There are two refinements over the previous method.

    First, the battery is divided into 10 discrete SOC

    levels (thus the 8% "battery segment" for a lead acid

    battery). Second, the load can have both "day" and

    "night" components defined by the given load

    profile. A load which is "night only" will exhibit

    poorer system performance than a load which is

    daytime only and matched more closely to the solar

    resource.

    In addition to probability distribution for the battery

    SOC levels, the algorithm also gives the probability

    of a deficit (LOLP), an estimate of that deficit, the

    probability of a surplus, the estimate of that surplus,

    and a measure of the robustness of these

    calculations. In fact there is so much information

    that we found it impossible to get it all into the

    output reports of this version of NSol !.

    In summary, NSol!presents a great deal of data to

    help the systems engineer evaluate the projected

    performance of the system, and to compare it to

    other options available. However, the user must

    remember that these results are subject to the

    accuracy of the input data, and to a number of

    assumptions discussed above. Annual variations in

    insolation may cause significant variations in systemperformance, even when the best input data is used.

    In final judgment, it is up to the systems engineer to

    design a system to best meet customer requirements.

    6.7 IVCurveAnalysisThis features enables a closer look at a simulated

    array IV curve for different periods of the standard

    day for each month. The user can look at either IV or

    PV curves for either a module or over the entire

    year.

    The simulated data is calculated using the modules /

    array

    6.8 Reports6.8.1 SystemSizingReportThe System Sizing Report shows basic sizing

    information using the ALR sizing method. Data is

    presented in both tabular and graphic formats, and

    includes array insolation, temperature, array output,

    system losses, daily load, night load %, monthly

    battery size and array/load ratio.

    A sample System Sizing Report is included in the

    Appendix.

    6.8.2 SystemAvailability(LOLP)ReportThe System Availability Report presents details of

    standalone system performance using the LOLP

    sizing method. Data is presented in both tabular and

    graphic formats, and includes array insolation,

    insolation variability, day-to-day correlation, and

  • 7/31/2019 NSol V4_6 Manual

    27/41

    PV System Sizing Program

    27

    array/load ratio, monthly battery size, average

    BSOC, monthly LOLP and month SEP.

    A sample System Availability Report is included in

    the Appendix.

    6.8.3 BatterySOCReportThe Battery SOC Report presents details of battery

    performance based on the LOLP sizing method.

    Data is presented in both tabular and graphic

    formats, and includes system summary information,

    as well as battery SOC bin data information similar

    to that presented in the program. The graph shows

    average battery SOC by month.

    A sample Battery SOC Report is included in the

    Appendix.

    6.8.4Standalone

    System

    Summary

    Report

    The System Availability Report presents details of

    standalone system performance using the LOLP

    sizing method. Data is presented in both tabular and

    graphic formats, and includes array insolation,

    insolation variability, day-to-day correlation, and

    array/load ratio, monthly battery size, average

    BSOC, monthly LOLP and month SEP.

    A sample System Availability Report is included in

    the Appendix.

  • 7/31/2019 NSol V4_6 Manual

    28/41

    PV System Sizing Program

    28

    7 SystemSizing Hybrid7.1 OverviewNSol!uses a simplified sizing calculation for

    estimating performance of hybrid power systems.

    The basic process is to calculate the energy requiredby the load during a typical month, subtract the

    energy available from the PV array, and calculate

    generator performance based on supplying the

    remaining energy. The result is a description ofgenerator operating hours, fuel consumption, and

    number of charge cycles for each month.

    7.2 SelectingComponentsPrior to starting the sizing process, the user must

    select a PV module, a battery, and at least one valid

    load. The user should also select a site, and enter a

    valid system voltage.

    The user must also enter the following generator and

    battery charger information:

    Generator Manufacturer Generator Model Genset Power Rating

    Genset Power Factor Rating Full Load Fuel Consumption (FLFC) Quarter Load Fuel Consumption (QLFC)

    Maintenance Information: Oil Change Interval Decoke Interval Overhaul Interval Generator Life

    Battery Charger Current Battery Charger Power Factor Battery Charger Efficiency In addition, the data input screen allows the

    following control setpoint inputs: Generator Start Battery State of Charge Generator Stop BSOC (normal charge) Normal Charge Coloumbic (Amp-hr)

    Efficiency

    Equalization Frequency The followingfigure shows the Hybrid system input

    screen:

    7.3 SettingArrayTiltThe array tilt, azimuth and tracking options should

    be set as described in Section 5.

    In general, hybrid system should have the arraytilted for maximum energy production, rather than

    worst case month. This is typically at or near

    latitude.

    7.4 HybridSystemAnalysisThe following process is used to make the generator

    calculations:

    1. The amp-hour deficit that must besupplied by the generator is calculated by

    subtracting the derated array amp-hours

    from the DC load amp hours. This isexpressed as generator amp-hours per

    month.

    2. The typical cycle is determined by findingthe difference between in battery State-of-

    Charge (SOC) for a typical charge cycle.

    These values are entered in the Hybrid Page

    of the Systems Inputs dialog box. Typical

    start of charge is 40% SOC and end of

  • 7/31/2019 NSol V4_6 Manual

    29/41

    PV System Sizing Program

    29

    charge is 85-95% SOC, so each cycle

    typically replaces 45-55% of the battery

    capacity.

    3. The time it takes to recharge the battery iscalculated by dividing the net battery

    charger output (rectifier rating minus the

    average DC load) into the amp-hourrecharge requirement, and dividing by the

    battery amp-hour recharge efficiency.

    (Note this number is typically very high

    for charge cycles up to 85% SOC, and

    decreases rapidly beyond that.)

    4. For example, with a 1000 Ah battery, a 100amp rectifier, a 10 amp load and a 95%

    battery efficiency, it would take a generator

    5.25 hours for a typical cycle from 40% to

    85% SOC.

    5. Generator fuel consumption is calculated

    based on the electrical load presented to thegenerator (as a percentage of its full load)

    multiplied by the number of hours that the

    generator operates.

    6. The number of cycles per month iscalculated by dividing the Gen Ah

    requirement by the net number of amp-hours

    during each charge cycle. This includes both

    the amp-hours that recharge the battery and

    the amp-hours that are supplied to the load

    while the generator is operating. This is

    often described as a fractional number of

    cycles e.g., 8.4 cycles for a given month.This means that the long term average

    would be 8.4, but any given year would

    probably have 8 or 9 cycles.

    7. Finally, a factor is added for periodicequalization of the batteries. This involves

    running the generator for an extended period

    of time to bring the batteries to full charge

    (and slightly beyond). The user enters the

    number of equalizations per month, which

    depends on the battery technology and

    control system being used.

    8. Operating hours and fuel consumption permonth are calculated by multiplying the

    parameters per typical cycle by the

    number of cycles in a given month, and

    adding the appropriate values for

    equalization.

    9. Monthly values are then totaled to giveannual values for the basic parameters.

    This a simplified approach, and ignores such factors

    as daily load profile, as well as daily, timed

    operation of the generators, as opposed to battery

    based demand operation, and the differences

    between DC Bus and AC Bus hybrids. It also

    simplifies factors such as multistage charging and

    battery aging. However, it will give a reasonableestimate of generator performance for most typical

    system designs.

    General design goals typically call for a limited use

    of generator-supplied energy, limited fuel use, or

    limited operating hours. The NSol!algorithm allows

    the designer to evaluate each of these variables in

    real time using different sizing options.

    7.5 HybridSystemAnalysisScreenThe basic hybrid system design tasks can be doneinteractively from the Hybrid page of the

    notebook.

    The Text button allows the user to switch between

    the graphic Display and the Text Display.

  • 7/31/2019 NSol V4_6 Manual

    30/41

  • 7/31/2019 NSol V4_6 Manual

    31/41

  • 7/31/2019 NSol V4_6 Manual

    32/41

    PV System Sizing Program

    32

    8.5 GridSystemScreensThere are two primary screens used for analysis of

    Grid-Connect Systems. The first is a summary page

    showing the monthly energy production of the PV

    array in graphic and tabular format when printed out.

    This information is also available in numerical form.

    The second is a set of graphs that show typical daily

    performance for each month of the year.

    8.6 GridSystemReportThe Grid Sizing Report presents data on grid system

    sizing and system performance. Data is presented in

    both tabular and graphic formats, and includes

    system summary information, as well as summary

    and detailed monthly information on insolation, DC

    performance and AC performance of the system.

    A sample Grid Sizing Report is included in the

    Appendix.

  • 7/31/2019 NSol V4_6 Manual

    33/41

    PV System Sizing Program

    33

    9 ReportsandExportingData9.1 ReportSummarySeven formal reports are available from NSol!:

    Tilt Analysis Report

    ALR Sizing Report LOLP Report BSOC Report System Summary Report Hybrid Analysis Report Grid Analysis Report

    Each of the individual graphs may be printed or

    exported to the clipboard for inclusion in a proposal.

    System data for the standalone and hybrid systems

    may be exported for spreadsheet analysis or further

    formatting and inclusion in a proposal.

    Detailed grid analysis data can be exported forfurther spreadsheet analysis.

    9.2 PrintingReports9.2.1 PrintingFormal reports can be printed in three ways:

    Clicking on the Printer speed button will print a

    report appropriate for the active page, if it is

    available.

    Choosing File _Print from the main menu

    accomplishes the same thing.

    Choosing File_PrintAll from the main menu

    allows the user to choose a set of reports to print

    with a single command.

    9.2.2 PageSetupNote you can use File_Print Setup to set the

    default print conditions. The reports work best when

    printed in portrait mode.

    9.2.3 PDFFilesReports can be printed out to a PDF file if the user

    has an appropriate printer driver (such as an AdobeAcrobat driver or CutePDF) installed.

    9.3 PrintingChartsCharts can be printed by clicking on the Print

    Chart Button which shows a small picture of a

    chart. (It is third from right on the Toolbar.) This

    will print the current visible chart.

    9.4 ExportingChartsCharts can be exported to the clipboard by clicking

    on the Export Chart Button which shows a small

    picture of a file with a red arrow. (It is second from

    right on the Toolbar.) This will copy the current

    visible chart to the as a Windows Metafile. This can

    then be pasted into any standard document, such as a

    word processing file.

    9.5 ExportingASCIIDataforSpreadsheets

    Summary Sizing Data can be exported by clickingchoosing File_Export from the main menu.

    The data can be exported as either comma separated

    values or tab separated values. This data can then be

    imported into a spreadsheet or word processingdocument for further formatting or analysis.

    9.6 ExportingGridDataforSpreadsheets

    The detailed grid-calculation data can be saved to a

    tab-separated file for further analysis by spreadsheet.

    Click on the [Export Data] button, then select a filename.

    The data fields are:

    Month Time of day Irradiance (Plane of Array) Ambient Temp Cell temp Temp Derating Module Output (DC) Array Output (DC)

    System Output (AC)

  • 7/31/2019 NSol V4_6 Manual

    34/41

    PV System Sizing Program

    34

    Appendix 1Sample Reports

  • 7/31/2019 NSol V4_6 Manual

    35/41

    PV System Sizing Program

    35

    Appendix 2Glossary of

    Terms

  • 7/31/2019 NSol V4_6 Manual

    36/41

  • 7/31/2019 NSol V4_6 Manual

    37/41

    PV System Sizing Program

    37

    Extraterrestrial Insolation The amount of solar radiation that strikes a surface outside the earth's atmosphere.

    Used to calculate the clearness ratio.

    Global Horizontal Insolation Insolation as measured by a horizontally mounted pyranometer. Typically

    expressed in Langleys, MJ/m2 or kWh/m2. NSol! uses the latter for its calculations.

    Insolation Solar radiation.

    Isc Short Circuit Current -- a measure of PV modules, typically found on the data sheet

    Ityp Typical operating current of a PV module, also call peak power current. Typically

    found on the datasheet.

    Kilowatt-hours A measure of electrical consumption or production. One kilowatt hour is one kilowatt

    for one hour.

    KT_Bar Clearness factor

    kWh Kilowatt-hour abbreviation

    LOLP Loss of Load Probability

    Loss-of-Load-Probability A measure of the reliability of a PV system. The LOLP in NSol ! is expressed as the

    percentage of "month-days" which will experience an outage. Example - a value of

    1.0% in October means that the load will be disconnected once every 100 "October"

    days. Since October has 31 days this is approximately once every three years.

    Markov Transition Matrix A matrix which gives estimates for the probability that the insolation value for the

    next day will be at level "j" given that it was at level "i" today. Used in the NSol !

    statistical LOLP calculations.

    Module A single PV module, typically 12 V and 40 to 60 watts.

    Monobloc A package with numerous battery cells in series. An automotive battery is an example

    of a monobloc. (See "cell".)

    MTM Markov Transition Matrix

    Photovoltaics The process of converting solar energy directly into electricity.

    PV Photovoltaics

    PVs What right-handed people call Photovoltaics

    Reflectance The percentage of insolation that strikes the ground which is reflected. A sandy desert

    or snowy field would have a higher reflectance than a grassy field or a puddle of mud.

    SOC State-of-Charge. The amount of energy remaining in a battery as a percentage of its

    overall capacity.

  • 7/31/2019 NSol V4_6 Manual

    38/41

    PV System Sizing Program

    38

    Sigma Ratio see variability

    Temperature - Ambient The temperature in an open outdoor space. NSol ! uses monthly average ambient

    temperatures to derate battery capacities.

    Tilt Factor The correction applied to the Global Horizontal Insolation used to determine the

    insolation on the tilted array.

    Variability (Insolation) A measure of the "steadiness" of the solar insolation. The ratio between the standard

    deviation (sigma) and the average value (mean) for the month.

    Voc Open Circuit Voltage. The voltage of a PV module with no load connected to it.

    Typically found on PV module data sheets.

    Vtyp Operating voltage of a PV module at its peak power.

    W(p ) Peak wattage output of a PV panel or PV array.

  • 7/31/2019 NSol V4_6 Manual

    39/41

    PV System Sizing Program

    39

    Appendix 3Sizing

    References

  • 7/31/2019 NSol V4_6 Manual

    40/41

    PV System Sizing Program

    40

    Sizing References

    L. L. Bucciarelli, "Estimating Loss-of-Power Probabilities of Standalone Photovoltaic Solar Energy

    Systems," Solar Energy Vol 32, No. 2, pp. 205-209, 1984

    L. L. Bucciarelli, "The Effect of Day-today Correlation in Solar Radiation on the Probability of Loss-ofPower

    In a Standalone Photovoltaic Energy System," Solar Energy Vol

    36, No. 1, pp. 11-14, 1986

    R. J. Aguiar, et al, "Simple Procedures for Generating Sequences of Daily Radiation Values Using a Library

    of Markov Transistion Matrices," Solar Energy Vol 40, No. 3, pp.

    269-279, 1988

    "The Frequency Distribution of Daily Insolation Values," Solar Energy Vol 27, pp. 1-5, 1981 DT

    Reindl, et al, "Diffuse Fraction Correlations," Solar Energy Vol 45, No. 1, pp. 1-7, 1990

    Insolation References

    "Solar Radiation Data Manual for Flat-Plate and Concentrating Solar Collectors"

    Document # NREL/TP-463-5607

    National Renewable Energy Laboratory

    1617 Cole Blvd

    Golden, CO 80401-3393

    USA

    Phone: (303) 275-4099

    "International Solar Irradiation Database"

    University of Massachusetts-Lowell

    Photovoltaic Program

    1 University Ave

    Lowell, MA 01854

    USA

    "National Solar Radiation Database"

    National Climactic Data Center

    Asheville, NC

    Phone (704) 259-0682

  • 7/31/2019 NSol V4_6 Manual

    41/41

    PV System Sizing Program

    TECH MEMO

    Subject: Insolation Conversions

    There are three basic units used in solar insolation inputs - kWh/m2, MJ/m2 and Langleys. This memo

    defines the conversion factors used between these factors.

    1. kWh/m2 Since we are working with electrical systems, this is the most convent set of units. For this

    reason, it is

    the default and requires no conversion.

    2. MJ/m2 1 Joule = 1 Watt-sec so

    1 kWh-hr = 3.6 x 106 J = 3.6 MJ

    (1 watt * 60 sec/min x 60 min/hr = 3600 watt-sec/hr

    so 1 kilowatt = 1,000 watts = 3,600,000 watt-sec/hr = 3.6 MJ / hr so 1 kWh = 1kW x 1 hr = 3.6 MJ)

    The conversion is thus: MJ/m2 / 3.6 = kWh/m2

    3. Langleys

    Langleys have the units cal per cm2 per hr.

    1 Langley = 4.184 x 104 J/m2

    so

    1 Langley = (4.184 x 104 J/m2) / (3.6 MJ / kWh-hr) = 1 / 86.04 kWh/m2

    The conversion is thus: Langleys / 86.04 = kWh/m2.