Asset: P.S. 65 - BROOKLYN, 158 RICHMOND STREET, New York, 11208
Inspection Id Inspection Type Time In Last Edited
SA : K065 Architectural - Senior 2020-01-28 10:56 AM 2020-02-05 3:17 PM
AA : K065 Architectural - Associate 2020-01-28 12:15 PM 2020-02-04 2:04 PM
Asset Data
Question Answer
Was the building fully accessible for inspection Yes
Principal(s) Information
Principal Name Max Milligan
Organization Achievement First East New York Middle School - Brooklyn
Did you meet with this Principal? No
Did this Principal provide feedback? Yes
Summary of Principal's Feedback Director of School Operations Ernesto Soto, commented on behalf ofthe Principal as follows: 1. The gutters and leaders occasionallyoverflow and need to be cleaned periodically.
Custodian Was not present
Fireman Alphonso Price
Building Square Footage 23000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 2+B+Attic+Tower
Comments on the Number of Classrooms 9
Comments on the Year Built 1873
Student Population 247
Staff Population 35
Weather Fair
Facade Photo
Richmond Street - Northwest View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 1 of 32
Main Entrance Photo
Facade A - Richmond Street
Roof Photo
Roof 3 - West View
Have any Systems/Major Building Components been upgraded? Yes
Systems: Gutters and leaders repairs.
Year: 2019
Systems: Partial Roofing repairs.
Year: 2014
Systems: Exterior Walls, Chimney and Parapets repointing; Leadersand Gutters replacement; Student and Staff Toilet Roomsupgrade; Basement Student Toilet Rooms upgrade to HCcompliance.
Year: 2013
Systems: Partial Roofing repairs.
Year: 2011
Systems: Schoolyard replacement.
Year: 2009
Systems: Perimeter Site Gates installation.
Year: 2007
Systems: Exterior Modernization Program including Roofing andFlashing replacement; Roof Hatch Doors replacement;Window and Window Guards replacement; Exterior Wallsrepointing and repairs.
Year: 2003
Have there been any New Building Additions? No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 2 of 32
Tandem Schools? No
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? No
Are SOME floors other than the 1st floor and basement accessible through compliantmeans?
No
Do any of the following spaces exist on the First floor? Classroom, Art Room,Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, ScienceLabs
No
Do any of the following spaces exist in the Basement? Classroom, Art Room,Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, ScienceLabs
Yes
For the rooms that do exist, are SOME of them accessible in the Basement? Yes
Boys and Girls or Unisex accessible toilets exist in the Basement? Yes
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings Yes Yes
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies Yes
Interior Elevators No
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms No
Auditorium No
Cafeteria Basement Yes Yes Yes Yes
Classrooms None on Accessible Route Yes No Not on Accessible Route
Computer Rooms No
Gymnasium No
Library Room 209 Yes No Not on Accessible Route
Main Office Room 102 Yes No Not on Accessible Route
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 3 of 32
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Rooms & Spaces
Multi-purpose Room No
Nurse's Room Basement Yes Yes
Pool No
Science Lab No
Toilet Rooms (Boys) Basement Yes Yes
Toilet Rooms (Girls) Basement Yes Yes
Toilet Rooms (Staff) Basement Yes No Accessory ArrangementClear opening < 32"Sink ArrangementTurning RadiusUrinal ArrangementWater ClosetArrangement
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Does not Exist
AWNINGS AND CANOPIES Does not Exist
CHIMNEY Inspected
Material Type(s) Masonry
Condition 3 - Fair
Deficiency BRICK: OPEN JOINTS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 4 of 32
Question Response
EXTERIOR
CHIMNEY
Roof Plan reference
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 - Chimney 2
Violations No violations recorded.
COPING Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CORNICE Inspected
Condition 2 - Between Good and Fair
Deficiency WOOD: DETERIORATED
Roof Plan reference
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 5 of 32
Question Response
EXTERIOR
CORNICE
Deficiency Photo1
Facade D
Violations No violations recorded.
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 4 - Between Fair and Poor
Deficiency WOOD: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION
Roof Plan reference
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 6 of 32
Question Response
EXTERIOR
DOORS Inspected
TRANSOM/SIDE LIGHT Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
EXTERIOR WALLS Inspected
Material Type(s) Masonry
Replacement Quantity 19,000
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 19,000
Instance Quantity Uom S.F.
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Elevation
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade E
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 7 of 32
Question Response
EXTERIOR
EXTERIOR WALLS Inspected
Deficiency BRICK: CRACKS/DISPLACED/SPALLED BRICK AT BUILDINGCORNERS
Roof Plan reference
Elevation
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REMOVE AND REBUILD
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency BRICK: DETERIORATED MASONRY SILLS
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 8 of 32
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 30
Quantity Uom L.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency BRICK: MAJOR / THRU CRACKS
Roof Plan reference
Elevation
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REMOVE AND REBUILD
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 9 of 32
Question Response
EXTERIOR
EXTERIOR WALLS
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency BRICK: EFFLORESCENCE
Roof Plan reference
Elevation
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 1
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Deficiency BRICK: MINOR CRACKS AND SPALLING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 10 of 32
Question Response
EXTERIOR
EXTERIOR WALLS
Roof Plan reference
Elevation
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action RESTITCH
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
EXTERIOR SOFFITS Does not Exist
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 500
Replacement Uom C.F.
InspectedInstance on Facades C, K
Instance Condition 2 - Between Good and Fair
Instance Quantity 500
Instance Quantity Uom C.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 11 of 32
Question Response
EXTERIOR
PARAPETS Inspected
Deficiency No deficiencies recorded
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 8,500
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF BARRIER Does not Exist
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on Metal: Roofs 1, 3, 4, 5, 6
Instance Condition 1 - Good
Instance Quantity 8,000
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2003
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
InspectedInstance on Modified Bitumen: Roof 2
Instance Condition 3 - Fair
Instance Quantity 500
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2003
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
ROOFING DRAINS Does not Exist
Specialties Inspected
BULKHEAD/PENTHOUSE Does not Exist
CUPOLA/ SPIRES/ TOWERS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Does not Exist
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Inspected
Condition 4 - Between Fair and Poor
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 12 of 32
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade H
Violations No violations recorded.
RAILINGS Inspected
Condition 3 - Fair
Deficiency RUST - MINOR
Roof Plan reference
Deficiency Quantity 15
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 13 of 32
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS Inspected
Condition 2 - Between Good and Fair
Deficiency CONCRETE: CRACKS/SPALLING - MINOR
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade H
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 3,000
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 3 - Fair
Deficiency RUST - MINOR
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 14 of 32
Question Response
EXTERIOR
WINDOWS
EXTERIOR GUARDS
Elevation
Deficiency Quantity 500
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
Material Type(s) Solid Wood
InspectedInstance on Wood: All Facades
Instance Condition 2 - Between Good and Fair
Instance Quantity 3,000
Instance Quantity Uom S.F.
Installation Year 2010
Source of Installation Custodial Staff
Deficiency No deficiencies recorded
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 3 - Fair
Deficiency WOOD COLUMNS/BEAMS: DETERIORATED
Deficiency Location/Instance Attic
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 15 of 32
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS
Deficiency Photo1
Attic
Violations No violations recorded.
Deficiency MASONRY BEARING WALL: CRACKED/SPALLED
Deficiency Location/Instance Basement - Pump Room, Cafeteria, Corridor
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action RESTITCH
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Pump Room
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
FOUNDATION WALLS Inspected
Material Type(s) Masonry
Condition 3 - Fair
Deficiency BRICK: OPEN JOINTS
Deficiency Location/Instance Basement - Pump Room
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 16 of 32
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS
Deficiency Photo1
Basement - Pump Room
Violations No violations recorded.
Deficiency BRICK: CRACKED/SPALLED
Deficiency Location/Instance Basement - Pump Room, Corridor
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action RESTITCH
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Corridor
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 3 - Fair
Deficiency WOOD COLUMNS AND BEAMS: DETERIORATED
Deficiency Location/Instance Attic
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 17 of 32
Question Response
INTERIOR
STRUCTURAL Inspected
ROOF STRUCTURE Inspected
Attic
Violations No violations recorded.
VAULTS-BUNKERS Does not Exist
AUDITORIUM Does not Exist
CAFETERIA Inspected
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
Not RequiredInstance on Basement
Fixed Equipment
Does not ExistInstance on Basement
Floor Finish
InspectedInstance on Basement
Condition 1 - Good
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on Basement
Stage
Does not ExistInstance on Basement
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency BRICK: CRACKS/SPALLING
Deficiency Location/Instance Near Entrance, Near windows
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near windows
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on Basement
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 18 of 32
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency METAL PAN: DAMAGED/MISSING
Deficiency Location/Instance Room 202, Principal Office
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Principal Office
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR AND FRAME
Deficiency Location/Instance Basement Nurse Office
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Basement Nurse Office
Violations No violations recorded.
Deficiency METAL CLAD WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 200, 100
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 19 of 32
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Door(s)
Deficiency Photo1
Room 200
Violations No violations recorded.
Floor Finish Inspected
Condition 5 - Poor
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Rooms 207, 205, 200, 103, 101 and others
Deficiency Quantity 1,000
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 200
Violations No violations recorded.
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Room 205, 204, 202
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 20 of 32
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish Inspected
Room 202
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Principal Office, Near Principal Office, Main Entrance
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Principal Office
Violations No violations recorded.
Specialties Does not Exist
GYMNASIUM Does not Exist
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency DETERIORATED/TORN-OUT/MISSING
Deficiency Location/Instance Stair B/1
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair B/1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 21 of 32
Question Response
INTERIOR
INTERIOR GUARDS Inspected
Violations No violations recorded.
KITCHEN Inspected
InspectedInstance on Basement (300 SF)
Ceiling
InspectedInstance on Basement (300 SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Basement (300 SF)
Condition 1 - Good
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Basement (300 SF)
Condition 5 - Poor
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Center, Servery, Near Entrance
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Entrance
Violations No violations recorded.
Walls
InspectedInstance on Basement (300 SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIBRARY Inspected
InspectedInstance on Room 209
Built-in Furnishing
Does not ExistInstance on Room 209
Ceiling
InspectedInstance on Room 209
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Room 209
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 22 of 32
Question Response
INTERIOR
LIBRARY
Floor Finish
InspectedInstance on Room 209
Condition 3 - Fair
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Near Entrance
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Entrance
Violations No violations recorded.
Walls
InspectedInstance on Room 209
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOCKER ROOM Does not Exist
MULTI-PURPOSE ROOM Does not Exist
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Does not Exist
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Does not Exist
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Yes
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Partition Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency WOOD: BROKEN/DETERIORATED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 23 of 32
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
Deficiency Location/Instance Near Principal Office
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Principal Office
Violations No violations recorded.
Deficiency CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Stair D/1
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair D/1
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance 2nd Floor, Inside Room 200
Deficiency Quantity 1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 24 of 32
Question Response
INTERIOR
TOILET ROOMS - STAFF
Door(s)
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
2nd Floor
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Does not Exist
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance 2nd Floor, Inside Room 200
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
2nd Floor
Violations No violations recorded.
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Basement - Girls
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 25 of 32
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Door(s)
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Basement - Girls
Violations No violations recorded.
Deficiency WOOD: DAMAGED LOUVER
Deficiency Location/Instance Basement - Boys
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Basement - Boys
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 5 - Poor
Deficiency RUST - MAJOR
Deficiency Location/Instance Basement - Boys
Deficiency Quantity 4
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 26 of 32
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Stalls
Deficiency Photo1
Basement - Boys
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Concrete Covering Does not Exist
Drainage System for Soil Does not Exist
DRINKING FOUNTAINS Does not Exist
FENCES Inspected
Condition 3 - Fair
Deficiency WROUGHT IRON: MISSING SECTIONS
Deficiency Location/Instance Ridgewood Avenue
Deficiency Quantity 120
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 27 of 32
Question Response
SITE
FENCES
Deficiency Photo1
Ridgewood Avenue
Violations No violations recorded.
Deficiency CHAIN LINK: DAMAGED/DETERIORATED
Deficiency Location/Instance Schoolyard North
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard North
Violations No violations recorded.
Deficiency CONCRETE CURB: DAMAGED/DETERIORATED
Deficiency Location/Instance Schoolyard
Deficiency Quantity 35
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard North
Violations No violations recorded.
Deficiency CHAIN LINK: DAMAGED POST/RAIL
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 28 of 32
Question Response
SITE
FENCES
Deficiency Location/Instance Schoolyard, Behind Building
Deficiency Quantity 40
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Behind Building
Violations No violations recorded.
Deficiency WROUGHT IRON: DAMAGED/DETERIORATED
Deficiency Location/Instance Richmond Avenue
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Richmond Avenue
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Does not Exist
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Does not Exist
Student Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 3 - Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 29 of 32
Question Response
SITE
PAVING
Student Use
Asphalt
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 120
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard
Violations No violations recorded.
Concrete Does not Exist
Pavers Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Concrete Does not Exist
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency HEAVING
Deficiency Location/Instance Ridgewood Avenue
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 30 of 32
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Ridgewood Avenue
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Ridgewood Avenue
Deficiency Quantity 300
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Ridgewood Avenue
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Does not Exist
PLAYING SURFACE Does not Exist
RETAINING WALLS Inspected
Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?
No
Condition 3 - Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Schoolyard South
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard South
Violations No violations recorded.
SEATING Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 31 of 32
Question Response
SITE
SEATING
Benches Inspected
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Metal/Wood/Plastic Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Bleachers Does not Exist
SITE WALLS (NOT RETAINING WALLS) Does not Exist
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K065
PB/A&W Print Date: 9/13/2020Page 32 of 32