    Power System

    Protection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent RelayTime Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE Standard

    Equations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Power System Protection

    S.A.Soman

    Department of Electrical EngineeringIIT Bombay

    Fundamentals of Overcurrent Protection

    http://find/
  • 7/31/2019 Oc Relay Seting

    2/34

    Power System

    Protection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent RelayTime Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE Standard

    Equations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    1 Principles of Overcurrent ProtectionLimitations of a Fuse

    Algorithm for Overcurrent Relay

    Time Multiplier Setting

    2 Classification of Overcurrent RelayLack of Coordination Problem

    IEC Standard Equations

    IEEE Standard Equations

    3

    Pick up Current SettingGuidelines

    Primary and Back up Relays

    Setting and Coordination

    4 Summary

    http://find/
  • 7/31/2019 Oc Relay Seting

    3/34

    Power System

    Protection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent RelayTime Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE Standard

    Equations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    1 Principles of Overcurrent ProtectionLimitations of a Fuse

    Algorithm for Overcurrent Relay

    Time Multiplier Setting

    2 Classification of Overcurrent RelayLack of Coordination Problem

    IEC Standard Equations

    IEEE Standard Equations

    3

    Pick up Current SettingGuidelines

    Primary and Back up Relays

    Setting and Coordination

    4 Summary

    http://find/
  • 7/31/2019 Oc Relay Seting

    4/34

    Power System

    Protection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent RelayTime Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE Standard

    Equations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    Limitations of a Fuse

    It is difficult to control the time to trip.This makes primary backup relay coordination difficult.

    Once fuse melts, it has to be replaced for

    reenergization of the equipment.

    Thus it is difficult to have remote operation.

    http://find/
  • 7/31/2019 Oc Relay Seting

    5/34

    Power System

    Protection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent RelayTime Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE Standard

    Equations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    1 Principles of Overcurrent ProtectionLimitations of a Fuse

    Algorithm for Overcurrent Relay

    Time Multiplier Setting

    2 Classification of Overcurrent RelayLack of Coordination Problem

    IEC Standard Equations

    IEEE Standard Equations

    3

    Pick up Current SettingGuidelines

    Primary and Back up Relays

    Setting and Coordination

    4 Summary

    http://find/http://goback/
  • 7/31/2019 Oc Relay Seting

    6/34

    Power System

    Protection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent RelayTime Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE Standard

    Equations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    Algorithm for Overcurrent Relay

    Set reference or threshold for discriminating

    overcurrent Iref.Measure device current I.

    Compute the ratio abs( IIref) which is known as the Plug

    Setting Multiplier.

    Trip the device, if PSM is above the threshold. Thethreshold is always greater than 1.

    http://find/http://goback/
  • 7/31/2019 Oc Relay Seting

    7/34

    Power System

    Protection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent RelayTime Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE Standard

    Equations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    http://find/http://goback/
  • 7/31/2019 Oc Relay Seting

    8/34

    Power System

    Protection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent RelayTime Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE Standard

    Equations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    1 Principles of Overcurrent ProtectionLimitations of a Fuse

    Algorithm for Overcurrent Relay

    Time Multiplier Setting

    2 Classification of Overcurrent RelayLack of Coordination Problem

    IEC Standard Equations

    IEEE Standard Equations

    3 Pick up Current Setting

    Guidelines

    Primary and Back up Relays

    Setting and Coordination

    4 Summary

    http://find/
  • 7/31/2019 Oc Relay Seting

    9/34

    Power System

    Protection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent RelayTime Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE Standard

    Equations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    Time Multiplier Setting

    Overcurrent relays normally play the dual roles of

    primary and backup protection.

    Backup action requires a wait state.By providing the additional setting feature of TMS, this

    can be achieved.

    TMS is defined as the ratio TTm

    , where T is the desired

    relay operating time for a given PSM and Tm is the

    corresponding operating time at TMS=1.

    Relay operating time can be varied by varying the TMS

    setting.

    http://find/http://goback/
  • 7/31/2019 Oc Relay Seting

    10/34

    Power System

    Protection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE Standard

    Equations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    http://find/
  • 7/31/2019 Oc Relay Seting

    11/34

    Power System

    Protection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE Standard

    Equations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    Classification of Overcurrent Relay

    Instantaneous relay

    Its action is very fast.It has only pick up setting.It does not have any TMS setting.This relay is not suitable for backup protection.

    http://find/
  • 7/31/2019 Oc Relay Seting

    12/34

    Power System

    Protection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE Standard

    Equations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    Classification of Overcurrent Relay

    Instantaneous relay

    Its action is very fast.It has only pick up setting.It does not have any TMS setting.This relay is not suitable for backup protection.

    Time delayed definite time relay

    It can be adjusted to issue trip decision after a specified

    delay.This delay is independant of PSM value.It has both time setting and pick up setting.It is used for short length feeders.

    http://find/
  • 7/31/2019 Oc Relay Seting

    13/34

    Power System

    ProtectionS.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE Standard

    Equations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    Overcurrent Protection Using Definite Time Relay

    R1 trips without any intentional time delay.

    R2 has to coordinate with R1 and its operation is

    delayed by CTI.

    R3 has to back up R2 and it is again time delayed.

    http://find/
  • 7/31/2019 Oc Relay Seting

    14/34

    Power System

    ProtectionS.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE Standard

    Equations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    1 Principles of Overcurrent ProtectionLimitations of a Fuse

    Algorithm for Overcurrent Relay

    Time Multiplier Setting

    2 Classification of Overcurrent RelayLack of Coordination Problem

    IEC Standard Equations

    IEEE Standard Equations

    3 Pick up Current Setting

    Guidelines

    Primary and Back up Relays

    Setting and Coordination

    4 Summary

    http://find/
  • 7/31/2019 Oc Relay Seting

    15/34

    Power System

    ProtectionS.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE Standard

    Equations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    Lack of Coordination Between Fuse and DT relay

    DT relay R1 has to back

    up fuse.

    After point X relay acts

    faster than fuse.

    This lack of coordination

    is due to different

    characteristics of fuse

    and relay.This lead to the

    development of inverse

    characteristics for

    overcurrent relay.

    http://find/
  • 7/31/2019 Oc Relay Seting

    16/34

    Power System

    ProtectionS.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE Standard

    Equations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    Classification of Overcurrent Relay

    Inverse definite minimum time relayIt is inverse in the initial part and tends to approach adefinite minimum operating time characteristics as thecurrent becomes high.This is the most widely used characteristics.

    http://find/
  • 7/31/2019 Oc Relay Seting

    17/34

    Power System

    ProtectionS.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE Standard

    Equations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    1 Principles of Overcurrent ProtectionLimitations of a Fuse

    Algorithm for Overcurrent Relay

    Time Multiplier Setting

    2

    Classification of Overcurrent RelayLack of Coordination Problem

    IEC Standard Equations

    IEEE Standard Equations

    3 Pick up Current Setting

    Guidelines

    Primary and Back up Relays

    Setting and Coordination

    4 Summary

    http://find/http://goback/
  • 7/31/2019 Oc Relay Seting

    18/34

    Power System

    ProtectionS.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE StandardEquations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    IEC Standard Equations for Inverse Characteristics

    Standard Inverse Characteristics

    t = TMS0.14

    (I/Is)0.02 1

    Very Inverse Characteristics

    t = TMS13.5

    (I/Is) 1

    Extremely Inverse Characteristics

    t = TMS80

    (I/Is)2 1

    http://find/
  • 7/31/2019 Oc Relay Seting

    19/34

    Power SystemProtection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE StandardEquations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    1 Principles of Overcurrent ProtectionLimitations of a Fuse

    Algorithm for Overcurrent Relay

    Time Multiplier Setting

    2

    Classification of Overcurrent RelayLack of Coordination Problem

    IEC Standard Equations

    IEEE Standard Equations

    3 Pick up Current Setting

    Guidelines

    Primary and Back up Relays

    Setting and Coordination

    4 Summary

    http://find/
  • 7/31/2019 Oc Relay Seting

    20/34

    Power SystemProtection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE StandardEquations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    IEEE Stanard Equations for Inverse Characteristics

    Moderately inverse: t= TD7

    0.0515

    (I/Is)0.021

    + 0.114

    Very inverse: t=TD

    7

    19.61(I/Is)21+ 0.491

    Extremely Inverse: t= TD7

    28.2

    (I/Is)21

    + 0.1217

    US CO8 Inverse: t=TD

    7 5.95

    (I/Is)2

    1+ 0.18

    US CO2 Inverse: t= TD7

    0.02394

    (I/Is)0.021

    + 0.01694

    http://find/
  • 7/31/2019 Oc Relay Seting

    21/34

    Power SystemProtection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE StandardEquations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    IEEE Standard Curves

    http://find/
  • 7/31/2019 Oc Relay Seting

    22/34

    Power SystemProtection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE StandardEquations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    1 Principles of Overcurrent ProtectionLimitations of a Fuse

    Algorithm for Overcurrent Relay

    Time Multiplier Setting

    2

    Classification of Overcurrent RelayLack of Coordination Problem

    IEC Standard Equations

    IEEE Standard Equations

    3 Pick up Current Setting

    Guidelines

    Primary and Back up Relays

    Setting and Coordination

    4 Summary

    http://find/
  • 7/31/2019 Oc Relay Seting

    23/34

    Power SystemProtection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE StandardEquations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    Faults are classified into two:

    Phase fault which do not involve ground.

    Earth fault which involve ground.

    http://find/
  • 7/31/2019 Oc Relay Seting

    24/34

    Power SystemProtection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE StandardEquations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Guidelines for Setting Pickup Current for Phase Fault

    Relays

    Pickup current should be above the maximum load

    current.Pickup current should be below minimum fault current.

    Pickup current should also be below the minimum fault

    current of the feeder that it has to back up.

    The back up relay also should provide time for primaryrelay to operate. This time interval is known as

    coordination time interval.

    F d l f O P i

    http://find/
  • 7/31/2019 Oc Relay Seting

    25/34

    Power SystemProtection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE StandardEquations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    1 Principles of Overcurrent ProtectionLimitations of a Fuse

    Algorithm for Overcurrent Relay

    Time Multiplier Setting

    2

    Classification of Overcurrent RelayLack of Coordination Problem

    IEC Standard Equations

    IEEE Standard Equations

    3 Pick up Current Setting

    Guidelines

    Primary and Back up Relays

    Setting and Coordination

    4 Summary

    http://find/
  • 7/31/2019 Oc Relay Seting

    26/34

    Power SystemProtection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE StandardEquations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Algorithm for Identifying Primary and Backup Relays

    Identify leaf nodes and

    root nodes.

    Find the parents of theactive child nodes.

    The corresponding

    relays should back up

    the leaf node relays.

    Update active child

    nodes to corresponding

    parent node.

    F d t l f O t P t ti

    http://find/
  • 7/31/2019 Oc Relay Seting

    27/34

    Power SystemProtection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE StandardEquations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    F d t l f O t P t ti

    http://find/
  • 7/31/2019 Oc Relay Seting

    28/34

    Power SystemProtection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE StandardEquations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    Fundamentals of Overcurrent Protection

    http://find/
  • 7/31/2019 Oc Relay Seting

    29/34

    Power SystemProtection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time Multiplier

    Setting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE StandardEquations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    Fundamentals of Overcurrent Protection

    http://find/http://goback/
  • 7/31/2019 Oc Relay Seting

    30/34

    Power SystemProtection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time MultiplierSetting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE StandardEquations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    http://find/
  • 7/31/2019 Oc Relay Seting

    31/34

    Fundamentals of Overcurrent Protection

  • 7/31/2019 Oc Relay Seting

    32/34

    Power SystemProtection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time MultiplierSetting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE StandardEquations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    1 Principles of Overcurrent ProtectionLimitations of a Fuse

    Algorithm for Overcurrent Relay

    Time Multiplier Setting

    2 Classification of Overcurrent Relay

    Lack of Coordination Problem

    IEC Standard Equations

    IEEE Standard Equations

    3 Pick up Current Setting

    GuidelinesPrimary and Back up Relays

    Setting and Coordination

    4 Summary

    Fundamentals of Overcurrent Protection

    http://find/
  • 7/31/2019 Oc Relay Seting

    33/34

    Power SystemProtection

    S.A.Soman

    Principles ofOvercurrentProtection

    Limitations of a Fuse

    Algorithm for

    Overcurrent Relay

    Time MultiplierSetting

    Classificationof OvercurrentRelay

    Lack of Coordination

    Problem

    IEC Standard

    Equations

    IEEE StandardEquations

    Pick upCurrentSetting

    Guidelines

    Primary and Back up

    Relays

    Setting and

    Coordination

    Summary

    Fundamentals of Overcurrent Protection

    Algorithm for Setting and Coordination of Overcurrent

    Relays in a Radial System

    Initialize the coordination tree.

    Are there any leaf nodes except the root? If yes, go to

    step 3, else go to step 7.

    Identify the leaf node in coordination tree.

    If the PSM of these relays are not set so far, set their

    PSM.

    Identify the parents of leaf nodes in step 3. Compute

    their PSM and TMS for backup protection andcoordination.

    Delete the leaf nodes. Update the coordination tree and

    go back to step 2.

    Coordination activity is complete.