Okonite Ampacity Tables: Single Conductor Electrical Cable Underground Direct Burial
http://www.okonite.com/engineering/single-conductor-underground-direct.html[20-04-2015 14:09:17]
Ampacity Tables Single Conductor Underground Direct Burial
Engineering Technical CenterOkonite Home PageContact Okonite
.
Single conductor cable direct burial1/C group buried 36 deep with cables laid on 7-1/2 centers, open circuited shield operation, i.e. shields bonded and grounded at one point only.Earth ambient temperature 20C Earth thermal resistivity RHO 90 100% load factor
One circuit three cables
one conductor Copper - direct burial one conductor Aluminum - direct burial
Conductor Size AWG-kcmil
Non-Shielded Shielded
600-2000 Volts Ampacity
2001-5000 Volts Ampacity
5001-35000 Volts Ampacity
90 C (194F)
90 C (194F)
105C (221F)
90 C (194F)
105C (221F)
8.........
6.........
4.........
2.........
1.........
1/0.........
2/0.........
3/0.........
4/0.........
250.........
350.........
500.........
750.........
1000.........
1250.........
1500.........
1750.........
2000.........
108.........
139.........
180.........
231.........
261.........
297.........
337.........
384.........
434.........
472.........
569.........
690.........
847.........
980.........
1083.........
1176.........
1257.........
1325.........
110...
140...
180...
230...
260...
295...
335...
385...
435...
470...
570...
690...
845...
980...
1085...
1175...
1255...
1325...
.115...
150...
195...
250...
280...
320...
365...
415...
465...
510...
615...
745...
910...
1055...
1165...
1265...
1355...
1430...
...
130...
170...
210...
240...
275...
310...
355...
405...
440...
535...
650...
805...
930...
1035...
1125...
1200...
1265...
...
140...
180...
225...
260...
295...
335...
380...
435...
475...
575...
700...
865...
1005...
1115...
1210...
1295...
1365...
Non-Shielded Shielded
600-2000 Volts Ampacity
2001-5000 Volts Ampacity
5001-35000 Volts Ampacity
90 C (194F)
90 C (194F)
105C (221F)
90 C (194F)
105C (221F)
84.........
108.........
140.........
180.........
203.........
231.........
263.........
299.........
338.........
368.........
444.........
540.........
667.........
778.........
868.........
952.........
1027.........
1094.........
85...
110...
140...
180...
205...
230...
265...
300...
340...
370...
445...
540...
665...
780...
870...
950...
1025...
1095...
90...
115...
150...
195...
220...
250...
285...
320...
365...
395...
480...
580...
720...
840...
935...
1025...
1105...
1180...
.......
110...
130...
165...
185...
215...
245...
275...
315...
345...
415...
510...
635...
740...
830...
910...
980...
1045...
...
110...
140...
175...
200...
230...
260...
295...
340...
370...
450...
545...
680...
795...
895...
980...
1060...
1130...
Single conductor cable direct burial
Home About us Products What's New Glossary Brochures Events
Contact Us
http://www.okonite.com/Product_Catalog/index.htmlhttp://www.okonite.com/engineering/ask-the-experts.htmlhttp://www.okonite.com/engineering/index.htmlhttp://www.okonite.com/engineering/index.htmlhttp://www.okonite.com/index.htmlhttp://www.okonite.com/Sales_Offices/index.htmlhttp://okonite.com/index.htmlhttp://okonite.com/index.htmlhttp://okonite.com/welcome.htmlhttp://okonite.com/welcome.htmlhttp://okonite.com/overview.htmlhttp://okonite.com/overview.htmlhttp://okonite.com/whatsnew.htmlhttp://okonite.com/whatsnew.htmlhttp://okonite.com/glossary.htmlhttp://okonite.com/glossary.htmlhttp://okonite.com/new-brochures.htmhttp://okonite.com/new-brochures.htmhttp://okonite.com/events.htmlhttp://okonite.com/events.htmlhttp://okonite.com/Sales_Offices/index.htmlhttp://okonite.com/Sales_Offices/index.htmlhttp://okonite.com/index.htmlhttp://okonite.com/index.html -
Okonite Ampacity Tables: Single Conductor Electrical Cable Underground Direct Burial
http://www.okonite.com/engineering/single-conductor-underground-direct.html[20-04-2015 14:09:17]
1/C group buried 36 deep with cables laid on 7-1/2 centers, second circuit similarly spaced. Groups separated 24", open circuited shield operation, i.e. shields bonded and grounded at one point only.Earth ambient temperature 20C Earth thermal resistivity RHO 90 100% load factor
Two circuits six cables
one conductor Copper - direct burial one conductor Aluminum - direct burial
Conductor Size AWG-kcmil
Non-Shielded Shielded
600-2000 Volts Ampacity
2001-5000 Volts Ampacity
5001-35000 Volts Ampacity
90 C (194F)
90 C (194F)
105C (221F)
90 C (194F)
105C (221F)
8.........
6.........
4.........
2.........
1.........
1/0.........
2/0.........
3/0.........
4/0.........
250.........
350.........
500.........
750.........
1000.........
1250.........
1500.........
1750.........
2000.........
101.........
130.........
167.........
214.........
241.........
275.........
311.........
354.........
399.........
435.........
522.........
631.........
773.........
892.........
985.........
1068.........
1140.........
1200.........
100...
130...
165...
215...
240...
275...
310...
355...
400...
435...
520...
630...
775...
890...
985...
1070...
1140...
1200...
.110...
140...
180...
230...
260...
295...
335...
380...
430...
470...
560...
680...
835...
960...
1060...
1150...
1230...
1295...
...
120...
160...
195...
225...
255...
290...
330...
375...
410...
495...
600...
740...
855...
945...
1025...
1095...
1150...
...
130...
170...
210...
240...
275...
315...
355...
405...
440...
530...
645...
795...
920...
1020...
1105...
1180...
1240...
Non-Shielded Shielded
600-2000 Volts Ampacity
2001-5000 Volts Ampacity
5001-35000 Volts Ampacity
90 C (194F)
90 C (194F)
105C (221F)
90 C (194F)
105C (221F)
79.........
101.........
130.........
167.........
188.........
214.........
243.........
276.........
311.........
339.........
408.........
494.........
609.........
708.........
790.........
865.........
932.........
991.........
80...
100...
130...
165...
190...
215...
245...
275...
310...
340...
410...
495...
610...
710...
790...
865...
930...
990...
85...
110...
140...
180...
200...
230...
260...
295...
335...
365...
440...
530...
655...
765...
851...
930...
1005...
1070...
...
95...
125...
155...
175...
200...
225...
255...
290...
320...
385...
470...
580...
680...
760...
830...
895...
950...
...
100...
130...
165...
190...
215...
245...
275...
315...
345...
415...
505...
625...
730...
820...
895...
965...
1025...
ENGINEERING TECHNICAL CENTER
Daily Metal Prices
Sustainability
Career Opportunities Quality Assurance Program
Every effort has been made to ensure the accuracy of this presentation.
However, information is subject to change. Not responsible for typographical errors.
1998 - 2015 Copyright The Okonite Company. All Rights
Reserved.
Send feedback regarding this Website to [email protected]. WELCOME | WHAT'S NEW | PRODUCT CATALOG | SALES OFFICES | EVENTS | MANUFACTURING PLANTS | SERVICE CENTERS | GLOSSARY | CAREER OPPORTUNITIES |
SEARCH OKONITE | ENGINEERING TECHNICAL CENTER | EMPTY STEEL RETURN INSTRUCTIONS
http://www.okonite.com/engineering/index.htmlhttp://okonite.com/adv/metal_prices/index.htmlhttp://okonite.com/adv/metal_prices/index.htmlhttp://okonite.com/sustainability.htmlhttp://okonite.com/sustainability.htmlhttp://okonite.com/careers/index.htmlhttp://okonite.com/careers/index.htmlhttp://okonite.com/qualityassurance.htmlhttp://okonite.com/qualityassurance.htmlhttp://okonite.com/qualityassurance.htmlhttp://okonite.com/qualityassurance.htmlmailto:[email protected]://okonite.com/welcome.htmlhttp://okonite.com/whatsnew.htmlhttp://okonite.com/Product_Catalog/index.htmlhttp://okonite.com/Sales_Offices/index.htmlhttp://okonite.com/Sales_Offices/index.htmlhttp://okonite.com/events.htmlhttp://okonite.com/plants.htmlhttp://okonite.com/centers.htmlhttp://okonite.com/glossary.htmlhttp://okonite.com/careers/index.htmlhttp://okonite.com/search.htmlhttp://okonite.com/engineering/index.htmlhttp://www.okonite.com/emptyreelreturns/index.html -
Okonite Ampacity Tables: Single Conductor Electrical Cable Underground Direct Burial
http://www.okonite.com/engineering/single-conductor-underground-direct.html[20-04-2015 14:09:17]
The Okonite Company
102 Hilltop Road
Ramsey, New Jersey 07446
Phone 201-825-0300
Fax 201-825-3524
mailto:[email protected] Ampacity Tables: Single Conductor Electrical Cable Underground Direct BurialVyZ3JvdW5kLWRpcmVjdC5odG1sAA==: form1: sp-q: input2: