operating, installation and maintenance manual for ct … · eco calorifier, its installation,...
TRANSCRIPT
By Appointment toHer Majesty the Queen
Boiler Manufacturers & EngineersHoval Ltd Newark
Date: March 2018
Ref: 4214941-02
Operating, Installation and Maintenance Manual for CT-plus eco Calorifiers
2 Table of Contents
3
4
5-6
7-8
9-13
14
15
16
17
18
19
20
21
Introduction
Description of CT-plus eco Calorifier
Technical and Performance Details CT-plus eco Calorifier
Installation and Piping Layouts
Unvented Systems
Commissioning & Operation
Inspection and Maintenance
Immersion heaters
Immersion heater wiring diagram
Fault Finding Chart
Wiring Diagrams for Open Vented Calorifiers
Wiring Diagrams for Unvented Calorifiers
Notes
egaPstnetnoC
These instructuctions should be read and understood before attempting to install,commission or operate this unit.
Material in this publication may not be reproduced without Hoval’s written permission.
Hoval reserve the right to change specifications without notice.
4214941-02March 2018
3Introduction
The installation should be in accordance withcurrent I.E.E. regulations, relevant British Stan-dard and Codes of Practice, Building Regula-tions and Local Authority Bylaws.
Commissioning should be arranged via theheating engineer. Hoval engineers are availableto carry out this work if requested. Where thecalorifier installation is part of a Hoval boilerpackage it will normally be commissioned atthe same time and entry made on the reportopposite.
Commissioning/Combustion Report
A note should be entered below by the person responsible for the plant, giving the boiler, calorifiermodel and its output and serial number, as indicated on the nameplate.
Calorifier Model:
Boiler type / Model:
Date of installation:
Output l/hr:
Serial Number:
4214941-02March 2018
Introduction
These instructions have been written to give a brief description of the CT-plus eco Calorifier, its installation, commissioning, operation and subsequent maintenance.
The installation of calorifiers and their ancillary equipment is normally carried out by an heating engineer. For the purpose of this manual he is regarded as the installer, and, as such, it is his responsibility to ensure that he has read and understood the contents of this manual before installing the calorifier.
It is essential that each calorifier has all services permanently connected to it before commis-sioning is requested.
For completion by Plantroom Attendant
For technical, servicing or parts enquiries, telephone, fax or email to Hoval Ltd quoting the calorifier(s)
serial number, as above.
4 Description of CT-plus Calorifier
• Suitable for use with any make of boiler• High efficiency heat transfer for rapid
D.H.W. regeneration.• Recirculation design removes danger of
temperature stratification.• Optimum D.H.W. storage - sufficient for quick
draw-off but with lower standing losses thanconventional large volume calorifiers.
• Low level connection for complete draining and flushing out. (CIBSE TM 13:2000 Recommendations to prevent Legionella Bacteria Contamination).
• Very low primary and secondary resistances.
• An electric immersion heater can be fitted by prior arrangement (three phase supply only).
• Large heating surface, suitable for operation with lower temperature primary feed from condensing boilers.
• See page 10 for unvented systems and the additional equipment required.
Internal view of CT-plus eco Calorifier
1. Primary Inlet2. Primary Outlet3. Cold feed4. Secondary Flow5. Secondary Return6. Drain7. Primary air release
cock8. High efficiency
insulation
9. Non-corrosive stainlesssteel cylinder
10. Special “ripple” innershell to enhanceheat transfer
11. Primary watersurrounds DHWcylinder
12. Thermostat(s)13. Inspection and cleaning
cover or plugged 2.1/4”inspection socket
(CT-plus eco 280-520)
7 4 1213
1
2
8
10
3
9
6 5
11
T&P valve on unvented calori ers only
4214941-02March 2018
Description of CT-plus Calorifier
ApplicationsCT-plus eco calorifiers are designed to operate with the full range of Hoval boilers up to 3.10 Bar pri-mary pressure, and are intended for the produc-tion and supply of DHW to commercial and indus-trial premises.The CT-plus eco is available in four model sizes with high performance outputs up to 1590 litres per hour.An ErP energy rating applies to models CT-plus eco 180, 280 & 420 (see page 5).General DetailsThe construction of the CT-plus eco is in the form of a vertical, free standing unit, comprising a high grade stainless steel inner vessel with a “rippled” wall to enhance heat exchanger efficiency. This is sur-rounded by a mild steel primary water jacket, which is encased with a 120mm thick insulated jacket. The assembly is mounted on four legs with the primary flow and return connections on the side. On all four models, the secondary flow is from the top and the smallest model (CT-plus eco 180) also has the secondary return and cold feed connections at the top. For the three larger models, all the con-nections other than secondary flow are at the base.
Performance of the four CT-plus eco models covers a range of outputs up to an hourly rating of 1590 litres/hour. Higher outputs can be provided by ar-ranging the units in modular formation. For most typical applications (other than process water generation) the key requirement is for adequate quantities of hot water over a relatively short period. On this basis, the CT-plus eco will provide significantly higher flow rates than its continuous hourly rate.
Key Features
5
Dimensions
Model A B C D E F G Inlet2 3 4 7
Lifting
1807
1904
1904
2300
753
853
943
943
346
346
346
346
1030
1280
1280
1676
138
85
85
85
165
120
120
120
90
85
85
85
1 1” 1” ” 1” ” 1 ” 1/ ”
1.1/4” 1.1/4”1.1/2”
1.1/2”
1.1/2”
1.1/2”
1.1/2”
1.1/2”
1.1/2”
1.1/2”
1.1/2”
1.1/2”
1.1/2”
1.1/2”
1.1/2”
1”
1”
1”
***
Position of electrical connectionsto thermostat. 240v 1 phase 50Hz * 2 No. lifting lugs provided on top plate.
Connection 9 - Primary air release cock.
Primary SecondaryConnections - BSP Male
CT plus eco 180
CT plus eco 280
CT plus eco 420
CT plus eco 520
Water Content WeightPrimary
litresSecondary
litresDrykg
Wetkg
61 180 177 418
94 280 211 585
114 420 248 782
135 520 302 957
Working Pressures.System. Max Working Pressure. Test Pressure.Primary 3.10 bar 5.18 bar
Working Temperatures.System. Normal Temp. Max Temp.
Primary 82 C 90 Co
oo
o
Secondary 6.00 bar 9.00 bar
Secondary 60 C 70 C
ModelCT plus eco 180
CT plus eco 280
CT plus eco 420
CT plus eco 520
Both sides flooded.
Technical and Performance Details
C
C
C
ErP energy rating classification.
Technical and Performance Details CT-plus eco Calorifier
8 91 5 6Outlet Cold feed Flow Return Drain T&P Valve Air release
1.1/4”
1.1/2”
1.1/2”
1/ ”
1/ ”
1/ ”
2
34
5
6
7
1
2
CT plus eco 180 CT plus eco 280-520
PLAN VIEW PLAN VIEW
4 35
7
9
T&P valve connectionfor unvented calorifiers(optional)
T&P valve connectionfor unvented calorifiers(optional)
Fit an anti-thermal loop to cold feed.
Pipe sizes can be expanded to suit site requirements if necessary on leaving the calorifier.
March 2018 4214941-02
EF
EFFE
93mm 93mm
* *
6 Outputs Based on 10oC Cold Feed, 82oC Primary Flow and 60oC Secondary Flow.
Model at dif
Hydraulic Resistanceat dif
Primary SecondaryFlow rate l/s Resistance mbar Flow rate l/s Resistance mbar
CT plus eco 180
CT plus eco 420
CT plus eco 280
CT plus eco 520
litres/secondContinuous hourly
draw off litres10 mins draw off
litres 0.751.121.50
180
1.502.50
7201000 280
1.502.002.78
96012501365
420
520550590
1.502.002.78
103713371590
520
0.751.121.50
1.502.50
1.502.002.781.502.002.78
3578
140
1550
152363132363
0.751.121.50
1.502.00
1.502.002.501.502.002.50
3067
120
1832
2645704071111
*
f .
f
Rating kW = Q x S.H. x (T2 - T1 )
Q = T1 = T C T2 = T C
= C
To calculate the load on the boiler for y.
Note for Hydraulic Testing: The primary jacket should not be pressurised without
steel vessel.
An adjustable secondary thermostat has a sensing point which ensures that the main body of water is held uniformly,
set level, normally 60oC - 65oC.
DHW Output
*Primary and Secondary Hydraulic Resistance.
3600
Model
CT plus eco 180
CT plus eco 420
CT plus eco 280
CT plus eco 520
Legionellae r
er r er shown above
Technical and Performance Details
When temporarily operating the primary side only, the pressure should not exceed 1 bar g and the secondary side should be vented.
Chloride!
!!
!!
March 8 2
7
A B
1
AAV 2
3
4
5
3
36
Primary Connections from Main Headers. Temperature control by pump.
Primary Water
Secondary Water
Anti-thermal loop
1
AAV 5
4 (if Required)
36
Primary Connections from Main Headers. Temperature control by diverting valve.
3
7
Primary Water
SecondaryWater
Installation and Piping Layouts
InstallationPosition the calori ers as required, ensuring that side and inspection opening clearances are adequate. Fit unions to all pipe connections ensuring that joint seals are Fit isolating valves to all pipework.
Installation and Piping Layouts
Note: The CT-plus calor er is with a separate DHW drain
tapping. The primary drain must be tted off the primary outlet connection in the site pipework.
Piping layoutFor the general design of water circuits refer to current British Standards and Codes of Practice. A simple pumped primary and return, ad-equately vented, is all that is needed. Secondary
To facilitate venting during drain down on unvented secondary systems, ensure that a manual vent valve is in the second-ary w between the calori er and the isolating valve. On open vented systems the vent should be taken from the same place.
Recommended Primary Systems (Open vented DHW system)
Key(1) Safety Valve recommended if noton adjacent boiler or system.(2) Spring loaded non-return valve.(3) Isolating valves.(4) Primary pump (For diagram “B”the main circulating pump may be
(5) Thermostat (linked to primarypump to control calori er DHWtemperature, for Diagram A).Fordiagram B the thermostat controlsthe diverting valve.(6) Drain cock.(7) Diverting valve (use 30 secondmotor).
Note:On Unvented systems there is a high temperature limit thermostat tted. The installer should wire this back to the control valve / primary pump and also a 2 port motorized valve. This should be on the primary inlet, to stop the w of primary water entering the calori er in the event of a high temperature condition.
connections are quite conventional. Connect the calori er(s) to the rest of the system according to the chosen layout. Examples of both primary and secondary systems are shown below:
! !
March 2018 4214941-02
8 Installation and Piping Layouts
C D
1
AAV
2
3
4
5
3
3 6
Primary Connections direct from boiler. Temperature control by pump.
Primary Water
Secondary Water
Flow
Return
Boiler
Anti-thermal loop
3
1
AAV 5
4 (if Required)
6
Primary Connections direct from boiler. Temperature control by diverting valve.
3
7
Primary Water
SecondaryWater
Return
3
Flow
Boiler
3
3
Boiler
Recommended Primary Systems Continued
Key(1) Safety Valve recommended if noton adjacent boiler or system.(2) Spring loaded non-return valve.(3) Isolating valves.(4) Primary pump (For diagram “D”the main circulating pump may be
(5) Thermostat (linked to primarypump to control calori er DHWtemperature, diagram C). Fordiagram D the thermostat controlsthe diverting valve.(6) Drain cock(7) Diverting valve (use 30 secondmotor).
Recommended Secondary Systems
Key(1) Relief valve adjacent to calori er.(2) Spring loaded non-return valve. Note: On CT-plus eco 180 the
secondary return and cold feed connections are at the top. The cold feed should be taken to a low level thermal syphon to avoid thermal circulation up the cold feed.
(3) Isolating valves.(4) Open vent.(5) Unvented system kit.(6) Secondary drain valve.
AAV
Secondary Connections OPEN VENTED.
Primary Water
SecondaryWater
1
2 3 3
3 3 6
Vent
Cold Feed
Secondary Return
31
4Manual Vent Valve
T & P Relief Valve
Secondary Connections UNVENTED.
Primary Water
SecondaryWater
2 3 33 36
Cold Feed
Secondary Return
3
5
35
2
Note:On Unvented systems there is a high temperature limit thermostat tted. The installer should wire this back to the control valve / primary pump and also a 2 port motorized valve. This should be on the primary inlet, to stop the w of primary water entering the calori er in the event of a high temperature condition.
March 2018 4214941-02
9Unvented Systems
An unvented hot water system differs from conventionalopen vented systems in that no vent pipe is providedand it is connected to the mains water supply, eliminatingthe need for the provision of cold water storage tanks inthe roof space. The functions, therefore, of the openvents and cold feeds have to be performed in otherways. There are two basic types of unvented system:(1) Direct off the mains,(2) Boosted water supply.
Direct off the mainsWhere mains pressure is sufficient the system can be connected straight off the mains. However, between the cold water supply and the DHW generator (i.e. the CT-plus eco calorifier) there must be an unvented system kit fitted.
Warning: Some pressure boostersets have an accumulator (expan-sion vessel). This is to reduce theamount of pump starts and shouldnot be confused with the systemexpansion vessel.
This kit should contain a minimum of the followingitems:-• An expansion vessel should be fitted between the
non-return valve and the calorifier to take up expandedwater during heat-up.
• An expansion relief valve should be fitted in the coldfeed between the expansion vessel and the calorifier.No means of isolating the calorifier from this valveshould be installed.
• A temperature and pressure relief valve should befitted directly in the calorifier as a thermal protectionto prevent the DHW reaching 100 deg C.
• A hand reset limit stat should be fitted in the calorifierto prevent the DHW overheating.
Balanced Unvented SystemsSome systems may be fitted with blending valves ormixers that require a balanced hot and cold watersupply. When sizing the strainer, the PRV, and checkvalve care must be taken to ensure they can pass theflow rates at the required pressure.Hovals’ standard unvented system kits are sized toreduced incoming pressure to 3 bar at a flow rate thatmeets the peak output of the calorifier only.
As shown in the above diagram, an unvented system kitcomprises of the following components:-• Strainer (this is optional, but good practice, to prevent
debris passing through the valves)• Pressure regulating valve (PRV), this allows the
pressure to be reduced and controlled at a presetpressure. A pressure gauge is supplied to indicatesystem pressure.
• Double non return valve, this prevents the expandedwater back-feeding into the mains supply andsubsequently seals the system.
• An expansion vessel should be fitted between the nonreturn valve and the calorifier to take up expandedwater during heat-up.
• An expansion relief valve should be fitted in the coldfeed between the expansion vessel and the calorifier.No means of isolating the calorifier from this valveshould be installed.
• A temperature and pressure relief valve should befitted directly in the calorifier as a thermal protectionto prevent the DHW reaching 100 deg C.
• A hand reset limit stat should be fitted in the calorifierto prevent the DHW overheating.
Boosted water supplyWhere mains water pressure is insufficient a coldwater booster set can be fitted. Normally these setshave integral pressure controls, in the form of eitherpressure transducers, pressure switches, and orpressure regulating valves. They also have a non returnvalve which prevents back-feeding. Systems where abooster set is installed should not have a vent and assuch are unvented.Boosted systems should have an unvented system kitfitted down-stream from the booster set.
T & P Relief Valve.
Control & hand reset limit stats.
Expansion relief valve c/w tundish.
Expansion Vessel.
Check valve.
PRV.
Strainer.
Unvented System Kit.
Cold Feed
March 2018 4214941-02
Unvented Systems
10
60 litre ¾” HP60-1”
Strainer P.R.V.
DoubleCheckValve
ExpansionVessel
ExpansionRelief
Valve &Tundish
T & PReliefValve*
T & P Relief Valve.
Control & hand reset limit stats.
Expansion relief valve c/w tundish.
Expansion Vessel.
Check valve.
PRV.
Strainer.
Unvented System Kit.
Cold Feed
60 litre ¾”
CT-plus eco 420 1” 1” 1” 80 litre ¾” 1”
CT-plus eco 520 1” 1” 1” 80 litre ¾” 1”
Warning: On balanced systemswith a common PRV, Strainer andDouble check valve, ensure thatthe valves are sufficiently sizedto cope with both hot and coldwater demand.
A separate Strainer and PRV can be fitted to both the hot and cold water services to give balanced system pressures. Alternatively, a larger Strainer and PRV can be installed to cope with both hot and cold water demands.Cold water booster sets tend to be sized on the total demand of the system and subsequently give a balanced condition.
Hoval Unvented System Kits
Hoval have carefully sized and selected a range of standard unvented system kits suitable for installation with the CT-plus eco range of calorifiers.
The various valves and fittings should be installed in the sequence shown on the right.
The size of the standard unvented kits are shown in the table below.
Please note that these kits are only sized for the cold feed going into one of the CT-plus eco calorifiers.
Using the PRV from a standard Hoval unvented kit to provide a balanced hot and cold water supply may cause pressure and water flow problems. Ensure that the PRV can cope with the demand from both the hot and cold water services.
Unvented Systems
HP80-1”
HP80-1”
1”
1.1/4”
1.1/2”
(Supplied with
*Supplied factory tted with unvented calori er
4214941-02March 2018
(discharge pipe(s) by others - not supplied by Hoval).
CT-plus eco 180 ¾”
CT-plus eco 280 ¾”
¾”
¾” HP60-1”
22mmDC222mmDC2
1.1/2”
Items in the Unvented System Kit
Cal
orifi
er
Mod
el
Kit R
efer
ence
11
Common Unvented System Kit.
Cold Feed
More than one calorifier can be installed off a single common cold feed. Each calorifier must have it’s own T & P valve and expansion relief valve. No means of isolating these safety valves from the calorifier should be installed.
Drain Cock By the Installer
Strainer
Pressure Reducing Valve Double
Check Valve
Expansion Vessel
Expansion Relief Valve and Tundish
Expansion Relief Valve and Tundish
Temperature and Pressure Relief Valve
Temperature and Pressure Relief Valve
Isolating Valve
Isolating Valve
Shared Unvented System Kits Feeding two or more calorifiers.
Cold Feed
Two or more calorifiers can be installed with individual unvented system kits. Where the expansion vessels have been sized to share the total system expansion the two feed lines can be joined by a pipe to allow both vessels to be used when one calorifier is isolated.
Drain Cock By the Installer
Strainer
Pressure Reducing Valve Double
Check Valve
Expansion Vessel
Expansion Relief Valve and Tundish
Expansion Relief Valve and Tundish
Temperature and Pressure Relief Valve
Temperature and Pressure Relief Valve
Isolating Valve
Isolating Valve
Strainer
Pressure Reducing Valve Double
Check Valve
Expansion Vessel
Cold Feed
Drain Cock By the Installer
Joining pipe.
Multi-calorifier Installations
Unvented Systems
Joining pipe
March 2018 4214941-02
12
Balanced hot and cold water services using two PRVs.
Cold Feed
The hot and cold water supplies can be balanced using two separate PRVs.
Drain Cock By the Installer
Strainer
Pressure Reducing Valve
Double Check Valve
Expansion Vessel
Expansion Relief Valve and Tundish
Temperature and Pressure Relief Valve
Isolating Valve
Balanced Cold Water Supply
Balanced Hot and Cold water supplies.
Unvented Systems
Unvented System with balancedhot and cold water services.
Cold Feed
The hot and cold water supplies can be balanced by utilizing the same strainer and PRV to control the two supply lines. Note it may be necessary to increase the size of these two fittings in comparison to the non-return valve in the calorifier cold feed line.
Drain Cock By the Installer
Strainer
Pressure Reducing Valve Double
Check Valve
Expansion Vessel
Expansion Relief Valve and Tundish
Temperature and Pressure Relief Valve
Isolating Valve
Balanced Cold Water Supply
March 2018 4214941-02
13
Fitting the Unvented System Kit.
Fit the components as indicated. In the suggestedschematics detailed on previous pages.
All components must be installed in a frost free area.
Ensure that valves and fittings are fitted correctly tosuit the direction of flow.
Set the Pressure reducing valve (PRV) to 3 bar.
Pipe off expansion relief valve via the tundish providedto a gulley.
Pipe expansion vessel into cold feed. Fit a lock shieldvalve and drain between the vessel and the cold feedline. This will allow the expansion vessel gas charge tobe checked during maintenance. This is shown on theright.
Installation of the Expansion Vessel.
Cold Feed
Fit a lock shield valve and drain to allow the expansion vessel to be isolated and drained for periodic inspection. Drain Cock
(By the Installer)
Strainer
Pressure Reducing Valve Double
Check Valve
Expansion Vessel
Lock Shield Valve (By the Installer)
Maintenance of Unvented System Kit.
Clean out strainer on commissioning and annually.
Check Expansion relief valve setting annually bytwisting the cap on top of the valve.
Check expansion vessel gas charge pressure, isolatethe vessel, drain off any water in the vessel and test thegas pressure using a tyre gauge.
Fault Finding.
Symptom Possible Cause(s) Remedial Action
(A) Reduction in water flow Blockage in strainer Clean out strainer.Blockage in PRV Clean out secondary strainer in PRV.Wrong PRV pressure setting Check PRV pressure setting alter if necessary.
(B)Discharge from expansion Debris on valve seat Twist test knob and replace if necessary. Relief valve. Wrong incoming pressure Adjust the pressure setting on PRV.
Expansion vessel diaphram Check expansion vessel gas charge.Failure.Insufficient Expansion vessel Check expansion vessel size.volume.
Expansion Vessel Sizing.Expansion Vessel Volume = System content (l) x C.o.E.
Vessel Efficiency
Vessel Efficiency = Max Pressure (Bar Abs) - Min Pressure (Bar Abs) Max Pressure (Bar Abs)
Where: Max Pressure is final desired working pressure + 1.Min Pressure is pressure setting on PRV + 1.C.o.E. at 60 Deg C is approx 0.02
Unvented Systems
March 2018 4214941-02
14
Commissioning Instructions
• Flush all swarf, filings and other debris out ofthe system, preferably using a proprietary flush-ing agent. Do not wash particles into the calorifier,this could cause subsequent corrosion.• Once the secondary side is fully flooded andsealed, fill the primary system completely andtreat the water with a good corrosion inhibitor(e.g. Fernox). Corrosion inhibitors are not usedin secondary (tap) water.• Ensure that all joints are water tight and allpipework is vented.• Check that all electrical connections are com-plete and correct.•Ensure that the thermostat(s) are wired up andthe sensor probes are fitted in the stat pocket.The thermostat may be wired into the boiler con-trols to activate the pumps or a motorised valve.The control thermostat can be adjusted to oper-ate between 30 deg C and 80 deg C and is usu-ally set to 60 deg C.
Pre-commissioning:
Important: Always fill the second-ary side of the calorifier beforethe primary. Pressurising the pri-mary when the secondary isempty may cause the secondarybottle to collapse.
Commissioning
(1) Light the boiler (refer to the appropriate boileroperating instructions).(2) Adjust the calorifier thermostat to the requiredoperating temperature.(3) Check that the thermostat is operating cor-rectly.(4) Ensure that the primary pump is working orprimary primary circuit is established.(5) Check that the operating temperature remainsconstant.
Operating Instructions
The calorifier thermostat when wired to the pri-mary circulating pump or diverting valve providescompletely automatic control. It is necessary onlyto adjust the thermostat if the occasion demands.
Warning: To avoid Legionellae, en-sure the calorifier control stat is setat a minimum of 60 deg C.
Commissioning & Operation
March 2018 4214941-02
Commissioning & Operation
15
Periodic Inspection
CleaningThe period between cleaning will depend on op-erating temperature and hardness of water. Lo-cal conditions will serve as a guide. Normally de-scaling will be required less often than with con-ventional calorifiers.
The following procedure should be adopted:
(1) Remove calorifier top casing panel.(2) Remove cleanout cover or inspection socket plugto access the calorifier internals.(3) Scrape the inside surface with a non ferrousscraper.
Note: Chemical cleaning can be carried out if re-quired, but such work should be undertaken in accordance with the instructions of the de-scal-ing compound manufacturer.
After chemically cleaning the DHW calorifer internal, ensure that the unit is thoroughly flushed out with clean water.
Following cleaning, replace cleanout cover us-ing a new gasket to prevent leaks or refit the inspection socket plug and seal accordingly.
Inspection and Maintenance
Draining Down
(1) Ensure that both primary and secondarypumps are switched off.(2) Isolate the primary inlet and outlet.(3) Fit hose to primary drain which should be in-stalled in primary outlet and run the hose toa gulley.
Note: The primary side of thecalorifier MUST always bedrained before the secondary.The secondary MUST always befilled before the primary.
Draining the calorifier downshould be done by following theprocedure below:-
When filling the calorifierfollow the above procedurebut in reverse.
The user is advised to carry out periodic inspec-tion between main servicing periods and it is rec-ommended that the specialist servicing companyalso carries them out.
• Inspect the calorifier casing for obvious signsof damage, corrosion or deterioration.• Inspect the calorifier siting for signs of crack-ing or settling.• Inspect all pipes and connections for obviousdamage or deterioration.• Remove calorifier top panel and examine in-terior for corrosion and deterioration.
(4) Open primary vent valve.(5) Open primary drain.(6) Isolate all secondary connections.(7) Fit hose to the secondary drain which is lo-cated underneath the calorifier and run the hoseto a gulley.(8) (On sealed systems) Open manual second-ary vent valve (this should be fitted in secondaryflow between calorifier and isolating valve).(9) Open secondary drain valve.
Model Joint Cat No.
CT plus 180 414035
CT plus 280-520 414007
4214941-02March 2018
Inspection & Maintenance
Note: For all CT-plus eco calorifiers supplied before November 2017 and new CT-plus eco 180 & 280 calorifiers - before opening the inspection cover always ensure you have a spare inspection cover joint.
16 Immersion Heaters
General• All work should be carried out by suitably qualified
personnel.• Heaters must be handled with care and stored in
dry conditions.• Adequate withdrawal space must be provided to
allow the removal of the heater assembly.• Carefully remove all protective packaging and
visually inspect unit for any transit damage.• All prevailing rules, regulations and bylaws in force
at the time and place of installation must beobserved.
• Heaters must only be immersed in the fluid theyare designed to heat.
• The introduction of alternative fluids even in smallconcentrations for purposes such as sterilisingmay cause serious damage to the heater and willinvalidate the warranty.
• Any modification not carried out by Heatex Limitedor its approved agent will invalidate certificationand warranty.
• Precautions must be taken to prevent damage toenclosure seals.
Installation• The heater should be securely fixed in position and
all terminal connections checked for tightnessbefore energising.
• The installed orientation of horizontally mountedheaters must be such that any thermostats orother temperature sensors are uppermost.
• Sealing gaskets must be undamaged.• The terminal box must not be used for tightening
heater into tank or vessel.
Electrical Supply Connection• Refer to wiring diagram on page 17.• The cable entry or gland plate is positioned on the
side of the terminal box.• Before connection ensure that the supply
corresponds with that specified on the rating label.• Ensure that the sizes and types of cables to be
used are suitably rated for the load and temperatureof the unit.
• Each heater must be protected by a suitably ratedover current device.
• The cables must enter the heater terminal box viaa suitable cable gland to maintain the IP rating andbe fitted by a qualified person.
Earth Connection
Operation• Ensure that the active sections of all the heating
elements are fully immersed in the fluid to beheated at all times whilst energized.
• Heat is transferred by means of electric heatingelements.
• Control of the heater is facilitated bythermostats, thermocouples or RTDs andreference should be made to the wiring diagraminside cover to ensure that these are correctlyconnected and set prior to energising the heater.
• Where a manual reset thermostat or cut-out isinstalled, the terminal box cover will have to beremoved after isolating the heater to enable areset to be carried out.
THESE HEATERS MUST BE EARTHEDAn earth connection is provid-ed inside the terminal box.
Routine Maintenance
Maintenance• All prevailing site safety regulations shall be
adhered to at all times.• Equipment is to be fully isolated from the
electrical supply and locked off before and whilstany work is being carried out.
3 Monthly• Generally inspect the equipment for external
damage or leaks.
6 Monthly• Isolate the electrical supply and remove the
cover.• Ensure the terminal box is clean and dry
internally.• Ensure the electrical terminals are intact and
secure.• Check that the heating element insulation
resistance is at least 2 mega ohms.• Check the continuity of all elements.• Refit cover with new gasket if required.• Ensure that earth continuity is maintained
between all exposed conductive material andmain site structure.
Annually• Carry out all 3 monthly and 6 monthly checks
as above.• Check for element failure or low insulation
resistance.
• If heaters are being left unused for a periodgreater than 3 months, carry out 6 monthlymaintenance before energizing.
March 2018 4214941-02
Immersion heaters
17Immersion heater Electrical Diagram
March 2018 4214941-02
Immersion heater wiring diagram
18 Fault finding
Please carry out checks as per the list below when faults occur. If you cannot rectify the fault,contact Hoval Customer Services or your installer. Telephone number and e-mail addressare shown on the rear cover.
Symptom Possible Cause Action
A. Primary WaterCircuit Inefficient
(1) Leakage in system.
(2) Pump faulty or inoperative.
(3) Boiler faulty or inoperative.
(4) Circuit not properly vented.
(5) Pump not of sufficient duty.
(1) Check pipe connection. Renewif required.
(2) Refer to appropriate pump partdocument.
(3) Refer to appropriate boiler partdocument.
(4) Vent primary system.
(5) Change pump speed or pump.
Symptom Possible Cause Action
A. Secondary watertemperature not assetting on thermostat.
(1) Leakage in system.
(2) Pump faulty or inoperative.
(3) Thermostat faulty.
(4) Electrical fault in control system.
(5) Calorifier scaled up.
(6) Calorifier not large enough for loadimposed.
(7) Low primary temperature.
(8) Diverting valve bypassing.
(1) Check pipe connection. Renewif required.
(2) Refer to appropriate pump partdocument.
(3) Check and replace if required.
(4) Refer to appropriate control sys-tem part document.
(5) Mechanically / chemically de-scale as necessary.
(6) Change calorifier or add calorifi-er / buffer vessel.
(7) Turn up boiler thermostats / in-crease primary flow rate.
(8) Check primary pipe cools whenhot.Water not required.
March 2018 4214941-02
Fault Finding Chart
19Electrical Diagrams
March 2018 4214941-02
Wiring Diagrams for Open Vented Calorifiers
20 Electrical Diagrams
March 2018 4214941-02
Wiring Diagram for Unvented Calorifiers
21Notes
March 2018 4214941-02
Conservation of EnergyProtection of the Environment
Hoval Limited, Northgate, Newark, Notts NG24 1JNTelephone: Service Desk - 01636 593413
Spares Desk - 01636 593412Fax - 01636 673532
e-mail: [email protected] and [email protected] Site: www.hoval.co.uk
March 2018 4214941-02