Original Device Manual Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English 7391068_00_UK 2016-03-02

Upload: others

Post on 01-Aug-2020

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

Original Device Manual

Fail-safe SmartPLC AC4S

with EtherNet/IP interface

AC422S

for ISO 13849 up to PL e

for IEC 62061 up to SIL CL 3

Firmware: 4.0.2

English

7391

068

_00

_U

K

2

016-0

3-0

2

Page 2: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

2

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Contents

Contents

1 Preliminary note 6

1.1 Legal and copyright information ........................................................................................... 7 1.2 Purpose of the document ..................................................................................................... 7 1.3 Symbols and formats used .................................................................................................. 8 1.4 Overview: User documentation for AC4S ............................................................................ 9 1.5 Modification history .............................................................................................................. 9

2 Safety instructions 10

2.1 Required background knowledge ......................................................................................11 2.2 Please note ........................................................................................................................11 2.3 Tampering with the unit ......................................................................................................12 2.4 Start-up behaviour of the controller....................................................................................12

3 System description 13

3.1 Intended use ......................................................................................................................14 3.1.1 Permitted use ............................................................................................................................. 14 3.1.2 Prohibited use ............................................................................................................................ 14

3.2 Information concerning the device .....................................................................................15 3.2.1 Where is what on the AS-i device? ............................................................................................. 16 3.2.2 Operating elements .................................................................................................................... 17 3.2.3 Display elements ........................................................................................................................ 17 3.2.4 Interfaces .................................................................................................................................... 18 3.2.5 Type label ................................................................................................................................... 21 3.2.6 Required accessories ................................................................................................................. 21

3.3 Hardware ............................................................................................................................22 3.3.1 Safety architecture ..................................................................................................................... 23 3.3.2 Operating states of AC422S ....................................................................................................... 29 3.3.3 Monitoring and securing mechanisms ........................................................................................ 30 3.3.4 Error detection and processing ................................................................................................... 31

3.4 Software .............................................................................................................................33 3.4.1 Software modules of the device ................................................................................................. 34 3.4.2 Safety functions .......................................................................................................................... 34 3.4.3 Certified software components for safe applications .................................................................. 34

4 Installation 35

4.1 Installation ..........................................................................................................................36 4.2 Electrical connection ..........................................................................................................36

4.2.1 Device supply ............................................................................................................................. 37 4.3 Connect devices to local I/O interface ...............................................................................38

4.3.1 Safety instructions ...................................................................................................................... 39 4.3.2 Supported connection types ....................................................................................................... 40 4.3.3 Supported device types .............................................................................................................. 41 4.3.4 Install safe device to local I/O interface ...................................................................................... 52 4.3.5 Install standard device on local I/O interface. ............................................................................. 52

5 Operation 53

5.1 Control of the graphical user interface ...............................................................................54 5.1.1 Function keys ............................................................................................................................. 55 5.1.2 Arrow keys .................................................................................................................................. 55

Page 3: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

3

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Contents

5.2 Menu view ..........................................................................................................................56 5.2.1 Menu navigation ......................................................................................................................... 56 5.2.2 Navigation aids ........................................................................................................................... 57

5.3 Page view ...........................................................................................................................59 5.3.1 Navigate on a page .................................................................................................................... 59 5.3.2 Use navigation aids .................................................................................................................... 59 5.3.3 Description of the control elements ............................................................................................ 60

5.4 Remote access ..................................................................................................................72 5.4.1 General....................................................................................................................................... 73 5.4.2 Recommended browsers............................................................................................................ 73 5.4.3 Operating instructions ................................................................................................................ 74

6 Menu 77

6.1 Start screen ........................................................................................................................78 6.2 Quick setup ........................................................................................................................79

6.2.1 Quick setup: Project AS-i networks ............................................................................................ 80 6.2.2 Quick setup: Configure the operating mode of the AS-i masters ................................................ 81 6.2.3 Quick setup: Configure the output access .................................................................................. 82 6.2.4 Quick setup: Access the device via QR code ............................................................................. 82 6.2.5 Quick setup: Configure the EtherNet/IP interface ....................................................................... 83 6.2.6 Quick setup: Set the configuration mode .................................................................................... 84 6.2.7 Quick setup: Set the configuration interface ............................................................................... 85 6.2.8 Quick setup: Address the AS-i slaves connected to AS-i master 1 ............................................ 87 6.2.9 Quick setup: Address the AS-i slaves connected to AS-i master 2 ............................................ 88

6.3 AS-i 1 / AS-i 2 .....................................................................................................................89 6.3.1 AS-i 1 / AS-i 2: Master setup ...................................................................................................... 90 6.3.2 AS-i 1 / AS-i 2: Diagnosis ........................................................................................................... 92 6.3.3 AS-i 1 / AS-i 2: AS-i slaves ......................................................................................................... 94

6.4 System .............................................................................................................................100 6.4.1 System: Programmable Logic Controller (PLC) ........................................................................ 101 6.4.2 System: Information ................................................................................................................. 107 6.4.3 System: Setup .......................................................................................................................... 108 6.4.4 System: Diagnosis .................................................................................................................... 119

6.5 Interfaces .........................................................................................................................120 6.5.1 Interfaces: Configuration interface ............................................................................................ 121 6.5.2 Interfaces: EtherNet/IP interface .............................................................................................. 124

6.6 Safety ...............................................................................................................................136 6.6.1 Safety: AS-i 1 master settings .................................................................................................. 137 6.6.2 Safety: AS-i 2 master settings .................................................................................................. 141 6.6.3 Safety: Local IOs ...................................................................................................................... 142 6.6.4 Safety: System ......................................................................................................................... 146

6.7 ifm system solutions .........................................................................................................147 6.7.1 Notes on ifm system solutions .................................................................................................. 148 6.7.2 Show information about installed ifm apps ............................................................................... 149 6.7.3 Install single/basic app ............................................................................................................. 149 6.7.4 Install multi app ........................................................................................................................ 150 6.7.5 Update ifm apps ....................................................................................................................... 151 6.7.6 Uninstall ifm apps ..................................................................................................................... 151

7 Setup 152

7.1 Mounting and electrical connection .................................................................................153 7.2 Install devices on the local I/O interface ..........................................................................153 7.3 Start screen 'Basic settings' .............................................................................................154

7.3.1 Change the basic settings of the device ................................................................................... 154

Page 4: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

4

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Contents

7.4 Notes on the firmware update ..........................................................................................156 7.5 Connect and address AS-i slaves ....................................................................................156 7.6 Setup of EtherNet/IP ........................................................................................................156 7.7 Setup of the configuration interface .................................................................................157 7.8 Replace standard AS-i slave ............................................................................................157 7.9 Replace safe AS-i slave ...................................................................................................158

8 Troubleshooting 159

8.1 Status LED .......................................................................................................................160 8.1.1 Status LED: Basic device ......................................................................................................... 160 8.1.2 Status LED: fieldbus EtherNet/IP ............................................................................................. 160

8.2 Online diagnosis function .................................................................................................161 8.2.1 Message types ......................................................................................................................... 161 8.2.2 Locate error sources ................................................................................................................ 161

8.3 Online Support Centre (OSC) ..........................................................................................162 8.3.1 OSC: Aktuelle Meldungen zeigen ............................................................................................. 163 8.3.2 OSC: Show message history .................................................................................................... 164

8.4 Availability of the fail-safe PLC ........................................................................................165 8.5 Display diagnostic protocol ..............................................................................................165

9 Appendix 166

9.1 Technical data ..................................................................................................................167 9.1.1 Environmental conditions ......................................................................................................... 168 9.1.2 Safety classification .................................................................................................................. 168 9.1.3 Power supply connections ........................................................................................................ 168 9.1.4 Electrical data ........................................................................................................................... 168 9.1.5 Display elements ...................................................................................................................... 169 9.1.6 Housing .................................................................................................................................... 169 9.1.7 Interfaces .................................................................................................................................. 170 9.1.8 AS-interface .............................................................................................................................. 171 9.1.9 Programmable Logic Controller (PLC) ..................................................................................... 171

9.2 Address assignment in Ethernet networks ......................................................................172 9.3 Configuration interface: connection concepts ..................................................................173

9.3.1 Direct link .................................................................................................................................. 174 9.3.2 Connection via Ethernet network .............................................................................................. 175

9.4 AS-i master ......................................................................................................................176 9.4.1 Operating modes of the AS-i master ........................................................................................ 177 9.4.2 Master flags .............................................................................................................................. 179

9.5 AS-i slaves .......................................................................................................................184 9.5.1 Profiles of AS-i slaves............................................................................................................... 185

9.6 Fieldbus EtherNet/IP ........................................................................................................196 9.6.1 Fieldbus objects ....................................................................................................................... 197 9.6.2 Fieldbus parameters ................................................................................................................. 199 9.6.3 Device-specific parameters ...................................................................................................... 200 9.6.4 Cyclic data ................................................................................................................................ 221 9.6.5 Acyclic data .............................................................................................................................. 254 9.6.6 Configuration mode .................................................................................................................. 371

9.7 OSC messages ................................................................................................................381 9.7.1 OSC messages: System .......................................................................................................... 382 9.7.2 OSC messages: AS-i 1 / AS-i 2 ................................................................................................ 383 9.7.3 OSC messages: Safety module ............................................................................................... 384 9.7.4 OSC messages: Safety PLCopen function blocks .................................................................... 401

Page 5: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

5

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Contents

10 Index 402

11 ifm weltweit • ifm worldwide • ifm à l’échelle internationale 407

Page 6: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

6

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Preliminary note Legal and copyright information

1 Preliminary note

Legal and copyright information ............................................................................................................... 7 Purpose of the document ......................................................................................................................... 7 Symbols and formats used ....................................................................................................................... 8 Overview: User documentation for AC4S ................................................................................................. 9 Modification history ................................................................................................................................... 9

14801

Page 7: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

7

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Preliminary note Legal and copyright information

>

1.1 Legal and copyright information 6088

© All rights reserved by ifm electronic gmbh. No part of this manual may be reproduced and used without the consent of ifm electronic gmbh.

All product names, pictures, companies or other brands used on our pages are the property of the respective rights owners: • AS-i is the property of the AS-International Association, (→ www.as-interface.net) • CAN is the property of the CiA (CAN in Automation e.V.), Germany (→ www.can-cia.org) • CODESYS™ is the property of the 3S – Smart Software Solutions GmbH, Germany (→ www.codesys.com) • DeviceNet™ is the property of the ODVA™ (Open DeviceNet Vendor Association), USA (→ www.odva.org) • EtherNet/IP® is the property of the →ODVA™ • IO-Link® (→ www.io-link.com) is the property of the →PROFIBUS Nutzerorganisation e.V., Germany • Microsoft® is the property of the Microsoft Corporation, USA (→ www.microsoft.com) • PROFIBUS® is the property of the PROFIBUS Nutzerorganisation e.V., Germany (→ www.profibus.com) • PROFINET® is the property of the →PROFIBUS Nutzerorganisation e.V., Germany • Windows® is the property of the →Microsoft Corporation, USA

>

1.2 Purpose of the document 20135

This document applies to devices of the type "SmartPLC AC4S with EtherNet/IP" interface" (art. no.: AC422S) with the firmware version 4.0.2.

These instructions describe the following topics:

Mounting and electrical connection of AC422S

Installation of additional devices (sensors, actuators) to the local I/O interface

Operation and configuration of the device via the menu (GUI and web interface)

Command channels, cyclic and acyclic data records

Error diagnostics and troubleshooting

Page 8: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

8

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Preliminary note Symbols and formats used

>

1.3 Symbols and formats used 15989

WARNING

Death or serious irreversible injuries may result.

CAUTION

Slight reversible injuries may result.

NOTICE

Property damage is to be expected or may result.

Important note Non-compliance can result in malfunction or interference

Information Supplementary note

► ... Request for action

> ... Reaction, result

→ ... "see"

abc Cross-reference

123 0x123 0b010

Decimal number Hexadecimal number Binary number

[...] Designation of pushbuttons, buttons or indications

Page 9: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

9

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Preliminary note Overview: User documentation for AC4S

>

1.4 Overview: User documentation for AC4S 18655

ifm electronic provides the following user documentation for the models of the device class "Fail-safe SmartPLC AC4S":

Document Content / Description

Data sheet Technical data of AC422S as a table

Operating instructions * Notes on mounting and electrical installation of AC422S

Setup, description of the operating and display elements, maintenance information, scale drawing

Device manual Notes on operation of AC422S via GUI and web interface

Description of the cyclic and acyclic data records, fieldbus parameters and command interface

Error description

Programming manual Notes on configuration of a AC422S system in CODESYS safety

Notes on programming of the standard PLC of AC422S

Notes on programming the fail-safe PLC of AC422S

Description of the device-specific CODESYS function libraries

Legend: *... The operating instructions are supplied with the device.

All documents can be downloaded from ifm's website. → www.ifm.com > Select country > [Data sheet search] > (Article no.) > [Operating instructions]

>

1.5 Modification history 4165

Version Subject Date

1.0 New creation of the document 03-02-2016

Page 10: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

10

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Safety instructions Modification history

2 Safety instructions

Required background knowledge ...........................................................................................................11 Please note .............................................................................................................................................11 Tampering with the unit ..........................................................................................................................12 Start-up behaviour of the controller ........................................................................................................12

213

Page 11: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

11

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Safety instructions Required background knowledge

>

2.1 Required background knowledge 13323

This document is intended for people with knowledge of control technology and PLC programming to IEC 61131-3.

To program the PLC, these people should also be familiar with the CODESYS software.

This document is intended for specialists. Specialists are people who, based on their relevant training and experience, are capable of identifying risks and avoiding potential hazards that may be caused during operation or maintenance of the product. The document contains information about the correct handling of the product.

► Read this document before use to familiarise yourself with operating conditions, installation and operation. Keep this document during the entire duration of use of the device.

► Follow the safety instructions. >

2.2 Please note 6091

11212

No characteristics are warranted with the information, notes and examples provided in this manual. With the drawings, representations and examples given no responsibility for the system is assumed and no application-specific particularities are taken into account.

► The manufacturer of the machine/equipment is responsible for ensuring the safety of the machine/equipment.

► Follow the national and international regulations of the country in which the machine/installation is to be placed on the market.

WARNING

Non-observance of these instructions can lead to property damage or personal injury. ifm electronic gmbh does not assume any liability in this regard.

► The acting person must have read and understood the safety instructions and the corresponding chapters in this manual before working on and with this device.

► The acting person must be authorised to work on the machine/equipment.

► The acting person must have the qualifications and training required to perform this work.

► Adhere to the technical data of the devices! You can find the current data sheet on ifm's homepage at: → www.ifm.com > Select your country > [Data sheet search] > (article number.) > [Technical data in PDF format]

► Note the installation and wiring information as well as the functions and features of the devices! → supplied installation instructions or on ifm's homepage: → www.ifm.com > Select your country > [Data sheet search] > (article number.) > [Operating instructions]

► Please note the corrections and notes in the release notes for the existing documentation, available on the ifm website: → www.ifm.com > Select your country > [Data sheet search] > (article number.) > [Operating instructions]

Page 12: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

12

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Safety instructions Tampering with the unit

>

2.3 Tampering with the unit 11242

WARNING

Tampering with the units can affect the safety of operators and machinery.

Tampering with the units is not allowed. In case of non-compliance our liability and warranty expire.

► Do not open the devices.

► Do not insert any objects into the devices.

► Prevent metal foreign bodies from penetrating.

>

2.4 Start-up behaviour of the controller 6827

15233 11575

WARNING

Danger due to unintentional and dangerous start of machine or plant sections.

► When creating the program, the programmer must ensure that no unintentional and dangerous start of machines or plant sections after a fault (e.g. e-stop) and the following fault elimination can occur. Realise restart inhibit.

► In case of an error, set the outputs concerned to FALSE in the program.

A restart can, for example, be caused by: • voltage restoration after power failure • reset after watchdog response because of too long a cycle time • error elimination after an E-stop

To ensure a safe behaviour of the controller:

► Monitor the voltage supply in the application program.

► In case of an error switch off all relevant outputs in the application program.

► Monitor actuators which can cause hazardous movements in the application program (feedback).

► Monitor relay contacts which can cause hazardous movements in the application program (feedback).

► If necessary, ensure that welded relay contacts in the application project cannot trigger or continue hazardous movements.

Page 13: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

13

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Start-up behaviour of the controller

3 System description

Intended use ...........................................................................................................................................14 Information concerning the device .........................................................................................................15 Hardware ................................................................................................................................................22 Software..................................................................................................................................................33

8697

This chapter describes the structure and the components of the system.

Page 14: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

14

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Intended use

>

3.1 Intended use 5310

NOTICE

Danger when device is overloaded or incorrectly used.

The device and / or the associated machine / plant may be damaged or destroyed or may malfunction if the limits of the "Technical data" for this device are exceeded or if the device is used outside the specified "Intended use".

► Use the device only within the limits of the Technical data (→ page 167) ( data sheet).

► Use the device only in accordance with the "Intended use".

>

3.1.1 Permitted use 7149

AC422S can assume the following functions:

AS-i master in 2 separate AS-i networks

Fail-safe programmable logic controller (PLC) and standard PLC for acquiring, processing and providing safe and non-safe data of the connected AS-i slaves and the channels of the local I/O interface

Gateway for the transmission of standard control and user data between a higher-level EtherNet/IP controller and the slaves in the AS-i networks

>

3.1.2 Prohibited use 5320

You MUST not use the device in the following areas:

outdoors,

beyond the limits of the technical data ( data sheet).

Page 15: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

15

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Information concerning the device

>

3.2 Information concerning the device

Where is what on the AS-i device? ........................................................................................................16 Operating elements ................................................................................................................................17 Display elements ....................................................................................................................................17 Interfaces ................................................................................................................................................18 Type label ...............................................................................................................................................21 Required accessories .............................................................................................................................21

5330

Page 16: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

16

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Information concerning the device

>

3.2.1 Where is what on the AS-i device? 8719

Legend:

Display

Status LED (H1)

2 function keys

4 arrow keys

Connector (X1) for AS-i 1, AS-i 2, functional earth

Connector (X2) for AUX

Local inputs and outputs (X4) (behind the front flap)

Front flap

Slot for SD card (X5) (behind the front flap)

Ethernet configuration interface (X3) (behind the front flap)

EtherNet/IP interface 2 (X6) with status LED (H2, H3)

EtherNet/IP interface 1 (X7) with status LED (H4, H5)

Page 17: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

17

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Information concerning the device

>

3.2.2 Operating elements 15840

The device provides the following operating elements. >

Arrow and function keys 15867

Below the display is the key panel with two function keys and four arrow keys. The operator controls the Graphical User Interface (GUI) of the device with the keys.

Technical data: → Operation >

3.2.3 Display elements 7062

The device provides the following display elements: >

Display 7083

The display is used to display the Graphical User Interface (GUI) of the device.

Operating notes: → Operation (→ page 53)

Technical data: → Display elements (→ page 169) >

Status LEDs 18985

The device features the following status LEDs which display the current status of system components.

Meaning of the LED colours and flashing frequencies: → Status LED (→ page 160)

Page 18: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

18

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Information concerning the device

>

3.2.4 Interfaces

Ethernet configuration interface .............................................................................................................19 Local input/output interface ....................................................................................................................19 SD card slot ............................................................................................................................................20 EtherNet/IP fieldbus interface .................................................................................................................20

7134

AC422S has the following interfaces.

Page 19: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

19

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Information concerning the device

>

Ethernet configuration interface 6982

The configuration interface (X3) is located behind the front flap of the device. It allows the user to access the following device functions:

web interface for device configuration and diagnosis

programming of the device-internal standard PLC using CODESYS

Configuration as fieldbus interface

Possible network topologies: → Configuration interface: connection concepts (→ page 173)

Technical data: → Interfaces (→ page 170) >

Local input/output interface 7152

The local input/output interface (X4) is behind the front flap of the device. Safe and non-safe peripherals without AS-i interface can be connected to the local inputs and outputs.

Connections of the local I/O interface:

4x output channels (OUT1 .... OUT4) → Local outputs (→ page 19)

2x voltage ground GND → Voltage source / voltage ground (→ page 19)

2x voltage source +24V → Voltage source / voltage ground (→ page 19)

8x input channels (IN1 ... IN8) → Local inputs (→ page 19)

>

Voltage source / voltage ground 19824

+24V and GND are used as voltage supply for the safety IO PCB of the safety module of AC422S.

Notes on the electrical connection: → Electrical connection (→ page 36) >

Local inputs 19825

The local I/O interface provides 8 input channels for the connection of devices (e.g. sensors, switches, light curtains). Each input channel can be used as safe or standard input. Configuration is effected via the programming system CODESYS.

Connection of peripherals: → Connect devices to local I/O interface (→ page 38)

Technical data: → Interfaces (→ page 170) >

Local outputs 19826

The local I/O interface provides 4 output channels for the connection of devices (e.g. actuators, relays). Each output channel can be used as safe or standard output. Configuration is effected via the programming system CODESYS.

Notes on the connection of peripherals: → Connect devices to local I/O interface (→ page 38)

Technical data: → Interfaces (→ page 170) >

Page 20: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

20

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Information concerning the device

Possible combinations of input and output channels 12095

The inputs IN1...IN8 can be configured both as safe and non-safe inputs.

The outputs OUT1...OUT4 can be configured both as safe and non-safe outputs.

This permits the following minimum or maximum input and output combinations:

Min. configuration Max. configuration

8 non-safe inputs

4 non-safe outputs

4 safe inputs, 2 channels (SIL3)

4 safe outputs, 1 channel (SIL3)

>

SD card slot 8699

The SD card slot (X5) is located behind the front flap of the device. The following actions can be performed with an SD card:

Save and restore the device configuration

Storage medium for access to standard PLC

Technical data: → Interfaces (→ page 170) >

EtherNet/IP fieldbus interface 12113

The device communicates with the higher-level control instance of the EtherNet/IP network via the EtherNet/IP interface (X6/X7).

Notes regarding connetion concepts: → Konfigurationsschnittstelle: Verbindungskonzepte (→ page 173)

Technical data: → Interfaces (→ page 170)

Page 21: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

21

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Information concerning the device

>

3.2.5 Type label 19822

The type label is on the right housing side of the device. It provides the following information:

QR code for product website

CE/cULus marking

Protection class

AS-i certification

TÜV certification

Hardware version

Operating voltage for – Aux / local IO PCB – AS-i

max. current consumption of the device

max. load per output channel of the local I/O interface

Type designation incl. device functionality – number of AS-i fieldbus gateways – classification of the AS-i masters – fail-safe PLC – fieldbus

Manufacturer identification

>

3.2.6 Required accessories 7078

To be able to operate the device in a sensible way you need the following accessories (not supplied with the device):

Depending on the selected voltage supply ( Operating instructions) you need:

a power supply for the 24 V power supply (e.g. art. no. DN3011)

for each AS-i master one AS-i power supply each (e.g. art. no. AC1236)

a data decoupling module AC1250 (accessory, optional)

Fail-safe and standard AS-i slaves

Fail-safe and standard devices for connecting with the local I/O interface

Page 22: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

22

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Hardware

>

3.3 Hardware

Safety architecture ..................................................................................................................................23 Operating states of AC422S ...................................................................................................................29 Monitoring and securing mechanisms ....................................................................................................30 Error detection and processing ..............................................................................................................31

19834

Page 23: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

23

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Hardware

>

3.3.1 Safety architecture

System architecture ................................................................................................................................24 Process safety time ................................................................................................................................27 Diagnostic coverage DC and MTTFd value ...........................................................................................28

19815

Page 24: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

24

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Hardware

>

System architecture 20485

The hardware structure of the safety module of AC422S corresponds to the implementation to DIN EN ISO 13849-1:2008, IEC 62061:2010 and IEC61508:2010 with a two-channel architecture with hardware fault tolerance (HFT = 1).

The device achieves the following characteristic safety values:

SIL 3 / SIL CL 3 referred to IEC 61508:2010 and IEC 62061:2010

Performance Level e EN ISO 13849-1:2008)

Category 4 (EN ISO 13849-1:2008)

The reachable characteristic safety values of the automation system implemented with AC422S depend on the following components:

Safety classification of the peripherals installed at the local I/O interface (→ Supported device types (→ page 41))

Safety classification of the installed safe AS-i slaves

AC422S has the following system architecture:

Page 25: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

25

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Hardware

>

Main module 19837

The main module is the central component of AC422S. It contains the recovery system and the firmware of the device and controls the communication between the individual system components via the backplane. The main module has interfaces to the following components:

Display (→ Display (→ page 25))

COM module (→ COM module (→ page 25))

Ethernet configuration interface

AS-i module (→ AS-i module (→ page 25))

Safety module (→ Safety module (→ page 26)) >

Display 19855

The display is the graphic user interface of AC422S via which the user can configure and diagnose the device. The display exchanges the resulting data with the main module. >

COM module 19856

The COM module provides the EtherNet/IP functionality of AC422S. This comprises the EtherNet/IP connection and the necessary firmware. The COM module receives the fieldbus data from the main module via an interface and transfers it to the fieldbus. Simultaneously it receives data from the fieldbus and transfers it to the main module for further processing. >

AS-i module 19843

The AS-i module provides the AS-i functionality of AC422S such as receiving, evaluating and transmitting AS-i telegrams without any logical preprocessing. It contains 2 AS-i masters controlling 2 separate AS-i circuits.

The following number of AS-i slaves can be connected to each AS-i master:

up to 62 non safe AS-i slaves or

up to 31 safe AS-i input slaves or

up to 15 AS-i control slaves to control safe AS-i output slaves

The AS-i module exchanges the data of the safe AS-i slaves with the safety module via the backplane.

All AS-i data is provided to the main module for representation on the display.

Page 26: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

26

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Hardware

>

Safety module 19840

The safety module contains the safety-related hardware of AC422S. The architecture of the safety module provides the following structural features:

1oo2 hardware architecture (1 out of 2 architecture)

2-channel structure with separate diagnostics in both channels

2-channel safe inputs selectable

1-channel and 2-channel safe outputs selectable

Built-in tests on both safe processing units (safety CPU 1/2)

Hardware failure tolerance (HFT) = 1

The safety module consists of the following components:

Safety CPU PCB with 2 processors for the control technology signal processing (safety CPU1/2)

Safety I/O PCB with a separate voltage supply for the local I/O interface

Both PCBs are separated from each other galvanically. They are supplied from separate voltage sources.

Both safety CPUs have separate watchdogs and reset circuits. They are interconnected via cross communication.

Both PCBs are interconnected via a serial interface for bidirectional data exchange.

The safety module has interfaces to the main module and the AS-i module.

Page 27: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

27

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Hardware

>

Process safety time 19839

The process safety time depends on the source and the objective of the request, the signal processing and the transmission length.

► When setting up the safety function, also take into account the process safety time of the application!

► Take into account other potential delays caused by upstream and downstream components (sensor, actuators) for time-related considerations. These times extend the fault reaction time.

► Process safety time of the other components of the safety function: data sheets of the manufacturers

For AC422S applies:

Safety timeAC422S < 70 ms (for cycle time 10 ms)

Safety time = fault detection time + fault reaction time

The user can set the cycle time of the fail-safe PLC of AC422S in the defined value range.

The following table shows the typical safety times. They include the response times of safe transmission and processing. The times to the respective clamp are shown. The response times of the sensors and actuators (→ operating instructions of the sensors / actuators) are not taken into account.

Source

Target

AS-i output local output channel

AS-i input 45 ms + 2 * cycle timefail-safe PLC 1 38 ms + 2 * cycle timefail-safe PLC

Local input channel 31 ms + 2 * cycle timefail-safe PLC 24 ms + 2 * cycle timefail-safe PLC1

Legend:

1 ... The process safety time is extended by 1 PLC cycle if the safe AS-i input slave or the safe local input channels are configured in CODESYS by means of the following logical devices:

SF_IN_ASi_dependent_filter_nshutdown

SF_IN_local_dependent_filter_nshutdown

If the safety time is shorter than the process safety time required by the safety function of the plant, a single fault can in the worst case lead to a faulty output signal for a short time but not to a loss of the safety function.

A loss of the safety function can only occur if the faulty signal cannot be corrected within the process safety time.

In the following cases a single fault cannot lead to a hazardous situation:

if the safe state is assumed

if the fault detection and the reaction to the fault happen within the process safety time

Page 28: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

28

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Hardware

>

Diagnostic coverage DC and MTTFd value 19841

The diagnostic coverage (DC) of AC422S is: 95 %

The MTTFd value of AC422S is: 100 years

The CCF value of AC422S is: 5 %

Page 29: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

29

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Hardware

>

3.3.2 Operating states of AC422S 19835

AC422S has the following operating states:

INIT

NORMAL OPERATION

SYSTEM STOP

Below the state chart:

INIT

After the start the device automatically goes into the INIT state ( ). In the INIT state the device undergoes the different hardware and integration tests (PBIT = Power-up Built-In Test). If the PBIT

test is successfully passed, the device takes the state NORMAL OPERATION ( ). If the PBIT

test is not passed, the device passes into the SYSTEM STOP ( ).

NORMAL OPERATION In NORMAL OPERATION the device of standard PLC and the fail-safe PLC provides a working environment. The states and the operation modes of the PLC applications are valid (see programming manual). Simultaneously and irrespective of the processing of the PLC applications the device continuously undergoes different hardware tests (CBIT = continuous built-in test). If this

CBIT test is not passed, the device goes into the SYSTEM STOP state ( ).

SYSTEM STOP In SYSTEM STOP the device is in the safe state. To leave the SYSTEM STOP state the operator

has to carry out a power-on reset. The device changes to the INIT state ( ).

Page 30: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

30

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Hardware

>

3.3.3 Monitoring and securing mechanisms 19836

>

System start / power on reset 19842

When the voltage supply has been applied, the safety module of AC422S automatically undergoes a power-on built-in test (PBIT). The PBIT consists of the following routines:

Test and installation of the safety-relevant hardware modules

Test of the program, configuration and user data in SDRAM (CRC test)

If at least one of these partial tests is failed, the system reacts as follows:

The safety module goes into the safe state

The transition from the fail-safe PLC to the safe operation is prevented

An error message is provided in the online support centre (OSC) of the device >

Normal operation 19844

During normal operation the safety module of AC422S continuously undergoes a continuous built-in test (CBIT). The CBIT detects accidental hardware errors. It monitors all safety-relevant hardware modules. The CBIT consists of the following routines:

Monitor the safety-relevant hardware modules with the required DC

Monitor all diagnostic data that is relevant for the safe functions

Monitor the program process

Depending on the error class the device triggers certain measures (→ Error classes (→ page 31)).

Page 31: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

31

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Hardware

>

3.3.4 Error detection and processing 19838

>

Error classes 19849

AC422S recognises the following error classes: >

Fatal error 19847

The following errors are classified as fatal errors:

error in the device (temperature exceeded, soiling)

error in the channels

Response to fatal errors:

The safety module goes into the safe state (→ Safe state (→ page 32)) >

Serious error 19848

Following errors are classified as serious errors:

Errors occurring in the periphery which do not affect the processing logic of the device

Response to serious errors:

The safety module goes into the safe state (→ Safe state (→ page 32)) >

Exception errors 19845

An exception error occurs when the device software is in a non foreseen state.

Response to exception errors:

The safety module goes into the safe state (→ Safe state (→ page 32)) >

Scheduling errors 19846

The following errors are classified as scheduling errors:

Errors in the correct processing of the different tasks in the course of which the operating system cannot make a task change any more so that the watchdog is triggered.

Response to scheduling errors:

All output channels of the local I/O interface go into the default state (= switched off)

All safe output slaves stop sending code sequences

Restart disable of the fail-safe PLC >

Error message 19850

AC422S signals occurring errors via the following mechanisms:

status LED (→ status LED (→ page 160))

online support Centre (→ Online Support Centre (OSC) (→ page 162))

Page 32: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

32

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Hardware

>

Safe state 19851

The safety module of AC422S is always in the safe state. Exceptions are the following operating states of the fail-safe PLC:

debug operation

download operation

safe operation

If a fatal, serious or exception error occurs during these operating states, the safety module of AC422S goes into the safe state.

The safe state is characterised by the following features:

All safe output channels of the local I/O interface are already power-free

All safe AS-i control slaves have stopped sending code sequences

the fail-safe PLC is in the STOP mode

the cyclic data transfer between safety module and basic device is interrupted

the data packages of the safe cross communication between the two safety CPUs are filled with zero sequences and marked as "invalid"

the basic device detects that the safety module is in the safe state and provides this information in the OSC and on the EtherNet/IP and configuration interface

All non safety-relevant functions of the basic device continue to be available in the safe state.

>

Reset error 19852

All error states (→ Error classes (→ page 31)) can only be exited using one of the following measures.

► Reboot the device (power-on reset)

Page 33: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

33

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Software

>

3.4 Software

Software modules of the device .............................................................................................................34 Safety functions ......................................................................................................................................34 Certified software components for safe applications ..............................................................................34

7077

Page 34: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

34

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

System description Software

>

3.4.1 Software modules of the device 19830

AC422S has the following software modules:

Software modules Description

Recovery system Environment for the firmware installation

Firmware Firmware of AC422S

CODESYS standard runtime system (standard PLC)

Runtime environment for the execution of CODESYS applications to IEC 61131

CODESYS safety runtime system (fail-safe PLC)

Certified runtime environment for the execution of safe CODESYS applications

Standard application CODESYS application for standard PLC

Safe application CODESYS application for fail-safe PLC (= safety function)

The user is responsible for setting the safe function of the application (= safe application). If necessary, he must also obtain an approval from the supervisory and test organisations according to the national regulations.

>

3.4.2 Safety functions 19854

AC422S provides the following safety functions:

Freely programmable fail-safe PLC

Safe reading of local digital inputs and linking via the fail-safe PLC

Safe control of local digital outputs via the fail-safe PLC

Safe reading of safe AS-i input slaves and linking via the fail-safe PLC

Control of safe AS-i output slaves via the fail-safe PLC

AC422S provides the programmer with a safe environment which is suited for the execution of a safe application to SIL3. The user is responsible for programming the safe application.

>

3.4.3 Certified software components for safe applications 19821

To program safe applications for AC422S ifm electronic provides certified software components for the programming environment CODESYS safety 3.5. In addition, the user can use the function libraries supplied with CODESYS safety.

Information about device-specific software components and about how to program standard PLC and the fail-safe PLC: → Programming manual fail-safe SmartPLC AC4S"

Page 35: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

35

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Software

4 Installation

Installation...............................................................................................................................................36 Electrical connection ...............................................................................................................................36 Connect devices to local I/O interface ....................................................................................................38

10257

This chapter informs about the connection of devices to the local I/O interface.

Page 36: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

36

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Installation

>

4.1 Installation 14343

The unit must be connected by a qualified electrician.

Observe the environmental conditions for the installation (→ Environmental conditions (→ page 168))! Ensure a condensation-free environment. Avoid excessive dust, vibration and shock. The air circulation through the vents must not be impeded. Installation in environments with ionising radiation is not permitted.

Avoid installation in direct vicinity of frequency inverters or other interfering sources.

Keep the installation space of the device free from electrically-conductive particles.

For proper installation of AC422S:

► Fix the device onto a 35 mm raised rail.

► Vertical installation (upright).

► Adhere to a minimum distance of 30 mm between the ventilation holes (perforated sheet) and other parts.

► Maximum operating altitude: 2000 m above sea level

► The protection rating of the device is IP 20. The device must be installed at a protected location (e.g. control cabinet with IP 54).

>

4.2 Electrical connection 14350

For proper electrical connection of AC422S:

The device must be connected by a qualified electrician.

► Disconnect power before connecting the device.

► Observe the national and international regulations for the installation of electrical equipment.

► Connect the device as indicated on the terminals.

► Ensure an electrical connection between AC422S (X1, terminal FE) and the ground of the installation.

► Lay the cables in a cable duct.

► For an overview of the possible kinds of supply: → Device supply (→ page 37)

► Select a power supply to supply the local IO interface which supplies a min. output current of 3 A.

► The cable length of the DC supply between power supply and AC422S is to be limited to max. 3 m.

► The safe local outputs should comply with the parameters nominal current and selectable inductance according to IEC 61131-2: 2008:

Nominal current: 0.5 A for each output port

Inductance: Utilisation category DC13 according to IEC60947-5-1, max. 25 Hz with a switch-on or switch-off time of min. 20 ms

Page 37: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

37

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Electrical connection

>

4.2.1 Device supply 19831

To operate an AS-i system, an AS-i power supply (e.g. AC1236) or the data decoupling module AC1250 (not supplied) with an AS-i or DC power supply is required.

► Power of the local I/O interface must be applied simultaneously with the device supply.

► Only connect an external voltage supply to the safety module with overcurrent protection.

► The safe power supply and the standard power supply must comply with the standard DIN EN 60950-1 for SELV/PELV.

► Supply the device with one of the following versions. >

Device supply via AUX, AS-i supply via AS-i power supply 19823

► Supply the device with a voltage of 24 V DC (18...32 SELV/PELV) (e.g. from the 24 V DN3011 power supply from ifm electronic). The connection is made to the terminals X2. The max. cable length is 3 m.

► To supply the AS-i lines, connect the terminals X1 to one or two AS-i power supplies.

► Ensure a low-resistance connection of the symmetry point of the device (terminal X1.5 FE) to the ground of the installation.

>

Device and AS-i supply via one common power supply 7141

► Plug the data decoupling module AC1250 (not supplied) into the terminals X1 and X2 to supply the device and the connected AS-i lines.

► Ensure a low-resistance connection of the data decoupling (terminal "FE") to the ground of the installation.

► The device and both AS-i lines are supplied via one power supply (SELV/PELV 21.5 V...31.6 V AS-i or AUX). The AS-i lines have a thermal short-circuit protection (4A).

A high-performance power supply can supply several AC422S.

Page 38: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

38

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Connect devices to local I/O interface

>

4.3 Connect devices to local I/O interface

Safety instructions ..................................................................................................................................39 Supported connection types ...................................................................................................................40 Supported device types ..........................................................................................................................41 Install safe device to local I/O interface ..................................................................................................52 Install standard device on local I/O interface..........................................................................................52

17640

Page 39: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

39

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Connect devices to local I/O interface

>

4.3.1 Safety instructions 19458

WARNING

Risk of personal injuries and/or damage to property.

Safety-relevant functions to SIL 3 / cat. 4 / PL e can only be implemented if one of the following input combinations is used for the connection of 2-channel sensors:

IN1 and IN8

IN2 and IN7

IN3 and IN6

IN4 and IN5

ifm electronic does not assume any guarantee for obtaining the required SIL / cat. / PL if other than the above-mentioned input combinations is used.

► Use one of the above-mentioned input combinations for the connection of 2-channel sensors.

NOTICE

Risk of material damage!

► Observe the original operating instructions of the safe sensor/actuator.

► Disconnect the devices to be connected before they are connected to the local inputs/outputs of AC422S.

► Only implement voltage supply of the peripherals with a power supply to SELV/PELV.

► Ensure that the input signals have a maximum frequency of 25 Hz for the connection of devices to the local I/O interface.

► Only connect devices that are supported by AC422S (→ Supported device types (→ page 41))!

► To obtain a certain safety integrity level to EN ISO 13849 or performance level to EN 62061, observe the max. obtainable SIL / cat. Z/PL values when devices are installed on the local I/O interface.

► When external sensors are connected, observe the max. permitted supply voltage of the sensor and select the supply of the local I/O interface accordingly.

► Do not connect any external potential.

► The signal cable length for external devices (sensors, actuators) is to be limited to max. 10 m.

Page 40: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

40

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Connect devices to local I/O interface

>

4.3.2 Supported connection types 11234

The local I/O interface of AC422S supports the connection of safe and non-safe devices. The following connection methods are possible:

Connection method Description

Input, 1 channel, non-safe corresponds to a standard input

The input value is read in the safe application by means of an FB.

Input, 2 channels, safe is composed of 2 standard inputs

The 2 logical input signals are monitored by means of a logical device and linked with a safe process signal.

The safe process signal can be used in the safe application.

Input, 2 channels with test pulse, safe is composed of 2 standard inputs

The 2 logical input signals are monitored by means of a logical device and linked with a safe process signal.

To detect cross-bridging the input signals are also checked for the presence of a test pulse.

The safe process signal can be used in the safe application.

Output, 1 channel, non-safe corresponds to a standard output

The output value is generated in the safe application by means of an FB.

Output, 1 channel, safe A safe process signal is provided on 1 output without additional monitoring.

Output, 2 channels, safe A safe process signal is provided on 2 outputs without additional monitoring

Page 41: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

41

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Connect devices to local I/O interface

>

4.3.3 Supported device types

Mechanical switches ...............................................................................................................................42 Electronic sensors ..................................................................................................................................44 Safety light curtains ................................................................................................................................46 Safety light grids .....................................................................................................................................48 Output relay ............................................................................................................................................50

11210

The local I/O interface (X4) supports the connection of the following safe device types.

The signals of the clock outputs of safe sensors are not evaluated by AC422S.

► Note possible effects of the obtainable SIL/PL of the entire system.

The proper function of a connected local device can only be obtained by selecting a logical device interface in CODESYS suitable for the operating conditions.

► Observe the notes of how to integrate safe devices in a CODESYS project (→ original programming manual, Configure safe devices at local I/O interface)!

Page 42: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

42

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Connect devices to local I/O interface

>

Mechanical switches 18456

>

Device type MS-1 11235

Circuit diagram/wiring diagram Description Safety classification

max. SIL max. PL max. cat.

Mechanical switch

Two-channel connection

not tested

3 e 4

The indicated safety classifications can only be obtained with protected wiring between switch and AC422S.

► Observe current standards of the country in which the AC422S automation system is to be operated.

Switch must meet the conditions of the standard IEC 60947-5-1 (Appendix K).

► Select the input circuits according to the max. safety classification (SIL / cat. / PL).

Page 43: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

43

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Connect devices to local I/O interface

>

Device type MS-2 14105

Circuit diagram/wiring diagram Description Safety classification

max. SIL max. PL max. cat.

Mechanical switch

Two-channel connection

Test with 2 time-shifted switch-off pulses on the input channels

Test signals are generated by AC422S.

3 e 4

Switch must meet the conditions of the standard IEC 60947-5-1 (Appendix K).

► Select the input and output circuits according to the max. safety classification (SIL / cat. / PL).

► If several MS-2 are connected, the test signals must be different.

► Observe current standards of the country in which the AC422S automation system is to be operated.

► Test the safety function within the two-error occurrence time. The second-error occurrence time takes 24 hours. Within this time the safety function of the device should be requested once.

Page 44: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

44

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Connect devices to local I/O interface

>

Electronic sensors 18457

>

Device type S-1 14198

Circuit diagram/wiring diagram Description Safety classification

max. SIL max. PL max. cat.

Electronic sensor

Two-channel connection (4-wire operation)

Self-testing with 2 OSSD outputs (test signals are generated by the sensor and filtered or ignored by AC422S

Examples (ifm art. no.): – GI701S – GM701S – GM705S

3 e 4

► Note the supply voltage limits of the sensor.

► Select the input circuits according to the max. safety classification (SIL / cat. / PL).

When the indicated ifm articles are used, the maximum safety classification according to the SIL/Cat./PL values listed in the table can be achieved. Note the current standards.

► If other than the indicated products are used, note the current standards.

► Test the safety function within the two-error occurrence time. The second-error occurrence time takes 24 hours. Within this time the safety function of the device should be requested once.

Page 45: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

45

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Connect devices to local I/O interface

>

Device type S-2 16192

Circuit diagram/wiring diagram Description Safety classification

max. SIL max. PL max. cat.

Electronic sensor

Two-channel connection (4-wire operation)

Self-testing with 2 OSSD outputs (test signals are generated by the sensor and filtered or ignored by AC422S

Examples (ifm art. no.): – GF711S – GG711S – GI711S – GG712S – GI712S – GG851S

2 d 4

► Note the supply voltage limits of the sensor.

► Select the input circuits according to the max. safety classification (SIL / cat. / PL).

When the indicated ifm articles are used, the maximum safety classification according to the SIL/Cat./PL values listed in the table can be achieved. Note the current standards.

► If other than the indicated products are used, note the current standards.

► Test the safety function within the two-error occurrence time. The second-error occurrence time takes 24 hours. Within this time the safety function of the device should be requested once.

Page 46: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

46

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Connect devices to local I/O interface

>

Safety light curtains 18458

>

Device type SLV-1 18449

Circuit diagram/wiring diagram Description Safety classification

max. SIL max. PL max. cat.

Safety light curtains type 2

Self-testing with 2 OSSD outputs (test signals are generated by the sensor and filtered or ignored by AC422S

Examples (ifm art. no.): – OY431S to OY440S – OY031S to OY040S – OY051S to OY060S – OY072S to OY080S – OY094S to OY100S

1 c --

► Note the supply voltage limits of the safety light curtain.

► Select the input circuits according to the max. safety classification (SIL / cat. / PL).

When the indicated ifm articles are used, the maximum safety classification according to the SIL/Cat./PL values listed in the table can be achieved. Note the current standards.

► If other than the indicated products are used, note the current standards.

► Test the safety function within the two-error occurrence time. The second-error occurrence time takes 24 hours. Within this time the safety function of the device should be requested once.

Page 47: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

47

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Connect devices to local I/O interface

>

Device type SLV-2 18450

Circuit diagram/wiring diagram Description Safety classification

max. SIL max. PL max. cat.

Safety light curtains type 4

Self-testing with 2 OSSD outputs (test signals are generated by the sensor and filtered or ignored by AC422S

Examples (ifm art. no.): – OY403S – OY405S – OY407S – OY001S to OY011S – OY041S to OY050S – OY061S to OY070S – OY082S to OY090S – OY104S to OY110S – OY441S to OY450S – OY221S to OY230S – OY204S to OY210S – OY241S to OY250S – OY261S to OY270S – OY282S to OY290S

3 e --

► Note the supply voltage limits of the safety light curtain.

► Select the input circuits according to the max. safety classification (SIL / cat. / PL).

When the indicated ifm articles are used, the maximum safety classification according to the SIL/Cat./PL values listed in the table can be achieved. Note the current standards.

► If other than the indicated products are used, note the current standards.

► Test the safety function within the two-error occurrence time. The second-error occurrence time takes 24 hours. Within this time the safety function of the device should be requested once.

Page 48: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

48

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Connect devices to local I/O interface

>

Safety light grids 18459

>

Device type SLG-1 18451

Circuit diagram/wiring diagram Description Safety classification

max. SIL max. PL max. cat.

Safety light grids type 2

Self-testing with 2 OSSD outputs (test signals are generated by the sensor and filtered or ignored by AC422S

Examples (ifm art. no.): – OY411S to OY413S – OY111S to OY113S

1 c --

► Note the supply voltage limits of the safety light grid.

► Select the input circuits according to the max. safety classification (SIL / cat. / PL).

When the indicated ifm articles are used, the maximum safety classification according to the SIL/Cat./PL values listed in the table can be achieved. Note the current standards.

► If other than the indicated products are used, note the current standards.

► Test the safety function within the two-error occurrence time. The second-error occurrence time takes 24 hours. Within this time the safety function of the device should be requested once.

Page 49: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

49

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Connect devices to local I/O interface

>

Device type SLG-2 18452

Circuit diagram/wiring diagram Description Safety classification

max. SIL max. PL max. cat.

Safety light grids type 4

Self-testing with 2 OSSD outputs (test signals are generated by the sensor and filtered or ignored by AC422S

Examples (ifm art. no.): – OY114S to OY116S – OY901S to OY903S – OY421S to OY423S – OY120S to OY122S – OY951S to OY953S

3 e --

► Note the supply voltage limits of the safety light grid.

► Select the input circuits according to the max. safety classification (SIL / cat. / PL).

When the indicated ifm articles are used, the maximum safety classification according to the SIL/Cat./PL values listed in the table can be achieved. Note the current standards.

► If other than the indicated products are used, note the current standards.

► Test the safety function within the two-error occurrence time. The second-error occurrence time takes 24 hours. Within this time the safety function of the device should be requested once.

Page 50: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

50

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Connect devices to local I/O interface

>

Output relay 18460

>

Device type AR-1 18453

Circuit diagram/wiring diagram Description Security classifications

max. SIL max. PL max. cat.

2 positively-guided relays with signal contact

2 output relays in series connection; common triggering of the relays via one output

Check-in of the signal contact via local input channel of AC422S

2 d 3

► Note the supply voltage limits of the relays.

► Select the input and output circuits according to the max. safety classification (SIL / cat. / PL).

► Test relay for correct operation once a year.

The indicated safety classifications can only be obtained with protected wiring between switch and AC422S.

► Observe current standards of the country in which the AC422S automation system is to be operated.

► Carry out suitable start-up tests.

Page 51: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

51

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Connect devices to local I/O interface

>

Device type AR-2 18454

Circuit diagram/wiring diagram Description Security classifications

max. SIL max. PL max. cat.

2 positively-guided relays with signal contact

2 output relays in series connection; Separate triggering of the relays via 2 outputs

Check-in of the signal contact via local input channel of AC422S

3 e 4

► Lay output signal cables protected against damage or test output signals.

► Note the supply voltage limits of the relays.

► Test relays for correct operation once a month.

► Select the input and output circuits according to the max. safety classification (SIL / cat. / PL).

► Observe current standards of the country in which the AC422S automation system is to be operated.

► Carry out suitable start-up tests.

Page 52: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

52

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Installation Connect devices to local I/O interface

>

4.3.4 Install safe device to local I/O interface 17700

To install a safe device to the local I/O interface:

► Observe the safety instructions. (→ Safety instructions (→ page 39))

► Disconnect AC422S.

► Place Combicon connector on local I/O interface (X4) and check connection.

► Connect safe device to the local I/O interface according to the installation instructions. >

4.3.5 Install standard device on local I/O interface. 17657

To install a standard device on local I/O interface:

► Observe the safety instructions. (→ Safety instructions (→ page 39))

► Disconnect AC422S.

► Place Combicon connector on local I/O interface (X4) and check connection.

► Connect standard device to the local I/O interface according to the installation instructions.

Page 53: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

53

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Connect devices to local I/O interface

5 Operation

Control of the graphical user interface ...................................................................................................54 Menu view...............................................................................................................................................56 Page view ...............................................................................................................................................59 Remote access .......................................................................................................................................72

14805

Page 54: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

54

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Control of the graphical user interface

>

5.1 Control of the graphical user interface 6930

Below the display is the key panel with six membrane keys. The operator controls the graphical user interface of the device with these keys. The key panel is closely linked to the navigation status bar.

Legend:

Label left function key

Navigation compass

Label right function key

Right function key

Left function key

[] arrow key

[] arrow key

[] arrow key

[] arrow key

Page 55: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

55

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Control of the graphical user interface

>

5.1.1 Function keys 7090

The two function keys allow the operator to trigger specified actions (e.g. tick a checkbox). The function of the function keys changes depending on the context.

The two text fields in the navigation status bar are associated with the function keys located directly below the display. They indicate the action that will be triggered if the function key is pressed in the current work step. If the function key is not labelled, it means that it has no function in the present situation.

Example (→ figure):

► The left function key triggers the action [Select].

► The right function key triggers the action [Back].

>

5.1.2 Arrow keys 7091

The fourarrow keys [],[], [] and [] can be used for navigation and selection.

The navigation compass shows which of the four arrow keys can be used in the respective work step.

Examples:

All arrow keys are active and will trigger a device response when pressed.

Only the arrow keys [] and [] are active and will trigger a device response when pressed.

Page 56: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

56

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Menu view

>

5.2 Menu view 6996

The menu view allows the user to select the menu page with the required control or display function.

Legend:

Info bar

Main navigation bar

Subnavigation bar 1

Subnavigation bar 2

Selected menu item (focus)

Navigation status bar with - labelling of the function keys - navigation compass

Long texts are displayed as scrolling text in the info bar.

>

5.2.1 Menu navigation 10967

The central operating elements in the menu view are the three navigation bars. They reflect the menu structure of the device software. Each navigation bar represents a menu level. The symbols in a navigation bar represent the submenus and menu items.

Rules for menu navigation:

► Use []/[] to navigate within a menu level.

> The selected symbol has the focus (= orange frame).

> If the selected symbol has a submenu, the corresponding subnavigation bar will automatically appear.

► Use [] to go one menu level down.

► Use [] to go one menu level up.

At the lowest menu level:

► Press [Select] function key to go to the page of the selected menu item (→ Page view (→ page 59)).

In the main navigation bar:

► Press [Back] function key to return to the start screen (→ Start screen (→ page 78)).

Page 57: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

57

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Menu view

>

5.2.2 Navigation aids 15830

The following screen elements help you navigate through the menu:

> The info bar shows the navigation path of the selected menu symbol.

> The navigation compass shows which navigation steps are possible from the current position.

Legend:

Info bar

Navigation path to the focused menu element: [System] > [PLC] > [Setup]

Menu element with focus

Navigation path to the focused menu element:

> >

>

Example 11770

To access the menu page containing the setting options for the device-internal PLC:

1. > Initial position when accessing the menu screen

2. ► Use [] to select the [System] menu symbol.

> The focus is on the [System] menu symbol.

> The first subnavigation bar appears.

3. ► Use [] to change to the first subnavigation barh.

> The focus is on the [Diagnosis] menu symbol.

4. ► Use [] to select the [PLC] menu symbol.

> The focus is on the [PLC] menu symbol.

> The second subnavigation bar appears.

5. ► Use [] to change to the second subnavigation bar.

> The focus is on the [Information] menu symbol.

Page 58: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

58

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Menu view

6. ► Use [] to select the [Setup] menu symbol.

> The focus is on the [Setup] menu symbol.

► Press the [Select] function key to go to the page view of the [Setup] menu item.

> The page shows the setting options for the device-internal PLC.

Page 59: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

59

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Page view

>

5.3 Page view 7959

The page view allows the user to select and execute a requested function.

Legend:

Info bar

Main navigation bar

Page

Scroll bar

Tab menu

Page element with focus

Navigation status bar with - labelling of function keys - navigation compass

>

5.3.1 Navigate on a page 15831

The page contains elements, that allow the operator to control the device or access information.

For page navigation, the following basic rules apply:

► Use the arrow keys []/[] to change between the different page elements.

> The selected element is marked (= orange frame).

► Use the [Back] function key to return to the tab menu / menu view.

Rules for using the different control elements: → Description of the control elements (→ page 60)

>

5.3.2 Use navigation aids 14838

The following aids offer navigation users additional orientation:

> The info bar shows detailed information about the selected element (focus).

Long texts are displayed as scrolling text in the info bar.

> The active menu symbol in the main navigation bar has a dark background.

> A scroll bar appears on the right side of the screen if the elements do not fit on the page.

> The navigation compass shows the navigation options in the active work step.

> The text fields in the navigation status bar show the current assignment of the function keys.

Page 60: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

60

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Page view

>

5.3.3 Description of the control elements

Tab menu/Tab ........................................................................................................................................61 Button .....................................................................................................................................................62 Checkbox ................................................................................................................................................62 List ..........................................................................................................................................................63 Slave selector .........................................................................................................................................64 Confirmation message ............................................................................................................................69 Numerical field ........................................................................................................................................70 Binary field ..............................................................................................................................................71

7013

A page consists of different control elements.

Page 61: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

61

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Page view

>

Tab menu/Tab 8737

A tab menu groups together the different functions of a menu page. A tab menu consists of at least two tabs. A tab combines related functions.

Example:

> The focused tab has an orange background

> The info bar displays the name of the active tab (in this example: Errors / slave).

> The symbols and indicate that there are more tabs on the left and right sides of the visible tab.

> The page shows the control elements that belong to the currently selected tab.

Tabs can have the following background colours:

= Tab has the focus

= Tab is active

= Tab is inactive

Use:

1 Select the menu item

► Go to the menu item with the tab menu.

> The tab menu appears.

> The focus is on the left-hand tab.

2 Select a tab

► Use [] / [] arrow key to select the desired tab.

> The focus (orange background) moves to the selected tab:

> The page shows the functions of the selected tab.

3 Activate the menu page

► Press [Select] function key to go to the page that belongs to the active tab.

> When going to the page, the tab menu remains visible.

> The background colour of the active tab turns grey.

4 Carry out the desired functions

► Use [] to select and execute the desired function.

5 Change to tab menu

► Press [Back] function key to change to the tab menu.

> The focus (orange background) moves to the active tab.

Page 62: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

62

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Page view

>

Button 14196

A button allows the operator to carry out a specified action once. The caption on the button describes the action.

Example:

Use:

1 Select a button

► Use the arrow keys [] / [] to select a button.

> The selected button gets an orange frame:

2 Activate the button

► Use [Select] function key to activate the selected button.

> The function is executed. >

Checkbox 7038

A checkbox permits the user to activate/deactivate a parameter. A checkbox control element consists of a checkbox and a caption.

Example:

Use:

1 Select a checkbox

► Use arrow key [] / [] to select the checkbox

> The focus (orange frame) moves to the selected checkbox

OR:

2 Check/uncheck a checkbox

► Use function key [Select] to check/uncheck the selected checkbox.

> The status change is indicated:

= checkbox is checked OR:

= checkbox is unchecked

The setting or clearing of a checkbox is not always immediately effective. Often the change must be confirmed by clicking a button (e.g. [Accept selection])!

Page 63: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

63

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Page view

>

List 7042

A list provides a set of defined values. The operator can select precisely one value from this set (= 1 of n selection).

Examples:

= list without caption

= list with caption

Use:

1 Select a list

► Use arrow key [] / [] to select the list.

> The focus (orange frame) moves to the selected list.

> The list shows the active value: (in this exampleGateway).

2 Activate the list

► Use function key [Select] to open the list.

> The opened list shows the selectable values.

3 Select a value

► Use arrow key [] / [] to select the desired value from the list.

> The background colour of the selected value turns orange.

4 Apply the selected value

► Use function key [Select] to apply the selected value. OR: Use function key [Back] to quit and close the list.

> The list shows the selected value.

The set value will not always become effective immediately. Often the change must be confirmed by clicking a button (e.g. [Accept selection])!

Page 64: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

64

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Page view

>

Slave selector

Overview of slave states .........................................................................................................................65 Overview of free slave addresses ..........................................................................................................67

7018

The slave selector is used to select an AS-i slave or an AS-i address.

Legend:

Indicator of AS-i master operating mode

AS-i address symbol

Highlighted AS-i address (focus)

Status message of highlighted AS-i address

> The status LED indicates the active operating mode of the AS-i master: = AS-i master in protected mode = AS-i master in projection mode

> Every field represents an AS-i address. An AS-i address can be occupied by: – a single slave symbol – an A/B slave pair symbol

> The row and column headers help to locate the AS-i address. Example: address of the field selected in the picture – row header: 1x (= tens digit of the AS-i address)

– column header: 8 (= units digit of the AS-i address)

– type of slave: single slave (= symbol fully occupies the address field) – resulting AS-i address: 18

> The symbol of the A/B slave pair appears when an A or B slave is used on this address.

The slave selector is used in the following overviews:

Overview of slave states (→ Overview of slave states (→ page 65))

Overview of free slave addresses (→ Overview of free slave addresses (→ page 67))

Page 65: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

65

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Page view

>

Overview of slave states 6992

> The slave selector shows an overview of the slaves in the selected AS-i network.

> The symbol colour signals the slave status. Meaning of symbols and colours: → Slave status: colour code + symbols (→ page 66)

> The text field displays the status of the selected AS-i slave. Possible status messages: - Slave active

- Not projected (= configuration error)

- Double address (= double address error)

- Periphery (= periphery fault)

Use:

1 Select an AS-i slave

► Use the arrow keys [], [], [] and [] to select the desired AS-i slave.

> The focus (= orange frame) is on the selected AS-i slave.

> The info bar shows the address of the selected AS-i slave.

> The text field shows a status message about the selected AS-i slave.

2 Activate the selected AS-i slave

► Use function key [Select] to activate the selected AS-i slave and go to the next menu page. OR: Use function key [Back] to cancel and leave the slave selector.

Page 66: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

66

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Page view

>

Slave status: colour code + symbols 11236

Single slave A/B slave Colour Meaning

grey No slave found: slave address is neither in the LPS nor in the LDS

green Slave is activated ( in LAS)

red Configuration error type 1: – slave is projected (in LPS) but was not found (in LDS)

yellow Slave signals a peripheral fault

pink Several slaves have the same address (double address error)

grey red Configuration error type 2: – the found slave (in LDS) is not projected (in LPS) – the found slave has another profile than projected

>

Meaning of the colour combinations (example: configuration error type 2) 11237

Symbol Colour Meaning

grey red grey

Configuration error type 2: – Single slave is projected (in LPS) but was not found (in LDS). – Instead, a new A slave with the same address was installed.

grey grey red

Configuration error type 2: – Single slave is projected (in LPS) but was not found (in LDS). – Instead, a new B slave with the same address was installed.

grey red Configuration error type 2: – A or B slave is projected (in LPS) but was not found (in LDS). – Instead, a new single slave with the same address was installed.

Page 67: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

67

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Page view

>

Overview of free slave addresses 6993

In this overview, the slave selector shows the free and occupied AS-i addresses.

> The symbol colour indicates the state of the AS-i address. Meaning of symbols and colours: → Free slave addresses: colour code + symbols (→ page 68)

> The text field displays the status of the selected AS-i slave. Possible status messages: - Free

- Missing slave

Use:

1 Select the AS-i address

► Use the arrow keys [], [], [] and [] to select the desired AS-i address.

> The focus (= orange frame) is on the selected AS-i address.

> The info bar displays the selected AS-i address.

> The text field shows a status message for the selected AS-i address.

2 Activate the selected AS-i address

► Use [Select] function key to activate the selected AS-i address and go to the next menu page. OR: Use [Back] function key to cancel and leave the slave selector.

Page 68: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

68

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Page view

>

Free slave addresses: colour code + symbols 11239

Single slave A/B slave Colour Meaning Prio.

grey Slave address is already used. --

turquoise Address is free according to LDS (= no slave found), however: address already belongs to a stored projection (= application profile).

1

blue Address is free according to LDS (= no slave found). Address is not used in a stored projection (= application profile).

2

>

Meaning of the colour combinations 11240

Symbol Colour Meaning

blue blue

Slave to be addressed is an A/B slave: A and B addresses are free.

blue grey

Slave to be addressed is an A/B slave: – A address is free. – B address is used.

grey blue

Slave to be addressed is an A/B slave: – Address is used. – B address is free.

turquoise turquoise

Slave to be addressed is an A/B slave: A and B addresses are free, but already used in a stored projection.

turquoise grey

Slave to be addressed is an A/B slave: – Address is free, but already used in a stored projection. – B address is used.

grey turquoise

Slave to be addressed is an A/B slave: – Address is used. – Address is free, but already used in a stored projection.

turquoise blue

Slave to be addressed is an A/B slave: – Address is free, but already used in a stored projection. – B address is free.

blue turquoise

Slave to be addressed is an A/B slave: – A address is free – Address is free, but already used in a stored projection.

Page 69: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

69

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Page view

>

Confirmation message 7033

The confirmation message is a security prompt. It appears when important changes are made to the system settings. The confirmation message shows the changes made. For the changes to become effective, they first need to be acknowledged by the operator.

Example:

> Action: Change AS-i slave address from 1a to 1b

> Confirmation message shows: – Action (= Change AS-i address)

– Slave address prior to change – Slave address after change

> The operator has the following input options: – function key [Select] – function key [Back]

Use:

1 Change the settings

► Change the system settings.

> The confirmation message appears.

2 Confirm the message

► Use function key [Select] to confirm the changes and apply the new value. OR: Use function key [Back] to reject the changes and continue to use the old value.

> The page displays the valid settings.

Page 70: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

70

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Page view

>

Numerical field 7046

The numerical field allows the operator to enter integer values. The value range is context-specific. Numerical fields are part of the following GUI elements:

Control element Example Meaning

IP address

Entry of an IP address (IPv4) in [w.x.y.z] format – w | x | y | z = network segments (value range: 0... 255)

Date

Date entry in [yyyy-mm-ss] format – yyyy = year (value range: 0000 ... 9999) – mm = month (value range: 01 ... 12) – dd = day (value range: 01 ... 31)

Time

Time entry in [hh:mm:ss] format – hh = hours (value range: 00 ... 12) – mm = minutes (value range: 00 .... 59) – ss = seconds (value range: 00 ... 59)

The numerical field for seconds (ss) cannot be edited!

Analogue value

Entry of an analogue output value Value range (per numerical field): 0 ... 9

Use (using the example of the numerical date field):

1 Select a numerical field

► Use arrow key [] / [] to select the date control element.

> The focus (= orange frame) is on the selected date control element.

> The date control element displays the current date

2 Activate the editing mode

► Press function key [Select] to enter the editing mode.

> The focus (orange frame) is on the right element

3 Set the desired value

► Use arrow key [] / [] to increment the desired value.

> The segment displays the new value.

Press and hold the arrow key [] / [] to rapidly move through larger value ranges.

4 Select the next segment

► Use the arrow key [] / [] to mark the segment to be edited.

> The focus (orange frame) moves to the marked segment

► Optional: Repeat steps 3 and 4 until all segments have the desired values.

Page 71: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

71

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Page view

5 Adopt the set values

► Use [Select] function key to confirm the set values and to leave the edit mode. OR: Use [Back] function key to reset the set values and to leave the edit mode.

> The date control element displays the valid date

The set value will not always become effective immediately. Often the change must be confirmed by clicking a button (e.g. [Accept selection])!

>

Binary field 7047

The binary field allows the operator to change a digital value bit-wise.

Example:

> Display of the 4-bit digital value:

Binary representation

= bit is on (= 1).

= bit is off (= 0).

Hexadecimal representation: 0xf = 1111

Use:

1 Select the binary field

► Use [] / [] arrow keyt o select the binary field.

> The focus (orange frame) is on the selected binary field.

> The control element shows the current value (digital and hexadecimal).

2 Activate the editing mode

► Press [Select] function key to enter the editing mode.

> The focus (orange frame) is on the right element.

3 Set the desired value

► Use [] / [] arrow key to set the desired value.

> The control element shows the new value in digital and hexadecimal format.

4 Select the next segment

► Use [] / [] arrow key to mark the segment to be edited.

> The focus (orange frame) is on the selected segment.

► Optional: Repeat steps 3 and 4 until all segments have the desired values.

5 Apply the set values

► Use [Select] function key to confirm the set values and to leave the edit mode. OR: Use [Back] function key to reset the set values and to leave the edit mode.

> The binary field displays the current value (binary and hexadecimal).

Page 72: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

72

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Remote access

>

5.4 Remote access

General ...................................................................................................................................................73 Recommended browsers ........................................................................................................................73 Operating instructions .............................................................................................................................74

7068

The device has an integrated web server. It generates a web interface which allows remote access to all device functions via an web browser. The web-interface allows the operator to easily configure, parameterise and monitor the device in permanent operation via an ethernet-based network.

Page 73: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

73

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Remote access

>

5.4.1 General 7069

The operating concept of the web interface follows the same philosophy as the operating concept of the local display. The web interface uses the same menu items, the same menu structure and the same symbols as the graphic user interface of the local display. >

Additional functions 14181

The web interface provides the following extra features compared to the user interface of the display:

Download Electronic Data Sheet (EDS) (→ Download the device and I/O description (→ page 127))

Download I/O description (→ Download the device and I/O description (→ page 127))

Adopt date and time settings of the PC/laptop (→ Adopt the system time of the PC (→ page 115))

Save diagnostics protocol (→ Store diagnostic protocol (→ page 118))

Use ifm system solutions (→ ifm-Systemlösungen (→ page 147))

>

5.4.2 Recommended browsers 7070

Use one of the following Internet browsers to correctly display the HTML pages of the web interface:

Microsoft Internet Explorer (from version 8.0)

Mozilla Firefox (from version 3.5)

Page 74: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

74

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Remote access

>

5.4.3 Operating instructions

Web interface: Access 10283

► PC / Laptop / mobile device: Start Internet browser.

► Internet browser: Enter IP address of the device in the address line (e.g. 192.168.82.2)

> Internet browser displays the start page of the web interface. >

Web interface: Navigation 14193

In the web interface, the pointing device (e.g. mouse, touchpad) is used instead of the following key functions:

Navigation functions of the arrow keys [], [], [], []

Selecting functiions of the function keys [Select] and [Back]

Example:

To select > :

► Place the cursor on symbol [AS-i 1] in the main navigation bar.

> symbol [AS-i 1] has the focus.

> Subnavigation bar appears.

> Navigation trail shows actual position in the menu tree: AS-i 1

► Place the cursor on symbol [Diagnosis] in the subnavigation bar.

> symbol [Diagnosis] has the focus.

> Navigation trail shows actual position in the menu tree: AS-i 1 > Diagnosis

► Click on symbol [Diagnosis]

> Web browser shows menu page [Diagnosis]

Page 75: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

75

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Remote access

>

Web interface: Password protection 14187

The web server has a basic password protection to prevent unwanted or unauthorised changes to the device settings via the web interface.

When the web interface is accessed, a status bar at the top shows if the user is logged in or logged out:

User is logged in: - Full access to device settings - Full access to diagnostics and information data

User is logged out: - No access to device settings - Access to diagnostics and information data

The password is: CAFE

The password protection cannot be deactivated!

The password cannot be changed!

>

Web interface login 14221

► Go to the web interface (→ Operating instructions (→ page 74)).

> At the top of the web interface, the status bar displays the following status message:

► Enter the fixed password in the [Password:] field.

► Click [Login] to log in to the web interface.

> The status bar displays the changed status:

> The operator has unlimited access to all menus and functions of the web interface.

The operator remains logged in if one of the following actions is carried out:

the web browser is closed and reopened

the PC/laptop is restarted

AC422S is restarted

To prevent unauthorised access to the device settings:

► Manually log off before you leave the web interface! (→ Disconnect from web interface (→ page 76))

► Remember to turn off the "Save password" function of your web browser before accessing the web interface!

► If the "Save password" function of your web browser is not turned off: delete the stored passwords in your browser settings!

Page 76: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

76

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Operation Remote access

>

Disconnect from web interface 14276

To log out of the web interface:

► Start web interface

> Status line with status message is displayed at the top of the web interface:

► Log out of the web interface by clicking [Logout]

> Status bar shows changed status

> User can only access menus in the web interface containing diagnostic and information data.

> An error message is displayed when a user in the web interface accesses a menu with device settings.

The user stays logged into the web interface even when the web browser is closed and then restarted.

To prevent unauthorised access to the device settings:

► After finishing the access via the web browser manually log out of the device web interface!

► When passwort memory function of the web browser is not deactivated: Delete all saved passwords in the browser settings!

Page 77: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

77

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Remote access

6 Menu

Start screen ............................................................................................................................................78 Quick setup .............................................................................................................................................79 AS-i 1 / AS-i 2 .........................................................................................................................................89 System ..................................................................................................................................................100 Interfaces ..............................................................................................................................................120 Safety ....................................................................................................................................................136 ifm system solutions .............................................................................................................................147

18788

This chapter describes the menu functions of the device’s graphical user interface.

Page 78: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

78

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Start screen

>

6.1 Start screen 14439

When starting the device, the start screen of the graphical user interface appears (special case: system start after initial commissioning or firmware update: → Start screen 'Basic settings' (→ page 154)). The start screen displays the status information of important system components. Moreover, the graphical user interface is accessed and operated from the start screen.

AS-i master 1 operation mode

= Protected mode

= Projection mode

AS-i master 2 operation mode → AS-i master 1 operation mode

Control instance of the AS-i slave outputs

= Manual with PLC

= Gateway with PLC

= PLC

Status of the EtherNet/IP connection

=active

=inactive

► Press [Menu] function key to go to the menu (→ Menu functions (→ page 79))

OR:

► Press [OSC] function key to go to the Online Support Center (→ Online Support Centre (OSC) (→ page 162))

Page 79: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

79

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Quick setup

>

6.2 Quick setup 7273

The [Quick setup] menu provides fast access to the most important device functions.

Navigation path Functions

→ Quick setup: Project AS-i networks (→ page 80) → Quick setup: Configure the operating mode of the AS-i masters (→ page 81) → Quick setup: Configure the output access (→ page 82) → Quick setup: Access the device via QR code (→ page 82) → Quick setup: configure the EtherNet/IP interface (→ page 83) → Quick setup: Set the configuration mode (→ page 84) → Quick setup: Set the configuration interface (→ page 85) → Quick setup: Address the AS-i slaves connected to AS-i master 1 (→ page 87) → Quick setup: Address the AS-i slaves connected to AS-i master 2 (→ page 88)

Page 80: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

80

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Quick setup

>

6.2.1 Quick setup: Project AS-i networks 8973

During projection adaptation, the AS-i master carries out the following actions:

The configuration data of all detected AS-i slaves (LDS) is saved

The detected AS-i slaves are added to the list of projected slaves (LPS)

To carry out the projection adaptation on AS-i master 1 and/or AS-i master 2:

1 Select the menu page

► Select [Project all] tab.

2 Select the AS-i master for projection adaptation

► Set the following parameters as required:

Parameter Meaning Possible values

[AS-i master 1] Select AS-i master 1 for projection adaptation

= Exclude AS-i master 1 from projection adaptation

= Include AS-i master 1 in projection adaptation

[AS-i master 2] Select AS-i master 2 for projection adaptation

(only available for devices with 2 AS-i masters)

= Exclude AS-i master 2 from projection adaptation

= Include AS-i master 2 in projection adaptation

3 Start the projection adaptation

► Press [Start projection process].

> The selected AS-i masters go into "projection mode".

> A projection adaptation is carried out on the selected AS-i masters.

> After the projection adaptation, the selected AS-i masters go into "protected mode".

Page 81: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

81

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Quick setup

>

6.2.2 Quick setup: Configure the operating mode of the AS-i masters 8974

Information regarding the operating modes of an AS-i master:→ Operating modes of the AS-i master (→ page 177)

To configure the operating modes of the AS-i masters:

1 Select the menu page

► Select [Operation modes] tab.

2 Configure the operating mode of AS-i master 1 and the behaviour of the connected AS-i slaves

> In group [AS-i master 1] , set the following parameters as required:

Parameter Meaning Possible values

[Projection mode] Active operating mode of the AS-i master

= Projection mode inactive: AS-i network runs in protected mode (normal mode)

= Projection mode active: AS-i network can be projected. (→ Quick setup: Address the AS-i slaves connected to AS-i master 1 (→ page 87) or → Quick setup: Address the AS-i slaves connected to AS-i master 2 (→ page 88))

[No slave reset] Behaviour of the AS-i slaves when changing the operating mode

= Slave is reset when changing the operating mode: When changing the operating mode, the AS-i slaves will be reset for a short moment (reset or offline phase).

= Slave is not reset when changing the operating mode: When changing the operating mode, the AS-i slaves continue to operate without interruption.

> Selected values are applied.

3 Optional: set the operating mode of AS-i master 2 and the behaviour of the AS-i slaves

► Repeat step 2 for the group [AS-i master 2].

Page 82: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

82

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Quick setup

>

6.2.3 Quick setup: Configure the output access 17867

Only one control instance at a time can have write access to the outputs of the connected AS-i slaves. The operator configures the control instance with the parameter [Output access].

To configure the control instance of the AS-i slave outputs:

1 Select the menu page

► Select [Operation modes] tab.

2 Set the control instance for the outputs of the AS-i slaves

► From the list [Output access], select the desired value:

Parameter Meaning Possible values

[Output access] Control instance of the AS-i slave outputs

Gateway = A higher-level PLC controls the outputs of the AS-i slaves.

Manual = The operator controls the outputs of the AS-i slaves via the graphical user interface.

PLC = The device-internal PLC controls the outputs of the AS-i slaves.

3 Save the changes

► Press [Accept selection] to save the changes.

> The selected instance controls the outputs of the AS-i slaves. >

6.2.4 Quick setup: Access the device via QR code 11764

The QR code (Quick Response Code) allows the operator to access the web interface of the device from a smartphone or tablet PC.

Requirements:

The AS-i device must be connected to a wireless LAN router with switch functionality. (→ Connection via Ethernet network (→ page 175))

The smartphone/tablet PC is connected to the wireless LAN router.

The smartphone/tablet PC provides a camera function.

The smartphone/tablet PC has a QR-code reader installed.

1 Select menu page

► Select the [QR-Code] tab.

> The display shows the QR code.

2 Read the QR code

► Start the QR code reading app and scan the QR code.

> The smartphone displays the web interface of the device (→ Remote access (→ page 72)).

Page 83: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

83

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Quick setup

>

6.2.5 Quick setup: Configure the EtherNet/IP interface 12131

The device provides the following options for configuration of the EtherNet/IP interface:

Manual = The operator sets the interface parameters (IP address, network mask, gateway address) manually.

Automatic = The interface parameters are automatically set through one of the following protocols.

– Dynamic Host Configuration Protocol (DHCP) – Bootstrap Protocol (BOOTP)

In order to obtain the interface parameters automatically via DHCP or BOOTP, the device must be connected to a DHCP or BOOTP server.

► Enable the DHCP/BOOTP server on the fieldbus controller.

► Connect the EtherNet/IP interface (X6/X7) to a DHCP/BOOTP server.

To configure the IP parameters of the EtherNet/IP interface:

1 Select the menu page

► Select [EtherNet/IP] tab.

2 Display the current settings

> The parameters below show the active settings:

Parameter Meaning Possible values

[IP mode] active configuration method Static = The operator sets the IP parameters manually.

DHCP = The interface receives the IP parameters from a DHCP server.

BOOTP = The interface receives the IP parameters from a BOOTP server.

[IP address] IP address of the interface e.g. 192.168.10.100

[Subnet mask] Network mask of the network segment

e.g. 255.255.255.0

[Gateway address] IP address of the network gateway

e.g. 192.168.10.1

► Select one of the following actions: – Configure the IP parameters manually: continue with → step 3 – Configure the IP parameters automatically: continue with → step 4

3 Configure the IP parameters manually

► From the list [IP mode], select the value Static.

► Set the following parameters as required: – [IP address] – [Subnet mask] – [Gateway address]

► Press [Accept] to save the changes.

► Continue with → step 5

Page 84: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

84

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Quick setup

4 Configure the IP parameters automatically

► From the list [IP mode], select either DHCP or BOOTP.

► Press [Accept] to save the changes.

> The device receives the IP parameters from a DHCP or BOOTP server.

The automatic configuration of the interface can take up to 10 seconds.

5 Display the current settings

> The parameters (→ step 2) show the active IP settings of the EtherNet/IP interface. >

6.2.6 Quick setup: Set the configuration mode 12236

The device can be configured in two different ways:

Top-down mode: The device-specific parameters and the module configuration are set via the projection software of the EtherNet/IP controller.

Independent mode: The parameters of the EtherNet/IP interface are set via the graphical user interface of the device.

More information: → configuration mode (→ page 371)

1 Select the menu page

► Select [EtherNet/IP] tab.

2 Set the configuration mode

► Set the following parameters as required:

Parameter Meaning Possible values

[Configuration mode] Active configuration mode of the device

Top-Down = The device-specific parameters and the module configuration are set via the projection software of the EtherNet/IP controller.

Independent = The parameters of the EtherNet/IP interface are set via the graphical user interface of the device.

3 Save the changes

► Press [Accept selection] to save the changes.

> The selected instance controls the outputs of the AS-i slaves.

Page 85: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

85

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Quick setup

>

6.2.7 Quick setup: Set the configuration interface 8991

The device provides the following options for configuration of the EtherNet configuration interface:

Manual = The operator sets the interface parameters (IP address, network mask, gateway address) manually.

Automatic = The interface parameters are set automatically. The operator can choose between these protocols:

– Dynamic Host Configuration Protocol (DHCP) – Zero Configuration Networking (Zeroconf)

The device must be connected to a DHCP server to automatically receive the interface parameters via DHCP.

► Connect the configuration interface (X3) to a DHCP server.

To configure the IP parameters of the configuration interface:

1 Select the menu page

► Select [Configuration interface] tab.

2 Show the active settings

> The parameters below show the active settings:

Parameter Meaning Possible values

[Optain IP address autom.]

Active method for the configuration of the interface parameters

= Manual assignment of the interface parameters through the operator

= Automatic assignment of the interface parameters

[IP status] Configuration protocol used Static = The operator sets the IP parameters manually.

DHCP = The IP parameters are set by a DHCP server.

Zeroconf = The IP parameters are set automatically with the Zeroconf protocol.

[IP address] IP address of the interface e.g. 192.168.0.100

[Subnet mask] Network mask of the network segment

e.g. 255.255.255.0

[Gateway address] IP address of the network gateway

e.g. 192.168.0.1

► Take one of the following actions: – Configure the IP parameters manually: continue with → step 3 – Configure the IP parameters automatically: continue with → step 4

3 Configure the IP parameters manually

► Uncheck [Optain IP address autom.].

► Set the following parameters as required: – [IP address]

Page 86: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

86

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Quick setup

– [Subnet mask] – [Gateway address]

► Press [Accept] to save the changes.

► Continue with → step 5

4 Configure the IP parameters automatically

► Check [Optain IP address autom.].

► Press [Accept] to save the changes.

> The device tries to obtain IP parameters from a DHCP server.

> If the IP parameter configuration via DHCP server fails, the device will generate the IP parameters by means of the Zeroconf protocol.

The automatic configuration of the interface takes approx. 10 seconds.

5 Show the current settings

> The parameters (→ step 2) show the active IP settings of the configuration interface.

Page 87: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

87

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Quick setup

>

6.2.8 Quick setup: Address the AS-i slaves connected to AS-i master 1 8992

To change the address of an AS-i slave connected to AS-i master 1:

1 Select the menu page

► Select [Addressing AS-i 1] tab.

2 Select the AS-i slave

> The page provides an overview of the current addressing and status of the AS-i slaves on the selected AS-i master (→ figure) Notes on colour codes: → Overview of slave states (→ page 65)

► Select the AS-i slave of which want to change the address.

► Use [Select] to activate the selected AS-i slave.

3 Select a new AS-i address

> The page provides an overview of the free AS-i addresses (→ figure) Notes on colour codes: → Overview of free slave addresses (→ page 67)

► Select the address to be assigned to the AS-i slave.

► Assign the selected address with [Select].

> The confirmation prompt appears.

► Confirm the message with [OK].

> The AS-i slave has new address.

> The page provides an overview of the current addressing and configuration errors (→ figure)

4 Address additional AS-i slaves (optional)

► Repeat steps 2 and 3 to address additional AS-i slaves.

After the address change, the present configuration no longer corresponds to the stored configuration.

> The slave status indicates a configuration error.

To eliminate the configuration error:

► Start a projection adaptation (→ Quick setup: Project AS-i networks (→ page 80)).

Page 88: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

88

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Quick setup

>

6.2.9 Quick setup: Address the AS-i slaves connected to AS-i master 2 11671

To change the address of an AS-i slave connected to AS-i master 2

1 Select the menu page

► Select [Addressing AS-i 2] tab.

2 Change the AS-i slave address

The procedure for addressing the AS-i slaves connected to AS-i master 2 is the same as for addressing the AS-i slaves connected to AS-i master 1 (→ Quick setup: address the AS-i slaves connected to AS-i master 1 (→ page 87)).

Page 89: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

89

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu AS-i 1 / AS-i 2

>

6.3 AS-i 1 / AS-i 2 15912

The [AS-i 1] / [AS-i 2] menus provide access to configuration and diagnosis functions of the AS-i network components.

Navigation path Content

>

>

AS-i master settings → Set the operating mode of the AS-i master (→ page 90) → Carry out a projection adaptation (→ page 91) → Set the monitoring functions of the AS-i master (→ page 91)

>

>

AS-i network diagnosis → Display and reset the error counters (→ page 92) → Display the error statistics of the AS-i slaves (→ page 92) → Display the voltage supply analysis (→ page 93) → Display and reset performance data (→ page 93)

>

>

AS-i slave settings → Display the input/output data of the AS-i slave (→ page 94) → Change the digital output values manually (→ page 96) → Change the analogue output values manually (→ page 96) → Show AS-i slave information (→ page 97) → Change an AS-i slave address (→ page 98) → Change an AS-i slave parameter output (→ page 98) → Change the Extended ID1 of the AS-i slave (→ page 99)

Page 90: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

90

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu AS-i 1 / AS-i 2

>

6.3.1 AS-i 1 / AS-i 2: Master setup 8996

The menu item [Master setup] provides access to the configuration options of the selected AS-i master. >

Set the operating mode of the AS-i master 15877

More information on the operating modes of the AS-i master: → Operating modes of the AS-i master (→ page 177)

To set the operating mode of the AS-i master:

1 Select the menu page

► > or >

2 Set the operating mode of AS-i master 1 and the behaviour of the connected AS-i slaves

> Set the following parameters as required:

Parameter Meaning Possible values

[Projection mode] Active operating mode of the AS-i master

= Projection mode inactive: AS-i network operates in protected mode (normal mode)

= Projection mode active: AS-i network can be projected.

[No slave reset] Behaviour of the AS-i slaves when changing the operating mode

= Slave is reset when changing the operating mode: When changing the operating mode, the AS-i slaves will be reset for a short moment (reset or offline phase).

= Slave is not reset when changing the operating mode: When changing the operating mode, the AS-i slaves continue to operate without interruption.

> Selected values are applied.

Page 91: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

91

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu AS-i 1 / AS-i 2

>

Carry out a projection adaptation 8938

During projection adaptation, the AS-i master stores the configuration of all AS-i slaves currently found on the AS-i network in its memory and assigns a valid AS-i address to each of them.

The projection adaptation can only be carried out in projection mode:

► [Projection mode] must be checked (→ Set the operating mode of the AS-i master (→ page 90)).

To launch the projection adaptation:

1 Select the menu page

► > or >

2 Carry out a projection adaptation

► Press [Start projection process] button.

> The projection adaptation is carried out.

If successful:

> All slaves on the AS-i master are projected.

If not successful:

> The Online Support Center displays an error message.

► Remove the error and repeat the process. >

Set the monitoring functions of the AS-i master 11728

To set the monitoring functions of the selected AS-i master:

1 Select the menu page

► > or >

2 Set the monitoring functions of the AS-i master

► Set the following parameters as required:

Parameter Meaning Possible values

[Automatic addressing] Behaviour if AS-i slave is replaced

= New AS-i slave obtains the next free address

= The new AS-i slave obtains the same address as the old AS-i slave if the following conditions are met: – The new AS-i slave has the address 0. – The old and the new AS-i slave have the same slave profile.

[Earth fault detection] Detection of earth faults = Do not detect earth faults in the AS-i system

= Detect earth faults in the AS-i system

[Double address detection]

Double address detection = Do not detect AS-i slaves with the same address

= Detect AS-i slaves with the same address

> Selected values are applied.

Page 92: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

92

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu AS-i 1 / AS-i 2

>

6.3.2 AS-i 1 / AS-i 2: Diagnosis 9039

The [Diagnosis] menu provides access to the diagnostic data of the selected AS-i network. >

Display and reset the error counters 9042

To display and reset the AS-i error counters:

1 Select the menu page

► > or >

► Select [Error counters] tab.

2 Display the error counters

> Page shows the following information:

Designation Meaning

Telegrams Number of message errors that occurred

Configuration Number of configuration errors that occurred

Voltage < 22,5V Number of voltage errors < 22.5 V

Voltage < 19,0V Number of voltage errors < 19.0 V

Earth fault Number of detected earth faults

3 Optional: reset the error counters

► Press [Reset] button.

> All error counters are reset to 0. >

Display the error statistics of the AS-i slaves 9087

To display the error messages of the AS-i slaves on the selected AS-i master:

1 Select the menu page

► > or >

► Select [Errors / slave] tab.

2 Display the error statistics of the AS-i slaves

> Page shows the following information:

Column header Meaning

Adress Address of the AS-i slave

S/A Number of errors of the single or A slave at this address

B Number of errors of the B slave at this address

► Use [] / [] to scroll through the table.

Page 93: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

93

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu AS-i 1 / AS-i 2

>

Display the voltage supply analysis 9088

To display the voltage supply analysis:

1 Select the menu page

► > or >

► Select [Power supply] tab.

2 Display the voltage supply analysis

> Page shows the following information:

Designation Meaning Possible values

Power supply Method of voltage supply Aux = Voltage is supplied separately by the AS-i network and AUX 24 V.

AS-i = Voltage is only supplied by the AS-i network.

Power24 = Voltage is supplied by data decoupling module.

AS-i voltage AS-i voltage measured (in [V]) e.g. 30.3 V

DC earth fault Evaluation of the network symmetry =

AS-i network is symmetrical

= AS-i network is asymmetrical

= AS-i network has earth fault

Graphical representation of the network symmetry:

>

Display and reset performance data 9089

To display the performance statistics of the selected AS-i master:

1 Select the menu page

► > or >

► Select [Performance] tab.

2 Display performance data

> Page shows the following information:

Designation Meaning

Activated slaves Number of active AS-i slaves on the AS-i network

AS-i cycle time [ms] AS-i cycle time (value in [ms])

minimum shortest cycle time

maximum longest cycle time

current current cycle time

3 Optional: reset the performance data

► Press [Reset] button.

> The saved statistic data for minimum and maximum cycle times are deleted.

Page 94: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

94

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu AS-i 1 / AS-i 2

>

6.3.3 AS-i 1 / AS-i 2: AS-i slaves 9037

The [AS-i Slaves] menu provides access to information and configuration options of the AS-i slaves.

The scope of configuration options shown ([Data] and [Setup] tab) varies according to the status of the selected AS-i slaves.

>

Display the input/output data of the AS-i slave 10934

To display the input/output data or the parameter output of the selected AS-i slaves:

1 Select the menu page

► > or >

► Select an AS-i slave (→ Slave selector (→ page 64)).

► Select [Data] tab.

2 Display input/output data

> Depending on the profile of the selected AS-i slave, the page displays the following data: >

Digital input 15972

Designation Meaning Example / Possible values

[Inputs] Current values of the digital inputs (binary and hexadecimal representation)

= Data bit is switched off (0 / OFF)

= Data bit is switched on (1 / ON)

>

Analogue input 15973

Designation Meaning Example / Possible values

[Inputs] Current values of the analogue input channels and information about their status

[Valid] The Valid bit indicates whether the displayed value is valid.

= Invalid value

= Valid value

[Overflow] The Overflow bit indicates whether the displayed value is within the value range.

= Value within valid value range

= Valid value range exceeded

>

Page 95: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

95

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu AS-i 1 / AS-i 2

Digital output 15974

Designation Meaning Example / Possible values

[Outputs] Current values of the digital outputs (binary and hexadecimal representation)

= Data bit is switched off (0 / OFF)

= Data bit is switched on (1 / ON)

[Jog mode] The parameter controls the behaviour of the outputs in the event of a changed output value.

= Jog mode disabled ("switch mode")

> The changes do not affect the output until you quit the editing mode.

= Jog mode enabled ("momentary switch mode")

> The changes immediately affect the output.

>

Analogue output 15975

Designation Meaning Example / Possible values

[Outputs] Current values of the analogue output channels and information about their status

[Analogue status]

Current status of the analogue outputs

= Not O.K.

= O.K.

[Channel x] Current value of the analogue output channel x (x = 1...n; n = number of channels per AS-i slave)

per digit: 0 ... 9

>

Parameter input 15843

Designation Meaning Example / Possible values

[Parameter input] Current value of the parameter input (binary and hexadecimal representation)

= Data bit is switched off (0 / OFF)

= Data bit is switched on (1 / ON)

>

Page 96: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

96

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu AS-i 1 / AS-i 2

Change the digital output values manually 10939

WARNING

Risk of personal injury! Risk of material damage to the machine/plant!

The operator is responsible for any consequences caused by the manual change of the digital ouput values!

► Secure the concerned area.

► Only trained personnel is allowed to set outputs manually.

If the jog mode is deactivated: After changing the slave outputs the output values remain on the changed values.

► Change the inverted outputs again immediately to the original values after the end of the test!

To change the digital output values of an AS-i slave manually:

1 Enable manual access to the outputs

► Set parameter [Output access] = Manual (→ Set output access (→ page 108)).

2 Select the menu page

► > or >

► Select an AS-i slave (→ Slave selector (→ page 64)).

► Select [Data] tab.

3 Set the digital output values manually

> The group [Outputs] displays the current value of the digital output (binary and hexadecimal representation).

► [Jog mode] to be set as required. (→ Digital output (→ page 95))

► Change the desired output value bit by bit.

> Selected value is applied. >

Change the analogue output values manually 10940

To change the analogue output values of an AS-i slave manually:

1 Enable manual access to the outputs

► Parameter [Output access] = set to Manual (→ Set output access (→ page 108)).

2 Select the menu page

► > or >

► Select an AS-i slave (→ Slave selector (→ page 64)).

► Select [Data] tab.

3 Set the analogue output values manually

> [Outputs] group shows the current value of the analogue output.

► Change the value of the requested channel one digit at a time (→ Numerical field (→ page 70)).

> Selected value is applied.

► Optional: repeat step 3 to change further channels.

Page 97: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

97

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu AS-i 1 / AS-i 2

>

Show AS-i slave information 10935

To display information about an AS-i slave:

1 Select the menu page

► > or >

► Select an AS-i slave (→ Slave selector (→ page 64)).

► Select [Information] tab.

2 Display information about the AS-i slave

> Page shows the following information:

Designation Meaning Possible values

[AS-i Slave address] Current address of the AS-i slave e.g. 13B

[Slave status] Current status of the AS-i slave = AS-i slave is active

= AS-i slave is missing

= Not projected

= Double address error

= Periphery fault

[AS-i slave profile] Current (= Current) and expected (= Preset) slave profile (IO, ID, ID2, ID1) in hexadecimal format

► Use [] / [] for page navigation.

Page 98: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

98

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu AS-i 1 / AS-i 2

>

Change an AS-i slave address 10944

To change the address of an AS-i slave:

1 Select the menu page

► > or >

► Select an AS-i slave (→ Slave selector (→ page 64)).

► Select [Setup] tab.

2 Change the address of the AS-i slave

► Press the [Change slave address] button.

> The page displays an overview of the free AS-i addresses (→ Overview of free slave addresses (→ page 67)).

► Select the address to be assigned to the AS-i slave and confirm with [Select] function key.

> Security prompt appears.

► Press [OK] to confirm the security prompt.

> The AS-i slave has a new address.

> The page displays an overview of the AS-i slave states (→ Overview of slave states (→ page 65)).

3 Optional: change further AS-i addresses.

► Repeat step 2 to change further AS-i slave addresses.

After the address change, the present configuration (LDS) no longer corresponds to the stored configuration (LPS).

> The OSC displays a configuration error.

To remove the configuration error:

► start a projection adaptation (→ Carry out a projection adaptation (→ page 91)).

>

Change an AS-i slave parameter output 10945

To change the parameter output of an AS-i slave:

1 Enable manual access to the outputs

► Set [Output access] = Manual (→ Set output access (→ page 108))

2 Select the menu page

► > or >

► Select an AS-i slave (→ Slave selector (→ page 64)).

► Select [Setup] tab.

3 Change the parameter output of the AS-i slave

> The group [Parameter output] displays the current assignment of the parameter output (binary and hexadecimal representation).

► Adjust the desired output value one position at a time.

> Selected value is applied.

Page 99: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

99

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu AS-i 1 / AS-i 2

>

Change the Extended ID1 of the AS-i slave 10952

To set the Extended ID1 of an AS-i slave:

1 Select the menu page

► > or >

► Select an AS-i slave (→ Slave selector (→ page 64)).

► Select [Setup] tab.

2 Set the Extended ID1

> The list [ID1] displays the current Extended ID1 value (hexadecimal format).

► Select the desired value for Extended ID1 from the list [ID1].

> Selected value is applied.

After changing the Extended ID1, the existing configuration no longer corresponds to the stored configuration:

> An error message appears (configuration error).

► Start a projection adaptation (→ Carry out a projection adaptation (→ page 91)).

Page 100: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

100

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

6.4 System 10979

The [System] menu provides access to functions that allow configuration of the system and the device-internal standard PLC.

Navigation path Functions

>

Device-internal standard PLC → System: Programmable Logic Controller (PLC) (→ page 101)

>

System information → Show version information (→ page 107)

>

System settings → Set output access (→ page 108) → Set the device cycle (→ page 109) → Switch the menu language (→ page 110) → Set the behaviour of the display (→ page 111) → Set the system time manually (→ page 113) → Synchronise the system time with an NTP server (→ page 114) → Adopt the system time of the PC (→ page 115) → Gerätekonfiguration speichern (→ page 116) → Restore the device configuration (→ page 117) → Store diagnostic protocol (→ page 118)

>

System diagnostics → Display diagnostic data (→ page 119)

Page 101: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

101

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

6.4.1 System: Programmable Logic Controller (PLC) 8955

The [PLC] menu provides access to the device-internal standard PLC.

Navigation path Functions

> >

standard PLC information: → Display the status of the CODESYS standard PLC (→ page 102) → Display information about standard PLC projects (→ page 102)

> >

standard PLC settings → Control a single standard PLC application (→ page 103) → Control standard PLC applications (→ page 104) → Show target visualisation (→ page 105)

> >

standard PLC diagnosis → Show memory used (→ page 106)

For information about the programming of the device-internal standard PLC with CODESYS, please refer to the programming manual: → www.ifm.com > Select country > [Data sheet search] > (Article no.) > [Operating instructions]

Page 102: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

102

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

PLC: Information 11778

The [Information] menu item provides access to the standard PLC status and project information. >

Display the status of the CODESYS standard PLC 14841

To display information about the current status of the device-internal standard PLC:

1 Select the menu page

► > >

► Select [Status] tab.

2 Display the status of the CODESYS standard PLC

> Page shows the following information:

Designation Meaning Possible values

Status LED Status of the device-internal standard PLC

= The CODESYS standard PLC is disabled.

= The CODESYS standard PLC is enabled.

[Version] CODESYS version e.g. 3.5.3.60

[Node name] Name of device in CODESYS project e.g.

>

Display information about standard PLC projects 14842

To obtain information about the CODESYS project stored on the device-internal standard PLC:

1 Select the menu page

► > >

► Select [Project] tab.

2 Display information about standard PLC projects

> Page shows the following information:

Designation Meaning

[Project] Name of the CODESYS project file

[Title] Name of the CODESYS project

[Version] Version number of the CODESYS project

[Author] Author of the CODESYS project

Page 103: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

103

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

PLC: Settings 16217

The [Settings] menu item provides access to the standard PLC applications (apps) on the device. >

Control a single standard PLC application 14846

[App x/y]

– x ... number of the app displayed – y ... total number of apps stored

Status and name of the application

= application has been stopped

= application has been started

Information concerning the application – date and time of creation – author – version of application – size

To control a single standard PLC application stored on the device:

1 Select the menu page

► > >

► Select [Applications] tab.

2 Select an application

► Use [] to select the message field.

> The focus (orange frame) is on the message field.

► Use [] / [] to select the requested application.

► Perform one of the following actions: – Launch a single standard PLC application: continue with → step 3 – Stop a single standard PLC application: continue with → step 4

3 Launch a single PLC application

► Press [Start] to launch the selected standard PLC application.

> The confirmation prompt appears.

► Press [OK] to confirm the prompt.

> The standard PLC application is started.

► Continue with → step 5

4 Stop a single standard PLC application

► Press [Stop] to stop the selected application.

> The confirmation prompt appears.

► Press [OK] to confirm the prompt.

> The application is stopped.

5 Display information about the standard PLC application

> The status display of the standard PLC application is updated

Page 104: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

104

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

Control standard PLC applications 14847

To control all standard PLC applications stored on the device:

1 Select the menu page

► > >

► Select [All applications] tab.

2 Display status information about the standard PLC applications

> Page shows the following information:

Designation Meaning

[Total] Number of applications stored on the device

[Started] Number of applications running

► Perform one of the following actions: – Launch all standard PLC applications: continue with → step 3 – Stop all standard PLC applications: continue with → step 4 – Reset all standard PLC applications: continue with → step 5

3 Launch all standard PLC applications

► Press [Start] button.

> The confirmation prompt appears.

► Press [OK] to confirm the prompt.

> All standard PLC applications are started.

► Continue with → step 6

4 Stop all standard PLC applications

► Press [Stop] button.

> The confirmation prompt appears

► Press [OK] to confirm the prompt.

> All standard PLC applications are stopped.

► Continue with → step 6

5 Reset all standard PLC applications

► Press [Reset] button.

> The confirmation prompt appears.

► Press [OK] to confirm the prompt.

> All standard PLC applications are reset and stopped.

6 Display the status of the standard PLC applications

> The page shows updated information about the stored standard PLC applications.

> The status of the [Start], [Stop] and [Reset] buttons is updated.

Page 105: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

105

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

Show target visualisation 9055

Using the CODESYS programming system, the user can optionally program a target visualisation to create an application-specific user interface for the display of AC422S. The target visualisation is loaded onto the device together with the CODESYS project, but it must be activated manually.

If no valid target visualisation is stored on the device, a green screen appears after activating the [Activate Target-Visu] button

To exit the target visualisation and return to the menu page:

► Press [] and [] simultaneously.

If the device does not react when entering [] + [], the key combination is deactivated.

► Activate the key combination using the system command "Show target visualisation" (→ Command 272 (0x0110) – Display target visualisation (→ page 303))!

To activate the target visualisation:

1 Select menu page

► > >

► Select the [Activate TargetVisu] tab.

2 Start the target visualisation

► Press [Activate Target-Visu] button.

> The confirmation message appears.

► Press [OK] button to confirm the message.

> The display shows the target visualisation.

Page 106: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

106

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

PLC: Diagnosis 10936

The [Diagnosis] menu item provides access to diagnostic data of the device-internal standard PLC. >

Show memory used 14845

To display information about the memory capacity currently used:

1 Select the menu page

► > >

► Select [Memory] tab.

2 Show memory used

> Page shows the following information:

Designation Meaning

CODESYS Memory capacity occupied by CODESYS data (in Kbytes)

free Free memory (in Kbytes)

The current usage of memory space is read out once when calling up the menu page. These values are not refreshed while the menu page is displayed. Any changes regarding the memory capacity (e.g. through download of a new CODESYS project) will therefore not be reflected in the displayed values.

To update the displayed values:

► Quit the [Diagnosis] menu page.

► Access the [Diagnosis] menu page again.

> The menu page displays the current memory usage of device.

Page 107: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

107

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

6.4.2 System: Information 7281

The [Information] menu item provides access to the version information about the system components. >

Show version information 11774

To display information about the hardware and software components of the device:

1 Select the menu page

► >

► Select [Version] tab.

2 Show version information

> Page shows the following information:

Designation Meaning Possible values

[Type] Article number of the device e.g. AC422S

[SN] Serial number of the device e.g. 000000113034

[Build] Version number of the installed firmware e.g. 4.0.2

[HW version] Version number of the device main board e.g. AA

Page 108: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

108

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

6.4.3 System: Setup 7274

The [Setup] menu item provides access to the configuration options of the system. >

Set output access 18627

To set the control instance for the outputs of the AS-i slaves:

1 Select the menu page

► >

► Select [System settings] tab.

2 Set the control instance for the outputs of the AS-i slaves

► Select the required value from the [Output access] list:

Parameter Meaning Possible values

[Output access] Control instance for the outputs of the AS-i slaves

Gateway = A higher-level PLC controls the outputs of the AS-i slaves.

Manual = The operator controls the outputs of the AS-i slaves via the graphical user interface.

PLC = The device-internal standard PLC controls the outputs of the AS-i slaves.

3 Save the changes

► Press [Accept selection] button to save the changes.

> The selected instance controls the outputs of the AS-i slaves.

The outputs of the safe AS-i slaves are always controlled by the failsafe PLC of the AC422S!

Page 109: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

109

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

Set the device cycle 8571

NOTICE

Risk of material damage to the machine/plant!

A device cycle that is too short can have undesirable effects on the correct transmission of the process and control data between the PLC and peripheral devices (higher-level PLC, AS-i slaves).

► Ensure a sufficiently long cycle time!

To set the device cycle:

1 Select the menu page

► >

► Select [System settings] tab.

2 Set the device cycle

► Folgende Parameter wie gewünscht einstellen:

Parameter Meaning Possible values

[Device cycle] Active → device cycle 1,5 ms = 1,5 milliseconds

2,0 ms = 2,0 milliseconds

2,5 ms = 2,5 milliseconds

3,0 ms = 3,0 milliseconds

3 Save the changes

► Press [Accept selection] aktivieren.

> Selected value is applied.

Page 110: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

110

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

Switch the menu language 7088

To select the language of the GUI texts:

1 Select the menu page

► >

► Select [System settings] tab.

2 Select the menu language

> The list [Language] shows the active language in which the GUI texts are displayed.

► Set the following parameters as required:

Parameter Meaning Possible values

[Language] Language in which the GUI texts are displayed

Deutsch = German

English = English

Français = French

Español = Spanish

Italiano = Italian

Português = Portuguese

3 Save the changes

► Press [Accept selection].

> GUI elements are displayed in the requested language. >

Optional: switch the language with a key combination 15834

The languages available on the device are saved in an ordered list:

German

English

French

Spanish

Italian

Portuguese

To switch the language with a key combination (from the active language):

► Press [] + [] to select the previous language in the list.

OR:

► Press [] + [] to select the next language in the list.

> GUI elements are displayed in the requested language.

The key combination allows you to change the language from any menu page.

Page 111: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

111

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

Set the behaviour of the display 9107

To set the display behaviour (screen saver, behaviour in case of inactivity):

1 Select the menu page

► >

► Select [System settings] tab.

2 Set the behaviour of the display

► Set the following parameters as required:

Parameter Meaning Possible values

[Screen saver] Status of the screen saver = Screen saver is inactive: Display remains permanently switched on.

= Screen saver is active: Display is switched off after 10 minutes of inactivity.

[Return to start screen] Display behaviour in case of extended period of user inactivity

= The currently selected menu page stays on the screen.

= When the set time has elapsed, the display automatically changes to the start screen.

> Selected values are applied.

Page 112: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

112

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

Set the system time 10954

The system time consists of date and time. The device provides the following options for setting the system time:

Manual: The operator sets the date and time manually.

Via NTP server: The device has an NTP client. The system time can be synchronised with an NTP server.

Apply the system time of a PC/laptop:

The device adopts the system time of a PC/laptop (only available via the web interface of the device)

To set the system time:

1 Select the menu page

► >

► Select [Clock] tab.

2 Display the current system time settings

> The following parameters display the current system time settings:

Parameter Meaning Possible values

[Activate NTP] = NTP client is deactivated: Device adopts the manually set values for [Time] and [Date].

= NTP client is not active: From an NTP server, the device adopts the values for [Time] and [Date].

Status LED Status of NTP client and synchronisation with NTP server

NTP not active = NTP client is deactivated: Applicable are the manually set values for [Time] and [Date].

NTP waiting = NTP client is active: Device waits for messages from NTP server.

NTP successful = NTP client is active: Time synchronisation with NTP server was successful.

[Time] System time (format [hh:mm:ss])

e.g. 12:23:56

[Date] System date (format [yyyy-mm-dd])

e.g. 2014-04-23

3 Select the configuration method

► Select one of the following: – Set the system time manually (→ page 113) – Synchronise the system time with an NTP server (→ page 114) – Adopt the system time of the PC (→ page 115)

Page 113: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

113

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

Set the system time manually 10963

To set the system time manually:

1 Select the menu page

► >

► Select [Clock] tab.

2 Deactivate the NTP client of the device

► Uncheck [Activate NTP] (→ Set the system time (→ page 112)).

► Press [Accept selection].

> The changes become effective.

> NTP status: NTP not active

3 Set the system time manually

► [Time] and [Date] must be set (Operating notes: → Numerical field (→ page 70))

> Selected values are applied.

Seconds cannot be changed manually. When leaving the edit mode, the seconds will be automatically set to 0.

Page 114: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

114

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

Synchronise the system time with an NTP server 10969

To synchronise the system time with an NTP server:

To synchronise the system time and date via Network Time Protocol (NTP), connect the configuration interface of the device to an NTP server directly or over a network.

1 Select the menu page

► >

► Select [Clock] tab.

2 Deactivate the NTP client

► Uncheck [Activate NTP] (→ Set the system time (→ page 112)).

> The IP address field and the [NTP-Offset] list can be edited.

3 Set the IP address of the NTP server and NTP offset

► Set the following parameters as required:

Parameter Meaning Possible values

IP address field IP address of the NTP server e.g. 192.168.0.100

List [NTP-Offset]

(optional)

Time zone of the NTP server in UTC (Universal Coordinated Time).

no offset = System time is taken from NTP server without offset

UTC -12:00 ...

UTC +12:00

Adopt time zones according to UTC division (displayed number of hours will be added/subtracted)

► Press [Accept selection].

> The device tries to synchronise the system time with the NTP server.

> NTP status: NTP waiting

In case of a successful synchronisation:

> NTP status: NTP successful

> [Time] and [Date] show the synchronised values.

In case of a failed synchronisation:

► Check the settings of the IP parameters of the configuration interface.

► Check the IP address of the NTP server.

► Repeat the process.

Page 115: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

115

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

Adopt the system time of the PC 15756

This function can only be executed via the web interface of the device.

To adopt the date and time of a PC/laptop:

1 Go to the web interface of the device

► Connect the PC/laptop to the configuration interface (X3) of the device.

► Start the web browser and access the web interface of the device.

2 Select the menu page

► >

► Select the [Clock] tab.

3 Adopt the system time of the PC/laptop

► Uncheck [Activate NTP] (→ Set the system time (→ page 112)).

► In group [Apply Time and Date from the PC] press [OK].

> The device applies the date and time of the PC/laptop.

> [Date] and [Time] display the system time.

Page 116: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

116

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

Clone device configuration 7276

AC422S makes it possible to create an image of the current device configuration, to transfer it to another device and activate there (clone). The export/import of the configuration file is made via an SD card.

A device configuration consists of the following settings:

System settings

AS-i 1/AS-i 2 settings

EtherNet/IP settings

standard PLC applications (incl. PLC task configuration and variables)

This function is only available via the local user interface of AC422S.

The safe PLC application (incl. safety PLC-task configuration, safety-code sequences and variables) is not part of the device configuration.

Cloning a device configuration is only possible if the following conditions are met.

Source and target device have the same firmware version.

Source and target device have the same article number.

>

Save the device configuration 16199

Pay attention to the notes (→ Clone device configuration (→ page 116))!

To save the currently valid device configuration on an SD card:

1 Select the menu page

► >

> Select [Configuration] tab.

2 Save the device configuration

► Insert an SD card with sufficient free space in the SD card slot.

► Press [Export Configuration].

> The device stores the currently valid device configuration on the SD card.

Page 117: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

117

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

Restore the device configuration 16200

NOTICE

Risk of data loss and undesirable system behaviour!

If the import of the device configuration is interrupted (e.g. because the device is disconnected from the electric circuit), not all the configuration data will saved on the device.

► Do not interrupt the recovery process!

► Ensure a stable voltage supply!

Pay attention to the notes (→ Clone device configuration (→ page 116))!

If there are more than one device configurations stored in the root directory of the SD card, then the newest file (time stamp) will be used for the restoring process.

To transfer a stored device configuration to the device:

1 Select the menu page

► >

► Select [Configuration] tab.

2 Restore the device configuration

► Insert an SD card with the stored device configuration in the SD card slot.

► Press [Import configuration] button.

> A warning message appears.

► Use [OK] to confirm the message.

> The device configuration is loaded and saved onto the device.

> The device reboots.

Page 118: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

118

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

Store diagnostic protocol 7040

Using the diagnostic protocol, the user can archive the current device configuration or provide all relevant information to the service staff via the device settings.

The diagnostic protocol contains the following information in the selected user language:

AS-i configuration

EtherNet/IP configuration

System settings

CODESYS information

OSC history

This function is only available via the web-interface of the device (→ Remote access (→ page 72)).

Requirements:

► Connect the device with PC/laptop (→ Configuration interface: connection concepts (→ page 173)).

► Start the web browser and open the web interface of the device (→ Recommended browsers (→ page 73)).

1 Select menu page

► >

► Select the [Diagnostic protocol] tab.

2 Store diagnostic protocol

► Press the [Generate diagnostic protocol] button.

> AC422S generates diagnostic protocol.

> The progress bar indicates the status of the process.

> A dialogue window appears.

► Select file name and memory location and press [OK] to confirm.

> The diagnostic protocol is stored as an HTML file at the selected location.

Page 119: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

119

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu System

>

6.4.4 System: Diagnosis 9053:

The [Diagnosis] menu item provides access to the diagnostic data of the device. >

Display diagnostic data 15827

To display the diagnostic data of the device:

1 Select the menu page

► >

2 Display the diagnostic data

> Page shows the following information:

Designation Meaning Possible values

Operating time [YY-DDD HH:MM]

Operating time of system and components

All times indicated in [YY-DDD-HH:MM] format:

YY = years DDD = days HH = hours MM = minutes

total Operating time of device

current Operating time of device since last system start

LCD Operating time of LCD

PLC Operating time of controller

Temperature Current device temperature Indications in [°C] (→ Note)

Power supply Voltage supply of device Aux = Voltage is supplied separately by AS-i network and AUX 24 V.

AS-i = Voltage is only supplied by the AS-i network.

Power module = Voltage is supplied by data decoupling module.

The temperature monitoring of AC422S continuously checks whether the system temperature exceeds the maximum permissible values. If certain limit values are exceeded, the temperature monitoring generates warnings or error messages which are displayed in the → Online Support Centre (OSC) (→ page 162).

The following temperature ranges apply:

Normal zone (0 °C ... 80 °C): no warnings, no error messages

Transitional zone (80.1 °C ... 85 °C): warnings

Critical zone: (> 85.1 °C): error messages

Page 120: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

120

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Interfaces

>

6.5 Interfaces 15143

The [Interfaces] menu provides access to the configuration options of the device's interfaces.

Navigation path Functions

>

Configuration interface → Configure the IP parameters manually (→ page 122) → Configure the IP parameters automatically (→ page 122) → Show EtherNet information (→ page 123)

>

EtherNet/IP interface → Interfaces: EtherNet/IP interface (→ page 124)

Page 121: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

121

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Interfaces

>

6.5.1 Interfaces: Configuration interface 7279

The [Configuration interface] menu provides access to the settings of the EtherNet configuration interface (port X3). >

Notes on IP settings 14856

The device provides the following options for configuration of the Ethernet configuration interface:

Manual = The operator sets the interface parameters (IP address, network mask, gateway address) manually.

Automatic = The interface parameters are set automatically. The operator can choose between these protocols:

– Dynamic Host Configuration Protocol (DHCP) – Zero Configuration Networking (Zeroconf)

To display the current configuration method and the active IP parameters of the configuration interface:

1 Select the menu page

► >

► Select [IP setup] tab.

2 Show the active settings

> The parameters below show the active settings:

Parameter Meaning Possible values

[Optain IP address autom.]

Active method for the configuration of the interface parameters

= Manual assignment of interface parameters through operator

= Automatic assignment of interface parameters

[IP status] Configuration protocol used Static = The operator sets the IP parameters manually.

DHCP = The IP parameters are set by a DHCP server.

Zeroconf = The IP parameters are set automatically with the Zeroconf protocol.

[IP address] IP address of the interface e.g. 192.168.0.100

[Subnet mask] Network mask of the network segment

e.g. 255.255.255.0

[Gateway address] IP address of the network gateway

e.g. 192.168.0.1

► Select one of the following options: – Configure the IP parameters manually (→ page 122) – Configure the IP parameters automatically (→ page 122)

Page 122: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

122

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Interfaces

>

Configure the IP parameters manually 14860

To configure the IP parameters of the configuration interface manually:

1 Select the menu page

► >

► Select [IP setup] tab.

2 Deactivate the NTP client

► Uncheck [Optain IP address autom.] (→ Notes on IP settings (→ page 121)).

> The IP address fields [IP address], [Subnet mask] and [Gateway address] can be edited.

3 Configure the IP parameters

► Configure the following parameters as required (→ Notes on IP settings (→ page 121)): – [IP address] – [Subnet mask] – [Gateway address]

4 Save the changes

► Press [Accept] button.

> Selected values are applied.

> [IP status] displays the active configuration method: Static >

Configure the IP parameters automatically 14859

The device must be connected to a DHCP server to automatically receive the interface parameters via DHCP.

► Connect the configuration interface (X3) to a DHCP server.

To configure the IP parameters of the configuration interface automatically:

1 Select the menu page

► >

► Select [IP setup] tab.

2 Enable the NTP client

► Activate the [Optain IP address autom.] check box (→ Notes on IP settings (→ page 121))

3 Save the changes

► Press [Accept] button.

> The device tries to obtain the IP parameters from a DHCP server.

> If the configuration of IP parameters via DHCP server fails, the device will generate the IP parameters with the Zeroconf protocol.

> [IP address], [Subnet mask] and [Gateway address] display the set IP parameters.

> Selected values are applied.

> [IP status] displays the active configuration method: DHCP or Zeroconf.

The automatic configuration of the IP parameters takes approx. 10 seconds.

>

Page 123: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

123

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Interfaces

Show EtherNet information 14857

To show Ethernet information regarding the configuration interface:

1 Select the menu page

► >

► Select [Ethernet informationen] tab.

2 Show Ethernet information

> The page shows the following information:

Designation Meaning

[MAC ID] MAC identification number of the interface

Page 124: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

124

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Interfaces

>

6.5.2 Interfaces: EtherNet/IP interface 16197

The [EtherNet/IP] menu provides access to information, settings and diagnostic data of the EtherNet/IP interface.

Navigation path Functions

> >

EtherNet/IP information → Show information (→ page 125) → Display EtherNet/IP data (→ page 126) → Display the module configuration (→ page 126) → Download the device and I/O description (→ page 127)

> >

EtherNet/IP settings → Configure the IP parameters manually (→ page 129) → Configure the IP parameters automatically (→ page 129) → Set the configuration mode (→ page 130) → Set the device-specific parameters (→ page 131) → Set the EtherNet/IP module configuration (→ page 133)

> >

EtherNet/IP diagnosis → Display diagnostic data (→ page 135)

Page 125: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

125

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Interfaces

>

EtherNet/IP: Information 11781

The menu item [Information] provides access to information regarding the EtherNet/IP interface. >

Show information 12166

To display information about the EtherNet/IP interface:

1 Select the menu page

► > >

► Select [Information] tab.

2 Show information about the EtherNet/IP interface

> Page shows the following information:

Designation Meaning

[Manufacturer ID] Displays the manufacturer ID

[Unit type] Displays the device type

[Product code] Displays the product code

[Revision no.] Displays the revision number

[SN] Displays the serial number

[Product name] Displays the product name

Page 126: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

126

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Interfaces

>

Display EtherNet/IP data 12168

To display the EtherNet/IP data:

1 Select the menu page

► > >

► Select [Data] tab.

2 Display EtherNet/IP data

> Page shows the following information:

Designation Meaning Possible values

[MAC-ID] MAC ID of the EtherNet/IP interface e.g. 00:02:01:01:27:CF

[RPI Zeit] RPI time in milliseconds [ms] (RPI = Requested Packet Interval)

[Analog. channels/O-slave]

Number of analogue channels per input slave

→ Set the device-specific parameters (→ page 131)

[Analog. channels/O-slave]

Number of analogue channels per output slave

→ Set the device-specific parameters (→ page 131)

[Failsafe state] Behaviour of the AS-i outputs in case of an interrupted EtherNet/IP connection

→ Set the device-specific parameters (→ page 131)

[Parameter download] The AS-i slave parameters are transferred when a EtherNet/IP connection is established.

Parameter can only be configured via the projection software!

= Parameters are not downloaded, i.e. the AS-i slaves are activated using the parameters that are set in the device.

= Each time a EtherNet/IP connection is established, the AS-i slave parameters are loaded from the EtherNet/IP controller to the device, activated in the slaves and stored non-volatilely.

[Change byte order] Byte order in a data word

The set parameter value applies to all attached tables.

→ Set the device-specific parameters (→ page 131)

>

Display the module configuration 12193

To display the current module configuration:

1 Select the menu page

► > > .

► Select [Module configuration] tab.

2 Display the module configuration

> The page shows the active configuration of the EtherNet/IP slots. (Meaning of parameter values:→ Set the EtherNet/IP module configuration (→ page 133))

Page 127: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

127

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Interfaces

>

Download the device and I/O description 12194

This function is only available via the web-interface of the device (→ Remote access (→ page 72)).

Requirements:

► Connect the device with PC/laptop (→ Configuration interface: connection concepts (→ page 173)).

► Start the web browser and open the web interface of the device (→ Recommended browsers (→ page 73)).

1 Select the menu page

► > >

► Select [File download] tab.

> The menu screen [File download] appears.

2 Download the EDS file and the description of the inputs and outputs.

► Click the link [Download EDS-Datei] to download the device description.

► Click the button [Download I/O Description file].

> The web server creates a description file of the inputs and outputs.

► Save the created file.

Page 128: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

128

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Interfaces

>

EtherNet/IP: Setup 16196

The [Setup] menu item provides access to the configuration options of the EtherNet/IP interface. >

Notes on IP settings 12228

The device provides the following options for configuration of the EtherNet/IP interface:

Manual = The operator sets the interface parameters (IP address, network mask, gateway address) manually.

Automatic = The interface parameters are automatically set through one of the following protocols.

– Dynamic Host Configuration Protocol (DHCP) – Bootstrap Protocol (BOOTP)

To display the current configuration method for IP parameters of the EtherNet/IP interface:

1 Select the menu page

► > >

► Select [Fieldbus] tab.

2 Display the current configuration method for IP parameters

> The [IP mode] list shows the active configuration method:

- Static = The operator sets the IP parameters manually.

- DHCP = The device receives the IP parameters from a DHCP server.

- BOOTP = The device receives the IP parameters from a BOOTP server.

3 Display the current IP parameters of the EtherNet/IP interface

> The following parameters show the current IP settings of the EtherNet/IP interface:

Designation Meaning

[IP address] IP address of the configuration interface

[Subnet mask] Subnet mask of the network segment

[Gateway address] IP address of the EtherNet gateway

Page 129: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

129

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Interfaces

>

Configure the IP parameters manually 15883

To manually configure the IP parameters of the EtherNet/IP interface:

1 Select the menu page

► > >

► Select [Fieldbus] tab.

2 Activate the manual configuration

► From the list [IP mode], select the value Static (→ Notes on IP settings (→ page 128)).

> The IP address fields [IP address], [Subnet mask] and [Gateway address] can be edited.

3 Set the IP parameters of the EtherNet/IP interface

► Set the following parameters as required: – [IP address] – [Subnet mask] – [Gateway address]

4 Save the changes

► Press [Accept] button.

> Selected values are applied. >

Configure the IP parameters automatically 15881

In order to obtain the interface parameters automatically via DHCP or BOOTP, the device must be connected to a DHCP or BOOTP server.

► Connect the EtherNet/IP interfaces (X6/X7) to a DHCP/BOOTP server.

1 Select the menu page

► > >

► Select [Fieldbus] tab.

2 Select the configuration method

► From the list [IP mode], select either DHCP or BOOTP.

3 Save the changes

► Press [Accept] button.

> The device receives the IP parameters from a DHCP or BOOTP server.

> Selected value is applied.

> [IP address], [Subnet mask] and [Gateway address] show the current values.

Page 130: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

130

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Interfaces

>

Set the configuration mode 15884

More information: → configuration mode (→ page 371)

To set the configuration mode of the device:

1 Select the menu page

► > >

► Select [Fieldbus] tab.

2 Select the configuration method for the EtherNet/IP parameters

> Set the following parameter as required:

Parameter Meaning Possible values

[configuration mode] Active configuration mode of the device

Top-Down = The device-specific parameters and the module configuration are set via the projection software of the EtherNet/IP controller.

Independent = The parameters of the EtherNet/IP interface are set via the graphical user interface of the device.

3 Save the changes

► Press [Accept].

> Selected value is applied.

Page 131: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

131

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Interfaces

>

Set the device-specific parameters 15909

The parameters can only be changed if the configuration mode is set to Independent (→ Set the configuration mode (→ page 130)).

To set the device-specific parameters: set the number of channels to be transmitted per analogue input slave:

1 Select the menu page

► > >

► Select [Parameter] tab.

2 Set the number of analogue channels per input slave

► Set the following parameter as required:

Parameter Meaning Possible values

[Analog. channels/I-slave] Number of analogue channels transmitted per input slave

1 channel per A/B = 1 channel per A/B slave OR: channels 1 + 3 per single slave

1 channel = 1 channel per single slave OR: 1 channel per A slave

2 channels = 2 channels per single slave OR: 2 channels per A slave

4 channels = 4 channels per single slave OR: 2 channels per A/B slave

3 Set the number of analogue channels per output slave

► Set the following parameter as required:

Parameter Meaning Possible values

[Analog. channels/O-slave]

Number of analogue channels transmitted per output slave

1 channel per A/B = 1 channel per A/B slave OR: channels 1 + 3 per single slave

1 channel = 1 channel per single slave OR: 1 channel per A slave

2 channels = 2 channels per single slave OR: 2 channels per A slave

4 channels = 4 channels per single slave OR: 2 channels per A/B slave

Page 132: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

132

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Interfaces

4 Set the failsafe state

► Set the following parameter as required:

Parameter Meaning Possible values

[Failsafe state] Behaviour of the slave outputs in case of an interrupted EtherNet/IP connection

Hold outputs = The outputs hold the values which were present immediately before the connection was interrupted.

Output reset = The outputs are reset to their initial values.

5 Set the byte order of a word

► Set the following parameter as required:

Parameter Meaning Possible values

[Change byte order] Byte order in a data word = Byte order remains unchanged.

= Byte order is inverted.

6 Save the changes

► Press [Accept].

> Selected values are applied.

Page 133: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

133

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Interfaces

>

Set the EtherNet/IP module configuration 12230

NOTICE

Risk of data loss!

For the transmission of cyclic process data between the device and the EtherNet/IP PLC, a limited number of data words is available for each direction of transmission:

Input data (= modules 1, 3, 5, 7, 9, 10, 13, 14): 248 words

Output data (= modules 2, 4, 6, 8, 11, 12, 15): 248 words

If the EtherNet/IP modules have been parameterised in such a way that the cyclic input and output data comprise more than 248 words per direction of transmission, any data from the 249th word will not be transmitted and will therefore be lost.

► Parameterise the EtherNet/IP modules in a way to ensure that the input and output data do not exceed the maximum number of words to be transmitted!

The EtherNet/IP modules can only be configured on the device if the configuration mode is set to Independent (→ Set the configuration mode (→ page 130)).

To define which cyclic process data are to be transmitted in the EtherNet/IP slots:

1 Select the menu page

► > >

► Select [Module configuration] tab.

2 Set the EtherNet/IP slots for the digital inputs and outputs of the AS-i slaves

> Set the following parameters as required:

Parameter Meaning Possible values

[EtherNet/IP Slot 1] Digital inputs of the S/A slaves connected to AS-i master 1

→ Slot 1 – Digital input data single or A slaves, AS-i master 1 (→ page 223)

[EtherNet/IP Slot 2] Digital outputs of the S/A slaves connected to AS-i master 1

→ Slot 2 – Digital output data single or A slaves, AS-i master 1 (→ page 223)

[EtherNet/IP Slot 3] Digital inputs of the S/A slaves connected to AS-i master 2 (only devices with 2 AS-i masters)

→ Slot 3 – Digital input data single or A slaves, AS-i master 2 (→ page 224)

[EtherNet/IP Slot 4] Digital outputs of the S/A slaves connected to AS-i master 2 (only devices with 2 AS-i masters)

→ Slot 4 – Digital output data single or A slaves, AS-i master 2 (→ page 224)

[EtherNet/IP Slot 5] Digital inputs of the B slaves connected to AS-i master 1

→ Slot 5 – Digital input data B slaves, AS-i master 1 (→ page 225)

[EtherNet/IP Slot 6] Digital outputs of the B slaves connected to AS-i master 1

→ Slot 6 – Digital output data B slaves, AS-i master 1 (→ page 225)

[EtherNet/IP Slot 7] Digital inputs of the B slaves connected to AS-i master 2 (only devices with 2 AS-i masters)

→ Slot 7 – Digital input data B slaves, AS-i master 2 (→ page 226)

[EtherNet/IP Slot 8] Digital outputs of the B slaves connected to AS-i master 2 (only devices with 2 AS-i masters)

→ Slot 8 – Digital output data B slaves, AS-i master 2 (→ page 226)

Page 134: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

134

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Interfaces

3 Set the EtherNet/IP slots for the analogue inputs and outputs of the AS-i slaves

► Set the following parameters as required:

Parameter Meaning Possible values

[EtherNet/IP Slot 9] Analogue inputs, area 1 → Slot 9 – Analogue input data (→ page 229)

[EtherNet/IP Slot 10] Analogue inputs, area 2 → Slot 10 – Analogue input data (→ page 230)

[EtherNet/IP Slot 11] Analogue outputs, area 1 → Slot 11 – Analogue output data (→ page 231)

[EtherNet/IP Slot 12] Analogue outputs, area 2 → Slot 12 – Analogue output data (→ page 232)

What data is transmitted in each word depends on the set values of the parameters [Analog. channels/I-Slave] and [Analog. channels/O-Slave]. → Set the device-specific parameters (→ page 131)

4 Configure the EtherNet/IP slot for diagnostic data

► Set the following parameters as required:

Parameter Meaning Possible values

[EtherNet/IP Slot 13] Diagnostic data transmitted to the fieldbus controller

→ Slot 13 – Diagnostic data (→ page 237)

5 Set the EtherNet/IP slots for the data between the EtherNet/IP controller and the device-internal PLC

► Set the following parameters as required:

Parameter Meaning Possible values

[EtherNet/IP Slot 14] Scope of data transferred from the device-internal PLC to the EtherNet/IP controller.

→ Slot 14 – Inputs from standard PLC (→ page 252)

[EtherNet/IP Slot 15] Scope of data transferred from the EtherNet/IP controller to the device-internal PLC.

→ Slot 15 – Outputs to standard PLC (→ page 253)

7 Save the changes

► Press [Accept].

> Selected values are applied.

Page 135: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

135

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Interfaces

>

EtherNet/IP: Diagnosis 9126

The menu item [Diagnosis] provides access to the diagnostic data of the EtherNet/IP interface: >

Display diagnostic data 15875

To display the diagnostic data of the EtherNet/IP interfaces:

1 Select the menu page

► > >

2 Display diagnostic data

> Page shows the following information:

Designation Meaning Possible values

[EtherNet/IP connection status] Displays the connection status of the EtherNet/IP interfaces

Status Port X6 Connection status port X6 = No connection to fieldbus controller

= Connection to fieldbus controller established

Status Port X7 Connection status port X7 = No connection to fieldbus controller

= Connection to fieldbus controller established

Page 136: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

136

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Safety

6.6 Safety 18912

The [Safety] menu provides access to the status and diagnostic information of the safety-relevant PLC of the device.

Navigation path Functions

>

AS-i 1 master settings: → Display the status of the safe AS-i slaves (→ page 137) → Display switching states of the safe AS-i input slaves (→ page 139)

>

AS-i 2 master settings: → Safety: AS-i 2 master settings (→ page 141)

>

Local inputs/outputs: → Display the switching states of the local inputs (→ page 142) → Display the switching states of the local outputs (→ page 144)

>

System: → Display status information of the fail-safe PLC (→ page 146)

The elements of the menu [Safety] are exclusively used for diagnostic purposes. Programming and controlling of the safety-relevant functions of AC422S must only be made via the development system CODESYS (→ programming manual)

Observe the notes on the meaning of deviating menu symbols of the [Safety] menu. → Availability of the fail-safe PLC (→ page 165)

Page 137: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

137

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Safety

>

6.6.1 Safety: AS-i 1 master settings 9019

The [AS-i 1 master settings] menu page provides access to diagnostic data and switching states of the safe AS-i input slaves on AS-i master 1. >

Display the status of the safe AS-i slaves 14850

The menu page shows status information about the safe AS-i input slaves on the selected AS-i master.

1 Select menu page

► >

► Select [Status inputs] tab.

2 Display the status of the safe AS-i slaves

> Menu page shows the slave selector of the safe AS-i input slaves.

Legend:

Address and status of the safe AS-i input slaves on the selected AS-i master → Diagnostic data: Colour codes + symbols (→ page 138)

Current configuration status of the fail-safe PLC → Configuration status: Colour codes + symbols (→ page 138)

Information about the marked slave

Virtual control slaves are not represented in this view.

Page 138: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

138

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Safety

>

Configuration status: Colour codes + symbols 18273

Symbol Colour Description

yellow No safe configuration available

green safe configuration available

>

Diagnostic data: Colour codes + symbols 10926

Symbol Colour Description

white No safe AS-i input slave present

grey Safe AS-i input slaves present but not part of the safe configuration

green Safe AS-i input slave operates correctly; no test necessary

yellow Test requested

red Error - no safe AS-i input slave connected - AS-i slave missing - AS-i slave present but master in the protected mode and slave not projected - logical device of the AS-i slave in the error state - logical device of the AS-i slave in the hardware error state - invalid or double code sequence

Logical devices are elements of the CODESYS programming system. They are used for the logical preprocessing of input signals.

For detailed information: → Programming manual fail-safe SmartPLC AC4S

For detailed information regarding the error causes: → Online Support Centre (OSC) (→ page 162)

>

Optional: change settings of the safe AS-i input slaves 11186

To change the settings of the selected safe AS-i input slaves:

► Use the arrow keys to mark the safe AS-i input slave.

► Use [Select] to activate the marked AS-i slave.

> Setting options of the selected safe AS-i input slave are displayed.

► Change the settings as requested.

For information about the settings of the safe AS-i slaves: → AS-i 1/ AS-i 2: AS-i slaves (→ page 94)

► Use [Back] to return to the display of the diagnostic data.

Page 139: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

139

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Safety

>

Display switching states of the safe AS-i input slaves 14851

The menu page shows switching states of the safe AS-i slaves on the selected AS-i master.

1 Select menu page

► >

► Select [Switching states] tab.

2 Select safe AS-i slave.

> Page shows slave selector with the switching states of the safe AS-i input slaves:

Legend:

Switching states S1/S2 of the safe AS-i input slaves (evaluation of the code half-sequences) → Switching states: Colour codes + symbols (→ page 139) → Meaning of the colour combinations (→ page 140)

Current configuration status of the fail-safe PLC → Configuration status: Colour codes + symbols (→ page 138)

Information about the marked switching states

>

Configuration status: Colour codes + symbols 18273

Symbol Colour Description

yellow No safe configuration available

green safe configuration available

>

Switching states: Colour codes + symbols 9020

Symbol Colour Description

white No safe AS-i input slave of the safe configuration

grey – Switch open – code sequence already taught

red – Switch open – code sequence not yet taught

green – Switch closed – code sequence taught – transferred code sequence is identical with taught code sequence

Page 140: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

140

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Safety

>

Meaning of the colour combinations 15872

Symbol Colour Description

grey grey

– switches S1 and S2 are open – the two code half-sequences have been taught

grey green

– switch S1 is open, code half-sequence has been taught – switch S2 is closed, code half-sequence has been taught

green grey

– switch S1 is closed, code half-sequence has been taught – switch S2 is open, code half-sequence has been taught

green green

– switches S1 and S2 are closed – the two code half-sequences are identical with the taught CODE half-sequences

red green

– switch S1 is open, code half-sequence has not been taught yet – switch S2 is closed, code half-sequence has been taught

green red

– switch S1 is closed, the code half-sequence has been taught – switch S2 is open, the code half-sequence has not been taught yet

red red

– switches S1 and S2 are open – the two code half-sequences have not been taught yet

>

Optional: change settings of the safe AS-i input slaves 11186

To change the settings of the selected safe AS-i input slaves:

► Use the arrow keys to mark the safe AS-i input slave.

► Use [Select] to activate the marked AS-i slave.

> Setting options of the selected safe AS-i input slave are displayed.

► Change the settings as requested.

For information about the settings of the safe AS-i slaves: → AS-i 1/ AS-i 2: AS-i slaves (→ page 94)

► Use [Back] to return to the display of the diagnostic data.

Page 141: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

141

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Safety

>

6.6.2 Safety: AS-i 2 master settings 9014

The [AS-i 2 master settings] menu page provides access to diagnostic data and switching states of the safe AS-i input slaves on AS-i master 2.

The menu functions correspond to the functions of the [AS-i 1 master settings] menu.

For information regarding the menu functions: → Safety: AS-i 1 master settings (→ page 137)

► For the selection of the menu page replace the symbol by .

Page 142: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

142

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Safety

>

6.6.3 Safety: Local IOs 16661

The [local IOs]menu page provides access to information about the switching states of the local inputs and outputs. >

Display the switching states of the local inputs 15874

To display the switching states of the local inputs:

1 Select menu page

► >

► Select [Local inputs] tab.

2 Display switching states of the local inputs

> Menu page shows the following information:

Legend:

Switching states of the local inputs (→ Switching states of the inputs: Colour codes + symbols (→ page 143))

Switching states of the logical devices of the local inputs (→ Switching states of the logical devices: Colour codes + symbols (→ page 143))

Text field with status information of the marked input

The switching states of the local inputs are only displayed if the safe application is in the RUN mode.

The switching states may be displayed although no safe configuration is stored on the device (→ Display status information of the fail-safe PLC (→ page 146)). The displayed data is invalid in this case.

► Select the required symbol with [] / [].

Page 143: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

143

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Safety

>

Switching states of the inputs: Colour codes + symbols 11776

Symbol Colour Description

grey Local input is switched off

green Local input is switched on

>

Switching states of the logical devices: Colour codes + symbols 9017

Symbol Colour Description

white Local input is configured as a non-safe input.

yellow Testing of the logical devices requested

green Logical device for safe inputs does not operate correctly.

red Logical device for safe inputs is in the error state.

Designation Description

[false] Logical device provides the safe value FALSE.

[true] Logical device provides the safe value TRUE.

Logical devices are elements of the CODESYS programming system. They are used for the logical preprocessing of input signals.

For detailed information: → Programming manual fail-safe SmartPLC AC4S

Page 144: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

144

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Safety

>

Display the switching states of the local outputs 9022

To display the switching states of the local outputs:

1 Select menu page

► >

► Select [Local outputs] tab.

2 Display the switching states of the local outputs

> Menu page shows the following information:

Legend:

Switching states of the logical devices of the local outputs (→ Switching states of the logical devices: Colour codes + symbols (→ page 145))

Switching states of the local outputs (→ Switching states of the local outputs: Colour codes + symbols (→ page 145))

Text field with status information of the marked output

The switching states of the local outputs are only displayed if the safe application is in the RUN mode.

The switching states may be displayed although no safe configuration is stored on the device (→ Display status information of the fail-safe PLC (→ page 146)). The displayed data is invalid in this case.

► Select the required symbol with [] / [].

Page 145: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

145

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Safety

>

Switching states of the local outputs: Colour codes + symbols 18799

Symbol Colour Description

grey Local output is switched off

green Local output is switched on

>

Switching states of the logical devices: Colour codes + symbols 14837

Symbol Colour Description

white Local output is configured as non-safe output

green Logical device for safe input operates correctly

red Logical device for safe output is in the error state

Designation Description

[false] Logical device provides the safe value FALSE

[true] Logical device provides the safe value TRUE

[pulse] A test pulse is generated on the output.

Logical devices are elements of the CODESYS programming system. They are used for the logical preprocessing of input signals.

For detailed information: → Programming manual fail-safe SmartPLC AC4S

Page 146: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

146

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu Safety

>

6.6.4 Safety: System 15913

The [System] menu page provides access to status information of the fail-safe PLC of AC422S. >

Display status information of the fail-safe PLC 14852

To display status information of the fail-safe PLC:

1 Select menu page

► >

2 Display status information of the fail-safe PLC

> Menu page shows the following information:

Designation Description Possible values

[F PLC firmware] Firmware version of the fail-safe PLC

e.g. 4.0.2

[Safety PLC status] Status of the fail-safe PLC Invalid Invalid state

Safe started Safety module correctly started

No application No safe configuration available

IEC task enabled Safe IEC task enabled

IEC task started Safe IEC task started

IEC error Error in the safe IEC task

RUN (debug) Safe application in the RUN mode (debug operation)

STOP (debug) Safe application in the STOP mode (debug operation)

RUN (safe) Safe application in the RUN mode (safe operation)

CODESYS error Fail-safe PLC in the safe error state

Hardware error Error in the hardware of AC422S

Page 147: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

147

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu ifm system solutions

>

6.7 ifm system solutions 7065

This menu is only available via the web interface of AC422S. → Remote access (→ page 72)

The [ifm system solutions] menu provides access to information and installation options for ifm system solutions.

Navigation path Functions

ifm system solutions: → Show information about installed ifm apps (→ page 149) → Install single/basic app (→ page 149) → Install multi app (→ page 150) → Update ifm apps (→ page 151) → Uninstall ifm apps (→ page 151)

Page 148: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

148

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu ifm system solutions

>

6.7.1 Notes on ifm system solutions 7053

With the AC422S, ifm electronic offers different system solutions for the simple implementation of typical applications. System solutions consist of applications which are processed by the device-internal CODESYS standard PLC.

ifm system solutions and user-created standard applications must not be stored and run simultaneously on the AC422S!

► Delete all CODESYS system solutions stored on the device before installing new ifm system solutions or user applications!

Users can download the available ifm system solutions from ifm's website. → www.ifm.com > Service > Download > Industrial communication

>

Types of ifm system solutions 8682

There are 2 types of ifm system solutions:

Single apps Single apps provide the user with a CODESYS-based solution. Single apps directly access the I/O mechanisms of the CODESYS standard PLC. Only one single app must be stored and executed on the device.

Basic app + multi apps Multi apps provide the user with the possibility to execute different CODESYS-based solutions in parallel. The multi apps use the services of the basic app in order to be able to access the inputs and outputs of AC422S at the same time. They operate as a pure communication layer between the I/O mechanisms of the CODESYS standard PLC and the connected multi apps. Maximum 5 multi apps at a time can be stored and executed in parallel on the device.

Page 149: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

149

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu ifm system solutions

>

6.7.2 Show information about installed ifm apps 9041

In order to display information about the ifm system solutions installed on the device:

1 Select menu page

► Select the [Information] tab.

2 Show information about installed ifm apps

> The browser window displays an overview of the installed ifm apps. The following information is displayed for each ifm app:

Information Meaning

[Name] Designation of the ifm system solution app

[Version] Version number of the ifm system solution app

[Type] Type of ifm app (single, basic, multi)

[Description] Description of the functionality of the ifm system solution app

[Licence information] Licence information about the ifm system solution in the selected user language

[Link to the ifm system solution app] Hyperlink for web visualisation of the ifm system solution app

>

6.7.3 Install single/basic app 7092

Only one single app, basic app or CODESYS standard PLC application must be stored on the device.

When installing a single/basic app, all ifm system solutions and CODESYS standard PLC applications stored on the device are deleted.

To install a single or basic app on the device:

1 Select menu page

► Select the [Installation] tab.

2 Select single/basic app

► Activate the [Search] button.

> A dialogue window appears.

► Select the requested single/basic app (*.ifmapp) and click [Open] to load it.

> The file name of the selected single/basic app is displayed.

3 Transfer the single/basic app to the device

► Click on [Transfer file] button to transfer the selected single/basic app to the device.

> The progress bar indicates the status of the process.

> After successful transfer: The window shows information about the copied single/basic app.

► Optional: Click on [Cancel] to stop the download process.

4 Install the single/basic app

► Activate the [Start installation] button.

> CODESYS standard PLC is stopped.

Page 150: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

150

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu ifm system solutions

> All ifm system solutions and CODESYS standard PLC applications on the device are deleted.

> The selected single/basic app is installed.

> The progress bar indicates the status of the installation process.

> CODESYS standard PLC is started.

> The installed single/basic app is automatically started (RUN state). >

6.7.4 Install multi app 6954

Maximum 5 multi apps must be stored on the device simultaneously.

To install a multi app on the device:

Requirements:

> The basic app is installed and started (RUN state) (→ Install single/basic app (→ page 149))

1 Select menu page

► Select the [Installation] tab.

2 Select multi app

► Activate the [Search] button.

> A dialogue window appears.

► Select the requested multi app (*.ifmapp) and click the [Open] button to load it.

> The file name of the selected multi app is displayed.

3 Transfer the multi app onto the device

► Click on [Transfer file] to transfer the selected multi app onto the device.

> The progress bar indicates the status of the process.

> After successful transfer: The window shows information about the copied multi app.

► Optional: Click on [Cancel] to stop the download process.

4 Install multi app

► Activate the [Start installation] button.

> CODESYS standard PLC is stopped.

> The selected multi app is installed.

> The progress bar indicates the status of the installation process.

> CODESYS standard PLC is started.

> The installed multi app is automatically started (RUN state).

► Optional: Repeat steps 2 to 4 to install further multi apps.

Page 151: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

151

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Menu ifm system solutions

>

6.7.5 Update ifm apps 6925

The user can update an ifm system solution installed on the device by overwriting it with the new version of the ifm system solution.

Naming convention for ifm apps:

AppName_x.y.z.ifmapp

AppName = x.y.z = ifmapp =

name of the ifm app version number of the ifm app file extension of an ifm app

To update an ifm system solution:

Requirements:

> The name of the new ifm app and the installed ifm app must be identical.

> The version number of the ifm app must be greater than that of the installed ifm app.

To determine the version of the installed ifm app: → Show information about installed ifm apps (→ page 149)

1 Download new ifm app

► Download new version of the ifm system solution (→ Notes on ifm system solutions (→ page 148)).

2 Update the installed ifm app

► Install the new ifm system solution – Single/basic app: → Install single/basic app (→ page 149) – multi app: → Install multi app (→ page 150)

>

6.7.6 Uninstall ifm apps 7014

When a basic app is uninstalled, all dependent multi apps are uninstalled, too.

Before uninstalling an ifm app, the CODESYS standard PLC of AC422S is stopped. After successful uninstallation, the CODESYS standard PLC is started again.

To uninstall an ifm system solution installed on the device:

1 Display installed ifm apps

► Show information about installed ifm apps (→ page 149)

2 Uninstall ifm app

► In the section of the respective ifm app: Activate the [Uninstall app] button.

> CODESYS standard PLC is stopped.

> The selected ifm app is uninstalled.

> CODESYS standard PLC is started.

Page 152: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

152

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Setup ifm system solutions

7 Setup

Mounting and electrical connection ......................................................................................................153 Install devices on the local I/O interface ...............................................................................................153 Start screen 'Basic settings' ..................................................................................................................154 Notes on the firmware update ..............................................................................................................156 Connect and address AS-i slaves ........................................................................................................156 Setup of EtherNet/IP .............................................................................................................................156 Setup of the configuration interface ......................................................................................................157 Replace standard AS-i slave ................................................................................................................157 Replace safe AS-i slave .......................................................................................................................158

15844

This section provides information for setting up the device following mounting, electrical installation and connection to AS-i network components.

Observe the notes on mounting and electrical connection of the device!

→ Operating instructions (supplied with the device)

Page 153: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

153

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Setup Mounting and electrical connection

>

7.1 Mounting and electrical connection 15953

► Install AC422S correctly (→ Installation (→ page 36)).

► Ensure correct electrical connection of AC422S (→ Electrical connection (→ page 36)). >

7.2 Install devices on the local I/O interface 10860

If non-safe and safe peripherals without AS-i interface are part of the system configuration, they have to be linked via the local I/O interface (X8) of AC422S.

Installation instructions for the local I/O interface: → Connect devices to local I/O interface (→ page 38)

The installation of the safe peripherals on the local I/O interface influences the obtainable characteristic safety figures (PL/SIL/cat.) of the entire system.

Observe the obtainable characteristic safety figures of the connection types for the installation of the safer peripherals on the local I/O interface.

Page 154: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

154

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Setup Start screen 'Basic settings'

>

7.3 Start screen 'Basic settings' 11226

The 'Basic settings' start screen appears after the following actions/events:

initial setup

firmware update

data loss due to battery failure

The basic settings provide access to the GUI texts, system time, etc.

The same operating notes as for the page view apply for the 'Basic settings' start screen (→ Page view (→ page 59)).

>

7.3.1 Change the basic settings of the device 18511

To change the basic settings of the device:

1 Start the device

► Connect the device to a circuit.

> The device starts.

> The display shows the start screen "Basic settings" (picture).

2 Set the language of the GUI texts

► The list shows the active language.

► Use [] / []to select the list.

> The focus (= orange frame) is on the selected list.

► Open the list with the left function key [Select].

► Use [] / [] to mark the desired language and press [Select] to activate it.

> The GUI texts appear in the selected language.

► Press [Next] to go to the next page.

3 Set the system time

Option 1: Set the system time manually

► [Time] and [Date] show the current system time.

► Activate [Activate NTP] checkbox.

> Status LED =

► In the [Time] roup, set the desired clock time one position at a time.

► In the [Date] group, set the desired date one position at a time.

► Press [Finish] to save the changes and go to the standard start screen.

Page 155: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

155

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Setup Start screen 'Basic settings'

Option 2: Synchronise the system time with an NTP server

► Activate [Activate NTP] checkbox.

> Status LED =

► Enter the IP address of the NTP server in the IP address field.

► Pick the time zone of the NTP server from the list (UTC format).

> The NTP client of the device synchronises the system time with the selected NTP server.

► Wait until status LED =

> [Date] and [Time] show the synchronised values.

► Press [Finish] to save the changes and go to the standard start screen.

Page 156: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

156

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Setup Notes on the firmware update

>

7.4 Notes on the firmware update 13545

An update of the firmware of AC422S must only be made by an authorised employee of ifm electronic gmbh.

► Contact your AS-i specialist for more information.

After a firmware update, the user must re-evaluate the existing, safety-relevant application and ensure that the defined safety function continues to be met correctly.

► Re-evaluate the safety-relevant application.

► Compile safety-relevant application again, load it to device and create boot application.

>

7.5 Connect and address AS-i slaves 9004

To integrate AS-i slaves into an AS-i network that is controlled by one of the AS-i masters of the device:

1 Connect and address the AS-i slave

► Connect ONE AS-i slave to be addressed to the requested AS-i network (AS-i 1 or AS-i 2) as described in the corresponding installation instructions.

► Assign the desired address to the AS-i slave (→ Quick setup: Address the AS-i slaves connected to AS-i master 1 (→ page 87) or → Quick setup: Address the AS-i slaves connected to AS-i master 2 (→ page 88)).

► Optional: Repeat step 1 to connect and address further AS-i slaves.

2 Project the AS-i network

► Carry out a projection adaptation on the AS-i master with the newly addressed AS-i slaves (→ Quick setup: Project AS-i networks (→ page 80)).

> The AS-i master adds the detected slaves (LDS) to the list of the projected slaves (LPS).

> The AS-i slaves have a valid address and are integrated in the AS-i network. >

7.6 Setup of EtherNet/IP 12123

Detailed information on how to configure the EtherNet/IP network: → operating instructions of the EtherNet/IP master

To connect the device to the EtherNet/IP network:

► Select one of the following options:

Use the top-down configuration mode:→ Configuration mode: Top-down (→ page 372)

Use the independent configuration mode: → Configuration mode: Independent (→ page 377)

Before setting the EtherNet/IP parameters, all slaves must be connected to and addressed in the AS-i network.

► Project the AS-i slaves (→ Connect and address AS-i slaves (→ page 156))

>

Page 157: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

157

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Setup Setup of the configuration interface

7.7 Setup of the configuration interface 9006

To set up the EtherNet configuration interface (X3):

► >

► Select [IP setup] tab.

► Set the interface parameters (→ Notes on IP settings (→ page 121)). >

7.8 Replace standard AS-i slave 18531

AC422S makes it possible to replace a standard AS-i slave by a new AS-i slave in the operating mode "protected mode".

Requirements:

> New and old AS-i slave have the same device profile (→ Profiles of the AS-i slaves (→ page 185)).

> The new AS-i slave has the address 0.

> Parameter [Automatische Adressierung] is activated (→ Set the monitoring functions of the AS-i master (→ page 91)).

1 Remove old AS-i slave

► Disconnect the AS-i slave to be replaced from the AS-i network

> AC422S detects a configuration error and generates a corresponding OSC message.

2 Install new AS-i slave

► Connect the new AS-i slave to the AS-i network.

> AC422S detects the new AS-i slave and automatically assigns the address of the old AS-i slave.

> The OSC error message disappears.

> The new AS-i slave is ready for operation.

Page 158: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

158

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Setup Replace safe AS-i slave

>

7.9 Replace safe AS-i slave 18612

AC422S makes it possible to replace an AS-i slave with a new safe AS-i slave in the operating mode "protected mode".

To be able to perform this action without any errors it is mandatory that the start-up test is activated for all AS-i input slaves.

If this condition is not met, proper operation of the safe AS-i input slaves cannot be guaranteed.

► For parameter setting of the logical devices for safe AS-i input slaves set the parameter "EnableStartupTest" = TRUE (→ Logical devices for safe AS-i slaves).

Requirements:

> New and old AS-i slave have the same AS-i profile (→ Profiles of the AS-i slaves (→ page 185)).

> New and old slave are of the same function type.

> The new AS-i slave has the address 0.

> The new safe AS-i input slave is unlocked.

> Parameter [Automatische Adressierung] is activated (→ Set the monitoring functions of the AS-i master (→ page 91)).

> Parameter "EnableStartupTest" for all safe AS-i input slaves is activated (→ programming manual, Logical devices for safe AS-i slaves).

1 Remove old AS-i slave

► Disconnect the safe AS-i slave to be replaced from the AS-i network

> AC422S detects a configuration error and generates a corresponding OSC message.

2 Install new AS-i slave

► Connect the new AS-i slave to the AS-i network.

> AC422S detects the new AS-i slave and automatically assigns the address of the old AS-i slave.

> AC422S detects incorrect code sequence and requests testing of the new AS-i slave via OSC message.

► Carry out test (e.g. E-stop switch: lock unlock).

> AC422S fills code table with code sequence of the new safe AS-i input slave.

> New safe AS-i input slave is ready for operation.

Page 159: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

159

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Troubleshooting Replace safe AS-i slave

8 Troubleshooting

Status LED ...........................................................................................................................................160 Online diagnosis function .....................................................................................................................161 Online Support Centre (OSC) ..............................................................................................................162 Availability of the fail-safe PLC .............................................................................................................165 Display diagnostic protocol ...................................................................................................................165

7288

This chapter offers information regarding fault detection and troubleshooting.

Page 160: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

160

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Troubleshooting Status LED

>

8.1 Status LED 7094

The status LEDs of the device provide information about the current state of system components.

Position of the status LED on device: → Where is what on the AS-i device? (→ page 16)

>

8.1.1 Status LED: Basic device 6950

Status LED Description

H1 green lights Device has started, warnings or error messages.

yellow flashes 0.5 Hz There is a warning but not an error message.

red flashes 2Hz There is an error message.

>

8.1.2 Status LED: fieldbus EtherNet/IP 12115

Status LED Description

H2 yellow off no data transmission

flashes Reception of data

H3 green off no physical connection

lights Physical connection OK

H4 yellow off no data transmission

flashes Reception of data

H5 green off no physical connection

lights Physical connection OK

Page 161: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

161

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Troubleshooting Online diagnosis function

>

8.2 Online diagnosis function 7055

The device offers an online diagnosis function. It helps the user to find and eliminate the source of occuring failures and errors. >

8.2.1 Message types 18986

The online diagnostic function of AC422S distinguishes 3 types of messages:

Symbol Message type Meaning

Error An error occurred; proper operation of the device is disturbed.

User action absolutely required

Warning An irregularity has occurred

User action required

Event An uncritical event has occurred

No user action required

>

8.2.2 Locate error sources 7063

The online diagnosis function helps the operator to locate the source of ooccuring warning and error messages. The menu symbols of the navigation path leading to the menu page, which generates a message, are overlain by a warning / error symbol. Thus, the operator can easily locate the error source.

Example:

> The following menu symbols are overlain by an error symbol:

Main navigation bar: [AS-i 1]

Sub navigation bar: [Slaves]

> Error source on menu page [AS-i 1] > [Slaves]

If a function unit of the device causes a warning and an error message at the same time, then the error symbol is displayed.

Page 162: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

162

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Troubleshooting Online Support Centre (OSC)

>

8.3 Online Support Centre (OSC) 11385

The online support centre (OSC) shows detailed information about occurring events, interference and errors.

The OSC appears as follows:

List to select the filter and the name of the selected filter

Message A message consists of error symbol, time stamp and error details

Cons. number of the error messages displayed and total number of messages

List to select the view [Current]: → OSC: Aktuelle Meldungen zeigen (→ page 163) [History]: → OSC: Show message history (→ page 164)

The following rules for the display of messages apply:

system components of AC422S (hardware, firmware): – All message types are displayed.

Logical devices (safe AS-i slaves and safe local devices): – Error state messages are always displayed. – The programmer can deactivate the state messages of the safe function

FBs of the SafetyPLCopen library: – Programmer can activate the transmission of the messages to the OSC

Page 163: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

163

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Troubleshooting Online Support Centre (OSC)

>

8.3.1 OSC: Aktuelle Meldungen zeigen 14279

The [Current] tab lists all current messages. The messages are in chronological order. Alle messages regarding warnings and errors are displayed.

Under [Current] only messages will be displayed, that are created in the non-safe part of the AC422S. Messages created in the safe part of the AC422S are only displayed in the message history (→ OSC: Show message history (→ page 164)).

Information about the different types of messages: → Message types (→ page 161)

Overview of possible OSC messages of the device: → OSC messages (→ page 381)

To view the error messages that are currently active:

1 Select the menu page

► On the start screen: Select [OSC] function key.

► Select [Current] tab.

2 Show current messages

> The page shows the error messages that are currently active.

► Press [] to select the message field.

> The focus (orange frame) is on the message field.

► Use []/[] to go through the error messages.

3 Optional: filter messages

► Set the following parameters as required:

Parameter Meaning Possible values

[Filter] System component the message was created in

All = Display all messages in chronological order of their occurrence (= preset).

AS-i 1 = Display messages that were created in AS-i master 1.

AS-i 2 = Display messages that were created in AS-i master 2 (only selectable for devices with 2 AS-i masters).

System = Display messages that were created in the system.

> Page shows filtered messages.

Page 164: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

164

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Troubleshooting Online Support Centre (OSC)

>

8.3.2 OSC: Show message history 11775

The [History] tab lists all messages which occurred during the operating time of the device. The messages are shown in chronological order. The device displays messages regarding events, warnings and errors.

The messages are stored in a ring buffer. The ring buffer can store 2000 messages. If full, the device overwrites the oldest message(s) (time stamp).

There is a message pair for each failure (warning, error). It indicates the time of occurrence of the failure and the time at which the cause of the failure was rectified. The symbols of the messages are correspondingly marked.

Example: Error message

= Time at which the error occurred

= Time at which the cause of the fault was rectified.

To display the history of messages created so far again:

1 Select menu page

► On the start screen: Select [OSC].

► Select [History] tab.

2 Display all messages

> The page shows all previously generated error messages.

► Press [] to select the message field.

> The focus (orange frame) is on the message field.

► Use []/[] to go through the error messages.

3 Optional: Filter messages

► Set the following parameters as required:

Parameter Meaning Possible values

[Filter] System component the message was created in

All = Display all messages in chronological order of their occurrence (= preset).

AS-i 1 = Display messages that were created in AS-i master 1.

AS-i 2 = Display messages that were created in AS-i master 2 (only selectable for devices with 2 AS-i masters).

System = Display messages that were created in the system.

> Page shows filtered messages.

Page 165: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

165

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Troubleshooting Availability of the fail-safe PLC

>

8.4 Availability of the fail-safe PLC 20705

The [Safety] menu symbol indicates the availability of the fail-safe PLC.

Symbol Description

Fail-safe PLC of AC422S operating reliably.

The operator has access to all sub-menus and functions of the [Safety] menu.

Fail-safe PLC of AC422S running internal hardware test (PBIT).

The operator can access the sub-menus and functions of the [Safety] menu.

The operator can access all other menus and their sub-menus and functions.

The fail-safe PLC of AC422S is not available due to a fatal error.

The operator can access the sub-menus and functions of the [Safety] menu.

► To determine the error cause: → Online Support Centre (OSC) (→ page 162)

If the menu symbol [Safety] remains greyed out for longer than 5 minutes and simultaneously the status LED lights yellow, the device has to be rebooted.

► To remove the error: Reboot the device (power reset)

>

8.5 Display diagnostic protocol 18990

To get an overview of the configuration and the current OSC messages, the operator can store the diagnostic protocol in the system

→ Store diagnostic protocol (→ page 118)

Page 166: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

166

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Display diagnostic protocol

9 Appendix

Technical data ......................................................................................................................................167 Address assignment in Ethernet networks ...........................................................................................172 Configuration interface: connection concepts ......................................................................................173 AS-i master ...........................................................................................................................................176 AS-i slaves ............................................................................................................................................184 Fieldbus EtherNet/IP ............................................................................................................................196 OSC messages ....................................................................................................................................381

7156

Page 167: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

167

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Technical data

>

9.1 Technical data

Environmental conditions .....................................................................................................................168 Safety classification ..............................................................................................................................168 Power supply connections ....................................................................................................................168 Electrical data .......................................................................................................................................168 Display elements ..................................................................................................................................169 Housing.................................................................................................................................................169 Interfaces ..............................................................................................................................................170 AS-interface ..........................................................................................................................................171 Programmable Logic Controller (PLC) .................................................................................................171

9011

Page 168: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

168

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Technical data

>

9.1.1 Environmental conditions 15940

Environmental conditions

Ambient temperature [°C] 0...50° for UL application: max. 45

Storage temperature [°C] -20...70

Max. perm. relative air humidity [%] 95, non condensing

Height above sea level [m] < 2000

Protection rating control cabinet IP54

>

9.1.2 Safety classification 15942

Safety classification

Standards SIL 3 (IEC 61508 : 2010)

SIL cl 3 (IEC 62061: 2010)

PL e / category 4 (EN ISO 13849-1 : 2008)

Mission time TM [h] 175200 (20 years)

PFH 1.21 x 10E-8

PFDavg 1.04 x 10E-4

MTTFd [years] 100

DC [%] 95

CCF [%] 5

>

9.1.3 Power supply connections 9047

Versorgungsanschlüsse

AS-i 1, AS-i 2, FE plug-in, 6 poles, Combicon

24 V Spannungsversorgung plug-in, 2 poles, Combicon

>

9.1.4 Electrical data 18981

Electrical data

Operating voltage [V] 18...32 DC (AUX)

Current consumption from 24 V DC and AS-i [mA] < 750 (24 V) / < 10 from AS-i 1 / < 10 V from AS-i 2

Electrical separation yes

Page 169: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

169

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Technical data

>

9.1.5 Display elements 9045

Display

Technology LCD, colour

Size 35 x 28 mm (1.8“)

Resolution 220 x 176 pixels

Colour depth 18 bits (= 262 144 possible colours)

LED

Possible colours red, green, yellow

>

9.1.6 Housing 9044

Housing

Degrees of protection IP20

Material Aluminium, steel sheet, Makrolon

Dimensions (W x H x D) [mm] 93 x 128,2 x 106,2

Page 170: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

170

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Technical data

>

9.1.7 Interfaces 18272

Inputs (local I/O interface)

Number 4 (two channels, safe)

8 (one channel, non safe)

Circuits DC PNP (type 2 to IEC 61131-2)

Sensor supply to SELV/PELV

Interface type * A

Voltage range [V] 24 DC (18...32 DC)

Input current [mA] 7

* ... ZVEI document "Klassifizierung binärer 24-V-Schnittstellen mit Testung im Bereich der Funktionalen Sicherheit" (classification of binary 24-V interfaces with tests in the field of functional safety")

Outputs (local I/O interface)

Number 2 (two channels, safe)

4 (one channel, safe)

4 (one channel, non safe)

Circuits Transistor PNP

Voltage range [V] 24 DC (18...32 DC)

External supply to SELV/PELV

Max. current load per output [mA] 500

Max. inductance [mH] 400

Max. switching frequency [Hz] 25

Utilisation category DC-13

Interface type * C

Electrically isolated yes

Short-circuit proof yes

* ... ZVEI document "Klassifizierung binärer 24-V-Schnittstellen mit Testung im Bereich der Funktionalen Sicherheit" (classification of binary 24-V interfaces with tests in the field of functional safety")

11070

EtherNet configuration interface

Connection 1x RJ45

Transmission 10/100 Mbits/s

Protocol HTTP, FTP, Telnet

Designation X3

12556

EtherNet fieldbus interface

Connection 2x RJ45

Transmission rate 10/100 Mbits/s

Transfer times PLC disabled: 0.7 ms

PLC enabled: 1.5 ... 3.0 ms (adjustable)

Jitter 0.7 ms

Page 171: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

171

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Technical data

EtherNet fieldbus interface

Protocol EtherNet/IP

Services and data Cyclic EtherNet/IP services incl. diagnostic data

Acyclic EtherNet/IP services incl. AS-i command channel

EDS file

Switch integrated 2-port switch (iRT capable)

Designation X6 (EtherNet/IP port 2)

X7 (EtherNet/IP port 1)

11072

SD card slot

Media SD memory cards (max. 32 Gbytes)

Format SDHC format is supported

Supported file formats FAT, FAT32

>

9.1.8 AS-interface 18616

AS-interface

Number of AS-i master 2

AS-i version 3.0

AS-i profile M4

>

9.1.9 Programmable Logic Controller (PLC) 15946

standard PLC

Type CODESYS Control Runtime System (incl. CODESYS WebVisu and TargetVisu)

Programming system CODESYS Development System V3.5 SP4 Patch 2

Programming language FBD, SFC, IL, CFC, LD, ST

Memory available for standard PLC applications / RETAIN variables

appr. 10 MB / 4072 Byte

Fail-safe PLC

Type CODESYS Control Safety Runtime System (certified)

Programming system CODESYS Development System V3.5 SP4 Patch 2 with installed ifm AS-i package 1.3.2.2

Programming languages FBD

Available memory for safe application / data 384 KBytes / 128 KBytes

Page 172: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

172

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Address assignment in Ethernet networks

>

9.2 Address assignment in Ethernet networks 14436

In the Ethernet network every IP address MUST be unique.

The following IP addresses are reserved for network-internal purposes and are therefore not allowed as an address for participants: nnn.nnn.nnn.0 | nnn.nnn.nnn.255.

Only network participants whose subnet mask is identical and whose IP addresses are identical with respect to the subnet mask can communicate with each other.

Rule: If part of the subnet mask = 255, the corresponding IP address parts must be identical. If part of the subnet mask = 0, the corresponding IP address parts must be different.

If the subnet mask = 255.255.255.0, 254 participants communicating with each other are possible in the network. If the subnet mask = 255.255.0.0, 256x254 = 65 024 participants communicating with each other are possible in the network.

In the same physical network different subnet masks of the participants are allowed. They form different groups of participants which cannot communicate with groups of participants having other subnet masks.

In case of doubt or problems please contact your system administrator.

Examples:

Participant A IP address

Participant A Subnet mask

Participant B IP address

Participant B Subnet mask

Communication of participants possible?

192.168.82.247 255.255.255.0 192.168.82.10 255.255.255.0 Yes, 254 participants possible

192.168.82.247 255.255.255.0 192.168.82.247 255.255.255.0 No (same IP address)

192.168.82.247 255.255.255.0 192.168.82.10 255.255.0.0 No (different subnet mask)

192.168.82.247 255.255.255.0 192.168.116.10 255.255.255.0 No (different IP address range: 82 vs. 116)

192.168.222.213 255.255.0.0 192.168.222.123 255.255.0.0 Yes, 65 024 participants possible

192.168.111.213 255.255.0.0 192.168.222.123 255.255.0.0 Yes, 65 024 participants possible

192.168.82.247 255.255.255.0 192.168.82.0 255.255.255.0 no; the whole network is disturbed because the IP address xxx.xxx.xxx.0 is not allowed

Page 173: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

173

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Configuration interface: connection concepts

>

9.3 Configuration interface: connection concepts

Direct link ..............................................................................................................................................174 Connection via Ethernet network .........................................................................................................175

7071

To be able to access the web interface and the programming interface of the device-internal PLC, the configuration interface (X3) must be connected to a computer. The device supports the following connection types:

Direct connection (→ Direct link (→ page 174))

Connection via an EtherNet network (→ Connection via Ethernet network (→ page 175))

Page 174: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

174

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Configuration interface: connection concepts

>

9.3.1 Direct link 12551

To establish a direct connection to the device:

► Connect configuration interface X3 of the device with the Ethernet interface of the PC/laptop.

► Setup the IP parameters of the configuration interface (X3) to enable communication between the device and the PC/Laptop. → Notes on IP settings (→ page 121) → Address assignment in Ethernet networks (→ page 172)

> Connection bewtween device and PC/Laptop is established.

Page 175: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

175

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Configuration interface: connection concepts

>

9.3.2 Connection via Ethernet network 12553

To establish a connection via a Ethernet network, the device has to be connected with a coupling element (e.g. Ethernet switch, WLAN router). >

Option 1: Transmit fieldbus and web interface data via different networks 14182

► Enable DHCP functionality of the Ethernet switch/WLAN router.

► Connect configuration interface (X3) via Ethernet cable with the Ethernet switch/WLAN router (

► Activate [Optain IP address autom.] (→ Notes on IP settings (→ page 121)).

► If required, activate the option 'Obtain an IP address automatically' in the IP settings of the PC.

► Connect PC/laptop with the Ethernet switch.

OR:

► Connect PC/laptop wireless with the WLAN router .

> Connection between device and PC/laptop is established.

>

Option 2: transfer fieldbus and web interface data over the same network 14183

► Connect the configuration interface (X3) to the EtherNet/IP interface (X7) using an EtherNet cable.

► Activate the DHCP function of the EtherNet switch for automatic assignment of IP addresses.

► Connect the EtherNet/IP interface (X6) to the EtherNet switch using an EtherNet cable.

► The parameter [Optain IP address autom.] must be activated (→ Notes on IP settings (→ page 121)).

► Connect the PC/laptop to the EtherNet switch using an EtherNet cable.

► If necessary, activate the option [Optain IP address automatically] in the IP settings of the PC/laptop.

> The device and the PC/laptop/mobile device are connected over the IP network.

Page 176: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

176

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i master

>

9.4 AS-i master

Operating modes of the AS-i master ....................................................................................................177 Master flags ..........................................................................................................................................179

8900

Master = Handles the complete organisation on the bus. The master decides on the bus access time and polls the →slaves cyclically.

Page 177: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

177

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i master

>

9.4.1 Operating modes of the AS-i master

Protected mode ....................................................................................................................................178 Projection mode ....................................................................................................................................178 Switch operating modes .......................................................................................................................178

8934

The AS-i master can be operated in one of the following operating modes:

Page 178: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

178

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i master

>

Protected mode 14833

In the operating mode "Protected mode" (= normal mode), the AS-i master only communicates with AS-i slaves that are entered in the list of projected slaves (LPS) and where current and target configuration match.

The AS-i master automatically detects the following actions and signals a configuration error:

an AS-i slave is added to the AS-i network (error message: Slave not projected)

an AS-i slave is removed from the AS-i network (error message: Slave not present)

Optionally, the operator can activate/deactivate the following monitoring functions (→ Set the monitoring functions of the AS-i master (→ page 91)):

Automatic addressing: When a defective slave is replaced, the AS-i master controls the addressing. The new AS-i slave obtains the same address as the old AS-i slave if the following conditions are met:

The new AS-i slave has the address 0.

Both AS-i slaves have the same device profile.

Double address recognition: The AS-i master recognises whether one or several AS-i slaves have the same address (error message: Double address error).

Earth-fault detection: The AS-i master detects any earth faults.

In the operating mode "Protected mode", the operator can control the PLC applications stored on the device (start, stop, reset). >

Projection mode 14848

In the operating mode "Projection mode", the AS-i master communicates with all AS-i slaves that are connected to the AS-i line and do not have the address 0. Missing AS-i slaves are not detected by the AS-i master.

In projection mode a projection adaptation can be carried out. The AS-i master reads the configuration data of all detected AS-i slaves and saves it permanently. >

Switch operating modes 5487

The operator / programmer can switch the operating modes of the AS-i master as follows:

per GUI / web interface (→ Set the operating mode of the AS-i master (→ page 90))

per function block Set_Mode (programming manual: → Set_Mode)

If an AS-i slave with the address 0 is connected, then the AS-i master cannot switch from "projection mode" into "protected mode" !

► Address the AS-i slave correctly.

► Switch the operating mode.

Page 179: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

179

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i master

>

9.4.2 Master flags

AS-i master status flags ........................................................................................................................180 Execution control flags .........................................................................................................................181 Host flags ..............................................................................................................................................182 DAE/EE flags ........................................................................................................................................183

16936

The master flags contain information about the status of the AS-i master and the fieldbus host.

The master flags are transmitted along with the input data of the digital AS-i slaves in the acyclic data set DS2 (→ DS2 – Digital inputs of the slaves and master flags (→ page 260)).

Page 180: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

180

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i master

>

AS-i master status flags 7160

The AS-i master status flags provide information about the status of the AS-i master. After a status change, the AS-i master immediately updates the flags.

The AS-i master status flags are saved in the following register:

AS-i master status flags

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

ECPS ECP – – WCD CM – HWDT SER HER

Legend:

Flag Designation Description Initial value at power-on

HER Hardware Error 1 (TRUE): a hardware error occurred during the power-on self test

0 (FALSE)

SER Software Error 1 (TRUE): Software error occurred: Stack Overflow, Stack Underflow, Undefined Opcode, Instruction Fault, Illegal Access, Watchdog Timeout

0 (FALSE)

HWDT Host Watchdog Timeout

1 (TRUE): Host watchdog not triggered by the host within 200 ms; master changed to the offline mode

0 (FALSE)

CM Configuration Missing 1 (TRUE): Configuration not yet fully received from the host. Becomes FALSE as soon as PCD, PP and LPS have been set

1 (TRUE)

WCD Watchdog Control Disabled

1 (TRUE): Signals the host that the watchdog signal is not processed in the master.

0 (FALSE)

ECP Execution Control Phase

Display of the different phases the execution control goes through during boot (→ table).

0

ECPS Execution Control Phase State

Display of the substates of the different execution control phases (→ table).

0

Execution Control Phase Execution Control Phase State

0 = inactive –

1 = start phase 0 = master start and initialisation 1 = wait for configuration 2 = wait for start

2 = reserved –

3 = offline phase –

4 = detection phase –

5 = activation phase –

6 = normal operation 0 = normal data exchange 1 = slave finder activated

Page 181: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

181

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i master

>

Execution control flags 7161

The execution control flags provide information about the execution control of the AS-i master. The flags are updated by the AS-i master immediately after each change.

The execution control flags are saved in the following register:

Execution control flags

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

– NOPF CCOK PE – DEA AAE POK OR APF NOA CA AA AN S0 COK

Legend:

Flag Designation Description Initial value at power-on

COK Config_OK 1 (TRUE): The configuration of all AS-i slaves on the network corresponds to the projection data (CDI=PCD for all activated slaves) && (LDS=LPS=LAS) Exception: Flag APF = 1 and LPS = empty, then COK = 1

0 (FALSE)

S0 LDS.0 1 (TRUE): Slave with address 0 found 0 (FALSE)

AN Auto_Address_Assign 1 (TRUE): Auto addressing possible (protected mode = active && auto addressing = active && PCD = CDI &&

LDS <=LPS)

0 (FALSE)

AA Auto_Address_Available 1 (TRUE): All the necessary conditions for auto addressing are fulfilled. The master waits for slave 0.

0 (FALSE)

CA Configuration_Active 0 (FALSE): 1 (TRUE):

Master in protected mode Master in projection mode

0 (FALSE)

NOA Normal_Operation_Active 1 (TRUE): Master is in the normal mode (The AS-i master has communicated with at least one slave since the last offline phase. Even if the slave disappears after this, the signal will remain set.)

0 (FALSE)

APF Asi_Power_Fail 0 (FALSE): 1 (TRUE):

AS-i voltage OK AS-i voltage too low

1 (TRUE)

OR Offline_Ready 1 (TRUE): Master has gone through the offline phase and waits for: APF = 0 and a timeout of 1s

0 (FALSE)

POK Periphery_OK 1 (TRUE): No peripheral faults present, all bits of LPF = 0.

0 (FALSE)

AAE Auto_Address_Enable 1 (TRUE): Auto addressing switched on (Echo of Set_Auto_Address_Enable of host)

0 (FALSE)

DEA Data_Exchange_Active 1 (TRUE): Data exchange between master and slaves activated (reflects DEA of host flags)

1 (TRUE)

0 (FALSE): Instead of the data exchange, ReadID is continually executed on the slaves.

PE Protocol Error 1 (TRUE): 0 (FALSE):

CTT protocol error No CTT protocol error

0 (FALSE)

Page 182: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

182

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i master

Flag Designation Description Initial value at power-on

CCOK CTT_Config_OK 1 (TRUE): The configuration of all CTT slaves on the network corresponds to the projected CCT data. (CCDI = PCCD for all CTT slaves)

0 (FALSE)

NOPF No_Offline_Phase_Flag 1 (TRUE): The master skips the offline phase if one of the following actions is performed: – change to protected mode – change of PCD – change of LPS – change of PCCD

0 (FALSE)

0 (FALSE): The master goes through the offline phase when changing to the protected mode the next time.

>

Host flags 7162

The host flags are regularly updated by the host. The AS-i master cyclically checks the host flags for changes.

The host flags are saved in the following register:

Host Flags

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

– – – – – – – – – – – – – – DEA OFF

Legend:

Flag Designation Description Initial value at power-on

OFF Offline 1 (TRUE): Execution control of the master changes to the offline mode. The function Set_Offline_Mode() is implemented via this flag.

0 (FALSE)

DEA Data_Exchange_Active 1 (TRUE): Data exchange activated between master and slaves. The function Set_Data_Exchange_Active() is implemented via this flag

1 (TRUE)

Page 183: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

183

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i master

>

DAE/EE flags 16935

The DAE/EE flags indicate if the double address detection and the earth fault detection are on.

The DEA/EE flags are saved in the following register:

DAE/EE flags

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

-- -- -- -- -- -- -- DAE active

-- -- -- -- -- -- -- EE active

Legend:

Flag Designation Description Initial value at PowerOn

DAE active

Double address detection active

1 (TRUE): 0 (FALSE):

Double address detection is on. Double address detection is off.

0 (FALSE)

EE active Earth fault detection is active

1 (TRUE): 0 (FALSE):

Earth fault detection is on. Earth fault detection is off.

1 (TRUE)

Page 184: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

184

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i slaves

>

9.5 AS-i slaves

Profiles of AS-i slaves ...........................................................................................................................185 8893

Slave = Passive participant on the bus, only replies on request of the →master. Slaves have a clearly defined and unique →address in the bus.

Page 185: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

185

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i slaves

>

9.5.1 Profiles of AS-i slaves

Configuration data (CDI) of the slaves (slave profiles) .........................................................................186 Slave profiles for slaves with combined transaction .............................................................................193 Combined transaction – Use of analogue channels in the gateway depending on the slave profile ...194

8902

Page 186: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

186

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i slaves

>

Configuration data (CDI) of the slaves (slave profiles)

Structure of the slave profile .................................................................................................................187 Description of the IO code for digital slaves .........................................................................................187 Description of the ID code (selection) ..................................................................................................188 Description of the extended ID code 1 .................................................................................................188 Description of the extended ID code 2 .................................................................................................189 Valid combinations IO code / ID code / extended ID code 2 ................................................................190

5346

The configuration data CDI (= Configuration Data Image) for single, A and B slaves is stored in a data word. The structure is shown below and is the same for all slaves.

Page 187: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

187

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i slaves

>

Structure of the slave profile 5347

The slave profile has the following structure: S-[IO code].[ID code].[ext. ID code2]

Bits 15...12 Bits 11...8 Bits 7...4 Bits 3...0

XID2 extended ID code 2

3rd figure in the slave profile

(AS-i slave v2.0 = 0xF *)

XID1 extended ID code 1

is no part of the slave profile

can be changed by the user

(AS-i slave v2.0 = 0xF *)

ID code ID code

2nd figure in the slave profile

IO code I/O configuration

1st figure in the slave profile

Example: AC2255 4 digital inputs, 2 digital outputs AS-i profile = S-7.A.E This results in the following configuration data of the slave:

0b1110 = 0xE (e.g.) 0b0111 = 0x7 0b1010 = 0xA 0b0111 = 0x7

The corresponding CDI data word is: 11100111 10100111 = 0xE7A7

*) AS-i slaves according to the AS-i specification 2.0 and older do not support the extended ID codes 1 and 2. In the master 0xF is stored for this configuration data. >

Description of the IO code for digital slaves 5349

Structure slave profile = S-[IO-Code].x.x

IO code [hex]

IO code (bits 3…0)

Function of the periphery bit

D3 D2 D1 D0

0 0000 input input input input

1 0001 output input input input

2 0010 input / output input input input

3 0011 output output input input

4 0100 input / output input / output input input

5 0101 output output output input

6 0110 input / output input / output input / output input

7 0111 input / output input / output input / output input / output

8 1000 output output output output

9 1001 input output output output

A 1010 input / output output output output

B 1011 input input output output

C 1100 input / output input / output output output

D 1101 input input input output

E 1110 input / output input / output input / output output

F 1111 not allowed

Page 188: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

188

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i slaves

>

Description of the ID code (selection) 5351

Structure slave profile = S-x.[ID-Code].x

ID code [hex]

ID code (Bits 3…0)

Description

0 0000 4 I/O connections for binary sensors and/or actuators with 1 signal each

1 0001 2 dual-signal I/O connections for binary sensors and/or actuators with 2 signals each

A 1010 slave operates in the extended addressing mode (B slave or A/B slave)

B 1011 slave corresponds to Safety-at-Work

F 1111 manufacturer-specific device (cannot be replaced with products from other manufacturers)

>

Description of the extended ID code 1 5353

Can be changed by the user, however not a part of the slave profile.

Default value: 0xF for single slaves 0x7 for A/B slaves

The value is evaluated and checked by the master. The user can make an additional distinction between slaves which do not differ in the AS-i system, e.g. slaves with different ranges for current, voltage or frequency. This prevents damage when replacing slaves with a wrong performance range.

Page 189: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

189

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i slaves

>

Description of the extended ID code 2 5355

>

Extended ID code 2 for analogue slaves with profile 7.3.x 5357

The extended ID code 2 is used to specify complex slaves.

Structure slave profile = S-7.3.[ext.ID code2]

Bit 3 Bit 2 Bit 1 Bit 0 Description

0 0 1-channel slave

0 1 2-channel slave

1 0 4-channel slave

1 1 4-channel slave (if slave has no extended ID code)

0 transparent data exchange = binary bits

1 analogue value transmission

0 output slave

1 input slave

The ID code 2 results from a combination of the options stated above. >

Extended ID code 2 for analogue slaves with profile 7.4.x 5358

The extended ID code 2 is used to specify complex slaves.

Structure slave profile = S-7.3.[ext. ID code2]

Bit 3 Bit 2 Bit 1 Bit 0 Description

0 0 1-channel slave

0 1 2-channel slave

1 0 4-channel slave

1 1 4-channel slave (if slave has no extended ID code)

0 0 0 0 4 binary inputs + 4 binary outputs

0 output slave

1 input slave

The ID code 2 results from a combination of the options stated above.

Page 190: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

190

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i slaves

>

Valid combinations IO code / ID code / extended ID code 2 5359

Structure slave profile = S-[IO code].[ID code].[ext. ID code2]

IO code [hex]

ID code [hex]

Ext. ID code 2

[hex] Meaning

0…E not: 9, B, D

0 x binary I/O connections for sensors and actuators

0, 3, 8 1 x 1 or 2 binary sensors or actuators with 2 signals each (dual-signal devices)

0 1 x 4 binary inputs for 2 dual-signal sensors

0…E not: 2A

A x slave operates in the "extended addressing mode" (B slave or A/B slave)

0 A E slave with extended address function: 4 binary inputs for 2 dual-signal sensors (e.g. I/O module AC2250)

0 B x slave corresponds to Safety-at-Work

0…E F x manufacturer-specific device (cannot be replaced by other products)

1 1 x single sensor with remote setting: 3 binary inputs + 1 binary output (e.g. sensor OC5226)

3 1 x 2 binary inputs for 1 dual-signal sensor AND 2 binary outputs for 1 dual-signal actuator

3 A x slave with extended address function

3 A 1 slave with extended address function: 2 binary inputs + 1 binary output

3 A 2 slave with extended address function: 4 binary inputs

6 0 x quick combined transaction type 5 of 8, 12 or 16 data bits by using 2, 3 or 4 slave addresses in a slave

7 0 F motor starter 2I + 2O (e.g. ZB0032)

7 0 E 4 binary inputs + 4 binary outputs (e.g. I/O module AC2251)

7 1 x interface for the transmission of 6...18-bit signals; analogue profile for combined transaction type 1; was replaced by S-7.3

7 2 x extended slave profile for the transmission of 6...18-bit signals; extended analogue profile for combined transaction type 1; was replaced by S-7.4

7 3 x

slave profile for 16-bit transmission with integrated support in the master; integrated analogue profile for combined transaction type 1

( Extended ID code 2 for analogue slaves with profile 7.3.x (→ page 189))

7 3 5 2 analogue outputs of 16 bits each (e.g. I/O module AC2618)

7 3 6 4 analogue outputs of 16 bits each (e.g. I/O module AC2518)

7 3 C 1 analogue input of 16 bits (e.g. sensor PPA020)

7 3 D 2 analogue inputs of 16 bits each (e.g. I/O module AC2616)

7 3 E 4 analogue inputs of 16 bits each (e.g. I/O module AC2516)

7 4 x

extended slave profile for 16-bit transmission with integrated support in the master; integrated extended analogue profile for combined transaction type 1

( Extended ID code 2 for analogue slaves with profile 7.4.x (→ page 189))

7 4 C RFID identification system for writing and reading RFID tags 15-bit data + 1-bit messages (e.g. DTA100)

Page 191: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

191

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i slaves

IO code [hex]

ID code [hex]

Ext. ID code 2

[hex] Meaning

7 A x slave operates in the "extended addressing mode" (B slave or A/B slave)

7 A 5 slave operates in the "extended addressing mode" (B slave or A/B slave) combined slave; supports combined transaction type 2

7 A 7 slave operates in the "extended addressing mode" (B slave or A/B slave) 4 binary inputs + 4 binary outputs

7 A 8 slave operates in the "extended addressing mode" (B slave or A/B slave) 1 channel for combined transaction type 4

7 A 9 slave operates in the "extended addressing mode" (B slave or A/B slave) dual channel for combined transaction type 4

7 A A slave operates in the "extended addressing mode" (B slave or A/B slave) 8 binary inputs + 8 binary outputs

7 A E slave operates in the "extended addressing mode" (B slave or A/B slave); dual sensor with actuator interface (e.g. sensor AC2317); 2 binary inputs + 2 binary outputs

7 B x safety slave with non-safe outputs

7 B 0 safety slave with non-safe outputs; 2 safe binary inputs (e.g. I/O module AC005S)

7 B E

safety sensor with non-safe outputs; 2 safe binary inputs AND 2 safe binary outputs AND 2 non-safe (relay) outputs (e.g. I/O module AC009S)

7 D x device for motor control (electromechanical)

7 D 0 electromechanical motor control with open sub-profile

7 D 1 electromechanical direct starter

7 D 2 electromechanical reverser

7 D 3 electromechanical direct starter with brake

7 D 4 electromechanical reverser with brake

7 D 5 electromechanical direct starter with accessories

7 D 6 electromechanical reverser with accessories

7 E x device for motor control (electronic)

7 E 0 electronic motor control with open sub-profile

7 E 1 electronic direct starter

7 E 2 electronic reverser

7 E 3 electronic direct starter with brake

7 E 4 electronic reverser with brake

7 E 5 electronic direct starter with accessories

7 E 6 electronic reverser with accessories

8 1 x 4 binary outputs for 2 dual-signal actuators

B 1 x dual-signal actuator with feedback: 2 binary outputs + 2 binary inputs

B A 5 slave operates in the "extended addressing mode" (B slave or A/B slave); supports combined transaction type 2

B A E slave operates in the "extended addressing mode" (B slave or A/B slave); 2 binary outputs + 2 binary inputs (e.g. AC2086 module)

Page 192: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

192

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i slaves

IO code [hex]

ID code [hex]

Ext. ID code 2

[hex] Meaning

D 1 x single actuator with monitoring: 1 binary output + 3 binary inputs

x = any value (0...F)

Devices with M4 master profile enable connection of slaves with more than 4 digital inputs/outputs. The transmission is combined: Part of the data transmission is carried out via the digital bits D0...D3, another part via the "analogue" channels.

The more data is transmitted, the longer it takes until all data of a slave has been transmitted.

Cycle time single slave = 5 ms Cycle time A/B slave (if address is only assigned to A or B slave) = 5 ms Cycle time A/B slave (if address is assigned to A and B slave) = 10 ms The cycle time for CTT transmission is a multiple of these values for individual data.

CTT = Combined Transaction Type

Page 193: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

193

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i slaves

>

Slave profiles for slaves with combined transaction 5362

Structure slave profile = S-[IO-Code].[ID-Code].[ext.ID-Code2]

Slave profile

Master profile

Assignment analogue channels in the device

Bits D0…D3

Additional acyclic string

data transaction

Combined transaction

CTT

Number of channels

Use analogue / digital

S-6.0 M4 1 I

and 1 O

2/3/4 x 4 binary inputs and

2/3/4 x 4 binary outputs –– no type 5

S-7.3 M3 1/2/4 I

or 1/2/4 O

1/2/4 analogue inputs or

1/2/4 binary outputs –– no type 1

S-7.4 M3 1/2/4 I

or 1/2/4 O

1/2/4 analogue inputs or

1/2/4 binary outputs

4 inputs or

4 outputs yes type 1

S-7.5.5 M4 0…4 I and

0…4 O

0…4 analogue inputs or

< 65 binary inputs and

0…4 analogue outputs or

< 65 binary outputs

2 inputs and

2 outputs yes type 2

S-7.A.5 M4 0…2 I and

0…2 O

0…2 analogue inputs or

< 33 binary inputs and

0…2 analogue outputs or

< 33 binary outputs

2 inputs and

1 output yes type 2

S-7.A.7 M4 –– –– 4 inputs

and 4 outputs

no type 3

S-7.A.8 M4

1 I

1 analogue input or

< 17 binary inputs 1 output no type 4

S-7.A.9 M4

2 I

2 analogue inputs or

< 33 binary inputs –– no type 4

S-7.A.A M4 1 I

and 1 O

8 binary inputs and

8 binary outputs –– no type 3

S-B.A.5 M4 0…2 I and

0…2 O

0…2 analogue inputs or

< 33 binary inputs and

0…2 analogue outputs or

< 33 binary outputs

–– yes type 2

Legend colour pattern:

binary inputs binary outputs analogue inputs analogue outputs

Page 194: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

194

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i slaves

>

Combined transaction – Use of analogue channels in the gateway depending on the slave profile 5366

Transaction Slave profile

Slave type

Number channel

s

Analogue input channels Analogue output channels

CH3 CH2 CH1 CH0 Trans CH3 CH2 CH1 CH0 Trans

CTT5 6.0.x S 1 – – – b – – – – b –

CTT1

7.3.C S 1 – – – a – – – – – –

7.3.D S 2 – – a a – – – – – –

7.3.E S 4 a a a a – – – – – –

7.3.4 S 1 – – – – – – – – a –

7.3.5 S 2 – – – – – – – a a –

7.3.6 S 4 – – – – – a a a a –

7.3.C S 1 – – – a – – – – – –

7.3.D S 2 – – a a – – – – – –

7.3.E S 4 a a a a – – – – – –

7.3.4 S 1 – – – – – – – – a –

7.3.5 S 2 – – – – – – – a a –

7.3.6 S 4 – – – – – a a a a –

CTT1

7.4.4 S 1 – – – – – – – – a X

7.4.5 S 2 – – – – – – – a a X

7.4.6 S 4 – – – – – a a a a X

7.4.C S 1 – – – a X – – – – –

7.4.D S 2 – – a a X – – – – –

7.4.E S 4 a a a a X – – – – –

CTT2 7.5.5 S 0…4 a b a b a b a b X a b a b a b a b X

CTT2 7.A.5 A 0…2 – – a b a b X – – a b a b X

7.A.5 B 0…2 a b a b – – X a b a b – – X

CTT3 7.A.7 A –

only binary –

only binary –

B – – –

CTT4 7.A.8 A 1 – – – a b – – – – – –

B 1 – a b – – – – – – – –

CTT4 7.A.9 A 2 – – a b a b – – – – – –

B 2 a b a b – – – – – – – –

CTT3 7.A.A A 1 – – – b – – – – b –

B 1 – b – – – – b – – –

CTT2 B.A.5 A 0…2 – – a b a b X – – a b a b X

B.A.5 B 0…2 a b a b – – X a b a b – – X

CHn = channel Trans. = transparent mode

S = single slave A = A slave B = B slave

a = analogue inputs/outputs (word) b = binary inputs/outputs (bits) – = not used

X = additional acyclic transaction of strings for device, parameters, diagnosis

Legend colour pattern:

binary inputs binary outputs analogue inputs analogue outputs

Page 195: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

195

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix AS-i slaves

Page 196: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

196

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

9.6 Fieldbus EtherNet/IP

Fieldbus objects ....................................................................................................................................197 Fieldbus parameters .............................................................................................................................199 Device-specific parameters ..................................................................................................................200 Cyclic data ............................................................................................................................................221 Acyclic data ..........................................................................................................................................254 Configuration mode ..............................................................................................................................371

13070

The Ethernet Industrial Protocol (EtherNet/IP) is a fieldbus system for industrial process communication in the automation technology. It extends the Ethernet standard by the object-oriented Common Industrial Protocol (CIP) as application layer.

The following tables shows the main features of the EtherNet/IP:

Topology star, tree, line

Recommendation: Switched Ethernet

Connection technology Standard Ethernet cable and connector

Screened 10/100 Mbit/s TX Ethernet cable

RJ45, M12

Transmission rate 10, 100 MBits

Transmission modes cyclic and acyclic

→ www.odva.org (umbrella organisation)

Page 197: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

197

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

9.6.1 Fieldbus objects 12947

EtherNet/IP is based on the Common Industrial Protocol (CIP). CIP encloses services and applications in so-called object classes. Each object class has certain features (attributes) and defined interfaces which can be used to access the functions of the object instance.

The AC422S uses the following object classes:

Assembly instance objects for the transmission of

device and EtherNet/IP parameters (→ Parameter data (→ page 197))

Cyclic process data, diagnostic data (→ Cyclic data (→ page 198))

Manufacturer-specific objects for the transmission of acyclic data (→ Acyclic data (→ page 198)) >

Page 198: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

198

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Parameter data 12620

The paramater data is transfered via the Configuration Assembly Object:

Object class [dec]

Instance

[dec]

Attribute [dec]

Content Access r = read w = write

max. no. of words

4 175 3 Parameter data (module configuration, device-specific parameters) r/w 122

Cyclic data 17451

Cyclic data is transferred in dynamic assembly objects:

Object class [dec]

Instance

[dec]

Attribute [dec]

Content Access r = read w = write

max. no. of words

4 100 3 Cyclic data from AC422S to the I/O scanner (EtherNet/IP slots 1, 3, 5, 7, 9, 10, 13, 14)

r max. 248

4 150 3 Cyclic data from the I/O scanner to AC422S (EtherNet/IP slots 2, 4, 6, 8, 11, 12, 15)

r/w max. 248

>

Acyclic data 17548

Acyclic data is transferred in manufacturer-specific objects:

Object class [dec]

Instance

[dec]

Attribute [dec]

Content Access r = read w = write

max. no. of words

801 1 1 Acyclic data sets (system) r 248

32 ... 47 Acyclic data sets (AS-i master 1) r/w* 248

64 ... 79 Acyclic data sets (AS-i master 2) r/w* 248

801 1 30 Command request channel, system r/w 248

31 Command reply channel, system r 248

801 1 62 Command request channel, AS-i master 1 r/w 248

63 Command reply channel, AS-i master 1 r 248

801 1 94 Command request channel, AS-i master 2 r/w 248

95 Command reply channel, AS-i master 2 r 248

* ... depends on acyclic data set (→ Overview: Acyclic data sets (→ page 258))

Page 199: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

199

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

9.6.2 Fieldbus parameters 17999

The fieldbus parameters provide information for the integration of the device into the EtherNet/IP network. The fieldbus parameters are set directly on the device.

Parameter Meaning Value range

IP address IP address (IPv4) of the device's EtherNet/IP interface

e.g.: 192.168.0.200

Subnet mask Subnet mask of the EtherNet/IP network segment

e.g.: 255.255.255.0

Gateway address IP address (IPv4) of the EtherNet/IP gateway

e.g.: 192.168.0.100

Page 200: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

200

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

9.6.3 Device-specific parameters

Parameters: Independent mode ...........................................................................................................201 Parameters: Top-down mode ...............................................................................................................202 Parameter setting via the configuration assembly object .....................................................................203 EDS-file.................................................................................................................................................220

12788

The device-specific parameters allow you to make individual adjustments to the system. Depending on the selected configuration mode, the following parameters are available.

Page 201: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

201

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Parameters: Independent mode 11058

Parameter Description Value range

Analogue channels per input slave Number of analogue channels per input slave

4 channels* = 4 channels (variable slave assignment)

2 channels = 2 channels (fixed slave assignment)

1 channel = 1 channel (fixed slave assignment)

1 channel per A/B slave =

1 channel per A/B slave (fixed slave assignment)

Analogue channels per output slave Number of analogue channels per output slave

4 channels* = 4 channels (variable slave assignment)

2 channels = 2 channels (fixed slave assignment)

1 channel = 1 channel (fixed slave assignment)

1 channel per A/B slave =

1 channel per A/B slave (fixed slave assignment)

Fail-safe state Behaviour of the slave outputs if an interrupted fieldbus connection is detected

Reset outputs* =

All AS-i outputs are switched off in case of an interrupted EtherNet/IP connection (value = 0).

Hold outputs = The outputs are held in the last valid state that existed before the interrupted connection was detected.

Change byte order Byte order in a word

Setting applies to all data of object class 4, instances 100 and 150

Disabled* = Byte order in word remains unchanged.

Enabled = Byte order in word is inverted.

* ... Default setting

In the 'Independent' configuration mode, the device-specific parameters are configured via the GUI of the device (→ Configuration mode: Independent (→ page 377)).

Page 202: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

202

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Parameters: Top-down mode 12792

Parameter Description Value range

Analogue channels per input slave Number of analogue channels per input slave

4 channels* = 4 channels (variable slave assignment)

2 channels = 2 channels (fixed slave assignment)

1 channel = 1 channel (fixed slave assignment)

1 channel per A/B slave =

1 channel per A/B slave (fixed slave assignment)

Analogue channels per output slave Number of analogue channels per output slave

4 channels* = 4 channels (variable slave assignment)

2 channels = 2 channels (fixed slave assignment)

1 channel = 1 channel (fixed slave assignment)

1 channel per A/B slave =

1 channel per A/B slave (fixed slave assignment)

Modify slave order analogue IN Order of analogue input slaves can be changed

Disabled* = The order of slaves remains unchanged (basic setting).

Enabled = The order of slaves can be changed (parameters in the following row).

1st analogue IN slave (slot 9) ... 15th analogue IN slave (slot 9)

1st analogue IN slave (slot 10) ... 15th analogue IN slave (slot 10)

Assignment of analogue input slaves 1 to 15 of AS-i master 1/2 to AS-i slave addresses

These settings are only effective if parameters Analogue channels per input slave = 4 channels and Modify slave order analogue IN = Enabled

Slave 1 AS-i master 1 Slave 2 AS-i master 1 ... Slave 31 AS-i master 1 Slave 1 AS-i master 2 Slave 2 AS-i master 2 ... Slave 31 AS-i master 2

Modify slave order analogue OUT Order of analogue output slaves can be changed

Disabled = The order of slaves remains unchanged (basic setting).

Enabled = The order of slaves can be changed (parameters in the following row).

1st analogue OUT slave (slot 11) ... 15th analogue OUT slave (slot 11)

1st analogue OUT slave (slot 12) ... 15th analogue OUT slave (slot 12)

Assignment of analogue output slaves 1 to 15 of AS-i master 1/2 to AS-i slave addresses

These parameters are only effective if parameters Analogue channels per out slave = 4 channels and Modify slave order analogue OUT = Enabled

Slave 1 AS-i master 1 Slave 2 AS-i master 1 ... Slave 31 AS-i master 1 Slave 1 AS-i master 2 Slave 2 AS-i master 2 ... Slave 31 AS-i master 2*

Fail-safe state Behaviour of the slave outputs if an interrupted fieldbus connection is detected

Reset outputs* =

All AS-i outputs are switched off in case of an interrupted Profinet connection (value = 0).

Hold outputs = The outputs are held in the last valid state that existed before the interrupted connection was detected.

Page 203: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

203

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Parameter Description Value range

Change byte order Change byte order in a word

Setting applies to all data of object class 4, instances 100 and 150

Disabled* = Byte order in a word remains unchanged.

Enabled = Byte order in a word is inverted.

AS-i parameter download Transmission of AS-i slave parameters from host to AC422S

Disabled* = The following AS-i parameter data is NOT sent to the AS-i system.

Enabled* = The following AS-i parameter data is sent to the AS-i system.

Param. slave 1(A) AS-i master 1 … Param. slave 31(A) AS-i master 1

Param. slave 1B AS-i master 1 … Param. slave 31B AS-i master 1

Param. slave 1(A) AS-i master 2 … Param. slave 31(A) AS-i master 2

Param. slave 1B AS-i master 2 … Param. slave 31B AS-i master 2

Parameters P3...P0 of the individual AS-i slaves

P3...P0 = 0x0 (= 0b0000) ... P3...P0 = 0xF (= 0b1111) for single slaves* P3...P0 = 0x7 (= 0b0111) for A/B slaves*

* ... Default settings

In 'Top-down' configuration mode, the device-specific parameters are set via the fieldbus projection software (→ Configuration mode: Top-down (→ page 372)).

>

Parameter setting via the configuration assembly object 9015

In the configuration mode "Top-Down" the parameter data is set in the EtherNet/IP-projection software (→ Configuration mode: Top-down (→ page 372)). By means of the configuration assembly object, the configuration is then transferred to the device and activated.

Only when a connection is established by the I/O scanner will the parameter data configured via the configuration assembly object be transferred to the device. Changes to the parameter data in the online mode of the controller will therefore only become effective after the next connection.

To trigger a new connection setup, perform one of the following actions:

Reboot the device

Briefly interrupt the EtherNet/IP connection between the I/O scanner and the device

Transfer the project from the higher-level controller to the device (download)

Restart the I/O scanner

The configuration in top-down mode includes the following parameters:

Parameters of the fieldbus slots (→ page 214)

Device-specific parameters (→ page 204)

Page 204: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

204

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Device-specific parameters 12812

Data points in the configuration assembly

Possible setting values

[hex]

Default values when using EDS

file

Description

with EDS without

EDS

AC1421 AC1422

C.Failsafe state n=60 00 X X Reset AS-i outputs

01 Hold AS-i outputs

C.Swap byteorder n=61 00 X X deactivated

01 activated

C.Analogue channels IN

n=62 01 1 channel

02 2 channels

04 X X 4 channels

0B 1 channel per A/B

C.Analogue channels OUT

n=63 01 1 channel

02 2 channels

04 X X 4 channels

0B 1 channel per A/B

C.Analogue IN order 1

n=64 00 X X deactivated

01 activated

C.1st analogue IN Slot 9 2

n=65 41 ... 5F 41 41

AS-i 1 slave 1... 31

81 ... 9F AS-i 2 slave 1... 31

C.2nd analogue IN Slot 9 2

n=66 41 ... 5F 42 42

AS-i 1 slave 1, 2 ... 31

81 ... 9F AS-i 2 slave 1... 31

C.3rd analogue IN Slot 9 2

n=67 41 ... 5F 43 43

AS-i 1 slave 1 ... 3 ... 31

81 ... 9F AS-i 2 slave 1 ... 31

C.4th analogue IN Slot 9 2

n=68 41 ... 5F 44 44

AS-i 1 slave 1 ... 4 ... 31

81 ... 9F AS-i 2 slave 1 ... 31

C.5th analogue IN Slot 9 2

n=69 41 ... 5F 45 45

AS-i 1 slave 1 ... 5 ... 31

81 ... 9F AS-i 2 slave 1 ... 31

C.6th analogue IN Slot 9 2

n=70 41 ... 5F

46 46

AS-i 1 slave 1 ... 6 ... 31

81 ... 9F AS-i 2 slave 1... 31

C.7th analogue IN Slot 9 2

n=71 41 ... 5F 47 47

AS-i 1 slave 1 ... 7 .... 31

81 ... 9F AS-i 2 slave 1 ... 31

C.8th analogue IN Slot 9 2

n=72 41 ... 5F 48 48

AS-i 1 slave 1 .. 8 ... 31

81 ... 9F AS-i 2 slave 1 ... 31

C.9th analogue IN Slot 9 2

n=73 41 ... 5F 49 49

AS-i 1 slave 1 ... 9 ... 31

81 ... 9F AS-i 2 slave 1 ... 31

C.10th analogue IN Slot 9 2

n=74 41 ... 5F 4A 4A

AS-i 1 slave 1 ... 10 ... 31

81 ... 9F AS-i 2 slave 1 ... 31

Page 205: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

205

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Data points in the configuration assembly

Possible setting values

[hex]

Default values when using EDS

file

Description

with EDS without

EDS

AC1421 AC1422

C.11th analogue IN Slot 9 2

n=75 41 ... 5F 4B 4B

AS-i 1 slave 1 ... 11 ... 31

81 ... 9F AS-i 2 slave 1 ... 31

C.12th analogue IN Slot 9 2

n=76 41 ... 5F 4C 4D

AS-i 1 slave 1 ... 12 ... 31

81 ... 9F AS-i 2 slave 1 ... 31

C.13th analogue IN Slot 9 2

n=77 41 ... 5F 4D 4D

AS-i 1 slave 1 ... 13 ... 31

81 ... 9F AS-i 2 slave 1 ... 31

C.14th analogue IN Slot 9 2

n=78 41 ... 5F 4E 4E

AS-i 1 slave 1 ... 14 ... 31

81 ... 9F AS-i 2 slave 1 ... 31

C.15th analogue IN Slot 9 2

n=79 41 ... 5F 4F 4F

AS-i 1 slave 1 ... 15 ... 31

81 ... 9F AS-i 2 slave 1 ... 31

C.1st analogue IN Slot 10 2

n=80 41 ... 5F 81 81

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 31

C.2nd analogue IN Slot 10 2

n=81 41 ... 5F 82 82

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1, 2 ... 31

C.3rd analogue IN Slot 10 2

n=82 41 ... 5F 83 83

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 3 ... 31

C.4th analogue IN Slot 10 2

n=83 41 ... 5F 84 84

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 4 ... 31

C.5th analogue IN Slot 10 2

n=84 41 ... 5F 85 85

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 5 ... 31

C.6th analogue IN Slot 10 2

n=85 41 ... 5F 86 86

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 6 ... 31

C.7th analogue IN Slot 10 2

n=86 41 ... 5F 87 87

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 7 ... 31

C.8th analogue IN Slot 10 2

n=87 41 ... 5F 88 88

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 8 ... 31

C.9th analogue IN Slot 10 2

n=88 41 ... 5F 89 89

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 9 ... 31

C.10th analogue IN Slot 10 2

n=89 41 ... 5F 8A 8A

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 10 ... 31

C.11th analogue IN Slot 10 2

n=90 41 ... 5F 8B 8B

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 11 ... 31

C.12th analogue IN Slot 10 2

n=91 41 ... 5F 8C 8C

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 12 ... 31

C.13th analogue IN Slot 10 2

n=92 41 ... 5F 8D 8D

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 13 ... 31

C.14th analogue IN n=93 41 ... 5F 8E 8E AS-i 1 slave 1 ... 31

Page 206: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

206

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Data points in the configuration assembly

Possible setting values

[hex]

Default values when using EDS

file

Description

with EDS without

EDS

AC1421 AC1422

Slot 10 2 81 ... 9F AS-i 2 slave 1 ... 14 ... 31

C.15th analogue IN Slot 10 2

n=94 41 ... 5F 8F 8F

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 15 ... 31

C.Analogue OUT order 1

n=95 00 X X deactivated

01 activated

C.1st analogue OUT Slot 11 3

n=96 41 ... 5F 50 50

AS-i 1 slave 1 ... 16 ...31

81 ... 9F AS-i 2 slave 1 ... 31

C.2nd analogue OUT

Slot 11 3

n=97 41 ... 5F 51 51

AS-i 1 slave 1 ... 17 ...31

81 ... 9F AS-i 2 slave 1 ... 31

C.3rd analogue OUT Slot 11 3

n=98 41 ... 5F 52 52

AS-i 1 slave 1 ... 18 ...31

81 ... 9F AS-i 2 slave 1 ... 31

C.4th analogue OUT Slot 11 3

n=99 41 ... 5F 53 53

AS-i 1 slave 1 ... 19 ...31

81 ... 9F AS-i 2 slave 1 ... 31

C.5th analogue OUT Slot 11 3

n=100 41 ... 5F 54 54

AS-i 1 slave 1 ... 20 ...31

81 ... 9F AS-i 2 slave 1 ... 31

C.6th analogue OUT Slot 11 3

n=101 41 ... 5F 55 55

AS-i 1 slave 1 ... 21 ...31

81 ... 9F AS-i 2 slave 1 ... 31

C.7th analogue OUT Slot 11 3

n=102 41 ... 5F 56 56

AS-i 1 slave 1 ... 22 ... 31

81 ... 9F AS-i 2 slave 1 ... 31

C.8th analogue OUT Slot 11 3

n=103 41 ... 5F 57 57

AS-i 1 slave 1 ... 23 ...31

81 ... 9F AS-i 2 slave 1 ... 31

C.9th analogue OUT Slot 11 3

n=104 41 ... 5F 58 58

AS-i 1 slave 1 ... 24 ...31

81 ... 9F AS-i 2 slave 1 ... 31

C.10th analogue OUT slot 11 3

n=105 41 ... 5F 59 59

AS-i 1 slave 1 ... 25 ...31

81 ... 9F AS-i 2 slave 1 ... 31

C.11th analogue OUT slot 11 3

n=106 41 ... 5F 5A 5A

AS-i 1 slave 1 ... 26 ...31

81 ... 9F AS-i 2 slave 1 ... 31

C.12th analogue OUT slot 11 3

n=107 41 ... 5F 5B 5B

AS-i 1 slave 1 ... 27 ...31

81 ... 9F AS-i 2 slave 1 ... 31

C.13th analogue OUT slot 11 3

n=108 41 ... 5F 5C 5C

AS-i 1 slave 1 ... 28 ...31

81 ... 9F AS-i 2 slave 1 ... 31

C.14th analogue OUT slot 11 3

n=109 41 ... 5F 5D 5D

AS-i 1 slave 1 ... 29 ...31

81 ... 9F AS-i 2 slave 1 ... 31

C.15th analogue OUT slot 11 3

n=110 41 ... 5F 5E 5E

AS-i 1 slave 1 ... 30, 31

81 ... 9F AS-i 2 slave 1 ... 31

C.1st analogue OUT Slot 12 3

n=111 41 ... 5F 91 91

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 16 ... 31

Page 207: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

207

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Data points in the configuration assembly

Possible setting values

[hex]

Default values when using EDS

file

Description

with EDS without

EDS

AC1421 AC1422

C.2nd analogue OUT

Slot 12 3

n=112 41 ... 5F 92 92

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 17 ... 31

C.3rd analogue OUT Slot 12 3

n=113 41 ... 5F 93 93

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 18 ... 31

C.4th analogue OUT Slot 12 3

n=114 41 ... 5F 94 94

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 19 ... 31

C.5th analogue OUT slot 12 3

n=115 41 ... 5F

95 95

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 20 ... 31

C.6th analogue OUT slot 12 3

n=116 41 ... 5F 96 96

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 21 ... 31

C.7th analogue OUT slot 12 3

n=117 41 ... 5F 97 97

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 22 ... 31

C.8th analogue OUT slot 12 3

n=118 41 ... 5F 98 98

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 23 ... 31

C.9th analogue OUT slot 12 3

n=119 41 ... 5F 99 99

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 24 ... 31

C.10th analogue OUT slot 12 3

n=120 41 ... 5F 9A 9A

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 25 ... 31

C.11th analogue OUT slot 12 3

n=121 41 ... 5F 9B 9B

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 26 ... 31

C.12th analogue OUT slot 12 3

n=122 41 ... 5F 9B 9B

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 27 ... 31

C.13th analogue OUT slot 12 3

n=123 41 ... 5F 9C 9C

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 28 ... 31

C.14th analogue OUT slot 12 3

n=124 41 ... 5F 9D 9D

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 29 ... 31

C.15th analogue OUT slot 12 3

n=125 41 ... 5F 9E 9E

AS-i 1 slave 1 ... 31

81 ... 9F AS-i 2 slave 1 ... 30, 31

C.AS-i Parameter Download 1

n=126 00 X X deactivated

01 activated

C.Parameter slave 1(A) AS-i 1 4

n=127 00 ... 0F 0F 0F Parameter for AS-i slave 1(A)

C.Parameter slave 2(A) AS-i 1 4

n=128 00 ... 0F 0F 0F Parameter for AS-i 1 slave 2(A)

C.Parameter slave 3(A) AS-i 1 4

n=129 00 ... 0F 0F 0F Parameter for AS-i 1 slave 3(A)

C.Parameter slave 4(A) AS-i 1 4

n=130 00 ... 0F 0F 0F Parameter for AS-i 1 slave 4(A)

Page 208: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

208

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Data points in the configuration assembly

Possible setting values

[hex]

Default values when using EDS

file

Description

with EDS without

EDS

AC1421 AC1422

C.Parameter slave 5(A) AS-i 1 4

n=131 00 ... 0F 0F 0F Parameter for AS-i 1 slave 5(A)

C.Parameter slave 6(A) AS-i 1 4

n=132 00 ... 0F 0F 0F Parameter for AS-i 1 slave 6(A)

C.Parameter slave 7(A) AS-i 1 4

n=133 00 ... 0F 0F 0F Parameter for AS-i 1 slave 7(A)

C.Parameter slave 8(A) AS-i 1 4

n=134 00 ... 0F 0F 0F Parameter for AS-i 1 slave 8(A)

C.Parameter slave 9(A) AS-i 1 4

n=135 00 ... 0F 0F 0F Parameter for AS-i 1 slave 9(A)

C.Parameter slave 10(A) AS-i 1 4

n=136 00 ... 0F 0F 0F Parameter for AS-i 1 slave 10(A)

C.Parameter slave 11(A) AS-i 1 4

n=137 00 ... 0F 0F 0F Parameter for AS-i 1 slave 11(A)

C.Parameter slave 12(A) AS-i 1 4

n=138 00 ... 0F 0F 0F Parameter for AS-i 1 slave 12(A)

C.Parameter slave 13(A) AS-i 1 4

n=139 00 ... 0F 0F 0F Parameter for AS-i 1 slave 13(A)

C.Parameter slave 14(A) AS-i 1 4

n=140 00 ... 0F 0F 0F Parameter for AS-i 1 slave 14(A)

C.Parameter slave 15(A) AS-i 1 4

n=141 00 ... 0F 0F 0F Parameter for AS-i slave 15(A)

C.Parameter slave 16(A) AS-i 1 4

n=142 00 ... 0F 0F 0F Parameter for AS-i 1 slave 16(A)

C.Parameter slave 17(A) AS-i 1 4

n=143 00 ... 0F 0F 0F Parameter for AS-i 1 slave 17(A)

C.Parameter slave 18(A) AS-i 1 4

n=144 00 ... 0F 0F 0F Parameter for AS-i 1 slave 18(A)

C.Parameter slave 19(A) AS-i 1 4

n=145 00 ... 0F 0F 0F Parameter for AS-i 1 slave 19(A)

C.Parameter slave 20(A) AS-i 1 4

n=146 00 ... 0F 0F 0F Parameter for AS-i 1 slave 20(A)

C.Parameter slave 21(A) AS-i 1 4

n=147 00 ... 0F 0F 0F Parameter for AS-i 1 slave 21(A)

C.Parameter slave 22(A) AS-i 1 4

n=148 00 ... 0F 0F 0F Parameter for AS-i 1 slave 22(A)

C.Parameter slave 23(A) AS-i 1 4

n=149 00 ... 0F 0F 0F Parameter for AS-i 1 slave 23(A)

C.Parameter slave 24(A) AS-i 1 4

n=150 00 ... 0F 0F 0F Parameter for AS-i 1 slave 24(A)

C.Parameter slave 25(A) AS-i 1 4

n=151 00 ... 0F 0F 0F Parameter for AS-i 1 slave 25(A)

C.Parameter slave 26(A) AS-i 1 4

n=152 00 ... 0F 0F 0F Parameter for AS-i 1 slave 26(A)

C.Parameter slave 27(A) AS-i 1 4

n=153 00 ... 0F 0F 0F Parameter for AS-i 1 slave 27(A)

Page 209: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

209

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Data points in the configuration assembly

Possible setting values

[hex]

Default values when using EDS

file

Description

with EDS without

EDS

AC1421 AC1422

C.Parameter slave 28(A) AS-i 1 4

n=154 00 ... 0F 0F 0F Parameter for AS-i 1 slave 28(A)

C.Parameter slave 29(A) AS-i 1 4

n=155 00 ... 0F 0F 0F Parameter for AS-i 1 slave 29(A)

C.Parameter slave 30(A) AS-i 1 4

n=156 00 ... 0F 0F 0F Parameter for AS-i 1 slave 30(A)

C.Parameter slave 31(A) AS-i 1 4

n=157 00 ... 0F 0F 0F Parameter for AS-i 1 slave 31(A)

C.Parameter slave 1B AS-i 1 4

n=158 00 ... 0F 07 07 Parameter for AS-i 1 slave 1B

C.Parameter slave 2B AS-i 1 4

n=159 00 ... 0F 07 07 Parameter for AS-i 1 slave 2B

C.Parameter slave 3B AS-i 1 4

n=160 00 ... 0F 07 07 Parameter for AS-i 1 slave 3B

C.Parameter slave 4B AS-i 1 4

n=161 00 ... 0F 07 07 Parameter for AS-i 1 slave 4B

C.Parameter slave 5B AS-i 1 4

n=162 00 ... 0F 07 07 Parameter for AS-i 1 slave 5B

C.Parameter slave 6B AS-i 1 4

n=163 00 ... 0F 07 7 Parameter for AS-i 1 slave 6B

C.Parameter slave 7B AS-i 1 4

n=1564

00 ... 0F 07 07 Parameter for AS-i 1 slave 7B

C.Parameter slave 8B AS-i 1 4

n=165 00 ... 0F 07 07 Parameter for AS-i 1 slave 8B

C.Parameter slave 9B AS-i 1 4

n=166 00 ... 0F 07 07 Parameter for AS-i 1 slave 9B

C.Parameter slave 10B AS-i 1 4

n=167 00 ... 0F 07 07 Parameter for AS-i 1 slave 10B

C.Parameter slave 11B AS-i 1 4

n=168 00 ... 0F 07 07 Parameter for AS-i 1 slave 11B

C.Parameter slave 12B AS-i 1 4

n=169 00 ... 0F 07 07 Parameter for AS-i 1 slave 12B

C.Parameter slave 13B AS-i 1 4

n=170 00 ... 0F 07 07 Parameter for AS-i 1 slave 13B

C.Parameter slave 14B AS-i 1 4

n=171 00 ... 0F 07 07 Parameter for AS-i 1 slave 14B

C.Parameter slave 15B AS-i 1 4

n=172 00 ... 0F 07 07 Parameter for AS-i 1 slave 15B

C.Parameter slave 16B AS-i 1 4

n=173 00 ... 0F 07 07 Parameter for AS-i 1 slave 16B

C.Parameter slave 17B AS-i 1 4

n=174 00 ... 0F 07 07 Parameter for AS-i 1 slave 17B

C.Parameter slave 18B AS-i 1 4

n=175 00 ... 0F 07 07 Parameter for AS-i 1 slave 18B

C.Parameter slave 19B AS-i 1 4

n=176 00 ... 0F 07 07 Parameter for AS-i 1 slave 19B

Page 210: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

210

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Data points in the configuration assembly

Possible setting values

[hex]

Default values when using EDS

file

Description

with EDS without

EDS

AC1421 AC1422

C.Parameter slave 20B AS-i 1 4

n=177 00 ... 0F 07 07 Parameter for AS-i 1 slave 20B

C.Parameter slave 21B AS-i 1 4

n=178 00 ... 0F 07 07 Parameter for AS-i 1 slave 21B

C.Parameter slave 22B AS-i 1 4

n=179 00 ... 0F 07 07 Parameter for AS-i 1 slave 22B

C.Parameter slave 23B AS-i 1 4

n=180 00 ... 0F 07 07 Parameter for AS-i 1 slave 23B

C.Parameter slave 24B AS-i 1 4

n=181 00 ... 0F 07 07 Parameter for AS-i 1 slave 24B

C.Parameter slave 25B AS-i 1 4

n=182 00 ... 0F 07 07 Parameter for AS-i 1 slave 25B

C.Parameter slave 26B AS-i 1 4

n=183 00 ... 0F 07 07 Parameter for AS-i 1 slave 26B

C.Parameter slave 27B AS-i 1 4

n=184 00 ... 0F 07 07 Parameter for AS-i 1 slave 27B

C.Parameter slave 28B AS-i 1 4

n=185 00 ... 0F 07 07 Parameter for AS-i 1 slave 28B

C.Parameter slave 29B AS-i 1 4

n=186 00 ... 0F 07 07 Parameter for AS-i 1 slave 29B

C.Parameter slave 30B AS-i 1 4

n=187 00 ... 0F 07 07 Parameter for AS-i 1 slave 30B

C.Parameter slave 31B AS-i 1 4

n=188 00 ... 0F 07 07 Parameter for AS-i 1 slave 31B

C.Parameter slave 1(A) AS-i 2 4

n=189 00 ... 0F 0F 0F Parameter for AS-i 2 slave 1(A)

C.Parameter slave 2(A) AS-i 2 4

n=190 00 ... 0F 0F 0F Parameter for AS-i 2 slave 2(A)

C.Parameter slave 3(A) AS-i 2 4

n=191 00 ... 0F 0F 0F Parameter for AS-i 2 slave 3(A)

C.Parameter slave 4(A) AS-i 2 4

n=192 00 ... 0F 0F 0F Parameter for AS-i 2 slave 4(A)

C.Parameter slave 5(A) AS-i 2 4

n=193 00 ... 0F 0F 0F Parameter for AS-i 2 slave 5(A)

C.Parameter slave 6(A) AS-i 2 4

n=194 00 ... 0F 0F 0F Parameter for AS-i 2 slave 6(A)

C.Parameter slave 7(A) AS-i 2 4

n=195 00 ... 0F 0F 0F Parameter for AS-i 2 slave 7(A)

C.Parameter slave 8(A) AS-i 2 4

n=196 00 ... 0F 0F 0F Parameter for AS-i 2 slave 8(A)

C.Parameter slave 9(A) AS-i 2 4

n=197 00 ... 0F 0F 0F Parameter for AS-i 2 slave 9(A)

C.Parameter slave 10(A) AS-i 2 4

n=198 00 ... 0F 0F 0F Parameter for AS-i 2 slave 10(A)

C.Parameter slave 11(A) AS-i 2 4

n=199 00 ... 0F 0F 0F Parameter for AS-i 2 slave 11(A)

Page 211: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

211

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Data points in the configuration assembly

Possible setting values

[hex]

Default values when using EDS

file

Description

with EDS without

EDS

AC1421 AC1422

C.Parameter slave 12(A) AS-i 2 4

n=200 00 ... 0F 0F 0F Parameter for AS-i 2 slave 12(A)

C.Parameter slave 13(A) AS-i 2 4

n=201 00 ... 0F 0F 0F Parameter for AS-i 2 slave 13(A)

C.Parameter slave 14(A) AS-i 2 4

n=202 00 ... 0F 0F 0F Parameter for AS-i 2 slave 14(A)

C.Parameter slave 15(A) AS-i 2 4

n=203 00 ... 0F 0F 0F Parameter for AS-i 2 slave 15(A)

C.Parameter slave 16(A) AS-i 2 4

n=204 00 ... 0F 0F 0F Parameter for AS-i 2 slave 16(A)

C.Parameter slave 17(A) AS-i 2 4

n=205 00 ... 0F 0F 0F Parameter for AS-i 2 slave 17(A)

C.Parameter slave 18(A) AS-i 2 4

n=206 00 ... 0F 0F 0F Parameter for AS-i 2 slave 18(A)

C.Parameter slave 19(A) AS-i 2 4

n=207 00 ... 0F 0F 0F Parameter for AS-i 2 slave 19(A)

C.Parameter slave 20(A) AS-i 2 4

n=208 00 ... 0F 0F 0F Parameter for AS-i 2 slave 20(A)

C.Parameter slave 21(A) AS-i 2 4

n=209 00 ... 0F 0F 0F Parameter for AS-i 2 slave 21(A)

C.Parameter slave 22(A) AS-i 2 4

n=210 00 ... 0F 0F 0F Parameter for AS-i 2 slave 22(A)

C.Parameter slave 23(A) AS-i 2 4

n=211 00 ... 0F 0F 0F Parameter for AS-i 2 slave 23(A)

C.Parameter slave 24(A) AS-i 2 4

n=212 00 ... 0F 0F 0F Parameter for AS-i 2 slave 24(A)

C.Parameter slave 25(A) AS-i 2 4

n=213 00 ... 0F 0F 0F Parameter for AS-i 2 slave 25(A)

C.Parameter slave 26(A) AS-i 2 4

n=214 00 ... 0F 0F 0F Parameter for AS-i 2 slave 26(A)

C.Parameter slave 27(A) AS-i 2 4

n=215 00 ... 0F 0F 0F Parameter for AS-i 2 slave 27(A)

C.Parameter slave 28(A) AS-i 2 4

n=216 00 ... 0F 0F 0F Parameter for AS-i 2 slave 28(A)

C.Parameter slave 29(A) AS-i 2 4

n=217 00 ... 0F 0F 0F Parameter for AS-i 2 slave 29(A)

C.Parameter slave 30(A) AS-i 2 4

n=218 00 ... 0F 0F 0F Parameter for AS-i 2 slave 30(A)

C.Parameter slave 31(A) AS-i 2 4

n=219 00 ... 0F 0F 0F Parameter for AS-i 2 slave 31(A)

C.Parameter slave 1B AS-i 2 4

n=220 00 ... 0F 07 07 Parameter for AS-i 2 slave 1B

C.Parameter slave 2B AS-i 2 4

n=221 00 ... 0F 07 07 Parameter for AS-i 2 slave 2B

C.Parameter slave 3B AS-i 2 4

n=222 00 ... 0F 07 07 Parameter for AS-i 2 slave 3B

Page 212: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

212

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Data points in the configuration assembly

Possible setting values

[hex]

Default values when using EDS

file

Description

with EDS without

EDS

AC1421 AC1422

C.Parameter slave 4B AS-i 2 4

n=223 00 ... 0F 07 07 Parameter for AS-i 2 slave 4B

C.Parameter slave 5B AS-i 2 4

n=224 00 ... 0F 07 07 Parameter for AS-i 2 slave 5B

C.Parameter slave 6B AS-i 2 4

n=225 00 ... 0F 07 07 Parameter for AS-i 2 slave 6B

C.Parameter slave 7B AS-i 2 4

n=226 00 ... 0F 07 07 Parameter for AS-i 2 slave 7B

C.Parameter slave 8B AS-i 2 4

n=227 00 ... 0F 07 07 Parameter for AS-i 2 slave 8B

C.Parameter slave 9B AS-i 2 4

n=228 00 ... 0F 07 07 Parameter for AS-i 2 slave 9B

C.Parameter slave 10B AS-i 2 4

n=229 00 ... 0F 07 07 Parameter for AS-i 2 slave 10B

C.Parameter slave 11B AS-i 2 4

n=230 00 ... 0F 07 07 Parameter for AS-i 2 slave 11B

C.Parameter slave 12B AS-i 2 4

n=231 00 ... 0F 07 07 Parameter for AS-i 2 slave 12B

C.Parameter slave 13B AS-i 2 4

n=232 00 ... 0F 07 07 Parameter for AS-i 2 slave 13B

C.Parameter slave 14B AS-i 2 4

n=233 00 ... 0F 07 07 Parameter for AS-i 2 slave 14B

C.Parameter slave 15B AS-i 2 4

n=234 00 ... 0F 07 07 Parameter for AS-i 2 slave 15B

C.Parameter slave 16B AS-i 2 4

n=235 00 ... 0F 07 07 Parameter for AS-i 2 slave 16B

C.Parameter slave 17B AS-i 2 4

n=236 00 ... 0F 07 07 Parameter for AS-i 2 slave 17B

C.Parameter slave 18B AS-i 2 4

n=237 00 ... 0F 07 07 Parameter for AS-i 2 slave 18B

C.Parameter slave 19B AS-i 2 4

n=238 00 ... 0F 07 07 Parameter for AS-i 2 slave 19B

C.Parameter slave 20B AS-i 2 4

n=239 00 ... 0F 07 07 Parameter for AS-i 2 slave 20B

C.Parameter slave 21B AS-i 2 4

n=240 00 ... 0F 07 07 Parameter for AS-i 2 slave 21B

C.Parameter slave 22B AS-i 2 4

n=241 00 ... 0F 07 07 Parameter for AS-i 2 slave 22B

C.Parameter slave 23B AS-i 2 4

n=242 00 ... 0F 07 07 Parameter for AS-i 2 slave 23B

C.Parameter slave 24B AS-i 2 4

n=243 00 ... 0F 07 07 Parameter for AS-i 2 slave 24B

C.Parameter slave 25B AS-i 2 4

n=244 00 ... 0F 07 07 Parameter for AS-i 2 slave 25B

C.Parameter slave 26B AS-i 2 4

n=245 00 ... 0F 07 07 Parameter for AS-i 2 slave 26B

Page 213: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

213

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Data points in the configuration assembly

Possible setting values

[hex]

Default values when using EDS

file

Description

with EDS without

EDS

AC1421 AC1422

C.Parameter slave 27B AS-i 2 4

n=246 00 ... 0F 07 07 Parameter for AS-i 2 slave 27B

C.Parameter slave 28B AS-i 2 4

n=247 00 ... 0F 07 07 Parameter for AS-i 2 slave 28B

C.Parameter slave 29B AS-i 2 4

n=248 00 ... 0F 07 07 Parameter for AS-i 2 slave 29B

C.Parameter slave 30B AS-i 2 4

n=249 00 ... 0F 07 07 Parameter for AS-i 2 slave 30B

C.Parameter slave 31B AS-i 2 4

n=250 00 ... 0F 07 07 Parameter for AS-i 2 slave 31B

Legend:

1 = Free slave assignment only possible in top-down mode. 2 = Parameter can only be set if [C.analogue IN order] = 01 and [C.Analogue channels IN] = 4 channels 3 = Parameter can only be set if [C.analogue OUT order] = 01 and [C.Analogue channels OUT] = 4 channels 4 = Parameter can only be set if [C.AS-i param. download] = 01

Page 214: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

214

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Parameters of the fieldbus slots 12811

NOTICE

Risk of data loss!

For the transmission of cyclic process data between the device and the EtherNet/IP PLC, a limited number of data words is available for each direction of transmission:

Input data (= modules 1, 3, 5, 7, 9, 10, 13, 14): 248 words

Output data (= modules 2, 4, 6, 8, 11, 12, 15): 248 words

If the EtherNet/IP modules have been parameterised in such a way that the cyclic input and output data comprise more than 248 words per direction of transmission, any data from the 249th word will not be transmitted and will therefore be lost.

► Parameterise the EtherNet/IP modules in a way to ensure that the input and output data do not exceed the maximum number of words to be transmitted!

Slot

[dec]

Data points in the configuration

assembly

Possible setting values [hex]

Default values when using EDS

file

Description

with EDS

without EDS

n+3 n+2 n+1 n AC1421 AC1422

1 C.Slot1 n=0 00 00 00 00 Empty module

00 00 10 02 1: digital IN AS-i 1, Slaves 01(A) ... 03(A)

00 00 10 04 1: digital IN AS-i 1, Slaves 01(A) ... 07(A)

00 00 10 06 1: digital IN AS-i 1, Slaves 01(A) ... 11(A)

00 00 10 08 1: digital IN AS-i 1, Slaves 01(A) ... 15(A)

00 00 10 0A 1: digital IN AS-i 1, Slaves 01(A) ... 19(A)

00 00 10 0C 1: digital IN AS-i 1, Slaves 01(A) ... 23(A)

00 00 10 0E 1: digital IN AS-i 1, Slaves 01(A) ... 27(A)

00 00 10 10 X X 1: digital IN AS-i 1, Slaves 01(A) ... 31(A)

2 C.Slot2 n=4 00 00 00 00 Empty module

00 00 20 02 2: digital OUT AS-i 1, Slaves 01(A) ... 03(A)

00 00 20 04 2: digital OUT AS-i 1, Slaves 01(A) ... 07(A)

00 00 20 06 2: digital OUT AS-i 1, Slaves 01(A) ... 11(A)

00 00 20 08 2: digital OUT AS-i 1, Slaves 01(A) ... 15(A)

00 00 20 0A 2: digital OUT AS-i 1, Slaves 01(A) ... 19(A)

00 00 20 0C 2: digital OUT AS-i 1, Slaves 01(A) ... 23(A)

00 00 20 0E 2: digital OUT AS-i 1, Slaves 01(A) ... 27(A)

00 00 20 10 X X 2: digital OUT AS-i 1, Slaves 01(A) ... 31(A)

3 C.Slot3 n=8 00 00 00 00 X Empty module

00 02 10 02 3: digital IN AS-i 2, Slaves 01(A) ... 03(A)

00 02 10 04 3: digital IN AS-i 2, Slaves 01(A) ... 07(A)

00 02 10 06 3: digital IN AS-i 2, Slaves 01(A) ... 11(A)

00 02 10 08 3: digital IN AS-i 2, Slaves 01(A) ... 15(A)

Page 215: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

215

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Slot

[dec]

Data points in the configuration

assembly

Possible setting values [hex]

Default values when using EDS

file

Description

with EDS

without EDS

n+3 n+2 n+1 n AC1421 AC1422

00 02 10 0A 3: digital IN AS-i 2, Slaves 01(A) ... 19(A)

00 02 10 0C 3: digital IN AS-i 2, Slaves 01(A) ... 23(A)

00 02 10 0E 3: digital IN AS-i 2, Slaves 01(A) ... 27(A)

00 02 10 10 X 3: digital IN AS-i 2, Slaves 01(A) ... 31(A)

4 C.Slot4 n=12 00 00 00 00 X Empty module

00 02 20 02 4: digital OUT AS-i 2, Slaves 01(A) ... 03(A)

00 02 20 04 4: digital OUT AS-i 2, Slaves 01(A) ... 07(A)

00 02 20 06 4: digital OUT AS-i 2, Slaves 01(A) ... 11(A)

00 02 20 08 4: digital OUT AS-i 2, Slaves 01(A) ... 15(A)

00 02 20 0A 4: digital OUT AS-i 2, Slaves 01(A) ... 19(A)

00 02 20 0C 4: digital OUT AS-i 2, Slaves 01(A) ... 23(A)

00 02 20 0E 4: digital OUT AS-i 2, Slaves 01(A) ... 27(A)

00 02 20 10 X 4: digital OUT AS-i 2, Slaves 01(A) ... 31(A)

5 C.Slot5 n=16 00 00 00 00 Empty module

00 01 10 02 5: digital IN AS-i 1, Slaves 01B ... 03B

00 01 10 04 5: digital IN AS-i 1, Slaves 01B ... 07B

00 01 10 06 5: digital IN AS-i 1, Slaves 01B ... 11B

00 01 10 08 5: digital IN AS-i 1, Slaves 01B ... 15B

00 01 10 0A 5: digital IN AS-i 1, Slaves 01B ... 19B

00 01 10 0C 5: digital IN AS-i 1, Slaves 01B ... 23B

00 01 10 0E 5: digital IN AS-i 1, Slaves 01B ... 27B

00 01 10 10 X X 5: digital IN AS-i 1, Slaves 01B ... 31B

6 C.Slot6 n=20 00 00 00 00 Empty module

00 01 20 02 6: digital OUT AS-i 1, Slaves 01B ... 03B

00 01 20 04 6: digital OUT AS-i 1, Slaves 01B ... 07B

00 01 20 06 6: digital OUT AS-i 1, Slaves 01B ... 11B

00 01 20 08 6: digital OUT AS-i 1, Slaves 01B ... 15B

00 01 20 0A 6: digital OUT AS-i 1, Slaves 01B ... 19B

00 01 20 0C 6: digital OUT AS-i 1, Slaves 01B ... 23B

00 01 20 0E 6: digital OUT AS-i 1, Slaves 01B ... 27B

00 01 20 10 X X 6: digital OUT AS-i 1, Slaves 01B ... 31B

7 C.Slot7 n=24 00 00 00 00 X Empty module

00 03 10 02 7: digital IN AS-i 2, Slaves 01B ... 03B

00 03 10 04 7: digital IN AS-i 2, Slaves 01B ... 07B

00 03 10 06 7: digital IN AS-i 2, Slaves 01B ... 11B

Page 216: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

216

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Slot

[dec]

Data points in the configuration

assembly

Possible setting values [hex]

Default values when using EDS

file

Description

with EDS

without EDS

n+3 n+2 n+1 n AC1421 AC1422

00 03 10 08 7: digital IN AS-i 2, Slaves 01B ... 15B

00 03 10 0A 7: digital IN AS-i 2, Slaves 01B ... 19B

00 03 10 0C 7: digital IN AS-i 2, Slaves 01B ... 23B

00 03 10 0E 7: digital IN AS-i 2, Slaves 01B ... 27B

00 03 10 10 X 7: digital IN AS-i 2, Slaves 01B ... 31B

8 C.Slot8 n=28 00 00 00 00 X Empty module

00 03 20 02 8: digital OUT AS-i 2, Slaves 01B ... 03B

00 03 20 04 8: digital OUT AS-i 2, Slaves 01B ... 07B

00 03 20 06 8: digital OUT AS-i 2, Slaves 01B ... 11B

00 03 20 08 8: digital OUT AS-i 2, Slaves 01B ... 15B

00 03 20 0A 8: digital OUT AS-i 2, Slaves 01B ... 19B

00 03 20 0C 8: digital OUT AS-i 2, Slaves 01B ... 23B

00 03 20 0E 8: digital OUT AS-i 2, Slaves 01B ... 27B

00 03 20 10 X 8: digital OUT AS-i 2, Slaves 01B ... 31B

9 C.Slot9 n=32 00 00 00 00 Empty module

00 00 50 08 9: analog IN range 1, 04 words

00 00 50 10 9: analog IN range 1, 08 words

00 00 50 18 9: analog IN range 1, 12 words

00 00 50 20 9: analog IN range 1, 16 words

00 00 50 28 9: analog IN range 1, 20 words

00 00 50 30 9: analog IN range 1, 24 words

00 00 50 38 9: analog IN range 1, 28 words

00 00 50 40 9: analog IN range 1, 32 words

00 00 50 48 9: analog IN range 1, 36 words

00 00 50 50 9: analog IN range 1, 40 words

00 00 50 58 9: analog IN range 1, 44 words

00 00 50 60 9: analog IN range 1, 48 words

00 00 50 68 9: analog IN range 1, 52 words

00 00 50 70 9: analog IN range 1, 56 words

00 00 50 78 X X 9: analog IN range 1, 60 words

10 C.Slot10

n=36 00 00 00 00 X Empty module

00 00 50 08 10: analog IN range 2, 04 words

00 00 50 10 10: analog IN range 2, 08 words

00 00 50 18 10: analog IN range 2, 12 words

00 00 50 20 10: analog IN range 2, 16 words

Page 217: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

217

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Slot

[dec]

Data points in the configuration

assembly

Possible setting values [hex]

Default values when using EDS

file

Description

with EDS

without EDS

n+3 n+2 n+1 n AC1421 AC1422

00 00 50 28 10: analog IN range 2, 20 words

00 00 50 30 10: analog IN range 2, 24 words

00 00 50 38 10: analog IN range 2, 28 words

00 00 50 40 10: analog IN range 2, 32 words

00 00 50 48 10: analog IN range 2, 36 words

00 00 50 50 10: analog IN range 2, 40 words

00 00 50 58 10: analog IN range 2, 44 words

00 00 50 60 10: analog IN range 2, 48 words

00 00 50 68 10: analog IN range 2, 52 words

00 00 50 70 10: analog IN range 2, 56 words

00 00 50 78 X 10: analog IN range 2, 60 words

11 C.Slot11

n=40 00 00 00 00 Empty module

00 00 60 08 11: analog OUT range 1, 04 words

00 00 60 10 11: analog OUT range 1, 08 words

00 00 60 18 11: analog OUT range 1, 12 words

00 00 60 20 11: analog OUT range 1, 16 words

00 00 60 28 11: analog OUT range 1, 20 words

00 00 60 30 11: analog OUT range 1, 24 words

00 00 60 38 11: analog OUT range 1, 28 words

00 00 60 40 11: analog OUT range 1, 32 words

00 00 60 48 11: analog OUT range 1, 36 words

00 00 60 50 11: analog OUT range 1, 40 words

00 00 60 58 11: analog OUT range 1, 44 words

00 00 60 60 11: analog OUT range 1, 48 words

00 00 60 68 11: analog OUT range 1, 52 words

00 00 60 70 11: analog OUT range 1, 56 words

00 00 60 78 X X 11: analog OUT range 1, 60 words

12 C.Slot12

n=44 00 00 00 00 X Empty module

00 00 60 08 12: analog OUT range 2, 04 words

00 00 60 10 12: analog OUT range 2, 08 words

00 00 60 18 12: analog OUT range 2, 12 words

00 00 60 20 12: analog OUT range 2, 16 words

00 00 60 28 12: analog OUT range 2, 20 words

00 00 60 30 12: analog OUT range 2, 24 words

00 00 60 38 12: analog OUT range 2, 28 words

00 00 60 40 12: analog OUT range 2, 32 words

Page 218: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

218

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Slot

[dec]

Data points in the configuration

assembly

Possible setting values [hex]

Default values when using EDS

file

Description

with EDS

without EDS

n+3 n+2 n+1 n AC1421 AC1422

00 00 60 48 12: analog OUT range 2, 36 words

00 00 60 50 12: analog OUT range 2, 40 words

00 00 60 58 12: analog OUT range 2, 44 words

00 00 60 60 12: analog OUT range 2, 48 words

00 00 60 68 12: analog OUT range 2, 52 words

00 00 60 70 12: analog OUT range 2, 56 words

00 00 60 78 X 12: analog OUT range 2, 60 words

13 C.Slot13

n=48 00 00 00 00 Empty module

00 00 D0 32 X 13: AC1421 (25 words)

00 02 D0 64 X 13: AC1422 (50 words)

00 00 D0 1A 13: AC13x7 AS-i 1 (13 words)

00 02 D0 34 13: AC13x7 AS-i 1+2 (26 words)

14 C.Slot14

n=52 00 00 00 00 X X Empty module

00 04 10 08 14: Inputs from AC142n-PLC, 4 words

00 04 10 10 14: Inputs from AC142n-PLC, 8 words

00 04 10 18 14: Inputs from AC142n-PLC, 12 words

00 04 10 20 14: Inputs from AC142n-PLC, 16 words

00 04 10 28 14: Inputs from AC142n-PLC, 20 words

00 04 10 30 14: Inputs from AC142n-PLC, 24 words

00 04 10 38 14: Inputs from AC142n-PLC, 28 words

00 04 10 40 14: Inputs from AC142n-PLC, 32 words

00 04 10 48 14: Inputs from AC142n-PLC, 36 words

00 04 10 50 14: Inputs from AC142n-PLC, 40 words

00 04 10 58 14: Inputs from AC142n-PLC, 44 words

00 04 10 60 14: Inputs from AC142n-PLC, 48 words

00 04 10 68 14: Inputs from AC142n-PLC, 52 words

00 04 10 70 14: Inputs from AC142n-PLC, 56 words

00 04 10 78 14: Inputs from AC142n-PLC, 60 words

00 04 10 98 14: Inputs from AC142n-PLC, 76 words

00 04 10 B8 14: Inputs from AC142n-PLC, 92 words

Page 219: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

219

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Slot

[dec]

Data points in the configuration

assembly

Possible setting values [hex]

Default values when using EDS

file

Description

with EDS

without EDS

n+3 n+2 n+1 n AC1421 AC1422

00 04 10 D8 14: Inputs from AC142n-PLC, 108 words

00 04 10 F0 14: Inputs from AC142n-PLC, 120 words

15 C.Slot15

n=56 00 00 00 00 X X Empty module

00 04 20 08 15: Outputs to AC142n-PLC, 4 words

00 04 20 10 15: Outputs to AC142n-PLC, 8 words

00 04 20 18 15: Outputs to AC142n-PLC, 12 words

00 04 20 20 15: Outputs to AC142n-PLC, 16 words

00 04 20 28 15: Outputs to AC142n-PLC, 20 words

00 04 20 30 15: Outputs to AC142n-PLC, 24 words

00 04 20 38 15: Outputs to AC142n-PLC, 28 words

00 04 20 40 15: Outputs to AC142n-PLC, 32 words

00 04 20 48 15: Outputs to AC142n-PLC, 36 words

00 04 20 50 15: Outputs to AC142n-PLC, 40 words

00 04 20 58 15: Outputs to AC142n-PLC, 44 words

00 04 20 60 15: Outputs to AC142n-PLC, 48 words

00 04 20 68 15: Outputs to AC142n-PLC, 52 words

00 04 20 70 15: Outputs to AC142n-PLC, 56 words

00 04 20 78 15: Outputs to AC142n-PLC, 60 words

00 04 20 98 15: Outputs to AC142n-PLC, 76 words

00 04 20 B8 15: Outputs to AC142n-PLC, 92 words

00 04 20 D8 15: Outputs to AC142n-PLC, 108 words

00 04 20 F0 15: Outputs to AC142n-PLC, 120 words

Page 220: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

220

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Derivation of parameter values for free slave assignment 17744

The following table shows the derivation of parameter values for a free assignment of slaves within the analogue areas.

A free assignment of analogue slaves in slots 9...12 can only be applied if the parameters [C.Analogue channels IN] and [C.Analogue channels OUT] are set to the value 4 channels!

Byte

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

AS-i 2 AS-i 1 Reserved Slave address (1...31)

Legend:

Master: AS-i master 1 = 0x40

AS-i master 2 = 0x80

Slave: Slave 1 = 0x01 ...

Slave 31 = 0x1F

Derivation: byte value = master + slave (→ Examples (→ page 220))

>

Examples 17745

Byte

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

1 0 0 0x02

= 0x82 = AS-i master 2, slave 2

0 1 0 0x1F

= 0x5F = AS-i master 1, slave 31

>

EDS-file 12789

The EDS file (Electronic Data Sheet)is used to easily integrate the AC422S in a fieldbus projecting software. The EDS supplies a profile of the fieldbus device in form of an ASCII file. It describes all features of the device such as communication parameters and objects.

The EDS file is saved in the device. It can be downloaded directly to the configuration PC via the web interface (→ Download the device and I/O description (→ page 127)).

Page 221: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

221

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

9.6.4 Cyclic data 12417

The cyclic process data are updated through the fieldbus mechanisms at regular intervals. They belong to the category of implicit messaging (→ Implicit Messaging) and are therefore real-time capable.

Slots combine the process data of several AS-i slaves. The following tables show the available EtherNet/IP modules.

The user must set the content and length of the cyclically transmitted data either at the device (→ Configuration mode: Independent (→ page 377)) or in the EtherNet/IP projection software by means the configuration assembly object (→ Configuration mode: Top-down (→ page 372), → Parameter setting via the configuration assembly object (→ page 203)).

Page 222: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

222

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

EtherNet/IP modules 12419

NOTICE

Risk of data loss!

For the transmission of cyclic process data between the device and the EtherNet/IP PLC, a limited number of data words is available for each direction of transmission:

Input data (= modules 1, 3, 5, 7, 9, 10, 13, 14): 248 words

Output data (= modules 2, 4, 6, 8, 11, 12, 15): 248 words

If the EtherNet/IP modules have been parameterised in such a way that the cyclic input and output data comprise more than 248 words per direction of transmission, any data from the 249th word will not be transmitted and will therefore be lost.

► Parameterise the EtherNet/IP modules in a way to ensure that the input and output data do not exceed the maximum number of words to be transmitted!

Slot

Description Further information

1 Digital input data single or A slaves, AS-i master 1 → Slot 1 – Digital input data single or A slaves, AS-i master 1 (→ page 223)

2 Digital output data single or A slaves, AS-i master 1 → Slot 2 – Digital output data single or A slaves, AS-i master 1 (→ page 223)

3 Digital input data single or A slaves, AS-i master 2

(only available for devices with 2 AS-i masters)

→ Slot 3 – Digital input data single or A slaves, AS-i master 2 (→ page 224)

4 Digital output data single or A slaves, AS-i master 2

(only available for devices with 2 AS-i masters)

→ Slot 4 – Digital output data single or A slaves, AS-i master 2 (→ page 224)

5 Digital input data B slaves, AS-i master 1 → Slot 5 – Digital input data B slaves, AS-i master 1 (→ page 225)

6 Digital output data B slaves, AS-i master 1 → Slot 6 – Digital output data B slaves, AS-i master 1 (→ page 225)

7 Digital input data B slaves, AS-i master 2

(only available for devices with 2 AS-i masters)

→ Slot 7 – Digital input data B slaves, AS-i master 2 (→ page 226)

8 Digital output data B slaves, AS-i master 2

(only available for devices with 2 AS-i masters)

→ Slot 8 – Digital output data B slaves, AS-i master 2 (→ page 226)

9 Analogue input data of up to 31 slaves, range 1* → Slot 9 – Analogue input data (→ page 229)

10 Analogue input data of up to 31 slaves, range 2* → Slot 10 – Analogue input data (→ page 230)

11 Analogue output data of up to 31 slaves, range 1** → Slot 11 – Analogue output data (→ page 231)

12 Analogue output data of up to 31 slaves, range 2** → Slot 12 – Analogue output data (→ page 232)

13 Diagnostic data → Slot 13 – Diagnostic data (→ page 237)

14 Data from the device-internal standard PLC to the EtherNet/IP PLC

→ Slot 14 – Inputs from standard PLC (→ page 252)

15 Data from the EtherNet/IP PLC to the device-internal standard PLC

→ Slot 15 – Outputs to standard PLC (→ page 253)

* ... Define the number of analogue channels and the slave number by means of the device parameters [analogue channels/I-slave] (→ Device-specific parameters (→ page 200)).

** ... Define the number of analogue channels and the slave number by means of the device parameters [analogue channels/O-slave] (→ Device-specific parameters (→ page 200)).

>

Page 223: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

223

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Slot 1 – Digital input data single or A slaves, AS-i master 1 12428

Slot

Description Value range Length [words]

1 Digital input data of single or A slaves, connected to AS-i master 1

Empty module = Module is disabled 0

01 ... 03 = Module is active with slaves 1(A) ... 3(A), AS-i master 1 1

01 ... 07 = Module is active with slaves 1(A) ... 7(A), AS-i master 1 2

01 ... 11 = Module is active with slaves 1(A) ... 11(A), AS-i master 1 3

01 ... 15 = Module is active with slaves 1(A) ... 15(A), AS-i master 1 4

01 ... 19 = Module is active with slaves 1(A) ... 19(A), AS-i master 1 5

01 ... 23 = Module is active with slaves 1(A) ... 23(A), AS-i master 1 6

01 ... 27 = Module is active with slaves 1(A) ...27(A), AS-i master 1 7

01 ... 31 = Module is active with slaves 1(A) ... 31(A), AS-i master 1 8

The data of 4 AS-i slaves is transmitted in each word (→ Mapping of the digital input/output data (→ page 227)). >

Slot 2 – Digital output data single or A slaves, AS-i master 1 12429

Slot

Description Value range Length [words]

2 Digital output data of single or A slaves, connected to AS-i master 1

Empty module = Module is disabled 0

01 ... 03 = Module is active with slaves 1(A) ... 3(A), AS-i master 1 1

01 ... 07 = Module is active with slaves 1(A) ... 7(A), AS-i master 1 2

01 ... 11 = Module is active with slaves 1(A) ... 11(A), AS-i master 1 3

01 ... 15 = Module is active with slaves 1(A) ... 15(A), AS-i master 1 4

01 ... 19 = Module is active with slaves 1(A) ... 19(A), AS-i master 1 5

01 ... 23 = Module is active with slaves 1(A) ... 23(A), AS-i master 1 6

01 ... 27 = Module is active with slaves 1(A) ...27(A), AS-i master 1 7

01 ... 31 = Module is active with slaves 1(A) ... 31(A), AS-i master 1 8

The data of 4 AS-i slaves is transmitted in each word (→ Mapping of the digital input/output data (→ page 227)).

Page 224: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

224

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Slot 3 – Digital input data single or A slaves, AS-i master 2 12430

Slot

Description Value range Length [words]

3 Digital input data of single or A slaves, connected to AS-i master 2 (only available for devices with 2 AS-i masters)

Empty module = Module is disabled 0

01 ... 03 = Module is active with slaves 1(A) ... 3(A), AS-i master 2 1

01 ... 07 = Module is active with slaves 1(A) ... 7(A), AS-i master 2 2

01 ... 11 = Module is active with slaves 1(A) ... 11(A), AS-i master 2 3

01 ... 15 = Module is active with slaves 1(A) ... 15(A), AS-i master 2 4

01 ... 19 = Module is active with slaves 1(A) ... 19(A), AS-i master 2 5

01 ... 23 = Module is active with slaves 1(A) ... 23(A), AS-i master 2 6

01 ... 27 = Module is active with slaves 1(A) ...27(A), AS-i master 2 7

01 ... 31 = Module is active with slaves 1(A) ... 31(A), AS-i master 2 8

The data of 4 AS-i slaves is transmitted in each word (→ Mapping of the digital input/output data (→ page 227)). >

Slot 4 – Digital output data single or A slaves, AS-i master 2 12431

Slot

Description Value range Length [words]

4 Digital output data of single or A slaves, connected to AS-i master 2 (only available for devices with 2 AS-i masters)

Empty module = Module is disabled 0

01 ... 03 = Module is active with slaves 1(A) ... 3(A), AS-i master 2 1

01 ... 07 = Module is active with slaves 1(A) ... 7(A), AS-i master 2 2

01 ... 11 = Module is active with slaves 1(A) ... 11(A), AS-i master 2 3

01 ... 15 = Module is active with slaves 1(A) ... 15(A), AS-i master 2 4

01 ... 19 = Module is active with slaves 1(A) ... 19(A), AS-i master 2 5

01 ... 23 = Module is active with slaves 1(A) ... 23(A), AS-i master 2 6

01 ... 27 = Module is active with slaves 1(A) ...27(A), AS-i master 2 7

01 ... 31 = Module is active with slaves 1(A) ... 31(A), AS-i master 2 8

The data of 4 AS-i slaves is transmitted in each word (→ Mapping of the digital input/output data (→ page 227)).

Page 225: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

225

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Slot 5 – Digital input data B slaves, AS-i master 1 12433

Slot

Description Value range Length [words]

5 Digital input data of B slaves, connected to AS-i master 1

Empty module = Module is disabled 0

01B ... 03B = Module is active with slaves 1B ... 3B, AS-i master 1 1

01B ... 07B = Module is active with slaves 1B ... 7B, AS-i master 1 2

01B ... 11B = Module is active with slaves 1B ... 11B, AS-i master 1 3

01B ... 15B = Module is active with slaves 1B ... 15B, AS-i master 1 4

01B ... 19B = Module is active with slaves 1B ... 19B, AS-i master 1 5

01B ... 23B = Module is active with slaves 1B ... 23B, AS-i master 1 6

01B ... 27B = Module is active with slaves 1B ... 27B, AS-i master 1 7

01B ... 31B = Module is active with slaves 1B ... 31B, AS-i master 1 8

The data of 4 AS-i slaves is transmitted in each word (→ Mapping of the digital input/output data (→ page 227)). >

Slot 6 – Digital output data B slaves, AS-i master 1 12435

Slot

Description Value range Length [words]

6 Digital output data of B slaves, connected to AS-i master 1

Empty module = Module is disabled 0

01B ... 03B = Module is active with slaves 1B ... 3B, AS-i master 1 1

01B ... 07B = Module is active with slaves 1B ... 7B, AS-i master 1 2

01B ... 11B = Module is active with slaves 1B ... 11B, AS-i master 1 3

01B ... 15B = Module is active with slaves 1B ... 15B, AS-i master 1 4

01B ... 19B = Module is active with slaves 1B ... 19B, AS-i master 1 5

01B ... 23B = Module is active with slaves 1B ... 23B, AS-i master 1 6

01B ... 27B = Module is active with slaves 1B ... 27B, AS-i master 1 7

01B ... 31B = Module is active with slaves 1B ... 31B, AS-i master 1 8

The data of 4 AS-i slaves is transmitted in each word (→ Mapping of the digital input/output data (→ page 227)).

Page 226: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

226

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Slot 7 – Digital input data B slaves, AS-i master 2 12436

Slot

Description Value range Length [words]

7 Digital input data of B slaves, connected to AS-i master 2 (only available for devices with 2 AS-i masters)

Empty module = Module is disabled 0

01B ... 03B = Module is active with slaves 1B ... 3B, AS-i master 2 1

01B ... 07B = Module is active with slaves 1B ... 7B, AS-i master 2 2

01B ... 11B = Module is active with slaves 1B ... 11B, AS-i master 2 3

01B ... 15B = Module is active with slaves 1B ... 15B, AS-i master 2 4

01B ... 19B = Module is active with slaves 1B ... 19B, AS-i master 2 5

01B ... 23B = Module is active with slaves 1B ... 23B, AS-i master 2 6

01B ... 27B = Module is active with slaves 1B ... 27B, AS-i master 2 7

01B ... 31B = Module is active with slaves 1B ... 31B, AS-i master 2 8

The data of 4 AS-i slaves is transmitted in each word (→ Mapping of the digital input/output data (→ page 227)). >

Slot 8 – Digital output data B slaves, AS-i master 2 12437

Slot

Description Value range Length [words]

8 Digital output data of B slaves, connected to AS-i master 2 (only available for devices with 2 AS-i masters)

Empty module = Module is disabled 0

01B ... 03B = Module is active with slaves 1B ... 3B, AS-i master 2 1

01B ... 07B = Module is active with slaves 1B ... 7B, AS-i master 2 2

01B ... 11B = Module is active with slaves 1B ... 11B, AS-i master 2 3

01B ... 15B = Module is active with slaves 1B ... 15B, AS-i master 2 4

01B ... 19B = Module is active with slaves 1B ... 19B, AS-i master 2 5

01B ... 23B = Module is active with slaves 1B ... 23B, AS-i master 2 6

01B ... 27B = Module is active with slaves 1B ... 27B, AS-i master 2 7

01B ... 31B = Module is active with slaves 1B ... 31B, AS-i master 2 8

The data of 4 AS-i slaves is transmitted in each word (→ Mapping of the digital input/output data (→ page 227)).

Page 227: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

227

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Mapping of the digital input/output data 13447

This table illustrates the mapping of digital input/output data of the individual slaves to the bytes of the transmitted words:

Word AS-i slave addresses

Bits 15...12

Bits 11...8

Bits 7...4

Bits 3...0

1 M flags* 1(A) / 1B 2(A) / 2B 3(A) / 3B

2 4(A) / 4B 5(A) / 5B 6(A) / 6B 7(A) / 7B

3 8(A) / 8B 9(A) / 9B 10(A) / 10B 11(A) / 11B

4 12(A) / 12B 13(A) / 13B 14(A) / 14B 15(A) / 15B

5 16(A) / 16B 17(A) / 17B 18(A) / 18B 19(A) / 19B

6 20(A) / 20B 21(A) / 21B 22(A) / 22B 23(A) / 23B

7 24(A) / 24B 25(A) / 25B 26(A) / 26B 27(A) / 27B

8 28(A) / 28B 29(A) / 29B 30(A) / 30B 31(A) / 31B

Legend:

* ... The master flags (M flags) are only transmitted in the digital input data (→ Table: master flags (→ page 228)).

>

Example: structure of the digital input data 13450

Task: The digital input data of slaves 1A, 3 and 6A of AS-i master 1 are to be transmitted.

Solution: Slot: 1 Module configuration: 01 ... 07

Data length: 2 words

The following table shows in which positions of the two word sized data block the digital input data of the slaves are transmitted:

Data block (2 words)

Bits 31...28

Bits 27...24

Bits 23...20

Bits 19...16

Bits 15...12

Bits 11...8

Bits 7...4

Bits 3...0

1A 3 6A

Page 228: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

228

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Table: Master flags 12475

Bits 12...15 of the first word of the digital input data contain the master flags. They provide information on the operating state of the AS-i master. The following table shows the meaning of each bit:

Bit 15 Bit 14 Bit 13 Bit 12

AS-i power fail (19 V)

Configuration error in the AS-i circuit

AS-i master is offline (AS-i data is invalid)

Periphery fault in the AS-i circuit

Possible values per bit: 0 = no error 1 = error

In the digital output data, bits 12...15 have no relevance and are not evaluated!

Page 229: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

229

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Slot 9 – Analogue input data 12438

Slot

Description Value range Length [words]

9 Data area with a maximum length of 60 words for cyclic transmission of analogue input information

Default setting: analogue inputs of AS-i slaves 01 ... 15, connected to AS-i master 1

The valid and

overflow flags that each

analogue AS-i input slave provides for each channel are NOT represented here. If required, they can be read out via the acyclic services. (→ The acyclic process data).

Empty module = Module is deactivated 0

004 words = Module is activated with 4 analog channels 4

008 words = Module is activated with 8 analog channels 8

012 words = Module is activated with 12analog channels 12

016 words = Module is activated with 16 analog channels 16

020 words = Module is activated with 20 analog channels 20

024 words = Module is activated with 24 analog channels 24

028 words = Module is activated with 28 analog channels 28

032 words = Module is activated with 32 analog channels 32

036 words = Module is activated with 36 analog channels 36

040 words = Module is activated with 40 analog channels 40

044 words = Module is activated with 44 analog channels 44

048 words = Module is activated with 48 analog channels 48

052 words = Module is activated with 52 analog channels 52

056 words = Module is activated with 56 analog channels 56

060 words = Module is activated with 60 analog channels 60

The exact mapping of analogue input data within this area depends on the parameter setting [Analog. channels/I-slave] (→ Configuration of the analogue channels in slots 9 ... 12 (→ page 233)).

Page 230: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

230

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Slot 10 – Analogue input data 124390

Slot

Description Value range Length [words]

10 Data area with a maximum length of 60 words for cyclic transmission of analogue input information

Default setting: analogue inputs of AS-i slaves 01.. 15, connected to AS-i master 2 (only available for devices with 2 AS-i masters)

The valid and

overflow flags that each analogue AS-i input slave provides for each channel are NOT represented here. If required, they can be read out via the acyclic services (Explicit Messaging) (→ The acyclic process data).

Empty module = Module is deactivated 0

004 words = Module is activated with 4 analog channels 4

008 words = Module is activated with 8 analog channels 8

012 words = Module is activated with 12 analog channels 12

016 words = Module is activated with 16 analog channels 16

020 words = Module is activated with 20 analog channels 20

024 words = Module is activated with 24 analog channels 24

028 words = Module is activated with 28 analog channels 28

032 words = Module is activated with 32 analog channels 32

036 words = Module is activated with 36 analog channels 36

040 words =Module is activated with 40 analog channels 40

044 words = Module is activated with 44 analog channels 44

048 words = Module is activated with 48 analog channels 48

052 words = Module is activated with 52 analog channels 52

056 words = Module is activated with 56 analog channels 56

060 words = Module is activated with 60 analog channels 60

The exact mapping of analogue input data within this area depends on the parameter setting [Analog. channels/I-slave] (→ Configuration of the analogue channels in slots 9 ... 12 (→ page 233)).

Page 231: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

231

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Slot 11 – Analogue output data 12440

Slot

Description Value range Length [words]

11 Data area with a maximum length of 60 words for cyclic transmission of analogue output information.

Default setting: analogue outputs of AS-i slaves 16...30, connected to AS-i master 1

Empty module = Module is deactivated 0

004 words = Module is activated with 4 analog channels 4

008 words = Module is activated with 8 analog channels 8

012 words = Module is activated with 12 analog channels 12

016 words = Module is activated with 16 analog channels 16

020 words = Module is activated with 20 analog channels 20

024 words = Module is activated with 24 analog channels 24

028 words = Module is activated with 28 analog channels 28

032 words = Module is activated with 32 analog channels 32

036 words = Module is activated with 36 analog channels 36

040 words = Module is activated with 40 analog channels 40

044 words = Module is activated with 44 analog channels 44

048 words = Module is activated with 48 analog channels 48

052 words = Module is activated with 52 analog channels 52

056 words = Module is activated with 56 analog channels 56

060 words = Module is activated with 60 analog channels 60

The exact mapping of analogue output data within this area depends on the parameter setting [Analog. channels/O-slave] (→ Configuration of the analogue channels in slots 9 ... 12 (→ page 233)).

Page 232: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

232

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Slot 12 – Analogue output data 12442

Slot

Description Value range Length [words]

12 Data area with a maximum length of 60 words for cyclic transmission of analogue output information.

Default setting: analogue outputs of AS-i slaves 16...30, connected to AS-i master 2 (only available for devices with 2 AS-i masters)

Empty module = Module is deactivated 0

004 words = Module is activated with 4 analog channels 4

008 words = Module is activated with 8 analog channels 8

012 words = Module is activated with 12 analog channels 12

016 words = Module is activated with 16 analog channels 16

020 words = Module is activated with 20 analog channels 20

024 words = Module is activated with 24 analog channels 24

028 words = Module is activated with 28 analog channels 28

032 words = Module is activated with 32 analog channels 32

036 words = Module is activated with 36 analog channels 36

040 words = Module is activated with 40 analog channels 40

044 words = Module is activated with 44 analog channels 44

048 words = Module is activated with 48 analog channels 48

052 words = Module is activated with 52 analog channels 52

056 words = Module is activated with 56 analog channels 56

060 words = Module is activated with 60 analog channels 60

The exact mapping of analogue output data within this area depends on the parameter setting [Analog. channels/O-slave] (→ Configuration of the analogue channels in slots 9 ... 12 (→ page 233)).

Page 233: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

233

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Configuration of the analogue channels in slots 9 ... 12 12471

The configuration of the EtherNet/IP device parameters [Analog. channels/I-slave] and [Analog. channels/O-slave] determines which analogue channels of the AS-i slaves are transmitted. The following table shows the meaning of the adjustable parameter values:

Parameter values Description

4 channels Variable slave assignment

The analogue channels of max. 30 slave addresses are transferred:

single slaves: channels 1...4 or: A slaves: channels 1+2 and B slaves: channels 1+2

The device-specific parameters (→ Device-specific parameters (→ page 204)) of the device allow you to individually define the order of 15 of the analogue slaves to be transferred, respectively (→ Table: variable slave assignment for slots 9 ... 12 (→ page 236)). All available slave addresses of both AS-i masters can be selected.

Preset, variable:

for slot 9: AS-i master 1: single slaves 1 ... 15 or: slave 1A ... 15A, 1B ... 15B

for slot 10: AS-i master 2: single slaves 1 ... 15 or: slave 1A ... 15A, 1B ... 15B

for slot 11: AS-i master 1: single slaves 16 ... 30 or: slave 16A .... 30A, 15B ... 30B

for slot 12: AS-i master 2: single slaves 16 ... 30 or: slave 16A .... 30A, 15B ... 30B

2 channels Fixed slave assignment

Of each transferring AS-i single and A address, the following analogue channels are transmitted:

of single slaves: channels 1+2 or: of A slaves: channels 1+2

The slave assignment is fixed (→ Table: fixed slave assignment for slots 9 ... 12 (→ page 234)). A configuration of the slave order in the device-specific parameters is ineffective.

1 channel Fixed slave assignment

Of each transferring AS-i single and A address, the following analogue channels are transmitted:

single slaves: channel 1 or: A slaves: channel 1

The slave assignment is fixed (→ Table: fixed slave assignment for slots 9 ... 12 (→ page 234)). A configuration of the slave order in the device-specific parameters is ineffective.

1 channel A/B-Slave Fixed slave assignment

Of each transferring slave address, the following analogue channels are transmitted:

single slaves: channels 1+3 or: A slaves: channel 1 and B slaves: channel 1

The slave assignment is fixed (→ Table: fixed slave assignment for slots 9 ... 12 (→ page 234)). A configuration of the slave order in the device-specific parameters is ineffective.

Page 234: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

234

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Table: Fixed slave assignment for slots 9 ... 12 12472

Word Word content for the following number of analogue channels per input/output slave

2 channels 1 channel 1 channel A/B-Slave

1 Mx / slave 1(A) / Channel 1 Mx / slave 1(A) / Channel 1 Mx / slave 1(A) / Channel 1

2 Mx / slave 1(A) / Channel 2 Mx / slave 2(A) / Channel 1 Mx / slave 1B / Channel 1 = Mx / slave 1 / Channel 3

3 Mx / slave 2(A) / Channel 1 Mx / slave 3(A) / Channel 1 Mx / slave 2(A) / Channel 1

4 Mx / slave 2(A) / Channel 2 Mx / slave 4(A) / Channel 1 Mx / slave 2B / Channel 1 = Mx / slave 2 / Channel 3

5 Mx / slave 3(A) / Channel 1 Mx / slave 5(A) / Channel 1 Mx / slave 3(A) / Channel 1

6 Mx / slave 3(A) / Channel 2 Mx / slave 6(A) / Channel 1 Mx / slave 3B / Channel 1 = Mx / slave 3 / Channel 3

7 Mx / slave 4(A) / Channel 1 Mx / slave 7(A) / Channel 1 Mx / slave 4(A) / Channel 1 1

8 Mx / slave 4(A) / Channel 2 Mx / slave 8(A) / Channel 1 Mx / slave 4B / Channel 1 = Mx / slave 4 / Channel 3

9 Mx / slave 5(A) / Channel 1 Mx / slave 9(A) / Channel 1 Mx / slave 5(A) / Channel 1

10 Mx / slave 5(A) / Channel 2 Mx / slave 10(A) / Channel 1 Mx / slave 5B /Channel 1 = Mx / slave 5 / Channel 3

11 Mx / slave 6(A) / Channel 1 Mx / slave 11(A) / Channel 1 Mx / slave 6(A) / Channel 1

12 Mx / slave 6(A) / Channel 2 Mx / slave 12(A) / Channel 1 Mx / slave 6B / Channel 1 = Mx / slave 6 / Channel 3

13 Mx / slave 7(A) / Channel 1 Mx / slave 13(A) / Channel 1 Mx / slave 7(A) / Channel 1

14 Mx / slave 7(A) / Channel 2 Mx / slave 14(A) / Channel 1 Mx / slave 7B / Channel 1 = Mx / slave 7 / Channel 3

15 Mx / slave 8(A) / Channel 1 Mx / slave 15(A) / Channel 1 Mx / slave 8(A) / Channel 1

16 Mx / slave 8(A) / Channel 2 Mx / slave 16(A) / Channel 1 Mx / slave 8B / Channel 1 = Mx / slave 8 / Channel 3

17 Mx / slave 9(A) / Channel 1 Mx / slave 17(A) / Channel 1 Mx / slave 9(A) / Channel 1

18 Mx / slave 9(A) / Channel 2 Mx / slave 18(A) / Channel 1 Mx / slave 9B / Channel 1 = Mx / slave 9 / Channel 3

19 Mx / slave 10(A) / Channel 1 Mx / slave 19(A) / Channel 1 Mx / slave 10(A) / Channel 1

20 Mx / slave 10(A) / Channel 2 Mx / slave 20(A) / Channel 1 Mx / slave 10B / Channel 1 = Mx / slave 10 / Channel 3

21 Mx / slave 11(A) / Channel 1 Mx / slave 21(A) / Channel 1 Mx / slave 11(A) / Channel 1

22 Mx / slave 11(A) / Channel 2 Mx / slave 22(A) / Channel 1 Mx / slave 11B / Channel 1 = Mx / slave 11 / Channel 3

23 Mx / slave 12(A) / Channel 1 Mx / slave 23(A) / Channel 1 Mx / slave 12(A) / Channel 1

24 Mx / slave 12(A) / Channel 2 Mx / slave 24(A) / Channel 1 Mx / slave 12B / Channel 1 = Mx / slave 12 / Channel 3

25 Mx / slave 13(A) / Channel 1 Mx / slave 25(A) / Channel 1 Mx / slave 13(A) / Channel 1

26 Mx / slave 13(A) / Channel 2 Mx / slave 26(A) / Channel 1 Mx / slave 13B / Channel 1 = Mx / slave 13 / Channel 3

27 Mx / slave 14(A) / Channel 1 Mx / slave 27(A) / Channel 1 Mx / slave 14(A) / Channel 1

28 Mx / slave 14(A) / Channel 2 Mx / slave 28(A) / Channel 1 Mx / slave 14B / Channel 1 = Mx / slave 14 / Channel 3

29 Mx / slave 15(A) / Channel 1 Mx / slave 29(A) / Channel 1 Mx / slave 15(A) / Channel 1

30 Mx / slave 15(A) / Channel 2 Mx / slave 30(A) / Channel 1 Mx / slave 15B / Channel 1= Mx / slave 15 / Channel 3

31 Mx / slave 16(A) /Channel 1 Mx / slave 31(A) / Channel 1 Mx / slave 16(A) / Channel 1

32 Mx / slave 16(A) / Channel 2 Mx / slave 16B / Channel 1 = Mx / slave 16 / Channel 3

33 Mx / slave 17(A) / Channel 1 Mx / slave 17(A) / Channel 1

34 Mx / slave 17(A) / Channel 2 Mx / slave 17B / Channel 1= Mx / slave 17 / Channel 3

35 Mx / slave 18(A) / Channel 1 Mx / slave 18(A) / Channel 1

36 Mx / slave 18(A) / Channel 2 Mx / slave 18B / Channel 1 = Mx / slave 18 / Channel 3

37 Mx / slave 19(A) / Channel 1 Mx / slave 19(A) / Channel 1

Page 235: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

235

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

38 Mx / slave 19(A) / Channel 2 Mx / slave 19B / Channel 1 = Mx / slave 19 / Channel 3

39 Mx / slave 20(A) / Channel 1 Mx / slave 20(A) / Channel 1

40 Mx / slave 20(A) / Channel 2 Mx / slave 20B / Channel 1 = Mx / slave 20 / Channel 3

41 Mx / slave 21(A) / Channel 1 Mx / slave 21(A) / Channel 1

42 Mx / slave 21(A) / Channel 2 Mx / slave 21B / Channel 1 = Mx / slave 21 / Channel 3

43 Mx / slave 22(A) /Channel 1 Mx / slave 22(A) / Channel 1

44 Mx / slave 22(A) / Channel 2 Mx / slave 22B / Channel 1 = Mx / slave 22 / Channel 3

45 Mx / slave 23(A) / Channel 1 Mx / slave 23(A) / Channel 1

46 Mx / slave 23(A) / Channel 2 Mx / slave 23B / Channel 1 = Mx / slave 23 / Channel 3

47 Mx / slave 24(A) / Channel 1 Mx / slave 24(A) / Channel 1

48 Mx / slave 24(A) / Channel 2 Mx / slave 24B / Channel 1 = Mx / slave 24 / Channel 3

49 Mx / slave 25(A) / Channel 1 Mx / slave 25(A) / Channel 1

50 Mx / slave 25(A) / Channel 2 Mx / slave 25B / Channel 1 = Mx / slave 25 / Channel 3

51 Mx / slave 26(A) / Channel 1 Mx / slave 26(A) / Channel 1

52 Mx / slave 26(A) / Channel 2 Mx / slave 26B / Channel 1 = Mx / slave 26 / Channel 3

53 Mx / slave 27(A) / Channel 1 Mx / slave 27(A) / Channel 1

54 Mx / slave 27(A) / Channel 2 Mx / slave 27B / Channel 1 = Mx / slave 27 / Channel 3

55 Mx / slave 28(A) / Channel 1 Mx / slave 28(A) / Channel 1

56 Mx / slave 28(A) / Channel 2 Mx / slave 28B / Channel 1 = Mx / slave 28 / Channel 3

57 Mx / slave 29(A) / Channel 1 Mx / slave 29(A) / Channel 1

58 Mx / slave 29(A) / Channel 2 Mx / slave 29B / Channel 1 = Mx / slave 29 / Channel 3

59 Mx / slave 30(A) / Channel 1 Mx / slave 30(A) /Channel 1

60 Mx / slave 30(A) / Channel 2 Mx / slave 30B / Channel 1 = Mx / slave 30 / Channel 3

Legend:

x ... - slot 9 + 11: x=1 (M1 = AS-i master 1) - slot 10 + 12: x=2 (M2 = AS-i master 2)

Page 236: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

236

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Table: variable slave assignment for slots 9 ... 12 13451

Word offset no.

Content of transmitted word for parameter value 4 channels

n Mx / slave m(A) / channel 1

n+1 Mx / slave m(A) / channel 2

n+2 Mx / slave m(A) / channel 1 = Mx / slave mB / channel 1

n+3 Mx / slave m(A) / channel 2 = Mx / slave mB / channel 2

Legend:

n ... number of 4-word blocks 1 = if 4 words are set ... 15 = if 60 words are set

x ... 1 = AS-i master 1 2 = AS-i master 2

m ... numerical part of the selected AS-i slave address

Variable AS-i slave assignment is only possible in top-down mode. In the EtherNet/IP projection software, each word can be assigned the data of an AS-i slave via the configuration assembly object. Otherwise, the preset values apply (→ Configuration of the analogue channels in slots 9 ... 12 (→ page 233)).

To assign a specific AS-i slave address to the transferring channels:

► Open the project in the EtherNet/IP projection software.

► Make the following settings in the configuration assembly object:

Activate the data point C.Analogue IN order (= 0x01).

Assign the desired slave addresses to the input channels in the data points C.1st analogue IN Slot 9 to

C.15th analogue IN Slot 10.

Activate the data point C. Analogue OUT order (= 0x01).

Assign the desired slave addresses to the output channels in the data points C.1st analogue OUT Slot 11

... C.15th analogue OUT Slot 12 .

► Save the set values and transfer the project to the device (download).

Page 237: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

237

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Slot 13 – Diagnostic data 12470

Slot

Description Value range Data length

[words]

13 Diagnostic data sent to the I/O scanner

Contents of diagnostic data: → following tables

Empty module 0

AC1421 25

AC1422 50

AC13x7 AS-i 1 *) 13

AC13x7 AS-i 1+2 *) 26

Legend:

*) ... compatible with the diagnostic data of predecessor models AC1327/37

Page 238: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

238

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Module setting: AC1421 12624

The diagnostic data for the module settings AC1421 have 25 words.

Overview diagnostic range:

Word Description

1 System diagnosis

2...5 AS-i master 1: AS-i diagnosis

6...9 AS-i master 1: list of missing slaves

10...13 AS-i master 1: List of non-projected slaves

14...17 AS-i master 1: List of slaves with wrong slave profile

18...21 AS-i master 1: list of peripheral faults

22...25 AS-i master 1: list of multiple addressed slaves

>

Diagnosis - system diagnosis 12657

System diagnosis:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 - - - - - - - - - - - - PS GI OT ISE

Legend:

Alarm Description

ISE Internal System Error Interner K6-Systemfehler

OT over temperature: temperature inside the device has exceeded the permissible max. temperature value

GI gateway inactive: the gateway mode was deactivated

PS PLC stop: The controller was stopped

Page 239: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

239

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Diagnosis - AS-i master 1: AS-i diagnosis 12658

AS-i master 1: AS-i diagnostics:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

2 - - PF19 PF22.

5 EF S0 PM IME - - - DAE PE CEIP CEAS CEMS

3 Voltage AS-i+ to AS-i- in mV

4 Voltage FE to AS-i- in mV

5 Symmetry in % (-100% ... +100%)

Legend:

Alarm Description

IME internal master error: Internal system error of an AS-i master

PM projection mode: AS-i master was set to the projection mode.

S0 slave 0 detected: New slave 0 was detected.

EF earth fault: Earth fault was detected

PF22.5 22.5V AS-i Power-Fail (classic AS-i Power) was detected.

PF19 19 AS-i Power-Fail (Power24) was detected.

CEMS Configuration Error – Missing Slave: AS-i configuration error, one or several slaves are projected, but not available.

CEAS Configuration Error – Additional Slave: AS-i configuration error, one or several slaves are available, but not projected.

CEIP Configuration Error – Invalid Profile: AS-i configuration error, the slave profiles of one or several slaves differ from the projected slave profiles.

PE periphery error: One or several AS-i slaves have a periphery error.

DAE duplicate address error: One or several multiple-addressing faults occurred.

Page 240: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

240

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Diagnosis - AS-i master 1: List of missing slaves 2659

AS-i master 1: list of missing slaves:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

6 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0

7 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

8 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B n.a.

9 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

If at least 1 bit is set in this list, the bit for CEMS is also set. (→ Diagnosis - AS-i master 1: AS-i diagnosis (→ page 239))

>

Diagnosis - AS-i master 1: List of non-projected slaves 12660

AS-i master 1: List of non-projected slaves:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

10 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0

11 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

12 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B n.a.

13 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

If at least 1 bit is set in this list, the bit for CEAS is also set. (→ Diagnosis - AS-i master 1: AS-i diagnosis (→ page 239))

>

Diagnosis - AS-i master 1: List of slaves with wrong slave profile 12663

AS-i master 1: List of slaves with wrong slave profile:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

14 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0

15 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

16 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B n.a.

17 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

If at least 1 bit is set in this list, the bit for CEIP is also set. (→ Diagnosis - AS-i master 1: AS-i diagnosis (→ page 239))

Page 241: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

241

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Diagnosis - AS-i master 1: List of peripheral faults 2664

AS-i master 1: list of peripheral faults:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

18 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0

19 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

20 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B n.a.

21 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

If at least 1 bit is set in this list, the bit for PE is also set. (→ Diagnosis - AS-i master 1: AS-i diagnosis (→ page 239))

>

Diagnosis - AS-i master 1: list of multiple addressed slaves 12665

AS-i master 1: list of multiple addressed slaves:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

22 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0

23 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

24 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B n.a.

25 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

If at least 1 bit is set in this list, the bit for DAE is also set. (→ Diagnosis - AS-i master 1: AS-i diagnosis (→ page 239)).

Page 242: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

242

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Module setting: AC1422 2625

The diagnostic data for the module settings AC1422 have 50 words. Words 1 to 25 correspond to

those of the module setting AC1421 (→ Module setting: AC1421 (→ page 238)).

Overview diagnostic range:

Word Description

1 System diagnosis

2...5 AS-i master 1: AS-i diagnosis

6...9 AS-i master 1: list of missing slaves

10...13 AS-i master 1: List of non-projected slaves

14...17 AS-i master 1: List of slaves with wrong slave profile

18...21 AS-i master 1: list of peripheral faults

22...25 AS-i master 1: list of multiple addressed slaves

26...29 AS-i master 2: AS-i diagnosis

30...33 AS-i master 2: list of missing slaves

34...37 AS-i master 2: List of non-projected slaves

38...41 AS-i master 2: List of slaves with wrong slave profile

42...45 AS-i master 2: list of peripheral faults

46...49 AS-i master 2: list of multiple addressed slaves

50 reserved

Page 243: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

243

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Diagnosis - system diagnosis 12738

→ Diagnosis - system diagnosis (→ page 238) >

Diagnosis - AS-i master 1: AS-i diagnosis 12739

→ Diagnosis - AS-i master 1: AS-i diagnosis (→ page 239) >

Diagnosis - AS-i master 1: list of missing slaves 12740

→ Diagnosis - AS-i master 1: List of missing slaves (→ page 240) >

Diagnosis - AS-i master 1: List of non-projected slaves 12741

→ Diagnosis - AS-i master 1: List of non-projected slaves (→ page 240) >

Diagnosis - AS-i master 1: List of slaves with wrong slave profile 12742

→ Diagnosis - AS-i master 1: List of slaves with wrong slave profile (→ page 240) >

Diagnosis - AS-i master 1: list of peripheral faults 12743

→ Diagnosis - AS-i master 1: List of peripheral faults (→ page 241) >

Diagnosis - AS-i master 1: list of multiple addressed slaves 12744

→ Diagnosis - AS-i master 1: list of multiple addressed slaves (→ page 241)

Page 244: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

244

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Diagnosis - AS-i master 2: AS-i diagnosis 12730

AS-i master 2: AS-i diagnostics:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

26 - - PF19 PF22.

5 EF S0 PM IME - - - DAE PE CEIP CEAS CEMS

27 Voltage AS-i+ to AS-i- in mV

28 Voltage FE to AS-i- in mV

29 Symmetry in % (-100% ... +100%)

Legend:

Alarm Description

IME internal master error: Internal system error of an AS-i master

PM projection mode: AS-i master was set to the projection mode.

S0 slave 0 detected: New slave 0 was detected.

EF earth fault: Earth fault was detected

PF22.5 22.5V AS-i Power-Fail (classic AS-i Power) was detected.

PF19 19 AS-i Power-Fail (Power24) was detected.

CEMS Configuration Error – Missing Slave: AS-i configuration error, one or several slaves are projected, but not available.

CEAS Configuration Error – Additional Slave: AS-i configuration error, one or several slaves are available, but not projected.

CEIP Configuration Error – Invalid Profile: AS-i configuration error, the slave profiles of one or several slaves differ from the projected slave profiles.

PE periphery error: One or several AS-i slaves have a periphery error.

DAE duplicate address error: One or several multiple-addressing faults occurred.

Page 245: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

245

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Diagnosis - AS-i master 2: list of missing slaves 12731

AS-i master 2: list of missing slaves:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

30 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0

31 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

32 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B n.a.

33 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

If at least 1 bit is set in this list, the bit for CEMS is also set. (→ Diagnosis - AS-i master 1: AS-i diagnosis (→ page 239))

>

Diagnosis - AS-i master 2: List of non-projected slaves 12732

AS-i master 2: List of non-projected slaves:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

34 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0

35 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

36 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B n.a.

37 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

If at least 1 bit is set in this list, the bit for CEAS is also set. (→ Diagnosis - AS-i master 1: AS-i diagnosis (→ page 239))

>

Diagnosis - AS-i master 2: List of slaves with wrong slave profile 12733

AS-i master 2: List of slaves with wrong slave profile:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

38 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0

39 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

40 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B n.a.

41 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

If at least 1 bit is set in this list, the bit for CEIP is also set. (→ Diagnosis - AS-i master 1: AS-i diagnosis (→ page 239))

Page 246: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

246

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Diagnosis - AS-i master 2: list of peripheral faults 12734

AS-i master 2: list of peripheral faults:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

42 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0

43 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

44 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B n.a.

45 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

If at least 1 bit is set in this list, the bit for PE is also set. (→ Diagnosis - AS-i master 1: AS-i diagnosis (→ page 239))

>

Diagnosis - AS-i master 2: list of multiple addressed slaves 12736

AS-i master 2: list of multiple addressed slaves:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

46 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0

47 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

48 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B n.a.

49 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

If at least 1 bit is set in this list, the bit for DAE is also set (→ Diagnosis - AS-i master 1: AS-i diagnosis (→ page 239)).

Page 247: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

247

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Module setting: AC13x7 AS-i 1 12626

The diagnostic data for the module setting AC13x7 AS-i 1 have 13 words.

Overview diagnostic range:

Word Description

1 AS-i master 1: Master flags

2...5 AS-i master 1: list of detected slaves (LDS)

6...9 AS-i master 1: configuration error

10...13 AS-i master 1: peripheral fault (LPF)

>

Diagnosis - AS-i master 1: Master flags 12674

AS-i master 1: AS-i diagnostics:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 - - - - - - - - - CNO

T -

PNOT

PF LDS0 CACT -

Legend:

Alarm Description

CACT Configuration Active: AS-i master is in the projection mode.

LDS0 LDS.0: A single slave with the address 0 was detected

PF AS-i_Power_Fail: AS-i voltage too low

PNOT NOT Periphery_OK: periphery fault

CNOT NOT Configuartion_OK: configuration error

- reserved

>

Diagnosis - AS-i master 1: list of detected slaves (LDS) 12675

AS-i master 1: list of detected slaves (LDS):

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

2 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0

3 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

4 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B n.a.

5 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

Possible value of slave fields:

0 ... slave was not detected 1.... slave was detected

>

Page 248: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

248

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Diagnosis - AS-i master 1: configuration error 12677

AS-i master 1: Configuration errors:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

6 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0

7 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

8 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B n.a.

9 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

Possible value of slave fields:

0 ... slave works correctly 1.... slave has caused configuration error

>

Diagnosis - AS-i master 1: peripheral fault (LPF) 12676

AS-i master 1: peripheral fault (LPF):

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

10 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) n.a.

11 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

12 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B n.a.

13 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

Possible value of slave fields:

0 ... slave works correctly 1.... slave has caused a periphery fault

Page 249: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

249

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Module setting: AC13x7 AS-i 1+2 12627

The diagnostic data for the module setting AC13x7 AS-i 1 have 25 words. Words 1 to 13 correspond

to those of the module setting AC13x7 AS-i 1 (→ Module setting: AC13x7 AS-i 1 (→ page 247)).

Overview diagnostic range:

Word Description

1 AS-i master 1: Master flags

2...5 AS-i master 1: list of detected slaves (LDS)

6...9 AS-i master 1: configuration error

10...13 AS-i master 1: peripheral fault (LPF)

14 AS-i master 2: Master flags

15...18 AS-i master 2: list of detected slaves (LDS)

19...22 AS-i master 1: configuration error

23...26 AS-i master 1: peripheral fault (LPF)

Page 250: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

250

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Diagnosis - AS-i master 1: Master flags 12759

→ Diagnosis - AS-i master 1: Master flags (→ page 247) >

Diagnosis - AS-i master 1: list of detected slaves (LDS) 12760

→ Diagnosis - AS-i master 1: list of detected slaves (LDS) (→ page 247) >

Diagnosis - AS-i master 1: configuration error 12761

→ Diagnosis - AS-i master 1: configuration error (→ page 248) >

Diagnosis - AS-i master 1: peripheral fault (LPF) 12762

→ Diagnosis - AS-i master 1: peripheral fault (LPF) (→ page 248) >

Diagnosis - AS-i master 2: Master flags 12763

AS-i master 2: Master flags:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

14 - - - - - - - - - CNOT - PNOT PF LDS

0 CAC

T -

Legend:

Alarm Description

CACT Configuration Active: AS-i master is in the projection mode.

LDS0 LDS.0: A single slave with the address 0 was detected

PF AS-i_Power_Fail: AS-i voltage too low

PNOT NOT Periphery_OK: periphery fault

CNOT NOT Configuartion_OK: configuration error

- reserved

>

Diagnosis - AS-i master 2: list of detected slaves (LDS) 12764

AS-i master 2: list of detected slaves (LDS):

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

15 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0

16 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

17 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B n.a.

18 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

Possible value of slave fields:

0 ... slave was not detected 1.... slave was detected

Page 251: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

251

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Diagnosis - AS-i master 2: configuration error 12765

AS-i master 2: Configuration errors:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

19 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0

20 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

21 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B n.a.

22 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

Possible value of slave fields:

0 ... slave works correctly 1.... slave has caused configuration error

>

Diagnosis - AS-i master 2: peripheral fault (LPF) 12674

AS-i master 2: peripheral fault (LPF):

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

23 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) n.a.

24 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

25 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B n.a.

26 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

Possible value of slave fields:

0 ... slave works correctly 1.... slave has caused a periphery fault

Page 252: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

252

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Slot 14 – Inputs from AC4S standard PLC 17747

Slot

Description Value range Size

[words]

14 Data from the device-internal standard PLC to the EtherNet/IP PLC

Empty module = module is deactivated 0

004 words = 4 words from AC4S standard PLC to fieldbus PLC 4

008 words = 8 words from AC4S standard PLC to fieldbus PLC 8

012 words = 12 words from AC4S standard PLC to fieldbus PLC 12

016 words = 16 words from AC4S standard PLC to fieldbus PLC 16

020 words = 20 words from AC4S standard PLC to fieldbus PLC 20

024 words = 24 words from AC4S standard PLC to fieldbus PLC 24

028 words = 28 words from AC4S standard PLC to fieldbus PLC 28

032 words = 32 words from AC4S standard PLC to fieldbus PLC 32

036 words = 36 words from AC4S standard PLC to fieldbus PLC 36

040 words = 40 words from AC4S standard PLC to fieldbus PLC 40

044 words = 44 words from AC4S standard PLC to fieldbus PLC 44

048 words = 48 words from AC4S standard PLC to fieldbus PLC 48

052 words = 52 words from AC4S standard PLC to fieldbus PLC 52

056 words = 56 words from AC4S standard PLC to fieldbus PLC 56

060 words = 60 words from AC4S standard PLC to fieldbus PLC 60

076 words = 76 words from AC4S standard PLC to fieldbus PLC 76

092 words = 92 words from AC4S standard PLC to fieldbus PLC 92

108 words = 108 words from AC4S standard PLC to fieldbus PLC 108

120 words = 120 words from AC4S standard PLC to fieldbus PLC 120

Page 253: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

253

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Slot 15 – Outputs to AC4S standard PLC 17746

Slot

Description Value range Size

[words]

15 Data from the EtherNet/IP PLC to the device-internal standard PLC

Empty module = module is deactivated 0

004 words = 4 words from fieldbus PLC to AC4S standard PLC 4

008 words = 8 words from fieldbus PLC to AC4S standard PLC 8

012 words = 12 words from fieldbus PLC to AC4S standard PLC 12

016 words = 16 words from fieldbus PLC to AC4S standard PLC 16

020 words = 20 words from fieldbus PLC to AC4S standard PLC 20

024 words = 24 words from fieldbus PLC to AC4S standard PLC 24

028 words = 28 words from fieldbus PLC to AC4S standard PLC 28

032 words = 32 words from fieldbus PLC to AC4S standard PLC 32

036 words = 36 words from fieldbus PLC to AC4S standard PLC 36

040 words = 40 words from fieldbus PLC to AC4S standard PLC 40

044 words = 44 words from fieldbus PLC to AC4S standard PLC 44

048 words = 48 words from fieldbus PLC to AC4S standard PLC 48

052 words = 52 words from fieldbus PLC to AC4S standard PLC 52

056 words = 56 words from fieldbus PLC to AC4S standard PLC 56

060 words = 60 words from fieldbus PLC to AC4S standard PLC 60

076 words = 76 words from fieldbus PLC to AC4S standard PLC 76

092 words = 92 words from fieldbus PLC to AC4S standard PLC 92

108 words = 108 words from fieldbus PLC to AC4S standard PLC 108

120 words = 120 words from fieldbus PLC to AC4S standard PLC 120

Page 254: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

254

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

9.6.5 Acyclic data

Overview: acyclic data ..........................................................................................................................255 Acyclic data records .............................................................................................................................257 Command channels ..............................................................................................................................283 Programmers' notes: call up acyclic services .......................................................................................370

12895

With the help of acyclic data, IO devices can be parameterised or configured, or status information can be read. The acyclic data are not automatically updated in the host controller, but have to be explicitly requested by means of special commands (→ Programmers' notes: call up acyclic services (→ page 370)).

The following acyclic data are available:

Acyclic data set → Overview: Acyclic data sets (→ page 258)

Fieldbus command channel → Overview: System commands (→ page 286) → Overview: AS-i master commands (→ page 305)

Page 255: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

255

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Overview: acyclic data 12459

The attributes in object class 801, instance 1, are preset as follows:

Attribute [dec]

from byte no.

[dec]

to byte no.

[dec]

Content DS Access r = read w = write

Number of

words

1 0 51 Read system information DS1 r 26

30 0 239 System command request channel -- r/w 120

31 0 239 System command reply channel -- r 120

32 0 69 M1: digital slave inputs 1(A)…31(A) and 1B…31B

(1 byte per slave) + M1 master flags (status AS-i master and exec.-ctl. flags and host flags)

DS2 r 35

33 0 149 M1: analogue slave inputs 1(A)…15(B) DS3 r 75

34 0 159 M1: analogue slave inputs 16(A)…31(B) DS4 r 80

35 0 63 M1: digital slave outputs 1(A)…31(A) and 1B…31B

(1 byte per slave) DS5 r/w 32

36 0 119 M1: analogue slave outputs 1(A)…15(B) DS6 r/w 60

37 0 127 M1: analogue slave outputs 16(A)…31(B) DS7 r/w 64

38 0 63 M1: status flags analogue outputs 1(A)…31(A) and 1B…31B DS8 r 32

39 0 31 M1: slave lists LAS, LDS, LPF, LCE DS9 r 16

40 0 7 M1: slave list LPS DS10 r 4

41 0 127 M1: current configuration data CDI DS11 r 64

42 0 127 M1: projected configuration data PCD DS12 r 64

43 0 63 M1: input parameter image DS13 r 32

44 0 63 M1: output parameter image DS14 r/w 32

46 0 143 M1: slave error counter, configuration error counter, AS-i cycle

counter DS15 r 72

47 0 23 M1: LCEMS, LCEAS, LDAE DS17 r 12

62 0 239 M1: command request channel -- r/w 120

63 0 239 M1: command reply channel -- r 120

64 0 69 M2: digital slave inputs 1(A)…31(A) and 1B…31B

(1 byte per slave) + M2 master flags (status AS-i master and exec.-ctl. flags and host flags)

DS2 r 35

65 0 149 M2: analogue slave inputs 1(A)…15(B) DS3 r 75

66 0 159 M2: analogue slave inputs 16(A)…31(B) DS4 r 80

67 0 63 M2: digital slave outputs 1(A)…31(A) and 1B…31B

(1 byte per slave) DS5 r/w 32

68 0 119 M2: analogue slave outputs 1(A)…15(B) DS6 r/w 60

69 0 127 M2: analogue slave outputs 16(A)…31(B) DS7 r/w 64

70 0 63 M2: status flags analogue outputs 1(A)…31(A) and 1B…31B DS8 r 32

71 0 31 M2: slave lists LAS, LDS, LPF, LCE DS9 r 16

72 0 7 M2: slave list LPS DS10 r 4

Page 256: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

256

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Attribute [dec]

from byte no.

[dec]

to byte no.

[dec]

Content DS Access r = read w = write

Number of

words

73 0 127 M2: current configuration data CDI DS11 r 64

74 0 127 M2: projected configuration data PCD DS12 r 64

75 0 63 M2: input parameter image DS13 r 32

76 0 63 M2: output parameter image DS14 r/w 32

78 0 143 M2: slave error counter, configuration error counter, AS-i cycle

counter DS15 r 72

79 0 23 M2: LCEMS, LCEAS, LDAE DS17 r 12

94 0 239 M2: command request channel -- r/w 120

95 0 239 M2: command reply channel -- r 120

Legend:

DS = M1 = M2 =

data set (→ Overview: acyclic data sets (→ page 258, → page 257)) AS-i master 1 AS-i master 2

Page 257: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

257

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Acyclic data records

Overview: Acyclic data sets ..................................................................................................................258 DS1 – System information ....................................................................................................................259 DS2 – Digital inputs of the slaves and master flags .............................................................................260 DS3 – Analogue inputs of slaves 1(A)...15(B) ......................................................................................261 DS4 – Analogue inputs of slaves 16(A)...31(B) ....................................................................................263 DS5 – Digital outputs of the slaves ......................................................................................................265 DS6 – Analogue outputs of slaves 1(A)...15(B)....................................................................................266 DS7 – Analogue outputs of slaves 16(A)...31(B)..................................................................................267 DS8 – Status of the analogue output data of the slaves 1...31 ............................................................268 DS9 – Slave lists LAS, LDS, LPF, LCE ................................................................................................270 DS10 – Slave list LPS ........................................................................................................................270 DS11 – Current configuration data CDI ................................................................................................271 DS12 – Projected configuration data PCD ...........................................................................................273 DS13 – Image of the input parameters of the slaves ...........................................................................275 DS14 – Image of the output parameters of the slaves .........................................................................276 DS15 – Slave error counter, configuration error counter, AS-i cycle counter ......................................277 DS17 – Error lists LCEMS, LCEAS, LDAE ...........................................................................................280 DS18 – Fieldbus information ................................................................................................................281

17036

The data records are transmitted acyclically upon request of the <fieldbus> master.

Page 258: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

258

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Overview: Acyclic data sets 17035

Data set no.

Content Access r = read w = write

Words

DS1 System information r 26

DS2 Digital slave inputs 1(A)…31(A) and 1B…31B + master flags (status AS-i master and exec.-ctl. flags and host flags)

r 36

DS3 Analogue slave inputs 1(A)…15(B) r 75

DS4 Analogue slave inputs 16(A)…31(B) r 80

DS5 Digital slave outputs 1(A)…31(A) and 1B…31B r/w 32

DS6 Analogue slave outputs 1(A)…15(B) r/w 60

DS7 Analogue slave outputs 16(A)…31(B) r/w 64

DS8 Status flags analogue outputs 1(A)…31(A) and 1B…31B r 32

DS9 Slave lists LAS, LDS, LPF, LCE r 16

DS10 Slave lists LPS r 4

DS11 Current configuration data CDI r 64

DS12 Projected configuration data PCD r 64

DS13 Input parameter image r 32

DS14 Input parameter image r/w 32

DS15 Slave error counter, configuration error counter, AS-i cycle counter r 72

DS16 n.a. – –

DS17 Error lists LCEMS, LCEAS, LDAE r 12

DS18 Read fieldbus info (only available via CODESYS) r 19

DS19 n.a. – –

DS20 n.a. – –

Page 259: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

259

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

DS1 – System information 8753

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0 Article number 1) (byte 0) = "A" Article number 1) (byte 1) = “C"

1 Article number 1) (byte 2) = A1 Article number 1) (byte 3) = A2

2 Article number 1) (byte 4) = A3 Article number 1) (byte 5) = A4

3 Device number 2) (byte 1) = G1 Device number 2) (byte 0) = G2

4 Serial number 3) (byte 0, MSB) Serial number 3) (byte 1)

5 Serial number 3) (byte 2) Serial number 3) (byte 3)

6 Serial number 3) (byte 4) Serial number 3) (byte 5)

7 Serial number 3) (byte 6) Serial number 3) (byte 7)

8 Serial number 3) (byte 8) Serial number 3) (byte 9)

9 Serial number 3) (byte 10) Serial number 3) (byte 11)

10 Software type Software Version (Major Version)

11 Software Version (Minor Version) Software Version (Build Version)

12 Operating hours 5) Total (byte 3, high byte) Operating hours 5) Total (byte 2)

13 Operating hours 5) Total (byte 1) Operating hours 5) Total (byte 0, low byte)

14 Operating hours 5) Uptime (byte 3, high byte) Operating hours 5) Uptime (byte 2)

15 Operating hours 5) Uptime (byte 1) Operating hours 5) Uptime (byte 0, low byte)

16 Operating hours 5) standard PLC (byte 3, high byte) Operating hours 5) standard PLC (byte 2)

17 Operating hours 5) standard PLC (byte 1) Operating hours 5) standard PLC (byte 0, low byte)

18 Operating hours 5) display (byte 3, high byte) Operating hours 5) display (byte 2)

19 Operating hours 5) display (byte 1) Operating hours 5) display (byte 0, low byte)

20 Device temperature 6) (byte 0, high byte) Device temperature 6) (byte 1, low byte)

21 reserved Number of AS-i masters

22 Language 7) (1st letter) Language 7) (2nd letter)

23 Return to start screen (on/off) Screen saver (on/off)

24 CODESYS standard PLC operating mode (activ/inactiv) Output access

25 Device cycle in µs (high byte) Device cycle in µs (low byte)

1) Article number: "AC" + A1 + A2 + A3 + A4 as character string, e.g. "AC1401" or "AC402S" 2) Device number: G1 + G2 as character string, e.g. "AB" 3) Serial number: 12-digit character string 5) Operating hours: in seconds, Unsigned Double word (32 bit) 6) Device temperature: in 1/100 °C, signed Word (16 bit), e.g. 4232 = 42.32 °C 7) Language: LANG_ID as ASCII code, e.g. "DE" = "D" + "E" = 0x44 + 0x45

Page 260: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

260

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

DS2 – Digital inputs of the slaves and master flags 8754

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0 reserved Slave 1(A): D3...D0 reserved reserved

1 reserved Slave 3(A): D3...D0 reserved Slave 2(A): D3...D0

2 reserved Slave 5(A): D3...D0 reserved Slave 4(A): D3...D0

3 reserved Slave 7(A): D3...D0 reserved Slave 6(A): D3...D0

4 reserved Slave 9(A): D3...D0 reserved Slave 8(A): D3...D0

5 reserved Slave 11(A): D3...D0 reserved Slave 10(A): D3...D0

6 reserved Slave 13(A): D3...D0 reserved Slave 12(A): D3...D0

7 reserved Slave 15(A): D3...D0 reserved Slave 14(A): D3...D0

8 reserved Slave 17(A): D3...D0 reserved Slave 16(A): D3...D0

9 reserved Slave 19(A): D3...D0 reserved Slave 18(A): D3...D0

10 reserved Slave 21(A): D3...D0 reserved Slave 20(A): D3...D0

11 reserved Slave 23(A): D3...D0 reserved Slave 22(A): D3...D0

12 reserved Slave 25(A): D3...D0 reserved Slave 24(A): D3...D0

13 reserved Slave 27(A): D3...D0 reserved Slave 26(A): D3...D0

14 reserved Slave 29(A): D3...D0 reserved Slave 28(A): D3...D0

15 reserved Slave 31(A): D3...D0 reserved Slave 30(A): D3...D0

16 reserved Slave 1B: D3...D0 reserved reserved

17 reserved Slave 3B: D3...D0 reserved Slave 2B: D3...D0

18 reserved Slave 5B: D3...D0 reserved Slave 4B: D3...D0

19 reserved Slave 7B: D3...D0 reserved Slave 6B: D3...D0

20 reserved Slave 9B: D3...D0 reserved Slave 8B: D3...D0

21 reserved Slave 11B: D3...D0 reserved Slave 10B: D3...D0

22 reserved Slave 13B: D3...D0 reserved Slave 12B: D3...D0

23 reserved Slave 15B: D3...D0 reserved Slave 14B: D3...D0

24 reserved Slave 17B: D3...D0 reserved Slave 16B: D3...D0

25 reserved Slave 19B: D3...D0 reserved Slave 18B: D3...D0

26 reserved Slave 21B: D3...D0 reserved Slave 20B: D3...D0

27 reserved Slave 23B: D3...D0 reserved Slave 22B: D3...D0

28 reserved Slave 25B: D3...D0 reserved Slave 24B: D3...D0

29 reserved Slave 27B: D3...D0 reserved Slave 26B: D3...D0

30 reserved Slave 29B: D3...D0 reserved Slave 28B: D3...D0

31 reserved Slave 31B: D3...D0 reserved Slave 30B: D3...D0

32 AS-i master status flags (→ AS-i master status flags (→ page 180))

33 Execution control flags (→ Execution control flags (→ page 181))

34 Host flags (→ Host flags (→ page 182))

35 DAE / EE-Flags (→ DAE/EE flags (→ page 183))

Page 261: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

261

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

DS3 – Analogue inputs of slaves 1(A)...15(B) 8756

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0...4 Analogue input data of single slave 1 or of (slave 1A and slave 1B)

5...9 Analogue input data of single slave 2 or of (slave 2A and slave 2B)

10...14 Analogue input data of single slave 3 or of (slave 3A and slave 3B)

15...19 Analogue input data of single slave 4 or of (slave 4A and slave 4B)

20...24 Analogue input data of single slave 5 or of (slave 5A and slave 5B)

25...29 Analogue input data of single slave 6 or of (slave 6A and slave 6B)

30...34 Analogue input data of single slave 7 or of (slave 7A and slave 7B)

35...39 Analogue input data of single slave 8 or of (slave 8A and slave 8B)

40...44 Analogue input data of single slave 9 or of (slave 9A and slave 9B)

45...49 Analogue input data of single slave 10 or of (slave 10A and slave 10B)

50...54 Analogue input data of single slave 11 or of (slave 11A and slave 11B)

55...59 Analogue input data of single slave 12 or of (slave 12A and slave 12B)

60...64 Analogue input data of single slave 13 or of (slave 13A and slave 13B)

65...69 Analogue input data of single slave 14 or of (slave 14A and slave 14B)

70...74 Analogue input data of single slave 15 or of (slave 15A and slave 15B)

Page 262: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

262

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Details of the 5-word areas 8758

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

n Analogue value channel 0 of single slave x or channel 0 of slave xA

n+1 Analogue value channel 1 of single slave x or channel 1 of slave xA

n+2 Analogue value channel 2 of single slave x or channel 0 of slave xB

n+3 Analogue value channel 3 of single slave x or channel 1 of slave xB

n+4 TIB -- TIA -- TOB -- TOA -- O3 V3 O2 V2 O1 V1 O0 V0

Legend:

On overflow bit 1 bit 0 = data is in the valid range 1 = data is in the invalid range (especially in case of input modules when the measuring range is not reached or exceeded)

TIx transfer to the slave (transfer Input)

1 bit from master profile M4 onwards: 0 = slave transmits input data as a value (15 bits long, plus sign) 1 = slave transmits input data as a bit pattern (16 bits long, no sign)

TOx transfer from the slave (transfer output)

1 bit from master profile M4 onwards: 0 = slave receives output data as a value (15 bits long, plus sign) 1 = slave receives output data as a bit pattern (16 bits long, no sign)

Vn valid bit 1 bit 0 = values in channel n are invalid 1 = values in channel n are valid Output data must be valid (Vn = 1) to be enabled in the AS-i slave!

Page 263: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

263

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

DS4 – Analogue inputs of slaves 16(A)...31(B) 8759

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0...4 Analogue input data of single slave 16 or of (slave 16A and slave 16B)

5...9 Analogue input data of single slave 17 or of (slave 17A and slave 17B)

10...14 Analogue input data of single slave 18 or of (slave 18A and slave 18B)

15...19 Analogue input data of single slave 19 or of (slave 19A and slave 19B)

20...24 Analogue input data of single slave 20 or of (slave 20A and slave 20B)

25...29 Analogue input data of single slave 21 or of (slave 21A and slave 21B)

30...34 Analogue input data of single slave 22 or of (slave 22A and slave 22B)

35...39 Analogue input data of single slave 23 or of (slave 23A and slave 23B)

40...44 Analogue input data of single slave 24 or of (slave 24A and slave 24B)

45...49 Analogue input data of single slave 25 or of (slave 25A and slave 25B)

50...54 Analogue input data of single slave 26 or of (slave 26A and slave 26B)

55...59 Analogue input data of single slave 27 or of (slave 27A and slave 27B)

60...64 Analogue input data of single slave 28 or of (slave 28A and slave 28B)

65...69 Analogue input data of single slave 29 or of (slave 29A and slave 29B)

70...74 Analogue input data of single slave 30 or of (slave 30A and slave 30B)

75...79 Analogue input data of single slave 31 or of (slave 31A and slave 31B)

Page 264: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

264

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Details of the 5-word areas 8758

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

n Analogue value channel 0 of single slave x or channel 0 of slave xA

n+1 Analogue value channel 1 of single slave x or channel 1 of slave xA

n+2 Analogue value channel 2 of single slave x or channel 0 of slave xB

n+3 Analogue value channel 3 of single slave x or channel 1 of slave xB

n+4 TIB -- TIA -- TOB -- TOA -- O3 V3 O2 V2 O1 V1 O0 V0

Legend:

On overflow bit 1 bit 0 = data is in the valid range 1 = data is in the invalid range (especially in case of input modules when the measuring range is not reached or exceeded)

TIx transfer to the slave (transfer Input)

1 bit from master profile M4 onwards: 0 = slave transmits input data as a value (15 bits long, plus sign) 1 = slave transmits input data as a bit pattern (16 bits long, no sign)

TOx transfer from the slave (transfer output)

1 bit from master profile M4 onwards: 0 = slave receives output data as a value (15 bits long, plus sign) 1 = slave receives output data as a bit pattern (16 bits long, no sign)

Vn valid bit 1 bit 0 = values in channel n are invalid 1 = values in channel n are valid Output data must be valid (Vn = 1) to be enabled in the AS-i slave!

Page 265: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

265

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

DS5 – Digital outputs of the slaves 8761

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0 reserved slave 1(A): D3...D0 reserved reserved

1 reserved Slave 3(A): D3...D0 reserved Slave 2(A): D3...D0

2 reserved Slave 5(A): D3...D0 reserved Slave 4(A): D3...D0

3 reserved Slave 7(A): D3...D0 reserved Slave 6(A): D3...D0

4 reserved Slave 9(A): D3...D0 reserved Slave 8(A): D3...D0

5 reserved Slave 11(A): D3...D0 reserved Slave 10(A): D3...D0

6 reserved Slave 13(A): D3...D0 reserved Slave 12(A): D3...D0

7 reserved Slave 15(A): D3...D0 reserved Slave 14(A): D3...D0

8 reserved Slave 17(A): D3...D0 reserved Slave 16(A): D3...D0

9 reserved Slave 19(A): D3...D0 reserved Slave 18(A): D3...D0

10 reserved Slave 21(A): D3...D0 reserved Slave 20(A): D3...D0

11 reserved Slave 23(A): D3...D0 reserved Slave 22(A): D3...D0

12 reserved Slave 25(A): D3...D0 reserved Slave 24(A): D3...D0

13 reserved Slave 27(A): D3...D0 reserved Slave 26(A): D3...D0

14 reserved Slave 29(A): D3...D0 reserved Slave 28(A): D3...D0

15 reserved Slave 31(A): D3...D0 reserved Slave 30(A): D3...D0

16 reserved Slave 1B: D3...D0 reserved reserved

17 reserved Slave 3B: D3...D0 reserved Slave 2B: D3...D0

18 reserved Slave 5B: D3...D0 reserved Slave 4B: D3...D0

19 reserved Slave 7B: D3...D0 reserved Slave 6B: D3...D0

20 reserved Slave 9B: D3...D0 reserved Slave 8B: D3...D0

21 reserved Slave 11B: D3...D0 reserved Slave 10B: D3...D0

22 reserved Slave 13B: D3...D0 reserved Slave 12B: D3...D0

23 reserved Slave 15B: D3...D0 reserved Slave 14B: D3...D0

24 reserved Slave 17B: D3...D0 reserved Slave 16B: D3...D0

25 reserved Slave 19B: D3...D0 reserved Slave 18B: D3...D0

26 reserved Slave 21B: D3...D0 reserved Slave 20B: D3...D0

27 reserved Slave 23B: D3...D0 reserved Slave 22B: D3...D0

28 reserved Slave 25B: D3...D0 reserved Slave 24B: D3...D0

29 reserved Slave 27B: D3...D0 reserved Slave 26B: D3...D0

30 reserved Slave 29B: D3...D0 reserved Slave 28B: D3...D0

31 reserved Slave 31B: D3...D0 reserved Slave 30B: D3...D0

Page 266: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

266

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

DS6 – Analogue outputs of slaves 1(A)...15(B) 8763

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0...3 analogue output data of single slave 1 or of (slave 1A and slave 1B)

4...7 Analogue output data of single slave 2 or of (slave 2A and slave 2B)

8...11 Analogue output data of single slave 3 or of (slave 3A and slave 3B)

12...15 Analogue output data of single slave 4 or of (slave 4A and slave 4B)

16...19 Analogue output data of single slave 5 or of (slave 5A and slave 5B)

20...23 Analogue output data of single slave 6 or of (slave 6A and slave 6B)

24...27 Analogue output data of single slave 7 or of (slave 7A and slave 7B)

28...31 Analogue output data of single slave 8 or of (slave 8A and slave 8B)

32...35 Analogue output data of single slave 9 or of (slave 9A and slave 9B)

36...39 Analogue output data of single slave 10 or of (slave 10A and slave 10B)

40...43 Analogue output data of single slave 11 or of (slave 11A and slave 11B)

44...47 Analogue output data of single slave 12 or of (slave 12A and slave 12B)

48...51 Analogue output data of single slave 13 or of (slave 13A and slave 13B)

52...55 Analogue output data of single slave 14 or of (slave 14A and slave 14B)

56...59 Analogue output data of single slave 15 or of (slave 15A and slave 15B)

>

Details 4 channels per analogue slave 8765

The following table shows the structure of the data image to set the parameter:

Analogue channels per input slave = 4

Analogue channels per output slave = 4

Word Offset-Nr.

Content of the transferred word for parameter setting = 4 channels

n Mx / slave m(A) / channel

n+1 Mx / slave m(A) / channel

n+2 Mx / slave m(A) / channel 1 = Mx / slave mB / channel 1

n+3 Mx / slave m(A) / channel 2 = Mx / slave mB / channel 2

Legend:

n ... Number of 4 word blocks 1 = for setting 4 words ... 15 = for setting 60 words

x ... 1 = AS-i master 1 2 = AS-i master 2

m ... Numeric part of the selected AS-i slave address

>

Page 267: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

267

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

DS7 – Analogue outputs of slaves 16(A)...31(B) 8766

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0...3 analogue output data of single slave 16 or of (slave 16A and slave 16B)

4...7 Analogue output data of single slave 17 or of (slave 17A and slave 17B)

8...11 Analogue output data of single slave 18 or of (slave 18A and slave 18B)

12...15 Analogue output data of single slave 19 or of (slave 19A and slave 19B)

16...19 Analogue output data of single slave 20 or of (slave 20A and slave 20B)

20...23 Analogue output data of single slave 21 or of (slave 21A and slave 21B)

24...27 Analogue output data of single slave 22 or of (slave 22A and slave 22B)

28...31 Analogue output data of single slave 23 or of (slave 23A and slave 23B)

32...35 Analogue output data of single slave 24 or of (slave 24A and slave 24B)

36...39 Analogue output data of single slave 25 or of (slave 25A and slave 25B)

40...43 Analogue output data of single slave 26 or of (slave 26 and slave 26B)

44...47 Analogue output data of single slave 27 or of (slave 27 and slave 27B)

48...51 Analogue output data of single slave 28 or of (slave 28 and slave 28B)

52...55 Analogue output data of single slave 29 or of (slave 29 and slave 29B)

56...59 Analogue output data of single slave 30 or of (slave 30 and slave 30B)

60...63 Analogue output data of single slave 31 or of (slave 31and slave 31B)

>

Details 4 channels per analogue slave 8765

The following table shows the structure of the data image to set the parameter:

Analogue channels per input slave = 4

Analogue channels per output slave = 4

Word Offset-Nr.

Content of the transferred word for parameter setting = 4 channels

n Mx / slave m(A) / channel

n+1 Mx / slave m(A) / channel

n+2 Mx / slave m(A) / channel 1 = Mx / slave mB / channel 1

n+3 Mx / slave m(A) / channel 2 = Mx / slave mB / channel 2

Legend:

n ... Number of 4 word blocks 1 = for setting 4 words ... 15 = for setting 60 words

x ... 1 = AS-i master 1 2 = AS-i master 2

m ... Numeric part of the selected AS-i slave address

>

Page 268: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

268

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

DS8 – Status of the analogue output data of the slaves 1...31 8768

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0 reserved

1 Status of the analogue output data of single slave 1 or of (slave 1A and slave 1B)

2 Status of the analogue output data of single slave 2 or of (slave 2A and slave 2B)

3 Status of the analogue output data of single slave 3 or of (slave 3A and slave 3B)

4 Status of the analogue output data of single slave 4 or of (slave 4A and slave 4B)

5 Status of the analogue output data of single slave 5 or of (slave 5A and slave 5B)

6 Status of the analogue output data of single slave 6 or of (slave 6A and slave 6B)

7 Status of the analogue output data of single slave 7 or of (slave 7A and slave 7B)

8 Status of the analogue output data of single slave 8 or of (slave 8A and slave 8B)

9 Status of the analogue output data of single slave 9 or of (slave 9A and slave 9B)

10 Status of the analogue output data of single slave 10 or of (slave 10A and slave 10B)

11 Status of the analogue output data of single slave 11 or of (slave 11A and slave 11B)

12 Status of the analogue output data of single slave 12 or of (slave 12A and slave 12B)

13 Status of the analogue output data of single slave 13 or of (slave 13A and slave 13B)

14 Status of the analogue output data of single slave 14 or of (slave 14A and slave 14B)

15 Status of the analogue output data of single slave 15 or of (slave 15A and slave 15B)

16 Status of the analogue output data of single slave 16 or of (slave 16A and slave 16B)

17 Status of the analogue output data of single slave 17 or of (slave 17A and slave 17B)

18 Status of the analogue output data of single slave 18 or of (slave 18A and slave 18B)

19 Status of the analogue output data of single slave 19 or of (slave 19A and slave 19B)

20 Status of the analogue output data of single slave 20 or of (slave 20A and slave 20B)

21 Status of the analogue output data of single slave 21 or of (slave 21A and slave 21B)

22 Status of the analogue output data of single slave 22 or of (slave 22A and slave 22B)

23 Status of the analogue output data of single slave 23 or of (slave 23A and slave 23B)

24 Status of the analogue output data of single slave 24 or of (slave 24A and slave 24B)

25 Status of the analogue output data of single slave 25 or of (slave 25A and slave 25B)

26 Status of the analogue output data of single slave 26 or of (slave 26A and slave 26B)

27 Status of the analogue output data of single slave 27 or of (slave 27A and slave 27B)

28 Status of the analogue output data of single slave 28 or of (slave 28A and slave 28B)

29 Status of the analogue output data of single slave 29 or of (slave 29A and slave 29B)

30 Status of the analogue output data of single slave 30 or of (slave 30A and slave 30B)

31 Status of the analogue output data of single slave 31 or of (slave 31A and slave 31B)

32 reserved

Page 269: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

269

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Details of the words shown above:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

n -- TOB -- TOA -- OVB -- OVA reserved

Legend:

OVx output valid 1 bit channel-independent bit "output data valid" from the slave:

CTT1: 0 = more than 3.5 s have elapsed since the last update of the output values 1 = slave requests new output data within the next 3 s

CTT2…CTT5: 0 = slave receives no new output data 1 = slave receives new output data

Only valid for analogue output slaves. For input slaves set OVx = "0"!

TOx transfer from the slave (transfer output)

1 bit from master profile M4 onwards: 0 = slave receives output data as a value (15 bits long, plus sign) 1 = slave receives output data as a bit pattern (16 bits long, no sign)

Page 270: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

270

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

DS9 – Slave lists LAS, LDS, LPF, LCE 8770

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0...3 LAS / list of active slaves

4...7 LDS / list of detected slaves

8...11 LPF / list of slaves with periphery faults

12...15 LCE / list of slaves with configuration errors

>

Details of the slave lists 8772

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

n 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0 *)

n+1 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

n+2 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B res.

n+3 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

*) LAS and LPS have no slave 0, therefore this bit is set to 0!

>

DS10 – Slave list LPS 8773

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0...3 List of projected slaves LPS

>

Details of the slave lists 8772

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

n 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0 *)

n+1 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

n+2 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B res.

n+3 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

*) LAS and LPS have no slave 0, therefore this bit is set to 0!

Page 271: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

271

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

DS11 – Current configuration data CDI 8775

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

ID2 code ID1 code ID code IO code

0 Slave 0 *)

1 Slave 1(A)

2 Slave 2(A)

3 Slave 3(A)

4 Slave 4(A)

5 Slave 5(A)

6 Slave 6(A)

7 Slave 7(A)

8 Slave 8(A)

9 Slave 9(A)

10 Slave 10(A)

11 Slave 11(A)

12 Slave 12(A)

13 Slave 13(A)

14 Slave 14(A)

15 Slave 15(A)

16 Slave 16(A)

17 Slave 17(A)

18 Slave 18(A)

19 Slave 19(A)

20 Slave 20(A)

21 Slave 21(A)

22 Slave 22(A)

23 Slave 23(A)

24 Slave 24(A)

25 Slave 25(A)

26 Slave 26(A)

27 Slave 27(A)

28 Slave 28(A)

29 Slave 29(A)

20 Slave 30(A)

31 Slave 31(A)

32 reserved

33 Slave 1B

34 Slave 2B

Page 272: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

272

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

ID2 code ID1 code ID code IO code

35 Slave 3B

36 Slave 4B

37 Slave 5B

38 Slave 6B

39 Slave 7B

40 Slave 8B

41 Slave 9B

42 Slave 10B

43 Slave 11B

44 Slave 12B

45 Slave 13B

46 Slave 14B

47 Slave 15B

48 Slave 16B

49 Slave 17B

50 Slave 18B

51 Slave 19B

52 Slave 20B

53 Slave 21B

54 Slave 22B

55 Slave 23B

56 Slave 24B

57 Slave 25B

58 Slave 26B

59 Slave 27B

60 Slave 28B

61 Slave 29B

62 Slave 30B

63 Slave 31B

*) contents for slave 0 only valid in CDI

Page 273: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

273

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

DS12 – Projected configuration data PCD 8779

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

ID2 code ID1 code ID code IO code

0 reserved

1 Slave 1(A)

2 Slave 2(A)

3 Slave 3(A)

4 Slave 4(A)

5 Slave 5(A)

6 Slave 6(A)

7 Slave 7(A)

8 Slave 8(A)

9 Slave 9(A)

10 Slave 10(A)

11 Slave 11(A)

12 Slave 12(A)

13 Slave 13(A)

14 Slave 14(A)

15 Slave 15(A)

16 Slave 16(A)

17 Slave 17(A)

18 Slave 18(A)

19 Slave 19(A)

20 Slave 20(A)

21 Slave 21(A)

22 Slave 22(A)

23 Slave 23(A)

24 Slave 24(A)

25 Slave 25(A)

26 Slave 26(A)

27 Slave 27(A)

28 Slave 28(A)

29 Slave 29(A)

20 Slave 30(A)

31 Slave 31(A)

32 reserved

33 Slave 1B

34 Slave 2B

Page 274: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

274

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

ID2 code ID1 code ID code IO code

35 Slave 3B

36 Slave 4B

37 Slave 5B

38 Slave 6B

39 Slave 7B

40 Slave 8B

41 Slave 9B

42 Slave 10B

43 Slave 11B

44 Slave 12B

45 Slave 13B

46 Slave 14B

47 Slave 15B

48 Slave 16B

49 Slave 17B

50 Slave 18B

51 Slave 19B

52 Slave 20B

53 Slave 21B

54 Slave 22B

55 Slave 23B

56 Slave 24B

57 Slave 25B

58 Slave 26B

59 Slave 27B

60 Slave 28B

61 Slave 29B

62 Slave 30B

63 Slave 31B

Page 275: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

275

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

DS13 – Image of the input parameters of the slaves 8781

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0 reserved Slave 1(A): P3...P0 reserved reserved

1 reserved Slave 3(A): P3...P0 reserved Slave 2(A): P3...P0

2 reserved Slave 5(A): P3...P0 reserved Slave 4(A): P3...P0

3 reserved Slave 7(A): P3...P0 reserved Slave 6(A): P3...P0

4 reserved Slave 9(A): P3...P0 reserved Slave 8(A): P3...P0

5 reserved Slave 11(A): P3...P0 reserved Slave 10(A): P3...P0

6 reserved Slave 13(A): P3...P0 reserved Slave 12(A): P3...P0

7 reserved Slave 15(A): P3...P0 reserved Slave 14(A): P3...P0

8 reserved Slave 17(A): P3...P0 reserved Slave 16(A): P3...P0

9 reserved Slave 19(A): P3...P0 reserved Slave 18(A): P3...P0

10 reserved Slave 21(A): P3...P0 reserved Slave 20(A): P3...P0

11 reserved Slave 23(A): P3...P0 reserved Slave 22(A): P3...P0

12 reserved Slave 25(A): P3...P0 reserved Slave 24(A): P3...P0

13 reserved Slave 27(A): P3...P0 reserved Slave 26(A): P3...P0

14 reserved Slave 29(A): P3...P0 reserved Slave 28(A): P3...P0

15 reserved Slave 31(A): P3...P0 reserved Slave 30(A): P3...P0

16 reserved Slave 1B: P3...P0 reserved reserved

17 reserved Slave 3B: P3...P0 reserved Slave 2B: P3...P0

18 reserved Slave 5B: P3...P0 reserved Slave 4B: P3...P0

19 reserved Slave 7B: P3...P0 reserved Slave 6B: P3...P0

20 reserved Slave 9B: P3...P0 reserved Slave 8B: P3...P0

21 reserved Slave 11B: P3...P0 reserved Slave 10B: P3...P0

22 reserved Slave 13B: P3...P0 reserved Slave 12B: P3...P0

23 reserved Slave 15B: P3...P0 reserved Slave 14B: P3...P0

24 reserved Slave 17B: P3...P0 reserved Slave 16B: P3...P0

25 reserved Slave 19B: P3...P0 reserved Slave 18B: P3...P0

26 reserved Slave 21B: P3...P0 reserved Slave 20B: P3...P0

27 reserved Slave 23B: P3...P0 reserved Slave 22B: P3...P0

28 reserved Slave 25B: P3...P0 reserved Slave 24B: P3...P0

29 reserved Slave 27B: P3...P0 reserved Slave 26B: P3...P0

30 reserved Slave 29B: P3...P0 reserved Slave 28B: P3...P0

31 reserved Slave 31B: P3...P0 reserved Slave 30B: P3...P0

Page 276: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

276

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

DS14 – Image of the output parameters of the slaves 8783

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0 reserved Slave 1(A): P3...P0 reserved reserved

1 reserved Slave 3(A): P3...P0 reserved Slave 2(A): P3...P0

2 reserved Slave 5(A): P3...P0 reserved Slave 4(A): P3...P0

3 reserved Slave 7(A): P3...P0 reserved Slave 6(A): P3...P0

4 reserved Slave 9(A): P3...P0 reserved Slave 8(A): P3...P0

5 reserved Slave 11(A): P3...P0 reserved Slave 10(A): P3...P0

6 reserved Slave 13(A): P3...P0 reserved Slave 12(A): P3...P0

7 reserved Slave 15(A): P3...P0 reserved Slave 14(A): P3...P0

8 reserved Slave 17(A): P3...P0 reserved Slave 16(A): P3...P0

9 reserved Slave 19(A): P3...P0 reserved Slave 18(A): P3...P0

10 reserved Slave 21(A): P3...P0 reserved Slave 20(A): P3...P0

11 reserved Slave 23(A): P3...P0 reserved Slave 22(A): P3...P0

12 reserved Slave 25(A): P3...P0 reserved Slave 24(A): P3...P0

13 reserved Slave 27(A): P3...P0 reserved Slave 26(A): P3...P0

14 reserved Slave 29(A): P3...P0 reserved Slave 28(A): P3...P0

15 reserved Slave 31(A): P3...P0 reserved Slave 30(A): P3...P0

16 reserved Slave 1B: P3...P0 reserved reserved

17 reserved Slave 3B: P3...P0 reserved Slave 2B: P3...P0

18 reserved Slave 5B: P3...P0 reserved Slave 4B: P3...P0

19 reserved Slave 7B: P3...P0 reserved Slave 6B: P3...P0

20 reserved Slave 9B: P3...P0 reserved Slave 8B: P3...P0

21 reserved Slave 11B: P3...P0 reserved Slave 10B: P3...P0

22 reserved Slave 13B: P3...P0 reserved Slave 12B: P3...P0

23 reserved Slave 15B: P3...P0 reserved Slave 14B: P3...P0

24 reserved Slave 17B: P3...P0 reserved Slave 16B: P3...P0

25 reserved Slave 19B: P3...P0 reserved Slave 18B: P3...P0

26 reserved Slave 21B: P3...P0 reserved Slave 20B: P3...P0

27 reserved Slave 23B: P3...P0 reserved Slave 22B: P3...P0

28 reserved Slave 25B: P3...P0 reserved Slave 24B: P3...P0

29 reserved Slave 27B: P3...P0 reserved Slave 26B: P3...P0

30 reserved Slave 29B: P3...P0 reserved Slave 28B: P3...P0

31 reserved Slave 31B: P3...P0 reserved Slave 30B: P3...P0

Page 277: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

277

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

DS15 – Slave error counter, configuration error counter, AS-i cycle counter 8785

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0 Error counter in slave 0

1 Error counter in slave 1(A)

2 Error counter in slave 2(A)

3 Error counter in slave 3(A)

4 Error counter in slave 4(A)

5 Error counter in slave 5(A)

6 Error counter in slave 6(A)

7 Error counter in slave 7(A)

8 Error counter in slave 8(A)

9 Error counter in slave 9(A)

10 Error counter in slave 10(A)

11 Error counter in slave 11(A)

12 Error counter in slave 12(A)

13 Error counter in slave 13(A)

14 Error counter in slave 14(A)

15 Error counter in slave 15(A)

16 Error counter in slave 16(A)

17 Error counter in slave 17(A)

18 Error counter in slave 18(A)

19 Error counter in slave 19(A)

20 Error counter in slave 20(A)

21 Error counter in slave 21(A)

22 Error counter in slave 22(A)

23 Error counter in slave 23(A)

24 Error counter in slave 24(A)

25 Error counter in slave 25(A)

26 Error counter in slave 26(A)

27 Error counter in slave 27(A)

28 Error counter in slave 28(A)

29 Error counter in slave 29(A)

20 Error counter in slave 30(A)

31 Error counter in slave 31(A)

32 reserved

33 Error counter in slave 1B

34 Error counter in slave 2B

35 Error counter in slave 3B

36 Error counter in slave 4B

Page 278: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

278

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

37 Error counter in slave 5B

38 Error counter in slave 6B

39 Error counter in slave 7B

40 Error counter in slave 8B

41 Error counter in slave 9B

42 Error counter in slave 10B

43 Error counter in slave 11B

44 Error counter in slave 12B

45 Error counter in slave 13B

46 Error counter in slave 14B

47 Error counter in slave 15B

48 Error counter in slave 16B

49 Error counter in slave 17B

50 Error counter in slave 18B

51 Error counter in slave 19B

52 Error counter in slave 20B

53 Error counter in slave 21B

54 Error counter in slave 22B

55 Error counter in slave 23B

56 Error counter in slave 24B

57 Error counter in slave 25B

58 Error counter in slave 26B

59 Error counter in slave 27B

60 Error counter in slave 28B

61 Error counter in slave 29B

62 Error counter in slave 30B

63 Error counter in slave 31B

64 AS-i cycle counter

65 Configuration error counter

66 AS-i error status

67 Telegram error rate

68 Message error counter

69 Voltage error counter 22.5V

70 Voltage error counter 19V

71 Earth fault counter

Page 279: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

279

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Legend:

AS-i error status ... Bit 0: Bit 1: Bit 2: Bit 3: Bit 4: Bit 8: Bit 9: Bit 10: Bit 11: Bit 12: Bit 13: Bit 14: Bit 15:

Configuration error type 1 (missing slave) Configuration error type 2 (too many slaves) Configuration error type 3 (slave with wrong profile) Peripheral fault Double address internal AS-i master error Projection mode Slave address 0 detected Earth fault Voltage drop below 22.5 V Voltage drop below 19.0 V reserved reserved

Telegram error rate ... Number of faulty telegrams during the past 2000 telegram cycles

Symmetry ... AS-i symmetry from -100% to +100%, 0% = symmetrical-to-ground Bit15: bit with sign

Page 280: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

280

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

DS17 – Error lists LCEMS, LCEAS, LDAE 15911

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0...3 LCEMS (list of configuration errors - missing slaves)

4...7 LCEAS (list of configuration errors - additional slaves)

8...11 LDAE (list of double address errors)

>

Details of the error lists 6658

The error lists (LCEMS, LCEAS, LDAE) have a size of 64 bits each. The respective bits each represent a slave address:

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

n 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) 0

n+1 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

n+2 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B -

n+3 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

Page 281: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

281

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

DS18 – Fieldbus information 17038

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0 Fieldbus state Fieldbus type

1 Ethernet connection status Profibus slave address

2 Profinet/EtherNet/IP IP address (byte 2) Profinet/EtherNet/IP IP address (byte 1, MSB)

3 Profinet/EtherNet/IP IP address (byte 4, LSB) Profinet/EtherNet/IP IP address (byte 3)

4 Profinet/EtherNet/IP subnet mask (byte 2) Profinet/EtherNet/IP subnet mask (byte 1, MSB)

5 Profinet/EtherNet/IP subnet mask (byte 4, LSB) Profinet/EtherNet/IP subnet mask (byte 3)

6 Profinet/EtherNet/IP gateway address (byte 2) Profinet/EtherNet/IP gateway address (byte 1, MSB)

7 Profinet/EtherNet/IP gateway address (byte 4, LSB) Profinet/EtherNet/IP gateway address (byte 3)

8 MAC0 (byte 2) MAC0 (byte 1, LSB)

9 MAC0 (byte 4) MAC0 (byte 3)

10 MAC0 (byte 6, MSB) MAC0 (byte 5)

11 MAC1 (byte 2) MAC1 (byte 1, LSB)

12 MAC1 (byte 4) MAC1 (byte 3)

13 MAC1 (byte 6, MSB) MAC1 (byte 5)

14 MAC2 (byte 2) MAC2 (byte 1, LSB)

15 MAC2 (byte 4) MAC2 (byte 3)

16 MAC2 (byte 6, MSB) MAC2 (byte 1, LSB)

17 Profinet host address (byte 2) Profinet host address (byte 1, MSB)

18 Profinet host address (byte 4, LSB) Profinet host address (byte 3)

Legend:

Fieldbus type

Name of the fieldbus 1 byte 0x00 = no fieldbus present 0x01 = Profinet 0x02 = Profibus 0x03 = EtherNet/IP

Fieldbus status

Status of the fieldbus connection

1 byte 0x00 = initialisation 0x01 = waiting for connection 0x02 = connection is being established 0x03 = configuration of the connection in progress 0x04 = parameter setting in progress 0x05 = waiting for module configuration 0x06 = cyclic data exchange with the fieldbus controller/host 0x07 = connection establishment

Profibus slave address

Profibus address of the device

1 byte 0x00 = no Profibus? 0x03 = address 3 ... 0x7B = address 123

Ethernet connection status

Status and Ethernet connections on ports X6 and X7

1 byte 0x00 = no connection 0x01 = connection on port X7 established, no connection on port X6 0x02 = connection on port X6 established, no connection on port X7 0x03 = connection on ports X6 and X7 established

Page 282: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

282

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Profinet/ EtherNet/IP IP address

IP address of the device 4 bytes One address segment per byte. e.g. 192.168.0.102 Byte 1: 192 = 0xC0 Byte 2: 168 = 0xA8 Byte 3: 0 = 0x00 Byte 4: 102 = 0x66

Profinet/ EtherNet/IP- Subnet mask

Subnet mask of the Ethernet network

4 bytes see Profinet/EtherNet/IP IP address

Profinet/ EtherNet/IP gateway address

IP address of the EtherNet gateway

4 bytes see Profinet/EtherNet/IP IP address

MAC0 MAC0-ID of the device 6 bytes One MAC segment per byte: e.g. 00:02:01:01:98:D2 Byte 1: D2 ... Byte 6: 00

For EtherNet/IP, MAC0 = 00:00:00:00:00:00.

MAC1 MAC1-ID of the device 6 bytes see MAC0

MAC2 MAC2-ID of the device 6 bytes see MAC0

MAC 1 equals MAC2

Profinet host address

IP address of the Profinet host

4 bytes see Profinet/EtherNet/IP IP address

No host address is displayed in EtherNet/IP

Page 283: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

283

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command channels

Principle of the command channels .....................................................................................................284 System commands ...............................................................................................................................285 AS-i master commands ........................................................................................................................304

16573

Page 284: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

284

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Principle of the command channels 13543

A command channel consists of a request channel and a response channel.

Command request channel (fieldbus master >>> device)

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 user ID

2 command number

3...120 command parameters

Command response channel (device >>> fieldbus master)

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5...120 reply data to the command

Unused bytes receive invalid values from old command replies. DO NOT evaluate!

>

Command status 8795

Status Status code [hex]

Description

OK 00 Command execution was successful. Response data is available and valid.

FAILED 01 Error when executing the command. The exact cause of the error occurred is stated in the command-specific error code. The response data is invalid.

TO 02 Timeout error: The command was cancelled due to timeout.

UC 03 Unknown Command: The transmitted command number is not known in the system.

NOP 04 Not valid parameter: The transmitted command parameter is invalid.

Page 285: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

285

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

System commands

Overview: System commands ..............................................................................................................286 Command 257 (0x0101) – Quick setup AS-i master 1 + 2...................................................................287 Command 259 (0x0103) – Select user language .................................................................................289 Command 260 (0x0104) – Change display settings ............................................................................291 Command 261 (0x0105) – Set output control ......................................................................................292 Command 262 (0x0106) – Set standard PLC operating mode ............................................................293 Command 265 (0x0109) – Set date/time .............................................................................................294 Command 266 (0x010A) – Set parameters of the NTP server ............................................................296 Command 267 (0x010B) – Read date / time / NTP settings ................................................................298 Command 268 (0x010C) – Reboot system ..........................................................................................300 Command 269 (0x010D) – Read fieldbus info .....................................................................................302 Command 272 (0x0110) – Display target visualisation ........................................................................303

11077

Page 286: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

286

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Overview: System commands 11078

Comm. no. [hex]

Comm. no. [dec]

Description

0101 257 Quick setup AS-i master 1 (and AS-i master 2, if available)

0103 259 Change the user language

0104 260 Change the display settings

0105 261 Configure the output access

0106 262 Set the standard PLC operating mode

0109 265 Set the date / time

010A 266 Set the NTP server parameters

010B 267 Read date / time / NTP settings

010C 268 Reboot the system

010D 269 Read fieldbus information (can only be executed in CODESYS!)

0110 272 Display target visualization

Page 287: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

287

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 257 (0x0101) – Quick setup AS-i master 1 + 2 11079

>

Command request channel (fieldbus master >>> device) 11080

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved M2 M1

4 ...120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

M1 AS-i master 1 1 bit 0 = "Quick set-up" command is NOT executed on the master 1 = "Quick set-up" command is executed on the master

M2 AS-i master 2 1 bit 0 = "Quick set-up" command is NOT executed on the master 1 = "Quick set-up" command is executed on the master

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

The command "blocks" further processing as long as the quick set-up needs. That means that the WRREC command signals "busy" until the function result is available. This may take a few seconds.

Page 288: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

288

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 11081

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code AS-i master 2

Possible command error codes (→ page 288) command error code AS-i master 1

Possible command error codes (→ page 288)

>

Possible command error codes 11087

Error Code [hex]

Error Meaning

0x00 no error

0x03 SD0 slave with address 0 connected

0x04 IM - no master M1 and/or M2 specified or: - master M2 does not exist (for units with 1 AS-i master)

When the Quick Setup is not executed for an AS-i master, the return value is always 0x00 (= OK).

The command status has the value Failed when one of the errors is present on AS-i master 1

or 2 after command execution.

Page 289: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

289

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 259 (0x0103) – Select user language 11089

Via the command the user lanaguage for the local HMI and the web interface can be set. The language setting always refers to both user interfaces. >

Command request channel (fieldbus master >>> device) 11090

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 LANG_ID

4 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legende:

MSG_ID User language 1 word 0x0000 = no language selection, only return active language 0x4445 = DE, German 0x454E = EN, English (default) 0x4652 = FR, French 0x4954 = IT, Italian 0x4553 = ES, Spanish 0x5054 = PT, Portuguese

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 290: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

290

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 18011

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 current LANG_ID

>

Possible command error codes 11095

Error Code [hex]

Error Meaning

0x00 no error

0x01 IL Language is unknown or not available in this software version

Error code only appears if command status = FAILED.

The error code 0x01 appears when querying the currently set language (LANG_ID = 0x0000).

This is to be interpreted as correct processing of the command.

Page 291: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

291

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 260 (0x0104) – Change display settings 11099

>

Command request channel (fieldbus master >>> device) 11100

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved RS DS

4 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

DS Screen saver 1 bit 0 = no screen saver for local display 1 = screen saver for local display activated

RS return to splash screen 1 bit 0 = when the time has elapsed, device remains on current page 1 = when the time has elapsed, devices changes to the splash screen

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

>

Command response channel (device >>> fieldbus master) 11086

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

>

Possible command error codes 11101

There are no error messages for this command.

Page 292: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

292

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 261 (0x0105) – Set output control 16673

Using this command, the controller instance for the outputs of the AS-i slaves can be set. >

Command request channel (fieldbus master >>> device) 16683

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved OC

4 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

OC Output Control 1 byte 0x01 = GW, gateway 0x02 = MAN, manual 0x03 = PLC, device-internal PLC

>

Command response channel (device >>> fieldbus master) 16685

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

>

Possible command error codes 16687

Error Code [hex]

Error Meaning

0x00 no error

0x01 IO Invalid parameter value transmitted for OC. OR: Control of the outputs could not be set.

Error code only appears if command status = FAILED.

Page 293: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

293

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 262 (0x0106) – Set standard PLC operating mode 16674

Using this command, the operating mode of the device-internal standard PLC can be set. >

Command request channel (fieldbus master >>> device) 16689

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved PLC

4 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

PLC Operating mode of the device-internal PLC

1 bit 0x00 = stop PLC application and switch off PLC 0x01 = switch on PLC and start PLC application (boot application)

>

Command response channel (device >>> fieldbus master) 16690

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

>

Possible command error codes 16691

Error Code [hex]

Error Meaning

0x00 no error

0x01 PF PLC operating mode could not be set.

Error code only appears if command status = FAILED.

Page 294: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

294

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 265 (0x0109) – Set date/time 16677

Using this command, the system time (date and time) of the device can be set. >

Command request channel (fieldbus master >>> device) 16694

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 month day

4 year (byte 2, MSB) year (byte 1, LSB)

5 minutes hours

6 reserved seconds

7 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

day day 1 byte 0x01 = 1 0x02 = 2 ... 0x1F = 31

month month 1 byte 0x01 = January 0x02 = February ... 0x0C = December

Year Year 1 word Possible values: 1971 ... 2037

0x07B3 = 1971 0x07B4 = 1972 ... 0x07F5 = 2037

Example: 2014 = 0x07DE year (MSB) = 0x07, year (LSB) = 0xDE

hours hours 1 byte 0x00 = 0 0x01 = 1 ... 0x17 = 23

minutes minutes 1 byte 0x00 = 0 0x01 = 1 ... 0x3B = 59

seconds seconds 1 byte 0x00 = 0 0x01 = 1 ... 0x3B = 59

Page 295: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

295

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 16695

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

>

Possible command error codes 16696

Error Code [hex]

Error Meaning

0x00 no error

0x01 IDT Transferred values for date/time are invalid and could not be set. Error

0x02 NAE NTP is active, transmitted value for time could not be set.

Deactivate NTP to be able to set the time.

Error code appears if command status = FAILED

Page 296: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

296

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 266 (0x010A) – Set parameters of the NTP server 16707

Using this command, the IP parameters of the NTP server can be set. >

Command request channel (fieldbus master >>> device) 16705

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 NTP Offset reserved NTP

4 NTP server IP address (high byte, net address) NTP server IP address

5 NTP server IP address NTP server IP address (low byte, host address)

6 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

NTP Setting the NTP client 1 bit 0x0 = NTP client is inactive 0x1 = NTP client is active

NTP Offset NTP server provides the time in UTC. NTP Offset indicates the difference between UTC and local time.

1 byte 0x00 = system clock in local time 0x01 = UTC -12:00 0x02 = UTC -11:00 0x03 = UTC -10:00 0x04 = UTC -09:00 0x05 = UTC -08:00 0x06 = UTC -07:00 0x07 = UTC -06:00 0x08 =.UTC -05:00 0x09 = UTC -04:00 0x0A = UTC -03:30 0x0B = UTC -03:00 0x0C = UTC -02:00 0x0D = UTC -01:00 0x0E = UTC +00:00 0x0F = UTC +01:00 0x10 = UTC +02:00 0x11 = UTC +03:00 0x12 = UTC +03:30 0x13 = UTC +04:00 0x14 = UTC +04:30 0x15 = UTC +05:00 0x16 = UTC +05:30 0x17 = UTC +05:45 0x18 = UTC +06:00 0x19 = UTC +06:30 0x1A = UTC +07:00 0x1B = UTC +08:00 0x1C = UTC +09:00 0x1D = UTC +09:30 0x1E = UTC +10:00 0x1F = UTC +11:00 0x20 = UTC +12:00

Page 297: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

297

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

NTP server IP address

IP address (IP-V4) of the NTP server

2 words Per segment of an IP address: 0 ....255

0x00 = 000 0x01 = 001 ... 0x0FF = 255

Example: IP address: 192.168.150.5 192 = 0xC0 (high byte) 168 = 0xA8 150 = 0x96 005 = 0x05 (low byte)

The duration of the synchronisation process depends on the settings of the NTP server. This means that the synchronised system time is not immediately available after activation of the NTP client.

► Do not query the synchronised system time immediately after activation of the NTP client.

>

Command response channel (device >>> fieldbus master) 16706

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

>

Possible command error codes 16707

Error Code [hex]

Error Meaning

0x00 no error

0x01 IS Wrong parameters transmitted. NTP server settings were not transmitted.

Error code appears if command status = FAILED

Page 298: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

298

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 267 (0x010B) – Read date / time / NTP settings 16679

Using this command, the current values for time, date and NTP settings can be read. >

Command request channel (fieldbus master >>> device) 16712

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Page 299: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

299

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 16713

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 month day

6 year (byte 2, MSB) year (byte 1, LSB)

7 minutes hours

8 reserved seconds

9 NTP Offset reserved NTP

10 NTP server IP address (high byte, net address) NTP server IP address

11 NTP server IP address NTP server IP address (low byte, host address)

Legend:

- day - month - year - hours - minutes - seconds

→ Command 266 (0x010A) – Set parameters of the NTP server (→ page 296)

- NTP - NTP Offset - NTP server IP address

→ Command 266 (0x010A) – Set parameters of the NTP server (→ page 296)

>

Possible command error codes 16714

Error Code [hex]

Error Meaning

0x00 no error

Page 300: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

300

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 268 (0x010C) – Reboot system 16680

Using the command, the device can be restarted. >

Command request channel (fieldbus master >>> device) 7032

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 0x4F (= O) 0x42 (= B)

4 0x54 (= T) 0x4F (= O)

5 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

To prevent an unintended or unauthorised restart of the system by calling the command 0x010C, a signature must be transmitted in addition. The command execution is stopped when

a wrong signature is transmitted.

The signature is: BOOT

Page 301: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

301

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 7044

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

>

Possible command error codes 7050

Error Code [hex]

Error Meaning

0x01 Command error: Reboot could not be carried out.

Error code only appears if command status = FAILED.

Page 302: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

302

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 269 (0x010D) – Read fieldbus info 7052

The command reads information via the fieldbus.

The command can only be executed using the function block ACnnnn_SysCmd under CODESYS! (→ programming manual, section ACnnnn_SysCmd)

>

Command request channel (fieldbus master >>> device) 7064

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

>

Command response channel (device >>> fieldbus master) 8909

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 ... 23 → DS18 – Fieldbus information (→ page 281)

>

Possible command error codes 7030

Error Code [hex]

Error Meaning

0x00 no error

Page 303: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

303

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 272 (0x0110) – Display target visualisation 20593

This command enables switching between the menu page of the GUI and the target visualisation as well as enables/disables the use of the key combination [] + []. >

Command request channel (fieldbus master >>> device) 20594

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 TargetVisu

4 Hotkey

5...120 The area is completely ignored. It does not matter whether the data area exists or what data is contained.

Legend:

TargetVisu Content of the device display

1 Word 0x0000 = display GUI 0x0001 = display target visualisation

Hotkey Key combination for switching from target visualisation to the menu page of the GUI

1 Word 0x0000 = key combination enabled 0x0001 = key combination disabled

>

Command reply channel (device >>> fieldbus master) 20595

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

>

Possible command error codes 20596

Error Code [hex]

Error Meaning

0x00 no error

0x01 Target visualisation cannot be displayed because CODESYS PLC is not active

Error code appears if command status = FAILED

Page 304: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

304

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

AS-i master commands

Overview: AS-i master commands .......................................................................................................305 Error codes of the AS-i master commands ..........................................................................................307 Command 01 (0x0001) – Change parameters of an AS-i slave ..........................................................310 Command 03 (0x0003) – Project the currrent AS-i network ................................................................312 Command 04 (0x0004) – Change LPS ................................................................................................313 Command 05 (0x0005) – Change the operating mode of the AS-i master ..........................................314 Command 06 (0x0006) – Change AS-i slave address .........................................................................315 Command 07 (0x0007) - Set the auto address mode of the AS-i master ..........................................317 Command 09 (0x0009) – Change extended ID1 in the AS-i slave ......................................................318 Command 10 (0x000A) - Change PCD ................................................................................................320 Command 13 (0x000D) – AS-i master supply voltage, symmetry, earth fault .....................................323 Command 21 (0x0015) – Read ID string of an AS-i profile (S-7.4) ......................................................325 Command 26 (0x001A) – Read AS-i master info .................................................................................328 Command 28 (0x001C) – Deactivate slave reset when changing to the protected mode ...................329 Command 33 (0x0021) - Read diagnosis string of an AS-i slave (S-7.4) ............................................330 Command 34 (0x0022) - Read parameter string of an AS-i slave (S-7.4) ...........................................332 Command 35 (0x0022) - Write parameter string of an AS-i slave (S-7.4) ...........................................334 Command 36 (0x0024) – CTT2 Standard ............................................................................................336 Command 37 (0x0025) – CTT2 standard write ....................................................................................338 Command 38 (0x0026) – CTT2 Vendor Specific Read ........................................................................340 Command 39 (0x0027) – CTT2 Vendor Specific Write ........................................................................342 Command 64 (0x0040) – CTT2 device group read ..............................................................................344 Command 65 (0x0041) – CTT2 Device Group Write ...........................................................................346 Command 66 (0x0042) – CTT2 Vendor Specific Selective Read From Buffer ....................................348 Command 67 (0x0043) – CTT2 Vendor Specific Selective Write From Buffer ....................................350 Command 68 (0x0044) – CTT2 Vendor Specific Selective Read ........................................................352 Command 69 (0x0045) – CTT2 Vendor Specific Selective Write ........................................................354 Command 70 (0x0046) – CTT2 device group selective Rread ............................................................356 Command 71 (0x0047) – CTT2 Device Group Selective Write ...........................................................358 Command 73 (0x0049) – CTT2 Vendor Specific Exchange ................................................................360 Command 74 (0x004A) – CTT2 Device Group Exchange ...................................................................362 Command 75 (0x004B) – CTT2 Device Group Selective Read From Buffer .......................................364 Command 76 (0x004C) – CTT2 Device Group Selective Write From Buffer .......................................366 Command 80 (0x0050) – Adjust AS-i master settings .........................................................................368 Command 81 (0x0051) – Reset error counter......................................................................................369

8797

Page 305: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

305

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Overview: AS-i master commands 7250

Command [hex]

Command [dec]

Description Note

0001 1 write parameters to a connected AS-i slave

0003 3

adopt and save currently connected AS-i slaves in the configuration

This command causes a reset of the fieldbus connection. The device must be rebooted!

ConfDataInput Slave → Projected Configuration Data and LDS → LPS

0004 4 Change the list of the projected AS-i slaves (LPS)

0005 5 set the operating mode of the AS-i master

0006 6 readdress a connected AS-i slave

0007 7 set the auto addressing mode of the AS-i master

0009 9 change the extended ID code 1 in the connected AS-i slave

000A 10 change PCD

000D 13 AS-i master supply voltage, symmetry, earth fault

0015 21 read ID string of an AS-i slave with profile S-7.4 Slave profile S-7.4

0019 25 Set test mode

001A 26 read AS-i master info

001C 28 Deactivation of the slave reset when changing to the protected mode

0021 33 read diagnosis string of an AS-i slave with profile S-7.4 Slave profile S-7.4

0022 34 read parameter string of an AS-i slave with profile S-7.4 Slave profile S-7.4

0023 35 write parameter string of an AS-i slave with profile S-7.4 Slave profile S-7.4

0024 36 CTT2 standard read: Acyclic standard read call of an AS-i slave with CTT2 profile

CTT2 slave profile *)

0025 37 CTT2 standard write: Acyclic standard write call of an AS-i slave with CTT2 profile

CTT2 slave profile *)

0026 38 CTT2 vendor specific read: acyclic manufacturer-specific read call of an AS-i slave with CTT2 profile

CTT2 slave profile *)

0027 39 CTT2 vendor specific write: acyclic manufacturer-specific write call of an AS-i slave with CTT2 profile

CTT2 slave profile *)

0040 64 CTT2 device group read: Acyclic devicegroup read call of an AS-i slave with CTT2 profile

CTT2 slave profile *)

0041 65 CTT2 device group write: Acyclic devicegroup write call of an AS-i slave with CTT2 profile

CTT2 slave profile *)

0042 66 CTT2 vendor specific selective read from buffer: Selective standard read call of an AS-i slave with CTT2 profile

CTT2 slave profile *)

0043 67 CTT2 vendor specific selective write from buffer: Selective standard write call of an AS-i slave with CTT2 profile

CTT2 slave profile *)

0044 68 CTT2 vendor specific selective read: Selective manufacturer-specific read call of an AS-i slave with CTT2 profile

CTT2 slave profile *)

0045 69 CTT2 vendor specific selective write: Selective manufacturer-specific write call of an AS-i slave with CTT2 profile

CTT2 slave profile *)

Page 306: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

306

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Command [hex]

Command [dec]

Description Note

0046 70 CTT2 device group selective read: Selective devicegroup read call of an AS-i slave with CTT2 profile

CTT2 slave profile *)

0047 71 CTT2 device group selective write: Selective devicegroup write call of an AS-i slave with CTT2 profile

CTT2 slave profile *)

0049 73 CTT2 vendor specific exchange: Manufacturer-specific data exchange with an AS-i slave with CTTS profile

CTT2 slave profile *)

004A 74 CTT2 device group exchange: Devicegroup data exchange with an AS-i slave with CTTS profile

CTT2 slave profile *)

004B 75 CTT2 device group selective read from buffer: Manufacturer-specific write/read call of an AS-i slave with CTTS profile

CTT2 slave profile *)

004C 76 CTT2 device group selective write from buffer: Devicegroup write/read call of an AS-i slave with CTTS profile

CTT2 slave profile *)

0050 80 Set AS-i master parameters

0051 81 Reset error counter

Legend:

CTT → chapter Combined transaction – Use of analogue channels in the gateway depending on the slave profile (→ page 194) *) CTT2 profiles = S-7.5.5, S-7.A.5 or S-B.A.5

Page 307: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

307

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Error codes of the AS-i master commands

General error codes ..............................................................................................................................308 Standard CTT2 error codes ..................................................................................................................308 CTT2 error object .................................................................................................................................309

8836

Page 308: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

308

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

General error codes 5682

Revision: 2014-03-05

Error Code [hex]

Error Meaning

0x01 NOK no slave response OR: master is in the offline mode when requesting the command

0x02 SND no slave with the old address found

0x03 SD0 slave with address 0 connected

0x04 SD2 slave with the new address already exists

0x05 DE error when deleting the old address

0x06 error when reading the IO configuration

0x07 SE error when writing the new address or extended ID code 1

0x08 AT new address could only be saved temporarily

0x09 ET extended ID code 1 could only be saved temporarily

0x0A NA the slave is not in the LAS

0x0B ID parameter or address invalid

0x0C faulty S-7.4 protocol sequence

0x0D ST S-7.4 protocol aborted (timeout)

0x0E IA invalid AS-i slave address for the S-7.4 protocol (e.g. B slaves)

0x0F SSA AS-i slave has aborted the S-7.4 string

0x10 AS-i S-7.4 no longer connected (no longer in LAS)

0x11 STA another S-7.4 transfer to the addressed AS-i slave is already active

0x12 HSE the previous segmented S-7.4 transfer was not yet completed

0x13 IDL invalid S-7.4 data length

0x14 master is in the wrong operating mode *)

0x16 timeout during command processing

0x17 CMD_PRE start requirements for S-7.4 command not met: - wrong slave profile (is not S-7.4) or: - slave is not in LAS or: - master is not in the Protected mode

0x18 NM master is not in the protected mode

0x19 master is not in projection mode

0x20 command could not be processed within the specified time

0xE0...0xEF CTT2 error detected by AS-i slave; CTT2 error codes (→ page 308)

0xF0 invalid CTT2 command

0xF1 invalid CTT2 response

0xF2 S-7.5 data length longer than 30 bytes

>

Standard CTT2 error codes 8931

The "standard CTT2 error code" provides information about errors occurred during processing of a CTT2 command. It is transmitted in data byte 0 of the response channel of a CTT2 command. The following table shows the possible values:

Page 309: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

309

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Error code Description

0x00 No fault

0x01 Invalid index

0x02 Invalid length

0x03 Command not implemented

0x04 Used, the command could not be completed in the specified time

0x05 Command was not acknowledged

0x06 Invalid sub-index

0x07 Command 'Selective Read Request' is missing

>

CTT2 error object 18393

In addition to the standard CTT2 error code, the "CTT2 error object" provides further manufacturer-specific information about errors which occurred during processing of a CTT2 command. It is transmitted in the response channel of a CTT2 command in the data bytes 0...5. The CTT2 error object has the following structure:

Data byte Content

0 standard CTT2 error code (→ standard CTT2 error codes (→ page 308))

1...4 manufacturer-specific error information (→ data sheet of the AS-i slave)

Page 310: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

310

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 01 (0x0001) – Change parameters of an AS-i slave 8799

Requirement: The addressed AS-i master must be in the protected mode.

Command 05 (0x0005) – Change the operating mode of the AS-i master (→ page 314)

>

Command request channel (fieldbus master >>> device) 11103

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 reserved reserved New output parameter

5...120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

If the requested slave address (SLA) is not in the list of activated slaves (LAS), the new parameters are stored in the AS-i master despite error message (error code 0x0A). If an AS-i slave with this address is added to the AS-i network at a later point, the slave automatically adopts the saved parameters.

Page 311: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

311

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 11104

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 reserved reserved Input parameters

6 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

>

Possible command error codes 11105

Error Code [hex]

Error Meaning

0x00 no error

0x01 NOK no slave response OR: master is in the offline mode when requesting the command

0x0A NA the slave is not in the LAS

0x0B ID parameter or address invalid

0x0E IA invalid AS-i slave address for the S-7.4 protocol (e.g. B slaves)

0x18 NM master is not in the protected mode

Page 312: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

312

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 03 (0x0003) – Project the currrent AS-i network 8805

(= project all)

Requirement: The addressed AS-i master must be in the projection mode.

Command 05 (0x0005) – Change the operating mode of the AS-i master (→ page 314)

This command causes a reset of the fieldbus connection. The device must be rebooted!

>

Command request channel (fieldbus master >>> device) 11107

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legende:

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

>

Command response channel (device >>> fieldbus master) 11086

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

>

Possible command error codes 11109

Error Code [hex]

Error Meaning

0x00 no error

0x03 SD0 slave with address 0 connected

0x19 master is not in projection mode

Page 313: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

313

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 04 (0x0004) – Change LPS 8806

Requirement: The addressed AS-i master must be in the projection mode.

Command 05 (0x0005) – Change the operating mode of the AS-i master (→ page 314)

>

Command request channel (fieldbus master >>> device) 11111

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 15(A) 14(A) 13(A) 12(A) 11(A) 10(A) 9(A) 8(A) 7(A) 6(A) 5(A) 4(A) 3(A) 2(A) 1(A) --

4 31(A) 30(A) 29(A) 28(A) 27(A) 26(A) 25(A) 24(A) 23(A) 22(A) 21(A) 20(A) 19(A) 18(A) 17(A) 16(A)

5 15B 14B 13B 12B 11B 10B 9B 8B 7B 6B 5B 4B 3B 2B 1B --

6 31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B

7...120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

>

Command response channel (device >>> fieldbus master) 11086

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

>

Possible command error codes 11112

Error Code [hex]

Error Meaning

0x00 no error

0x19 master is not in projection mode

Page 314: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

314

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 05 (0x0005) – Change the operating mode of the AS-i master 8807

>

Command request channel (fieldbus master >>> device) 11114

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved MOD

4 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

MOD operating mode 1 byte 0x00 = set master to the normal mode (protected mode) 0x01 = set master to the projection mode

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

>

Command response channel (device >>> fieldbus master) 11086

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

>

Possible command error codes 11115

Error Code [hex]

Error Meaning

0x00 no error

0x03 SD0 slave with address 0 connected

Page 315: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

315

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 06 (0x0006) – Change AS-i slave address 8808

Requirement: The addressed AS-i master must be in the projection mode.

Command 05 (0x0005) – Change the operating mode of the AS-i master (→ page 314)

>

Command request channel (fieldbus master >>> device) 11117

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST old SLA

4 reserved reserved ST new SLA

5...120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 316: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

316

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 11086

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

>

Possible command error codes 11118

Error Code [hex]

Error Meaning

0x00 no error

0x01 NOK no slave response OR: master is in the offline mode when requesting the command

0x02 SND no slave with the old address found

0x03 SD0 slave with address 0 connected

0x04 SD2 slave with the new address already exists

0x05 DE error when deleting the old address

0x06 error when reading the extended ID code 1

0x07 SE error when writing the new address or extended ID code 1

0x08 AT new address could only be saved temporarily

0x09 ET extended ID code 1 could only be saved temporarily

0x18 NM master is not in the protected mode

Page 317: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

317

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 07 (0x0007) - Set the auto address mode of the AS-i master 8811

>

Command request channel (fieldbus master >>> device) 11120

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved AutoAd

4 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

AutoAd automatic addressing 1 byte 00 = deactivate automatic addressing 01 = activate automatic addressing

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

>

Command response channel (device >>> fieldbus master) 11086

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

>

Possible command error codes 11101

There are no error messages for this command.

Page 318: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

318

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 09 (0x0009) – Change extended ID1 in the AS-i slave 8812

>

Command request channel (fieldbus master >>> device) 11121

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 reserved new Extended ID-Code 1

5 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 319: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

319

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 11086

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

>

Possible command error codes 11121

Error Code [hex]

Error Meaning

0x00 no error

0x02 SND no slave with the old address found

0x03 SD0 slave with address 0 connected

0x05 DE error when deleting the old address

0x06 error when reading the extended ID code 1

0x07 SE error when writing the new address or extended ID code 1

0x09 ET extended ID code 1 could only be saved temporarily

0x0E IA invalid AS-i slave address 0 or 0B, or address 0 indicated twice

0x18 NM master is not in the protected mode

0x21 invalid ID code 1 (if bit 3 is set for A/B slave)

Page 320: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

320

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 10 (0x000A) - Change PCD 8814

>

Command request channel (fieldbus master >>> device) 11125

Offset Word no.

Bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

ID2-Code ID1-Code ID-Code IO-Code

1 UID

2 command number

3 reserved

4 Slave 1(A)

5 Slave 2(A)

6 Slave 3(A)

7 Slave 4(A)

8 Slave 5(A)

9 Slave 6(A)

10 Slave 7(A)

11 Slave 8(A)

12 Slave 9(A)

13 Slave 10(A)

14 Slave 11(A)

15 Slave 12(A)

16 Slave 13(A)

17 Slave 14(A)

18 Slave 15(A)

19 Slave 16(A)

20 Slave 17(A)

21 Slave 18(A)

22 Slave 19(A)

23 Slave 20(A)

24 Slave 21(A)

25 Slave 22(A)

26 Slave 23(A)

27 Slave 24(A)

28 Slave 25(A)

29 Slave 26(A)

30 Slave 27(A)

31 Slave 28(A)

32 Slave 29(A)

33 Slave 30(A)

Page 321: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

321

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Offset Word no.

Bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

ID2-Code ID1-Code ID-Code IO-Code

34 Slave 31(A)

35 reserved

36 Slave 1B

37 Slave 2B

38 Slave 3B

39 Slave 4B

40 Slave 5B

41 Slave 6B

42 Slave 7B

43 Slave 8B

44 Slave 9B

45 Slave 10B

46 Slave 11B

47 Slave 12B

48 Slave 13B

49 Slave 14B

50 Slave 15B

51 Slave 16B

52 Slave 17B

53 Slave 18B

54 Slave 19B

55 Slave 20B

56 Slave 21B

57 Slave 22B

58 Slave 23B

59 Slave 24B

60 Slave 25B

61 Slave 26B

62 Slave 27B

63 Slave 28B

64 Slave 29B

65 Slave 30B

66 Slave 31B

67...120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Page 322: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

322

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

Legend:

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

>

Command response channel (device >>> fieldbus master) 11086

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

>

Possible command error codes 11112

Error Code [hex]

Error Meaning

0x00 no error

0x19 master is not in projection mode

Page 323: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

323

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 13 (0x000D) – AS-i master supply voltage, symmetry, earth fault 8815

>

Command request channel (fieldbus master >>> device) 11107

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legende:

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 324: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

324

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 11128

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 reserved reserved PF1 PF2 SE EF PM PS

6 Voltage ASi+ to ASi- in [mV]

7 Voltage FE to ASi- in [mV]

8 Symmetry (-100...100) in [%]

9 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

EF earth fault 1 bit 0 = no earth fault is detected 1 = asymmetric supply voltage; classified as earth fault

PF1 powerfail 22.5 V 1 bit 0 = no AS-i Power Fail (classic APF)

1 = AS-i voltage < 22.5 V There is an AS-i power fail (classic APF)

PF2 powerfail 19 V 1 bit 0 = no AS-i Power Fail (24V APF)

1 = AS-i voltage < 19 V There is an AS-i power fail (24V APF)

PM powermodule 1 bit 0 = no data decoupling module is connected 1 = a data decoupling module is connected

PS powersource 1 bit 0 = the device is supplied from AUX 1 = the device is supplied from AS-i

SE status earth fault detection

1 bit 0 = no earth fault detection possible (e.g. no AS-i voltage) 1 = earth fault detection provides valid data

>

Possible command error codes 11101

There are no error messages for this command.

Page 325: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

325

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 21 (0x0015) – Read ID string of an AS-i profile (S-7.4) 8822

>

Command request channel (fieldbus master >>> device) 11130

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legende:

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 326: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

326

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 11131

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 Number of bytes received as from word no. 4 reserved ST reflected slave address

6 I/O 2D DT Start DT Count Mux field E type

7 number of parameter bytes to be read EDT Read reserved Diag reserved

8 EDT Write reserved Number of parameter bytes to be written

9 Device-specific information Manufacturer identification

10...m Device-specific information Device-specific information

(m+1)...120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

2D double data transfer 1 bit double data transfer (redundancy) possible

0 = simple data transfer 1 = double data transfer

number of parameter bytes to be read

1 byte number of bytes which can be read as parameter string

00 = no parameter string readable 01...DBhex = 01...219dec = number of bytes

number of parameter bytes to be written

1 byte number of bytes which can be written as parameter string

00 = no parameter string readable 01...DBhex = 01...219dec = number of bytes

Diag slave supports the 7.4 diagnosis string

1 bit 0 = diagnosis string is not supported 1 = diagnosis string is supported

DT-Count number of data triples 3 bits (information for the driver in the master)

DT-Start start triple 3 bits (information for the driver in the master)

E type slave function + data structure

5 bits characterises the slave as regards functionality and data structure

00 = reserved 01 = transmitted values are measured values 02 = transmitted values are 16 digital bit values 03 = normal operation in 4-bit mode (4I/4O) 04...1Fhex = 04...31dec = reserved

EDT read reserved 3 bits reserved for later profiles

EDT write reserved 3 bits reserved for later profiles

device-specific information

1 byte as an option more bytes for the manufacturer-specific device description

manufacturer identification

1 byte defined manufacturer number assigned by AS-International

I/O direction of data 1 bit direction of data for the devices with E type 3

0 = input 1 = output

Mux field number of multiplexed data words

3 bits 0…3 number = value in "Mux field" +1

Page 327: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

327

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

>

Possible command error codes 11132

Error Code [hex]

Error Meaning

0x00 no error

0x01 NOK no slave response OR: master is in the offline mode when requesting the command

0x0D ST S-7.4 protocol aborted (timeout)

0x0E IA invalid AS-i slave address for the S-7.4 protocol (e.g. B slaves)

0x10 AS-i S-7.4 slave deleted from LAS during current transmission

0x11 STA another S-7.4 transfer to the addressed AS-i slave is already active

0x17 CMD_PRE start requirements for S-7.4 command not met: - wrong slave profile (is not S-7.4) or: - slave is not in LAS or: - master is not in the Protected mode

Page 328: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

328

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 26 (0x001A) – Read AS-i master info 8827

>

Command request channel (fieldbus master >>> device) 11107

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legende:

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

>

Command response channel (device >>> fieldbus master) 11137

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 M12 reserved

6 Master firmware version, places before the decimal point

7 Master firmware version, decimal places

8 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

M12 number of AS-i masters 1 byte 0x00 = device has 1 AS-i master 0x01 = device has 2 AS-i masters

>

Possible command error codes 11101

There are no error messages for this command.

Page 329: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

329

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 28 (0x001C) – Deactivate slave reset when changing to the protected mode 8828

When changing from the projection mode to the protected mode, all slaves are normally briefly reset (reset or offline phase). This may lead to problems when the system is running. In such cases the "deactivation of the slave reset" prevents the short deactivation of the slave outputs during changing of the operating mode. >

Command request channel (fieldbus master >>> device) 11139

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved OLP

4 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

OLP offline phase = slave reset

1 byte 0x00 = offline phase when changing over to the protected mode 0x01 = no offline phase when changing over to the protected mode

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

>

Command response channel (device >>> fieldbus master) 11086

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

>

Possible command error codes 11101

There are no error messages for this command.

Page 330: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

330

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 33 (0x0021) - Read diagnosis string of an AS-i slave (S-7.4) 8829

>

Command request channel (fieldbus master >>> device) 11130

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legende:

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

>

Page 331: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

331

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 11141

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 Number of bytes received reserved ST reflected slave address

6...m Diagnosis byte n+1 Diagnosis byte n

(m+1)...120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

>

Possible command error codes 11132

Error Code [hex]

Error Meaning

0x00 no error

0x01 NOK no slave response OR: master is in the offline mode when requesting the command

0x0D ST S-7.4 protocol aborted (timeout)

0x0E IA invalid AS-i slave address for the S-7.4 protocol (e.g. B slaves)

0x10 AS-i S-7.4 slave deleted from LAS during current transmission

0x11 STA another S-7.4 transfer to the addressed AS-i slave is already active

0x17 CMD_PRE start requirements for S-7.4 command not met: - wrong slave profile (is not S-7.4) or: - slave is not in LAS or: - master is not in the Protected mode

Page 332: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

332

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 34 (0x0022) - Read parameter string of an AS-i slave (S-7.4) 8830

>

Command request channel (fieldbus master >>> device) 11130

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legende:

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

>

Page 333: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

333

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 11143

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 Number of bytes received reserved ST reflected slave address

6 ... m Parameter byte n+1 Parameter byte n

(m+1) ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

>

Possible command error codes 11132

Error Code [hex]

Error Meaning

0x00 no error

0x01 NOK no slave response OR: master is in the offline mode when requesting the command

0x0D ST S-7.4 protocol aborted (timeout)

0x0E IA invalid AS-i slave address for the S-7.4 protocol (e.g. B slaves)

0x10 AS-i S-7.4 slave deleted from LAS during current transmission

0x11 STA another S-7.4 transfer to the addressed AS-i slave is already active

0x17 CMD_PRE start requirements for S-7.4 command not met: - wrong slave profile (is not S-7.4) or: - slave is not in LAS or: - master is not in the Protected mode

Page 334: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

334

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 35 (0x0022) - Write parameter string of an AS-i slave (S-7.4) 8831

>

Command request channel (fieldbus master >>> device) 11145

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 Number of bytes to be transmitted reserved ST SLA

4...m parameter byte n+1 parameter byte n

(m+1)...120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

The number of the bytes to be sent must be divisible by 2 since the system always transmits only multiples of 2 bytes in the S7.4 protocol.

Page 335: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

335

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 11143

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 Number of bytes received reserved ST reflected slave address

6 ... m Parameter byte n+1 Parameter byte n

(m+1) ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

>

Possible command error codes 11146

Error Code [hex]

Error Meaning

0x00 no error

0x01 NOK Slave does not answer or AS-i master switches to offline mode during command execution OR: Timeout of slaves, switching of operating states with As-i parameters was not processed by the slave. Calling a not supported operating state can also cause this error message.

0x0C 7.4 sequence failed. AS-i slave generated wrong 7.4 sequence

0x0D ST S-7.4 protocol aborted (timeout)

0x0E IA invalid AS-i slave address for the S-7.4 protocol (e.g. B slaves)

0x0F SSA AS-i slave has aborted the S-7.4 string

0x10 AS-i S-7.4 slave deleted from LAS during current transmission

0x11 STA another S-7.4 transfer to the addressed AS-i slave is already active

0x12 HSE the previous segmented S-7.4 transfer was not yet completed

0x13 IDL invalid S-7.4 data length

0x14 invalid S-7.4 command

0x17 CMD_PRE start requirements for S-7.4 command not met: - wrong slave profile (is not S-7.4) or: - slave is not in LAS or: - master is not in the Protected mode

Page 336: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

336

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 36 (0x0024) – CTT2 Standard 8832

CTT2 profiles = S-7.5.5, S-7.A.5 or S-B.A.5

>

Command request channel (fieldbus master >>> device) 11148

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 DL IX

5 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

DL data length 1 byte number of bytes to be transferred

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

IX index 1 byte pointer to the page to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 337: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

337

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 18370

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 number of bytes received reserved ST reflected slave address

6 data byte 0 RC

7 ... m data byte n+1* data byte n

* ... If the number of bytes to be transmitted is odd, a zero byte (= 0x00) is transmitted in the data byte n+1.

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

RC CTT2 Response Code 1 byte 0x50 = No CTT2 error on command execution : The following data bytes contain the requested data.

0x90 = CTT2 error on command execution: - Data byte 0 contains → Standard CTT2 error codes (→ page 308). - The data in the following data bytes is irrelevant.

>

Possible command error codes 11150

Error code Error Description

0x00 No fault

0x0A NA Slave is not in the LAS

0x14 IC Invalid S-7.4 command

0x17 CMD_PRE Start requirements for S-7.4 command not met: - Wrong slave profile (is not S-7.4) or: - Slave is not in LAS or: - Master is not in the protected mode

0xE1 CTT2_ACYCL_RD_NOK Command execution error

0xE2 CTT2_ACYCL_CMD_NOK Invalid command

0xE3 CTT2_ACYCL_RESP_NOK Wrong response data or internal error

0xE4 CTT2_ACYCL_WR_LEN_NOK Wrong data length when writing

0xE5 CTT2_ACYCL_STATE_NOK Invalid state of the CTT2 state machine when executing the command

0xE6 CTT2_ACYCL_STATE_RESET Reset when executing the command

0xE7 CTT2_ACYCL_RD_LEN_NOK Wrong data length when reading

0xE8 CTT2_ACYCL_RD_WR_LEN_NOK Wrong data length when reading / writing

0xEF CTT2_ACYCL_CMD_TIMEOUT Timeout

Page 338: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

338

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 37 (0x0025) – CTT2 standard write 8848

>

Command request channel (fieldbus master >>> device) 11152

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 DL IX

5 ... m Data byte (n+1) Data byte n

(m+1) ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

DL data length 1 byte number of bytes to be transferred

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

IX index 1 byte pointer to the page to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 339: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

339

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 18375

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 Command error code

5 reserved reserved ST Reflected slave address

6 data byte 0 RC

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

RC CTT2 Response Code 1 byte 0x51 = No CTT2 error on command execution : The data in the following data bytes is irrelevant.

0x91 = CTT2 error on command execution: Data byte 0 contains → Standard CTT2 error codes (→ page 308).

>

Possible command error codes 11150

Error code Error Description

0x00 No fault

0x0A NA Slave is not in the LAS

0x14 IC Invalid S-7.4 command

0x17 CMD_PRE Start requirements for S-7.4 command not met: - Wrong slave profile (is not S-7.4) or: - Slave is not in LAS or: - Master is not in the protected mode

0xE1 CTT2_ACYCL_RD_NOK Command execution error

0xE2 CTT2_ACYCL_CMD_NOK Invalid command

0xE3 CTT2_ACYCL_RESP_NOK Wrong response data or internal error

0xE4 CTT2_ACYCL_WR_LEN_NOK Wrong data length when writing

0xE5 CTT2_ACYCL_STATE_NOK Invalid state of the CTT2 state machine when executing the command

0xE6 CTT2_ACYCL_STATE_RESET Reset when executing the command

0xE7 CTT2_ACYCL_RD_LEN_NOK Wrong data length when reading

0xE8 CTT2_ACYCL_RD_WR_LEN_NOK Wrong data length when reading / writing

0xEF CTT2_ACYCL_CMD_TIMEOUT Timeout

Page 340: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

340

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 38 (0x0026) – CTT2 Vendor Specific Read 8849

CTT2 profiles = S-7.5.5, S-7.A.5 or S-B.A.5

>

Command request channel (fieldbus master >>> device) 11148

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 DL IX

5 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

DL data length 1 byte number of bytes to be transferred

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

IX index 1 byte pointer to the page to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 341: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

341

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 18371

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 number of bytes received reserved ST reflected slave address

6 data byte 0 RC

7 ... m data byte n+1* data byte n

* ... If the number of bytes to be transmitted is odd, a zero byte (= 0x00) is transmitted in the data byte n+1.

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

RC CTT2 Response Code 1 byte 0x52 = No CTT2 error on command execution : The following data bytes contain the requested data.

0x92 = CTT2 error on command execution: The following data bytes 0...5 contain → CTT2 error object (→ page 309).

>

Possible command error codes 11150

Error code Error Description

0x00 No fault

0x0A NA Slave is not in the LAS

0x14 IC Invalid S-7.4 command

0x17 CMD_PRE Start requirements for S-7.4 command not met: - Wrong slave profile (is not S-7.4) or: - Slave is not in LAS or: - Master is not in the protected mode

0xE1 CTT2_ACYCL_RD_NOK Command execution error

0xE2 CTT2_ACYCL_CMD_NOK Invalid command

0xE3 CTT2_ACYCL_RESP_NOK Wrong response data or internal error

0xE4 CTT2_ACYCL_WR_LEN_NOK Wrong data length when writing

0xE5 CTT2_ACYCL_STATE_NOK Invalid state of the CTT2 state machine when executing the command

0xE6 CTT2_ACYCL_STATE_RESET Reset when executing the command

0xE7 CTT2_ACYCL_RD_LEN_NOK Wrong data length when reading

0xE8 CTT2_ACYCL_RD_WR_LEN_NOK Wrong data length when reading / writing

0xEF CTT2_ACYCL_CMD_TIMEOUT Timeout

Page 342: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

342

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 39 (0x0027) – CTT2 Vendor Specific Write 8850

CTT2 profiles = S-7.5.5, S-7.A.5 or S-B.A.5

>

Command request channel (fieldbus master >>> device) 11152

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 DL IX

5 ... m Data byte (n+1) Data byte n

(m+1) ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

DL data length 1 byte number of bytes to be transferred

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

IX index 1 byte pointer to the page to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 343: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

343

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 11153

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 reserved reserved ST reflected slave address

6 Data byte 0 RC

7 ... m Data byte n+1 Data byte n

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

RC CTT2 Response Code 1 byte 0x53 = No CTT2 error on command execution : The data in the following data bytes is irrelevant.

0x93 = CTT2 error on command execution: The following data bytes 0...5 contain → CTT2 error object (→ page 309).

>

Possible command error codes 11150

Error code Error Description

0x00 No fault

0x0A NA Slave is not in the LAS

0x14 IC Invalid S-7.4 command

0x17 CMD_PRE Start requirements for S-7.4 command not met: - Wrong slave profile (is not S-7.4) or: - Slave is not in LAS or: - Master is not in the protected mode

0xE1 CTT2_ACYCL_RD_NOK Command execution error

0xE2 CTT2_ACYCL_CMD_NOK Invalid command

0xE3 CTT2_ACYCL_RESP_NOK Wrong response data or internal error

0xE4 CTT2_ACYCL_WR_LEN_NOK Wrong data length when writing

0xE5 CTT2_ACYCL_STATE_NOK Invalid state of the CTT2 state machine when executing the command

0xE6 CTT2_ACYCL_STATE_RESET Reset when executing the command

0xE7 CTT2_ACYCL_RD_LEN_NOK Wrong data length when reading

0xE8 CTT2_ACYCL_RD_WR_LEN_NOK Wrong data length when reading / writing

0xEF CTT2_ACYCL_CMD_TIMEOUT Timeout

Page 344: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

344

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 64 (0x0040) – CTT2 device group read 8851

CTT2 profiles = S-7.5.5, S-7.A.5 or S-B.A.5

>

Command request channel (fieldbus master >>> device) 11148

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 DL IX

5 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

DL data length 1 byte number of bytes to be transferred

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

IX index 1 byte pointer to the page to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 345: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

345

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 18372

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 number of bytes received reserved ST reflected slave address

6 data byte 0 RC

7 ... m data byte n+1* data byte n

* ... If the number of bytes to be transmitted is odd, a zero byte (= 0x00) is transmitted in the data byte n+1.

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

RC CTT2 Response Code 1 byte 0x54 = No CTT2 error on command execution : The following data bytes contain the requested data.

0x94 = CTT2 error on command execution: The following data bytes 0...5 contain → CTT2 error object (→ page 309).

>

Possible command error codes 11150

Error code Error Description

0x00 No fault

0x0A NA Slave is not in the LAS

0x14 IC Invalid S-7.4 command

0x17 CMD_PRE Start requirements for S-7.4 command not met: - Wrong slave profile (is not S-7.4) or: - Slave is not in LAS or: - Master is not in the protected mode

0xE1 CTT2_ACYCL_RD_NOK Command execution error

0xE2 CTT2_ACYCL_CMD_NOK Invalid command

0xE3 CTT2_ACYCL_RESP_NOK Wrong response data or internal error

0xE4 CTT2_ACYCL_WR_LEN_NOK Wrong data length when writing

0xE5 CTT2_ACYCL_STATE_NOK Invalid state of the CTT2 state machine when executing the command

0xE6 CTT2_ACYCL_STATE_RESET Reset when executing the command

0xE7 CTT2_ACYCL_RD_LEN_NOK Wrong data length when reading

0xE8 CTT2_ACYCL_RD_WR_LEN_NOK Wrong data length when reading / writing

0xEF CTT2_ACYCL_CMD_TIMEOUT Timeout

Page 346: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

346

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 65 (0x0041) – CTT2 Device Group Write 8852

CTT2 profiles = S-7.5.5, S-7.A.5 or S-B.A.5

>

Command request channel (fieldbus master >>> device) 11152

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 DL IX

5 ... m Data byte (n+1) Data byte n

(m+1) ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

DL data length 1 byte number of bytes to be transferred

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

IX index 1 byte pointer to the page to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 347: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

347

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 18386

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 reserved reserved ST reflected slave address

6 data byte 0 RC

7 ... m data byte n+1 data byte n

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

RC CTT2 Response Code 1 byte 0x55 = No CTT2 error on command execution : The data in the following data bytes is irrelevant.

0x95 = CTT2 error on command execution: The following data bytes 0...5 contain → CTT2 error object (→ page 309).

>

Possible command error codes 11150

Error code Error Description

0x00 No fault

0x0A NA Slave is not in the LAS

0x14 IC Invalid S-7.4 command

0x17 CMD_PRE Start requirements for S-7.4 command not met: - Wrong slave profile (is not S-7.4) or: - Slave is not in LAS or: - Master is not in the protected mode

0xE1 CTT2_ACYCL_RD_NOK Command execution error

0xE2 CTT2_ACYCL_CMD_NOK Invalid command

0xE3 CTT2_ACYCL_RESP_NOK Wrong response data or internal error

0xE4 CTT2_ACYCL_WR_LEN_NOK Wrong data length when writing

0xE5 CTT2_ACYCL_STATE_NOK Invalid state of the CTT2 state machine when executing the command

0xE6 CTT2_ACYCL_STATE_RESET Reset when executing the command

0xE7 CTT2_ACYCL_RD_LEN_NOK Wrong data length when reading

0xE8 CTT2_ACYCL_RD_WR_LEN_NOK Wrong data length when reading / writing

0xEF CTT2_ACYCL_CMD_TIMEOUT Timeout

Page 348: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

348

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 66 (0x0042) – CTT2 Vendor Specific Selective Read From Buffer 8853

CTT2 profiles = S-7.5.5, S-7.A.5 or S-B.A.5

>

Command request channel (fieldbus master >>> device) 11159

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 SIX IX

5 ... m reserved DL

(m+1) ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

DL data length 1 byte number of bytes to be transferred

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

IX index 1 byte pointer to the page to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

SIX sub-index 1 byte pointer on element on this page ( data sheet of the slave)

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 349: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

349

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 18387

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 number of bytes received reserved ST reflected slave address

6 data byte 0 RC

7 ... m data byte n+1 data byte n

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

RC CTT2 Response Code 1 byte 0x58 = No CTT2 error on command execution : The following data bytes contain the requested data.

0x98 = CTT2 error on command execution: The following data bytes 0...5 contain → CTT2 error object (→ page 309).

>

Possible command error codes 11150

Error code Error Description

0x00 No fault

0x0A NA Slave is not in the LAS

0x14 IC Invalid S-7.4 command

0x17 CMD_PRE Start requirements for S-7.4 command not met: - Wrong slave profile (is not S-7.4) or: - Slave is not in LAS or: - Master is not in the protected mode

0xE1 CTT2_ACYCL_RD_NOK Command execution error

0xE2 CTT2_ACYCL_CMD_NOK Invalid command

0xE3 CTT2_ACYCL_RESP_NOK Wrong response data or internal error

0xE4 CTT2_ACYCL_WR_LEN_NOK Wrong data length when writing

0xE5 CTT2_ACYCL_STATE_NOK Invalid state of the CTT2 state machine when executing the command

0xE6 CTT2_ACYCL_STATE_RESET Reset when executing the command

0xE7 CTT2_ACYCL_RD_LEN_NOK Wrong data length when reading

0xE8 CTT2_ACYCL_RD_WR_LEN_NOK Wrong data length when reading / writing

0xEF CTT2_ACYCL_CMD_TIMEOUT Timeout

Page 350: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

350

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 67 (0x0043) – CTT2 Vendor Specific Selective Write From Buffer 8855

CTT2 profiles = S-7.5.5, S-7.A.5 or S-B.A.5

>

Command request channel (fieldbus master >>> device) 11162

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 SIX IX

5 Data byte 0 DL

6 ... m Data byte (n+1) Data byte n

(m+1) ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legende:

DL data length 1 byte number of bytes to be transferred

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

IX index 1 byte pointer to the page to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

SIX sub-index 1 byte pointer on element on this page ( data sheet of the slave)

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 351: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

351

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 18388

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 number of bytes received reserved ST reflected slave address

6 data byte 0 RC

7 ... m data byte n+1 data byte n

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

RC CTT2 Response Code 1 byte 0x59 = No CTT2 error on command execution : Data byte 0 contains the number of bytes to be read (block length); Valid values: 0x00 ... 0xFF (→ data sheet of the AS-i slave)

0x99 = CTT2 error on command execution: The following data bytes 0...5 contain → CTT2 error object (→ page 309).

>

Possible command error codes 11150

Error code Error Description

0x00 No fault

0x0A NA Slave is not in the LAS

0x14 IC Invalid S-7.4 command

0x17 CMD_PRE Start requirements for S-7.4 command not met: - Wrong slave profile (is not S-7.4) or: - Slave is not in LAS or: - Master is not in the protected mode

0xE1 CTT2_ACYCL_RD_NOK Command execution error

0xE2 CTT2_ACYCL_CMD_NOK Invalid command

0xE3 CTT2_ACYCL_RESP_NOK Wrong response data or internal error

0xE4 CTT2_ACYCL_WR_LEN_NOK Wrong data length when writing

0xE5 CTT2_ACYCL_STATE_NOK Invalid state of the CTT2 state machine when executing the command

0xE6 CTT2_ACYCL_STATE_RESET Reset when executing the command

0xE7 CTT2_ACYCL_RD_LEN_NOK Wrong data length when reading

0xE8 CTT2_ACYCL_RD_WR_LEN_NOK Wrong data length when reading / writing

0xEF CTT2_ACYCL_CMD_TIMEOUT Timeout

Page 352: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

352

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 68 (0x0044) – CTT2 Vendor Specific Selective Read 8857

CTT2 profiles = S-7.5.5, S-7.A.5 or S-B.A.5

>

Command request channel (fieldbus master >>> device) 11159

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 SIX IX

5 ... m reserved DL

(m+1) ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

DL data length 1 byte number of bytes to be transferred

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

IX index 1 byte pointer to the page to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

SIX sub-index 1 byte pointer on element on this page ( data sheet of the slave)

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 353: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

353

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 18387

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 number of bytes received reserved ST reflected slave address

6 data byte 0 RC

7 ... m data byte n+1 data byte n

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

RC CTT2 Response Code 1 byte 0x58 = No CTT2 error on command execution : The following data bytes contain the requested data.

0x98 = CTT2 error on command execution: The following data bytes 0...5 contain → CTT2 error object (→ page 309).

>

Possible command error codes 11150

Error code Error Description

0x00 No fault

0x0A NA Slave is not in the LAS

0x14 IC Invalid S-7.4 command

0x17 CMD_PRE Start requirements for S-7.4 command not met: - Wrong slave profile (is not S-7.4) or: - Slave is not in LAS or: - Master is not in the protected mode

0xE1 CTT2_ACYCL_RD_NOK Command execution error

0xE2 CTT2_ACYCL_CMD_NOK Invalid command

0xE3 CTT2_ACYCL_RESP_NOK Wrong response data or internal error

0xE4 CTT2_ACYCL_WR_LEN_NOK Wrong data length when writing

0xE5 CTT2_ACYCL_STATE_NOK Invalid state of the CTT2 state machine when executing the command

0xE6 CTT2_ACYCL_STATE_RESET Reset when executing the command

0xE7 CTT2_ACYCL_RD_LEN_NOK Wrong data length when reading

0xE8 CTT2_ACYCL_RD_WR_LEN_NOK Wrong data length when reading / writing

0xEF CTT2_ACYCL_CMD_TIMEOUT Timeout

Page 354: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

354

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 69 (0x0045) – CTT2 Vendor Specific Selective Write 8858

CTT2 profiles = S-7.5.5, S-7.A.5 or S-B.A.5

>

Command request channel (fieldbus master >>> device) 11162

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 SIX IX

5 Data byte 0 DL

6 ... m Data byte (n+1) Data byte n

(m+1) ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legende:

DL data length 1 byte number of bytes to be transferred

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

IX index 1 byte pointer to the page to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

SIX sub-index 1 byte pointer on element on this page ( data sheet of the slave)

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 355: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

355

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 18388

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 number of bytes received reserved ST reflected slave address

6 data byte 0 RC

7 ... m data byte n+1 data byte n

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

RC CTT2 Response Code 1 byte 0x59 = No CTT2 error on command execution : Data byte 0 contains the number of bytes to be read (block length); Valid values: 0x00 ... 0xFF (→ data sheet of the AS-i slave)

0x99 = CTT2 error on command execution: The following data bytes 0...5 contain → CTT2 error object (→ page 309).

>

Possible command error codes 11150

Error code Error Description

0x00 No fault

0x0A NA Slave is not in the LAS

0x14 IC Invalid S-7.4 command

0x17 CMD_PRE Start requirements for S-7.4 command not met: - Wrong slave profile (is not S-7.4) or: - Slave is not in LAS or: - Master is not in the protected mode

0xE1 CTT2_ACYCL_RD_NOK Command execution error

0xE2 CTT2_ACYCL_CMD_NOK Invalid command

0xE3 CTT2_ACYCL_RESP_NOK Wrong response data or internal error

0xE4 CTT2_ACYCL_WR_LEN_NOK Wrong data length when writing

0xE5 CTT2_ACYCL_STATE_NOK Invalid state of the CTT2 state machine when executing the command

0xE6 CTT2_ACYCL_STATE_RESET Reset when executing the command

0xE7 CTT2_ACYCL_RD_LEN_NOK Wrong data length when reading

0xE8 CTT2_ACYCL_RD_WR_LEN_NOK Wrong data length when reading / writing

0xEF CTT2_ACYCL_CMD_TIMEOUT Timeout

Page 356: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

356

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 70 (0x0046) – CTT2 device group selective Rread 8857

CTT2 profiles = S-7.5.5, S-7.A.5 or S-B.A.5

>

Command request channel (fieldbus master >>> device) 11159

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 SIX IX

5 ... m reserved DL

(m+1) ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

DL data length 1 byte number of bytes to be transferred

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

IX index 1 byte pointer to the page to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

SIX sub-index 1 byte pointer on element on this page ( data sheet of the slave)

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 357: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

357

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 18392

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 number of bytes received reserved ST reflected slave address

6 data byte 0 RC

7 ... m data byte n+1 data byte n

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

RC CTT2 Response Code 1 byte 0x5A = No CTT2 error on command execution : The following data bytes contain the requested data.

0x9A = CTT2 error on command execution: The following data bytes 0...5 contain → CTT2 error object (→ page 309).

>

Possible command error codes 11150

Error code Error Description

0x00 No fault

0x0A NA Slave is not in the LAS

0x14 IC Invalid S-7.4 command

0x17 CMD_PRE Start requirements for S-7.4 command not met: - Wrong slave profile (is not S-7.4) or: - Slave is not in LAS or: - Master is not in the protected mode

0xE1 CTT2_ACYCL_RD_NOK Command execution error

0xE2 CTT2_ACYCL_CMD_NOK Invalid command

0xE3 CTT2_ACYCL_RESP_NOK Wrong response data or internal error

0xE4 CTT2_ACYCL_WR_LEN_NOK Wrong data length when writing

0xE5 CTT2_ACYCL_STATE_NOK Invalid state of the CTT2 state machine when executing the command

0xE6 CTT2_ACYCL_STATE_RESET Reset when executing the command

0xE7 CTT2_ACYCL_RD_LEN_NOK Wrong data length when reading

0xE8 CTT2_ACYCL_RD_WR_LEN_NOK Wrong data length when reading / writing

0xEF CTT2_ACYCL_CMD_TIMEOUT Timeout

Page 358: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

358

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 71 (0x0047) – CTT2 Device Group Selective Write 8860

CTT2 profiles = S-7.5.5, S-7.A.5 or S-B.A.5

>

Command request channel (fieldbus master >>> device) 11162

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 SIX IX

5 Data byte 0 DL

6 ... m Data byte (n+1) Data byte n

(m+1) ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legende:

DL data length 1 byte number of bytes to be transferred

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

IX index 1 byte pointer to the page to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

SIX sub-index 1 byte pointer on element on this page ( data sheet of the slave)

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 359: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

359

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 18391

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 number of bytes received reserved ST reflected slave address

6 data byte 0 RC

7 ... m data byte n+1 data byte n

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

RC CTT2 Response Code 1 byte 0x5B = No CTT2 error on command execution : Data byte 0 contains the block length (= number of bytes to be read); Valid values: 0x00 ... 0xFF (→ data sheet of the AS-i slave)

0x9B = CTT2 error on command execution: The following data bytes 0...5 contain → CTT2 error object (→ page 309).

>

Possible command error codes 11150

Error code Error Description

0x00 No fault

0x0A NA Slave is not in the LAS

0x14 IC Invalid S-7.4 command

0x17 CMD_PRE Start requirements for S-7.4 command not met: - Wrong slave profile (is not S-7.4) or: - Slave is not in LAS or: - Master is not in the protected mode

0xE1 CTT2_ACYCL_RD_NOK Command execution error

0xE2 CTT2_ACYCL_CMD_NOK Invalid command

0xE3 CTT2_ACYCL_RESP_NOK Wrong response data or internal error

0xE4 CTT2_ACYCL_WR_LEN_NOK Wrong data length when writing

0xE5 CTT2_ACYCL_STATE_NOK Invalid state of the CTT2 state machine when executing the command

0xE6 CTT2_ACYCL_STATE_RESET Reset when executing the command

0xE7 CTT2_ACYCL_RD_LEN_NOK Wrong data length when reading

0xE8 CTT2_ACYCL_RD_WR_LEN_NOK Wrong data length when reading / writing

0xEF CTT2_ACYCL_CMD_TIMEOUT Timeout

Page 360: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

360

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 73 (0x0049) – CTT2 Vendor Specific Exchange 8863

CTT2 profiles = S-7.5.5, S-7.A.5 or S-B.A.5

>

Command request channel (fieldbus master >>> device) 11168

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 RL IX

5 Data byte 0 WL

6 ... m Data byte (n+1) Data byte n

(m+1) ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legende:

IX index 1 byte pointer to the page to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

RL read length 1 byte number of bytes to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

WL write length 1 byte number of bytes to be written

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

Page 361: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

361

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 18389

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 number of bytes received reserved ST reflected slave address

6 data byte 0 RC

7 ... m data byte n+1* data byte n

* ... If the number of bytes to be transmitted is odd, a zero byte (= 0x00) is transmitted in the data byte n+1.

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

RC CTT2 Response Code 1 byte 0x5D = No CTT2 error on command execution The following data bytes contain the requested data.

0x9D = CTT2 error on command execution The following data bytes 0...5 contain → CTT2 error object (→ page 309).

>

Possible command error codes 11150

Error code Error Description

0x00 No fault

0x0A NA Slave is not in the LAS

0x14 IC Invalid S-7.4 command

0x17 CMD_PRE Start requirements for S-7.4 command not met: - Wrong slave profile (is not S-7.4) or: - Slave is not in LAS or: - Master is not in the protected mode

0xE1 CTT2_ACYCL_RD_NOK Command execution error

0xE2 CTT2_ACYCL_CMD_NOK Invalid command

0xE3 CTT2_ACYCL_RESP_NOK Wrong response data or internal error

0xE4 CTT2_ACYCL_WR_LEN_NOK Wrong data length when writing

0xE5 CTT2_ACYCL_STATE_NOK Invalid state of the CTT2 state machine when executing the command

0xE6 CTT2_ACYCL_STATE_RESET Reset when executing the command

0xE7 CTT2_ACYCL_RD_LEN_NOK Wrong data length when reading

0xE8 CTT2_ACYCL_RD_WR_LEN_NOK Wrong data length when reading / writing

0xEF CTT2_ACYCL_CMD_TIMEOUT Timeout

Page 362: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

362

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 74 (0x004A) – CTT2 Device Group Exchange 8866

CTT2 profiles = S-7.5.5, S-7.A.5 or S-B.A.5

>

Command request channel (fieldbus master >>> device) 11168

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 RL IX

5 Data byte 0 WL

6 ... m Data byte (n+1) Data byte n

(m+1) ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legende:

IX index 1 byte pointer to the page to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

RL read length 1 byte number of bytes to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

WL write length 1 byte number of bytes to be written

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

Page 363: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

363

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 18390

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 number of bytes received reserved ST reflected slave address

6 data byte 0 RC

7 ... m data byte n+1* data byte n

* ... If the number of bytes to be transmitted is odd, a zero byte (= 0x00) is transmitted in the data byte n+1.

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

RC CTT2 Response Code 1 byte 0x5E = No CTT2 error on command execution : The following data bytes contain the requested data.

0x9E = CTT2 error on command execution: The following data bytes 0...5 contain → CTT2 error object (→ page 309).

>

Possible command error codes 11150

Error code Error Description

0x00 No fault

0x0A NA Slave is not in the LAS

0x14 IC Invalid S-7.4 command

0x17 CMD_PRE Start requirements for S-7.4 command not met: - Wrong slave profile (is not S-7.4) or: - Slave is not in LAS or: - Master is not in the protected mode

0xE1 CTT2_ACYCL_RD_NOK Command execution error

0xE2 CTT2_ACYCL_CMD_NOK Invalid command

0xE3 CTT2_ACYCL_RESP_NOK Wrong response data or internal error

0xE4 CTT2_ACYCL_WR_LEN_NOK Wrong data length when writing

0xE5 CTT2_ACYCL_STATE_NOK Invalid state of the CTT2 state machine when executing the command

0xE6 CTT2_ACYCL_STATE_RESET Reset when executing the command

0xE7 CTT2_ACYCL_RD_LEN_NOK Wrong data length when reading

0xE8 CTT2_ACYCL_RD_WR_LEN_NOK Wrong data length when reading / writing

0xEF CTT2_ACYCL_CMD_TIMEOUT Timeout

Page 364: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

364

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 75 (0x004B) – CTT2 Device Group Selective Read From Buffer 8861

CTT2 profiles = S-7.5.5, S-7.A.5 or S-B.A.5

>

Command request channel (fieldbus master >>> device) 11159

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 SIX IX

5 ... m reserved DL

(m+1) ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

DL data length 1 byte number of bytes to be transferred

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

IX index 1 byte pointer to the page to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

SIX sub-index 1 byte pointer on element on this page ( data sheet of the slave)

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 365: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

365

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 18392

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 number of bytes received reserved ST reflected slave address

6 data byte 0 RC

7 ... m data byte n+1 data byte n

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

RC CTT2 Response Code 1 byte 0x5A = No CTT2 error on command execution : The following data bytes contain the requested data.

0x9A = CTT2 error on command execution: The following data bytes 0...5 contain → CTT2 error object (→ page 309).

>

Possible command error codes 11150

Error code Error Description

0x00 No fault

0x0A NA Slave is not in the LAS

0x14 IC Invalid S-7.4 command

0x17 CMD_PRE Start requirements for S-7.4 command not met: - Wrong slave profile (is not S-7.4) or: - Slave is not in LAS or: - Master is not in the protected mode

0xE1 CTT2_ACYCL_RD_NOK Command execution error

0xE2 CTT2_ACYCL_CMD_NOK Invalid command

0xE3 CTT2_ACYCL_RESP_NOK Wrong response data or internal error

0xE4 CTT2_ACYCL_WR_LEN_NOK Wrong data length when writing

0xE5 CTT2_ACYCL_STATE_NOK Invalid state of the CTT2 state machine when executing the command

0xE6 CTT2_ACYCL_STATE_RESET Reset when executing the command

0xE7 CTT2_ACYCL_RD_LEN_NOK Wrong data length when reading

0xE8 CTT2_ACYCL_RD_WR_LEN_NOK Wrong data length when reading / writing

0xEF CTT2_ACYCL_CMD_TIMEOUT Timeout

Page 366: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

366

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 76 (0x004C) – CTT2 Device Group Selective Write From Buffer 8862

CTT2 profiles = S-7.5.5, S-7.A.5 or S-B.A.5

>

Command request channel (fieldbus master >>> device) 11162

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 reserved reserved ST SLA

4 SIX IX

5 Data byte 0 DL

6 ... m Data byte (n+1) Data byte n

(m+1) ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legende:

DL data length 1 byte number of bytes to be transferred

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

IX index 1 byte pointer to the page to be read

permitted values: 0x00…0xFF = 0…255 ( data sheet of the slave)

SIX sub-index 1 byte pointer on element on this page ( data sheet of the slave)

SLA slave address 5 bits 0x00…0x1F = 0…31

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

UID user ID 1 word 0x0000…0xFFFF = 0…65535 The user ID ensures clear identification of the commmand response data of the command request data sent before. The user can assign any user ID in the command request. The AS-i master reflects the user ID from the command request into the corresponding command response.

Page 367: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

367

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command response channel (device >>> fieldbus master) 18391

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

5 number of bytes received reserved ST reflected slave address

6 data byte 0 RC

7 ... m data byte n+1 data byte n

Legend:

ST slave type 1 bit 0 = single slave or A slave 1 = B slave (= addition of 0x20 or 32 to the slave address)

RC CTT2 Response Code 1 byte 0x5B = No CTT2 error on command execution : Data byte 0 contains the block length (= number of bytes to be read); Valid values: 0x00 ... 0xFF (→ data sheet of the AS-i slave)

0x9B = CTT2 error on command execution: The following data bytes 0...5 contain → CTT2 error object (→ page 309).

>

Possible command error codes 11150

Error code Error Description

0x00 No fault

0x0A NA Slave is not in the LAS

0x14 IC Invalid S-7.4 command

0x17 CMD_PRE Start requirements for S-7.4 command not met: - Wrong slave profile (is not S-7.4) or: - Slave is not in LAS or: - Master is not in the protected mode

0xE1 CTT2_ACYCL_RD_NOK Command execution error

0xE2 CTT2_ACYCL_CMD_NOK Invalid command

0xE3 CTT2_ACYCL_RESP_NOK Wrong response data or internal error

0xE4 CTT2_ACYCL_WR_LEN_NOK Wrong data length when writing

0xE5 CTT2_ACYCL_STATE_NOK Invalid state of the CTT2 state machine when executing the command

0xE6 CTT2_ACYCL_STATE_RESET Reset when executing the command

0xE7 CTT2_ACYCL_RD_LEN_NOK Wrong data length when reading

0xE8 CTT2_ACYCL_RD_WR_LEN_NOK Wrong data length when reading / writing

0xEF CTT2_ACYCL_CMD_TIMEOUT Timeout

Page 368: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

368

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 80 (0x0050) – Adjust AS-i master settings 16772

>

Command request channel (fieldbus master >>> device) 16774

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 Setting reserved MOD

4 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

Legend:

Setting Selection of the diagnostic function

0x01 = ground-fault detection (EE) 0x02 = double address recognition (DAE)

MOD Activate/deactivate the selected diagnostic function in the settings

0 = deactivate function 1 = activate function

>

Command response channel (device >>> fieldbus master) 16775

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

>

Possible command error codes 16776

Error Code [hex]

Error Meaning

0x00 no error

0x01 IP Wrong parameter assigned. Setting was not adopted.

Page 369: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

369

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Command 81 (0x0051) – Reset error counter 16773

Command sets the following counters to 0:

Telegram errors

All slave telegram errors

Configuration errors

Voltage drops < 22.5 V

Voltage drops < 19.0 V

Earth faults

Error distribution telegram errors >

Command request channel (fieldbus master >>> device) 16778

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 UID

2 command number

3 ... 120 The area is completely ignored.

It does not matter whether the data area exists or what data is contained.

>

Command response channel (device >>> fieldbus master) 16779

Offset Word no.

bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 reflected user ID

2 reflected command number

3 reserved Command status (→ page 284)

4 command error code

>

Possible command error codes 11101

There are no error messages for this command.

Page 370: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

370

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Programmers' notes: call up acyclic services 11208

EtherNet/IP controllers use the Message (MSG) command to send data/commands asynchronously to

another network participant and receive its response.

For detailed information about the Message (MSG) command: → operating instructions of

the EtherNet/IP controller used!

Page 371: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

371

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

9.6.6 Configuration mode 12945

To properly set the AC422S for permanent operation in the EtherNet/IP network, type and scope of the data to be transmitted as well as the parameters of the EtherNet/IP interface need to be defined. The following configuration modes are available:

Configuration mode: Top-down (→ page 372)

Configuration mode: Independent (→ page 377)

Page 372: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

372

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Configuration mode: Top-down 12948

In configuration mode 'Top-down', the device-specific parameters and the paramaters of the fieldbus slots are set in the projecting software of the EtherNet/IP controller. The created configuration is then transferred to AC422S (download).

Example: Configure AC422S in top-down mode and integrate in a RSLogix-5000 project >

1 Preparations

► Connect AC422S to the → I/O scanner

► Configure the IP settings of the configuration interface (X3) in line with the network requirements (→ Notes on IP settings (→ page 121)).

► Enabled the top-down configuration mode (→ Set the configuration mode (→ page 130)).

► Download and unpack the ESD file (→ Download the device and I/O description (→ page 127)).

► Import the downloaded EDS file in RSLogix 5000 (→ operating instructions RSLogix 5000). >

2 Open/Create a EtherNet/IP project

► Start RSLogix 5000.

► Open an existing EtherNet/IP project. OR Create a new EtherNet/IP project with the EtherNet/IP controller and I/O scanner.

>

3 Add AC422S to the project

► In the project structure: Right-click on [I/O Configuration] > [Name_of_I/O_scanner] > [Ethernet]

> The context menu appears.

► Create a new device with [New Module].

> The dialogue box [Select Module Type] appears.

► Select one of the following options:

Option 1: configure the device using the EDS file

► In the [Catalog] tab, select AC422S and confirm with [Create].

> The [New Module] window appears.

► Set the following parameters:

Parameter Meaning Possible values

Name short description of device

name appears in the tree structure of the RSLogix-5000 project

e.g. _AC1421

Description detailed description of device (optional)

max. 128 characters

e.g. I/O adapter

IP address IP address of the device's EtherNet/IP interface e.g. 192.168.10.10

► In the group [Module Definition], press [Change ...].

Page 373: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

373

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

> The [Module Definition] window appears.

► Set the parameters as shown:

► Press [OK] to confirm the input and to close the window.

> AC422S appears in the tree structure of the project.

► Continue with → step 4

Option 2: configure the device without EDS file

► Select [Catalog]: I/O adapter ETHERNET MODULE (Generic Ethernet Module) and confirm with [Create].

Page 374: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

374

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

> The [New Module] window appears.

► Set the parameters as shown:

► Press [OK] to confirm the input and to close the window.

> AC422S appears in the tree structure of the project.

>

4 Set the fieldbus parameters and the module configuration

► In the tree structure: double-click on [Controller ETIP_Controller] > [Controller Tags]

> The detailed view of the controller tags appears.

Page 375: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

375

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

► Click on [_AC422S:C]

> The detailed view shows a table with the current values of the configuration assembly instance (device-specific parameters, module configuration)

► For each row (= parameter): enter the desired parameter value in the [Value] column (→ Parameter setting via the configuration assembly object (→ page 203))

► Save the project. >

5 Transfer the set configuration to the controller (download)

► Set the communication path to the device (→ operating instructions RSLogix 5000).

► Transfer the project to the EtherNet/IP controller and start it.

> AC422S: the start screen shows the status of the EtherNet/IP connection:

EtherNet/IP active >

6 Optional: import the description of the inputs and outputs into the project

► Download the I/O description file (→ Download the device and I/O description (→ page 127)).

► In RSLogix 5000: Select [Tools] > [Import] > [Tag and Logic Comments ...] to start the wizard for importing the I/O description.

> The [Import] dialogue box appears.

Page 376: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

376

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

► Select the downloaded file (*.csv) and click [Import] to load it.

► In the tree structure: double-click on [Controller Tags]

> The detailed view of the controller tags appears.

> [_AC422S:I] and [_AC422S:O] show descriptions of the inputs and outputs.

Page 377: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

377

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

>

Configuration mode: Independent 12949

In configuration mode 'Independent', the device-specific parameters are set via the local display on the AC422S (→ Set the configuration mode (→ page 130), → Set the EtherNet/IP module configuration (→ page 133)). The assembly configuration defined in the projecting software is not evaluated.

Example: Configure AC422S in Independent mode and integrate in a RSLogix 5000 project

>

1 Preparations

► Connect AC422S to the → I/O scanner.

► Configure the IP settings of the configuration interface (X3) in line with the network requirements (→ Notes on IP settings (→ page 121)).

► Enable the "independent" configuration mode (→ Set the configuration mode (→ page 130)).

► Download and unpack the ESD file (→ Download the device and I/O description (→ page 127)).

► Import the downloaded EDS file in RSLogix 5000 (→ operating instructions RSLogix 5000). >

2 Set the device-specific parameters and the module configuration

► Set the fieldbus parameters → Set the device-specific parameters (→ page 131)

► Set the module configuration → Set the EtherNet/IP module configuration (→ page 133)

>

3 Open/Create a EtherNet/IP project

► Start RSLogix 5000.

► Open an existing EtherNet/IP project. OR Create a new EtherNet/IP project with the EtherNet/IP controller and I/O scanner.

>

4 Add AC422S to the project

► In the project structure: Right-click on [I/O Configuration] > [Name_of_I/O_scanner] > [Ethernet]

> The context menu appears.

► Create a new device with [New Module].

> The dialogue box [Select Module Type] appears.

► Select one of the following options:

Option 1: configure the device using the EDS file

► In the [Catalog] tab, select AC422S and confirm with [Create].

> The [New Module] window appears.

► Set the following parameters:

Parameter Meaning Possible values

Name short description of device

name appears in the tree structure of the RSLogix-5000 project

e.g. _AC422S

Description detailed description of device (optional)

max. 128 characters

e.g. I/O adapter

IP address IP address of the device's EtherNet/IP interface e.g. 192.168.10.10

► In the group [Module Definition], press [Change ...].

Page 378: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

378

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

> The [Module Definition] window appears.

► Set the parameters as shown:

► Press [OK] to confirm the input and to close the window.

> AC422S appears in the tree structure of the project.

► Continue with → step 5

Option 2: configure the device without EDS file

► Select [Catalog]: I/O adapter ETHERNET MODULE (Generic Ethernet Module) and confirm with [Create].

> The [New Module] window appears.

Page 379: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

379

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

► Set the parameters as shown:

In the "independent" configuration mode, the value entered for [Assembly Instance] has no relevance since the parameters are set directly on the device (→ Set the device-specific parameters and the module configuration (→ page 377)).

Irrespective of the value entered for [Size], RSLogix 5000 creates a data field in the controller tags with a length of 251 bytes.

► Press [OK] to confirm the input and to close the window.

► AC422S appears in the tree structure of the project:

>

5 Transfer the set configuration to the controller (download)

► Set the communication path to the device (→ operating instructions RSLogix 5000).

► Transfer the project to the EtherNet/IP controller and start it.

> AC422S: the start screen shows the status of the EtherNet/IP connection:

EtherNet/IP active >

Page 380: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

380

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix Fieldbus EtherNet/IP

6 Optional: import the description of the inputs and outputs into the project

► Download the I/O description file (→ Download the device and I/O description (→ page 127)).

► In RSLogix 5000: Select [Tools] > [Import] > [Tag and Logic Comments ...] to start the wizard for importing the I/O description.

> The [Import] dialogue box appears.

► Select the downloaded file (*.csv) and click [Import] to load it.

► In the tree structure: double-click on [Controller Tags]

> The detailed view of the controller tags appears.

> [_AC422S:I] and [_AC422S:O] show descriptions of the inputs and outputs.

Page 381: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

381

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

>

9.7 OSC messages

OSC messages: System ......................................................................................................................382 OSC messages: AS-i 1 / AS-i 2 ............................................................................................................383 OSC messages: Safety module ...........................................................................................................384 OSC messages: Safety PLCopen function blocks ...............................................................................401

18959

This section contains information about the messages for events, warnings and faults of the AC422S.

Page 382: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

382

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

>

9.7.1 OSC messages: System 14284

Message Type Corrective measures

An internal device error was detected <Fehlernummer>

Error ► Note the message and contact the ifm service center

Permitted temperature limit value inside the device was exceeded (<xxx.x> °C)

Warning ► Check thermal conditions of the system environment

First operation after delivery Event not necessary

The output control was set to <Gateway,manuell,SPS>

Event not necessary

System power-up completed, <SW-Version> Event not necessary

A system reset was requested manually Event not necessary

The user-specific message history was deleted. Event not necessary

The device was reset to factory settings via <HMI, Feldbus>.

Event not necessary

PLC used for more than 10 hours. Event not necessary

The project <Name> was loaded. Event not necessary

The PLC was set to the operating mode <Projektierungsmodus, geschützter Betrieb>.

Event not necessary

The firmware was updated from <FW-Version> to version <FW-Version>.

Event not necessary

The settings of the fieldbus interface were modified

Event not necessary

The fieldbus connection was established Event not necessary

The fieldbus connection was aborted Event not necessary

The IP settings of the configuration interface were changed

Event not necessary

Page 383: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

383

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

>

9.7.2 OSC messages: AS-i 1 / AS-i 2 16029

Message Type Corrective measures

System errors: AS-i master <1,2> Error ► Reboot the device

If the error occurs again:

► Note the message and contact the ifm service center!

Earth fault: AS-i <1,2> Error ► Check for earth fault of AC422S

Incorrect profile: AS-i <1,2>, slave <1(A)..31(A), 1B..31B> with profile <S-x.x.x> expected, but <S-y.y.y> found.

Error ► Check profile of the AS-i slave

Config error: AS-i <1,2>, slave <1(A)..31(A), 1B..31B> with the profile <S-x.x.x> missing

Error ► Check connections of the AS-i slave

► Reconnect AS-i slave

Config error: AS-i <1,2>, slave <1(A)..31(A), 1B..31B> with the profile <S-x.x.x> is available but not projected

Error ► Carry out projection process ([Quick setup] > [Project all])

Protocol error: AS-i <1, 2>, slave <1(A)..31(A), 1B..31B> no data transmission

Error ► Improve the transmission quality on the AS-i line

Double address detected: AS-i <1, 2>, slave <1(A)..31(A), 1B..31B>

Error ► Remove an AS-i slave with a double address from the AS-i network

► Readdress the remaining AS-i slave

► Reconnect removed AS-i slave to the AS-i network

The automatic addressing is not activated for AS-i <1,2>.

Warning ► Activate automatic addressing ([AS-i1]/[AS-i2] > [Master setup])

A voltage drop of 19.0 V was detected on AS-i master <1,2>

Warning ► Check voltage supply of the device and replace if necessary

A voltage drop of 22.5 V was detected on AS-i master <1,2>

Warning ► Check voltage supply of the device and replace if necessary

Increased message error rate: AS-i <1, 2>, slave <1(A)..31(A), 1B..31B>

Warning ► Improve the transmission quality on the AS-i line

Peripheral fault: AS-i <1, 2>, slave <1(A)..31(A), 1B..31B>

Warning ► Check displayed AS-i slave

AS-i slave with address 0 cannot be automatically readdressed (wrong profile)

Warning ► Activate automatic addressing ([AS-i1]/[AS-i2] > [Master setup]

Manual output change: AS-i <1, 2>, slave <1(A)..31(A), 1B..31B>, value: <0..F, 0..32768>

Event not necessary

Manual parameter change: AS-i <1, 2>, slave <1(A)..31(A), 1B..31B>, value: <0..F, 0..32768>

Event not necessary

AS-i master <1,2> was switched to the <geschützten Betrieb,Projektierungsmodus>

Event not necessary

AS-i projection process was carried out. Event not necessary

AS-i slave with the address 0 was detected Event not necessary

Page 384: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

384

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

>

9.7.3 OSC messages: Safety module 14278

Message Type Corrective measures

An internal fault in the safety board was detected <Fehlernummer1>, <Fehlernummer2>

Error ► Note the message and contact the ifm service centre.

Wrong code sequence on the safe slave AS-i <1,2>, Slave <1,...,31>

Error ► Replace slave with slave with unambiguous code sequence

Configured slave missing: AS-i <1,2>, slave <1,...,31>

Error ► Connect the missing AS-i slave to the AS-i network OR:

► Carry out projection adaptation ([Quick-Setup] > [Alles projektieren])

Cross-networking participant <Name> missing Error ► Check cross networking

The safety board was switched to the operating mode <Operate, Maintenance>

Event not necessary

The safety configuration "<Name>" was loaded Event not necessary

The safety configuration "<Name>" was deleted Event not necessary

The safety configuration is not readable Event not necessary

The safety configuration "<Name>" was enabled by <Kurzzeichen>

Event not necessary

Page 385: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

385

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

>

OSC messages: AS-i 1 / AS-i 2 (safety) 6977

Message Type Corrective measures

ASi_GlobalCom_FailureAscendingAddrSequ_e; currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Error ► Note the message and contact the ifm service centre

ASi_GlobalCom_FailureMissingBusCycleEvents_e; currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Error ► Note the message and contact the ifm service centre

At least two AS-i slaves with the same code sequence were detected: currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Error ► Replace one of the slaves with slave with unambiguous code sequence

The code sequence of a safe input slave is not compliant: currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Error ► Replace one of the slaves with slave with unambiguous code sequence

Error in code sequence during the teach process (0x5827): currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Error ► Replace one of the slaves with slave with unambiguous code sequence

Error in code sequence during the teach process (0x5820): currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Error ► Replace one of the slaves with slave with unambiguous code sequence

Safe AS-i input slave of type positively guided waiting for testing: currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Error ► Carry out testing for safe AS-i slave

ASi_SYS_ERROR_CFG_CANTADDSLAVE_e; currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Error ► Test parameters of the logical interface of the AS-i slave and correct, if required

Page 386: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

386

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

>

OSC messages: CODESYS (safety) 6979

Message Type Corrective measures

CODESYS: invalid FB parameter "ASi_Master": currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Warning ► Check setting of the parameter "ASi_Master"

CODESYS: multiple use of an AS-i address: currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Warning ► Check addressing of the AS-i slaves

CODESYS: FB parameter "ASi_SlaveAdr" in invalid range: currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Warning ► Check setting of the parameter "ASi_SlaveAdr"

Simultaneous activation of both help signals of a safe AS-i output module: currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Warning ► Check program code

CODESYS: FB parameter "ASi_SlaveAdr" refers to a non configured AS-i address: currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Warning ► Check configuration of the AS-i network

► Check setting of the parameter "ASi_SlaveAdr"

CODESYS: too many instances of "SF_OUTcontrol_ASi" created: currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Warning ► Check configuration of the AS-i network

► Check the number of the created logical devices for virtual control slaves

Page 387: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

387

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

>

OSC messages: System (safety) 9137

Message Type Corrective measures

Overvoltage on the internal supply detected: tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Check voltage supply of the device and replace, if necessary

Undervoltage on the internal supply detected: tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Check voltage supply of the device and replace, if necessary

The internal device temperature has exceeded the warning threshold of 78°C: tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Check thermal conditions of the system environment

The internal device temperature has exceeded the error threshold of 85°C: tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Check thermal conditions of the system environment

The internal device temperature has fallen below the error threshold of -5°C: tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Check thermal conditions of the system environment

Error in the file system (0x4045): Please contact the ifm service centre: tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

Error in the file system (0x4043): Please contact the ifm service centre: tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

Short circuit on a local output: tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Check connections of the local I/O interface.

Undervoltage or overvoltage detected on the internal supply: tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Check voltage supply of the device and replace if necessary

Overvoltage detected on the external supply: tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Check voltage supply of the device and replace if necessary

Undervoltage detected on the external supply: tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Check voltage supply of the device and replace if necessary

The operating mode of the safe PLC was changed (tmn=%s; ln=%s; p1=%s; p2=%s)

Note not necessary

The use of safe AS-i output slaves requires at least 5 active AS-i slaves in the network.

Error ► At least 5 AS-i slaves configured in the network.

System error: BIT_ADC_DETERMINATION_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_ADCVOLT_INIT_HNDL_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_ADCVOLT_INIT_STRT_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_ALLOC_SFB_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System information: BIT_ASI_ADD_INP_SLAVE_INFO_2; tmn=%s; ln=%s; p1=%s; p2=%s

Note ► Note the message and contact the ifm service centre.

System information: BIT_ASI_ADD_OUT_SLAVE_INFO_2; tmn=%s; ln=%s; p1=%s; p2=%s

Note ► Note the message and contact the ifm service centre.

System warning: BIT_ASI_CANT_ADD_IN_WARN_2; tmn=%s;

Warning ► Note the message and contact the ifm service centre.

Page 388: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

388

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

Message Type Corrective measures

ln=%s; p1=%s; p2=%s

System warning: BIT_ASI_CANT_ADD_OUT_WARN_2; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System information: BIT_ASI_ENOUGH_SLAVES_INFO_2; tmn=%s; ln=%s; p1=%s; p2=%s

Note ► Note the message and contact the ifm service centre.

System warning: BIT_ASI_LOST_FRMSYNC_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_ASI_M1EVENT_ORDER_WARN_2; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_ASI_M2EVENT_ORDER_WARN_2; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System information: BIT_ASI_RX_LOST_FRMSY_INFO_1; tmn=%s; ln=%s; p1=%s; p2=%s

Note ► Note the message and contact the ifm service centre.

System information: BIT_ASI_RX_WR_FRMPARI_INFO_1; tmn=%s; ln=%s; p1=%s; p2=%s

Note ► Note the message and contact the ifm service centre.

System information: BIT_ASI_RX_WRG_STA_FR_INFO_1; tmn=%s; ln=%s; p1=%s; p2=%s

Note ► Note the message and contact the ifm service centre.

System warning: BIT_ASI_SV_QUEUE_FULL_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_ASI_SYNC_CODESEQ_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_ASI_TEACH_QUEUE_F_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_ASI_TX_FIFO_FULL_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_ASI_WRONG_FRMPARI_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System error: BIT_ASIUART_IRQ_INST_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_ASIUART_SETUP_BD_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BAD_CMD_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BAD_CRC_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BAD_DATA_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BAD_FORMAT_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BAD_SEQUENCE_ERR_1; Error ► Note the message and contact the ifm service centre.

Page 389: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

389

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

Message Type Corrective measures

tmn=%s; ln=%s; p1=%s; p2=%s

System error: BIT_BITSPS_INTERNAL_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BSP_CLK_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BSP_DMA_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BSP_DRAM_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BSP_EXC_ABORT_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BSP_EXC_PREFETCH_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BSP_EXC_REENTRANCE_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BSP_EXC_SWI_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BSP_EXC_UNDEF_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BSP_FPGA_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BSP_HW_NO_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BSP_LOWINIT_READY_GOOD_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BSP_SEU_PROT_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_BSP_VER_GOOD_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System warning: BIT_CBIT_ERRCNT_WARN_2; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System error: BIT_CC_COUNTER_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_CC_CRC_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_CC_FORCE_FATAL_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_CC_INTERNAL_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_CC_TASKSEND_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_CC_WRONG_CPUID_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_CC_WRONG_LENGTH_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_CC_WRONG_TASKID_ERR_1; tmn=%s;

Error ► Note the message and contact the ifm service centre.

Page 390: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

390

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

Message Type Corrective measures

ln=%s; p1=%s; p2=%s

System warning: BIT_CHALCOMM_CNCT_DENIED_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System error: BIT_CHALCOMM_CONNECT_GOOD_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System warning: BIT_CHALCSTHK_EXEC_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_CHALSYNC_RCV_TO_WARN_2; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_CHALSYNC_SND_TO_WARN_2; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_CHFILE_EXEC_CMD_WARN_0; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_CHFILE_FILE_LOC_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_CHFILE_INPARA_CHK_WARN_0; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_CHFILE_INPARA_FDE_WARN_0; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_CHFILE_INPARA_GET_WARN_0; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System error: BIT_CHFILE_MISSING_OB_WARN_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System warning: BIT_CHFILE_PARA_OPENF_WARN_0; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_CHFILE_PARA_READD_WARN_0; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_CHFILE_PARA_WRFIL_WARN_0; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_CHFILE_READSIZE_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_CHFILE_RESP_CMD_WARN_2; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_CHFILE_RSP_FILE_H_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_CHFILE_RSP_FILENA_WARN_0; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

Page 391: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

391

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

Message Type Corrective measures

System warning: BIT_CHFILE_WRITESIZE_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_CIO_EXCHANGE_VAR_WARN_2; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_CNS_SETUP_FAULT_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System error: BIT_COM_RECV_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_COM_SEND_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_COMMON_MEM0_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_COMMON_MEM2_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_COMMON_STRING_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_CORELIB_VERSION_GOOD_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_CS_BGINIT_READY_GOOD_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_CS_CLK_MONITOR_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_CS_CYCLE_TIMEOUT_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_CS_INIT_1OO2_GOOD_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_CS_INTERN_ISYS_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_CS_REMOTE_TRG_TMO_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_CS_SYSTEM_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_CSP_VERSION_GOOD_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_DEV_UNINIT_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_DIAG_FATAL_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_DIAG_INTERNAL_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System warning: BIT_DIAG_IPC_INV_DATA_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System error: BIT_DIAG_IPC_SND_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_DIAG_TOO_LESS_IRQS_ERR_2; tmn=%s;

Error ► Note the message and contact the ifm service centre.

Page 392: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

392

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

Message Type Corrective measures

ln=%s; p1=%s; p2=%s

System error: BIT_DIAG_TOO_MANY_IRQS_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_DPRAM_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_EMBEX_SYSTEM_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_EXEC_RSP_TIMEOUT_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_FPGA_READY_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_FPGA_VER_GOOD_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System warning: BIT_GFS_DPRAM_READ_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System error: BIT_HBIT_DETECT_LIVE_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_HBIT_INPUT_FREEZE_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_HBIT_INPUT_TST_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_HBIT_OUTPUT_DIS_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_HBIT_OUTPUT_ENABLE_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_HBIT_OUTPUT_TST_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_HBIT_RSP_EVALUATION_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_HBIT_RSP_MAN_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_HBIT_RSP_TIMEOUT_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_HBIT_TST_MAN_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_HBIT_TST_REQ_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_HBIT_TST_RSP_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_HBIT_TST_SREG_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_HW_VER_GOOD_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_HW_WRONG_CPUID_ERR_0; tmn=%s;

Error ► Note the message and contact the ifm service centre.

Page 393: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

393

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

Message Type Corrective measures

ln=%s; p1=%s; p2=%s

System error: BIT_IHAL_ERROR_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_IHAL_INIT_READY_GOOD_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_INIT_SFB_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_INVALID_NUMERIC_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_CONFIG_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_CPU_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_CYCLE_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_IN_SHORT_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_INIT_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_OUT_NOT_OFF_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_OUT_SHORT_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_PARA_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_RSP_HDL_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_SB_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_SSP_BUSY_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System warning: BIT_LIO_SSP_BUSY_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System error: BIT_LIO_SSP_HANDLE_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_SSP_R_BUSY_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System warning: BIT_LIO_SSP_RNOT_EMPTY_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System error: BIT_LIO_START_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_STATE_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_STOP_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_TIMEOUT_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_TMR_NOTRUN_ERR_1; Error ► Note the message and contact the ifm service centre.

Page 394: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

394

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

Message Type Corrective measures

tmn=%s; ln=%s; p1=%s; p2=%s

System error: BIT_LIO_TMR_READ_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_TMR_RUN_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_TST_HDL_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_WBIT_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System warning: BIT_LIO_WRONG_STATE_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System error: BIT_LIO_X_LOC_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_X_MSG_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_X_NOMSG_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_LIO_X_Q_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_MMU_INIT_PART_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_NULLPOINTER_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_BSP_EXC_INST_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_BSP_INIT_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_BSP_IRQ_INIT_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_BSP_IRQ_INSTL_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_BSP_LOW_INIT_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_EVENT_NAME_SET_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_EVT_RECV_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_EVT_SEND_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_EVT_STRT_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_INIT_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_IOC_CL_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_IOC_OPN_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

Page 395: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

395

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

Message Type Corrective measures

System error: BIT_OS_IOC_RD_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_IOC_WR_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_MEMCPY_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_MSGQ_ACC_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_MSGQ_CREATE_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_MUTEX_CREATE_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_RETURN_OSSTART_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_SEM_CREATE_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_SEM_OVERFLOW_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System warning: BIT_OS_SEM_OVERFLOW_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System error: BIT_OS_SEM_PEND_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_SEM_POST_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_SEM_QUERY_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_SEM_SET_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_SEM_TO_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_SF_EXEPTION_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_SPWN_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_TASK_CREATE_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_TASK_NAME_SET_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_TASK_NOT_CALLED_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_TASK_NOT_PRESENT_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_TASK_RESUME_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

Page 396: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

396

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

Message Type Corrective measures

System error: BIT_OS_TASK_SUSPEND_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_TASK_TOLESSTIMETICKS_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OS_VER_GOOD_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OSSP_ACCESS_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OSSP_CACHECFG_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OSSP_MPUCFG_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OSSP_PRCSS_ASSIGN_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OSSP_PRCSS_CREATE_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OSSP_SHM_ASSIGN_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OSSP_SHM_CREATE_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OSSP_STKPATTERN_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_OSSP_STKUSAGE_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_PBIT_EXT_VOLT_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_PBIT_INPUT_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_PBIT_LEVEL_2_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_PBIT_LIFE_SIGNAL_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_PBIT_OUT_ENABLE_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_PBIT_STAND_ORDER_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_PUT_SFB_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_READY_GOOD_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System warning: BIT_SAFESTORAGE_CRC_WARN_2; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System error: BIT_SAFESTORAGE_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

Page 397: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

397

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

Message Type Corrective measures

System warning: BIT_SAFESTORAGE_READ_WARN_2; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_SB_GETACTLEN_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System error: BIT_SB_INIT_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System warning: BIT_SB_NOBUF_AVAIL_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_SB_NOBUF_RELEASED_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_SB_REC_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_SB_SEND_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_SB_SETACTLEN_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System error: BIT_SPS_ACK_TIMEOUT_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_SPS_APPROM_TIME_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_SPS_TMR_READ_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_SW_VER_GOOD_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_SYNC_SFB_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_SYSLUT_CRC_MISM_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_SYSLUT_GET_MAIN_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_SYSLUT_SAFE_MISM_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System warning: BIT_SYSLUT_VERS_MISM_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System error: BIT_TEMP__INIT_HNDL_ERR_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_TEMP_I2C_ERROR_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_TEMP_MAX_POSS_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_TEMP_MIN_POSS_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_TEMP_SENSOR_ERR_0; Error ► Note the message and contact the ifm service centre.

Page 398: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

398

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

Message Type Corrective measures

tmn=%s; ln=%s; p1=%s; p2=%s

System error: BIT_TEMP_SENSOR_VAL_ERR_1; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_TEMP_THRSVIOL_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_TEMP_VALUE_GOOD_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System warning: BIT_TIMEOUT_MCOOKIE_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_TL_INVALID_CMD_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_TL_RD_NOT_ACCEPT_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_TL_WR_NOT_ACCEPT_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System error: BIT_VALID_ITEM_FOUND_GOOD_0; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_VER_MISM1OO2_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_WRONG_ASiPII_CRC32_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System error: BIT_WRONG_CHECKSUM_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

System warning: BIT_WRONG_CHID_MSG_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System warning: BIT_WRONG_MHEADER_WARN_1; tmn=%s; ln=%s; p1=%s; p2=%s

Warning ► Note the message and contact the ifm service centre.

System error: BIT_WRONG_PROG_FLOW_ERR_2; tmn=%s; ln=%s; p1=%s; p2=%s

Error ► Note the message and contact the ifm service centre.

Page 399: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

399

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

>

OSC messages: Logical devices (safety) 7010

Message Type Corrective measures

ERROR (%s): DC=%s, DC-1=%s, AS-i %s, slave %s

Error Logical device of the safe AS-i slave in locked error state

ERROR (%s): DC=%s, DC-1=%s, terminals %s and %s

Error Logical device of the safe local input/output in locked error state

ERROR: (%s), DC=%s, DC-1=%s, P1=%s, P2=%s

Error Logical device of the safe AS-i slaves or the safe local inputs/outputs in locked error state

INIT (%s): DC=%s, DC-1=%s, AS-i %s, slave %s

Note Logical device of the safe AS-i slave in INIT state

INIT (%s): DC=%s, DC-1=%s, terminals %s and %s

Note Logical device of the safe local input/output in INIT state

INIT: (%s), DC=%s, DC-1=%s, P1=%s, P2=%s Note Logical device of the safe AS-i slave or the safe local input/output in INIT state

OFF (%s): DC=%s, DC-1=%s, AS-i %s, slave %s

Note Logical device of the safe AS-i slave provides safe OFF

OFF (%s): DC=%s, DC-1=%s, terminals %s and %s

Note Logical device of the safe local inputs/outputs provides safe OFF

OFF: (%s), DC=%s, DC-1=%s, P1=%s, P2=%s Note Logical device of the safe AS-i slave or the safe local input/output provides safe OFF

ON (%s): DC=%s, DC-1=%s, AS-i %s, slave %s Note Logical device of the safe AS-i slave provides safe ON

ON (%s): DC=%s, DC-1=%s, terminals %s and %s

Note Logical device of the safe local input/output provides safe ON

ON: (%s), DC=%s, DC-1=%s, P1=%s, P2=%s Note Logical device of the safe AS-i slave or the safe local input/output provides safe ON

TESTING (%s): DC=%s, DC-1=%s, AS-i %s, slave %s

Note Logical device of the safe AS-i slave requests testing

TESTING (%s): DC=%s, DC-1=%s, terminals %s and %s

Note Logical device of the safe local inputs/outputs requests testing

TEST: (%s), DC=%s, DC-1=%s, P1=%s, P2=%s Note Logical device of the safe AS-i slave or the safe local input/output requests testing

Page 400: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

400

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

>

OSC messages: Local inputs/outputs (safety) 20743

Message Type Corrective measures

Test signal for cross-fault monitoring cannot be detected: currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Error ► Check settings of the parameter of the logical "SF_local_testpulse"

Cross fault on a safe input: currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Error ► Check connection to local device.

CODESYS: dynamic parameter "IN_Channel" on FB "GetLocal...": currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Error ► Check setting of the parameter "IN_Channel" on FB.

CODESYS: "local_IO" Channel A = 0: currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Error ► Check setting of the parameter "Channel A" an the logical device.

CODESYS: "local_IO" Channel B = 0: currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Error ► Check setting of the parameter "Channel B" on the logical device.

CODESYS: "local_IO" Channel A = Channel B: currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Error ► Check setting of the parameter "Channel A" and "Channel B" on the logical device.

CODESYS: "local_IO" multiple use of a channel in the configuration: currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Error ► Check channel use in the configuration.

CODESYS: simultaneous use of a channel as safe and non-safe information: currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Error ► Check channel use in the configuration.

CODESYS: FB parameter "IN_Channel_X" refers to a non-configured safe local input: currDev=%s; currDiagState=%s; prevDiagState=%s; addr1=%s; addr2=%s

Error ► Check channel use in the configuration.

Page 401: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

401

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Appendix OSC messages

>

9.7.4 OSC messages: Safety PLCopen function blocks 20613

Diagnostic codes of the safety PLCopen function blocks are transferred to the OSC by means of the FB Ctrl_SetDiagInfo. The resulting OSC messages have the following structure:

Message #LogID: [currDevice] [hwid] [currDiagState] [prevDiagState] [Addr1] [Addr2]

Parameter Description Possible values

Message #LogID ID of the source of the message 0x8001 = CODESYS_LOG_ID

currDevice ID of the safety-PLCopen function block the diagnostic code of which is displayed; corresponds to the value defined by the programmer for "FB_Type"

→ Ctrl_SetDiagInfo, input parameters

hwid Instanz-ID des FB → Ctrl_SetDiagInfo, input parameters

CurrDiagState current state of the StateMachine of the safety PLCopen FB

→ operating instructions safety PLCopen library in CODESYS

PrevDiagState State of the StateMachine of the safety PLCopen FB in the previous PLC cycle

→ operating instructions safety PLCopen library in CODESYS

Addr1 Instance number of the safety PLCopen function block the diagnostic code of which is displayed; corresponds to the value defined by the programmer for "FB_Number"

→ Ctrl_SetDiagInfo, input parameters

Addr2 Reserved 0x0 constant

Page 402: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

402

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Index

10 Index

A

Acyclic data ................................................................................. 198, 254

Acyclic data records............................................................................. 257

Acyclic process data

Error codes .................................................................................................... 41

Add AC422S to the project ......................................................... 372, 377

Additional functions................................................................................ 73

Address assignment in Ethernet networks .......................................... 172

Adopt the system time of the PC ......................................................... 115

Analogue input ....................................................................................... 94

Analogue output ..................................................................................... 95

Appendix .............................................................................................. 166

Arrow and function keys ........................................................................ 17

Arrow keys ............................................................................................. 55

AS-i 1 / AS-i 2 ........................................................................................ 89

AS-i slaves ..................................................................................................... 94

Diagnosis ....................................................................................................... 92

Master setup .................................................................................................. 90

AS-i master .......................................................................................... 176

AS-i master commands ....................................................................... 304

AS-i master status flags ....................................................................... 180

AS-i module ........................................................................................... 25

AS-i slaves ........................................................................................... 184

AS-interface ......................................................................................... 171

Availability of the fail-safe PLC ............................................................ 165

B

Binary field ............................................................................................. 71

Button ..................................................................................................... 62

C

Carry out a projection adaptation .......................................................... 91

Certified software components for safe applications ............................ 34

Change an AS-i slave address .............................................................. 98

Change an AS-i slave parameter output ............................................... 98

Change the analogue output values manually ...................................... 96

Change the basic settings of the device ............................................. 154

Change the digital output values manually ........................................... 96

Change the Extended ID1 of the AS-i slave .......................................... 99

Checkbox ............................................................................................... 62

Clone device configuration .................................................................. 116

COM module .......................................................................................... 25

Combined transaction ................................................................. 193, 194

Combined transaction – Use of analogue channels in the gateway depending on the slave profile ............................................................ 194

Command 07 (0x0007) - Set the auto address mode of the AS-i master .................................................................................................. 317

Command 01 (0x0001) – Change parameters of an AS-i slave ......... 310

Command 03 (0x0003) – Project the currrent AS-i network ............... 312

Command 04 (0x0004) – Change LPS ............................................... 313

Command 05 (0x0005) – Change the operating mode of the AS-i master .................................................................................................. 314

Command 06 (0x0006) – Change AS-i slave address ........................ 315

Command 09 (0x0009) – Change extended ID1 in the AS-i slave ..... 318

Command 10 (0x000A) - Change PCD ............................................... 320

Command 13 (0x000D) – AS-i master supply voltage, symmetry, earth fault ...................................................................................................... 323

Command 21 (0x0015) – Read ID string of an AS-i profile (S-7.4) .... 325

Command 257 (0x0101) – Quick setup AS-i master 1 + 2 ................. 287

Command 259 (0x0103) – Select user language................................ 289

Command 26 (0x001A) – Read AS-i master info ................................ 328

Command 260 (0x0104) – Change display settings ........................... 291

Command 261 (0x0105) – Set output control ..................................... 292

Command 262 (0x0106) – Set standard PLC operating mode ........... 293

Command 265 (0x0109) – Set date/time ............................................ 294

Command 266 (0x010A) – Set parameters of the NTP server ........... 296

Command 267 (0x010B) – Read date / time / NTP settings ............... 298

Command 268 (0x010C) – Reboot system ......................................... 300

Command 269 (0x010D) – Read fieldbus info .................................... 302

Command 272 (0x0110) – Display target visualisation ....................... 303

Command 28 (0x001C) – Deactivate slave reset when changing to the protected mode .................................................................................... 329

Command 33 (0x0021) - Read diagnosis string of an AS-i slave (S-7.4) ............................................................................................................. 330

Command 34 (0x0022) - Read parameter string of an AS-i slave (S-7.4) ............................................................................................................. 332

Command 35 (0x0022) - Write parameter string of an AS-i slave (S-7.4) ............................................................................................................. 334

Command 36 (0x0024) – CTT2 Standard ........................................... 336

Command 37 (0x0025) – CTT2 standard write ................................... 338

Command 38 (0x0026) – CTT2 Vendor Specific Read ...................... 340

Command 39 (0x0027) – CTT2 Vendor Specific Write ....................... 342

Command 64 (0x0040) – CTT2 device group read ............................ 344

Command 65 (0x0041) – CTT2 Device Group Write .......................... 346

Command 66 (0x0042) – CTT2 Vendor Specific Selective Read From Buffer ................................................................................................... 348

Command 67 (0x0043) – CTT2 Vendor Specific Selective Write From Buffer ................................................................................................... 350

Command 68 (0x0044) – CTT2 Vendor Specific Selective Read ....... 352

Command 69 (0x0045) – CTT2 Vendor Specific Selective Write ....... 354

Command 70 (0x0046) – CTT2 device group selective Rread ........... 356

Command 71 (0x0047) – CTT2 Device Group Selective Write .......... 358

Command 73 (0x0049) – CTT2 Vendor Specific Exchange ............... 360

Command 74 (0x004A) – CTT2 Device Group Exchange .................. 362

Command 75 (0x004B) – CTT2 Device Group Selective Read From Buffer ................................................................................................... 364

Command 76 (0x004C) – CTT2 Device Group Selective Write From Buffer ................................................................................................... 366

Command 80 (0x0050) – Adjust AS-i master settings ........................ 368

Command 81 (0x0051) – Reset error counter .................................... 369

Command channels ............................................................................. 283

Command reply channel (device >>> fieldbus master) ...................... 303

Command status .................................................................................. 284

Configuration data (CDI) of the slaves (slave profiles) ....................... 186

Configuration interface

connection concepts.................................................................................... 173

Configuration mode ............................................................................. 371

Independent ................................................................................................. 377

Top-down ..................................................................................................... 372

Configuration of the analogue channels in slots 9 ... 12 ..................... 233

Configuration status

Colour codes + symbols ...................................................................... 138, 139

Configure the IP parameters automatically ................................ 122, 129

Configure the IP parameters manually ....................................... 122, 129

Confirmation message ........................................................................... 69

Connect and address AS-i slaves ....................................................... 156

Connect devices to local I/O interface ................................................... 38

Connection via Ethernet network ........................................................ 175

Page 403: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

403

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Index

Control a single standard PLC application .......................................... 103

Control of the graphical user interface .................................................. 54

Control standard PLC applications ...................................................... 104

CTT2 error object ................................................................................. 309

Cyclic data .................................................................................. 198, 221

D

DAE/EE flags ....................................................................................... 183

Derivation of parameter values for free slave assignment .................. 220

Description of the control elements ....................................................... 60

Description of the extended ID code 1 ................................................ 188

Description of the extended ID code 2 ................................................ 189

Description of the ID code (selection) ................................................. 188

Description of the IO code for digital slaves ........................................ 187

Details 4 channels per analogue slave....................................... 266, 267

Details of the 5-word areas ......................................................... 262, 264

Details of the error lists ........................................................................ 280

Details of the slave lists ....................................................................... 270

Device and AS-i supply via one common power supply ....................... 37

Device supply ........................................................................................ 37

Device supply via AUX, AS-i supply via AS-i power supply .................. 37

Device temperature ............................................................................. 119

Device type AR-1 ................................................................................... 50

Device type AR-2 ................................................................................... 51

Device type MS-1 .................................................................................. 42

Device type MS-2 .................................................................................. 43

Device type S-1 ..................................................................................... 44

Device type S-2 ..................................................................................... 45

Device type SLG-1................................................................................. 48

Device type SLG-2................................................................................. 49

Device type SLV-1 ................................................................................. 46

Device type SLV-2 ................................................................................. 47

Device-specific parameters ........................................................ 200, 204

Diagnosis - AS-i master 1

AS-i diagnosis ..................................................................................... 239, 243

configuration error ............................................................................... 248, 250

list of detected slaves (LDS) ............................................................... 247, 250

list of missing slaves ................................................................................... 243

List of missing slaves .................................................................................. 240

list of multiple addressed slaves ......................................................... 241, 243

List of non-projected slaves ................................................................ 240, 243

list of peripheral faults ................................................................................. 243

List of peripheral faults ................................................................................ 241

List of slaves with wrong slave profile ................................................ 240, 243

Master flags ......................................................................................... 247, 250

peripheral fault (LPF) .......................................................................... 248, 250

Diagnosis - AS-i master 2

AS-i diagnosis ............................................................................................. 244

configuration error ....................................................................................... 251

list of detected slaves (LDS) ....................................................................... 250

list of missing slaves ................................................................................... 245

list of multiple addressed slaves ................................................................. 246

List of non-projected slaves ........................................................................ 245

list of peripheral faults ................................................................................. 246

List of slaves with wrong slave profile ........................................................ 245

Master flags ................................................................................................. 250

peripheral fault (LPF) .................................................................................. 251

Diagnosis - system diagnosis ..................................................... 238, 243

Diagnostic coverage DC and MTTFd value .......................................... 28

Diagnostic data

Colour codes + symbols .............................................................................. 138

Digital input ............................................................................................ 94

Digital output .......................................................................................... 95

Direct link ............................................................................................. 174

Disconnect from web interface .............................................................. 76

Display .............................................................................................17, 25

Display and reset performance data ..................................................... 93

Display and reset the error counters ..................................................... 92

Display diagnostic data ............................................................... 119, 135

Display diagnostic protocol .................................................................. 165

Display elements ...........................................................................17, 169

Display EtherNet/IP data ..................................................................... 126

Display information about standard PLC projects ............................... 102

Display power-on time ......................................................................... 119

Display status information of the fail-safe PLC ................................... 146

Display switching states of the safe AS-i input slaves ........................ 139

Display the error statistics of the AS-i slaves ........................................ 92

Display the input/output data of the AS-i slave ..................................... 94

Display the module configuration ........................................................ 126

Display the status of the CODESYS standard PLC ............................ 102

Display the status of the safe AS-i slaves ........................................... 137

Display the switching states of the local inputs ................................... 142

Display the switching states of the local outputs ................................. 144

Display the voltage supply analysis ....................................................... 93

Download the device and I/O description ............................................ 127

DS1 – System information ................................................................... 259

DS10 – Slave list LPS ....................................................................... 270

DS11 – Current configuration data CDI............................................... 271

DS12 – Projected configuration data PCD .......................................... 273

DS13 – Image of the input parameters of the slaves .......................... 275

DS14 – Image of the output parameters of the slaves ........................ 276

DS15 – Slave error counter, configuration error counter, AS-i cycle counter ................................................................................................. 277

DS17 – Error lists LCEMS, LCEAS, LDAE ......................................... 280

DS18 – Fieldbus information ............................................................... 281

DS2 – Digital inputs of the slaves and master flags ............................ 260

DS3 – Analogue inputs of slaves 1(A)...15(B) ..................................... 261

DS4 – Analogue inputs of slaves 16(A)...31(B) ................................... 263

DS5 – Digital outputs of the slaves ..................................................... 265

DS6 – Analogue outputs of slaves 1(A)...15(B) .................................. 266

DS7 – Analogue outputs of slaves 16(A)...31(B) ................................ 267

DS8 – Status of the analogue output data of the slaves 1...31 ........... 268

DS9 – Slave lists LAS, LDS, LPF, LCE ............................................... 270

E

EDS-file ................................................................................................ 220

Electrical connection .............................................................................. 36

Electrical data ...................................................................................... 168

Electronic sensors ................................................................................. 44

Environmental conditions .................................................................... 168

Error classes .......................................................................................... 31

Error codes of the AS-i master commands ......................................... 307

Error detection and processing ............................................................. 31

Error message ....................................................................................... 31

Ethernet configuration interface ............................................................ 19

EtherNet/IP

Diagnosis ..................................................................................................... 135

Information ................................................................................................... 125

Setup ........................................................................................................... 128

EtherNet/IP fieldbus interface ................................................................ 20

EtherNet/IP modules............................................................................ 222

Example ................................................................................................. 57

Page 404: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

404

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Index

structure of the digital input data ................................................................. 227

Examples ............................................................................................. 220

Exception errors ..................................................................................... 31

Execution control flags ........................................................................ 181

Extended ID code 2 for analogue slaves with profile 7.3.x ................. 189

Extended ID code 2 for analogue slaves with profile 7.4.x ................. 189

Extended ID-Code 1 ............................................................................ 188

Extended ID-Code 2 ............................................................................ 189

F

Fatal error .............................................................................................. 31

Fieldbus EtherNet/IP............................................................................ 196

Fieldbus objects ................................................................................... 197

Fieldbus parameters ............................................................................ 199

Free slave addresses

colour code + symbols .................................................................................. 68

Free slave addresses, overview ............................................................ 67

Function keys ......................................................................................... 55

G

General .................................................................................................. 73

General error codes ............................................................................. 308

H

Hardware ............................................................................................... 22

Host flags ............................................................................................. 182

Housing ................................................................................................ 169

I

ID code ................................................................................................. 188

ifm system solutions ............................................................................ 147

ifm weltweit • ifm worldwide • ifm à l’échelle internationale ................. 407

Information concerning the device ........................................................ 15

Install devices on the local I/O interface .............................................. 153

Install multi app .................................................................................... 150

Install safe device to local I/O interface ................................................. 52

Install single/basic app ........................................................................ 149

Install standard device on local I/O interface. ....................................... 52

Installation ........................................................................................35, 36

Intended use .......................................................................................... 14

Interfaces .............................................................................. 18, 120, 170

Configuration interface ................................................................................ 121

EtherNet/IP interface ................................................................................... 124

IO code ................................................................................................ 187

L

Legal and copyright information .............................................................. 7

List ......................................................................................................... 63

Local input/output interface ................................................................... 19

Local inputs ............................................................................................ 19

Local outputs ......................................................................................... 19

Locate error sources ............................................................................ 161

M

Main module .......................................................................................... 25

Mapping of the digital input/output data .............................................. 227

Master flags ......................................................................................... 179

Meaning of the colour combinations ..............................................68, 140

Meaning of the colour combinations (example

configuration error type 2) ............................................................................. 66

Mechanical switches .............................................................................. 42

Menu ...................................................................................................... 77

Menu navigation .................................................................................... 56

Menu view .............................................................................................. 56

Message types ..................................................................................... 161

Modification history .................................................................................. 9

Module setting

AC13x7 AS-i 1 ............................................................................................. 247

AC13x7 AS-i 1+2 ......................................................................................... 249

AC1421 ........................................................................................................ 238

AC1422 ........................................................................................................ 242

Monitoring and securing mechanisms ................................................... 30

Mounting and electrical connection ..................................................... 153

N

Navigate on a page................................................................................ 59

Navigation aids ...................................................................................... 57

Normal operation ................................................................................... 30

Notes on ifm system solutions ............................................................. 148

Notes on IP settings.................................................................... 121, 128

Notes on the firmware update ............................................................. 156

Numerical field ....................................................................................... 70

O

Online diagnosis function .................................................................... 161

Online Support Centre (OSC).............................................................. 162

Open/Create a EtherNet/IP project ............................................ 372, 377

Operating elements ............................................................................... 17

Operating instructions ............................................................................ 74

Operating modes of the AS-i master ................................................... 177

Operating states of AC422S .................................................................. 29

Operation ............................................................................................... 53

Option 1

Transmit fieldbus and web interface data via different networks ............... 175

Option 2

transfer fieldbus and web interface data over the same network .............. 175

Optional

change settings of the safe AS-i input slaves ..................................... 138, 140

import the description of the inputs and outputs into the project ....... 375, 380

switch the language with a key combination .............................................. 110

OSC

Aktuelle Meldungen zeigen ......................................................................... 163

Show message history ................................................................................ 164

OSC messages .................................................................................... 381

AS-i 1 / AS-i 2 .............................................................................................. 383

AS-i 1 / AS-i 2 (safety) ................................................................................. 385

CODESYS (safety) ...................................................................................... 386

Local inputs/outputs (safety) ....................................................................... 400

Logical devices (safety) ............................................................................... 399

Safety module.............................................................................................. 384

Safety PLCopen function blocks ................................................................. 401

System ......................................................................................................... 382

System (safety)............................................................................................ 387

Output relay ........................................................................................... 50

Overview

acyclic data .................................................................................................. 255

Acyclic data sets .......................................................................................... 258

AS-i master commands ............................................................................... 305

System commands ...................................................................................... 286

User documentation for AC4S ........................................................................ 9

Overview of free slave addresses ......................................................... 67

Page 405: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

405

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Index

Overview of slave states ........................................................................ 65

P

Page view .............................................................................................. 59

Parameter data .................................................................................... 198

Parameter input ..................................................................................... 95

Parameter setting via the configuration assembly object .................... 203

Parameters

Independent mode ...................................................................................... 201

Top-down mode .......................................................................................... 202

Parameters of the fieldbus slots .......................................................... 214

Permitted use ......................................................................................... 14

PLC

Diagnosis ..................................................................................................... 106

Information ................................................................................................... 102

Settings ........................................................................................................ 103

Please note ............................................................................................ 11

Possible combinations of input and output channels ............................ 20

Power supply connections ................................................................... 168

Preliminary note ....................................................................................... 6

Preparations ............................................................................... 372, 377

Principle of the command channels .................................................... 284

Process safety time ............................................................................... 27

Profiles of AS-i slaves .......................................................................... 185

Programmable Logic Controller (PLC) ................................................ 171

Programmers' notes

call up acyclic services ................................................................................ 370

Prohibited use ........................................................................................ 14

Projection mode ................................................................................... 178

Protected mode ................................................................................... 178

Purpose of the document ........................................................................ 7

Q

Quick setup ............................................................................................ 79

Access the device via QR code .................................................................... 82

Address the AS-i slaves connected to AS-i master 1................................... 87

Address the AS-i slaves connected to AS-i master 2................................... 88

Configure the EtherNet/IP interface .............................................................. 83

Configure the operating mode of the AS-i masters ...................................... 81

Configure the output access ......................................................................... 82

Project AS-i networks .................................................................................... 80

Set the configuration interface ...................................................................... 85

Set the configuration mode ........................................................................... 84

R

Recommended browsers ....................................................................... 73

Remote access ...................................................................................... 72

Replace safe AS-i slave ...................................................................... 158

Replace standard AS-i slave ............................................................... 157

Required accessories ............................................................................ 21

Required background knowledge .......................................................... 11

Reset error ............................................................................................. 32

Restore the device configuration ......................................................... 117

S

Safe state ............................................................................................... 32

Safety ................................................................................................... 136

AS-i 1 master settings ................................................................................. 137

AS-i 2 master settings ................................................................................. 141

Local IOs ..................................................................................................... 142

System ......................................................................................................... 146

Safety architecture ................................................................................. 23

Safety classification ............................................................................. 168

Safety functions ..................................................................................... 34

Safety instructions ...........................................................................10, 39

Safety light curtains ............................................................................... 46

Safety light grids .................................................................................... 48

Safety module ........................................................................................ 26

Save the device configuration ............................................................. 116

Scheduling errors ................................................................................... 31

SD card slot ........................................................................................... 20

Serious error .......................................................................................... 31

Set output access ................................................................................ 108

Set the behaviour of the display .......................................................... 111

Set the configuration mode.................................................................. 130

Set the device cycle ............................................................................. 109

Set the device-specific parameters ..................................................... 131

Set the device-specific parameters and the module configuration ..... 377

Set the EtherNet/IP module configuration ........................................... 133

Set the fieldbus parameters and the module configuration................. 374

Set the monitoring functions of the AS-i master .................................... 91

Set the operating mode of the AS-i master ........................................... 90

Set the system time ............................................................................. 112

Set the system time manually.............................................................. 113

Setting RTC ......................................................................................... 112

Setup .................................................................................................... 152

Setup of EtherNet/IP ............................................................................ 156

Setup of the configuration interface ..................................................... 157

Show AS-i slave information.................................................................. 97

Show EtherNet information .................................................................. 123

Show information ................................................................................. 125

Show information about installed ifm apps .......................................... 149

Show memory used ............................................................................. 106

Show target visualisation ..................................................................... 105

Show version information .................................................................... 107

Slave addresses, free ............................................................................ 67

Slave profile ......................................................................................... 187

Slave profiles for slaves with combined transaction ........................... 193

Slave selector ........................................................................................ 64

Slave status

colour code + symbols .................................................................................. 66

overview......................................................................................................... 65

Overview ........................................................................................................ 65

Slot 1 – Digital input data single or A slaves, AS-i master 1 ............... 223

Slot 10 – Analogue input data ............................................................. 230

Slot 11 – Analogue output data ........................................................... 231

Slot 12 – Analogue output data ........................................................... 232

Slot 13 – Diagnostic data ..................................................................... 237

Slot 14 – Inputs from standard PLC .................................................... 252

Slot 15 – Outputs to standard PLC ...................................................... 253

Slot 2 – Digital output data single or A slaves, AS-i master 1 ............. 223

Slot 3 – Digital input data single or A slaves, AS-i master 2 ............... 224

Slot 4 – Digital output data single or A slaves, AS-i master 2 ............. 224

Slot 5 – Digital input data B slaves, AS-i master 1 .............................. 225

Slot 6 – Digital output data B slaves, AS-i master 1 ........................... 225

Slot 7 – Digital input data B slaves, AS-i master 2 .............................. 226

Slot 8 – Digital output data B slaves, AS-i master 2 ........................... 226

Slot 9 – Analogue input data ............................................................... 229

Software ................................................................................................. 33

Software modules of the device ............................................................ 34

Standard CTT2 error codes ................................................................. 308

Page 406: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

406

ifm Original Device Manual Fail-safe SmartPLC with EtherNet/IP interface (AC422S), Firmware 4.0.2 2016-03-02

Index

Start screen ........................................................................................... 78

Start screen 'Basic settings' ................................................................. 154

Start-up behaviour of the controller ....................................................... 12

Status LED ........................................................................................... 160

Basic device ................................................................................................ 160

fieldbus EtherNet/IP .................................................................................... 160

Status LEDs ........................................................................................... 17

Store diagnostic protocol ..................................................................... 118

Structure of the slave profile ................................................................ 187

Supported connection types .................................................................. 40

Supported device types ......................................................................... 41

Switch operating modes ...................................................................... 178

Switch the menu language .................................................................. 110

Switching states

Colour codes + symbols .............................................................................. 139

Switching states of the inputs

Colour codes + symbols .............................................................................. 143

Switching states of the local outputs

Colour codes + symbols .............................................................................. 145

Switching states of the logical devices

Colour codes + symbols ...................................................................... 143, 145

Symbols

free slave addresses ..................................................................................... 67

slave status.................................................................................................... 65

Symbols and formats used ...................................................................... 8

Synchronise the system time with an NTP server............................... 114

System ................................................................................................. 100

Diagnosis ..................................................................................................... 119

Information ................................................................................................... 107

Programmable Logic Controller (PLC) ....................................................... 101

Setup ........................................................................................................... 108

System architecture ............................................................................... 24

System commands .............................................................................. 285

System description ................................................................................ 13

System start / power on reset ................................................................ 30

T

Tab menu/Tab ....................................................................................... 61

Table

Fixed slave assignment for slots 9 ... 12 .................................................... 234

Master flags ................................................................................................. 228

variable slave assignment for slots 9 ... 12 ................................................ 236

Tampering with the unit ......................................................................... 12

Technical data ..................................................................................... 167

Transfer the set configuration to the controller (download)........ 375, 379

Troubleshooting ................................................................................... 159

Type label .............................................................................................. 21

Types of ifm system solutions ............................................................. 148

U

Uninstall ifm apps ................................................................................ 151

Update ifm apps ................................................................................... 151

Use navigation aids ............................................................................... 59

V

Valid combinations IO code / ID code / extended ID code 2............... 190

Voltage source / voltage ground ............................................................ 19

W

Web interface

Access ........................................................................................................... 74

Navigation ...................................................................................................... 74

Password protection ...................................................................................... 75

Web interface login ................................................................................ 75

Where is what on the AS-i device? ....................................................... 16

Page 407: Original Device Manual Fail-safe SmartPLC AC4S · Fail-safe SmartPLC AC4S with EtherNet/IP interface AC422S for ISO 13849 up to PL e for IEC 62061 up to SIL CL 3 Firmware: 4.0.2 English

11 ifm weltweit • ifm worldwide • ifm à l’échelle internationale

Version: 2015-03-06 8310

www.ifm.com • Email: [email protected]

Service hotline: 0800 / 16 16 16 (only Germany, Mo-Fr 07.00...18.00 h)

ifm Niederlassungen • Sales offices • Agences

D ifm electronic gmbh Vertrieb Deutschland

Niederlassung Nord • 31135 Hildesheim • Tel. 0 51 21 / 76 67-0

Niederlassung West • 45128 Essen • Tel. 02 01 / 3 64 75 -0

Niederlassung Mitte-West • 58511 Lüdenscheid • Tel. 0 23 51 / 43 01-0

Niederlassung Süd-West • 64646 Heppenheim • Tel. 0 62 52 / 79 05-0

Niederlassung Baden-Württemberg • 73230 Kirchheim • Tel. 0 70 21 / 80 86-0

Niederlassung Bayern • 82178 Puchheim • Tel. 0 89 / 8 00 91-0

Niederlassung Ost • 07639 Tautenhain • Tel. 0 36 601 / 771-0

ifm electronic gmbh • Friedrichstraße 1 • 45128 Essen

A

OFF

B, L

BR

CH

CN

CND

CZ

DK

E

F

FIN

GB, IRL

GR

H

I

IL

IND

J

MAL

MEX

N

NL

P

PL

RA, ROU

ROK

RP

RUS

S

SGP

SK

THA

TR

UA

USA

ZA

ifm electronic gmbh • 1120 Wien • Tel. +43 16 17 45 00

ifm efector pty ltd. • Mulgrave Vic 3170 • Tel. +61 3 00 365 088

ifm electronic N.V. • 1731 Zellik • Tel. +32 2 / 4 81 02 20

ifm electronic Ltda. • 03337-000, Sao Paulo SP • Tel. +55 11 / 2672-1730

ifm electronic ag • 4 624 Härkingen • Tel. +41 62 / 388 80 30

ifm electronic (Shanghai) Co. Ltd. • 201203 Shanghai • Tel. +86 21 / 3813 4800

ifm efector Canada inc. • Oakville, Ontario L6K 3V3 • Tel. +1 800-441-8246

ifm electronic spol. s.r.o. • 25243 Průhonice • Tel. +420 267 990 211

ifm electronic a/s • 2605 BROENDBY • Tel. +45 70 20 11 08

ifm electronic s.a. • 08820 El Prat de Llobregat • Tel. +34 93 479 30 80

ifm electronic s.a. • 93192 Noisy-le-Grand Cedex • Tél. +33 0820 22 30 01

ifm electronic oy • 00440 Helsinki • Tel . +358 75 329 5000

ifm electronic Ltd. • Hampton, Middlesex TW12 2HD • Tel. +44 208 / 213-0000

ifm electronic Monoprosopi E.P.E. • 15125 Amaroussio • Tel. +30 210 / 6180090

ifm electronic kft. • 9028 Györ • Tel. +36 96 / 518-397

ifm electronic s.a. • 20041 Agrate-Brianza (MI) • Tel. +39 039 / 68.99.982

Astragal Ltd. • Azur 58001 • Tel. +972 3 -559 1660

ifm electronic India Branch Office • Kolhapur, 416234 • Tel. +91 231-267 27 70

efector co., ltd. • Chiba-shi, Chiba 261-7118 • Tel. +81 043-299-2070

ifm electronic Pte. Ltd • 47100 Puchong Selangor • Tel. +603 8063 9522

ifm efector S. de R. L. de C. V. • Monterrey, N. L. 64630 • Tel. +52 81 8040-3535

Sivilingeniør J. F. Knudtzen A/S • 1396 Billingstad • Tel. +47 66 / 98 33 50

ifm electronic b.v. • 3843 GA Harderwijk • Tel. +31 341 / 438 438

ifm electronic s.a. • 4410-136 São Félix da Marinha • Tel. +351 223 / 71 71 08

ifm electronic Sp. z o.o. • 40-106 Katowice • Tel. +48 32-608 74 54

ifm electronic s.r.l. • 1107 Buenos Aires • Tel. +54 11 / 5353 3436

ifm electronic Ltd. • 140-884 Seoul • Tel. +82 2 / 790 5610

Gram Industrial, Inc. • 1770 Mantilupa City • Tel. +63 2 / 850 22 18

ifm electronic • 105318 Moscow • Tel. +7 495 921-44-14

ifm electronic a b • 41250 Göteborg • Tel. +46 31 / 750 23 00

ifm electronic Pte. Ltd. • Singapore 609 916 • Tel. +65 6562 8661/2/3

ifm electronic s.r.o. • 835 54 Bratislava • Tel. +421 2 / 44 87 23 29

SCM Allianze Co., Ltd. • Bangkok 10 400 • Tel. +66 02 615 4888

ifm electronic Ltd. Sti. • 34381 Sisli/Istanbul • Tel. +90 212 / 210 50 80

TOV ifm electronic • 02660 Kiev • Tel. +380 44 501 8543

ifm efector inc. • Exton, PA 19341 • Tel. +1 610 / 5 24-2000

ifm electronic (Pty) Ltd. • 0157 Pretoria • Tel. +27 12 345 44 49

Technische Änderungen behalten wir uns ohne vorherige Ankündigung vor. We reserve the right to make technical alterations without prior notice.

Nous nous réservons le droit de modifier les données techniques sans préavis.